equipment submittal - bidnet

137
Equipment Submittal Submersible Pumps and Control System November 2014 Project: ………………… Fargo Lift Station Marion County, Oregon Owner: …………… Marion County Public Works 5155 Silverton Road Salem, OR 97305 Tel: (503) 588-5036 Contact: Bob Pankrantz Supplier: ……………… Xylem Water Solutions USA, Inc. Flygt Products 2630 North Marine Drive Portland, OR 97217 Tel: (503) 240-1980 Fax: (503) 240-3445

Upload: others

Post on 30-Jan-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

Equipment Submittal Submersible Pumps and Control System

November 2014

Project: ………………… Fargo Lift Station

Marion County, Oregon

Owner: …………… Marion County Public Works

5155 Silverton Road

Salem, OR 97305

Tel: (503) 588-5036

Contact: Bob Pankrantz

Supplier: ……………… Xylem Water Solutions USA, Inc.

Flygt Products

2630 North Marine Drive

Portland, OR 97217

Tel: (503) 240-1980

Fax: (503) 240-3445

Page 1 of 2

Scope of Supply

Re: Marion County - Fargo LS retrofit

Pumps and Accessories

Qty Description

2 Flygt Model NP-3171.095 4" volute Submersible pump equipped with a 460 Volt

/ 3 phase / 60 Hz 35 HP 3550 RPM motor, 278 impeller, 1 x 50 Ft. length of

submersible cable, FLS leakage detector, volute is prepared for Flush Valve

1 Startup and training by factory trained technician

2 4” discharge connection

2 2” x 4” intermediate guide bar bracket

2 2” upper guide bar bracket

2 SS kellems grip for cable.

Level Sensors and Accessories

Qty Description

1 Level transducer, 0-5M range, 39’ cable

2 Flygt ENM-10 float sensor, 40’ cable

2 Flygt Chain sling unit with grip eye

1 Cable holder, stainless steel

Xylem Water Solutions USA, Inc. Flygt Products

2630 North Marine Dr

Portland, Oregon 97217

Tel (503) 240-1980

Fax (503) 240-3445

Page 2 of 2

Controls

Qty Description

1 Duplex control panel for use with 35 hp, 460 volt, 3 phase pumps and including the following features:

Type 4 floor mounted enclosure Inner door interlocked main circuit breaker Pump circuit breaker for each pump Flygt SmartRun variable speed drives 3 phase surge arrestor Control power transformer Anti-condensation heater with thermostat Current transformers for each pump Inner door mounted components:

o High level indicator o Overflow indicator o Power OK indicator o 15A GFCI duplex receptacle

Inner door mounted components for each pump: o Run indicator o Elapsed time meter

DC power supply and battery backup for controller Red alarm beacon light Audible alarm Dry alarm output contacts for SCADA interfacing:

o High level o Pump 1 fail o Pump 2 fail o Power fail

Space allowance for existing radio Wires numbered Terminal blocks, control relays and circuit breakers as required UL508A listed

1 Pump disconnect panel including the following features: Type 4X 304ss wall mounted enclosure Anti-condensation heater with thermostat Single channel analog barrier Four channel intrinsically safe barrier Three Flygt ENM-10 float sensors, 30’ cable One level transducer, 0-5M range, 39’ cable Terminal blocks as required Wires numbered UL698A listed

TABLE OF CONTENTS

Section 1 Submersible Pumps Pump Technical Data and Performance Curve Dimensional Drawing Power Cable Data Performance Specification

Section 2 Submersible Pumps Accessories Discharge Connection Upper Guide Bar Bracket Intermediate Guide Bar Bracket Flygt Grip Eye Unit Cable Grip

Section 3 Level Sensors and Accessories Level Transducer** Float Level Sensor** Cable Holder Chain Sling and Grip Eye

Section 4 Pump Controls Control Drawings Pump Control Panel Bill of Materials Pump Control Panel Component Data Sheets Pump Disconnect Panel Bill of Materials Pump Disconnect Panel Component Data Sheets

Section 5 Warranty and Service Warranty Service Locations Contact List

** Included in Section 4

Section 1 Submersible Pumps

Patented self cleaning semi-open channel impeller, ideal f or pumping inwaste water applications. Possible to be upgraded with Guide-pin®f or ev en better clogging resistance. Modular based design with highadaptat ion grade.

Head

278 168mm278 168mm

61.2%

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

[f t]

0 100 200 300 400 500 600 700 [US g.p.m.]

Impeller

Frequency

Motor

Rated v oltage

-

Rated power

Rated speed

Number of poles

Rated current

460 V60 Hz

35 hp

2

3530 1/min

40 A

NP 3171 SH 3~ 278

Motor #

3~

Suction Flange Diameter

Dimensional drwgNP, FP 3171. 091, 095, 181, 185, 350, 390 SH

2" GUIDE BARS FOR NEW INSTALLATION 3" GUIDE BARS FOR RETROFIT * DIMENSION TO END OF GUIDE BARS * * DIMENSION FOR 2"/3" GUIDE BARS

NP,FP 3171.091, 095, 181, 185, 350, 390 SH

MIN

LEV

EL

(TO FURTHEST POINT)

REF.LINE

DN100

REF.LINE

GUIDE BARS

Z Z

Z Z VIEW

MIN

CL

OF

DIS

CH

*

**72/22

200

100

250

476 **561/610

**85/135

2"/3"

116

249

60 **

326/

265

400

292

84 99

5

70

1046 **770/820

209

168 168

209

209

209

45°

BOLT Ø20(4x)

Impeller diameter 168 mmNumber of blades 2

N3171.095 25-18-2AA-W 35hpStator v ariant 9

Phases

Starting current 292 A

Technical specification

Note: Picture might not correspond to the current configuration.

Power f actor

Ef f ic iency

1/1 Load3/4 Load1/2 Load

1/1 Load3/4 Load1/2 Load

0.910.890.82

91.0 %91.5 %92.0 %

100 mmCurve according to: ISO 9906 grade 2 annex 1 or 2

P - Semi permanent, WetInstallation:

Configuration

Impeller material Hard-Iron ™

General

Discharge Flange Diameter 100 mm

Water, pure

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

Head

EfficiencyTotal efficiency

Shaft power P2Power input P1

NPSH-values

278 168mm278 168mm

61.2%

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

278 168mm278 168mm

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

278 168mm278 168mm

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

278 168mm (P2)278 168mm (P2)

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

278 168mm (P1)278 168mm (P1)

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

278 168mm278 168mm

135 ft

53.8 %

49.5 %

19.3 hp

20.9 hp

14 ft 304 US g.p.m.

0102030405060708090

100110120130140150160170180190200

[ft]

01020304050

[%]

14

16

18

20

[hp]

101520253035[ft]

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]

Motor #

60 Hz

Phases 3~

460 VNumber of poles 2

Rated power 35 hp

Starting currentRated current 40 A

Rated speed 3530 1/min

N3171.095 25-18-2AA-W 35hpStator variant

Number of blades 2

Power factor

NP 3171 SH 3~ 278

Suction Flange Diameter

Performance curvePump

Impeller diameter 168 mm

Motor

Rated voltage

292 A

Efficiency

1/1 Load3/4 Load1/2 Load

1/1 Load3/4 Load1/2 Load

Frequency9 0.91

91.0 %

0.890.82

91.5 %92.0 %

100 mm

Curve according to: ISO 9906 grade 2 annex 1 or 2

Discharge Flange Diameter 100 mm

Water, pure

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

Head

278 168mm

61.2%

135 ft

304 US g.p.m.0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

145

150

155

160

165

170

175

180

185

190

195

200

205

210

[ft]

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]

1

NP 3171 SH 3~ 278Duty Analysis

Curve according to: ISO 9906 grade 2 annex 1 or 2

Indiv idual pump Total

1 304 US g.p.m. 135 ft 19.3 hp 304 US g.p.m. 135 ft 19.3 hp 53.8 % 856 kWh/US MG 14 ft

Pumps running Specific /System Flow Head Shaft power Flow Head Shaft power Pump eff. energy NPSHre

Water, pure

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

Head

EfficiencyTotal efficiency

Shaft power P2Power input P1

NPSH-values

278 168mm278 168mm

61.2%

55 Hz55 Hz

61.2%

50 Hz50 Hz

61.2%

45 Hz45 Hz

61.2%

40 Hz40 Hz

61.2%

278 168mm278 168mm55 Hz55 Hz50 Hz50 Hz45 Hz45 Hz40 Hz40 Hz 278 168mm278 168mm55 Hz55 Hz50 Hz50 Hz45 Hz45 Hz40 Hz40 Hz

278 168mm (P2)278 168mm (P2)

55 Hz55 Hz

50 Hz50 Hz

45 Hz45 Hz40 Hz40 Hz

278 168mm (P1)278 168mm (P1)

55 Hz55 Hz

50 Hz50 Hz

45 Hz45 Hz40 Hz40 Hz

278 168mm278 168mm

55 Hz55 Hz50 Hz50 Hz

45 Hz45 Hz40 Hz40 Hz

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

[ft]

0

10

20

30

40

50

[%]

0

4

8

12

16

20

[hp]

5

10

15

20

25

30

35

[ft]

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]

NP 3171 SH 3~ 278VFD Curve

Curve according to: ISO 9906 grade 2 annex 1 or 2Water, pure

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

Head

278 168mm

61.2%

135 ft

304 US g.p.m.

55 Hz

61.2%

50 Hz

61.2%

45 Hz

61.2%

40 Hz

61.2%

05

101520253035404550556065707580859095

100105110115120125130135140145150155160165170175180185190195200205210

[ft]

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]

1

NP 3171 SH 3~ 278VFD Analysis

Curve according to: ISO 9906 grade 2 annex 1 or 2

Indiv idual pump Total

1 60 Hz 304 US g.p.m. 135 ft 19.3 hp 304 US g.p.m. 135 ft 19.3 hp 53.8 % 856 kWh/US MG 14 ft1 55 Hz 277 US g.p.m. 111 ft 14.5 hp 277 US g.p.m. 111 ft 14.5 hp 53.8 % 711 kWh/US MG 12 ft1 50 Hz 251 US g.p.m. 92.1 ft 10.9 hp 251 US g.p.m. 92.1 ft 10.9 hp 53.8 % 595 kWh/US MG 10.3 ft1 45 Hz 226 US g.p.m. 74.6 ft 7.94 hp 226 US g.p.m. 74.6 ft 7.94 hp 53.8 % 494 kWh/US MG 8.71 ft1 40 Hz 201 US g.p.m. 58.9 ft 5.57 hp 201 US g.p.m. 58.9 ft 5.57 hp 53.8 % 407 kWh/US MG 7.22 ft

Pumps running Specific /System Frequency Flow Head Shaft power Flow Head Shaft power Hyd eff. energy NPSHre

Water, pure

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

NP 3171 SH 3~ 278Dimensional drawing

Dimensional drwgNP,FP 3171.091,095,181,185,350,390 SH

2" GUIDE BARS FOR NEW INSTALLATION 3" GUIDE BARS FOR RETROFIT * DIMENSION TO END OF GUIDE BARS ** DIMENSION FOR 2"/3" GUIDE BARS

NP,FP 3171.091, 095, 181, 185, 350, 390 SH

MIN

LEV

EL

(TO FURTHEST POINT)

REF.LINE

DN100

REF.LINE

GUIDE BARS

Z Z

Z Z VIEW

MIN

CL O

F DI

SCH

*

**72/22

200

100

250

476 **561/610

**85/135

2"/3"

116

249

60 **

326/

265

400

292

84 99

5

70

1046 **770/820

209

168 168

209

209

209

45°

BOLT Ø20(4x)

Last updateCreated on

2014-11-11Created byProject IDProject

akramer
Typewritten Text
Fargo Lift Station Submersible Pumps

2012‐10

‐12

Flyygt Suubmer

rsible

Motorr Cablles

This broespeciaassortm

S

Flygt

Why ch

Flygt SUThey arto yourSUBCA

Long lif

» High t70°C wa» Superabrasio» ExtremWithsta» Chem» Ozone Ensures

» Tight a perfec» Retainpropertpressur Preven

» Condtemperminimiz

ochure conally designe

ment contain

Flygt SUBCFlygt HCR (Silicone CaMedium Vo

t SUBCA

hoose a Fly

UBCAB® is re made forr product wB® for a low

fetime

temperaturater temperior mechann and tear

mely low waands water d

mical resistae, oil and fl

s a reliable

outer diamct fit with cans its mechaties and witre of the sea

nts insulatio

uctor insularature ratingzes the risk

ntains an oved for subns the follo

CAB® (Heat and Cable (Heat Roltage Cabl

AB®

ygt SUBCA

a range ofr use with Fwill never w life cycle

re resistancerature nical strengresistance ater absorpdepths up tnce within ame resista

e leak-free

meter toleraable entry sanical and pthstands theal sleeve

on deterio

ation with ag of 90°C, wfor insulati

verview of mersible uwing cable

Chemical ReResistant) le

AB®?

f pump molygt pumpslet you docost, durab

e: up to

gth and high

ption rate: to 50 m pH 3–10 ant

fit

nces ensuresleeve physical e high

ration

a which on cracks

1

the Flygt mse and ma

es for varyin

esistant)

otor power s and mixerown, whatebility and m

h

e

B

» co» caaw» adp» caco Scfr

» ot» su C

»

motor cablade of careng applicati

Page 1-5Page 6 Page 6-7Page 7

cables esprs and makever your

minimum do

uilt-in mon

Secure proonnection oEliminate tables that owkward to Screened cdapted for ump superAll screeneables ≥10 montrol core

creened verequency d

Reduce elether electroSecure cor

upervision

Complies w

See table a

e assortmeefully selecons:

pecially deve sure that application

own time.

nitoring co

oper monitoof pump sehe use of s

often get dahandle control corethe use of tvision syste

ed cables amm2 have bs

ersions fordrive (VFD)

ectromagneonics rrect communits

with interna

at page 10

ent. The cacted materi

veloped bythe cable a

n is. Choos

ores

oring and eensors mall auxiliaamaged an

es specificathe Flygt Mem nd all unsc

built-in scre

r variable ) operation

etic emissio

unication w

ational stan

bles are als. The

y Xylem. attached se Flygt

easy

ary d are

ally MAS 800

reened eened

n

ons to

with

ndards

Genera

Flygt Sproduct For remwith cocontrol with tw800 pum

The scrunwantquarries

FeatureMax. shand instemperOuter sheathimateriaConducinsulatiomateria

ConducmateriaRated V(phase tearth, pto phasMore informa

al propertie

UBCAB® its in applic

mote pump ontrol cores

solution ofisted pair omp supervi

reened Flyed electros, and indu

e Fheath ulation

rature

7(A

ng al

Cty

ctor on

al

Hrupnta

ctors al

C

Voltage to

phase se)

E64N

ation FMM

es for Flyg

s designedations whe

control, Fls. You onlyf a motor cof screenedision system

ygt SUBCAmagnetic r

ustrial areas

Flygt SUBC70 °C and 9AWG 60 °C

Chlorinatedype: 5GM5

High densityubber (HEP

propylene rnumbers maable below

Copper stra

Europe: ≥ 1600/1000 V450/750 V North AmerFlygt standaM1997.47.0M1997.47.0

t SUBCAB®

d for use re the amb

ygt providey need onable plus ad control cm.

AB® is usedradiation. T.

AB® 0 °C

C and 90 °C

polyethyle)

y ethylene-PR/3GI3) orubber (EPRarked * in th have EPR, nds

0 mm2 and. Remaining

rica and Caard docume0004, M1990024

2

®

with standbient tempe

es a simplee cable in

a separate cores specif

d with VarTypical app

C)

ene rubber

propylene r Ethylene-R/3GI3). Parhe assortmthe rest HE

d 7G6+s(2xg models:

nada: 600 Vents

97.47.0009,

dard and eerature doe

e and reliabstead of ucontrol cabfically adap

riable Freqplications f

Scr70 °(AW

(CPE Chlrub

rt ent

EPR.

Higpro

Copscre

x0,5):

V

EurNor600

FlygM1

explosion ps not excee

ble solutionsing the cle. The ran

pted for the

quency Drivfor this cab

eened Flyg°C and 90 °

WG 60 °C an

orinated pober (CPE ty

h density eopylene rub

pper strandeened tinneope: 600/1rth America0 V

gt standard997.47 002

proof submed 70°C.

n through itconventiona

ge includee use of Fly

ves (VFD) ble include

gt SUBCAB°C nd 90 °C)

olyethyleneype: 5GM5

ethylene-bber (HEPR/

ds includinged copper 1000 V a and Cana

d document23

mersible

ts cables al pump s cables

ygt MAS

to limit e mines,

e )

/3GI3)

g wires

da:

t

S

Flygt S

Type

3 core

4 core

** See p

Fig. 1

SUBCAB®10-35 mm

Fig. 4

Screened SUB2,5-50 mm

UBCAB® a

Denomin(mm

3G1

3G2

4G1

4G2

4G4

4G6

page 9

® m2

BCAB® m2

ssortment

nation m2)

F

.5

.5

.5

.5

4

6

Sc

Part No.(* EPR)

lygt SUBCA

94 20 40*

94 19 31*

94 20 41*

94 20 42*

94 20 43*

94 20 44*

3

Fig. 2 SUBCAB®

50-120 mm2

Fig. 5

creened SUBC70-120 mm2

Nominal current

capacity at 30°C (Amp)**

AB® without

23

32

23

32

42

54

2

CAB® 2

Outer diamete

(mm)

control cor

10 - 11

11 - 12

10.5 - 11.

12.5 - 13.

16 - 17

18 - 19

Scre

control e

r Weightkg/m

es

0.16

0.24

5 0.20

5 0.28

0.44

0.57

Fig. 3

ened SUBCA1,5 mm2

Fig. 6

SUBCAB® lement desig1,2,3 and 5

t Bendingradius (cm)

10

11

10

12

16

18

n in fig.

g Fig. No.

Type

4 core

7 core

** See p

Denomin(mm

4G1.5 +

4G2.5 +

4G4 + 2

4G6 + 2

4G10 + S

4G16 + S

4G25 + S

4G35 + S

3x50 + 2GS(2x0

3x70 + 2GS(2x0

3x95 + 2GS(2x0

3x120 + 2GS(2x0

7G2.5 +

7G4 + 2

7G6 + S(

page 9

nation m2)

2x1.5 9

2x1.5 9

2x1.5 9

2x1.5 9

S(2x0.5) 9

S(2x0.5) 9

S(2x0.5) 9

S(2x0.5) 9

G35/2 + 0.5) 9

G35/2 + 0.5) 9

G50/2 + 0.5) 9

G70/2 + 0.5) 9

2x1.5 9

2x1.5 9

2x0.5) 9

Part No.(* EPR)

Flygt SUBC

94 20 61*

94 20 59*

94 20 60*

94 20 56*

94 19 81

94 19 82

94 19 83

94 19 84

94 19 85

94 19 86

94 19 87

94 19 88

94 20 82*

94 20 80*

94 19 80

4

Nominal current

capacity at 30°C (Amp)**

CAB® with co

23

32

42

54

75

100

127

157

192

246

298

346

32

42

54

Outer diameter

(mm)

ontrol cores

15 - 16

17 - 18

20 - 22

24 - 26

24 - 26

26 - 28

32 - 34

35 - 37

35 - 37

38 - 41

47 - 50

54 - 56

20 - 22

22 – 24

24 - 26

Weightkg/m

s

0.32

0.43

0.63

0.83

0.85

1.30

1.70

2.24

2.60

3.30

4.50

5.70

0.60

0.84

0,85

t Bendingradius (cm)

15

17

20

24

26

26

32

35

35

38

47

54

20

22

24

g Fig.No.

1

1

1

1

2

2

2

2

akramer
Highlight
akramer
Highlight
akramer
Highlight
akramer
Highlight
akramer
Highlight
akramer
Highlight
akramer
Highlight
akramer
Line
akramer
Oval

Temp

Tempe

The curIf the amhandle accordi

Examp

Select c

• Sele

Calc

Cho

Ambien

Accord

Am

21-25

26-30

31-35

36-40

41-45

46-50

51-55

56-60

61-70

MaxiThe ma

Examp

Flygt SUweighs

Bend

The min

perature

rature corr

rrent capacmbient temhas to be tng to the ta

le

cable for a p

ect correctio

culate "virtu

oose 4 G 6 m

nt tempera

ing to IEC 6

bient Tem

mum mximum me

le

UBCAB® 4 G2.6 kg/m, s

ding rad

nimum ben

e correct

rection fac

ities for Flymperature e

taken into able.

pump with

on factor fo

ual" current

mm2 at 52°

ature corre

60364-5-52

p. (°C)

echanicchanical loa

G 50 p/No.so the max.

ius

nding radius

tion

ctors for Fly

gt cables axceeds 30°considerati

a pump cu

or 52°C in th

t 33 / 0,76 =

C. rated 54

ection facto

23 table 52-

Cor

1,04

1,00

0,96

0,91

0,87

0,82

0,76

0,71

0,58

cal load

ad on Flygt

. 94 19 85 c

. length tha

s of Flygt ca

9

ygt cables

re designe°C, the maxion. The cu

rrent of 33

he table (0,

= 44A

4A

ors

-D1 and NE

rection Fac

t cables is 1

can take a mat can hang

ables is 10

d for duty aximum currurrent rating

A and an a

76 ).

EC table 31

ctor

1.5 kg/mm2

max. load o vertically is

x outer dia

at 30°C ament rating tg must be a

ambient tem

0-16 (USA/

Ambi

70-77

79-86

88-95

97-104

106-113

115-122

124-131

133-140

142-158

conductor

f 1.5 x 4 x 5s 300 / 2.6

meter.

bient tempthe conducadjusted (lo

mperature o

/Canada) in

ent Temp

r area.

50 =300 kg= 115m ca

perature. ctors can owered)

of 52°C:

n air.

(F)

. It ble.

FlygtFlygt SU

IEC 602

IEC 602

IEC 608

IEC 608

IEC 603

IEC 603

IEC 603

CSA C2

UL 1581

CCC.GB

EN 505

Othe

Cable T

Flygt HC

Flygt HC

Flygt HC

Flygt HC

Silicone

Silicone

Medium

Medium

Medium

t SUBCAUBCAB® ca

Standard

245

228 class 5

811-1-1 CLA

811-2-1 CLA

332-1

332-2

364-5-523

22.2 No.49-

1

B5013/IEC6

25-2-21

r cables

Type

CR

CR

CR

CR

e cable

e cable

m voltage c

m voltage c

m voltage c

AB® stanables comp

d

AUSE 9

AUSE 10

-1992

60245

s standa

Sta

IEC

IEC

SS

NE

VD

IEC

able DI

able DI

able DI

dards aly with the

TypeFlexible cain general

Conducto

Oil resistan

Oil resistan

Flame reta

Flame reta

Current

Flexible cain general

Flexible cain general

Flexible cain general

Flexible cain general

rds and

andard/Ap

C 60287

C 60332-3

S 424 02 46

EMA WC 27

DE 0207

C 60332-1

N VDE 250

N VDE 298

N VDE 207

10

and apprfollowing g

e able VD

r VD

nt VD

nt VD

ardant VD

ardant VD

VD

able VD

able HD

able EN

able EN

d approv

pproval

Cat A

7500

0

8 part 4

7

rovals general stan

Standa

DE 0207 pa

DE 0250

DE 0282 pa

DE 0472 pa

DE 0472 pa

DE 0295

DE 0298

DE 0472

D 22.4

N 50525-2-2

N 50363-1:2

vals

Type

Curren

Flame

Condu

Materi

Curren

Flame

Materi

Curren

Insulat

ndards:

ard

rt 20

rt 810

rt 803-A

rt 804-B

21

2005

nt rating

retardant

uctor insula

ial

nt rating

retardant

ial

nt rating

tion materia

Typ

Material

Material

Material

Oil resista

Flame ret

Conducto

Current

Testing

Flexible cgeneral

Cables fosubmersi

Material

ation mater

al

pe

ant

tardant

or

cable in

or ble use

ial

NP3171.095 SPECIFICATIONS REQUIREMENTS Furnish and install 2 submersible non-clog wastewater pump(s). Each pump shall be equipped with an 35 HP submersible electric motor, connected for operation on 460 volts, phase, 60 hertz service, with 50 feet of submersible cable (SUBCAB) suitable for submersible pump applications. The power cable shall be sized according to NEC and ICEA standards and also meet with P-MSHA Approval. The pump shall be supplied with a mating cast iron 4 inch discharge connection and be capable of delivering 300 GPM at 131 TDH. Each pump shall be fitted with chain sling unit and Flygt grip eye. The working load of the lifting system shall be 50% greater than the pump unit weight. PUMP DESIGN CONFIGURATION The pump shall be supplied with a mating cast iron __4___ inch discharge connection and be capable of delivering __300__ GPM at _131__ FT. TDH. The pump(s) shall be automatically and firmly connected to the discharge connection, guided by no less than two guide bars extending from the top of the station to the discharge connection. There shall be no need for personnel to enter the wet-well. Sealing of the pumping unit to the discharge connection shall be accomplished by a machined metal to metal watertight contact. Sealing of the discharge interface with a diaphragm, O-ring or profile gasket will not be acceptable. No portion of the pump shall bear directly on the sump floor. Each pump shall be fitted with chain sling unit and grip eye. PUMP CONSTRUCTION Major pump components shall be of grey cast iron, ASTM A-48, Class 35B, with smooth surfaces devoid of blow holes or other irregularities. The lifting handle shall be of stainless steel. All exposed nuts or bolts shall be of stainless steel construction. All metal surfaces coming into contact with the pumpage, other than stainless steel or brass, shall be protected by a factory applied spray coating of acrylic dispersion zinc phosphate primer with a polyester resin paint finish on the exterior of the pump. Sealing design shall incorporate metal-to-metal contact between machined surfaces. Critical mating surfaces where watertight sealing is required shall be machined and fitted with Nitrile rubber O-rings. Fittings will be the result of controlled compression of rubber O-rings in two planes and O-ring contact of four sides without the requirement of a specific torque limit. Rectangular cross sectioned gaskets requiring specific torque limits to achieve compression shall not be considered as adequate or equal. No secondary sealing compounds, elliptical O-rings, grease or other devices shall be used. COOLING SYSTEM Each unit shall be provided with an integral motor cooling system. A stainless steel motor cooling jacket shall encircle the stator housing, providing for dissipation of motor heat regardless of the type of pump installation. An impeller, integral to the cooling system and driven by the pump shaft, shall provide the necessary circulation of the cooling liquid through the jacket. The cooling liquid shall pass about the stator housing in the closed loop system in turbulent flow providing for superior heat transfer. The cooling system shall have one fill port and one drain port integral to the cooling jacket. The cooling system shall provide for continuous pump operation in liquid or ambient temperatures of up to 104°F (40°C.). Operational restrictions at temperatures below 104°F are not acceptable. Fans, blowers or auxiliary cooling systems that are mounted external to the pump motor are not acceptable. CABLE ENTRY SEAL The cable entry seal design shall preclude specific torque requirements to insure a watertight and submersible seal. The cable entry shall consist of dual cylindrical elastomer grommets, flanked by washers, all having a close tolerance fit against the cable outside diameter and the entry inside diameter. The grommets shall be compressed by the cable entry unit, thus providing a strain relief function. The assembly shall provide ease of changing the cable when necessary using the same entry seal. The cable entry junction chamber and motor shall be sealed from each other, which

shall isolate the stator housing from foreign material gaining access through the pump top. Epoxies, silicones, or other secondary sealing systems shall not be considered equal. MOTOR The pump motor shall be a NEMA B design, induction type with a squirrel cage rotor, shell type design, housed in an air filled, watertight chamber. The stator windings shall be insulated with moisture resistant Class H insulation rated for 180°C (356°F). The stator shall be insulated by the trickle impregnation method using Class H monomer-free polyester resin resulting in a winding fill factor of at least 95%. The motor shall be inverter duty rated in accordance with NEMA MG1, Part 31.The stator shall be heat-shrink fitted into the cast iron stator housing. The use of multiple step dip and bake-type stator insulation process is not acceptable. The use of pins, bolts, screws or other fastening devices used to locate or hold the stator and that penetrate the stator housing are not acceptable. The motor shall be designed for continuous duty while handling pumped media of up to 104°F. The motor shall be capable of no less than 30 evenly spaced starts per hour. The rotor bars and short circuit rings shall be made of aluminum. Three thermal switches shall be embedded in the stator end coils, one per phase winding, to monitor the stator temperature. These thermal switches shall be used in conjunction with and supplemental to external motor overload protection and shall be connected to the motor control panel. The junction chamber shall be sealed off from the stator housing and shall contain a terminal board for connection of power and pilot sensor cables using threaded compression type terminals. The use of wire nuts or crimp-type connectors is not acceptable. The motor and the pump shall be produced by the same manufacturer.

The motor service factor (combined effect of voltage, frequency and specific gravity) shall be 1.15. The motor shall have a voltage tolerance of +/- 10%. The motor shall be designed for continuous operation in up to a 40°C ambient and shall have a NEMA Class B maximum operating temperature rise of 80°C. A motor performance chart shall be provided upon request exhibiting curves for motor torque, current, power factor, input/output kW and efficiency. The chart shall also include data on motor starting and no-load characteristics. Motor horsepower shall be sufficient so that the pump is non-overloading throughout its entire performance curve, from shut-off to run-out. The motor and cable shall be capable of continuous submergence underwater without loss of watertight integrity to a depth of 65 feet or greater. BEARINGS The integral pump/motor shaft shall rotate on two bearings. The motor bearings shall be sealed and permanently grease lubricated with high temperature grease. The upper motor bearing shall be a two row angular contact ball bearing. The lower bearing shall be a two row angular contact ball bearing to handle the thrust and radial forces. The minimum L10 bearing life shall be 50,000 hours at any usable portion of the pump curve. MECHANICAL SEALS Each pump shall be provided with a positively driven dual, tandem mechanical shaft seal system consisting of two seal sets, each having an independent spring. The lower primary seal, located between the pump and seal chamber, shall contain one stationary and one positively driven rotating corrosion and abrasion resistant tungsten-carbide ring. The upper secondary seal, located between the seal chamber and the seal inspection chamber shall be a leakage-free seal. The upper seal shall contain one stationary and one positively driven rotating corrosion and abrasion resistant tungsten-carbide seal ring. The rotating seal ring shall have small back-swept grooves laser inscribed upon its face to act as a pump as it rotates, returning any fluid that should enter the dry motor chamber back into the lubricant chamber. All seal rings shall be individual solid sintered rings. Each seal interface shall be held in place by its own spring system. The seals shall not depend upon direction of rotation for sealing. Mounting of the lower seal on the impeller hub is not acceptable. Shaft seals without positively driven rotating members or conventional double mechanical seals containing either a common single or double spring acting between the upper and lower seal faces are not acceptable. The seal springs shall be isolated from the pumped media to prevent materials from packing around them, limiting their performance.

Each pump shall be provided with a lubricant chamber for the shaft sealing system. The lubricant chamber shall be designed to prevent overfilling and shall provide capacity for lubricant expansion. The seal lubricant chamber shall have one drain and one inspection plug that are accessible from the exterior of the motor unit. The seal system shall not rely upon the pumped media for lubrication. The area about the exterior of the lower mechanical seal in the cast iron housing shall have cast in an integral concentric spiral groove. This groove shall protect the seals by causing abrasive particulate entering the seal cavity to be forced out away from the seal due to centrifugal action. A separate seal leakage chamber shall be provided so that any leakage that may occur past the upper, secondary mechanical seal will be captured prior to entry into the motor stator housing. Such seal leakage shall not contaminate the motor lower bearing. The leakage chamber shall be equipped with a float type switch that will signal if the chamber should reach 50% capacity. PUMP SHAFT The pump and motor shaft shall be a single piece unit. The pump shaft is an extension of the motor shaft. Shafts using mechanical couplings shall not be acceptable. The shaft shall be stainless steel – ASTM A479 S43100-T. Shaft sleeves will not be acceptable. IMPELLER The impeller shall be of Hard-IronTM (ASTM A-532 (Alloy III A) 25% chrome cast iron), dynamically balanced, semi-open, multi-vane, back swept, screw-shaped, non-clog design. The impeller leading edges shall be mechanically self-cleaned automatically upon each rotation as they pass across a spiral groove located on the volute suction. The leading edges of the impeller shall be hardened to Rc 60 and shall be capable of handling solids, fibrous materials, heavy sludge and other matter normally found in wastewater. The screw shape of the impeller inlet shall provide an inducing effect for the handling of up to 5% sludge and rag-laden wastewater. The impeller to volute clearance shall be readily adjustable by the means of a single trim screw. The impeller shall be locked to the shaft, held by an impeller bolt and shall be coated with alkyd resin primer. VOLUTE / SUCTION COVER The pump volute shall be a single piece gray cast iron, ASTM A-48, Class 35B, non-concentric design with smooth passages of sufficient size to pass any solids that may enter the impeller. Minimum inlet and discharge size shall be as specified. The volute shall have a replaceable suction cover insert ring in which are cast spiral-shaped, sharp-edged groove(s). The spiral groove(s) shall provide trash release pathways and sharp edge(s) across which each impeller vane leading edge shall cross during rotation so to remain unobstructed. The insert ring shall be cast of Hard-IronTM (ASTM A-532 (Alloy III A) 25% chrome cast iron) and provide effective sealing between the multi-vane semi-open impeller and the volute housing. PROTECTION Each pump motor stator shall incorporate three thermal switches, one per stator phase winding and be connected in series, to monitor the temperature of the motor. Should the thermal switches open, the motor shall stop and activate an alarm. A float switch shall be installed in the seal leakage chamber and will activate if leakage into the chamber reaches 50% chamber capacity, signaling the need to schedule an inspection. The thermal switches and float switch shall be connected to a Mini CAS control and status monitoring unit. The Mini CAS unit shall be designed to be mounted in the pump control panel. .

Section 2 Submersible Pumps Accessories

Issued: Supersedes: 4/14 2/12

Standard CP/NP Discharge Connections (Cast Iron)

Note:The discharge connection shown hereis typical in appearence for most pumps.

B

DC

K

J I

A

E

GF

H

2" - 3045, 3057, CP/DP/FP-3068.

2 1/2" - DP/FP-3068.

3" - 3045, 3057, CP-3068.

3" - DP-3068, 3080, 3085, 3102, 3127, 3153. 4" - 3080, 3085, 3102, 3127, 3153, 3171, 3202.

6" - 3102, 3127(MT), 3153, 3171.

6" - 3153, 3171, 3202.

6" - R3231 6" - 3127(LT), 3301, 3315.

