ethernet m-bus metering interface controller...3 after reboot the user has to re-access the emic as...

16
EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 1 Installation Instructions EMIC/MBA Ethernet M-BUS Metering Interface Controller Important: Retain these instructions These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com 1 Dimensions 3 INSTALLATION 1 BOX CONTENTS 2 STORING CONTENTS 1 Box Contents .................................................................1 2 Storing ...........................................................................1 3 InstallatioN.....................................................................1 3.1 Installation - Mounting ...................................................1 4 Cleaning and Maintenance .........................................16 5 Disposal .......................................................................16 3.1 INSTALLATION - MOUNTING HO 2 0 %RH 70 %RH 0 °C 32 °F +70 °C 158 °F EMIC EMIC/MDA Installation Instructions (TG201147) EMIC 100 mm (3.93”) 77 mm (3.03”) 88 mm (3.46”) 19 mm (0.75”) 26 mm (1.02”) 40 mm (1.57”) 108 mm (4.21”) 127 mm (5”) 25 mm (0.98”) It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

Upload: others

Post on 25-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 1

Installation Instructions

EMIC/MBAEthernet M-BUS Metering Interface Controller

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com

1 Dimensions

3 InSTAllATIon

1 Box ConTEnTS 2 SToRIng

ConTEnTS1 Box Contents .................................................................12 Storing ...........................................................................13 InstallatioN.....................................................................1

3.1 Installation - Mounting ...................................................14 Cleaning and Maintenance .........................................165 Disposal .......................................................................16

3.1 InSTAllATIon - MoUnTIng

H O2

0 %RH 70 %RH0 °C32 °F

+70 °C158 °F

EMIC

EMIC/MDAInstallation Instructions(TG201147)

EMIC

100 mm (3.93”)

77 mm (3.03”)

88 mm (3.46”) 19 mm (0.75”)26 mm (1.02”)

40 m

m (1

.57”

)

108

mm

(4.2

1”)

127

mm

(5”)

25 m

m (0

.98”

)

It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

Page 2: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

2 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

2 Mounting Requirements

2 Mounting Position

3.1 InSTAllATIon - MoUnTIng (continued)

EMIC

EMIC

EMIC

Option 1; on a flat surface

Option 2; on a DIN rail

EMIC

EMIC

either or

4 off Ø4 mm 2 off Ø7 mm

EMIC

4 off screws supplied

EMIC

EMIC

EMIC

H O2

0 90 %RH0 °C

32 °F+70 °C158 °F

Page 3: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 3

Installation Instructions EMIC/MBA

4 Connect Power Supply

5 Connect to Supervisor/Trend network over Ethernet

3.1 InSTAllATIon - MoUnTIng (continued)

24 VdcPower Supply

+24 Vdc

0 Vdc

+

-EMIC

2 part connector 2 screw terminals for 0.5 to 2.5 mm2 cross section area (20 to 14 AWG) cable

EMIC

Ethernet hub or switche.g: EDS205 5 port unmanaged switchavailable from Trend

either

or direct connect

RJ45

24 Vdc ± 15% regulated (300 mA @ 24 Vdc)

XCITE/XA crossover adaptor order separately (XCITE/XA/5 pack of 5)

standard Ethernetcable - see aboveweb browser only

(not 963)

standard Ethernet cableCat 5e twisted pair

RJ45RJ45 100 m (109 yds) max.

ensure correct polarity

The 24 Vdc supply must be floating (not earthed/grounded)

Page 4: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

4 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

6 Connect to Meters using RS232/M-Bus Converter

7 Switch on Power 6 Check Power lEDs

3.1 InSTAllATIon - MoUnTIng (continued)

O

I

EMIC

Beep!

check power

press resetbutton

(green)

(green)

▪ EMIC/MBA is master, meters are slaves. ▪ Trend TPW3/TPW20 converters have straight-through RS232 connections as shown. Some converters may require RX/

TX crossover. ▪ Use standard 2-wire telephone cable to wire the bus.

Note: Ensure meters are confi gured with Comms setting, as described in section 3.2 step 10.3. Each meter should be set up with a unique M-Bus primary address (slave address), as described in section 3.2 step 8.4.

M+ M+M- M-RXD

TXD

GND

RX

TX

GND

M+

M-

Pin 1 1 DSR 2 RTS 3 GND 4 TXD 5 RXD 6 DCD 7 CTS 8 DTR

EMIC

L BluOBlkR

RBlk

Gn

GnYBnGrey

Or

Signal Colour

Note that image above shows the fl at side of the RJ45 connector

RS232/M-BusConverter(e.g.TPW3)

Meter 1 Meter n

M-Bus

RJ45

RS232

(not used)cable supplied

(EJ107231)

RS232/M-BusConverter(e.g.TPW3)

