Even Better than the Best Building Ever?The ZICER and Elizabeth Fry Low Energy Buildings
Keith Tovey M.A., PhD, CEng, MICEEnergy Science Director: Low Carbon Innovation Centre
School of Environmental Sciences
![Page 2: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/2.jpg)
Main Energy Conservation Projects at UEA
• Constable Terrace/ Nelson Court Student Residences
• Elizabeth Fry Building
• Combined Heat and Power
• School of Medicine
• ZICER Building
The Future
• Absorption Chilling
![Page 3: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/3.jpg)
The Elizabeth Fry Building
![Page 4: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/4.jpg)
The Elizabeth Fry Building
•Termodeck Construction
•Air is circulated through whole fabric of building
•Heated using a normal domestic heating boiler (24 kW)
•No heat supply needed at temperatures as cool as 9oC
•Triple glazing with Low Emissivity Glass ~ quadruple glazing
•180 mm insulated cavity
•300 mm roof insulation
•100 mm floor insulation
•Air – Pressure Test at 50 Pa – not to exceed 1.0 ach
• Actual performance 0.97 ach
• Has deteriorated slightly since 1996
• Uses regenerative Heat Exchangers 85% with heat recovery
![Page 5: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/5.jpg)
Fresh Air
Stale Air
Stale Air
Fresh Air
Operation of Regenerative Heat Exchangers
![Page 6: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/6.jpg)
Electricity Comsumption - Elzabeth Fry
0
20
40
60
80
100
120
140
Elizabeth Fry low average
kWh
/m2/y
rGas Consumption - Elizabeth Fry
0
50
100
150
200
250
Elizabeth Fry Low Average
kWh
/m2/y
r
Heating/Hot Water
0102030405060708090
1995 1996 1997
kW
h/m
2/yr
Hot Water
Space Heating
The performance of the building has improved with
time
Energy Consumption in Elizabeth Fry
Heating provided by domestic sized boilers.
Energy requirement 20% of good practice for Academic Buildings.
![Page 7: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/7.jpg)
44
96
ECON 19 Good PracticeType 3 Office
Elizabeth Fry
100
90
80
70
60
50
40
30
20
10
0
kg/m2/an
num
gas electricity
carbon dioxide emissions
thermal comfort +28%
air quality +36%
lighting +25%
noise +26%
Elizabeth Fry
User Satisfaction
An energy efficient building reduces carbon dioxide
AND
is a better building to work in.
Elizabeth Fry: Carbon Dioxide Emissions and User Satisfaction
![Page 8: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/8.jpg)
The ZICER Building
• Follows the tradition of the Elizabeth Fry Building
• Uses Termodeck construction
• Draws heat from University Heating Main
• Has a 34 kW array of Photo Voltaic cells on top floor and roof
Zuckerman Institute for Connective Environmental
Research
![Page 9: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/9.jpg)
ZICER Construction
![Page 10: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/10.jpg)
ZICER Construction
![Page 11: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/11.jpg)
ZICER Construction
Ducts in floor slab
![Page 12: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/12.jpg)
Installation of Solar Panels
![Page 13: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/13.jpg)
0
10
20
30
40
50
Eli
za
be
thF
ry (
Ne
w)
Eli
za
be
thF
ry (
20
02
)
ZIC
ER
kg
CO
2/m
2/y
r
gas
electricity
Elizabeth Fry performance has improved over years. ZICER will be better and less than 70% of emissions of mid 90’s best practice building
Photovoltaic cells will generate ~ 30 kW and save 20 tonnes CO2 per annum.
Projected Performance of ZICER
![Page 14: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/14.jpg)
Variation of Carbon Emission and Carbon Index with Building Regulations
0
10
20
30
40
50
60
70
0 1 2 3 4 5 6 7 8 9 10
Carbon Index
kg
CO
2/m
2 /yr
1976
19901985
2002
1994
Elizabeth FryZICER
Theorectical Perfection in 2002 Regulations
pre-war
1955
1965
Variation of Carbon Emission and Carbon Index problems with current Building Regulations
0
2
4
6
8
10
12
14
16
18
20
7 8 9 10
Carbon Indexk
g C
O2/
m2 /y
r 2002
Elizabeth FryZICER
Theorectical Perfection in 2002 Regulations
Performance of Elizabeth Fry and ZICER
![Page 15: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/15.jpg)
UEA Combined Heat and Power Scheme
![Page 16: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/16.jpg)
UEA CHP Scheme
• Until 1999 most heat for space heating was supplied by large boilers
• Primary main temperature ~ 110 – 120oC
• All electricity imported
• Energy bill was in excess of £1 million per year
• Three 1 MWe generators are now installed
• Provide the majority of the electricity for the campus
• Export electricity at periods of low demand
• Waste heat is used a primary heat source
• Supplemented by existing boilers
• CHP has reduced that figure by £400 000 per year
![Page 17: Even Better than the Best Building Ever? The ZICER and Elizabeth Fry Low Energy Buildings Keith Tovey M.A., PhD, CEng, MICE Energy Science Director: Low](https://reader035.vdocument.in/reader035/viewer/2022062714/56649d2a5503460f949feffb/html5/thumbnails/17.jpg)
CHP Review
839015101.79.26537.68555.0tonnes 0.2770.1860.43kg/kWh 331503514815819895328kWh1997/98balloons totaloilgaselectricity
571010278.0255.55256.92698.90.02486.7-420.1 tonnes
0.2770.1860.186 0.43-0.43 kg/ kWh
922563282630771451007815630431578310097700020436531kWh1999/00
balloonstotaloilCHPboilersGener-ationimportexportelectricity
Saving in CO2 emissions as a result of CHP - 4824 tonnes CO2 or 31.9%
Equivalent to 2680 hot air balloons.
[Note: UEA expanded during time and consumption increased so CO2 savings are really higher than this].