4

7 7/8

5 1/2

9 7/8

9 7/8

11

11

19 3/4

11 1/8

4 1/2

4 3/4

4 1/8

8

8

10

10

15 3/4

10

5 1/2

7 7/8

5 1/2

10 5/8

10 5/8

12 3/16

12 3/16

19 3/4

12 3/16

7 1/4

11 7/16

10 3/4

15 3/8

15 3/8

15 3/8

15 15/16

23 5/8

15 15/16

6 3/4

9 7/8

6 3/4

15 3/4

15 3/4

17 3/4

17 3/4

15 3/4

18

3 15/16

6 1/2

3 15/16

7 7/8

7 7/8

9 7/8

9 7/8

7 7/8

10 1/8

7/8

4 9/16

7/8

4 9/16

4 9/16

4 9/16

4 9/16

6 7/8

4 9/16

3 13/16

11 5/8

6 3/4

14

14 3/8

15 9/16

15 9/16

20 11/16

15 9/16

---

45°

---

45°

22.5°

22.5°

22.5°

22.5°22.5°

2"-11 1/2 NPT

2 1/2"

3-8 NPT

3"

4"

6"

6"

6"6"

2"

2 1/2"

2"

3"

4"

5 1/2"

5 1/2"

6"6"

486 55 01

493 17 06

555 48 01

444 68 05

540 13 05

444 70 06

602 33 06

388 25 06604 56 06

PartNumber

Disch.Inlet

Disch.Outlet

All dimensions (inches)

D E F G H IA B C

---

5 5/8

---

6

7 1/2

9 1/2

9 7/16

9 7/16

9 7/16

K

---

90° x 4

---

90° x 4

45° x 8

45° x 8

45° x 8

45° x 845° x 8

JPumpModel

Note: Alternative discharge connections may be available, contact Flygt Application Engineering.

Caution:Contact Flygt applications engineering department when making a pump/discharge connection combination other than those paired in the chart above.

akramer
Highlight
akramer
Highlight
akramer
Line
akramer
Oval

Issued: Supersedes:

Upper Guide Bar Bracket (for 3000, 5500 & 8000 Series Pumps)

Note: use with 3" nominal guide bars

Note: use with 2" nominal guide bars

OPTIONAL:NUT RAILFEATURE

Standard for the following pumps:

Standard for the following pumps:

9/11 8/10

NUT RAIL

BRACKET

LATERAL NUT

NP/FP-3171NP/FP-3202

CP/NP/RP-3231CP-3240NP-3301

CP/NP-3306CP/NP-3312

NP-3315CP-3351

CP/NP-3356CP/NP-3400

CP-3501CP-3531CP-3602CP-3800HP-5570

11-11/16"

7-1/8"

4-3/8"

4-1/4"

3/8" PLAIN WASHER (2)14-46 50 07

3/8" LOCKWASHER (2)14-46 50 67

3/8"-16 LATERAL NUT14-46 37 05

HEX. HEAD BOLT (2),3/8"-16 x 7/8"14-46 20 25

MOUNTING HARDWARE14-59 00 00 (stainless steel)

MOUNTING HARDWARE14-59 00 00 (stainless steel)

DP-3068DP-3080

CP/DP/FP/NP-3085NP-3102NP-3127

NP/FP-3153NP/FP-3171

HP-5520, 5530DP-8050, 8053, 8056, 8058

3/8" PLAIN WASHER (2)14-46 50 07

3/8" LOCKWASHER (2)14-46 50 67

3/8"-16 LATERAL NUT14-46 37 05

HEX. HEAD BOLT (2),3/8"-16 x 7/8"14-46 20 25

2" UPPER GUIDE BAR BRACKET

613 68 00 Galvanized Steel613 68 04 316 Stainless Steel

3" UPPER GUIDE BAR BRACKET

661 54 00 Galvanized Steel661 54 01 316 Stainless Steel

6-11/16"

9-13/16"

1/2" Ø1/2"4-9/16"

3-1/8"

5-1/2"

Akramer
Rectangle
Akramer
Rectangle
Akramer
Rectangle
Akramer
Rectangle
Akramer
Rectangle
Akramer
Highlight
akramer
Rectangle
akramer
Typewritten Text
akramer
Typewritten Text
akramer
Rectangle
akramer
Typewritten Text
akramer
Typewritten Text
akramer
Typewritten Text
akramer
Typewritten Text
akramer
Typewritten Text
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle
akramer
Rectangle

Wire M

anagement P

roducts?????

IMPORTANT!

It is important that you read allbreaking strength, safety andtechnical data relating to thisproduct on pages T-43 throughT-48.

E

M

Single Eye, Split Mesh, Rod Closing

Single Eye, Split Mesh, Lace Closing

E

M

E

M

Single Eye, Closed Mesh

Single Eye, Closed Mesh*For permanent support when cable end is available to be installed through grip.Cable Diameter Approx. Breaking E M Catalog Range Inches (cm) Strength Lbs. (N) Inches (cm) Inches (cm) Numbers

.50”-.62” (1.27-1.57) 530 (2,357) 7” (17.78) 10” (25.40) 02401013

.63”-.74” (1.60-1.88) 790 (3,514) 8” (20.32) 10” (25.40) 02401014

.75”-.99” (1.90-2.51) 1,020 (4,537) 8” (20.32) 13” (33.02) 02401015

1.00”-1.24” (2.54-3.15) 1,610 (7,161) 9” (22.86) 14” (35.56) 02401017

1.25”-1.49” (3.17-3.78) 1,610 (7,161) 10” (25.40) 15” (38.10) 02401018

1.50”-1.74” (3.81-4.42) 1,610 (7,161) 12” (30.48) 17” (43.18) 02401019

1.75”-1.99” (4.44-5.05) 2,150 (9,563) 14” (35.56) 19” (48.26) 02401020

2.00”-2.49” (5.08-6.32) 3,260 (14,500) 16” (40.64) 21” (53.34) 02401021

2.50”-2.99” (6.35-7.59) 3,260 (14,500) 18” (45.72) 23” (58.42) 02401022

3.00”-3.49” (7.62-8.86) 4,900 (21,795) 21” (53.34) 25” (63.50) 02401023

3.50”-3.99” (8.89-10.13) 4,900 (21,795) 24” (60.96) 27” (68.58) 02401024

Single Eye, Split Mesh, Lace Closing*For permanent support when cable end is not available.Cable Diameter Approx. Breaking E M Catalog Range Inches (cm) Strength Lbs. (N) Inches (cm) Inches (cm) Numbers

.50”-.62” (1.27-1.57) 530 (2,357) 7” (17.78) 10” (25.40) 02202013

.63”-.74” (1.60-1.88) 790 (3,514) 8” (20.32) 10” (25.40) 02202014

.75”-.99” (1.90-2.51) 1,020 (4,537) 8” (20.32) 13” (33.02) 02202015

1.00”-1.24” (2.54-3.15) 1,610 (7,161) 9” (22.86) 14” (35.56) 02202017

1.25”-1.49” (3.17-3.78) 1,610 (7,161) 10” (25.40) 15” (38.10) 02202018

1.50”-1.74” (3.81-4.42) 1,610 (7,161) 12” (30.48) 17” (43.18) 02202019

1.75”-1.99” (4.44-5.05) 2,150 (9,563) 14” (35.56) 19” (48.26) 02202020

2.00”-2.49” (5.08-6.32) 3,260 (14,500) 16” (40.64) 21” (53.34) 02202021

2.50”-2.99” (6.35-7.59) 3,260 (14,500) 18” (45.72) 23” (58.42) 02202022

3.00”-3.49” (7.62-8.86) 4,900 (21,795) 21” (53.34) 25” (63.50) 02202023

3.50”-3.99” (8.89-10.13) 4,900 (21,795) 24” (60.96) 27” (68.58) 02202024

Single Eye, Split Mesh, Rod Closing*For support when cable end is not available.Cable Diameter Approx. Breaking E M Catalog Range Inches (cm) Strength Lbs. (N) Inches (cm) Inches (cm) Numbers

.50”-.62” (1.27-1.57) 790 (3,514) 7” (17.78) 81/2” (21.59) 02203013

.63”-.74” (1.60-1.88) 790 (3,514) 8” (20.32) 81/2” (21.59) 02203014

.75”-.99” (1.90-2.51) 1,020 (4,537) 8” (20.32) 101/2” (26.67) 02203015

1.00”-1.24” (2.54-3.15) 1,610 (7,161) 9” (22.86) 121/2” (31.75) 02203017

1.25”-1.49” (3.17-3.78) 1,610 (7,161) 10” (25.40) 141/2” (36.83) 02203018

1.50”-1.74” (3.81-4.42) 1,610 (7,161) 12” (30.48) 151/2” (39.37) 02203019

1.75”-1.99” (4.44-5.05) 2,150 (9,563) 14” (35.56) 161/2” (41.91) 02203020

2.00”-2.49” (5.08-6.32) 3,260 (14,500) 16” (40.64) 191/2” (49.53) 02203021

2.50”-2.99” (6.35-7.59) 3,260 (14,500) 18” (45.72) 211/2” (54.61) 02203022

3.00”-3.49” (7.62-8.86) 5,750 (25,576) 21” (53.34) 231/2” (59.69) 02203023

3.50”-3.99” (8.89-10.13) 5,750 (25,576) 24” (60.96) 251/2” (64.77) 02203024

E-Eye length M-Mesh length at nominal diameter* Change catalog number from 022 to 024 for stainless steel. Consult factory foravailability.

T-31Dimensions in Inches (mm) www.hubbell-wiring.comDimensions in Inches (mm) www.hubbell-wiring.com

Wire M

anagement P

roductsS

upport Grips

Support GripsStandard Duty SupportSingle Eye, Single Weave, Stainless Steel

asheehan
Line
asheehan
Line
asheehan
Rectangle
asheehan
Rectangle
asheehan
Rectangle
akramer
Rectangle
akramer
Highlight
akramer
Oval

Section 3 Level Sensors and Accessories

Issued: Supersedes:

Mounting Hardwareto be supplied by user.

CABLE HOLDER304L Stainless Steel653 31 00

Used for all pumps.

10-1/4

8-1/2

1-3/4 1-3/4

3-3/4

3-7/16

3/8

19/32

1-3/161/4

1/8

9/09

Cable Holder

11/00

akramer
Highlight

Supersedes:Issued:AccessoriesWater & Wastewater

Flygt Pump LiftTM Lifting System

11/09

The normal method of lowering and raising a CP pump in and out of a lift station is by use of a chain or cable attached to the pump. The length of the chain or cable is dependent on the depth of the station. The average length would probably be between 18 to 20 ft. and in certain cases may be much longer. In many cases, depending on the lifting device (usually a hoist), the operator may have to take a second or third bite on the pump chain in order to lift the pump clear of the station.

An added accessory to the Flygt line is the pattented Flygt Pump LiftTM System which consists of 33 ft. of nylon line, a short length of high tensile strength stainless steel chain and a forged “Grip-Eye” of wrought alloy steel.

The operation of this positive recovery system is as follows:

1. Connect the small eye of the grip-eye to the end of the hoist cable.

2. Slip the end of the nylon line through the large eye of the grip-eye. The nylon line simply acts as a guide for the grip-eye on its way down to the short length of the pump lifting chain.

3. While keeping the nylon line (guide line) taut, proceed to lower the grip-eye until it is well positioned over the pump lifting chain.

4. Release the tension on the nylon guide line. The lifting chain will now take a position to become engaged in the grip-eye.

5. Gradually take up tension on the hoist cable and the grip-eye will make a positive grip on the pump lifting chain. Continue hoisting until the pump is clear of the station.

Caution: The Grip-Eyes may only be used with the corresponding special Flygt Chain Sling Units.

Grip-Eyes are not warrantied if other chains are used.

Refer to the following pages for pump models and correct assembly.

4/08

GRIP-EYE CHAIN SLING

HOIST HOOK NYLON LINE

(Customer to supply extra shackle) A shackle can be used in conjunction with the standard ring should customer choose not to remove and replace pump handle.

FIG. 2(Standard) The end ring of the Chain Sling is slipped over the pump lifting handle.

FIG. 1

akramer
Line

Supersedes:Issued:AccessoriesWater & Wastewater

Flygt Pump LiftTM Lifting System

8/00 5/97

Chain Sling Ass'y

Grip-Eye

A

B

C

D

E

442 18 00

620 09 00

13-1/2

2-3/8

7-7/8

2-3/8

1/2

*442 18 06

620 09 00

11-1/4

2-3/4

7-7/8

2-3/8

5/8

*442 18 05

620 09 01

24-13/16

2-3/16

13-3/4

4-3/4

7/8

Fig. 1 Fig. 2Item

All dimensions are in inches *Stainless Steel

B

A

C

E

D

Fig. 1

D

BE

AC

Fig. 2

pmup eht gnirewoLpmup eht gnitfiL

akramer
Highlight
akramer
Highlight

Supersedes:Issued:AccessoriesWater & Wastewater

Flygt Pump LiftTM Lifting System

Flygt Pump LiftTM System Specification

Submersible pump shall be furnished with a pump lifting-chain positive-recovery system consisting of the following components:

1. Minimum of 10 meters (33 ft.) of nylon line, of diameter matching weight of lifting chain required, connected to a short length (approximately ten links long) of high tensile strength proof-tested chain of required capacity, connected to the lifting eye or lifting bail of the submersible pump.

2. A forged “grip-eye” of wrought alloy steel, provided separately to connect to the end of the lifting cable or chain of the pump lifting device.

The operation of the pump lifting-chain positive-recovery system shall be as follows:

1. Connect small eye of grip-eye to end of chain or cable of external mechanical of lifting device.

2. Slip top end of nylon line through large eye of grip-eye.

3. Lower grip-eye to top of pump while maintaining a taut nylon line, making sure short length of chain fastened to pump is also taut.

4. Release tension on nylon line when grip-eye has reached pump top. Make certain upper end of nylon line has been secured.

5. Take up tension on cable or chain of lifting device, grip-eye will engage links of short chain and lift pump.

Device shall be the same as the “Flygt Pump LiftTM” manufactured by ITT Water & Wastewater, Shelton, Connecticut or approved equal.

Black Box Specification - Flygt Pump LiftTM System

Furnish with each submersible pump one complete Flygt Pump LiftTM system or approved equal. The system shall consist of 10 meters (33 ft.) nylon line, short length of high tensile strength proof-tested chain and forged steel Grip-Eye for use with mechanical lifting device (furnished by others). System shall be appropriately sized for weight of pump to be lifted.

7/10 11/09

Section 4 Pump Control Panel and

Pump Disconnect Panel

PROJECT SUMMARY

PROJECT NAME: MARION COUNTY, AURORA, ORFARGO L/S

QUOTE NO. 081514SM3, 081514SM4ORDER NO. SUBMITTALDRAWING: EDW-CD-XYL-105

VOLTAGE: 480VACPHASE: THREE PHASE, 3WWIRES: L1, L2, L3, GND

ELECTRICAL SERVICE

CONTROL SYSTEM

TYPE: LIFT STATIONCONTROLLER: SRC311SENSORS: LEVEL TRANSDUCER + (2)FLOATSNO. PUMPS: 2MOTOR HP: 35HP, 460V, 3PH, 46FLAENCLOSURE: 60 x 36 x 16, FLOOR MOUNTED

TYPE 4

NOTE:RADIO TELEMETRY EQUIPMENT

SUPPLIED BY OTHERS

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 1

100

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

119

120

121

122

123

124

125

126

127

128

129

130

131

132

133

134

135

136

137

138

139

140

141

142

143

144

145

146

147

148

149

150

151

152

153

154

155

156

157

158

GFCIRECEPT

9 10 12 13

SIGNAL PDP

SLDN1 80 81 SLD 82 83

TransformerFerraz

FSShawmut

Cat. No. FSPDB2A

FerrazFSShawmut

Cat. No. FSPDB2A

FerrazFSShawmut

Cat. No. FSPDB2A

BACK PANEL LAYOUT - 57" x 33"

ON

OFF

ON

OFF

CB

3

1 2 3 4

CR1

ON

OFF

TS1FL

CB

2

TS2

CB1 PCB1 PCB2 MCB

SK

3241

SK

3241

SRC311 #1(FRAME 5)

SRC311 #2(FRAME 5)

CR3

CR4

CR5

CR2

CR7

CR6

CB

5C

B6

CB

4

HT(ELEVATED 3" OFF

BACK PANEL)

1 2

AL1

60.0

018

.00

36.00

PUMPSENSORSAC PDP

FAN

INTA

KE

FAN

INTA

KE

FAN

EX

HA

US

T

FAN

EX

HA

US

T

RADIO

PS

SCADA

104100 101 105102 103 106 107

(DOCUMENT SHELF)

HMI HMI

BAT

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 2

200

201

202

203

204

205

206

207

208

209

210

211

212

213

214

215

216

217

218

219

220

221

222

223

224

225

226

227

228

229

230

231

232

233

234

235

236

237

238

239

240

241

242

243

244

245

246

247

248

249

250

251

252

253

254

255

256

257

258

90 91 92 93

FLOATS, LXDCR

96 97 G

ISR

ISB

TYPE 4X SS304 SINGLE DOOR ENCLOSURE.ENCLOSURE SIZE 24"H X 24"W X 10"D WALL MOUNTED.

HT

10 11 12 13 14 15 N

1 2 3 4

PUMP 1 PUMP 2

BACKPANEL SIZE 21"H X 21"W.

INTRINSICALLYSAFEAREA10

.00

FRONT

24.0

0

24.00

G

R

PUMP 1FAULT

PUMP 1RUNNING

G

R

PUMP 1FAULT

PUMP 1RUNNING

R

OVERFLOWALARM

R

HIGH LEVELALARM

W

POWEROK

RADIOTEST

PUMP DISCONNECTPANEL PDP

G G

HMI HMI

GFCIRECEPT

I

O

I

O

I

O

PUMP 1 PUMP 2 MAIN

INNER DOOR LAYOUT - 57" x 33"

Hazardous AreaClass I Groups A,B,C,DClass II Groups E,F,GClass III

PDB1 L1 L2 L3

2L3

2L2

2L1

1L3

1L2

1L1

1T3

1T2

1T1

400400

2(WHT)

35 HP 460V46 FLAPUMP 1

T1

T2FLS SENSOR

2T3

2T2

2T1

35 HP 460V46 FLAPUMP 2

T1

T2

PUMP 1

PUMP 2

SHT.6

3L1 3L3

CB113A

SRC311 #1

GND

L1 U

L2 V

L3 W

SRC311 #2

GND

L1 U

L2 V

L3 W

PDPPCB180A

PCB280A

1T1

1T2

1T3

2T1

2T2

2T3

1

2

3

4

1

GND

GND

FLS SENSOR

GND

GND

SHT.6

XFR2KVA

PANELGROUND

X1

H1 H4H3 H2

X2120V

L1 L2 L3

FROM DISTRIBUTION PANEL480VAC, THREE PHASE, 60 HZ, 3 WIRE + GND

GND

MCB150A

ENCLOSURE HEATER200W

FAN

HT

6 ENCLOSURE FAN#1TS1

FAN

7

ENCLOSURE FAN#28TS2

FAN

CB45A

CB315A GFCI-15A

GFCI RECEPTACLEGENERAL USE

5

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 3

300

301

302

303

304

305

306

307

308

309

310

311

312

313

314

315

316

317

318

319

320

321

322

323

324

325

326

327

328

329

330

331

332

333

334

335

336

337

338

339

340

341

342

343

344

345

346

347

348

349

350

351

352

353

354

355

356

357

358

500 500

358358

ALARMSILENCE

23

24

21

ALARM SILENCE RELAYNO - 421NC - 422

AUDIBLE ALARM

ALARM BEACON

CR3A1 A2

12

CR3

11 14

CR3

3 2

RX1 X2

AL3

OVERFLOW LEVEL RELAYNO - 420,517,704

HIGH LEVEL RELAYNO - 421,518,706

11 14

HIGH LEVELCR2

1 2(WHT)

FL

BLK RED

11 14

OVERFLOWCR1

CR1A1 A2

CR2A1 A2

FAN

HT

10

12

13

PUMP DISCONNECT PANEL - PDP

N1

N1

3

FSHH

FSH

12

13

11 14

SRC 2 FAULTCR5

11 14

SRC 1 FAULTCR4

Hazardous AreaClass I Groups A,B,C,DClass II Groups E,F,GClass III

9

42

52

31 33

51

ISR

41

CH.1

CH.2

11

12

21

22

13

14

23

24

613

613

CB62A

CB52A

RX1 X2

AL5

RX1 X2

AL4

OVERFLOW LEVEL IND

HIGH LEVEL INDICATOR

10

9

21

AA

90

91

92

93

9

10

12

13

CB210A

25

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 4

400

401

402

403

404

405

406

407

408

409

410

411

412

413

414

415

416

417

418

419

420

421

422

423

424

425

426

427

428

429

430

431

432

433

434

435

436

437

438

439

440

441

442

443

444

445

446

447

448

449

450

451

452

453

454

455

456

457

458

PUMP 1 RUN LIGHT

458458

GX1 X2

RL1

17 18

RUNRL2

31

23

PUMP 2 RUN LIGHTGX1 X2

RL2

17 18

RUNRL2

ETM1

ETM2

PUMP 1 RUN TIME HRS

PUMP 2 RUN TIME HRS

32 CR4A1 A2

CR5A1 A2

14 15

FAULTRL1

14 15

FAULTRL1

RX1 X2

AL1

RX1 X2

AL2

PUMP 2 FAULT LIGHT

PUMP 2 FAULT RELAYNO - 423,710

PUMP 1 FAULT LIGHT

PUMP 1 FAULT RELAYNO - 422,708

21 24

HIGH LEVELCR2

21 24

OVERFLOWCR1

CR6A1 A2

HIGH LEVEL RELAYNO - 602,615

36

37

38

700 700

3 2

SRC311 #1

SRC311 #2

WX1 X2

PL1

CR7A1 A2

POWER FAIL RELAYNC - 708

POWER OK LIGHT

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 5

500

501

502

503

504

505

506

507

508

509

510

511

512

513

514

515

516

517

518

519

520

521

522

523

524

525

526

527

528

529

530

531

532

533

534

535

536

537

538

539

540

541

542

543

544

545

546

547

548

549

550

551

552

553

554

555

556

557

558

98

4-20MASRC#1

1

2

4

6

8

10

12

3

5

7

9

11

13

+24V

EXT BLOCK

ALM RESET

LSHH

+10V

T2 SENSOR

GND

LVL OUT

GND

LVL INPUT(4-20MA)

ACTIVE PUMP

STO-

STO+ (+24V)

1

2

4

6

8

10

12

3

5

7

9

11

13

SRC311 #1

SRC311 #2

RJ45

15

17

14

16

18

RL1-C

RL1-NO

RL1-NC

RL2-B

RL2-A

SHT.5

15

17

14

16

18

RL1-C

RL1-NO

RL1-NC

RL2-B

RL2-A

RJ45PUMP #2

FLS SENSORRES T1

T2

85

86

WHT

81

80

83

82

GND

GND

RED(+)

BRN(-)

PRIMARYLEVEL

SENSORLXDCR14-20MA

2

1

2

4

3

(OUT+)

(+)(+)

(IN+)

(OUT+)

(+)

31 33

(IN-)

ISB1

(IN+)

CH.1

CH.2

14

13

24

23

44

52

51

42

414428

PUMP DISCONNECT PANELPDP

1

3

99

98

GND

Hazardous AreaClass I Groups A,B,C,DClass II Groups E,F,GClass III

GND SLD

+24V

EXT BLOCK

ALM RESET

LSHH

+10V

T2 SENSOR

GND

LVL OUT

GND

LVL INPUT(4-20MA)

ACTIVE PUMP

STO-

STO+ (+24V)

81

80

83

82

SLD

SLD

GND SLD

4

4-20MASRC#2

BLK

WHT

BLK

WHT

BLK

WHT

BLK 87

88

21 24

HIGH LEVELCR6

11 14

HIGH LEVELCR6

SHT.5

PUMP #1FLS SENSOR

RES T1

T2

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 6

600

601

602

603

604

605

606

607

608

609

610

611

612

613

614

615

616

617

618

619

620

621

622

623

624

625

626

627

628

629

630

631

632

633

634

635

636

637

638

639

640

641

642

643

644

645

646

647

648

649

650

651

652

653

654

655

656

657

658

DUPLEXRECEPTACLEGFI

RADIO ONLY

COM

COM

COM

COM

IN1

IN2

IN3

IN4

IN1

IN2

IN3

IN4

41 44

SRC 1 FAULTCR4

41 44

SRC 2 FAULTCR5

100

101

102

103

104

105

QUICK TALK RADIO(EXISTING)

41 44

HIGH LEVELCR2

106

107

558558

RADIOTEST

41 42

POWER FAILCR7

CB72A

GFCI RECEPTACLERADIO USE ONLY

102

103

104

105

106

107

100

101

BAT1+ -

NOTE:RADIO TELEMETRY EQUIPMENT

SUPPLIED BY OTHERS

SHEET NO.

REVISION

DWG NO.EDW-CD-XYL-105

0

OF 7

PROJECT

DESIGN BY DATE11-3-2014

THIS DOCUMENT IS THE PROPRIETARY PROPERTY OF FLYGT. IT HAS BEEN FURNISHED UPON THE CONDITION THAT IT SHALL NOT BE RELEASED, DUPLICATED, USED OR DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WITHOUT THE EXPRESS WRITTEN PERMISSION OF FLYGT AND SHALL BE CONSIDERED CONFIDENTIAL INFORMATION.ORDER NO. / QUOTE NO.

DESCRIPTION

DUPLEX SRC311, 35HP, 460V, TYPE 4

MARION COUNTY - AURORA, OR FARGO PUMP LIFT STATION

SDM

/ 081514SM3,4 7

700

701

702

703

704

705

706

707

708

709

710

711

712

713

714

715

716

717

718

719

720

721

722

723

724

725

726

727

728

729

730

731

732

733

734

735

736

737

738

739

740

741

742

743

744

745

746

747

748

749

750

751

752

753

754

755

756

757

758

DATE: 11-7-2014

PANEL: PCP

REV.

QTY LEGEND DESCRIPTION MFG PART NO.

ENCLOSURE & COMPONENTS

1

Enclosure; 60 x 36 x 16, Type 4, 3PT Latch, Wall

Mounted Hoffman A60H36FLP3PT

1 Enclosure; 60 x 36 Panel Hoffman A60P36

Enclosure; Floor Stand Kit, 18 High Hoffman AFK1816

1 Enclosure; Inner Door Kit, Aluminum OSI DF60X36AL

A/R Din Rail; 1 Meter

Custom

Connector C103PM

A/R Terminal Block; UK 5N, 30A, 600V Phoenix 3004362

A/R End Block; ENS 35N Phoenix 800886

A/R End Cover; D-UK 4/10 (UK 5 & 6) Phoenix 303020

3 PDB Terminal Block; 175A, Power Dist, 1IN/4OUT Mersen FSPDB2A

1 HT Heater; 200W w/Thermostat Hoffman D-AH2001A

2 TS Thermostat; 32-140 DegF Stego 01141.9-00

2 FAN Axial Fan, 135CFM, 120VAC Rittal 3241.110

2 FAN Exhaust Grille For 135CFM Fan Rittal 3240.200

4 FAN Grille Cover Shroud, Type 4/3R Rittal 3240.085

2 FAN Filter, Fine Rittal 3182.100

POWER COMPONENTS

1 MCB Circuit Breaker; 3P, 150A, 18kAIC@480V Square D HDL36150

2 PCB1,2 Circuit Breaker; 3P, 80A, 18kAIC@480V Square D HDL36080

3

MCB,PCB1

,2 Circuit Breaker; Handle, Door Interlock Square D S29338

1 CB1 Circuit Breaker; 2P, 10A, 10kAIC@480V Square D MGN61319

1 XFR Transformer; 2000VA, 240x480-120/240V Square D 9070T2000D1

1 XFR Transformer: Fingersafe Cover Kit Square D 9070FSC2

3 CB5-7 Circuit Breaker; 1P, 2A, 10kAIC@120V Square D 60103

1 CB4 Circuit Breaker; 1P, 5A, 10kAIC@120V Square D 60106

1 CB2 Circuit Breaker; 1P, 10A, 10kAIC@120V Square D 60110

1 CB3 Circuit Breaker; 1P, 15A, 10kAIC@120V Square D 60112

2 GFCI1,2 Receptacle; Duplex, 15A, GFI Leviton 8599-W

BILL OF MATERIAL

JOB NAME

CUSTOMER

MARION COUNTY, AURORA, OR - FARGO L/S

XYLEM WATER SOLUTIONS USA, INC.

QUOTE NO. 081514SM3.1

DRIVE COMPONENTS

2 SRC1,2

SmartRun SRC311 Drive; 40HP, 480V, 3 Phase,

Frame Size 5 Flygt/Xylem SRC311-5-4-0300K-55

CONTROL COMPONENTS

2 RL1,2 Pilot Light, 30mm, Nema 4X, Green, 120V LED, PTT Square D 9001SKT38LGG31

4 AL1,2,4,5 Pilot Light, 30mm, Nema 4X, Red, 120V LED, PTT Square D 9001SKT38LRR31

1 PL1 Pilot Light, 30mm, Nema 4X, White, 120V LED, PTT Square D 9001SKT38LWW31

2

Push Button, 30mm, Nema 4X, 1NO, Black, Full

Guard Square D 9001SKR1BH5

1 AL3 Beacon; Red, 120VAC Ingram LX25R

1 FL Flasher; 150W, 120VAC Ingram SS150W

1 AA Audible Alarm; 120VAC, 85dB Floyd Bell MW-09-201-Q

2 ETM1,2 Hour Meter; Non-Reset, 120VAC, LCD Redington 3410-1000

7 CR1-7 Relay, 4PDT, 8A, LED, PTT, 120VAC Coil Schneider RXM4AB2F7

7 CR1-7 Relay, Socket, DIN, Box Lug Schneider RXZE2M114M

EXTERNAL CONTROL COMPONENTS

Spec-00290 F

Wall-Mount EnclosurEs Type 4 Wall-MounT enclosures

EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEMild stEEl1

Spec-00290F763.422.2211763.422.2600

Mild stEElWall-Mount EnclosurEstypE 4 Wall-Mount EnclosurEs

continuous HingE WitH claMps, typE 4

industry standards

UL 508A Listed; Type 4, 12, 13; File No. E61997cUL Listed per CSA C22.2 No. 94; Type 4, 12, 13; File No. E61997

NEMA/EEMAC Type 3, 4, 12, and 13CSA, File No. 42186: Type 4 and 12IEC 60529, IP66

applicationThese single-door enclosures feature a hinged door with clamps on three sides to create a secure seal in indoor or outdoor environments. The gray polyester powder finish inside and out provides enhanced corrosion protection in outdoor applications.

spEciFications• 16 or 14 gauge steel (see table)• Seams continuously welded and ground smooth

• External wall-mounting brackets• Formed external flanges around all sides of enclosure opening• Stainless steel door clamps on three sides of door• Removable heavy gauge stainless steel continuous hinge pin• Hasp and staple provided for padlocking• Data pocket is high-impact thermoplastic• Collar studs provided for mounting optional panels• Bonding provision on door

FinisHANSI 61 gray polyester powder paint inside and out

accEssoriEsSee also Accessories.Industrial Corrosion InhibitorsFast-Operating Clamp AssemblyIncandescent Light PackageCompact Cooling FansSteel and Stainless Steel Window Kits See also the Popular Accessories table forlloing the Standard Products table.

ModiFication and custoMiZationHoffman excels at modifying and customizing products to your specifications. Contact your local Hoffman sales office or distributor for complete information.Bulletin: A4

Standard Product

Catalog Number AxBxC in. AxBxC mmBodyGauge Panel

ConductivePanel

Panel SizeD x E (in.)

Panel SizeD x E (mm) F (in.) F (mm)

Numberof Clamps

DataPocket

A16H12ALP 16.00 x 12.00 x 6.00 406 x 305 x 152 16 A16P12 A16P12G 13.00 x 9.00 330 x 229 1.25 32 4 SmallA16H16ALP 16.00 x 16.00 x 6.00 406 x 406 x 152 16 A16P16 A16P16G 13.00 x 13.00 330 x 330 3.00 76 4 SmallA16H20ALP 16.00 x 20.00 x 6.00 406 x 508 x 152 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 SmallA20H16ALP 20.00 x 16.00 x 6.00 508 x 406 x 152 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 SmallA20H20ALP 20.00 x 20.00 x 6.00 508 x 508 x 152 16 A20P20 A20P20G 17.00 x 17.00 432 x 432 3.00 76 4 SmallA24H12ALP 24.00 x 12.00 x 6.00 610 x 305 x 152 16 A12P24 A12P24G 9.00 x 21.00 229 x 533 1.25 32 5 SmallA24H16ALP 24.00 x 16.00 x 6.00 610 x 406 x 152 16 A24P16 A24P16G 21.00 x 13.00 533 x 330 3.00 76 5 SmallA24H20ALP 24.00 x 20.00 x 6.00 610 x 508 x 152 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 SmallA24H24ALP 24.00 x 24.00 x 6.00 610 x 610 x 152 16 A24P24 A24P24G 21.00 x 21.00 533 x 533 3.00 76 5 SmallA30H20ALP 30.00 x 20.00 x 6.00 762 x 508 x 152 14 A30P20 A30P20G 27.00 x 17.00 686 x 432 3.00 76 5 SmallA30H24ALP 30.00 x 24.00 x 6.00 762 x 610 x 152 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 LargeA36H24ALP 36.00 x 24.00 x 6.00 914 x 610 x 152 14 A36P24 A36P24G 33.00 x 21.00 838 x 533 3.00 76 5 LargeA16H12BLP 16.00 x 12.00 x 8.00 406 x 305 x 203 16 A16P12 A16P12G 13.00 x 9.00 330 x 229 1.25 32 4 SmallA20H16BLP 20.00 x 16.00 x 8.00 508 x 406 x 203 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 SmallA20H20BLP 20.00 x 20.00 x 8.00 508 x 508 x 203 16 A20P20 A20P20G 17.00 x 17.00 432 x 432 3.00 76 4 SmallA20H24BLP 20.00 x 24.00 x 8.00 508 x 610 x 203 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 4 SmallA24H20BLP 24.00 x 20.00 x 8.00 610 x 508 x 203 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 SmallA24H24BLP 24.00 x 24.00 x 8.00 610 x 610 x 203 16 A24P24 A24P24G 21.00 x 21.00 533 x 533 3.00 76 5 SmallA24H30BLP 24.00 x 30.00 x 8.00 610 x 762 x 203 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 7 SmallA30H20BLP 30.00 x 20.00 x 8.00 762 x 508 x 203 14 A30P20 A30P20G 27.00 x 17.00 686 x 432 3.00 76 5 SmallA30H24BLP 30.00 x 24.00 x 8.00 762 x 610 x 203 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 LargeA30H30BLP 30.00 x 30.00 x 8.00 762 x 762 x 203 14 A30P30 A30P30G 27.00 x 27.00 686 x 686 3.00 76 7 LargeA36H24BLP 36.00 x 24.00 x 8.00 914 x 610 x 203 14 A36P24 A36P24G 33.00 x 21.00 838 x 533 3.00 76 5 LargeA36H30BLP 36.00 x 30.00 x 8.00 914 x 762 x 203 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 LargeA42H30BLP 42.00 x 30.00 x 8.00 1067 x 762 x 203 14 A42P30 A42P30G 39.00 x 27.00 991 x 686 3.00 76 8 SmallA42H36BLP 42.00 x 36.00 x 8.00 1067 x 914 x 203 14 A42P36 A42P36G 39.00 x 33.00 991 x 838 3.00 76 8 LargeA48H36BLP 48.00 x 36.00 x 8.00 1219 x 914 x 203 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 LargeA60H36BLP 60.00 x 36.00 x 8.00 1524 x 914 x 203 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 LargeA20H16CLP 20.00 x 16.00 x 10.00 508 x 406 x 254 14 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 SmallA24H20CLP 24.00 x 20.00 x 10.00 610 x 508 x 254 14 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 SmallA30H24CLP 30.00 x 24.00 x 10.00 762 x 610 x 254 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 LargeA36H30CLP 36.00 x 30.00 x 10.00 914 x 762 x 254 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 LargeA48H30CLP 48.00 x 30.00 x 10.00 1219 x 762 x 254 14 A48P30 A48P30G 45.00 x 27.00 1143 x 686 3.00 76 8 SmallA48H36CLP 48.00 x 36.00 x 10.00 1219 x 914 x 254 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 LargeA60H36CLP 60.00 x 36.00 x 10.00 1524 x 914 x 254 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 LargeA30H24DLP 30.00 x 24.00 x 12.00 762 x 610 x 305 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 LargeA36H30DLP 36.00 x 30.00 x 12.00 914 x 762 x 305 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 LargeA48H36DLP 48.00 x 36.00 x 12.00 1219 x 914 x 305 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 LargeA36H30FLP 36.00 x 30.00 x 16.00 914 x 762 x 406 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 LargeA48H36FLP 48.00 x 36.00 x 16.00 1219 x 914 x 406 14 48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 LargeA60H36FLP 60.00 x 36.00 x 16.00 1524 x 914 x 406 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 LargePurchase panels separately. Optional stainless steel, conductive, composite and aluminum panels are available for most sizes.