Page 5: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 5

Installation Instructions EMIC/MBA

9 Connect Ethernet (if required)

10 Connect Universal Inputs (In1 to In3)

1 Connect Universal Inputs (IN1 to IN3)

3.1 InSTAllATIon - MoUnTIng (continued)

3.2 InSTAllATIon - ConfIgURIng

EMIC

check Ethernet connection

EMIC

1 2 3 4DIPON

check all poles set to off (default)

1 Connect supervisor/PC as in 3.1 step 5 above

2 Note PC must have fi xed IP address

3 Open internet browser, enter EMIC’s IP address/ (default = 192.168.1.227)

4 Enter the user name/password

Admin

password

User name: Admin (default)

Password: password (default)

Select ‘login’

(green)

Note that if the User name or Password have been forgotten a default password may be obtained from Trend Technical Support using the process described in the EMIC Engineering Manual (TE201084)

These instructions rely on the EMIC being set to defaults; if not the address and login may have to change, also if DHCP has been enabled the EMIC may have to be accessed by its hostname. EMIC IPTool (available from Trend Partnernet website) can be used if the IP address is unknown.

(green)(green)

Page 6: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

6 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

2 Set up language for web pages (if required to be changed from English)

3.2 InSTAllATIon - ConfIgURIng (continued)

1 Log on as in 3.2 step 1

2 Select language flags

3 Select language

4 Select Save to store selected language

Available languages are:English, German, Danish, Spanish, Finnish, French, Italian, Dutch, Polish, Russian, Swedish

Page 7: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 7

Installation Instructions EMIC/MBA

4 Set up Time and Date

3 Confi gure EMIC IP Settings (If required to be different from default)

3.2 InSTAllATIon - ConfIgURIng (continued)

1 Select Local IP Settings

continued on next page

Used to timestamp plots and alarms

1 Select Local IP Settings

2 Change settings

3 Set up browser

a. Host name: set up if DHCP enabled as in step e. (15 characters maximum).

b. IP address: changed to fi xed IP address on network where EMIC installed

c. Subnet mask: change to suit network where EMIC is installed

d. Default gateway: IP address of default router on same subnet as EMIC

e. DHCP enabled: select this if auto IP addressing (DHCP) required.

f. Select Set and reboot: save changes and restart EMIC

Enter the new IP address in browser as in 3.2 step 1.3 above (or set hostname if DHCP enabled) and enter user name and password as in 3.2 step 1.4 above

Beep!

4

Page 8: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

8 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

4 Set up Time and Date (continued)

5 Set up UDP group

3.2 InSTAllATIon - ConfIgURIng (continued)

If Trend system uses different group to 57612 (default) - used to build network

3 Select Time and Date

4 Set up Time and Date

a Set up UDP group

b Select Set and reboot

1 Select UDP Group

a Set time

b Set date

c Select Save

2 Set up UDP group

3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1

Page 9: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 9

Installation Instructions EMIC/MBA

6 Set up Virtual outstations

7 Set up gUIDs

3.2 InSTAllATIon - ConfIgURIng (continued)

Each meter is represented as a virtual outstation

1 Select Num.OSs / LAN number

2 Add outstation(s)

a. Enter outstation device address. This must be unique on the internetwork.

(range 1 to 119 excluding 2, 3, 10)

b. Select + to add the outstation.

c. Repeat a/b above to create an outstation for each meter

3 Set up Lan

a. Enter Lan number of this Lan. This must be unique on the internetwork.

(range 1 to 119 excluding 2, 3, 10)

b. Select Set to save value

a. Set up Human GUID and Machine GUID to be the same as the other Trend alarm producing devices (e.g. IQ3s, EMICs) on the site. If IQ3s also on site use GUIDs copied from SET.

b. Select Save to save values

1 Select GUID

2 Set up GUIDs

If sending IP alarms on a multi-site system

Page 10: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

10 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

8 Configure Meters.

3.2 InSTAllATIon - ConfIgURIng (continued)

1 Close down Network Configuration page

2 Select Meter configuration

3 Add a meter

4 Set up meter

a b c d* e* f*

a Select slave number, (primary address of meter on M-BUS, 1 to 249)

Note that the meter’s primary address may have to be set up. (e.g for Trend HMM all meters have primary address of 1 with secondary address printed on label; use utility software to access meter using secondary address and to change primary address).

b Select meter type (e.g. Trend HMM)

c Select virtual outstation as created in 3.2 step 5.2

d Set Identifier to download default*

e Set Labels to download default*

f Set Units to download default*

* settings d,e,f will automatically populate identifiers, labels, and sensors in virtual outstations

