3 1 - Distance protection 2 - Three-phase power swing unit 3 - Directional earth fault protection 4 - AC supervision circuits 5 - DC supervision circuits 6 - STUB protection 7 - Auxiliary relays 8 - Fault locator 9 - (Printer for fault locator) 10 - Disturbance recorder 11 - Signaling unit 12 - Parts of event recorder 13 - Breaker failure protection - 1 CB 14 - Tripping relays 15 - Autoreclosing for one CB 16 - Synchrocheck for one CB 17 - Auxiliary transformers for disturbance recorder Two relay panels 600 mm x 650 mm x 2250 mm Functional Integration Functional IntegrationTRANSCRIPT
Evolution and Prospects ofEvolution and Prospects of
Relay Protection and Relay Protection and Automation SystemsAutomation Systems
Moderator:Janez V. Zakonjšek
2
SC B5 Colloquium, Madrid 2007SC B5 Colloquium, Madrid 2007
Preferential Subject 2 – “Acceptable Functional Integration in Substation P&C for Transmission Systems”
Question PS2-11Is any user already planning to employ the “two boxes per
bay” solution in transmission, or the “two boxes per substation” system?
Are there equipment available in the market? When can these solutions be adopted?
Which are the advantages and disadvantages or obstacles?How can these obstacles be overcome?
3
1
23
4 56 789
10
11 1213 14
1516
17
1 - Distance protection2 - Three-phase power swing unit3 - Directional earth fault protection4 - AC supervision circuits5 - DC supervision circuits6 - STUB protection7 - Auxiliary relays8 - Fault locator9 - (Printer for fault locator)10 - Disturbance recorder11 - Signaling unit12 - Parts of event recorder13 - Breaker failure protection - 1 CB14 - Tripping relays15 - Autoreclosing for one CB16 - Synchrocheck for one CB17 - Auxiliary transformers for disturbance recorder
Two relay panels 600 mm x 650 mm x 2250 mm
Functional IntegrationFunctional Integration
4
1
23
4 56 789
10
11 1213 14
1516
17
1 - Distance protection2 - Three-phase power swing unit3 - Directional earth fault protection4 - AC supervision circuits5 - DC supervision circuits6 - STUB protection7 - Auxiliary relays8 - Fault locator9 - (Printer for fault locator)10 - Disturbance recorder11 - Signaling unit12 - Parts of event recorder13 - Breaker failure protection - 1 CB14 - Tripping relays15 - Autoreclosing for one CB16 - Synchrocheck for one CB17 - Auxiliary transformers for disturbance recorder
Two relay panels 600 mm x 650 mm x 2250 mm
E
C
Functional Integration - 1994Functional Integration - 1994
5
1
23
4 56 789
10
11 1213 14
1516
17
1 - Distance protection2 - Three-phase power swing unit3 - Directional earth fault protection4 - AC supervision circuits5 - DC supervision circuits6 - STUB protection7 - Auxiliary relays8 - Fault locator9 - (Printer for fault locator)10 - Disturbance recorder11 - Signalling unit12 - Parts of event recorder13 - Breaker failure protection - 1 CB14 - Tripping relays15 - Autoreclosing for one CB16 - Synchrocheck for one CB17 - Auxiliary transformers for disturbance recorder
Two relay panels 600 mm x 650 mm x 2250 mm
E
C
++SELF SUPERVISIONSELF SUPERVISION
++COMMUNICATIONCOMMUNICATION
++++++++++
Functional Integration - 1994Functional Integration - 1994
11
And What Shall We Do Now?And What Shall We Do Now?RCC
IEC61850
IEC61850
i iii
12
And What Shall We Do Now?And What Shall We Do Now?RCC
IEC61850
IEC61850
i iii
13
And What Shall We Do Now?And What Shall We Do Now?RCC
IEC61850
IEC61850
i iii
Power
Power
14
No problem with problems
Power
Power
And What Shall We Do Now?And What Shall We Do Now?RCC
i iii