SMartin
Rectangle
SMartin
Highlight
SMartin
Text Box
A60H36FLP3PT
SMartin
Line

Spec-00290 F

Wall-Mount EnclosurEs Type 4 Wall-MounT enclosures

PH 763.422.2211 • FAX 763.422.2600 • HOFFMANONLINE.COMEQUIPMENT PROTECTION Mild stEEl 2

Popular Accessories Enclosure Width (B Dimension) Hole Seals Window Kits12 in. (305 mm) AS050 APWK53NF16 in. (406 mm) AS050 APWK53NF20 in. (508 mm) AS050 APWK53NF24 in. (610 mm) AS050 APWK53NF30 in. (762 mm) AS050 APWK53NF36 in. (914 mm) AS050 APWK53NF

Spec-00484 J

Mounting Accessories Mounting Kits

EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEAccessories3

FLoor stAnd kit

industrY stAndArdsProduct maintains UL/CSA Type 4, 4X (stainless steel only) and Type 12 when properly installed on Hoffman Type 4 or Type 12 enclosures.

APPLicAtionKits are easily installed on most wall-mount Hoffman enclosures. Can also be used to elevate Hoffman free-stand enclosures.

To install, drill holes in the bottom of the enclosure and bolt the floor stands to the enclosure.It is not necessary to remove the wall-mount brackets from the enclosure.

sPeciFicAtions12 gauge steel floor stand has an ANSI 61 gray polyester powder finish over pretreated surfaces. Stainless steel floor stand is available in Type 316 and Type 304.

coMPonentsEach kit includes two stands. Two sets of floor stands are recommended for enclosures larger than double door free-stand enclosures.

orderingSpecial heights, depths, materials and finishes can be provided on custom order. Consult factory for information.Bulletin: A4SY, A80

Catalog Number Material Height, H (in.) Height, H (mm) Width, C (in.) Width, C (mm) L (in.) L (mm)AFK0608 Steel 6.00 152 8.06 205 7.06 179AFK0610 Steel 6.00 152 10.06 256 7.06 179AFK0612 Steel 6.00 152 12.06 306 7.06 179AFK0618 Steel 6.00 152 18.06 459 7.06 179AFK1208 Steel 12.00 305 8.06 205 8.12 206AFK1210 Steel 12.00 305 10.06 256 8.12 206AFK1212 Steel 12.00 305 12.06 306 8.12 206AFK1216 Steel 12.00 305 16.06 408 8.12 206AFK1218 Steel 12.00 305 18.13 461 8.12 206AFK1220 Steel 12.00 305 20.06 510 8.12 206AFK1808 Steel 18.00 457 8.06 205 9.17 233AFK1810 Steel 18.00 457 10.06 256 9.17 233AFK1812 Steel 18.00 457 12.06 306 9.17 233AFK1816 Steel 18.00 457 16.06 408 9.17 233AFK2408 Steel 24.00 610 8.06 205 10.23 260AFK2410 Steel 24.00 610 10.06 256 10.23 260AFK2412 Steel 24.00 610 12.06 306 10.23 260AFK2416 Steel 24.00 610 16.06 408 10.23 260AFK0608SS Stainless Steel, 304 6.00 152 8.06 205 9.09 231AFK0610SS Stainless Steel, 304 6.00 152 10.06 256 9.09 231AFK0612SS Stainless Steel, 304 6.00 152 12.06 306 9.09 231AFK0618SS Stainless Steel, 304 6.00 152 18.06 459 9.09 231AFK0624SS Stainless Steel, 304 6.00 152 24.06 611 9.09 231AFK1208SS Stainless Steel, 304 12.00 305 8.06 205 9.09 231AFK1210SS Stainless Steel, 304 12.00 305 10.06 256 9.09 231AFK1212SS Stainless Steel, 304 12.00 305 12.06 306 9.09 231AFK1216SS Stainless Steel, 304 12.00 305 16.06 408 9.09 231AFK1218SS Stainless Steel, 304 12.00 305 18.06 459 9.09 231AFK1224SS Stainless Steel, 304 12.00 305 24.06 611 9.09 231AFK1808SS Stainless Steel, 304 18.00 457 8.06 205 9.09 231AFK1810SS Stainless Steel, 304 18.00 457 10.06 256 9.09 231AFK1812SS Stainless Steel, 304 18.00 457 12.06 306 9.09 231AFK1816SS Stainless Steel, 304 18.00 457 16.06 408 9.09 231AFK1818SS Stainless Steel, 304 18.00 457 18.06 459 9.09 231AFK1824SS Stainless Steel, 304 18.00 457 24.06 611 9.09 231AFK2408SS Stainless Steel, 304 24.00 610 8.06 205 9.09 231AFK2410SS Stainless Steel, 304 24.00 610 10.06 256 9.09 231AFK2412SS Stainless Steel, 304 24.00 610 12.06 306 9.09 231

SMartin
Rectangle
SMartin
Line

Spec-00484 J

Mounting Accessories Mounting Kits

PH 763.422.2211 • FAX 763.422.2600 • HOFFMANONLINE.COMEQUIPMENT PROTECTION Accessories 4

Catalog Number Material Height, H (in.) Height, H (mm) Width, C (in.) Width, C (mm) L (in.) L (mm)AFK2416SS Stainless Steel, 304 24.00 610 16.06 408 9.09 231AFK2418SS Stainless Steel, 304 24.00 610 18.06 459 9.09 231AFK2424SS Stainless Steel, 334 24.00 610 24.06 611 9.09 231AFK0608SS6 Stainless Steel, 316 6.00 152 8.06 205 9.09 231AFK0610SS6 Stainless Steel, 316 6.00 152 10.06 256 9.09 231AFK0612SS6 Stainless Steel, 316 6.00 152 12.06 306 9.09 231AFK0618SS6 Stainless Steel, 316 6.00 152 18.06 459 9.09 231AFK0624SS6 Stainless Steel, 316 6.00 152 24.06 611 9.09 231AFK1208SS6 Stainless Steel, 316 12.00 305 8.06 205 9.09 231AFK1210SS6 Stainless Steel, 316 12.00 305 10.06 256 9.09 231AFK1212SS6 Stainless Steel, 316 12.00 305 12.06 306 9.09 231AFK1216SS6 Stainless Steel, 316 12.00 305 16.06 408 9.09 231AFK1218SS6 Stainless Steel, 316 12.00 305 18.06 459 9.09 231AFK1224SS6 Stainless Steel, 316 12.00 305 24.06 611 9.09 231AFK1808SS6 Stainless Steel, 316 18.00 457 8.06 205 9.09 231AFK1810SS6 Stainless Steel, 316 18.00 457 10.06 256 9.09 231AFK1812SS6 Stainless Steel, 316 18.00 457 12.06 306 9.09 231AFK1816SS6 Stainless Steel, 316 18.00 457 16.06 408 9.09 231AFK1818SS6 Stainless Steel, 316 18.00 457 18.06 459 9.09 231AFK1824SS6 Stainless Steel, 316 18.00 457 24.06 611 9.09 231AFK2408SS6 Stainless Steel, 316 24.00 610 8.06 205 9.09 231AFK2410SS6 Stainless Steel, 316 24.00 610 10.06 256 9.09 231AFK2412SS6 Stainless Steel, 316 24.00 610 12.06 306 9.09 231AFK2416SS6 Stainless Steel, 316 24.00 610 16.06 408 9.09 231AFK2418SS6 Stainless Steel, 316 24.00 610 18.06 459 9.09 231AFK2424SS6 Stainless Steel, 316 24.00 610 24.06 611 9.09 231

25

Custom Connector Corporation • 1738 E. 30th, Cleveland, OH 44114 • 216/241-1679 • Fax 216/241-5529E-mail: [email protected] • Web: www.customconnector.com

RELAY SOCKET ACCESSORIES DIN RAIL DRAWINGS & SPECIFICATIONS

PART NO. DESCRIPTION SERIES NO.

C-103-PM Prepunched Aluminum DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-104-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-105-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-106-2PM Prepunched Steel DIN Rail (2 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

.984[25.00]

1.063[27.00]

.287[7.29]

.943[23.95]

1.378[35.00]

.177[4.50]

R.

1.083[27.50] 1.378[35.00]TYP.

39.370 [1000.00]

R.

1.063[27.00]

.295[7.50]

1.378[35.00]

.709[18.00]

.205[5.20]

.492[12.50] .984[25.00]

39.370[1000.00]

1.063[27.00]1.378[35.00]

.709[18.00]

.492[12.50] .984[25.00]

39.370[1000.00] .590[15.00]

R.

.248[6.30]

.039[1.00]

.709[18.00]

.492[12.50] .984[25.00]

78.740[2000.00]

R.

.248[6.30] 1.378[35.00] 1.063[27.00]

.295[7.50]

OTHER STYLES AND HOLE PATTERNS AVAILABLE. CONSULT FACTORY

SMartin
Rectangle
SMartin
Line
SMartin
Line

I2

FSPDB Finger-Safe Power Distribution Blocks

Safety evolvingMersen FSPDBs introduce a new level of safety and ease for installing power distribution blocks. An IP20 level of finger-safe protection is achieved using FSPDBs,eliminating the need for special covers or custom Plexiglas sheets to protect your panels. FSPDBs (sizes 1 to 4) simply snap onto 35mm DIN rail to provide the quickest installation. Modular design also allows for multi pole applications by use of assembly pins. FSPDBs provide a safe, convenient way of splicing cables, splitting primary power into a variety of secondary circuits or providing a fixed junction tap-o f point.

Ratings:Volts : 600VAmps: : 175 to 840ASCCR : 100kA with proper fuse.

Contact Technical Services for instruction sheet and/or DC Ratings.

Features/Benefits: • Finger-safe protection

Fully insulated block ensures touch safe isolation of live parts. Recessed termination screws and wire openings provide IP20 grade protection and qualify as “finger-safe” per IEC 529

• Compact modularitySingle or multiple pole configurations in the most compact foot rint. Allows users to build smaller or higher density panels.

• Snap on DIN-rail mountingSizes 1 to 4 feature integral DIN rail adaptors allowing for quick and easy installations on 35mm DIN rail yielding lower installed costs.

• Captive termination screwsUnique channel design ensures captive metric wire termination screws. Screws can never be lost.

• Available accessoriesFor multi-pole panel mounting, simply snap in pins for rigid fi . Cap plugs provide the ability to maintain touch safety on unused openings. Circuit identification markers simply snap into blocks to ID circuits. nd anchors provide rigid end stops.

• Multiple wire ratingsProvide users more versatility by offering capability of using multiple conductors in #2 and 2/0 openings.

• AC & DC ratingsFSPDB1, 2, and 3 have been evaluated for use at 1000V (AC or DC) provided they are installed on DIN-rails only and with barriers between poles of opposite polarity of sufficient size to maintain requi ed spacings.

Approvals: • UL Recognized Component

Guide XCFR2, File E73571 • CSA Certified: Class 6228, Fil

69363

For the most current product performance data visit us-ferrazshawmut.mersen.com and use catalog search. I3

I

Catalog Numbers

A

B

C

DE

F

G

H

J

K

A

B

C

DE

F

G

HI

K

J

Figure 1 Figure 2

Dimension

FSPDB1A FSPDB2A FSPDB3A FSPDB4A FSPDB5A

FSPDB1C FSPDB2C FSPDB3C FSPDB4C FSPDB5C

Figure 1 Figure 1 Figure 2 Figure 1 Figure 2

mm in mm in mm in mm in mm in

A 25.4 1.00 28.4 1.12 46.9 1.85 39 1.54 72 2.84

B 43.3 1.70 57.8 2.28 64.3 2.53 108 4.25 91 3.58

C 49.5 1.95 56.0 2.21 64.3 2.53 80 3.15 80 3.15

D 45.1 1.78 51.6 2.03 59.8 2.36 75.5 2.97 - -

E 39.4 1.55 39.4 1.55 51.5 2.03 50.1 1.97 50.1 1.97

F 72.6 2.86 87.7 3.45 100.8 3.97 145.5 5.73 145 5.71

G 59.6 2.35 74.6 2.94 82.4 3.24 120.6 4.75 127.5 5.02

H 5.3 0.21 5.1 0.20 6.5 0.26 7 0.28 3 0.12

I - - - - 31.5 1.24 - - 52 2.04

J 5.3 0.21 6.4 0.25 6.5 0.26 6.5 0.26 6.5 0.26

K 10 0.40 11.7 0.46 8.9 0.35 16 0.63 8.5 0.34

Catalog No. Description

FSPIN1 Accessory pin to form multiple pole block

FSCIM1Circuit identification marker for 2/0 & #2 max. conductors (Qty of 100)

FSCIM2 Circuit identification marker for 350, 400 & 600 kcmil max. conductors (Qty of 100)

FSCAP1 Cap plug for spare 2/0 openings

FSCAP2 Cap plug for spare 350 kcmil openings

FSCP3 Cap plug for spare 600 kcmil opening

FSEA Pair of end anchors

Multiple Wire Ratings (Same Size & Type Wires Only)

2/0 Openings #2 Openings

(2) #4 AWG (2) #10 AWG (2) #6 AWG (2-4) #12 AWG

(2) #6 AWG (2) #12 AWG (2) #8 AWG (2-4) #14 AWG

(2) #8 AWG (2) #14 AWG (2-4) #10 AWG

•Contact Mersen Technical Services at [email protected] for fuse type and maximum ampere required.

Dimensions

FSPDB Finger-Safe Power Distribution Blocks

Catalog Number Ampere Rating (Based on NEC Table 310-16 for 75° C Cu wire only)

Line LoadShort Circuit Current Rating

Aluminum Copper Wire Range Wire Range Openings Per Pole

(Connector rated for 90° C Cu/AL wire)

(Connector rated for 75° C Cu wire only)

AWG/ mm2 Openings AWG/ kcmil

mm2

FSPDB1A FSPDB1C 175 2/0-#14 70-2.5 1 2/0-#14 70-2.5 1 100kA•

FSPDB2A FSPDB2C 175 2/0-#14 70-2.5 1 #2-#14 35-2.5 4 100kA•

FSPDB3A FSPDB3C 310350-#6 185-16

1 #8-#14 8-2.5 8 100kA•2/0-#14 70-2.5

FSPDB4A FSPDB4C 335 400-#6 185-16 1 400-#6 185-16 1 100kA•

FSPDB5A FSPDB5C 840 600-#4 300-25 2 600-#4 300-25 2 100kA•

Accessories

SMartin
Rectangle
SMartin
Line

Construction

• Attractive and durable housing is anodizedaluminum

• Thermostat, standard on all units, is adjustablefrom 0°F to 100°F (-18°C to 38°C)

• Fan draws cool air from the bottom of theenclosure and passes this air across thethermostat and heating elements beforebeing released into enclosure cavity

• Heated air is discharged through the top ofthe heater unit

• Four 10-32 self-tapping screws are includedwith each heater

• Ball bearing fan runs continuously for eventemperature distribution

• Terminal strip with clamp connector thataccepts both solid and stranded wire

Finish

Brushed aluminum.

Industry Standards

UL Component RecognizedCSA ListedCE

Hoffman electric heaters should be centered aslow as possible on an interior enclosure panel.This permits the unit to heat the cool airlocated at the bottom of the enclosure. Formaximum efficiency and longevity, the heatershould be mounted in a vertical position withthe terminal block to the bottom and the airoutlet openings at the top in a sealedenclosure free from dust or debris. However,the unit will also effectively distribute heat ifturned 90 degrees with the terminal block outthe bottom and the air outlet at the side.Although enclosure panels are preferable,heaters may be installed on any flat sheet metalsurface. Do not install heaters on wood panels.

Heat sensitive components should not beplaced near the heater discharge area since thisair can be quite warm.The clearance rangedefines the space that must be kept free ofthese components for proper and safeoperation of the heater.

Application

Designed to protect sensitive mechanical,electrical, and electronic equipment from theharmful effects of condensation, corrosion, andlow temperatures.Thermostatically controlledfan-driven heater units maintain a stabletemperature within enclosures so criticalcomponents can perform more reliably over a longer period of time.

Catalog WeightNumber Watts Voltage Hz Amps lb. (kg.)DAH1001A 100 115 50/60 0.9 4.00 (1.81)

DAH1002A 100 230 50/60 0.6 4.00 (1.81)

DAH2001A 200 115 50/60 1.7 4.00 (1.81)

DAH2002A 200 230 50/60 0.9 4.00 (1.81)

DAH4001B 400 115 50/60 3.3 6.00 (2.72)

DAH4002B 400 230 50/60 1.7 6.00 (2.72)

DAH8001B 800 115 50/60 6.5 6.00 (2.72)

DAH8002B 800 230 50/60 3.3 6.00 (2.72)

Standard Sizes Electric Heaters

9.46 Data subject to change without notice 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.

Electric Heaters

Installation

CAUTION

These electric heaters are not designed for use in dusty, dirty, corrosive, or hazardouslocations.

Portions of the heater can get hot. Adequateprotection must be taken to protect peoplefrom potential burns, and to protect othercomponents from this heat.

Hoffman recommends this heater only beinstalled in a totally-enclosed metalenclosure.

Do not install heaters on wood panels.

Rev. A October 2004

SMartin
Rectangle
SMartin
Line
SMartin
Highlight

9.47Data subject to change without notice 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.

Heaters

Electric H

eaters

9

Bulletin

D85

Dimensions and Clearance Range for DAH1001A, -2A and DAH2001A, -2A

Dimensions and Clearance Range for DAH4001B, -2B and DAH8001B, -2B

Bulletin

D85

Technical Data

Regu

latin

g

KT 011 Small Thermostat

||

KT01

1/11

-12/

US

Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.

STEGO, Inc. · 1395 South Marietta Parkway · Building 800 · Marietta, GA 30067 · Tel: (770) 984-0858 · Fax: (770) 984-0615Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com

Compact design

Wide adjustment range

Color coded temperature dials

DIN rail mountable

Thermostat NC (normally closed)Thermostat opens on temperature rise - for regulating heaters or for switching signal devices.Comes with red temperature dial.

Thermostat NO (normally open)Thermostat closes on temperature rise - for regulating filter fans and heat exchangers or forswitching signal devices. Comes with blue temperature dial.

Switching difference 12.6 °F ± 7 °F tolerance (7 K ± 4 K)

Sensor element thermostatic bimetal

Contact type snap-action contact

Service life > 100,000 cycles

Max. switching capacity 15 A resistive / 2 A inductive @ AC 120 V

10 A resistive / 2 A inductive @ AC 250 V

DC 30 W

Max. inrush current AC 16 A for 10 sec.

Connection 2-pole terminal, clamping torque 0.5 Nm max.:

solid wire - AWG 14 max. (2.5 mm²)

stranded wire (with wire end ferrule) - AWG 16 (1.5 mm²)

Housing plastic, UL 94V-0, light grey

Mounting clip for 35 mm DIN rail, EN 60715

(or for Exhaust Filter EF 118 Series)

Mounting position vertical

Operating / Storage temperature -49 to +176 °F (-45 to +80 °C)

Dimensions 2.4 x 1.3 x 1.7” (60 x 33 x 43 mm)

Weight approx. 1.4 oz. (40 g)

Protection type IP20

Setting range Part No. (NC) Part No. (NO) Approvals+32 to +140 °F 01140.9-00 01141.9-00 UL File No. E164102, CSA, VDE

0 to +60 °C 01146.9-00 01147.9-00 UL File No. E164102, CSA, VDE-10 to +50 °C 01142.0-00 N/A UL File No. E164102, CSA, VDE+10 to +70 °C N/A 01149.9-00 UL File No. E164102, CSA, VDE-15 to +45 °C 01157.0-00 01156.0-00 UL File No. E164102, CSA, VDE+20 to +80 °C 01159.0-00 01158.0-00 UL File No. E164102, CSA, VDE

1.3” (33 mm)

1.7

”(4

3m

m)

2.4

”(6

0m

m)

NC (red) NO (blue) Wiring examples

KT 011 Thermostat Heater KT 011 Thermostat e.g. Fan KT 011 Thermostat e.g. Signal Device

SMartin
Highlight
SMartin
Rectangle
SMartin
Line

Industrial Buyers Guide 207For additional technical information visit www.rittal-corp.com

Metric measurements for this product are exact, imperial measurements are rounded to the nearest whole number

Air Displacement: 12 - 39 cfm (20 - 66 m3/h)Part No. (Filter Fan and Filter Unit) 3237.100 3237.110 3237.124 3238.100 3238.110 3238.124

Rated operating voltage V, Hz 230, 50/60 115, 50/60 24 (DC) 230, 50/60 115, 50/60 24 (DC)

Dimensions inches (mm)

B1/H1 5 x 5 (116.5 x 116.5) 6 x 6 (148.5 x 148.5)

B2/H2 4 x 4 (92 x 92) 5 x 5 (124 x 124)

T1 1 (16) 1 (16)

Max. installation depth mm T2 2 (43) 2 (58.5)

Air throughput, unimpeded air flow 12/15 cfm (20/25 m3/h) 12 cfm (20 m3/h) 32/39 cfm (55/66 m3/h) 32 cfm (55 m3/h)

“Air throughput with outlet filterincluding standard filter mat cfm” 1 x SK 3237.200: 9/11 cfm (15/18 m3/h) 1 x SK 3238.200: 25/29 cfm (43/50 m3/h)

2 x SK 3238.200: 27/33 cfm (46/56 m3/h)

Diagonal fan Self-starting shaded pole motor DC motor Self-starting shaded

pole motor DC motor

Rated current 0.065 A/0.052 A 0.14 A/0.12 A 0.14 A 0.12 A/0.11 A 0.24 A/0.23 A 0.28 A

Power consumption 11 W/9 W 3 W 19 W/17 W 6 W

Pre-fuse 2 A

Noise level 38/43 dB (A) 38 dB (A) 46/49 dB (A) 46 dB (A)

Operating temperature range F° (C°) 5 to 131° F (–15 to +55° C)

Storage temperature range F °(C°) -22 to 180° F (–30 to +85° C)

Color RAL 7035

Part No. outlet filter 3237.200 3238.200

Accessories PU Page

Filter mats 5 3321.700 3322.700 270

Fine filter mats 5 – 3238.055 270

Hose-proof hood - 304 stainless steel 1 3237.0801) 3238.0802) 272

Hose-proof hood - RAL 7035 1 3237.0851) 3238.0853) 272

Blanking cover 1 3237.020 3238.020 -

Thermostat 1 3110.000 265

Digital temperature display 1 3114.200 266

Hygrostat 1 3118.000 265

Speed control 1 3120.200 268

Special voltages and colors available on request. We reserve the right to make technical modifications.1) UL type 3R 2) UL type 4X 3) UL type 3R/4

Filter Fan

Configuration: Filter fan unit ready for installation, including filter mats, self adhesive mojunting template and instructions.

Protection Ratings: NEMA 12 / IP 54 standardNEMA 12 / IP 55 with additional fine filter matNEMA 3R / 4X / IP 56 with additional fine filter mat and hose-proof hood

Property Rights: German Registered Design No. M 93 04 846

Certifications:CE - 3527009UL/cUL - 76083

H2

B2

H1

T2

B1

T1

B = WidthT = Depth

Industrial Buyers Guide 209For additional technical information visit www.rittal-corp.com

Air Displacement: 106 - 147 cfm (180 - 250 m3/h)Part No. (Filter Fan and Filter Unit) 3240.100 3240.110 3240.124 3241.100 3241.110 3241.124

Rated operating voltage V, Hz 230, 50/60 115, 50/60 24 (DC) 230, 50/60 115, 50/60 24 (DC)

Dimensions inches (mm)

B1/H1 10 x 10 (255 x 255)

B2/H2 9 x 9 (224 x 224)

T1 .98 (25)

Max. installation depth inches (mm) T2 4.21 (107)

Air throughput, unimpeded air flow 106/94 cfm (180/160 m3/h) 106 cfm (180 m3/h) 135/147 cfm (230/250 m3/h) 135 cfm (230 m3/h)

Air throughput with outlet filterincluding standard filter mat

1 x SK 3240.200: 81/71 cfm (138/121 m3/h)2 x SK 3240.200: 97/82 cfm (165/140 m3/h)1 x SK 3243.200: 97/82 cfm (165/140 m3/h)

1 x SK 3240.200: 108/120 cfm (183/205 m3/h)2 x SK 3240.200: 119/135 cfm (203/230 m3/h)1 x SK 3243.200: 119/135 cfm (203/230 m3/h)

Diagonal fan Self-starting shaded pole motor DC motor Self-starting shaded pole motor DC motor

Rated current 0.19 A/0.18 A 0.38 A/0.36 A 0.07 A 0.27 A/0.28 A 0.54 A/0.52 A 0.2 A

Power consumption 33 W/33 W 10 W 42 W/46 W 43 W/46 W 25 W

Pre-fuse 2 A 4 A 2 A 4 A 2 A

Noise level 51/46 dB (A) 51 dB (A) 54/56 dB (A) 54 dB (A)

Operating temperature range F° (C°) -22 to 131° F (–30 to +55° C)

Storage temperature range F° (C°) -22 to 185° F (–30 to +85° C)

Color RAL 7035

Part No. outlet filter 3240.200

Accessories PU Page

Filter mats 5 3172.100 270

Fine filter mats 5 3182.100 270

Hose-proof hood - 304 stainless steel 1 3240.0801) 272

Hose-proof hood - RAL 7035 1 3240.0852) 272

Blanking cover 1 3240.020 -

Thermostat 1 3110.000 265

Digital temperature display 1 3114.200 266

Hygrostat 1 3118.000 265

Speed control 1 3120.200 268

Special voltages and colors available on request. We reserve the right to make technical modifications.1) UL type 4X 2) UL type 3R/4

Filter Fan

SMartin
Highlight
SMartin
Highlight
SMartin
Rectangle
SMartin
Rectangle
SMartin
Line
SMartin
Rectangle
SMartin
Line
SMartin
Rectangle
SMartin
Highlight

Industrial Buyers Guide272 Inch and pound measurements are rounded to the nearest whole number

Accessories

Filter mats for air conditionersRittal cooling units are low-maintenance and are supplied without filter mats. Filter mats may be used for extreme conditions.

Material:Open-celled polyurethane foamed plastic withexcellent physical and mechanical properties.Temperature-resistant from -40 to 176° F (-40 to +80° C).Thickness: 0.4" (10 mm)

For TopTherm air conditioners H x W x D inches (mm) PU Part No.

3302.300/3302.310 4 x 8 x 0.4 (95 x 190 x 10) 3 3286.110

3302. . . ./3303. . . ./3361. . . . 8 x 10 x 0.4 (200 x 265 x 10) 3 3286.300

3304. . . ./3305. . . ./3328. . . ./3329. . . ./3332. . . ./ 3366. . . . 11 x 14 x 0.4 (268 x 344 x 10) 3 3286.400

3273. . . ./3382. . . ./3383. . . ./3384. . . ./3385. . . ./ 3359. . . . 10 x 21 x 0.4 (255 x 530 x 10) 3 3286.500

3386. . . ./3387. . . . 12 x 28 x 0.4 (300 x 720 x 10) 3 3286.600

3377. . . . 8 x 8 x 0.4 (210 x 205 x 10) 3 3253.010

For discontinued air conditioners H x W x D inches (mm) PU Part No.

3296. . . ./3272.100/3290. . . ./3280.100/3299. . . ./ 3261. . . . 13 x 21 x 0.4 (332 x 539 x 10) 3 3286.100

3265.100/3266.100 13 x 11 x 0.4 (332 x 270 x 10) 3 3267.100

3256. . . . 12 x 16 x 0.4 (300 x 395 x 10) 3 3254.000

3293. . . ./3281.100/3298. . . ./3279.100/3260. . . ./ 3269. . . ./3262.100/3393. . . ./3381.100/3391. . . . 12 x 13 x 0.4 (313 x 334 x 10) 3 3294.100

3255. . . ./3395. . . . 10 x 14 x 0.4 (245 x 350 x 10) 3 3253.000

3394. . . . 8 x 12 x 0.4 (200 x 315 x 10) 3 3285.000

3292.134/3278.134 10 x 13 x 0.4 (250 x 325 x 10) 3 3286.000

For Dimensions inches (mm)

Part No. Stain-less

Part No. RAL 7035

3237... 9 x 6 x 2(230 x 150 x 40) 3237.0801) 3237.0852)

3238... 10 x 7 x 2(245 x 176 x 55) 3238.0801) 3238.0852)

3239... 13 x 9 x 2(33 x 233 x 55) 3239.0801) 3239.0852)

3240, 3241...

15 x 11 x 3(390 x 282 x 85) 3240.0801) 3240.0852)

3243, 3244...

19 x 14 x 4(480 x 350 x 110) 3243.080 3243.085

3321. . . 10 x 6 x 2 (260 x 150 x 40) 3321.800 3321.835

3322. . . 11 x 7 x 2 (270 x 176 x 55) 3322.800 3322.835

3323. . . 16 x 9 x 2 (410 x 233 x 55) 3323.800 3323.835

3324. . . 3325. . .

20 x 11 x 3 (500 x 282 x 85) 3324.800 3324.835

3326. . . 3327. . .

22 x 14 x 4 (560 x 350 x 110) 3326.800 3326.835

1)UL Type 4X2)UL Type 4

Hose-proof hoodsFor filter fan units/outlet filters

When the hose-proof hood is mounted above the filter fan unit and outlet filter a rating of IP 56 (UL 3R) to EN 60 529/10.91 is achieved. Particularly suitable for use in the food industry.

Material: Stainless steel Painted steel RAL 7035 (light gray)

Protection Ratings: In conjunction with the filter fan units/outlet filters, UL Type 3R + 12 is met. UL and cUL recognized

UL file: E76083

SMartin
Rectangle
SMartin
Rectangle
SMartin
Line

© 2011 Schneider ElectricAll Rights Reserved

PowerPact™ H-, J-, and L-Frame Circuit Breakers Catalog Numbering

811/2011 ™

The PowerPact™ H-, J-, and L-frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. H- and J-frame circuit breakers are available with either thermal-magnetic or Micrologic™ electronic trip units. L-frame circuit breakers are available with Micrologic electronic trip unit.