5. Repeat steps 3 and 4 for each meter, and then select Save to store settings

Page 11: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 11

Installation Instructions EMIC/MBA

9 Set up outstation

3.2 InSTAllATIon - ConfIgURIng (continued)

continued on next page

1 Select Network configuration

2 Select Outstation

3 Select Address module

Page 12: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

12 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

9 Set up outstations (continued)

3.2 InSTAllATIon - ConfIgURIng (continued)

continued on next page

a For Trend Lan Alarms: Ensure Use IP Alarms (unchecked) 1. Set Alarm Address (range 1 - 119 excluding 2,3,10) 2. Set Remote Lan (range 1 - 119 excluding 2,3,10)

b or For IP Alarms: Set Use IP Alarms (checked) 1. Set IP address (e.g; 192, 168, 125, 123) 2. Set Port number (e.g; 1003)

c Select Save to store settings

4 Set up address module If required to send alarms

5 Set up Sensors a Select Sensors

Page 13: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 13

Installation Instructions EMIC/MBA

10 Set up MoDBUS Comms Settings

9 Set up outstations (continued)

3.2 InSTAllATIon - ConfIgURIng (continued)

1 Close down Network configuration page

2 Select Comms settings

For communication with meters over MODBUS (RS485)

b Set up Sensor ParametersIf required to send alarms or plot sensors

1 2 3 4 5 6

1. Set High Alarm Limit as sensor value rises through this level it will trigger high alarm (if enabled)

2. Set Low Alarm Limit as sensor value falls below this level it will trigger low alarm if enabled)

3. Enable High Alarm

4. Enable Low Alarm

5. Enable sensor to be plotted (Note: maximum of 1024 plots per EMIC)

6. Set up plot interval - interval between storing values in a plot record

(Alternatively select ‘Set all’ to set all sensors to be plotted at same interval as set in interval box)

c. Repeat for each sensor as required and select Save to store settings

6 Repeat 3.2 steps 9.2 to 9.5 for each virtual outstation

continued on next page

Page 14: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

14 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

12 Confi gure Other Devices and Test System

11 Check MoDBUS lED

10 Set up MoDBUS Comms Settings (continued)

3.2 InSTAllATIon - ConfIgURIng (continued)

e.g.Outstation 1(meter 1) sensor 1 value = xx kwhEMIC

TCP/IP

Meter 1

Ethernet

Ethernet

Meter 2Note that each virtual outstation appears as an IQ3 to 963

EMIC(green)

(red)

(green)(yellow)

P1

EMIC Engineering Manual(TE201084), Appendix 2, Trouble Shooting

3 Set up Comms settings Set up to match meters; all meters must have same settings

Ensure these values are at default (see step 13):Port Number 1Port Type RS232Baud Rate 2400Polling Interval 15 minutes (see step13)Post-init delay None (see step 13)Zero values on comms failure Comms failure threshold 4

Select Save to store values

(red)

Page 15: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015. 15

Installation Instructions EMIC/MBA

14 Settings using Text Comms (as required)

13 Customise Settings (as required)

3.2 InSTAllATIon - ConfIgURIng (continued)

EMIC Engineering Manual(TE201084)

Section Parameter / function DescriptionCalculations Source Operands

OperationsDestinations

Set up calculations as described in manual for Cumulative kWh (3 calculations per meter).Set up additional calculations if required

Users (6 off) PIN numberPIN level

Authority >95 to access meter parameters

Trend Security (6 off) LAN numberOS address

Enable each PIN number in Users to access groups of networked devices

Admin (Change Password)

User namePassword

Authority to access EMIC web pages

Outstation Addressmode

Identifier Identifies Outstation - Defaults to meter type

Outstation Sensor Label Units

Label and units for each meter parameter

Comms Settings Timeout Default 150ms. Detects transmission to a non-existant meter

Zero values on Comms FailComms Fail Threshold

Allows values from meter to be zeroed on comms fail, and number of failed messages before comms failure declared to be setup.

Virtual Outstations DeleteDuplicate

Administering outstations

Meter Configuration Delete Administering MetersBackup/Restore Restore Restore backup file from PC to EMIC (e.g.if unit fails)

EMIC/MDA Data Sheet (TA201081)EMIC Engineering Manual (TE201084)

In addition Knob, Digital Input, Switch, Analogue node, and Binary node modules and their parameters can be set up using Text Communications (e.g using SET); these can be used in calculations. Digital input modules can be programmed to generate alarms.

Module/Parameter Text Comms Code DescriptionPlot (P1 to P99)BBUFnotification threshold

N Each plot module can have a notification threshold informing the supervisor by way of an event alarm that the data should be read.

Page 16: Ethernet M-BUS Metering Interface Controller...3 After reboot the user has to re-access the EMIC as per 3.2 step1, then re-enter network configuration as 3.2 step 3.1 EMIC/MBA Installation

16 EMIC/MBA Installation Instructions TG201147 Issue 4, 18-Dec-2015.

EMIC/MBA Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

TR CU Certification

15 Back up EMIC (To save EMIC configuration to a file on the PC in case of unit failure)

4 ClEAnIng AnD MAInTEnAnCEThere are no serviceable parts inside the unit.

1 Return to Main menu

2 Select Back up and restore

3 Select Back up

4 A dialogue box will be launched on your PC

The configuration file will be saved

3.2 InSTAllATIon - ConfIgURIng (continued)

5 DISPoSAl

WEEE Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.