Catalog Numbering

Table 1: Interrupting RatingUL/CSA/NOM IEC 647-2 Icu/Ics

240 Vac 480 Vac 600 Vac 250 Vdc1 500 Vdc1

1 DC ratings only available with PowerPact H or J circuit breakers with thermal-magnetic trip units.

220/240 Vac 380/440/415 Vac 500/525 Vac 250 Vdc1,2

2 IEC DC rating only available on PowerPact J-frame circuit beakers.

500 Vdc1,2

D 25 kA 18 kA 14 kA 20 kA — 25/25 kA 18/18 kA 14/14 kA 20 kA 20 kA

G 65 kA 35 kA 18 kA 20 kA 20 kA 65/65 kA 35/35 kA 18/18 kA 20 kA 20 kA

J 100 kA 65 kA 25 kA 20 kA — 100/100 kA 65/65 kA 25/25 kA 20 kA 20 kA

L 125 kA 100 kA 50 kA 20 kA — 125/125 kA 100/100 kA 50/50 kA 20 kA 20 kA

Trip Unit

Micrologic Electronic Trip Units

U31 LI Standard Protection U33 LSI Standard Protection U43 LSI plus Ammeter U44 LSIG plus Ammeter U53 LSI plus Energy Management U54 LSIG plus Energy Management M37 Magnetic Only (L-Frame Only)M38 Motor Protector Circuit Breaker StandardS40 400 A Molded Case Switch (L-Frame Automatic Switch)S60 600 A Molded Case Switch (L-Frame Automatic Switch)F40 400 A L-Frame Only (No Trip Unit)F60 600 A L-Frame Only (No Trip Unit)

Thermal-Magnetic Trip Units

— Standard Fixed Trip Unit (Suitable for reverse connection)F06 60 A H-Frame Only (No trip unit)F15 150 A H-Frame Only (No trip unit)F25 250 A J-Frame Only (No trip unit)T Complete Circuit Breaker (Frame + removable trip unit)S15 150 A Molded Case Switch (H-Frame automatic switch)S17 175 A Molded Case Switch (J-Frame automatic switch)S25 250 A Molded Case Switch (J-Frame automatic switch)C 100% Rated Continuous Current Rating1

M71 30 A H-Frame Motor Circuit Protector (MCP)M72 50 A H-Frame Motor Circuit Protector (MCP)M73 100 A H-Frame Motor Circuit Protector (MCP)M74 150 A H-Frame Motor Circuit Protector (MCP)M75 250 A J-Frame Motor Circuit Protector (MCP)D81 500 Vdc 150–175 A J-Frame Molded Case Circuit BreakerD82 500 Vdc 200–250 A J-Frame Molded Case Circuit BreakerR 100% Rated Continuous Current Rating Complete Circuit Breaker

(Frame + removable trip unit)

1 100% ratings valid for:3P H/J frame unit mount only3P/4P L-frame 250 A and 400 A unit mount3P L-frame 250 A and 400 A I-Line

I-Line™ Phasing

— ABC (3P)6 CBA (3P)1 AB (2P)2 AC (2P)3 BA (2P)4 BC (2P)5 CA (2P)6 CB (2P)

Frame

H H-FrameJ J-FrameL L-Frame

Poles

2 2P3 3P4 4P

Amperage

060 60 A100 100 A150 150 A250 250 A400 400 A600 600 A000 Switch or

Frame only

Voltage

6 600 Vac

Terminations

L Lugs Line/Load SideM Lugs Line SideP Lugs Load SideF Bus BarA I-LineS Rear ConnectedN Plug-inD DrawoutK Reverse I-Line

Performance Level (kA) (See Table 1)

Accessory Suffix Code (See Table 2)

– J L L 3 6 250 T – – – – –

Brand

_ Square DN Schneider

Electric

SMartin
Rectangle
SMartin
Highlight

PowerPact™ H-, J-, and L-Frame Circuit BreakersCircuit Breakers

2511/2011© 2011 Schneider Electric

All Rights Reserved™

H- and J-Frame Catalog Numbers

Unit-Mount Circuit Breaker Catalog Numbers

Table 14: PowerPact H-Frame 150 A Unit-Mount Thermal-Magnetic Circuit Breakers (600 Vac, 250 Vdc) with Factory Sealed Trip Unit (Suitable for Reverse Connection)

Current Rating @ 40 C

Fixed AC Magnetic Trip

Interrupting RatingStandard Lug KitTerminal Wire Range

D G J1 L1

Hold TripStandard (80%) Rated

100% Rated2

Standard (80%) Rated

100% Rated2

Standard (80%) Rated

100% Rated2

Standard (80%) Rated

100% Rated2

H-Frame, 150 A, 2P, 600 Vac 50/60Hz, 250 Vdc3

15 A 350 A 750 A HDL26015 HDL26015C HGL26015 HGL26015C HJL26015 HJL26015C HLL26015 HLL26015C

AL150HD14–3/0 AWGAl or Cu

20 A 350 A 750 A HDL26020 HDL26020C HGL26020 HGL26020C HJL26020 HJL26020C HLL26020 HLL26020C25 A 350 A 750 A HDL26025 HDL26025C HGL26025 HGL26025C HJL26025 HJL26025C HLL26025 HLL26025C30 A 350 A 750 A HDL26030 HDL26030C HGL26030 HGL26030C HJL26030 HJL26030C HLL26030 HLL26030C35 A 400 A 850 A HDL26035 HDL26035C HGL26035 HGL26035C HJL26035 HJL26035C HLL26035 HLL26035C40 A 400 A 850 A HDL26040 HDL26040C HGL26040 HGL26040C HJL26040 HJL26040C HLL26040 HLL26040C45 A 400 A 850 A HDL26045 HDL26045C HGL26045 HGL26045C HJL26045 HJL26045C HLL26045 HLL26045C50 A 400 A 850 A HDL26050 HDL26050C HGL26050 HGL26050C HJL26050 HJL26050C HLL26050 HLL26050C60 A 800 A 1450 A HDL26060 HDL26060C HGL26060 HGL26060C HJL26060 HJL26060C HLL26060 HLL26060C70 A 800 A 1450 A HDL26070 HDL26070C HGL26070 HGL26070C HJL26070 HJL26070C HLL26070 HLL26070C80 A 800 A 1450 A HDL26080 HDL26080C HGL26080 HGL26080C HJL26080 HJL26080C HLL26080 HLL26080C90 A 800 A 1450 A HDL26090 HDL26090C HGL26090 HGL26090C HJL26090 HJL26090C HLL26090 HLL26090C100 A 900 A 1700 A HDL26100 HDL26100C HGL26100 HGL26100C HJL26100 HJL26100C HLL26100 HLL26100C110 A 900 A 1700 A HDL26110 HDL26110C HGL26110 HGL26110C HJL26110 HJL26110C HLL26110 HLL26110C125 A 900 A 1700 A HDL26125 HDL26125C HGL26125 HGL26125C HJL26125 HJL26125C HLL26125 HLL26125C150 A 900 A 1700 A HDL26150 HDL26150C HGL26150 HGL26150C HJL26150 HJL26150C HLL26150 HLL26150C

H-Frame, 150 A, 3P, 600 Vac 50/60Hz, 250 Vdc

15 A 350 A 750 A HDL36015 HDL36015C HGL36015 HGL36015C HJL36015 HJL36015C HLL36015 HLL36015C

AL150HD14–3/0 AWGAl or Cu

20 A 350 A 750 A HDL36020 HDL36020C HGL36020 HGL36020C HJL36020 HJL36020C HLL36020 HLL36020C25 A 350 A 750 A HDL36025 HDL36025C HGL36025 HGL36025C HJL36025 HJL36025C HLL36025 HLL36025C30 A 350 A 750 A HDL36030 HDL36030C HGL36030 HGL36030C HJL36030 HJL36030C HLL36030 HLL36030C35 A 400 A 850 A HDL36035 HDL36035C HGL36035 HGL36035C HJL36035 HJL36035C HLL36035 HLL36035C40 A 400 A 850 A HDL36040 HDL36040C HGL36040 HGL36040C HJL36040 HJL36040C HLL36040 HLL36040C45 A 400 A 850 A HDL36045 HDL36045C HGL36045 HGL36045C HJL36045 HJL36045C HLL36045 HLL36045C50 A 400 A 850 A HDL36050 HDL36050C HGL36050 HGL36050C HJL36050 HJL36050C HLL36050 HLL36050C60 A 800 A 1450 A HDL36060 HDL36060C HGL36060 HGL36060C HJL36060 HJL36060C HLL36060 HLL36060C70 A 800 A 1450 A HDL36070 HDL36070C HGL36070 HGL36070C HJL36070 HJL36070C HLL36070 HLL36070C80 A 800 A 1450 A HDL36080 HDL36080C HGL36080 HGL36080C HJL36080 HJL36080C HLL36080 HLL36080C90 A 800 A 1450 A HDL36090 HDL36090C HGL36090 HGL36090C HJL36090 HJL36090C HLL36090 HLL36090C100 A 900 A 1700 A HDL36100 HDL36100C HGL36100 HGL36100C HJL36100 HJL36100C HLL36100 HLL36100C110 A 900 A 1700 A HDL36110 HDL36110C HGL36110 HGL36110C HJL36110 HJL36110C HLL36110 HLL36110C125 A 900 A 1700 A HDL36125 HDL36125C HGL36125 HGL36125C HJL36125 HJL36125C HLL36125 HLL36125C150 A 900 A 1700 A HDL36150 HDL36150C HGL36150 HGL36150C HJL36150 HJL36150C HLL36150 HLL36150C

1 UL Listed/CSA Certified as current limiting circuit breakers.2 100% rated circuit breakers have copper lugs and can be used with copper wire only.3 HD and HG circuit breakers are true 2-pole construction.

SMartin
Rectangle
SMartin
Rectangle
SMartin
Line

© 2011 Schneider ElectricAll Rights Reserved

PowerPact™ H-, J-, and L-Frame Circuit Breakers Accessories and Auxiliaries

10411/2011 ™

Rotary Operating Handles

Directly Mounted Rotary Operating Handles

Door-Mounted (Extended) Rotary Operating Handle

Directly Mounted Rotary Operating Handle

pushto

trip

0616

3068

Installation The directly mounted rotary operating handle replaces the circuit breaker front accessory cover (secured by screws).

Operation

The direct rotary handle maintains:• Suitability for isolation• Indication of three positions: I (ON), Tripped and O (OFF)• Access to the “push-to-trip” button• Visibility of, and access to, trip unit settings• The circuit breaker may be locked in the OFF position by using one to three

padlocks (not supplied)

Models • Standard with black handle• VDE type with red handle and yellow bezel for machine tool control

Variations

Accessories transform the standard direct rotary handle for the following situations:• Motor control centers (MCCs):

– Opening of door prevented when circuit breaker is on– Closing of circuit breaker inhibited when door is open

• Machine tool control; complies with CNOMO E03.81.501N; degree of protection IP54• Early make or early break contacts may be installed into direct mount rotary handle

Standards The directly-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561

I/ON(Closed)

Tripped

O/OFF(Open)

Door Mounted Rotary Operating Handle

Installation

The door-mounted (extended) rotary operating handle is made up of:• A unit that replaces the front accessory cover of the circuit breaker (secured by screws)• An assembly (handle and front plate) on the door that is always secured in the same position, whether the

circuit breaker is installed vertically or horizontally• An adjustable extension shaft• The handle mechanism can be used in NEMA 3R and 12 enclosure applications

Operation

The door mounted operating handle makes it possible to operate circuit breakers installed in enclosure from the front. The door mounted operating handle maintains:• Suitability for isolation• Indication of the three positions OFF (O), ON (I) and tripped• Visibility of and access to trip unit settings when the door is open• Degree of protection: IP40 as per IEC 529Defeatable interlock prevents opening of door when circuit breaker is onThe circuit breaker may be locked in the off position by using one to three padlocks, padlock shackle diameter 0.19–0.31 in. (5–8 mm); padlocks are not supplied; locking prevents opening of the enclosure door

Shaft Length

The shaft length is the distance between the back of the circuit breaker and the door:• Minimum shaft length is 7.4 (185 mm)• Maximum shaft length is 24 in. (600 mm)• Extended shaft length must be adjusted

Models • Standard with black handle• VDE type with red handle and yellow bezel for machine tool control

Variations For drawout configurations, the extended rotary handle is also available with a telescopic shaft containing two stable positions

Standards The door-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561

SMartin
Rectangle

PowerPact™ H-, J-, and L-Frame Circuit BreakersAccessories and Auxiliaries

10511/2011© 2011 Schneider Electric

All Rights Reserved™

Class 9421 NEMA Door Mounted Rotary Operating Handles

Table 91: Rotary Operated Handles

H- and J-Frame L-Frame

Device DescriptionFactory Installed

Suffix

Field Installable

Kit No.

Factory Installed

Suffix

Field Installable

Kit No.

Direct Mounted

Standard Handle Black Handle only RD10 S29337 RD10 S32597

Standard Black Handle with One early-break switch RD12 S29337 +

S29345 — —

Two early-make switches RD13 S29337 + S29346 — —

Red handle on yellow bezel

Handle Only RD20 S29339 RD20 S32599

One early-break switch RD22 S29339 + S29345 — —

Two early-make switches RD23 S29339 + S29346 — —

MCC Conversion Accessory — S429341 — S32606

CNOMO Conversion Accessory — — — S32602

Door Mounted

Standard black handle Handle Only RE10 S29338 RE10 S32598

Standard Black Handle with: Two early make switches RE13 S29338 + S29345 — —

Red handle on yellow bezel Handle Only RE20 S29340 RE20 S32600

Telescoping RT10 S29343 RT10 S32603

Accessories

Key lock adapter — S429344 — S32604

Key locks

Ronis 1351.500 — S41940 — S41940

Profalux KS5 B24 D4Z — S42888 — S42888

2 Ronis keylocks with 1 key — S41950 — S41950

2 Profalux keylocks with 1 key — S42878 — S42878

Indication Auxiliary SwitchOne early-break switch — — — S32605

Two early-make switches — — — S29346

Installation

The extended rotary operating handle is made up of:• A mounting plate that provides a rotary actuator for a standard toggle circuit breaker• Handle assemblies available for NEMA 3, 3R, 4, and 4X• Available in standard or short (3 in.) handle assemblies

OperationThe door mounted operating handle makes it possible to operate circuit breakers installed in enclosure from the front. Provides ON (I) and OFF (O) indicationThe circuit breaker may be locked in the off position

Shaft Length

The shaft length is the distance between the back of the circuit breaker and the door:• Minimum mounting depth is 5.5 in. (138 mm)• Maximum mounting depth is 10.75 in. (273 mm) with standard shaft• Maximum mounting depth is 21.3 in. (543 mm) with long shaft

H- and J-Frame Class 9421 Door-Mounted Operating MechanismDescription Catalog No.

Standard Shaft Kit 9421LJ1Long Shaft Kit 9421LJ4

SMartin
Rectangle
SMartin
Highlight
SMartin
Line

www.schneider-electric.us

7M

INIA

TU

RE

AN

D M

OL

DE

D C

AS

EC

IRC

UIT

BR

EA

KE

RS

© 2012 Schneider ElectricAll Rights Reserved

7-17

Multi 9™ Miniature Circuit Breakers

UL 489 C60 480 Vac and UL489A C60 Miniature Circuit BreakersClass 860 / Refer to Catalog 0860CT0201

Multi 9 C60 UL 489 Listed 480V Miniature Circuit Breakers• UL 489 Listed, CSA C22.2 No. 5.1; Also IEC 60947-2; CE marked• 480Y/277 Vac @ 10 kA (2P and 3P), 277 Vac @ 10 kA (1P)• 0.5 A through 20 A• 1P, 2P, 3P, 18 mm wide per pole

• UL 486B Listed single-barrel lug: (2) 18–10 AWG (1-25 mm2) cables, Cu only• Optional ring tongue terminals

• A wide range of electrical and mechanical accessories• Suitable for reverse feeding• Trip-free mechanism• Positive indication of contact disconnect

Multi 9 C60 UL 489A Listed Miniature Circuit Breakers for DC Telecommunication ApplicationsA limited range of C60 products are UL Listed as UL 489A circuit breakers for protection of DC telecommunications circuits.

Interrupting Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7-3Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-20Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-54

Trip Curve Use Magnetic Release

C For typical loads 7–10 x ampere rating (7–14 for DC)

D For high inrush 10–14 x ampere rating

Table 7.28: UL 489 Circuit Breakers (480Y/277 Vac)

Rating (A)

C Curve—7–10 Times Ampere Rating (7–14 DC) D Curve—10–14 Times Ampere Rating

1P 2P 3P 1P 2P 3P

Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price Cat. No. $ Price

Single-Barrel Wire Lug

0.5 MGN61300 168.00 — — — — MGN61333 168.00 — — — —

1 MGN61301 168.00 MGN61312 357.00 MGN61323 519.00 MGN61334 168.00 MGN61345 357.00 MGN61356 519.00

2 MGN61302 168.00 MGN61313 357.00 MGN61324 519.00 MGN61335 168.00 MGN61346 357.00 MGN61357 519.00

3 MGN61303 168.00 MGN61314 357.00 MGN61325 519.00 MGN61336 168.00 MGN61347 357.00 MGN61358 519.00

4 MGN61304 168.00 MGN61315 357.00 MGN61326 519.00 MGN61337 168.00 MGN61348 357.00 MGN61359 519.00

5 MGN61305 168.00 MGN61316 357.00 MGN61327 519.00 MGN61338 168.00 MGN61349 357.00 MGN61360 519.00

6 MGN61306 168.00 MGN61317 357.00 MGN61328 519.00 MGN61339 168.00 MGN61350 357.00 MGN61361 519.00

8 MGN61307 168.00 MGN61318 357.00 MGN61329 519.00 MGN61340 168.00 MGN61351 357.00 MGN61362 519.00

10 MGN61308 168.00 MGN61319 357.00 MGN61330 519.00 MGN61341 168.00 MGN61352 357.00 MGN61363 519.00

15 MGN61309 168.00 MGN61320 357.00 MGN61331 519.00 MGN61342 168.00 MGN61353 357.00 MGN61364 519.00

20 MGN61310 168.00 MGN61321 357.00 MGN61332 519.00 MGN61343 168.00 MGN61354 357.00 MGN61365 519.00

Ring Tongue Terminal

0.5 MGN61366 168.00 — — — — MGN61399 168.00 — — — —

1 MGN61367 168.00 MGN61378 357.00 MGN61389 519.00 MGN61400 168.00 MGN61411 357.00 MGN61422 519.00

2 MGN61368 168.00 MGN61379 357.00 MGN61390 519.00 MGN61401 168.00 MGN61412 357.00 MGN61423 519.00

3 MGN61369 168.00 MGN61380 357.00 MGN61391 519.00 MGN61402 168.00 MGN61413 357.00 MGN61424 519.00

4 MGN61370 168.00 MGN61381 357.00 MGN61392 519.00 MGN61403 168.00 MGN61414 357.00 MGN61425 519.00

5 MGN61371 168.00 MGN61382 357.00 MGN61393 519.00 MGN61404 168.00 MGN61415 357.00 MGN61426 519.00

6 MGN61372 168.00 MGN61383 357.00 MGN61394 519.00 MGN61405 168.00 MGN61416 357.00 MGN61427 519.00

8 MGN61373 168.00 MGN61384 357.00 MGN61395 519.00 MGN61406 168.00 MGN61417 357.00 MGN61428 519.00

10 MGN61374 168.00 MGN61385 357.00 MGN61396 519.00 MGN61407 168.00 MGN61418 357.00 MGN61429 519.00

15 MGN61375 168.00 MGN61386 357.00 MGN61397 519.00 MGN61408 168.00 MGN61419 357.00 MGN61430 519.00

20 MGN61376 168.00 MGN61387 357.00 MGN61398 519.00 MGN61409 168.00 MGN61420 357.00 MGN61431 519.00

Table 7.29: UL 489A Circuit Breakers for DC Telecommunications Applications (1P, 2 Modules, C curve)

Rating (A) Cat. No. $ Price Rating (A) Cat. No. $ Price

0.5 60406 120.00 10 60414 101.00

1 60407 101.00 13 60415 101.00

2 60408 101.00 15 60416 101.00

3 60409 101.00 20 60417 101.00

4 60410 101.00 30 60418 101.00

5 60411 101.00 40 60419 111.00

6 60412 101.00 50 60420 117.00

8 60413 101.00 60 60421 123.00

1P UL489 C60

2P UL489 C60

3PUL489 C60

DE2 Discount Schedule

SMartin
Rectangle

© 2002–2010 Schneider ElectricAll Rights Reserved

Multi 9™ System Catalog Section 2—UL and CSA Rated Protection Devices

1607/2010

UL 489/CSA C22.2 No.5 Listed 240 Vac C60 Circuit Breakers (AC)

A selected range of Multi-9 circuit breakers rated 240 V are UL 489/CSA C22.2 No.5 Listed. Unlike UL 1077 Supplementary Protectors, these UL 489/CSA C22.2 No.5 circuit breakers can be used for branch circuit protection as required by the National Electrical Code.

As shown in tables Table 5 and Table 6, the UL 489/CSA C22.2 No.5 Listed products are available in C and D curves. They include devices ranging from 0.5 to 35 A.

Standard Features

• Fast closing: Allows increased withstand to the high inrush currents of some loads.

• Trip-free mechanism: Contacts cannot be held in the I-ON position when the C60 circuit breaker is tripped automatically.

• Positive indication of contact disconnect. Green mechanical indication on front face of circuit breaker shows that all poles are open.

• C curve: Overcurrent protection for all application types. Magnetic release operates from 7 to 10 times ampere rating (7 to 14 for DC applications).

UL 489/CSA C22.2 No.5 Listed Multi 9 C60 Circuit Breakers

Table 4: Specifications for UL 489/CSA C22.2 No.5 240 V Listed C60 Circuit Breakers

High Voltage Withstand 6 kV

Connector: Box Lug

Rating UL 486A File No. E216919 (Use with Copper Wire Only)

Connection

0.5–25 A: 14–4 AWG (2–25 mm2) Cables Torque to 22 lb-in. (2.48 N•m)

30–35 A: 14–2 AWG (1–35 mm2) Cables Torque to 31 lb-in. (3.52 N•m)

Connector: Ring TongueUse Single UL Listed or CSA Certified Insulated Ring Tongue Only

Screw dia. 0.2 in. (5 mm)Torque to 18 lb-in. (2.03 N•m)

Max Ring Terminal Width 0.54 in. (14 mm)

Mounting 35 mm DIN rail

Degree of ProtectionCase IP40 as per IEC 529

Terminals IP20

Temperatures

Calibration

Storage

Operating

25°C (77°F)

-40 to 80°C (-40 to 176°F)

-30 to 70°C (-22 to 158°F)

Plug-On Auxiliary Modules with Mechanical Linkage:

MN Undervoltage Trip

MX + OF Shunt Trip/Auxiliary Switch

OF Auxiliary Switch

SD Alarm Switch

Tropicalization Treatment 2 Relative Humidity: 95% at 131°F (55°C)

Number of Operating Cycles Electrical (O-C) 6,000 load, 4,000 no-load

See specifications Table 2 for dimensions, weights and interrupting ratings

1P 2P 3P

Multi 9™ System CatalogSection 2—UL and CSA Rated Protection Devices

1707/2010© 2002–2010 Schneider Electric

All Rights Reserved

• D curve: Overcurrent protection for loads with high inrush currents (motors, transformers). Magnetic release operates between 10 and 14 times ampere rating (no dc rating for D curve).

• Suitable for reverse feeding.

• Allows locking in O-OFF position using padlock attachment.

Connections

Three versions of field wiring connectors are available for the 240 Vac UL 489/CSA C22.2 No.5 Listed devices:

• Box lug, meeting UL 486A requirements

• Ring tongue terminal with 5 mm screw

• Ring Tongue terminals with Fingersafe (IP20) shrouds

The circuit breakers can be ordered with the following combinations of connectors:

• Line terminal box lug/load terminal box lug

• Line terminal ring tongue/load terminal ring tongue (for fingersafe version, add -F suffix to catalog number)

Standards

• UL 489 Circuit Breaker: File No. E215117

• Single pole 15–20 A is UL Listed as SWD (switching duty).

• 1-, 2-, and 3-pole 15–35 A are HID (high intensity discharge) rated.

• CSA C22.2 No. 5.1 Circuit Breakers: File No. 179014

• IEC 60947-2

• CE Marked

Figure 5: Connection Options for 240 Vac UL 489/CSA C22.2 No.5 Listed Devices

Box Lug

Box Lug

Ring Tongue

Ring Tongue

Fingersafe Ring Tongue

Fingersafe Ring Tongue

© 2002–2010 Schneider ElectricAll Rights Reserved

Multi 9™ System Catalog Section 2—UL and CSA Rated Protection Devices

1807/2010

Catalog Numbers

NOTE: UL 489/CSA C22.2 No.5 Listed Multi 9 circuit breakers are calibrated at 25°C (77°F). Please refer to the rating tables (page 83) for applications at temperatures greater than 25°C (77°F).

NOTE: The NEC requires that the continuous load applied to the circuit breaker shall not exceed 80% of the circuit breaker ampere rating.

Table 5: Catalog Numbers for C Curve, UL 489/CSA C22.2 No.5 Listed 240 Vac C60 Miniature Circuit Breakers (Box Lug and Ring Tongue Terminal Combinations)

Rating 1P 2P 3P

Box/Box Ring/Ring1

1 IP-20 Fingersafe ring tongue terminals may be ordered with an F suffix (example: 60210F)

Box/Box Ring/Ring1 Box/Box Ring/Ring1

0.5 A

1 A

1.5 A

60100

60101

60102

60200

60201

60202

60134

60135

60136

60234

60235

60236

60168

60169

60268

60269

2 A

3 A

4 A

60103

60104

60105

60203

60204

60205

60137

60138

60139

60237

60238

60239

60170

60171

60172

60270

60271

60272

5 A

6 A

7 A

60106

60107

60108

60206

60207

60208

60140

60141

60142

60240

60241

60242

60173

60174

60175

60273

60274

60275

8 A

10 A

13 A

60109

60110

60111

60209

60210

60211

60143

60144

60145

60243

60244

60245

60176

60177

60178

60276

60277

60278

15 A

20 A

25 A

60112

60113

60114

60212

60213

60214

60146

60147

60148

60246

60247

60248

60179

60180

60181

60279

60280

60281

30 A

35 A

60115

60116

60215

60216

60149

60150

60249

60250

60182

60183

60282

60283

Table 6: Catalog Numbers for D Curve, UL 489/CSA C22.2 No.5 Listed 240 Vac C60 Miniature Circuit Breakers (Line/Load as Box Lug or Ring Tongue Terminals)

Rating 1P 2P 3P

Box/Box Ring/Ring1

1 IP-20 Fingersafe ring tongue terminals may be ordered with an F suffix (example: 60210F)

Box/Box Ring/Ring1 Box/Box Ring/Ring1

0.5 A

1 A

1.5 A

60117

60118

60119

60217

60218

60219

60151

60152

60153

60251

60252

60253

60184

60185

60284

60285

2 A

3 A

4 A

60120

60121

60122

60220

60221

60222

60154

60155

60156

60254

60255

60256

60186

60187

60188

60286

60287

60288

5 A

6 A

7 A

60123

60124

60125

60223

60224

60225

60157

60158

60159

60257

60258

60259

60189

60190

60191

60289

60290

60291

8 A

10 A

13 A

60126

60127

60128

60226

60227

60228

60160

60161

60162

60260

60261

60262

60192

60193

60194

60292

60293

60294

15 A

20 A

25 A

60129

60130

60131

60229

60230

60231

60163

60164

60165

60263

60264

60265

60195

60196

60197

60295

60296

60297

30 A

35 A

60132

60133

60232

60233

60166

60167

60266

60267

60198

60199

60298

60299

SMartin
Rectangle
SMartin
Rectangle
SMartin
Rectangle
SMartin
Rectangle

MECHANICAL

TERMINAL TERMINAL PRODUCTI.D. ACCOMMODATION I.D.

Brass, hot

Grounding

Silver, neutral

15A 125V, NEMA 5-15R; 20A 125V Feed-Through

ELECTRICAL

DIELECTRIC CURRENT TEMP.VOLTAGE INTERR. RISE

Withstands 10kA 1500V

perUL 498

F3

Hos

pita

l & C

omm

erci

al G

rade

GFC

I Dev

ices

15A 125V & 20A 125VHospital & Commercial Grade, GFCI's 2 YEAR LIMITED

To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: www.leviton.com

30C max at fullrated current

after 50 cyclesoverload at150% rated

current for bothAC and DC appl.

per UL 498

ENVIRONMENTAL

FLAMMABILITY OPERATING TEMP.

Rated V-2 per UL 94 -35C to 65C

Ratings permanently

marked on device

#14 - #12 AWG solid or stranded

copper wire

8598-HG & 8898-HG SERIES 8598,8898, 8599-L & 8599-CP SERIES 8590 SERIES 8299 SERIES

1.7 (43.2 mm)

1.12 (28 mm)

2.7

(68.

6 m

m)

4.21

(10

6.93

mm

)

15A 125VRECEPTACLE

CLASS ACLASS ALEVITONLEVITON

GFC

I C

LAS

S

2

0 A

MP

125V

1.53 (38.9 mm)

TEST TEST

TESTTEST

TES

T ME

NS

UE

LTE

ST M

EN

SU

EL

TES

T MO

NTH

LYTE

ST M

ON

THLY

SU

IVE

Z IN

STR

UC

TIO

NS

UIV

EZ

INS

TRU

CTI

ON

FOLL

OW

DIR

EC

TIO

NS

FOLL

OW

DIR

EC

TIO

NS RESETRESET RESET RESET

8590-W8598-E 8599-CPI8599-I

Back & Side Wired

TRIP LEVEL

5±1 mA

8599-LW

20A 125V, NEMA 5-20R at Receptacle & Feed-Through

8598-HGR

GFCI®

1.7 (43.2 mm)

1.12 (28 mm)

2.7

(68.

6 m

m)

4.21

(10

6.93

mm

)

15A 125VRECEPTACLE

CLASS ACLASS ALEVITONLEVITON

GFC

I C

LAS

S

2

0 A

MP

125V

1.53 (38.9 mm)

TEST TEST

TESTTEST

TES

T ME

NS

UE

LTE

ST M

EN

SU

EL

TES

T MO

NTH

LYTE

ST M

ON

THLY

SU

IVE

Z IN

STR

UC

TIO

NS

UIV

EZ

INS

TRU

CTI

ON

FOLL

OW

DIR

EC

TIO

NS

FOLL

OW

DIR

EC

TIO

NS RESETRESET RESET RESET

1.7 (43.2 mm)

1.12 (28 mm)

2.7

(68.

6 m

m)

4.21

(10

6.93

mm

)

15A 125VRECEPTACLE

CLASS ALEVITON

GFC

I C

LAS

S

2

0 A

MP

125V

1.53 (38.9 mm)

OFF

O

SWITCH

RESETRESET

FOLL

OW

DIR

EC

TIO

NS

SU

IVE

Z IN

STR

UC

TIO

N

TES

T MO

NTH

LYTE

ST M

EN

SU

ELTEST

TEST

GROUND FAULT CIRCUITINTERRUPTER-MISC. MOTORCONTROLLER AND SWITCH

1.7 (43.2 mm)

1.12 (28 mm)

2.7

(68.

6 m

m)

4.21

(10

6.93

mm

)

15A 125VRECEPTACLE

CLASS ALEVITON

TEST

TEST

TES

T ME

NS

UE

LTE

ST M

ON

THLY

SU

IVE

Z IN

STR

UC

TIO

NFO

LLO

W D

IRE

CTI

ON

S RESET RESET

GFC

I125V

60HZ

FEE

D TH

RO

UG

H 20A

CLA

SS

A

AC

ON

LYS

WIT

CH

1000

W 1

20V

1.53 (38.9 mm)

COLOR SHALLOW WALLBOX EXTENDERFOR GFCI's

Brown 6197Ivory 6197-IWhite 6179-W

8299-G

15A 125V, NEMA 5-15R;20A 125V Feed-Through

FACE GFCI GFCI GFCI GFCI GFCI GFCICOLOR HOSPITAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE COMMERCIAL GRADE

SMARTLOCK® SMARTLOCK® SMARTLOCK® SMARTLOCK® DUPLEX w/ RED & BLANK FACEDUPLEX w/ LED DUPLEX w/ LED DUPLEX w/ 41/2” Leads BLACK BUTTONS S-P SWITCH

Contractor Pack 1.5HP@120V ACMeets 2003 Meets 2003 Meets 2003 Meets 2003 Meets 2003 Meets 2003

UL Requirements UL Requirements UL Requirements UL Requirements UL Requirements UL Requirements

Brown 8598-HG 8598 8599 – – –Ivory 8598-HGI 8598-I 8599-I† 8599-LI 8599-CPI 8590-IWhite 8598-HGW 8598-W 8599-W† 8599-LW 8599-CPW 8590-WGray 8598-HGG 8598-G 8599-G – – –Red 8598-HGR 8598-R 8599-R – – –Black – 8598-E 8599-E – – 8590-EAlmond 8598-HGA 8598-A 8599-A† – 8599-CPA –

Brown 8898-HG 8898 8899 – – –Ivory 8898-HGI 8898-I 8899-I† – – –White 8898-HGW 8898-W 8899-W† – – –Gray 8898-HGG 8898-G 8899-G – – –Red 8898-HGR 8898-R – – – –Black – – 8899-E – – –Almond 8898-HGA 8898-A 8899-A† – – –

#LR-57811 #057–

AC HORSEPOWER RATINGS

1.5

STANDARDS & CERTIFICATIONS

NEMA ANSI UL UL CSA NOMWD-6 C-73 943 Fed Spec C22.2

Class A Listed& 498 WC-596

FACE GFCI COMBO DEVICE RECEPTACLECOLOR & SINGLE-POLE SWITCH

Meets 2003 UL Requirements

Ivory 8299-IWhite 8299-WGray 8299-GAlmond 8299-A

† Includes matching nylon wallplate.

F Section 4/27/05 2:08 PM Page 4

SMartin
Rectangle
SMartin
Rectangle
SMartin
Line

Product Data Sheet 9070FSC2TERM COVER (10 kits/package)

List Price $30.00 USD

Availability Stock Item: This item is normally stocked in our distribution facility.

TechnicalCharacteristics

Category 16204 - Transformers, Industrial Control, Fuse Blocks & Accessories, Type T

Discount Schedule CP8

GTIN 00785901904755

Package Quantity 10

Weight 0.07 lbs.

Availability Code Stock Item: This item is normally stocked in our distribution facility.

Returnability Y

Country of Origin US

Shipping and Ordering

As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this document.

Generated: 08/21/2012 16:32:02

© 2012 Schneider Electric. All rights reserved.

1

SMartin
Highlight

Industrial Control TransformersType T Transformers

8© 1999–2005 Schneider Electric All Rights Reserved 08/2005

120 Volt Control Secondary

Voltage and Connection Options

Voltage Code

Voltages Connections

Primary Secondary Primary Secondary

D1220 x 440230 x 460240 x 480

110115120

220/230/240 V:Connect to H1 and H4Jumper H1 with H3Jumper H2 with H4

440/460/480 V:Connect to H1 and H4Jumper H2 with H3

Connect to X1 and X2

H1

X2 X1

H2H3 H4

DimensionsVA Catalog

NumberFigure

Acc. Key

A B C E F Slots

UL CE IN mm IN mm IN mm IN mm IN mm IN mm

25 25 9070T25D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10

50 50 9070T50D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10

75 75 9070T75D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12

100 100 9070T100D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12

150 150 9070T150D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10

200 200 9070T200D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10

250 160 9070T250D1 2 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 0.20 x 0.38 5 x 10

300 200 9070T300D1 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10

350 250 9070T350D1 2 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10

500 300 9070T500D1 2 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10

750 500 9070T750D1 2 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 0.28 x 0.56 7 x 14

1000 630 9070T1000D1 2 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 0.28 x 0.56 7 x 14

1500 1000 9070T1500D1 2 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 0.28 x 0.56 7 x 14

2000 1500 9070T2000D1 2 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 0.28 x 0.56 7 x 14

3000 2000 9070T3000D1 3 I 7.24 184 9.00 229 8.75 222 4.63 118 7.63 194 0.44 x 1.13 11 x 29

5000 3000 9070T5000D1 3 I 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194 0.44 x 1.13 11 x 29

Figure 3

BD

A

EF

C

DA B

F E

C

Figure 2Figure 1

C

BDA

EF

SMartin
Rectangle
SMartin
Line

Technical Specification

SRC 311 - SmartRun™

SRC311 v.3.0TS

Software version 3.x

Technical SpecificationProduct design

The SRC 311 is a pump drive with the SmartRun™ functionality, which is dedicated forwastewater pump stations. The drive is one of the components that is included in a pumpsystem solution for pump stations. The system consists of a level sensor, a level switch,and the drive that controls and monitors the pumps in the pump station. The system isreliable, energy efficient, and does not need extra monitor or control devices. The systemcan include up to three drives and pumps with alternation and full redundancy.

ApprovalSRC 311 version Approvals

200–240V CE, cUL

380–480V CE, cUL

500–600V CE, cUL, CSA

Facility requirementsCheck that the following requirements are met:

Environment

The drive must be protected from direct sunlight and from rainfall.

Altitude

Maximum altitude for non-de-rated operation is 1000 m (3281 ft).

Maximum altitude with UL approval is 2000 m (6562 ft).

Maximum altitude without UL approval is 4000 m (13 123 ft).

Ambient temperature

Activity °C (°F)

Operation –10 – 40 (14 – 104)

De-rated operation Maximum 50 (122)

Storage –40 – 60 (–40 – 140)

Humidity requirements

The relative humidity must not exceed 95% (non-condensing).

Air requirements

The air surrounding the unit must be free from:

• Excessive dust• Acids• Salt

Conformal coating is applied according to IEC standard 60721–3–2, Class 3C2.

Input voltageDepending upon the model and power rating, the drives are designed for directconnection to the following supplies

Technical Specification

SRC 311 - SmartRun™ Technical Specification 3

Model Number Supply Voltage Phases Frequency (Hz)

SRC311-X-X-XXXXX-XX 200 – 240 V ± 10% 1 50, 60

3

380 – 480 V ± 10% 3

500 – 600 V ± 10% 3

All SRC 311 monitor phase imbalance. A phase imbalance of > 3% results in SRC 311tripping. For input supplies which have a supply imbalance greater than 3%, an input linereactor is recommended. Alternatively, SRC 311 can be operated as a single-phase supplydrive with 50% de-rating.

Output power and current ratingsAll drives have an overload capacity of 150% for 60 seconds.

IP66

Table 1: 200 – 240 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)None UL UL

4.0 5.0 3 17.3 20 20 6.0 18.0 2.5

Table 2: 380 – 480 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)

None UL UL

4.0 5.0 2 10.8 16 15 2.5 9.5 1.5

5.5 7.5 3 13.3 16 15 2.5 14.0 2.5

7.5 10.0 3 18.5 25 25 4.0 18.0 2.5

Table 3: 500– 600 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)

None UL UL

4.0 – 2 7.1 10 10 2.5 6.5 1.5

5.5 – 2 14.4 25 20 2.5 9.0 2.5

7.5 – 3 14.4 25 20 2.5 12.0 2.5

11.0 – 3 23.6 40 35 2.5 17.0 2.5

IP55

Table 4: 200 – 240 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)

None UL UL

5.5 7.5 4 25.0 32 30 6.0 24.0 4.0

7.5 10.0 4 32.9 40 35 10.0 30.0 6.0

15.0 20.0 5 69.6 80 80 25.0 61.0 16.0

Technical Specification

4 SRC 311 - SmartRun™ Technical Specification

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)

None UL UL

22.0 30.0 6 92.3 125 125 35.0 90.0 25.0

37.0 50.0 6 150.2 200 175 70.0 150.0 35.0

Table 5: 380 – 480 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)None UL UL

11.0 15 4 26.5 32 30 6.0 24 6.0

15.0 20 4 32.9 40 40 6.0 30.0 6.0

18.5 25 4 46.6 63 60 16.0 39.0 10.0

22.0 30 4 54.1 63 60 16.0 46.0 10.0

30 40 5 69.6 80 80 35.0 61.0 16.0

37 50 5 76.9 100 100 35.0 70.0 25.0

45.0 60 6 92.3 125 125 50 .0 90.0 25.0

55.0 75 6 116.9 160 150 70.0 110.0 35.0

75.0 120 6 153.2 200 175 70.0 150.0 35.0

Table 6: 500 – 600 V (± 10%) 3–phase input, 3–phase output

kW HP Frame Size Nominal InputCurrent (A)

Fuse/MCB, type B) (A) Supply cable(mm2)

NominalOutputCurrent (A)

SUBCAB®

cable (mm2)None UL UL

15.0 - 4 35.0 63 40 6.0 22.0 6.0

22.0 - 4 53.8 80 60 10.0 34.0 10.0

30.0 - 4 67.5 100 70 16.0 43.0 16.0

37.0 - 5 81.3 125 100 25.0 54.0 25.0

45.0 - 5 97.5 125 125 35 .0 65.0 35.0

55.0 - 6 131.3 200 150 35.0 78.0 35.0

75.0 - 6 162.5 250 200 50.0 105.0 50.0

90.0 - 6 187.5 250 250 70.0 130.0 70.0

110.0 - 6 187.5 250 250 70.0 150.0 70.0

Cable length

The maximum cable length is 100 m (328 ft). Screened cable must be used.

The PWM output switching from any inverter using a long motor cable can cause anincrease in the voltage at the motor terminals, depending on the cable length andinductance. The rise time and peak voltage can affect the service life of the motor. Flygtrecommends using an output choke for motor cable lengths of 50 m or more to ensuregood motor service life.

For UL-compliant installation, use copper wire with a minimum insulation temperaturerating of 75°C (167°F). When using fuses, the type must be Class CC or Class J.

Technical Specification

SRC 311 - SmartRun™ Technical Specification 5

SMartin
Rectangle
SMartin
Line

DimensionsFrame size 2 – 3

A

E

BC

D

G

H

F

I

Frame size 2 3

A mm (in) 257.0 (10.12) 310.0 (12.20)

B mm (in) 220.0 (8.67) 276.5 (10.89)

C mm (in) 200.0 (7.87) 251.5 (9.90)

D mm (in) 28.5 (1.12) 33.4 (1.31)

E mm (in) 238.0 (9.37) 256.0 (10.08)

F mm (in) 188.0 (7.40) 210.5 (8.29)

G mm (in) 176.0 (6.93) 197.5 (7.78)

H mm (in) 4.2 (0.17) 4.2 (0.17)

I mm (in) 8.5 (0.33) 8.5 (0.33)

Frame size 4 – 6

A BC

DEGF

HI

Frame size 4 5 6

A mm (in) 450.0 (17.72) 540.0 (21.26) 865.0 (34.06)

B mm (in) 428.0 (16.85) 515.0 (20.28) 830.0 (32.68)

Technical Specification

6 SRC 311 - SmartRun™ Technical Specification

Frame size 4 5 6

C mm (in) 433.0 (17.05) 520.0 (20.47) 840.0 (33.07)

D mm (in) 8.0 (0.315) 8.0 (0.315) 10.0 (0.394)

E mm (in) 252.0 (9.92) 270.0 (10.63) 330.0 (12.99)

F mm (in) 171.0 (6.73) 235.0 (9.25) 330.0 (12.99)

G mm (in) 110.0 (4.33) 175.0 (6.89) 200.0 (7.87)

H mm (in) 4.25 (0.167) 4.25 (0.167) 5.50 (0.217)

I mm (in) 7.5 (0.295) 7.5 (0.295) 11.0 (0.295)

WeightFrame 2 3 4 5 6

Kg 4.8 7,3 11,5 22,5 50,0

Torque values for installationScrew Frame size Torque Nm (lbs-in)

Control terminal All 0.8 (7)

Power terminal 2 – 3 1 (8.85)

4 1.2 – 1.5 (10.6 – 13.2)

5 2.5 – 4.5 (22.5 – 39.8)

6 8 (70.8)

Mounting clearance

Y

X

X

Y

X Minimum 200 mm (7.87 in)Y Minimum 10 mm (0.349 in)

Typical drive heat losses are 3% of operating load conditions.

NOTICE:

The operating ambient temperature of the drive must be maintained.

Technical Specification

SRC 311 - SmartRun™ Technical Specification 7

Terminals

1 2 3 4 5 6 7 8 9 1011Control Terminal Unit 1

1 2 3 4 5 6

Power terminal Unit 1 and 2 Control Terminal Unit 2

3

1 2

4 5

6

7

891011

12 15

16 1920 21

22

23

1825

26

2728

1324

WS0

03610

1213 1 2 3 4 5 6 7 8 9 10111213

M M14

17

1. Incoming power2. RFI-toroid core, for sizes 2 and 33. Brown lead4. Black lead5. Grey lead6. Ground (earth)7. Pump 18. T1, (pump 1)9. T2, (pump 1)10. T31 (pump 1)11. T41 (pump 1)12. Black lead13. Control screen lead14. Level switch15. • EU: Grey

• US: Red16. Screen lead of the shared communication cable17. Signal leads of the shared communication cable18. Pump 219. T1 (pump 2)20. T2 (pump 2)21. T31 (pump 1)22. T41 (pump 1)23. Screen lead of the shared communication cable24. Screen lead of the level sensor cable25. Level sensor signal lead26. Level sensor lead –27. Level sensor lead +28. White

Figure 1: Two pump system

1 Isolate and terminate T3 and T4 in an end-sleeve.

Technical Specification

8 SRC 311 - SmartRun™ Technical Specification

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 1

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 1

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 3

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 3

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 2

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 2

+-

MM

M

WS0

07550

Figure 2: Three pump system

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 1

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 1

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 3

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 3

Ext block+24 V

Alarm resetHigh level in

GndT2 in

Lvl signal outGndLvl signal inActive pumpInhibit inInhibit out

+ 10 V

12

34

56

78

910

1112

13

Control Term

inal Unit 2

Relay 1 NORelay 1 Com

Relay 1 NCRelay 2 comRelay 2 NO

1415

1617

18

Relay Term

inal Unit 2

WS0

07551

Figure 3: Three pump I/O alternation system

Table 7: Power

Terminal Type Function

1 L1/L Incoming power to the drive

Technical Specification

SRC 311 - SmartRun™ Technical Specification 9

Terminal Type Function

2 L2/N Incoming power to the drive

3 L3 Incoming power to the drive

4 U Outgoing power for the pump

5 V Outgoing power for the pump

6 W Outgoing power for the pump

Table 8: Control I/O

Terminal Type Function

1 +24V utput (maximum 100 mA2) +24V external supply for backup power

2 Digital input 8-30V DC Pump block input

3 Digital input 8-30V DC External alarm reset

4 Digital input 8-30V DC Level switch

5 + 10V output (maximum 20 mA Out) Unused

6 Analog input 0-20 mA Pump sensor (T2)

7 Ground (earth)

8 Analog output 4-20 mA Level sensor output

9 Ground (earth)

10 Analog input 4-20 mA Level sensor input

11 Digital output 0-10 V Pump running output

12 Hardware inhibit input

13 Hardware inhibit output (0V)

Relay

14 Relay 1 common, 250V AC, 30V DC, 5A User configurable relay #1 (A-sum alarm)

15 Relay 1 NO, 250V AC, 30V DC, 5A User configurable relay #1 (A-sum alarm)

16 Relay 1 NC, 250V AC, 30V DC, 5A User configurable relay #1 (A-sum alarm)

17 Relay 2 common, 250V AC, 30V DC, 5A User configurable relay #2 (Pump runningoutput)

18 Relay 2 NO, 250V AC, 30V DC, 5A User configurable relay #2 (Pump runningoutput)

Table 9: Extension relay card

Terminal Type Function

1 Relay 3 common, 250V AC, 30V DC, 5A User configurable relay #3

2 Relay 3 contact, 250V AC, 30V DC, 5A User configurable relay #3

3 Relay 4 common, 250V AC, 30V DC, 5A User configurable relay #4

4 Relay 4 contact, 250V AC, 30V DC, 5A User configurable relay #4

5 Relay 5 common, 250V AC, 30V DC, 5A Relay #5 (Pump running output)

6 Relay 5 contact, 250V AC, 30V DC, 5A Pump running output

Table 10: External I/O controller card

Terminal Type Function

1 Extended digital input 1 External I/O Auto mode

2 Extended digital input 2 External Hand mode

2 The limitation in current allows FLS to be connected

Technical Specification

10 SRC 311 - SmartRun™ Technical Specification

Terminal Type Function

3 Extended digital input 3 Activate external I/O control3

4 NC Normally closed

5 Extended relay common

6 Extended relay normally open contact

CommunicationThe drive is equipped with an RJ45 connector. The connection is used to set up a networkvia a wired connection. The connector contains two independent RS485 connections andboth can be used simultaneously.

NOTICE:

This RJ45 connector is not an Ethernet connection. Do not connect directly to an Ethernetport. The voltage destroys the Ethernet device.

1 8765432WS0

03606

1. Not used2. Not used3. 0 V4. RS485- Optibus5. RS485+ Optibus6. +24 V, power supply7. RS485- ModbusRTUx8. RS485+ ModbusRTU

All the drives parameters are read and written over the fieldbus communication. Processparameters that are marked as configurable are also accessed and read, but processparameters that are marked with a fixed value cannot be read or set over the fieldbuscommunication.

Any external system that wants to read process data and alarms from the drive must beconfigured with the correct parameter addresses for the drive.

Contact sales support for more information regarding communication.

OptionsExternal Keypads and Optistick

• OLED External Keypad• Optistick

Cables splitters, PC Kit

• RS485 Data cable Splitter• RS485 Data cable w- RJ45• USB to RS485 Connection kit

3 Extended digital input 3 needs to be activate for External digital input 1 and 2 to work.

Technical Specification

SRC 311 - SmartRun™ Technical Specification 11

Xylem |’zīləm|

1) The tissue in plants that brings water upward from the roots2) A leading global water technology company

We're 12,000 people unified in a common purpose: creating innovativesolutions to meet our world's water needs. Developing new technologies thatwill improve the way water is used, conserved, and re-used in the future is centralto our work. We move, treat, analyze, and return water to the environment, andwe help people use water efficiently, in their homes, buildings, factories andfarms. In more than 150 countries, we have strong, long-standing relationshipswith customers who know us for our powerful combination of leading productbrands and applications expertise, backed by a legacy of innovation.

For more information on how Xylem can help you, go to xyleminc.com

Xylem Water SolutionsManufacturing AB361 80 EmmabodaSwedenTel: +46-471-24 70 00Fax: +46-471-24 47 01http://tpi.xyleminc.com

Visit our Web site for the latest version of this documentand more information

The original instruction is in English. All non-Englishinstructions are translations of the original instruction.

© 2012 Xylem Inc

882877_3.0_en-US_2013-10_TS.SRC311

1

2

3

4

5

6

7

8

9

10

48

Pilot Lights—UL Types 4, 4X, 13/NEMA 4, 4X, 13 For use in hazardous locations, see page 53 . Legend plate not included .

Description Voltage Style With Red Fresnel Color Cap

With Green Fresnel Color Cap

With Other Color Cap (2)

Without Color Cap

9001SKP1

StandardPilot Light(Fresnel color cap shown)

110–120 V, 50–60 Hz Transformer SKP1R31 SKP1G31 SKP1b SKP1220–240 V, 50–60 Hz Transformer SKP7R31 SKP7G31 SKP7b SKP724–28 Vac/Vdc Full Voltage SKP35R31 SKP35G31 SKP35b SKP35For other voltages (1)

Transformer, Flashing or LED (3)

SKPaR31 SKPaG31 SKPab SKPa

Full Voltage, Neon or Resistor (4)

SKPaR31 SKPaG31 SKPab SKPa

9001SKT1

Push-To-TestPilot Light(Fresnel color cap shown)

110–120 V, 50–60 Hz Transformer SKT1R31 SKT1G31 SKT1b SKT1220–240 V, 50–60 Hz Transformer SKT7R31 SKT7G31 SKT7b SKT724–28 Vac/Vdc Full Voltage SKT35R31 SKT35G31 SKT35b SKT35For other voltages(1)

92% SKTaR31 SKTaG31 SKTab SKTaFull Voltage, Neon or Resistor (4)

SKTaR31 SKTaG31 SKTab SKTa

9001SKTR38

Remote TestPilot Light(Fresnel color cap shown)

120 Vac Only Resistor SKTR38R31 SKTR38G31 SKTR38b SKTR3824–28 Vac Only Full Voltage SKTR35R31 SKTR35G31 SKTR35b SKTR35For other voltages(1)

Full Voltage or Resistor (5)

SKTRaR31 SKTRaG31 SKTRab SKTRa

(1) Replace a with the voltage assembly code as chosen from the tables on page 54. Example: SKTaR31 with 208 Vac red LED voltage = SKT37LRR31.

(2) Replace b with the color code as chosen from the color code table below. Example: SKP1b with a blue fresnel cap = SKP1L31.

(3) The cap must be the same color as the LED light module chosen, e.g., for a green LED, use a green color cap.(4) On neon light modules, use clear color caps only.(5) Use only full voltage or resistor voltage assembly codes on remote test pilot lights. Do not choose LED, neon or transformer codes.

For AC use only.

Color Caps Color b Plastic Fresnel b Plastic Domed

AmberBlueClearGreenRedWhiteYellow

A31L31C31G31R31W31Y31

A9L9C9G9R9W9Y9

Harmony™ 9001K/SK/KX 30 mm push buttons9001SK – Pilot lights

References (continued)

Product range:page 36

Specificationspage 38

Dimensions:page 60

Mounting:page 61

Note: When ordering, add prefix “9001” to the reference.

To select and order Contact Blocks, Light Modules, Knobs, and Accessories, see pages 50 to 59.

R

M

M O.L.

L2

321

L1

STOPSTART

L2

C

Test

L1

M

STOP

LSI

M3

(TEST) C

(TEST) C L2

L2

L1(SIG)

CR

M2

M1

L2(TEST) C

START

TEST BUTTONL1 L2

L1(SIG)

L1(SIG)

Push-to-test Pilot Light

Remote Test Pilot Light

Typical Wiring Diagrams

R

M

M O.L.

L2

321

L1

STOPSTART

L2

C

Test

L1

M

STOP

LSI

M3

(TEST) C

(TEST) C L2

L2

L1(SIG)

CR

M2

M1

L2(TEST) C

START

TEST BUTTONL1 L2

L1(SIG)

L1(SIG)

Push-To-Test Pilot Light

Remote Test Pilot Light

SMartin
Rectangle
SMartin
Highlight
SMartin
Text Box
9001SKT38LGG31 9001SKT38LRR31 9001SKT38LWW31
SMartin
Line

1

2

3

4

5

6

7

8

9

10

41

Non-Illuminated Momentary Push Button Operators—UL Types 4, 4X, 13/NEMA 4, 4X, 13 For use in hazardous locations, see page 53 . Contact blocks and legend plate not included unless otherwise noted .

Description Color Operator with 1 N .O . and1 N .C . Contact (KA1)

Operator with 1 N .O . Contact (KA2)

Operator with 1 N .C . Contact(KA3)

Operator Only No Contacts (5)

9001SKR1BFull Guard

Black SKR1BH13 SKR1BH5 SKR1BH6 SKR1BRed SKR1RH13 SKR1RH5 SKR1RH6 SKR1RGreen SKR1GH13 SKR1GH5 SKR1GH6 SKR1GUniversal (1) SKR1UH13 SKR1UH5 SKR1UH6 SKR1UOther (2) SKR1bH13 SKR1bH5 SKR1bH6 SKR1b

9001SKR3BNo Guard

Black SKR3BH13 SKR3BH5 SKR3BH6 SKR3BRed SKR3RH13 SKR3RH5 SKR3RH6 SKR3RGreen SKR3GH13 SKR3GH5 SKR3GH6 SKR3GUniversal (1) SKR3UH13 SKR3UH5 SKR3UH6 SKR3UOther (2) SKR3bH13 SKR3bH5 SKR3bH6 SKR3b

9001SKR2BExtended Guard

Black SKR2BH13 SKR2BH5 SKR2BH6 SKR2BRed SKR2RH13 SKR2RH5 SKR2RH6 SKR2RGreen SKR2GH13 SKR2GH5 SKR2GH6 SKR2GUniversal (1) SKR2UH13 SKR2UH5 SKR2UH6 SKR2UOther (2) SKR2b SKR2bH5 SKR2bH6 SKR2b

9001SKR4B 1-3/8 in (35 mm)

Mushroom Button

Snap-In Mushroom ButtonBlack SKR4BH13 SKR4BH5 SKR4BH6 SKR4BRed SKR4RH13 SKR4RH5 SKR4RH6 SKR4RRed (3) SKR4R05H13 SKR4R05H5 SKR4R05H6 SKR4R05Green SKR4GH13 SKR4GH5 SKR4GH6 SKR4GOther (4) SKR4dH13 SKR4dH5 SKR4dH6 SKR4dScrew-On Mushroom Button with Set Screw SecurityBlack SKR24BH13 SKR24BH5 SKR24BH6 SKR24BRed SKR24RH13 SKR24RH5 SKR24RH6 SKR24RGreen SKR24GH13 SKR24GH5 SKR24GH6 SKR24GOther (4) SKR24dH13 SKR24dH5 SKR24dH6 SKR24d

9001SKR5 2-1/4 in (57 mm)

Mushroom Button

Snap-In Mushroom ButtonBlack SKR5BH13 SKR5BH5 SKR5BH6 SKR5BRed SKR5RH13 SKR5RH5 SKR5RH6 SKR5RRed (3) SKR5R05H13 SKR5R05H5 SKR5R05H6 SKR5R05Green SKR5GH13 SKR5GH5 SKR5GH6 SKR5GOther (4) SKR5dH13 SKR5dH5 SKR5dH6 SKR5dScrew-On Mushroom Button with Set Screw SecurityBlack SKR25BH13 SKR25BH5 SKR25BH6 SKR25BRed SKR25RH13 SKR25RH5 SKR25RH6 SKR25RGreen SKR25GH13 SKR25GH5 SKR25GH6 SKR25GOther (4) SKR25dH13 SKR25dH5 SKR25dH6 SKR25d

Color CodesColor b SKR1, 2, 3 Place Color Code in Reference d SKR4, 5, 24, 25 Place Color Code in ReferenceBlue L LYellow Y YWhite W —Orange S SGray E —(1) The universal push button operators contain one each of the following color inserts: black, red, green, yellow, orange, blue and white.(2) Replace b with the color code as chosen from the color code table above.(3) Knob has the words “Emergency Stop” in raised letters highlighted in white for readability.(4) Replace d with the color code as chosen from the color code table above(5) These operators can be ordered complete with contact blocks. For maximum block usage, see page 51. Add the “H” number chosen from

page 51 to the end of the operator reference number and add the cost of the “H” number to the operator cost.

To select and order Contact Blocks, Light Modules, Knobs, and Accessories, see pages 50 to 59.

Harmony™ 9001K/SK/KX 30 mm push buttons9001SK – Push buttons and mushroom operators

References (continued)

Product range:page 36

Specificationspage 38

Dimensions:page 60

Mounting:page 61

Note: When ordering, add prefix “9001” to the reference.

SMartin
Rectangle
SMartin
Rectangle
SMartin
Text Box
9001SKR1BH5
SMartin
Line

Website:www.ingramproducts.com e-mail: [email protected] ph (904)733-2230 fax

UL Recognized. Can be used in UL NEMA Type 3, 3R, 4, 4X, 12 and 13 enclosures (E121431)Lens molded from GE Lexan that is shatter resistant and UV stabilizedLow profile, top mounted gives 360 degree visibilityHose down proofAvailable in 5 colors: Red, Blue, Amber and Clear

Alarm Light

The Ingram LX25 is a UL 3, 3R, 4, 4X, 12, 13 low cost alarm light suitable for heavy duty applications inside and outdoors. The lens is molded from tough shatter resistant GE Lexan. This tamper resistant light is particularly useful in areas with high ambient noise levels where an audible signal may not be heard.

Ingram also offers daylight visible 120VAC sixty LED bulbs that fit the LX25 or any standard E26 screw-in socket.Red LED Bulb: Ingram p/n LEDBR120AAmber LED Bulb: Ingram p/n LEDBA120AFor best results, use red lens with red bulb, amber lens with amber bulb, or clear lens with either.

Features Technical SpecificationsVoltage: 12V, 24V, 120VACCurrent Draw: 120VAC 0.21 Amps max. (Filament)

120VAC 0.017 Amps max. (LED)12V 2.10 Amps max. (Filament)24V 1.1 Amps max. (Filament)

The LX25 comes with a 25 watt, 120V incandescent bulb.25 watt incandescent bulbs at 12 and 24V are available for special order as well. They work equally well with AC or DC voltages.

8725 Youngerman Court, Ste 206, Jacksonville, FL 32244

INGRAMP R O D U C T S, I N C.

Part No.: LX25

Rev. 4Cut-Away View Hole Pattern For Mounting

3 5/8"4 3/8"

3 1/4"

40 W ATT

1 1/4"

or 1 1/2 Knock Out

8-32 TAP(2 REQ'D)

2"2"

1 3/8" 1 3/8"

2"

2"

Ø 1/4"

Ø 2"

Enclosure Wall

Shatter ResistantG.E. Lexan Globe

Mounting Bracket

2" Knock outor 2" hole

#8 - 32 MountingScrew

Gasket

LX25 Assembly

25W A TT

This highly reliable encapsulated solid state flasher is designed for use with incandescent or LED resistive loads. It can be used to directly flash 15 to 150-watt incandescent light bulb.

E121431

Operating voltage is 120 volts AC

Full wave AC output

Maximum tungsten load is 1.25 amps

Minimum pilot load is 10 VA

Flash rate: 75 flashes per minute ±5%, factory set

Operating temperature is -20°C to 40°C

Insulated 20 gauge wire leads are 6" long

Website:www.ingramproducts.com e-mail: [email protected] ph (904)778-2444 fax8725 Youngerman Court, Ste 206, Jacksonville, FL 32244

Solid State Flasher

Technical Specifications

Part No.: SSF150W

INGRAMP R O D U C T S, I N C.

On/Off Recycling Ratio

OnTime

OffTime

OffTime

OnTime

OffTime

OnTime

OnTime

Reset

Off

Energized

De-energized

Input Power

Output

Applied

0.4 seconds off time followed by 0.4 second on time

OffTime

SSF150WFLASHER

H

N

3KΩ RESISTOR20 WATT

R BK

For flasher to operate properly with low current drawLED bulbs, a shunt resistor should be used

Connection

FLASHER

MAX LOADTUNGSTEN 1.25 amps

PILOT DUTY 10 VA

120 VAC INPUT

1/2"

Ø 1/4"

1 1/2"1.000"

1.000"

Ø 15/16"

0.46(11.7)

1.125 X 24

1.0±0.1(25.4±2.5)

1.35(34.3)

REAR VIEW SIDE VIEW

0.43(10.9)

0.89(22.6)

INCHES(mm)

(±0.76)±0.03TOLERANCES ARE:

DIMENSIONS ARE IN:

(27.2 D)1.07 D

(32.8 D)1.29 D

FRONT VIEWRING

FOR REFERENCE ONLY

(8.0)0.315

THREADS

(35.8 D)1.41 D

MW-09-201-Q

The MW-09-201-Q is a warble tone alarm with a typical loudness level of 95 dB(A). It can be operated over a voltage range of 30-120VAC and warbles at a rate of 15 times per second. The terminals are standard 0.25" quick-connect blades. The case is designed for panel mounting in a 1.125" hole with a knurled ring nut.

SPECIFICATIONS

DIMENSIONS

Operating Mode: Medium Loud Warble Tone Operating Voltage: 30-120 Vac Nominal Operating Voltage: 110 Vac Operating Frequency: High Frequency Peak: 2900±250 Hz. Low Frequency Peak: 2200±250 Hz. 15±25% Cycles per second Typical Operating Current: 5 mA at 30 Vac 20 mA at 120 Vac Typical Sound Pressure: 85±5 dB(A), at 30 Vac, at 24 inches (61 cm), at 25°C 95±5 dB(A), at 120 Vac, at 24 inches (61 cm), at 25°C. Termination: Quick Connect Blades, 0.25 (6.3) Width, 0.032 (0.8) Thickness Termination Strength: Pull test with a maximum of 22 pounds (10 kg) load Operating Temperature: -20°C to +65°C. Storage Temperature: -40°C to +85°C. Surge Voltage: 20% over maximum rated voltage for less than 5 minutes. Part Recognized By: Underwriters Laboratory Construction Materials: Case- Plastic “NORYL® N-190”, Flame Retardant UL 94-VO, Black Internal Circuit- Audio-oscillator and piezoelectric driver Potting- 2 parts epoxy resin or silicone, black Diaphragm- Stainless Steel 304 Gasket (Sold Separately)– 0.062” Thick, 60 Durometer Neoprene Environmental Durability: Salt Spray- Withstand exposure to salt spray per ASTM B117 for a period of 300 hours with no decrease in sound output Humidity- 95% relative humidity at +40°C continuously for 100 hours. Vibration- Withstands vibration between 0 and 55 Hz. on all axes. Life Expectancy: 10 years under normal operating conditions. Warranty: For a period of two years from the date of manufacture under normal operating conditions.

MOUNTING HOLE

PANEL MOUNTING

0.25 (6.3) THICKFITS PANELS UP-TO

1.125 D(28.6 D)

0.070 D(1.78 D)

0.160

(6.4)0.250

(4)

(7.9)

0.312(7.9)

0.312

"Q" TERMINALS

0.032(0.81)

P.O. Box 12400 • 897 Higgs Avenue • Columbus, OH 43212-0400 Tel: 614/294-4000 • Fax: 614/291-0823 email: [email protected] • www.floydbell.com

All specifications subject to change without notice. Copyright © 2004 Floyd Bell Inc.

Made in USA

TYP

ICAL

OU

TPU

T S

OU

ND

INPUT VOLTAGE Vac40

80

90

100

8060

INP

UT

CU

RR

ENT

(mA)

5

15

10

100PR

ESS

UR

E dB

(A),

at 2

feet

vs. INPUT VOLTAGE PERFORMANCE.

20

120

70

• Durable Stainless Steel 304 Diaphragm

• Epoxy Encapsulated Electronics

• UL Approved

• NEMA 4X Certified with Optional Gasket

• Reliable Piezoelectric Technology

An ISO 9001:2000 Registered Company Revision: 7.04

Frequency 2900 500 HzMedium Loud Series - 95db(A) at 2 feet

+

Medium Warble Series

CaseStyle

Volume Control Option/UL Model# Voltage

Sound Levelat

min maxV V

Currentat

min maxV V

T**

05 -UL MW-05-616-P 5-16Vdc 80 95 8mA 18mA P

05 -UL MW-05-530-P 5-30Vdc 80 95 8mA 18mA P

05 -UL MW-05-550-P 15-36Vac/dc 75 95 3mA 8mA P

09 X-UL MW-09-616-Q 5-16Vdc 80 95 8mA 18mA Q

09 X-UL MW-09-616-S 5-16Vdc 80 95 8mA 18mA S

09 X-UL MW-09-616-W 5-16Vdc 80 95 8mA 18mA W

09 X-UL MW-09-530-Q 5-30Vdc 80 95 8mA 18mA Q

09 X-UL MW-09-530-S 5-30Vdc 80 95 8mA 18mA S

09 X-UL MW-09-530-W 5-30Vdc 80 95 8mA 18mA W

09 X-UL MW-09-531-Q 5-24Vac/dc 75 95 4mA 24mA Q

09 X-UL MW-09-531-S 5-24Vac/dc 75 95 4mA 24mA S

09 X-UL MW-09-531-W 5-24Vac/dc 75 95 4mA 24mA W

09 X-UL MW-09-948-Q 9-48Vdc 90 95 4mA 24mA Q

09 X-UL MW-09-948-S 9-48Vdc 90 95 4mA 24mA S

09 X-UL MW-09-948-W 9-48Vdc 90 95 4mA 24mA W

09 X-UL MW-09-550-Q 15-36Vac/dc 75 95 3mA 8mA Q

09 X-UL MW-09-550-S 15-36Vac/dc 75 95 3mA 8mA S

09 X-UL MW-09-550-W 15-36Vac/dc 75 95 3mA 8mA W

09 X-UL MW-09-201-Q 40-120Vac 75 95 3mA 8mA Q

09 X-UL MW-09-201-S 40-120Vac 75 95 3mA 8mA S

09 X-UL MW-09-201-W 40-120Vac 75 95 3mA 8mA W

09 X-UL MW-09-301-Q 140-220Vac 75 95 3mA 8mA Q

09 X-UL MW-09-301-S 140-220Vac 75 95 3mA 8mA S

09 X-UL MW-09-301-W 140-220Vac 75 95 3mA 8mA W

X: Denotes model is available with optional volume control.This simple manual shutter provides variable attenuation up to 20dBa typical.

UL: Denotes model is a UL Recognized Component

**Terminations:

W- Leads: 2 wires 24 AWG StrandedCopper, vinyl insultated. 2.75"long, 1/4" end stripped, color-coded.

P-PC Pins: 2 PC Pins. 180 apart onA 0.500" R from center, 0.032"diameter.

o

S-Screw terminals: 6-32 x 1/4" longstainless steel screw for wirewith lug attachment.

Q-0.250" quick connect terminals:0.250" width, 0.033" thickness,brass electro-tin plated for push-on (quick connect) attachmentsor direct solder.

09/09/02

SMartin
Rectangle
SMartin
Line

8

Model 34 Electronic LCD Hour Meter

Description

Features

Specifi cations

••••••

Display: LCD with large 0.28” [7mm] high fi gures black on light background

Run indicator: Blinking decimal point

Reset: Remote, manual and non-reset (remote reset not available on surface mount housing)

Hour Meter Resolution: 0.01 or 0.1 Hour, displayed; 1 second, internal

Accuracy: ± 0.1% @ room temperature ± 0.2% over the specifi ed temperature range

Records & Displays: 9999999.9 - hours & 1/10’s or 999999.99 - hours & 1/100’s

Power: Self powered - battery life 15+ years

Terminations: Standard 0.250” [6.4mm] spades 1 meter wire (inductive)

Output: Format: Open-Drain MOSFET with Source connected to Common (see note 3)

Maximum Withstanding voltage: 30VDC, reference to Common Maximum Load current: 0.1Amp

Environmental: Temperature: (Storage and Operating) -40 to +185˚F [-40 to +85˚C] Humidity: 95% RH per SAE J1378 Vibration: 20g @ 10 to 80 Hz per SAE J1378 Shock: 44 to 55g’s per SAE J1378 Dielectric: 1000VAC 50/60 Hz for 1 minute Compliance: Compliant to the European WEEE and RoHS Directives

Sealing: Totally sealed

EMC Compliance: EN61326:1997 with A1:1998 and A2:2001 for industrial environments

Protection Against: Alternator load dump: 150V EMI (Electromag- netic Interface): +400V @ 500Hz inductive switching and reverse polarity

Enclosure: Totally sealed from moisture and dirt, NEMA 4/4X, 12, & IP66 compliant from the front when properly mounted using the optional gasket. (Not applicable to Snap-In Model)

Approvals: UL and cUL Recognized (fi le # ELIY2.E36690), CE, SAE, NEMA 4/4X compliant

Weight: 1oz [28g]

••••••••

Description

The Redington Model 34 LCD Hour Meter provides a large display, with 0.28” [7mm] high characters, in the industry size housings. The Hour Meters are available in 5 different housings, including a surface mount inductive input model. All models are totally sealed and are capable of submersion in 6’ [2 meters] of water. A wide operating voltage, 10-300VDC and 20-300VAC, and inductive input make the Model 34 versatile for all indoor and outdoor applications. All models are NEMA 4/4X, 12, & IP66 rated when used with the optional gasket and have a polarized lens which assures high visability in an outdoor environment.

Options

• Totally sealed from moisture and dirtAC or DC voltage input in the same unitTachometer/Hour Meter versionsCompact depthFits in existing panel openingsAlways on display15+ Year Battery Life

Maintenance Meters are offered with a maximum of 3 “Redi-Alerts” to alert users when service is due. Models are available with front panel fi eld or fac-tory programmable alerts. Not only does the display fl ash to get attention, but it displays a choice of 7 different .08”[2mm] maintenance icons. Models are available as a Preset Timer with a MOSFET output for the actuation of external alarms or indicator lamps. Users can program or specify the service interval and fl ash duration for each Redi-Alert. Flash duration is the amount of time in hours that the specifi c icon fl ashes before and after the service interval. If a front panel manual reset of the Redi-Alert is required the front panel models with switches must be specifi ed.

A choice of 6 housingsA choice of reset modesFront panel programmablePreset Timer with outputCan be programmed with starting timeProgrammable output thresholds Preset Hour Meter/time up or down Up to 3 Redi-Alerts/7 icons

Inputs: 10-300VDC and 20-300VAC-50/60Hz <2mA VIH 20VAC or 10VDC minimum VIL 3VAC or 3VDC maximum

www.trumeter.com

9

Model 34 Electronic LCD Hour Meter

Dimensions

FunctionsPreset Hour Meter: The preset function is centered on the output signal. When the time reaches the preset value, the output signal is turned “on”. The Preset function is time “up”.Upon reaching the preset value the preset can be automatically reset, or it can await an external reset.

Inductive Models: The surface mount Inductive unit is designed with an inductive interface. The unit will sense the firing of a spark plug on most small gasoline powered internal combustion engines. The wire lead from the unit is wrapped around the spark plug wire. Inductive models are available with and without tachometers. Most small engines provide 1 spark per RPM, in which case the maximum RPM is 30,000. Some small engines provide 2 sparks per RPM, the maximum RPM is then 15,000. Models are available that can be field (front panel switches) or factory programmed for 1.0, 2.0, or 0.5 sparks/pulses per RPM.

Front Panel Switch Functions: Front panel switches can be used for reset, display selection and programming. The two front Panel switches are used as follows:

SEL: During programming this switch is used to select options. The SEL switch is used during programming to move horizontally in the programming flow chart.

RST: This is the reset switch during normal operation. During programming the RST switch is used to enter an option. The RST switch is used during programming to move vertically in the programming flow chart.

Available Icons

SERVICE

CHANGE

OIL

OIL FILTER

AIR FILTER

LAMP

MUFFLER

1.60 [40.6]

1.41 [35.8] .05 [1.3].05 [1.3]

.75 [19.0]

.88 [22.3].25 [6.3]

1.43 [36.3]

.34 [8.6]

.89 [22.6].28 [7.0]

1.10 [27.9] .50 [12.7]

1.75 [44.4]

1.41 [35.8].05 [1.3].05 [1.3]

.75 [19.0]

.88 [22.3].25 [6.3]

1.43 [36.3]

.34 [8.6]

.89 [22.6]

.28 [7.0]1.10 [27.9] .50 [12.7]

1.29 [32.7].05 [1.3]

.03 [0.7]

.75 [19.0]

.88 [22.3].25 [6.3]

1.43 [36.3]

.34 [8.6]

.79 [20.0].28 [7.0]

.50 [12.7]

2.21 [56.1]

1.98 [50.3]

.05 [1.3]

Rectangular Flush Mount 2-Hole Mount

Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm]Maximum Panel Thickness: 0.375” [9.5mm]

Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm]

Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm]Maximum Panel Thickness: 0.375” [9.5mm]

Flush Round/SAE Mount

www.trumeter.com

10

Model 34 Electronic LCD Hour Meter

Applications

Medical Devices Control Panels Production EquipmentGenerators Garden Tractor Marine Equipment

Notes1. When interfacing the Model 34 with a Solid State Relay or AC Sensor, the leakage current needs to be considered. Contact the factory or see the application note at www.redingtoncounters.com

2. Exceeding the Absolute Voltage Range and the Absolute Maximum Limits may result in damage to the unit.

3. The open-drain MOSFET acts like an open-collector NPN trasistor. Care should be taken since there is no current limiting protection in the unit.

1.29 [32.7]

.05 [1.3]

.03 [0.7]

.75 [19.0]

.88 [22.3].25 [6.3]

1.43 [36.3]

.34 [8.6]

.28 [7.0]

.50 [12.7]

2.87 [72.9]1.98 [50.3]

.79 [20.0]

.05 [1.3]

1.29 [32.7]

.05 [1.3]

.05 [1.3]

.75 [19.0]

.88 [22.3].25 [6.3]

1.43 [36.3]

.34 [8.6]

.79 [20.0].28 [7.0]

.50 [12.7]

1.10 [27.9]

1.60 [40.6]

2.12 [54.0]

1.41 [35.8]

.05 [1.3]

.50 [12.7]

.89 [22.6].28 [7.0]

1.10 [27.9]

1.75 [44.4]

.55 [14.0]

39.37 [1000.00]

3-Hole Mount Snap-In Mount

Surface Mount

Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm]

Panel Cutout: 1.46” [37mm] x 0.95” [24.1mm]Minimum Panel Thickness: 0.04” [1.0mm]

Maximum Panel Thickness: 0.125” [3.18mm]

www.trumeter.com

Part Number Description Gasket

3410-0000 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS NON-RESET 5003-010

3410-0010 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS REMOTE-RESET 5003-010

3410-0020 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS PROGRAMMING 5003-010

3410-1000AC/DC HOUR METER THREE HOLE CASE 1/4" SPADE TERMINALS NON-

RESET5003-017

3410-1010AC/DC HOUR METER THREE HOLE CASE 1/4" SPADE TERMINALS

REMOTE-RESET5003-017

3410-2000AC/DC HOUR METER FLUSH RECT CASE 1/4" SPADE TERMINALS NON-

RESET5003-009

3410-2010AC/DC HOUR METER FLUSH RECT CASE 1/4" SPADE TERMINALS

REMOTE-RESET5003-009

3410-3000AC/DC HOUR METER ROUND SAE CASE 1/4" SPADE TERMINALS NON-

RESET5003-009

3410-3010AC/DC HOUR METER ROUND SAE CASE 1/4" SPADE TERMINALS

REMOTE-RESET **SPECIAL ORDER** MOQ = 50 PCS5003-009

3410-5000AC/DC HOUR METER SNAP-IN CASE 1/4" SPADE TERMINALS NON-

RESET

3410-5010AC/DC HOUR METER SNAP-IN CASE 1/4" SPADE TERMINALS REMOTE-

RESET

NOTE PART NUMBERS MUST END IN -XX20 TO BE PROGRAMMABLE

5003-010 NEMA 4X GASKET TWO HOLE MOUNT

5003-017 NEMA 4X GASKET THREE HOLE MOUNT

5003-009 NEMA 4X GASKET SAE ROUND MOUNT

www.trumeter.com

5003-009 NEMA 4X GASKET FLUSH RECT MOUNT

SMartin
Rectangle
SMartin
Highlight
SMartin
Line

Zelio® Plug-in Relays RXM Miniature RelaysProduct Description

4© 2005–2008 Schneider Electric All Rights Reserved 01/2008

Product Description

The RXM miniature relay range consists of:

1. 12 A relays with DPDT contacts, 10 A relays with 3PDT contacts, 6 A relays with 4PDT contacts, and 3 A “low level” relays with 4PDT contacts. All of these relays have the same dimensions.

2. Sockets with mixed or separate contact terminals.

3. Protection modules (diode, RC circuit or varistor). All these modules are common to all sockets.

4. A metal hold-down clip for all sockets.

5. A plastic hold-down clip for all sockets.

6. A 2-pole bus jumper that can be used on sockets with separate contact terminals to simplify wiring when creating a jumper between the coil terminals.

7. Clip-in markers for all the sockets except RXZ E2M114.

Relay Description

1. Spring return push button for testing the contacts (green: DC, red: AC).

2. Mechanical “relay status” indicator.

3. Optional removable lock-down door and push button, enabling forced maintaining of the contacts for test or maintenance purposes. During operation, this lock-down door must always be in the closed position.

4. Bipolar LED (depending on version) indicating the relay status.

5. Removable marker for relay identification.

6. Four notches for DIN rail mounting adapter or panel mounting adapter.

7. Eight, eleven, or fourteen pins.

8. Area by which the product can be easily gripped.

9. Mounting adapter enabling direct mounting of the relay on a panel.

10. Mounting adapter enabling direct mounting of the relay on a DIN rail.

Socket Description

Sockets with Mixed Contact Terminals

1. Connection by screw clamp terminals or box lug connector.

2. Fourteen female contacts for the relay pins.

3. Location for protection modules.

4. Locking components for plastic and metal hold-down clips.

5. Locating slot for mounting on DIN rail.

6. Two or four mounting holes for panel mounting.

NOTE: The inputs are mixed with the relay coil terminals, with the outputs being located on the opposite side of the socket.

7

6

2

1

5

3

4or

1

2

7

3

4

56

8

9 910

1

2

3

4

5

Outputs

Inputs

Coil Terminals

6

RXM Miniature Relays Zelio® Plug-in RelaysSpecifications and Characteristics

501/2008 © 2005–2008 Schneider Electric All Rights Reserved

Sockets with Separate Contact Terminals

1. Box lug connector.

2. Eight, eleven, or fourteen female contacts for the relay pins.

3. Location for protection modules.

4. Locking components for plastic and metal hold-down clips.

5. Locating slot for mounting on DIN rail.

6. Two mounting holes for panel mounting.

7. Location for bus jumpers (see mounting on sockets on page 11).

NOTE: The inputs and outputs are separated from the relay coil terminals.

1

6

2

3

4

5 7

Outputs

Inputs

Coil Terminals

General characteristics

Conforming to standards IEC/EN 61810-1 (iss. 2), UL 508, CSA C22-2 n° 14

Product certifications cULus File E164862 CCN NLDX, NLDX7; cURus File E164862 CCN NLDX2, NLDX8; CSA pending; CE; RoHS compliant

Ambient air temperature around the device

Storage -40–185 °F (-40–85 °C)

Operation -40–131 °F (-40–55 °C)

Vibration resistance Conforming to IEC/EN 60068-2-6 > 6 gn (10–50 Hz)

Degree of protection Conforming to IEC/EN 60529 IP 40

Shock resistanceconforming to IEC/EN 60068-2-27

Opening 10 gn

Closing 5 gn

Protection category (see page 38) RT I

Mounting position Any

Insulation characteristics

Rated insulation voltage (Ui) 250 V (IEC), 300 V (UL, CSA)

Rated impulse withstand voltage (Uimp) 3.6 kV (1.2/50 µs)

Dielectric strength(rms voltage)

Between coil and contact 2,500 Vac

Between poles 2,500 Vac

Between contacts 1,500 Vac

Contact characteristics

Relay type RXM2ABppp RXM3ABppp RXM4ABppp RXM4GBppp

Number and type of contacts (see page 12) DPDT 3PDT 4PDT 4PDT

Contact materials AgNi AgAu–Bifurcated

Conventional thermal current (Ith)

For ambient temperature y 131 °F (55 °C) 12 A 10 A 6 A 3 A

Rated operational current

Conforming to IEC in utilization category AC-1

N.O. 12 A 10 A 6 A 2 A

N.C. 6 A 5 A 3 A 1 A

Conforming to UL Resistive @277 Vac, hp @120 Vac 12 A, 1/2 hp 10 A, 1/3 hp 8 A, 1/3 hp 3 A, 1/16 hp

Maximum operating rateIn operating cycles/hour

No load 18,000

Under load 1,200

Switching voltage Maximum 250 Vac/Vdc

Switching capacityMinimum 10 mA on 17 V 2 mA on 5 V

Maximum 3,000 VA 2,500 VA 1,500 VA 750 VA

Utilization coefficient 20%

Mechanical durability in millions of operating cycles 10

Electrical durabilityin millions of operating cycles Resistive load 0.1

6© 2005–2008 Schneider Electric All Rights Reserved 01/2008

Zelio® Plug-in Relays RXM Miniature RelaysSpecifications and Characteristics

Electrical durability of contacts

Resistive load AC

A=RXM2ABppp B=RXM3ABppp C=RXM4ABppp D=RXM4GBppp

105

106

107

2 30 1

A BDCD

urab

ility

(N

umbe

r of

ope

ratin

g cy

cles

)

Switching capacity (kVA)

Coil characteristics

Average consumptionAC 1.2 VA

DC 0.9 W

Drop-out voltage thresholdAC u 0.15 Uc

DC u 0.1 Uc

Operating time(response time)

Between coil energization and making of the N.O. contact

AC 20 ms

DC 20 ms

Between coil de-energization and making of the N.C. contact

AC 20 ms

DC 20 ms

Coil voltage Uc 12 V 24 V 48 V 110 V 120 V 125 V 220 V 230 V 240 V

Relay coil voltage codes JD BD ED FD — GD MD — —

DC

Average resistance at 68 °F (20 °C) ± 10% 160 Ω 650 Ω 2,600 Ω 11,000 Ω — 11,000 Ω 14,000 Ω — —

Operating voltage limitsMin. 9.6 V 19.2 V 38.4 V 88 V — 100 V 176 V — —

Max. 13.2 V 26.4 V 52.8 V 121 V — 138 V 242 V — —

Relay coil voltage codes — B7 E7 — F7 — M7 P7 U7

AC

Average resistance at 68 °F (20 °C) ± 15% — 180 Ω 770 Ω — 4,430 Ω — 15,000 Ω 15,000 Ω 15,500 Ω

Operating voltage limitsMin. — 19.2 V 38.4 V — 96 V — 176 V 184 V 192 V

Max. — 26.4 V 52.8 V — 132 V — 242 V 253 V 264 V

Socket characteristics

Socket type RXZE2S108M RXZE2S111M RXZE2S114M RXZE2M114 RXZE2M114M

Relay types used RXM2ppppp RXM3ppppp RXM4ppppp RXM2ppppp1

RXM4pppppRXM2ppppp1

RXM4ppppp

Product certifications cURus File E172326 CCN SWIV2, SWIV8; CSA (pending); CE; RoHS compliant

Conventional thermal current (Ith) 12 A 10 A

Degree of protection Conforming to IEC/EN 60529 IP 20

Connection

Solid wire without cable end 1 conductor: AWG 20–12 (0.5–2.5 mm2)2 conductors: AWG 20–14 (0.5–1.5 mm2)

Flexible wire with cable end 1 conductor: AWG 24–14 (0.2–2.5 mm2)2 conductors: AWG 24–16 (0.2–1.5 mm2)

Flexible wire without cable end 1 conductor: AWG 24–14 (0.2–2.5 mm2)2 conductors: AWG 24–16 (0.2–1.5 mm2)

Maximum tightening torque 5.3 lbf-in (0.6 Npm) (M3 screw)

Contact terminal arrangement Separate Mixed

Bus jumper Ith: 5 A Yes No1 When mounting relay RXM2ppppp on socket RXZE2Mpppp, the thermal current must not exceed 10 A.

RXM Miniature Relays Zelio® Plug-in RelaysOrdering Information

701/2008 © 2005–2008 Schneider Electric All Rights Reserved

RXMpAB2F7

Miniature relays with lockable test button, without LED (sold in lots of 10)

Number and type of contacts - Thermal current (Ith)

DPDT - 12 A 3PDT - 10 A 4PDT - 6 A

Coil Voltage Catalog NumberWeight

Catalog NumberWeight

Catalog NumberWeight

lb. kg lb. kg lb. kg

12 Vdc RXM2AB1JD 0.082 0.037 RXM3AB1JD 0.084 0.038 RXM4AB1JD 0.080 0.036

24 Vdc RXM2AB1BD 0.082 0.037 RXM3AB1BD 0.084 0.038 RXM4AB1BD 0.080 0.036

48 Vdc RXM2AB1ED 0.082 0.037 RXM3AB1ED 0.084 0.038 RXM4AB1ED 0.080 0.036

110 Vdc RXM2AB1FD 0.082 0.037 RXM3AB1FD 0.084 0.038 RXM4AB1FD 0.080 0.036

220 Vdc — — — — — — RXM4AB1MD 0.080 0.036

24 Vac RXM2AB1B7 0.082 0.037 RXM3AB1B7 0.084 0.038 RXM4AB1B7 0.080 0.036

48 Vac RXM2AB1E7 0.082 0.037 RXM3AB1E7 0.084 0.038 RXM4AB1E7 0.080 0.036

120 Vac RXM2AB1F7 0.082 0.037 RXM3AB1F7 0.084 0.038 RXM4AB1F7 0.080 0.036

230 Vac RXM2AB1P7 0.082 0.037 RXM3AB1P7 0.084 0.038 RXM4AB1P7 0.080 0.036

240 Vac — — — — — — RXM4AB1U7 0.080 0.036

Miniature relays with lockable test button, with LED (sold in lots of 10)

12 Vdc RXM2AB2JD 0.082 0.037 RXM3AB2JD 0.084 0.038 RXM4AB2JD 0.080 0.036

24 Vdc RXM2AB2BD 0.082 0.037 RXM3AB2BD 0.084 0.038 RXM4AB2BD 0.080 0.036

48 Vdc RXM2AB2ED 0.082 0.037 RXM3AB2ED 0.084 0.038 RXM4AB2ED 0.080 0.036

110 Vdc RXM2AB2FD 0.082 0.037 RXM3AB2FD 0.084 0.038 RXM4AB2FD 0.080 0.036

125 Vdc — — — — — — RXM4AB2GD 0.080 0.036

24 Vac RXM2AB2B7 0.082 0.037 RXM3AB2B7 0.084 0.038 RXM4AB2B7 0.080 0.036

48 Vac RXM2AB2E7 0.082 0.037 RXM3AB2E7 0.084 0.038 RXM4AB2E7 0.080 0.036

120 Vac RXM2AB2F7 0.082 0.037 RXM3AB2F7 0.084 0.038 RXM4AB2F7 0.080 0.036

230 Vac RXM2AB2P7 0.082 0.037 RXM3AB2P7 0.084 0.038 RXM4AB2P7 0.080 0.036

RXM4GB2F7

Miniature relays with low level contacts, without LED (sold in lots of 10)

Miniature relays with low level contacts, with LED (sold in lots of 10)

Number and type of contacts - Thermal current (Ith) Number and type of contacts - Thermal current (Ith)

4PDT - 3 A 4PDT - 3 A

Coil Voltage Catalog NumberWeight

Coil Voltage Catalog NumberWeight

lb. kg lb. kg

12 Vdc RXM4GB1JD 0.080 0.036 12 Vdc RXM4GB2JD 0.080 0.036

24 Vdc RXM4GB1BD 0.080 0.036 24 Vdc RXM4GB2BD 0.080 0.036

48 Vdc RXM4GB1ED 0.080 0.036 48 Vdc RXM4GB2ED 0.080 0.036

110 Vdc RXM4GB1FD 0.080 0.036 110 Vdc RXM4GB2FD 0.080 0.036

24 Vac RXM4GB1B7 0.080 0.036 24 Vac RXM4GB2B7 0.080 0.036

48 Vac RXM4GB1E7 0.080 0.036 48 Vac RXM4GB2E7 0.080 0.036

120 Vac RXM4GB1F7 0.080 0.036 120 Vac RXM4GB2F7 0.080 0.036

230 Vac RXM4GB1P7 0.080 0.036 230 Vac RXM4GB2P7 0.080 0.036

240 Vac RXM4GB2U7 0.080 0.036

SMartin
Rectangle
SMartin
Line
SMartin
Highlight

RXM Miniature Relays Zelio® Plug-in RelaysOrdering Information

901/2008 © 2005–2008 Schneider Electric All Rights Reserved

RXZ E2M114M withrelay RXM4AB2P7TQ

RXZ E2S114M withrelay RXM4AB2F7TQ

Miniature relays with lockable test button, without LED (sold in lots of 100)Number and type of contacts - Thermal current (Ith)DPDT - 12 A 4PDT - 6 A

Coil Voltage Catalog NumberWeight

Catalog NumberWeight

lb. kg lb. kg

12 Vdc — — — RXM4AB1JDTQ 0.080 0.036

24 Vdc RXM2AB1BDTQ 0.082 0.037 RXM4AB1BDTQ 0.080 0.036

48 Vdc — — — RXM4AB1EDTQ 0.080 0.036

110 Vdc — — — RXM4AB1FDTQ 0.080 0.036

220 Vdc — — — RXM4AB1MDTQ 0.080 0.036

24 Vac RXM2AB1B7TQ 0.082 0.037 RXM4AB1B7TQ 0.080 0.036

48 Vac — — — RXM4AB1E7TQ 0.080 0.036

120 Vac RXM2AB1F7TQ 0.082 0.037 RXM4AB1F7TQ 0.080 0.036

230 Vac RXM2AB1P7TQ 0.082 0.037 RXM4AB1P7TQ 0.080 0.036

Miniature relays with LED (sold in lots of 100)

24 Vdc — — — RXM4AB2BDTQ 0.080 0.036

24 Vac RXM2AB2B7TQ 0.082 0.037 RXM4AB2B7TQ 0.080 0.036

230 Vac RXM2AB2P7TQ 0.082 0.037 RXM4AB2P7TQ 0.080 0.036

Sockets (sold in lots of 10)

Contact terminal arrangement Connection Relay type Catalog NumberWeightlb. kg

MixedScrew clamp terminals RXM2pppp 1

RXM4pppp RXZE2M114 2 0.11 0.048

Box lug connector RXM2pppp 1

RXM4pppp RXZE2M114M 2 0.12 0.056

Separate Box lug connectorRXM2pppp RXZE2S108M 3 0.13 0.058RXM3pppp RXZE2S111M 2 0.15 0.066RXM4pppp RXZE2S114M 2 0.15 0.070

1 When mounting relay RXM2ppppp on socket RXZE2Mpppp, the thermal current must not exceed 10 A.2 Thermal current Ith: 10 A3 Thermal current Ith: 12 A

RXM 041pp7

Protection modules (sold in lots of 20)

Description Voltage For use with Catalog NumberWeightoz. g

Diode 6–250 Vdc All sockets RXM040W 0.11 3.0

RC circuit24–60 Vac All sockets RXM041BN7 0.35 10.0110–240 Vac All sockets RXM041FU7 0.35 10.0

Varistor6–24 Vac/Vdc All sockets RXM021RB 1.06 30.024–60 Vac/Vdc All sockets RXM021BN 1.06 30.0110–240 Vac/Vdc All sockets RXM021FP 1.06 30.0

REXL4pp

Timing relays

Description For use with Catalog NumberWeightlb. kg

2 timed DPDT contacts (function A—On-delay)

Sockets RXZ EpppppREXL2pp 4 0.09 0.042

4 timed 4PDT contacts (function A—On-delay) REXL4pp 4 0.09 0.042

4 Please refer to the Zelio® Time - Timers catalog (9050CT0001R2/05).

RXZ400

Accessories (sold in lots of 10)

Description For use with Catalog NumberWeightoz. g

Metal hold-down clip All sockets RXZ400 0.04 1.0Plastic hold-down clip All sockets RXZR335 0.18 5.0Bus jumper, 2-pole (Ith: 5 A) All sockets with separate contacts RXZS2 0.18 5.0Mounting adapter for DIN rail 5 All relays RXZE2DA 0.14 4.0Mounting adapter for mounting directly to a panel All relays RXZE2FA 0.07 2.0

Clip-in markersAll relays (sheet of 108 markers) RXZL520 2.82 80.0All sockets except RXZE2M114 RXZL420 0.04 1.0

5 Test button becomes inaccessible.

SMartin
Rectangle
SMartin
Line

10© 2005–2008 Schneider Electric All Rights Reserved 01/2008

Zelio® Plug-in Relays RXM Miniature RelaysDimensions

RelaysRXMpppppp RXM2 RXM3 RXM4Common view Pin side view

1.57 (40) 0.83(21)

1.06

(27)

0.28(7)

0.24(6)

0.10(2.5)

0.10(2.5)

210.26(6.5)

0.24(6)

0.16(4)

0.53(13.5)

0.10(2.5)

0.10(2.5)

0.18(4.5)

21

0.53(13.5)

= =

0.10(2.5

0.10(2.5)0.53

(13.5)

= ==

SocketsRXZE2M114 RXZE2M114M

RXZE2Spppp RXZE2S108M RXZE2S111M RXZE2S114MCommon side view Pin side view

(1) Relays(2) Add-on protection module(3) Hold-down clip(4) 2 elongated holes Ø 0.14 x 0.26 (3.5 x 6.5)(5) 2 bus jumpers

(1)

(2)

(3)

1.00(25.5)

347

A214

A113

246

448

145

12

1

11

9

21

10

31

11

41

12

22

2

32

3

42

4

(4)

0.75(19)

1.57(40)

1.18(30)

0.35(9)

0.91(23)

0.83(21)1.18(30)2.72

(69)0.28(7)

1.56

(39.

5)

2.40

(61)

0.14

(3.5

)3.

11(7

9)

0.14(3.5)

0.67(17)

1.69(43)

0.93(23.5)

1.97(50)

1.06(27)

2.64(67)

1.57

(40)

3.15

(80)

44

8

34

7

24

6

14

5

42

4

32

3

22

2

12

1

A1

13

A2

1441

12

31

11

21

10

11

9

(3)

(1)

(2)

0.14(3.5)

0.28(7)

2.40(61)

0.91(23)

(3)

(2)

(1)

(5)

0.28(7)

0.75(19)

1.14(29)2.76

(70)

0.14

(3.5

)3.

11(7

9)

0.93(23.5)1.06(27)

1.50

(38)

41

12

11

9

44

8

14

5

A1

13

A2

14

42

4

12

1

0.14(3.5)

319

346

A1

13

A2

14

32

3

218

245

22

2

117

144

12

1

0.93(23.5)1.06(27)

1.50

(38)

0.14(3.5)

0.93(23.5)1.06(27)

1.50

(38)

0.14(3.5)

41

12

31

11

21

10

11

944

8

34

7

24

6

14

542

4

32

3

22

2

12

1

A1

13

A2

14

Dimensions = Inches(mm)

RXM Miniature Relays Zelio® Plug-in RelaysDimensions

1101/2008 © 2005–2008 Schneider Electric All Rights Reserved

Plastic clamp and clip-in markers

RXZR335 RXZL420 Mounting on all sockets

(1) Clip-in markers for all sockets except RXZE2M114.

2.24(57)

1.06

(27)

0.47

(12)

0.56

(14.

2)

1.04(26.5)

3.19(81)

3.72

(94.

5)

(1)

Bus jumper Metal clamp

RXZS2 Mounting on sockets with separate contacts (view from below) RXZ400

Example of bus jumper mounting on sockets

(1) 2 bus jumpers (polarity A2)(2) 2 bus jumpers (polarity A1)

0.09

(2.2

)

0.29

(7.3

)

0.98(25)

0.87(22) 0.09

(2.3)

(1)(1)

(2)(2)

1.46(37)

1.02

(26)

0.05(1.2)

Mounting adapter for rail 1 Mounting adapter for panelRXZE2DA RXZE2FA

1 Test button becomes inaccessible

1.50

(38)

0.24(6)

0.16(4)

0.94(24)

0.12 (3)

1.89

(48)

0.91(23)2.01

(51)

1.89(48)

1.93(49)

0.14(3.5)

1.69

(43)

1.50

(38)

0.16(4)

0.94(24)

0.14(3.5)

Dimensions = Inches(mm)

12© 2005–2008 Schneider Electric All Rights Reserved 01/2008

Zelio® Plug-in Relays RXM Miniature RelaysWiring Diagrams

Miniature relaysRXM2ppppp RXM3ppppp RXM4ppppp

Numbers shown in italics correspond to NEMA marking. Viewed from pin end.

A2

A1

414442

111412

1

125

149

11

4

428

4412

4113

A1

14

A2

A2

A1

313432

212422

111412

1

12

4

147

11

2

22

5

248

21

3

32

6

349

3113

A1

14

A2

A2

A1

414442

212422

313432

111412

1

125

149

11

4

428

4412

41

2

226

2410

21

3

327

3411

3113

A1

14

A2

DATE: 11-7-2014

PANEL: PDP

REV:

QTY LEGEND DESCRIPTION MFG PART NO.

ENCLOSURE & COMPONENTS

1Enclosure; 24 x 24 x 8, Nema 4X, SS304, Wall Mount, 3 Point Latch Hoffman A24H2408SSLP3PT

1 Enclosure; 24 x 24 Panel Hoffman A24P24

1 Enclosure; Drip Shield 24 In, SS304 Hoffman ADK24SS6

A/R Din Rail; 1 Meter Custom Connector C103PM

A/R Terminal Block; UK 5N, 30A, 600V Phoenix 3004362A/R End Block; ENS 35N Phoenix 800886A/R End Cover; D-UK 4/10 (UK 5 & 6) Phoenix 3030206 Distribution Block; 175A, 1IN/1OUT Mersen FSPDB1A

1 HT Heater; 100W, 120V Hoffman D-AH1001A

CONTROL COMPONENTS

1 ISRBarrier, Pulse, Two Channel, Isolated, 24-230VAC/DC PR Electronics 5202B4

1 ISBBarrier, Analog, Single Channel, Isolated, 24-230VAC/DC PR Electronics 5104B-B2A

EXTERNAL EQUIPMENT

2 FSHH,FSH Float; ENM-10 Level Regulator, 40 Ft Xylem 5828830

1 LXDCRLevel Transducer, 3400 Series Hydro-Static, 0-30 Ft Range, 39 Ft Cable (Std) MJK 209925

MARION COUNTY, AURORA, OR - FARGO L/S

XYLEM WATER SOLUTIONS USA, INC

QUOTE NO. 081514SM4.1

BILL OF MATERIAL

JOB NAME

CUSTOMER

Spec-00090 G

Wall-Mount EnclosurEs Wall-Mount EnclosurEs and accEssoriEs

EQUIPMENT PROTECTION SOLUTIONSSUBJECT TO CHANGE WITHOUT NOTICEstainlEss stEEl1

Spec-00090G763.422.2211763.422.2600

stainlEss stEElWall-Mount EnclosurEsWall-Mount EnclosurEs and accEssoriEs

continuous HingE WitH 3-Point latcH, tyPE 4X

inDustry stanDarDs

UL 508A Listed; Type 3R, 4, 4X, 12; File No. E61997cUL Listed per CSA C22.2 No 94; Type 3R, 4, 4X, 12; File No. E61997

NEMA/EEMAC Type 3R, 4, 4X, 12, 13IEC 60529, IP66Meets NEMA Type 3RX requirements

aPPlicationThese enclosures feature Hoffman’s exclusive POWERGLIDE™ Handle with 3-point latching, ideal for indoor or outdoor applications that require corrosion protection, convenient access, and padlocking security.

sPEciFications• 14 gauge Type 304 or 316L stainless steel bodies and doors• Seams continuously welded and ground smooth• Seamless foam-in-place gasket• Rolled lip around three sides of door • Internal 3-point latch and Type 316L stainless steel padlocking

POWERGLIDE Handle • Remove door by pulling stainless steel continuous hinge pin• Data pocket is high-impact thermoplastic• Collar studs provided for mounting optional panels• Exterior hardware on Type 316L stainless steel enclosures

matches enclosure material• Bonding provision on door; grounding stud on body

FinisHDoor, sides, top and bottom have smooth #4 brushed finish. Handle is electropolished.

accEssoriEsSee also Accessories.Panels for Type 3R, 4, 4X, 12 and 13 EnclosuresSteel and Stainless Steel Window KitsH2OMIT™ Vent Drains, Type 4XH2OMIT™ Thermoelectric Dehumidifier

MoDiFication anD custoMiZationHoffman excels at modifying and customizing products to your specifications. Contact your local Hoffman sales office or distributor for complete information.Bulletin: A4SW3

Standard Product

Catalog Number AxBxC in./mmStainlessSteel Type

F in./mm

SteelPanel

ConductivePanel

StainlessSteel Panel

Panel SizeD x E in./mm

DataPocket

A24H2006SSLP3PT 24.00 x 20.00 x 6.00 610 x 508 x 152

304 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

A24H2006SS6LP3PT 24.00 x 20.00 x 6.00 610 x 508 x 152

316L 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

A24H2008SSLP3PT 24.00 x 20.00 x 8.00 610 x 508 x 203

304 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

A24H2008SS6LP3PT 24.00 x 20.00 x 8.00 610 x 508 x 203

316L 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

A24H2408SSLP3PT 24.00 x 24.00 x 8.00 610 x 610 x 203

304 3.0076

A24P24 A24P24G A24P24SS6 21.00 x 21.00533 x 533

Small

A24H2408SS6LP3PT 24.00 x 24.00 x 8.00 610 x 610 x 203

316L 3.0076

A24P24 A24P24G A24P24SS6 21.00 x 21.00533 x 533

Small

A30H2408SSLP3PT 30.00 x 24.00 x 8.00 762 x 610 x 203

304 3.0076

A30P24 A30P24G A30P24SS6 27.00 x 21.00686 x 533

Large

A30H2408SS6LP3PT 30.00 x 24.00 x 8.00 762 x 610 x 203

316L 3.0076

A30P24 A30P24G A30P24SS6 27.00 x 21.00686 x 533

Large

A30H3008SSLP3PT 30.00 x 30.00 x 8.00 762 x 762 x 203

304 3.0076

A30P30 A30P30G A30P30SS6 27.00 x 27.00686 x 686

Large

A30H3008SS6LP3PT 30.00 x 30.00 x 8.00 762 x 762 x 203

316L 3.0076

A30P30 A30P30G A30P30SS6 27.00 x 27.00686 x 686

Large

A36H2408SSLP3PT 36.00 x 24.00 x 8.00 914 x 610 x 203

304 3.0076

A36P24 A36P24G A36P24SS6 33.00 x 21.00838 x 533

Large

A36H2408SS6LP3PT 36.00 x 24.00 x 8.00 914 x 610 x 203

316L 3.0076

A36P24 A36P24G A36P24SS6 33.00 x 21.00838 x 533

Large

A36H3008SSLP3PT 36.00 x 30.00 x 8.00 914 x 762 x 203

304 3.0076

A36P30 A36P30G A36P30SS6 33.00 x 27.00838 x 686

Large

A36H3008SS6LP3PT 36.00 x 30.00 x 8.00 914 x 762 x 203

316L 3.0076

A36P30 A36P30G A36P30SS6 33.00 x 27.00838 x 686

Large

A48H3608SSLP3PT 48.00 x 36.00 x 8.00 1219 x 914 x 203

304 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A48H3608SS6LP3PT 48.00 x 36.00 x 8.00 1219 x 914 x 203

316L 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A24H2010SSLP3PT 24.00 x 20.00 x 10.00 610 x 508 x 254

304 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

SMartin
Rectangle
SMartin
Line
SMartin
Highlight
SMartin
Highlight

Spec-00090 G

Wall-Mount EnclosurEs Wall-Mount EnclosurEs and accEssoriEs

PH 763.422.2211 • FAX 763.422.2600 • HOFFMANONLINE.COMEQUIPMENT PROTECTION SOLUTIONS stainlEss stEEl 2

Catalog Number AxBxC in./mmStainlessSteel Type

F in./mm

SteelPanel

ConductivePanel

StainlessSteel Panel

Panel SizeD x E in./mm

DataPocket

A24H2010SS6LP3PT 24.00 x 20.00 x 10.00 610 x 508 x 254

316L 3.0076

A24P20 A24P20G A24P20SS6 21.00 x 17.00533 x 432

Small

A36H3010SSLP3PT 36.00 x 30.00 x 10.00 914 x 762 x 254

304 3.0076

A36P30 A36P30G A36P30SS6 33.00 x 27.00838 x 686

Large

A36H3010SS6LP3PT 36.00 x 30.00 x 10.00 914 x 762 x 254

316L 3.0076

A36P30 A36P30G A36P30SS6 33.00 x 27.00838 x 686

Large

A42H3010SSLP3PT 42.00 x 30.00 x 10.00 1067 x 762 x 254

304 3.0076

A42P30 A42P30G A42P30SS6 39.00 x 27.00991 x 686

Large

A48H3610SSLP3PT 48.00 x 36.00 x 10.00 1219 x 914 x 254

304 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A48H3610SS6LP3PT 48.00 x 36.00 x 10.00 1219 x 914 x 254

316L 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A24H2412SSLP3PT 24.00 x 24.00 x 12.00 610 x 610 x 305

304 3.0076

A24P24 A24P24G A24P24SS6 21.00 x 21.00533 x 533

Small

A24H2412SS6LP3PT 24.00 x 24.00 x 12.00 610 x 610 x 305

316L 3.0076

A24P24 A24P24G A24P24SS6 21.00 x 21.00533 x 533

Small

A30H2412SSLP3PT 30.00 x 24.00 x 12.00 760 x 610 x 305

304 3.0076

A30P24 A30P24G A30P24SS6 27.00 x 21.00686 x 533

Large

A30H2412SS6LP3PT 30.00 x 24.00 x 12.00 762 x 610 x 305

316L 3.0076

A30P24 A30P24G A30P24SS6 27.00 x 21.00686 x 533

Large

A36H3012SSLP3PT 36.00 x 30.00 x 12.00 914 x 762 x 305

304 3.0076

A36P30 A36P30G A36P30SS6 33.00 X 27.00838 x 686

Large

A36H3012SS6LP3PT 36.00 x 30.00 x 12.00 914 x 762 x 305

316L 3.0076

A36P30 A36P30G A36P30SS6 33.00 X 27.00838 x 686

Large

A36H3612SSLP3PT 36.00 x 36.00 x 12.00 914 x 914 x 305

304 3.0076

A36P36 A36P36G A36P36SS6 33.00 x 33.00838 x 838

Large

A36H3612SS6LP3PT 36.00 x 36.00 x 12.00 914 x 914 x 305

316L 3.0076

A36P36 A36P36G A36P36SS6 33.00 x 33.00838 x 838

Large

A42H3612SSLP3PT 42.00 x 36.00 x 12.00 1067 x 914 x 305

304 3.0076

A42P36 A42P36G A42P36SS6 39.00 x 33.00991 x 838

Large

A48H3612SSLP3PT 48.00 x 36.00 x 12.00 1219 x 914 x 305

304 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A48H3612SS6LP3PT 48.00 x 36.00 x 12.00 1219 x 914 x 305

316L 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A60H3612SSLP3PT 60.00 x 36.00 x 12.00 1524 x 914 x 305

304 3.0076

A60P36 A60P36G A60P36SS6 57.00 x 33.001448 x 838

Large

A60H3612SS6LP3PT 60.00 x 36.00 x 12.00 1524 x 914 x 305

316L 3.0076

A60P36 A60P36G A60P36SS6 57.00 x 33.001448 x 838

Large

A48H3616SSLP3PT 48.00 x 36.00 x 16.00 1219 x 914 x 406

304 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A48H3616SS6LP3PT 48.00 x 36.00 x 16.00 1219 x 914 x 406

316L 3.0076

A48P36 A48P36G A48P36SS6 45.00 x 33.001143 x 838

Large

A60H3616SSLP3PT 60.00 x 36.00 x 16.00 1524 x 914 x 406

304 3.0076

A60P36 A60P36G A60P36SS6 57.00 x 33.001448 x 838

Large

A60H3616SS6LP3PT 60.00 x 36.00 x 16.00 1524 x 914 x 406

316L 3.0076

A60P36 A60P36G A60P36SS6 57.00 x 33.001448 x 838

Large

Purchase panels separately. Optional stainless steel, composite and aluminum panels are available for most sizes.

Spec-00480 E

Drip ShielDS Drip ShielDS

EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEAcceSSorieS1

Spec-00480e763.422.2211763.422.2600

AcceSSorieSDrip ShielDSDrip ShielDS

Drip ShielD Kit for type 12 encloSureS

Protects door hardware from dripping water and settling dust. Attaches quickly and easily to the enclosure with stainless steel screws and sealing washers (hardware is furnished). Stainless steel hinge pin and stainless steel door clamping assemblies are furnished to replace the standard hinge pin and door clamping assemblies. A tube of sealing compound is also supplied with each kit. Manufactured from 14 gauge steel with an ANSI 61 gray polyester powder paint finish over pretreated surfaces.Bulletin: A80

Catalog Number For

Fits EnclosureSize B in./mm

ADK12A Single-Door Wall-Mount Enclosures 12.00305

ADK16A Single-Door Wall-Mount Enclosures 16.00406

ADK20A Single-Door Wall-Mount Enclosures 20.00508

ADK24A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 24.00610

ADK30A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 30.00762

ADK36A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 36.00914

ADK42A Two-Door Floor-Mount, Continuous Hinge Enclosures 42.001067

ADK48A Two-Door Floor-Mount, Continuous Hinge Enclosures-Door Floor-Mount Enclosures

48.001219

ADK60A Two-Door Floor-Mount, Continuous Hinge Enclosuresoor Floor-Mount Enclosures

60.001524

ADK72A Two-Door Floor-Mount, Continuous Hinge Enclosuresoor Floor-Mount Enclosures

72.001829

Two-Door Drip Shield kits are not designed for use on 48.00-in. (1219-mm) wide and 60.00-in. (1524-mm) wide Two-Door Type 12 Wall-Mount Enclosures.

Drip ShielD Kit for type 12 free-StAnDing AnD floor-Mount encloSureS With conceAleD hingeSProtects door hardware from dripping water and settling dust. Attaches quickly and easily to the enclosure with stainless steel screws and sealing washers (hardware is furnished). A tube of sealing compound is also supplied with each kit. Manufactured from 14 gauge steel with an ANSI 61 gray polyester powder paint finish over pretreated surfaces.

Bulletin: A80

Catalog Number ForFits Enclosure Size B in./mm

ADK24HH Single-Door Free-Stand/Floor-Mount Enclosures 24.00610

ADK30HH Single-Door Free-Stand/Floor-Mount Enclosures 30.00762

ADK36HH Single-Door Free-Stand/Floor-Mount Enclosures 36.00914

ADK42HH Two-Door Free-Stand/Floor-Mount Enclosures 42.001067

ADK48HH Two-Door Free-Stand/Floor-Mount Enclosures 48.001067

ADK60HH Two-Door Free-Stand/Floor-Mount Enclosures 60.001524

ADK72HH Two-Door Free-Stand/Floor-Mount Enclosures 72.001829

StAinleSS Steel Drip ShielD Kit for type 4 AnD 4X WAll-Mount encloSureS

Easily installed on Type 4 and 4X wall-mount enclosures (excluding quick-release latch models). Protects door from dripping water and settling dust. Attaches quickly and easily to the enclosure with stainless steel screws and sealing washers (furnished). A tube of sealing compound is supplied with each kit. Manufactured from 14 gauge Type 316 stainless steel. Kits can be special ordered for other Hoffman enclosures. Consult factory for more information. Product maintains UL/CSA Type 4, 4X and 12 rating when properly installed on a Hoffman enclosure.Bulletin: A4SY

Catalog NumberFits Enclosure Size B in./mm

ADK12SS6 12.00305

ADK16SS6 16.00406

ADK20SS6 20.00508

ADK24SS6 24.00610

ADK30SS6 30.00762

ADK36SS6 36.00914

SMartin
Rectangle
SMartin
Line
SMartin
Highlight

25

Custom Connector Corporation • 1738 E. 30th, Cleveland, OH 44114 • 216/241-1679 • Fax 216/241-5529E-mail: [email protected] • Web: www.customconnector.com

RELAY SOCKET ACCESSORIES DIN RAIL DRAWINGS & SPECIFICATIONS

PART NO. DESCRIPTION SERIES NO.

C-103-PM Prepunched Aluminum DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-104-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-105-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

C-106-2PM Prepunched Steel DIN Rail (2 Meter Lengths) ES, GT, MT, OT, ST(note: Other lengths available, consult factory)

.984[25.00]

1.063[27.00]

.287[7.29]

.943[23.95]

1.378[35.00]

.177[4.50]

R.

1.083[27.50] 1.378[35.00]TYP.

39.370 [1000.00]

R.

1.063[27.00]

.295[7.50]

1.378[35.00]

.709[18.00]

.205[5.20]

.492[12.50] .984[25.00]

39.370[1000.00]

1.063[27.00]1.378[35.00]

.709[18.00]

.492[12.50] .984[25.00]

39.370[1000.00] .590[15.00]

R.

.248[6.30]

.039[1.00]

.709[18.00]

.492[12.50] .984[25.00]

78.740[2000.00]

R.

.248[6.30] 1.378[35.00] 1.063[27.00]

.295[7.50]

OTHER STYLES AND HOLE PATTERNS AVAILABLE. CONSULT FACTORY

SMartin
Rectangle

I2

FSPDB Finger-Safe Power Distribution Blocks

Safety evolvingMersen FSPDBs introduce a new level of safety and ease for installing power distribution blocks. An IP20 level of finger-safe protection is achieved using FSPDBs,eliminating the need for special covers or custom Plexiglas sheets to protect your panels. FSPDBs (sizes 1 to 4) simply snap onto 35mm DIN rail to provide the quickest installation. Modular design also allows for multi pole applications by use of assembly pins. FSPDBs provide a safe, convenient way of splicing cables, splitting primary power into a variety of secondary circuits or providing a fixed junction tap-o f point.

Ratings:Volts : 600VAmps: : 175 to 840ASCCR : 100kA with proper fuse.

Contact Technical Services for instruction sheet and/or DC Ratings.

Features/Benefits: • Finger-safe protection

Fully insulated block ensures touch safe isolation of live parts. Recessed termination screws and wire openings provide IP20 grade protection and qualify as “finger-safe” per IEC 529

• Compact modularitySingle or multiple pole configurations in the most compact foot rint. Allows users to build smaller or higher density panels.

• Snap on DIN-rail mountingSizes 1 to 4 feature integral DIN rail adaptors allowing for quick and easy installations on 35mm DIN rail yielding lower installed costs.

• Captive termination screwsUnique channel design ensures captive metric wire termination screws. Screws can never be lost.

• Available accessoriesFor multi-pole panel mounting, simply snap in pins for rigid fi . Cap plugs provide the ability to maintain touch safety on unused openings. Circuit identification markers simply snap into blocks to ID circuits. nd anchors provide rigid end stops.

• Multiple wire ratingsProvide users more versatility by offering capability of using multiple conductors in #2 and 2/0 openings.

• AC & DC ratingsFSPDB1, 2, and 3 have been evaluated for use at 1000V (AC or DC) provided they are installed on DIN-rails only and with barriers between poles of opposite polarity of sufficient size to maintain requi ed spacings.

Approvals: • UL Recognized Component

Guide XCFR2, File E73571 • CSA Certified: Class 6228, Fil

69363

For the most current product performance data visit us-ferrazshawmut.mersen.com and use catalog search. I3

I

Catalog Numbers

A

B

C

DE

F

G

H

J

K

A

B

C

DE

F

G

HI

K

J

Figure 1 Figure 2

Dimension

FSPDB1A FSPDB2A FSPDB3A FSPDB4A FSPDB5A

FSPDB1C FSPDB2C FSPDB3C FSPDB4C FSPDB5C

Figure 1 Figure 1 Figure 2 Figure 1 Figure 2

mm in mm in mm in mm in mm in

A 25.4 1.00 28.4 1.12 46.9 1.85 39 1.54 72 2.84

B 43.3 1.70 57.8 2.28 64.3 2.53 108 4.25 91 3.58

C 49.5 1.95 56.0 2.21 64.3 2.53 80 3.15 80 3.15

D 45.1 1.78 51.6 2.03 59.8 2.36 75.5 2.97 - -

E 39.4 1.55 39.4 1.55 51.5 2.03 50.1 1.97 50.1 1.97

F 72.6 2.86 87.7 3.45 100.8 3.97 145.5 5.73 145 5.71

G 59.6 2.35 74.6 2.94 82.4 3.24 120.6 4.75 127.5 5.02

H 5.3 0.21 5.1 0.20 6.5 0.26 7 0.28 3 0.12

I - - - - 31.5 1.24 - - 52 2.04

J 5.3 0.21 6.4 0.25 6.5 0.26 6.5 0.26 6.5 0.26

K 10 0.40 11.7 0.46 8.9 0.35 16 0.63 8.5 0.34

Catalog No. Description

FSPIN1 Accessory pin to form multiple pole block

FSCIM1Circuit identification marker for 2/0 & #2 max. conductors (Qty of 100)

FSCIM2 Circuit identification marker for 350, 400 & 600 kcmil max. conductors (Qty of 100)

FSCAP1 Cap plug for spare 2/0 openings

FSCAP2 Cap plug for spare 350 kcmil openings

FSCP3 Cap plug for spare 600 kcmil opening

FSEA Pair of end anchors

Multiple Wire Ratings (Same Size & Type Wires Only)

2/0 Openings #2 Openings

(2) #4 AWG (2) #10 AWG (2) #6 AWG (2-4) #12 AWG

(2) #6 AWG (2) #12 AWG (2) #8 AWG (2-4) #14 AWG

(2) #8 AWG (2) #14 AWG (2-4) #10 AWG

•Contact Mersen Technical Services at [email protected] for fuse type and maximum ampere required.

Dimensions

FSPDB Finger-Safe Power Distribution Blocks

Catalog Number Ampere Rating (Based on NEC Table 310-16 for 75° C Cu wire only)

Line LoadShort Circuit Current Rating

Aluminum Copper Wire Range Wire Range Openings Per Pole

(Connector rated for 90° C Cu/AL wire)

(Connector rated for 75° C Cu wire only)

AWG/ mm2 Openings AWG/ kcmil

mm2

FSPDB1A FSPDB1C 175 2/0-#14 70-2.5 1 2/0-#14 70-2.5 1 100kA•

FSPDB2A FSPDB2C 175 2/0-#14 70-2.5 1 #2-#14 35-2.5 4 100kA•

FSPDB3A FSPDB3C 310350-#6 185-16

1 #8-#14 8-2.5 8 100kA•2/0-#14 70-2.5

FSPDB4A FSPDB4C 335 400-#6 185-16 1 400-#6 185-16 1 100kA•

FSPDB5A FSPDB5C 840 600-#4 300-25 2 600-#4 300-25 2 100kA•

Accessories

SMartin
Rectangle
SMartin
Line

Construction

• Attractive and durable housing is anodizedaluminum

• Thermostat, standard on all units, is adjustablefrom 0°F to 100°F (-18°C to 38°C)

• Fan draws cool air from the bottom of theenclosure and passes this air across thethermostat and heating elements beforebeing released into enclosure cavity

• Heated air is discharged through the top ofthe heater unit

• Four 10-32 self-tapping screws are includedwith each heater

• Ball bearing fan runs continuously for eventemperature distribution

• Terminal strip with clamp connector thataccepts both solid and stranded wire

Finish

Brushed aluminum.

Industry Standards

UL Component RecognizedCSA ListedCE

Hoffman electric heaters should be centered aslow as possible on an interior enclosure panel.This permits the unit to heat the cool airlocated at the bottom of the enclosure. Formaximum efficiency and longevity, the heatershould be mounted in a vertical position withthe terminal block to the bottom and the airoutlet openings at the top in a sealedenclosure free from dust or debris. However,the unit will also effectively distribute heat ifturned 90 degrees with the terminal block outthe bottom and the air outlet at the side.Although enclosure panels are preferable,heaters may be installed on any flat sheet metalsurface. Do not install heaters on wood panels.

Heat sensitive components should not beplaced near the heater discharge area since thisair can be quite warm.The clearance rangedefines the space that must be kept free ofthese components for proper and safeoperation of the heater.

Application

Designed to protect sensitive mechanical,electrical, and electronic equipment from theharmful effects of condensation, corrosion, andlow temperatures.Thermostatically controlledfan-driven heater units maintain a stabletemperature within enclosures so criticalcomponents can perform more reliably over a longer period of time.

Catalog WeightNumber Watts Voltage Hz Amps lb. (kg.)DAH1001A 100 115 50/60 0.9 4.00 (1.81)

DAH1002A 100 230 50/60 0.6 4.00 (1.81)

DAH2001A 200 115 50/60 1.7 4.00 (1.81)

DAH2002A 200 230 50/60 0.9 4.00 (1.81)

DAH4001B 400 115 50/60 3.3 6.00 (2.72)

DAH4002B 400 230 50/60 1.7 6.00 (2.72)

DAH8001B 800 115 50/60 6.5 6.00 (2.72)

DAH8002B 800 230 50/60 3.3 6.00 (2.72)

Standard Sizes Electric Heaters

9.46 Data subject to change without notice 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.

Electric Heaters

Installation

CAUTION

These electric heaters are not designed for use in dusty, dirty, corrosive, or hazardouslocations.

Portions of the heater can get hot. Adequateprotection must be taken to protect peoplefrom potential burns, and to protect othercomponents from this heat.

Hoffman recommends this heater only beinstalled in a totally-enclosed metalenclosure.

Do not install heaters on wood panels.

Rev. A October 2004

SMartin
Rectangle
SMartin
Line
SMartin
Line

9.47Data subject to change without notice 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.

Heaters

Electric H

eaters

9

Bulletin

D85

Dimensions and Clearance Range for DAH1001A, -2A and DAH2001A, -2A

Dimensions and Clearance Range for DAH4001B, -2B and DAH8001B, -2B

Bulletin

D85

Pulse isolator

5202B2 channels - 2 or 4 outputs–Dual output–5-port 3.75 kVAC galvanic isolation–Cable error detection–Universal supply by AC or DC–

ConnectionApplication

Pulse isolator with safety barrier for the supply of NAMURsensors installed in the hazardous area.

Pulse isolator with safety barrier for the detection ofmechanical contacts installed in the hazardous area.

One input signal can be used on two separate outputs.•A cable error alarm can be detected on a separate output.•

Technical characteristicsPR5202B1 and 5202B2 have relays with change-overcontacts or open NPN collectors available in the safe area.

PR5202B4 has 4 SPST relays, which are activatedsimultaneously two and two, available in the safe area. Eachrelay can be programmed to the function N.O. or N.C.

Inputs, outputs and supply are floating and galvanicallyseparated.

5202B is designed according to strict safety requirements andis therefore suitable for application in SIL 2 installations.

Mounting / installationMounted vertically or horizontally on a DIN rail. Up to 84channels per meter can be mounted.

This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for informationpurpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability

SMartin
Rectangle
SMartin
Highlight
SMartin
Rectangle
SMartin
Text Box
5202B4
SMartin
Line

Environmental ConditionsSpecifications range....................................... -20°C to +60°CCalibration temperature................................. 20...28°CRelative humidity............................................ < 95% RH (non-cond.)Protection degree........................................... IP20

Mechanical specificationsDimensions (HxWxD)..................................... 109 x 23.5 x 130 mmWeight approx................................................ 230 gWire size........................................................ 1 x 2.5 mm2 stranded wireScrew terminal torque.................................... 0.5 Nm

Common specificationsSupply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or

19.2...300 VDCFuse............................................................... 400 mA SB / 250 VACMax. power consumption............................... ≤ 1.5 W (2 channels), 5202B1

and 5202B2Max. power consumption............................... ≤ 2.0 W (2 channels), 5202B4Internal consumption...................................... ≤ 1.5 W (2 channels), 5202B1

and 5202B2Internal consumption...................................... ≤ 2.0 W (2 channels), 5202B4Isolation voltage, test /working........................................................... 3.75 kVAC / 250 VACAuxiliary supplies: NAMURsupply............................................................. 8 VDC / 8 mAEMC immunity influence................................ < ±0.5%Extended EMC immunity: NAMURNE 21, A criterion, burst................................. < ±1%

Input specificationsSensor types.................................................. NAMUR according to EN

60947-5-6 / Mechanicalcontact

Frequency range............................................ 0...5 kHzPulse length................................................... > 0.1 msInput resistance.............................................. 1 kΩTrig level, signal............................................. < 1.2 mA, > 2.1 mATrig level, cable fault...................................... < 0.1 mA, > 6.5 mA

Output specificationsRelay output: Max. switchingfrequency....................................................... 20 HzMax. voltage................................................... 250 VRMSMax. current................................................... 2 AACMax. AC power.............................................. 100 VAMax. load at 24 VDC...................................... 1 AOpto, NPN outputs: Max. switchingfrequency....................................................... 5 kHzMin. pulse length, NPN output....................... > 0.1 msMax. load, current / voltage............................ 80 mA / 30 VDCVoltage drop at 25 mA / 80mA.................................................................. < 0.75 VDC / < 2.5 VDC

ApprovalsEMC............................................................... EN 61326-1LVD................................................................ EN 61010-1PELV/SELV.................................................... IEC 364-4-41 and EN 60742ATEX.............................................................. DEMKO 99ATEX127186UL................................................................... UL 913, UL 508GOST R......................................................... YesGOST Ex........................................................ Yes

5202B-091013

Lerbakken 10 · DK-8410 Rønde Tel. +45 8637 2677 · Fax +45 8637 3085

www.prelectronics.dk

PRetrans 5104B

1- or 2-channel version

3- / 5-port 3.75 kVAC galvanic isolation

Loop supply > 17.1 V in Ex area

20 programmable measurement ranges

Universal supply by AC or DC

Application:

•Supplyvoltageandsafetybarrierfor2-wiretransmittersmountedinahazardousarea.

•Safetybarrierforanaloguecurrent/voltagesignalsfromahazardousarea.

•1:1orsignalconversionofanaloguecurrent/voltagesignals.

Technical characteristics:

•The20factory-calibratedmeasurementrangesinthe5104BcanbeselectedbytheinternalDIP-switcheswithouttheneedforrecalibration.Specialmeasurementrangescanbedelivered.

•PR5104Bisbasedonmicroprocessortechnologyforgainandoffset.Theanaloguesignalistransmittedataresponsetimeoflessthan25ms.

•Inputs,outputs,andsupplyarefloatingandgalvanicallyseparated.

•Theoutputcanbeconnectedeitherasanactivecurrent/voltagetransmitterorasa2-wiretransmitter.

Mounting / installation:

•MountedverticallyorhorizontallyonaDINrail.Bywayofthe2-channelversionupto84channelspermetrecanbemounted.

•NB:5104BisrecommendedasExbarrierfor5331D,5333D,5334B,5343B,6331B,6333B,and6334B.

Ex REPEATER / POWER SUPPLY

3-wire transmitter

Current, mA

Voltage

2-wire transmitter

Output

Supply

Supply

Supply

Supply

Output

Output

Output

5104BY104-UK(1017)

5104B

Order : 5104B

0…20 mA : A4…20 mA : B0…10 V : E2…10 V : FSpecial : X

Special : 00…20 mA : 14…20 mA : 20…1 V : 40.2…1 V : 50…10 V : 62…10 V : 7

Single : ADouble : B

Type Input Output Channels

Electrical specifications:

Specifications range:-20°Cto+60°CCommon specifications:Supplyvoltage,universal.................. 21.6...253VAC 50...60Hz or19.2...300VDCInternalconsumption........................ ≤2W(2channels)Max.consumption............................. ≤3W(2channels)Fuse................................................... 400mASB/250VACIsolationvoltage,test/operation...... 3.75kVAC/250VACSignal/noiseratio............................. Min.60dB(0...100kHz)Responsetime(0...90%,100...10%)... <25msCalibrationtemperature..................... 20...28°CAccuracy,thegreaterofthegeneralandbasicvalues:

Auxiliarysupply:Loopsupply(pin44...42and54...52). 28...17.1VDC/0...20mAMax.wiresize.......................................... 1x2.5mm2strandedwireScrewterminaltorsion....................... 0.5NmRelativehumidity............................... <95%RH(non-cond.)Dimensions(HxWxD)......................... 109x23.5x130mmDINrailtype....................................... DIN46277Protectiondegree.............................. IP20Weight............................................... 225gCurrent input:Measurementrange.......................... 0...20mAMin.measurementrange(span)........ 16mAMax.offset......................................... 20%ofmax.valueInputresistance................................. Nom.10Ω+PTC10 Ω

Voltage input:Measurementrange.......................... 0...10VDCMin.measurementrange(span)........ 8VDCMax.offset......................................... 20%ofmax.valueInputresistance................................. >2MΩCurrent output and 2-wire 4...20 mA output:Signalrange(span)............................ 0...20mAMin.signalrange(span).................... 16mAMax.offset......................................... 20%ofmax.valueLoad(max.)........................................ 20mA/600Ω/12VDCLoadstability..................................... ≤0.01%ofspan/100ΩCurrentlimit....................................... ≤28mAMax.externalloopsupply................. 29VDCEffectofexternalloopsupplyvoltagechange.................................. <0.005%ofspan/VVoltage output:Signalrange(span)............................ 0...1VDC/0...10VDCMin.signalrange(span).................... 0.8VDC/8VDCMax.offset......................................... 20%ofmax.valueLoad(min.)......................................... 500kΩEEx / I.S. approval:DEMKO99ATEX126013.................... II(1)GD [EExia]IICApplicableinzone............................ 0,1,2,20,21or22Ex / I.S. data: Um..................................................... :250VUo...................................................... :28VDCIo........................................................ :93mADCPo...................................................... :0.65WLo....................................................... :3mHCo...................................................... :0.08µF

UL,applicableinzone....................... IS,Cl.I,Div.1,Gr.A,B,C,D IS,Cl.I,zone0/1,Gr.IIC IS,Cl.II,Div.1Gr.E,F,G ULControlDrawingNo.............. 5104QU01Marine approval:DetNorskeVeritas,Ships&Offshore.. Stand.forCertific.No.2.4GOST R approval:VNIIFTRI,CertNo.............................. www.prelectronics.comObserved authority requirements: Standard:EMC2004/108/EC............................ EN61326-1LVD2006/95/EC................................ EN61010-1PELV/SELV......................................... IEC364-4-41 andEN60742ATEX94/9/EC.................................... EN50014,EN50020and EN50281-1-1UL...................................................... UL913,UL508

Of span=Ofthepresentlyselectedrange

Basic values

Temperaturecoefficient

Basicaccuracy

Inputtype

mA

Volt

≤±16µA

≤±8mV

≤±1.6µA/°C

≤±0.8mV/°C

General values

Temperaturecoefficient

Absoluteaccuracy

Inputtype

All ≤±0.1%ofspan ≤±0.01%ofspan/°C

EMCimmunityinfluence........................... <±0.5%ofspanExtendedEMCimmunity:NAMURNE21,Acriterion,burst.............. <±1%ofspan

SMartin
Highlight
SMartin
Highlight
SMartin
Highlight
SMartin
Highlight
SMartin
Text Box
5104B-B2B
SMartin
Line

Issued: Supersedes:

When the level drops, the micro switch is activated....

When it reaches the highest permissible point, the second regulator reacts....

pumping stops and the level begins to rise....

and pumping resumes.

66'66'20'43'66'66'66'66'66'

582 88 27582 88 28582 88 29582 88 30582 88 31582 88 32582 88 33582 88 34582 88 35

0.65 - 0.800.80 - 0.950.95 - 1.100.95 - 1.100.95 - 1.101.05 - 1.201.20 - 1.301.401.50

Min. oper. temp. 32°F (0°C) Max. oper. temp. 140°F (60°C) Max. applied voltage 250VAC/30VDCElec. cable size AWG 19/3Max. amperage - 16A @ 250VAC Resistive load - 16A @ 250VAC 5A @ 30VDCInductive load - 4A @ 250VACMax. angular displacement 60° Operating point - rising 37°Operating point - descending 17°

Specific Gravityof Liquid

CableLength

ENM-10Sensor Specifications

ENM-10Part Number

The simplest possible method for level control! A mechanical micro switch in a plastic casing, freely suspended at the desired height from its own cable. When the liquid level reaches the regulator, the casing will tilt and the mechanical switch will close or break the circuit, thereby starting or stopping a pump or actuating an alarm device. No wear, no maintenance! Use in sewage pumping stations, for ground water and drainage pumping - in fact, for most level control applications - the ENM-10 is the ideal solution.

The regulator casing is made of polypropylene and the cable is sheathed with a special PVC compound. The plastic components are welded and screwed together - adhesive is never used. Impurities and deposits will not adhere to the smooth casing.

This level regulator is available in different versions, depending upon the medium in which it is to be used. The standard model can be obtained with 20, 43 or 66 feet of cable for liquids with specific gravities between 0.95 and 1.10. For other specific gravities, the regulator is only available with 66 feet of cable. The regulator can withstand temperatures of 32°F to 140°F.

Flygt Monitoring DevicesENM-10 Liquid Level Sensors

6/94 6/90

SMartin
Rectangle
SMartin
Line

Issued: Supersedes:

In Figure 1, liquid level is below the lowest level sensor (FLS 1). All sensors are hanging straight in the wet well, therefore, the circuits in the sensor are not complete and no signal is being sent to the control. Both pumps are OFF.

In Figure 2, as the liquid level rises, FLS-1 tilts and the sensors mechanical micro-switch completes the circuit sending a signal to energize the control. At this point both pumps are still in the OFF mode.

In Figure 3, the liquid level has risen to a level that tilts level sensor #2, completing its circuit.

a) This signal to the control activates the contactor in the control which, in turn, starts the lead pump.

b) Level sensor #2 also at this time activates the alternator in the control which automatically selects the other pump to become the lead pump on the next start-up cycle. The alternation of the pumps as the "lead" pump serves two purposes:

1) The two pumps will accumulate approximately equal amounts of wear thus maximizing their useful life.

2) Allows for many more starts per hour as the starting frequency is divided between the two pumps.

If the capacity of the lead pump is greater than the inflow to the station, the liquid level will start to drop. The pump will continue to run (due to a holding circuit in the control) until the level drops below sensor #1. Sensor #1, on drawdown, acts as the low level shut-off. Pump OFF.

Figure 4 shows the sequence when the capacity of the lead pump is less than the inflow to the station. In this case, the liquid level will gain on the pump and rise to sensor #3 which will then send a signal to the main control starting the second or lag pump. If their combined capacity is greater than the inflow, both pumps will continue to operate (due to the holding circuit in the control) until the liquid level drops below the low level shut off sensor #1.

Figure 5 indicates a condition where the inflow to the station is greater than the combined capacity of both pumps. The liquid level will rise to the high level sensor

#4. When sensor #4 tilts, it will send a signal to an alarm system, normally an alarm bell or red alarm light. There are other options for alarm conditions such as alert by telephone, etc. The alarm system issues a warning that something has happened in the station that could result in an overflow condition. This could be a control problem, one or both pumps not operating, pumps not operating up to capacity, etc. Regardless of the cause, an alarm calls for immediate action.

For most installations, the low level shut-off sensor should be located approximately at the top of the pump volute. However, there are certain situations where maximum cooling may be required such as when pumping warm liquids; in certain cases with pumps that do not have cooling jackets; some large horsepower units, etc. Also in situations where the NPSH requires a liquid level that is above the pump volute. When in doubt, contact Flygt Application Engineering.

Flygt Monitoring DevicesENM-10 Liquid Level Sensors

6/94 6/90

Issued: Supersedes:

Fig. 2

Fig. 4

Fig. 5

Fig. 3

Fig. 1

FLS-1

FLS-2

FLS-3

FLS-4

Flygt Monitoring DevicesENM-10 Liquid Level Sensors

6/94 6/90

Issued: Supersedes:

Flygt Monitoring DevicesENM-10 Liquid Level Sensors

ENM-10 Level SensorConnected for Pump-Down

The Flygt ENM-10 Liquid Level Sensor can be utilized to monitor a "Pump Down" operation (as in a lift station application) or a "Pump UP" (filling) operation as may be required in certain industrial applications. The ENM-10 sensor cable contains three wires; Red, Black and White. The Red wire is common to both sequences. Using the Red and Black wires as the liquid level pilot circuit, the

ENM-10 will operate in the "Pump Down" mode, activating the pumps at a selected high liquid level and shut off at a selected low liquid level. Using the Red and White wires as the pilot circuit will activate the pumps in a "Pump UP" mode controlling the filling of a sump, tank etc. In this case the pumps are activated at a selected low level and shut off at a selected high level.

WHITE

24VPOWER IN

TO ENM-10CONTROL

WHITE CONDUCTOR TIED OFF & TAPED.

BLACKRED

PUMP OFF

PUMP ON

WHITE

24VPOWER IN

TO ENM-10CONTROL

BLACKRED

WHITE CONDUCTOR TIED OFF & TAPED.

ENM-10 Level SensorConnected for Filling

BLACKRED

PUMP ON

BLACKCONDUCTOR TIED OFF & TAPED.

WHITE

PUMP OFF

24VPOWER IN

TO ENM-10CONTROL

BLACKRED

BLACK CONDUCTOR TIED OFF & TAPED.

WHITE

24VPOWER IN

TO ENM-10CONTROL

The Flygt ENM-10 Liquid Level Sensoris not a "floating" device.

The On/Off pump operating sequence is performed by its submerged tilting action.

POSITION 1

POSITION 2

6/94 6/90

Issued: Supersedes:

Flygt Monitoring DevicesENM-10 Liquid Level Sensors

3/11 6/94

The liquid in which level regulation is practiced most frequently is water. Of the millions of regulators in use all over the world today, it is estimated that nine out of ten work in water.

The ENM-10 is virtually insensitive to many aggressive liquids with its body of polypropylene, a cord of PVC

0 = No affect, 1= Minor to Moderate Resistance and 2 = Non-Resistant.The density of a liquid determines the bouyancy of the regulator. The ENM-10 is made for seven different densities.

or NBR/PVC nitrile/PVC rubber and a protective sleeve of EPDM rubber.

The table shows how resistant the material is to different chemicals at two different temperatures. The classification is broken down into three categories:

Chemical Resistance List

CHEMICAL RESISTANCE LIST

0 = No affect, 1 = Minor to moderate, 2 = Severe affect. — = No information available.

The liquid in which level regulation is practiced most frequently is, of course, water. Of the millions of regu-lators in use all over the world today, it is estimated that nine out of ten work in water.However, with a float body of polypropylene, a cable of PVC or NBR/PVC nitrile/PVC rubber and a ben-ding relief of EPDM rubber, the ENM-10 is virtually insensitive to many aggressive liquids.The table shows how resistant the ENM-10 equipped with either PVC or NBR/PVC nitrile/PVC rubber cable, is to different chemicals at two different temperatures.

The classification is broken down into the followingcategories:0 = No effect, 1 = Minor to moderate and 2 = Severe effect. The sign — means that information is not avai-lable.Keep in mind also that the density of the liquid deter-mines the bouyancy of the regulator. The ENM-10 is made for seven different densities. See page 2.

PVC cable NBR/PVC PVC cable NBR/PVC PVC cable NBR/PVC nitrile/PVC nitrile/PVC Solvents and nitrile/PVCAcids rubber cable Salts rubber cable miscellaneous rubber cable

20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C (68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F)

Acetic Acid 50% 1 2 0 0Acetic Acid 75% 2 2 0 0Benzoic Acid 2 2 0 0Boric Acid 5% 0 — 0 0Butyric Acid 2 2 2 2

Chromic Acid 10% 0 2 2 2Citric Acid 0 1 0 0HydrobromicAcid 5% 1 2 0 0HydrochloricAcid 10% 0 1 0 1HydrochloricAcid 37% 1 2 0 2

Hydrocyanic Acid 10% 0 0 1 2Hydrofluori Acid 5% 0 2 0 1Hypochloric Acid 1 2 2 2Maleic Acid 2 2 2 2Nitric Acid 5% 1 1 1 1

Nitric Acid 65% 2 2 2 2Oleic Acid 1 2 2 2Oxalic Acid 50% 1 1 1 2Phosphoric Acid 25% 0 0 1 2Phosphoric Acid 85% 0 0 1 2

Sulphuric Acid 10% 1 2 1 2Sulphuric Acid 78% 2 2 2 2Tannic Acid 0 0 0 0Tartaric Acid 1 1 1 1

Bases

Ammonium Hydroxide 0 — 0 0Calcium Hydroxide 0 0 0 0Potassium Hydroxide 1 2 0 0Sodium Hydroxide 1 2 0 0

Aluminium Chloride 0 0 0 0Calcium Sulphate 0 0 0 0Calcium Chloride 0 0 0 0Calcium Nitrate 0 0 0 0Copper Chloride 0 0 0 0

Copper Sulphate 0 0 0 0Ferric Chloride 0 0 0 0Ferrous Sulphate 0 0 0 0Magnesium Chloride 0 0 0 0Potassium Sulphate 0 0 0 0

Potassium Nitrate 0 0 0 0Potassium Carbonate 1 1 1 1Potassium Bicarbonate 0 0 0 0

Sodium Sulphate 0 0 0 0Sodium Chloride 0 0 0 0Sodium Nitrate 0 0 0 0Sodium Bicarbonate 0 0 0 0Sodium Carbonate 0 0 0 0

Tin Chloride 1 1 1 1Zinc Sulphate 0 0 0 0Zinc Chloride 0 0 0 0

Oils

Castor Oil 1 1 1 1Cocoanut Oil 0 — 0 2Corn Oil 2 2 2 2Diesel Oil 2 2 2 2

Linseed Oil 2 2 2 2Mineral Oils 2 2 2 2Olive Oil 1 1 1 1Silicone Oils 0 0 0 0

Aceton 2 2 2 2Aniline 2 2 1 2Benzene 2 2 2 2Butyl Alcohol 2 2 0 1Carbon Tetrachloride 2 2 2 2

Chlorobenzene 2 2 2 2Chloroform 2 2 2 2Ethyl Alcohol 2 2 0 1Ethyl Ether 2 2 2 2Ethyl Acetate 2 2 2 2

Ethylene Dichloride 2 2 2 2Ethylene Chloride 2 2 2 2Formaldehyde 37% 1 2 0 0Gasoline 2 2 2 2Kerosene 2 2 2 2

Methyl Alcohol 2 2 0 0Methyl Ethyl Ketone 2 2 2 2Methylene Chloride 2 2 2 2Nitrobenzene 2 2 2 2Phenol 2 2 2 2

Toluene 2 2 2 2Trichlorethylene 2 2 2 2Turpentine 2 2 2 2Xylene 2 2 2 2

Gases

Carbon Dioxide 0 0 0 0Carbon Monoxide 0 0 0 0Chlorine (wet) 2 2 2 2Hydrogen Sulphide 0 0 1 1Sulphur Dioxide (wet) 1 1 2 2

Always observe local regulations: Take particular note of: • risk of fire/explosio• hygiene requirements

Data Sheet Expert™ Hydrostatic Level Transmitters

US 2.75 Expert 081110

MJK Expert™ 3400 Level Transmitter is de-signed for use in waterworks, sewage treatment plants and industrial applications where accurate and long term stable level measuring is required. It is very robust and designed for applications in rough environments with aggressive chemicals and aggressive fluids.

A major design feature is the programming facil-ity. With a standard USB interface and a laptop computer, the servicing transmitter can be programmed on-the-fly to the required measur-ing range.

Specifications MJK Expert™ 3400 Hydrostatic Level Transmitter

Nominal measuring range 0 - 1 ft. 0 - 3 ft. 0 - 10 ft. 0 - 30 ft. 0 - 100 ft. 0 - 300 ft. 0 - 1000 ft.

Measuring principle Ceramic capacitive, relative pressure

Min. programmable range 0 -.9 ft. 0 -.9 ft. 0 - 3 ft. 0 - 9' 0 - 30' 0 - 90' 0 - 300'

Max. programmable range 0 - 3 ft. 0 - 3 ft. 0 - 10' 0 - 30' 0 - 100' 0 - 300' 0 - 1000'

Max. overpressure 75 psi 75 psi 100 psi 150 psi 275 psi 600 psi 600 psi

Temperature range -5 °F to 105 °F

Temp. deviation, zero point Better than ± 0.01 % / °F

Temperature deviation, FS Better than ± 0.005 % / °F

Linearity / Stability Better than ± 0.5 % FS / ± 0.5 % FS

Measurement accuracy Better than ± 0.1 % FS @ 50-85 °F, and better than ± 0.2 % FS @ full temp. range

Long time stability Better than ± 0.1 % FS per year

Materials Housing: PPS (Ryton), diaphragm: 99,9 % Al2O3, measurement cell packing: Viton®

Supply voltage 10 - 30 V DC (12 - 30 V DC for cable lengths above 315 ft.)

Output signal 2-wire 4 - 20 mA (passive transmitter)

Cable 2 × AWG 20 (pressure) + 5 x AWG 25 (data), shielded, PUR insulation

Cable length 39 ft. 39 ft. 39 ft. 39 ft. 114 ft. 314 ft. 1014 ft.

Enclosure NEMA 6P, withstands a static pressure equal to max. overpressure

Approvals UL® Class 1 Division 1 Group A-D, ATEX: II 2G EEx ia IIC T5/T6 andCE: EN61000-6-3/-4:2001, EN61000-6-1/-2:1999,EN50014:1997 E, EN50020:2002

➀ Can be delivered with other cable lengths on request.

2.4 in.

9.3

in.

Dimensions and Accessories

Cable bracket for MJK model 3400(1 pc. is delivered with each transmitter)

Order numbers

MJK Expert™ 3400 Level Transmitter

5.31 1.26

Dia.1.97

1” NP

T

5.31 1.42

Dia.1.97

MJK Expert™ 3400 Level Transmitter

Order Numbers

209921 Expert™ 3400, range 0 - 1 ft. WG 209928 Expert™ 3400, range 0 - 1000 ft. WG

209922 Expert™ 3400, range 0 - 3 ft. WG 209991 Expert™ 3400, range 0 - 1 ft. 1" NPT top

209923 Expert™ 3400, range 0 - 10 ft. WG 209992 Expert™ 3400, range 0 - 3 ft. 1" NPT top

209925 Expert™ 3400, range 0 - 30 ft. WG 209993 Expert™ 3400, range 0 - 10 ft. 1" NPT top

209926 Expert™ 3400, range 0 - 100 ft. WG 209996 Expert™ 3400, range 0 - 100 ft. 1" NPT top

209927 Expert™ 3400, range 0 - 300 ft. WG 202925 Expert™ 3400 w/ special meas. range

SMartin
Rectangle
SMartin
Rectangle
SMartin
Line

CATALOG CUBIC DESCR IPT ION PKG . STD. UPC

NUMBER IN . COLOR OUTLETS TY PE PK G . BAR CO DE

5320-0 17.5 Gray 3–1/2" Shr ink 20

5320-1 17.5 Whi te 3–1/2" Shr ink 20

5320-2 17.5 Bronze 3–1/2" Shr ink 20

5320-5 17.5 Gray 3–1/2" Carded 6

5320-6 17.5 Whi te 3–1/2" Carded 6

5320-7 17.5 Bronze 3–1/2" Carded 6

5324-0 17.0 Gray 3–3/4" Shr ink 20

5324-5 17.0 Gray 3–3/4" Carded 6

SINGLE-GANG BOXES

DIE CAST ALUMINUM

ORDERING INFORMATION - DIMENSIONS

Applications

• For use in branch circuit wiring

in wet, damp, or dry locations

• May be used as a weatherproof

junction box, or as a housing for

receptacles, switches, and GFCI’s

Product Features

• Reinforced connector outlets

• State-of-the-art powder coat finish

• Eight box mounting options with

detachable lugs provided

• Two closure plugs included

• Ground screw installed

• Multi-lingual instructions

in each package

Compliances

• – Standard 514A

• – C22.2 No. 18

• NEMA 3R Rated

®

®

SINGLE-GANG BOXES: GENERAL DIMENSIONS

END VIEW

ONE OUTLET

END VIEW

TWO OUTLETS

5320-0 TO 5320-7

5324-0 TO 5324-5

5321-0 TO

5321-7, 5330-0 5322-0, 5331-0

5323-0, 5332-0

2 " D E E P, W I T H L U G S – T H R E E T H R E A D E D O U T L E T S – 4 - 1 / 2 " x 2 - 3 / 4 "

CATALOG CUBIC DESCR IPT ION PKG . STD. UPC

NUMBER IN . COLOR OUTLETS TY PE PK G . BAR COD E

5321-0 17.0 Gray 4–1/2" Shr ink 20

5321-1 17.0 Whi te 4–1/2" Shr ink 20

5321-2 17.0 Bronze 4–1/2" Shr ink 20

5321-5 17.0 Gray 4–1/2" Carded 6

5321-6 17.0 Whi te 4–1/2" Carded 6

5321-7 17.0 Bronze 4–1/2" Carded 6

5330-0 16.5 Gray 4–3/4" Shr ink 20

2 " D E E P, W I T H L U G S – F O U R T H R E A D E D O U T L E T S – 4 - 1 / 2 " x 2 - 3 / 4 "

CATALOG CUBIC DESCR IPT ION PKG . STD. UPC

NUMBER IN . COLOR OUTLETS TY PE PK G . BAR CO DE

5322-0 16.5 Gray 5–1/2" Shr ink 20

5331-0 16.0 Gray 5–3/4" Shr ink 20

5323-0 17.0 Gray 5–1/2" Shr ink 20

5332-0 16.5 Gray 5–3/4" Shr ink 20

2 " D E E P, W I T H L U G S – F I V E T H R E A D E D O U T L E T S – 4 - 1 / 2 " x 2 - 3 / 4 "

CATALOG CUBIC DESCR IPT ION PKG . STD. UPC

NUMBER IN . COLOR OUTLETS TYPE PKG . BAR CODE

5385-0 21.3 Gray 3–1/ 2 " Shr ink 15

5386-0 21.3 Gray 3–3/ 4 " Shr ink 15

5387-0 21.3 Gray 3–1" Shr ink 15

2 - 5 / 8 " D E E P, W I T H L U G S – T H R E E T H R E A D E D O U T L E T S – 4 - 1 / 2 " x 2 - 3 / 4 "

5385-0 TO 5387-0

D5W

EATH

ER

PR

OO

F B

OX

ES,

CO

VE

RS A

ND

LIG

HTIN

G

SMartin
Rectangle
SMartin
Line

www.taymac.com 12

M E T A L L O W P R O F I L E I N - U S E C O V E R SSuperior Commercial Quality Die-Cast Metal Construction

Patented Quick-Fit™ Keyhole Mounting System Allows

Installation in Under a Minute

TAYMAC ITEM # UPC NUMBER DESCRIPTION DEPTH COLOR SHELF PACK SHELF PACK WEIGHT (LBS)

Metal Low Profile In-Use CoversMX4280S 0-92326-10128-8 Vertical 8-in-1 2” Grayy 6 4.75

MX4280WH 0-92326-11740-1 Vertical 8-in-1 2” White 6 4.75

MX4280Z 0-92326-11739-5 Vertical 8-in-1 2” Bronze 6 4.75

MX4380S 0-92326-10134-9 Horizontal 8-in-1 2” yGray 3 2.53

MX5280S 0-92326-10135-6 Vertical Deep 8-in-1 2.5” Grayy 2 1.80

MX7280S 0-92326-10137-0 Vertical 2-Gang 55-in-1 2” yGray 2 2.35

Patented Universal-Fit™ Technology

Mounting Hardware, Gasket and Installation InstructionsIncluded

Meets or Exceeds Extra Duty Specifications

Lockable Open or Closed

& 2011 NEC® Compliant

3R Compliant

Multiple combinations of duplex, GFCI, switch, and rounds: 1 1/4", 1 3/8", 1 9/16", 1 5/8", 1 11/16", 2 1/8", 2 1/4", 2 7/16"

+ + ++= =+

Switch 1 1/4" 1 3/8" 1 9/16" & 1 5/8" 1 11/16" 2 1/8"

WithoutAdaptor2 1/4"

=Adapter

(Included)DuplexGFCI

+ += orAdapter

(Included)

DuplexGFCI Switch 1 3/8" 1 9/16"& 1 5/8"

1 11/16" 2 1/8"1 1/4"Adapter

(Included)Adapter

(Included)

or

WithoutAdaptor2 1/4"

DuplexGFCI Switch 1 3/8" 1 9/16"& 1 5/8"

1 11/16" 2 1/8"1 1/4"Adapter

(Included)Adapter

(Included)

or

WithoutAdaptor2 1/4"

Meets or Exceeds EXTRA-DUTY SSpecifications!

SMartin
Rectangle
SMartin
Line
SMartin
Rectangle

Section 5 Warranty and Service

WARRANTY XYLEM WATER SOLUTIONS USA, INC.

For the period defined, XYLEM WATER SOLUTIONS USA, INC. offers a commercial warranty to the original End Purchaser against defects in workmanship and material on Flygt Products. Warranty covers Flygt parts and labor as outlined in ADDENDUM – A.

COVERAGE: XYLEM WATER SOLUTIONS USA, INC. will pay the cost of parts and labor during the warranty period, provided that the Flygt product, with cable attached, is returned prepaid to an XYLEM WATER SOLUTIONS USA, INC. Authorized Service Facility for Flygt Product repairs. Coverage for Flygt parts and labor will be provided for the period shown in ADDENDUM - A. The warranty period will begin from date of shipment or date of a valid Start-up (For permanently installed pumps only). In cases where the Start-up date is used as the beginning of the warranty on a permanently installed Flygt pump, a Start-up Report completed by an approved service technician from an XYLEM WATER SOLUTIONS USA, INC. Authorized Service Facility for Flygt products must be received by the XYLEM WATER SOLUTIONS USA, INC. Area Service Manager for Flygt Products within thirty (30) days of the initial onset of the unit placed into service. If not received, the beginning of the warranty coverage will default to the Flygt product ship date. A Start-up for a permanently installed Flygt pump must occur within one (1) year from the date of shipment from an XYLEM WATER SOLUTIONS USA, INC. authorized facility for Flygt Products or warranty will automatically default to ship date as start of warranty. (See STORAGE section) When using the start-up date as the beginning of the warranty, a copy of the Start-up Report will be required to support any Warranty Claims. Warranty on Flygt Dewatering pumps will begin with ship date only. No other date on Flygt Dewatering pumps will be considered. XYLEM WATER SOLUTIONS USA, INC.’S sole obligation under this Warranty for Flygt Products shall be to replace, repair or grant credit for Flygt Products upon XYLEM WATER SOLUTIONS USA, INC.’S exclusive determination that the Flygt Product does not conform to the above warranty. In the event that the Flygt product is replaced, warranty on the replacement product will be equal to the balance remaining on the original product or ninety (90) days, whichever is greater. MISUSE: This Warranty shall not apply to any Flygt product or part of Flygt product which (i) has been subjected to misuse, misapplication, accident, alteration, neglect, or physical damage (ii) has been installed, operated, used and/or maintained in a manner which is in an application that is contrary to XYLEM WATER SOLUTIONS USA, INC.’S printed instructions as it pertains to installation, operation and maintenance of Flygt Products, including but without limitation to (iii) operation of equipment without being connected to monitoring devices supplied with specific products for protection; or (iv) damaged due to a defective power supply, improper electrical protection, faulty installation or repair, ordinary wear and tear, corrosion or chemical attack, an act of God, an act of war or by an act of terrorism; or (v) has been damaged resulting from the use of accessory equipment not sold by XYLEM WATER SOLUTIONS USA, INC. or not approved by XYLEM WATER SOLUTIONS USA, INC. in connection with Flygt products. WEAR PARTS: This warranty does not cover costs for standard and/or scheduled maintenance performed, nor does it cover Flygt parts that, by virtue of their operation, require replacement through normal wear (aka: Wear Parts), unless a defect in material or workmanship can be determined by XYLEM WATER SOLUTIONS USA, INC.. Wear Parts are defined as Cutters, Cutting Plates, Impellers, Agitators, Diffusers, Wear Rings (Stationary or Rotating), Volutes (when used in an abrasive environment), oil, grease, cooling fluids and/or any items deemed necessary to perform and meet the requirements of normal maintenance on all Flygt equipment.

WARRANTY XYLEM WATER SOLUTIONS USA, INC.

DISCLAIMERS: (i) XYLEM WATER SOLUTIONS USA, INC.’S warranties are null and void when Flygt Products are exported outside of the United States of America without the knowledge and written consent of XYLEM WATER SOLUTIONS USA, INC. U.S.A., INC.; (ii) XYLEM WATER SOLUTIONS USA, INC. makes no independent warranty or representation with respect to parts or products manufactured by others and provided by XYLEM WATER SOLUTIONS USA, INC. (however, XYLEM WATER SOLUTIONS USA, INC. will extend to the Purchaser any warranty received from XYLEM WATER SOLUTIONS USA, INC.’S supplier for such parts or products).

LIMITATIONS: XYLEM WATER SOLUTIONS USA, INC. NEITHER ASSUMES, NOR AUTHORIZES ANY PERSON OR COMPANY TO ASSUME FOR XYLEM WATER SOLUTIONS USA, INC., ANY OTHER OBLIGATION IN CONNECTION WITH THE SALE OF ITS FLYGT EQUIPMENT. ANY ENLARGEMENT OR MODIFICATION OF THIS WARRANTY BY A FLYGT PRODUCT DISTRIBUTOR, OR OTHER SELLING AGENT SHALL BECOME THE EXCLUSIVE RESPONSIBILITY OF SUCH ENTITY. THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY AND ALL OTHER EXPRESS OR IMPLIED WARRANTIES, GUARANTEES, CONDITIONS OR TERMS OF WHATEVER NATURE RELATING TO FLYGT PRODUCT(S), INCLUDING AND WITHOUT LIMITATION ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH ARE HEREBY EXPRESSLY DISCLAIMED AND EXCLUDED. PURCHASER’S EXCLUSIVE REMEDY AND XYLEM WATER SOLUTIONS USA, INC.’S AGGREGATE LIABILITY FOR BREACH OF ANY OF THE FOREGOING WARRANTIES IS LIMITED TO REPAIRING OR REPLACING FLYGT PRODUCTS AND SHALL IN ALL CASES BE LIMITED TO THE AMOUNT PAID BY THE PURCHASER HEREUNDER. IN NO EVENT IS XYLEM WATER SOLUTIONS USA, INC. LIABLE FOR ANY OTHER FORM OF DAMAGES, WHETHER DIRECT, INDIRECT, LIQUIDATED, INCIDENTAL, CONSEQUENTIAL, PUNITIVE, EXEMPLARY OR SPECIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE, LOSS OF PROFIT, LOSS OF ANTICIPATED SAVINGS OR REVENUE, LOSS OF INCOME, LOSS OF BUSINESS, LOSS OF PRODUCTION, LOSS OF OPPORTUNITY OR LOSS OF REPUTATION.

XYLEM WATER SOLUTIONS USA, INC. WILL NOT BE HELD RESPONSIBLE FOR TRAVEL EXPENSES, RENTED EQUIPMENT, OUTSIDE CONTRACTOR'S FEES, OR ANY EXPENSES ASSOCIATED WITH A FLYGT PRODUCT REPAIR SHOP NOT AUTHORIZED BY XYLEM WATER SOLUTIONS USA, INC. U.S.A., INC. REIMBURSEMENT COSTS FOR CRANES AND/OR ANY SPECIAL EQUIPMENT USED IN CONJUNCTION FOR THE REMOVAL AND/OR REINSTALLATION OF ANY FLYGT EQUIPMENT IS NOT COVERED UNDER THIS WARRANTY.

ANY UNAUTHORIZED ALTERATIONS TO SUPPLIED FLYGT EQUIPMENT USED WITHOUT XYLEM WATER SOLUTIONS USA, INC. SUPPLIED FLYGT BRAND CABLE OR CONTROLS WILL NOT BE COVERED UNDER THIS WARRANTY, UNLESS IT CAN BE PROVEN SUCH ANCILLARY EQUIPMENT IS SUITABLE FOR THE PURPOSE AND EQUAL TO XYLEM WATER SOLUTIONS USA, INC. SUPPLIED FLYGT BRAND CABLES OR CONTROLS THAT WOULD ORIGINALLY HAVE BEEN SUPPLIED WITH THE TYPE OF EQUIPMENT IN USE.

REQUIREMENTS: A copy of Electrical System Schematics of the Control used (including a Control’s Bill of Material) could be required to support a Warranty Claim when a non Flygt Brand Control is used. In addition, a written record, hereby known as “the log”, will be associated with each unit serial number and must be maintained by the organization having product maintenance responsibility. The log must record each preventative maintenance activity and any repair activity during the life of the warranty or verification that an XYLEM WATER SOLUTIONS USA, INC. authorized Service Contract for Flygt Products is in force and must be available for review and/or auditing. Failure to meet these conditions could render this warrant null and void. Such logs could be required to determine warranty coverage.

WARRANTY XYLEM WATER SOLUTIONS USA, INC.

STORAGE: Should a delay occur between ship date and the date of start-up, maintenance as outlined in XYLEM WATER SOLUTIONS USA, INC.’S Care & Maintenance Manual for Flygt Products must be performed by the “CONTRACTOR” and/or “OWNER” during any such period of storage. Documentation providing proof and outlining what maintenance was performed must be provided to XYLEM WATER SOLUTIONS USA, INC. or its Flygt Products representative within thirty (30) days of said maintenance, or the XYLEM WATER SOLUTIONS USA, INC. warranty for Flygt Products could be considered void.

CONTROLS: Warranty coverage for permanently installed controls will start for the end purchaser on the date of shipment.. This warranty does not apply to controls that have been damaged due to a defective and/or improper input power supply, improper electrical protection, accidental damage, improper or unauthorized installation and/or repair, unauthorized alteration, negligence, environmental corrosion or chemical attack, improper maintenance or storage of control, any act of God, an act of war, an act of terrorism or damage resulting from the use of accessory equipment not approved by XYLEM WATER SOLUTIONS USA, INC.. Further, this warranty does not apply in the event an adjustment is found to correct the alleged defect.

Solid state devices will be covered for a period of one (1) year. Electrical control panels containing controllers, PLC’s, drives, soft starts, and other computerized equipment will require Transient Voltage Surge Suppression (TVSS) protection in order to satisfy the requirements of this warranty. The protection equipment associated with the control must be kept in working condition during the life of the warranty. Auxiliary equipment supplied with the control (air-conditioners etc.) is limited by the respective original equipment manufacturer’s warranty offered. Consumable items such as: light bulbs, fuses, and relays are covered under normal operating conditions. Electrical surges experienced during startups and/or during normal operating use of the control panel will cause the consumable items not to be covered under this warranty policy. Components not supplied by XYLEM WATER SOLUTIONS USA, INC. will not covered by this warranty.

TOP (The Optimum Pump Station) XYLEM WATER SOLUTIONS USA, INC. will warrant the Flygt TOP pre-engineered fiberglass pump station components against defects in material and workmanship for a period of one (1) year from date of start-up or eighteen (18) months from date of shipment and is valid only to the original owner of the station. Warranty shall cover the cost of labor and materials required to correct any warrantable defect, excluding any removal and reinstallation costs, FOB XYLEM WATER SOLUTIONS USA, INC.’S authorized warranty service location for Flygt’s TOP.

Flygt Products contained within a TOP pre-engineered fiberglass pump station will carry the standard XYLEM WATER SOLUTIONS USA, INC. warranty for Flygt products and/or accessories installed in the TOP pre-engineered fiberglass pump station.

All Flygt Product restrictions and/or limitations as outlined and described within the context of this warranty are germane to all sections of this XYLEM WATER SOLUTIONS USA, INC. Warranty document.

XYLEM WATER SOLUTIONS USA, INC. US

WARRANTYXYLEM WATER SOLUTIONS USA, INC.

Ver 8 -120909

ADDENDUM A – WARRANTY COVERAGE BY PRODUCT

Months Months Months Months MonthsPRODUCT PRODUCT SERIES AND CONFIGURATION

1 - 12 13 - 18 19 - 36 37 - 39 40 - 60

Axial Flow/ Mixed Flow/ Centrifugal Pumps & Mixers3000 Series (NP

100% 50% 25%

Electrical Control Panels (permanently installed) Xylem Manufactured Control Panels - 3 - Years 100% - 1 YR LIMITED - 2 - YR

Abrasion/Corrosion Resistant & Chopper/ Grinder Pumps3000 Series (MP, MF, MH, FS, FP, HP, HS)5000 Series (HP, HS)8000.280 Series (DP, DZ, DT, DS, DF)

100%

Dewatering Pumps2000 Series (BS, KS)3000 Series (CS, NS, DS)8000.280 Series (DS, DF)

100% (From Ship Date)

TOPS Fiberglass Pump Station 100% (From Ship Date)

Accessories Permanent / Portable100%

(From ShipDate)

Hydro ejectors/ Aerators HE, JA 100%

Portable Pump Controls Control Boxes (Nolta, MSHA etc,)100%

(From ShipDate)

Small Pumps 3045, 3057, SX100%

(From ShipDate)

Parts - * All new spare parts100%

(From ShipDate)

* - Parts that fail where used in a repair are warranted for one (1) year from the date of the repair for the failed part only – no labor.

lpheatt
Rectangle
lpheatt
Rectangle

Corporate Headquarters

Xylem Water Solutions USA, Inc.Flygt/WEDECO Products14125 South Bridge CircleCharlotte, NC 28273 Tel. (704) 409-9700Fax.(704) 295-9080

[email protected]://www.xyleminc.com

To find a Flygt product sales office near you, visit:

http://www.xyleminc.com

Xylem Water Solutions USA, Inc.

Flygt Product Direct Sales Offices

LPheatt
Oval
lpheatt
Rectangle

Flygt Product Direct Sales Offices

California:

Xylem Water Solutions USA, Inc.790-A Chadbourne Road Fairfield, CA 94534-9643 Tel: (707) 422-9894 Fax: (707) 422-9808

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.11161 Harrel Street Mira Loma, CA 91752 Tel: (951) 332-3668 Fax: (951) 332-3679

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.13350 Gregg Street Suite 108 Poway, CA 92064Tel: (858) 679 9344Fax: (858) 679 9480

[email protected]://xyleminc.com

Connecticut:

Xylem Water Solutions USA, Inc.1000 Bridgeport Ave., Suite 402 Shelton, CT 06484 Tel: (203) 712-8999 Fax: (203) 712-8998

[email protected]://xyleminc.com

Florida:

Xylem Water Solutions USA, Inc.Florida, LLC2152 Sprint Blvd Apopka, FL 32703 Tel: (407) 880-2900 Fax: (407) 880-2962

[email protected]://xyleminc..com

Xylem Water Solutions USA, Inc.Florida, LLC1730 Tenth Street W Riviera Beach, FL 33404 Tel: (561) 848-1200 Fax: (561) 848-1299

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.Florida, LLC5771 Country Lakes Drive Ft. Myers, FL 33905 Tel: (239) 693-5226 Fax: (239) 693-1485

[email protected]://xyleminc.com

Georgia:

Xylem Water Solutions USA, Inc.124 Airport Park Drive Garden City, GA 31408 Tel: (912) 966-1577 Fax: (912) 966-1579

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.90 Horizon Drive Suwanee, GA 30024 Tel: (770) 932-4320 Fax: (770) 932-4321

[email protected]://xyleminc.com

Illinois:

Xylem Water Solutions USA, Inc.8402 West 183rd Street Suite ATinley Park, IL 60477 Tel: (708) 342-0484 Fax: (708) 342-0491

[email protected]://xyleminc.com

Indiana:

Xylem Water Solutions USA, Inc.Indiana, LLC7615 West New York St.Indianapolis, IN 46214 Tel: (317) 273-4470Fax: (317) 273-4480

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.Indiana, LLC950 Maxwell AvenueEvansville, IN 47711 Tel: (812) 421-2486Fax: (812) 421-4612

[email protected]://xyleminc.com

Kentucky:

Xylem Water Solutions USA, Inc.3865 Produce Road Suite 225 Louisville, KY 40218 Tel: (502) 969-0186 Fax: (502) 969-0576

[email protected]://xyleminc.com

Massachusetts:

Xylem Water Solutions USA, Inc.78K Olympia Avenue Woburn, MA 01801 Tel: (781) 935-6516 Fax: (781) 938-0364

[email protected]://xyleminc.com

New York:

Xylem Water Solutions USA, Inc.600 Mile Crossing Blvd Suite 3 Rochester, NY 14624 Tel: (585) 426-0280 Fax: (585) 426-3947

[email protected]://xyleminc.com

North Carolina:

Xylem Water Solutions USA, Inc.14125 South Bridge CircleCharlotte, NC 28273 Tel: (704) 504-8804 Fax: (704) 504 8773

[email protected]://xyleminc.com

Ohio:

Xylem Water Solutions USA, Inc.1615 State Route 131Milford, OH 45150Tel: (513) 831-7867 Fax: (513) 831-7868

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.121 Commerce Park DriveWesterville, OH 43082Tel: (513) 831-7867Fax: (614) 895-2646

[email protected]://xyleminc.com

Oregon:

Xylem Water Solutions USA, Inc.2630 North Marine Drive Portland, OR 97217 Tel: (503) 240-1980 Fax: (503) 240-3445

[email protected]://xyleminc.com

Pennsylvania:

Xylem Water Solutions USA, Inc.2330 Yellow Springs Road Malvern, PA 19355 Tel: (610) 647-6620 Fax: (610) 647-5563

[email protected]://xyleminc.com

Texas:

Xylem Water Solutions USA, Inc.2400 Tarpley Road Carrollton, TX 75006-2407 Tel: (972) 418-2400 Fax: (972) 416-9570

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.204 Industrial Boulevard Cedar Park, TX 78613 Tel: (512) 260-0281 Fax: (512) 260-0286

[email protected]://xyleminc.com

Xylem Water Solutions USA, Inc.1959 Saratoga Blvd, Bldg. 29 Corpus Christi, TX 78417 Tel: (361) 808-7867 Fax: (361) 225-2965

flygt_tx2@~xyleminc.comhttp://xyleminc.com

Xylem Water Solutions USA, Inc.17352 Bell North DriveSchertz, TX 78154 Tel: (210) 946-7867Fax: (210) 651-3057

[email protected]://xyleminc.com

Wisconsin:

Xylem Water Solutions USA, Inc.N27 W23291 Roundy Drive Pewaukee, WI 53072 Tel: (262) 544-1922 Fax: (262) 544-1399

[email protected]://xylemwin.com

LPheatt
Rectangle

SUBMERSIBLE PUMPS & MIXERS

Engineered for Life

Authorized Service & Sales Facility

for

Warranty & Non-Warranty Repair Work

To order service or parts or answer any questions, contact your local branch office:

XYLEM / FLYGT PRODUCTS

2630 North Marine Drive

Portland, OR 97217

PHONE: 503-240-1980

FAX: 503-240-3445

Replacement Parts Sales and Service: Dave Olson (Ext. 2902175) [email protected]

Sales Person: Simon Cartwright (Ext. 2902174)

[email protected] Andee Kramer (Ext. 2902170)

[email protected]

Application Engineer: Adam Sheehan (Ext. 2902176) [email protected]

Certified Factory Trained Technician: Saxon Williams (Ext. 2902180)

[email protected]