exemple calcul foc

Upload: flavian-gafia

Post on 26-Feb-2018

245 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/25/2019 Exemple Calcul Foc

    1/36

    EXAMPLE 1

    FIRE DESIGN OF AN UNPROTECTED BEAM USING GRAPHS

    This worked example covers the fire design of a hot-rolled IPE section forming part of

    floor structure of an office building. The beam is uniformly loaded and restrained against

    lateral torsional buckling by the presents of a concrete slab supported on the top flange.

    The beam is to be designed to achieve R! fire resistance without the use of fire

    protection material. In this worked example thermal actions are determined using "#$$%.

    Mechanical actions at normal temperature

    The characteristic value of the load is&

    The design value of the load is&

    The applied bending moment and shear force are given by&

    Design at normal temperature

    The IPE '$$ section is a (lass section in bending.

    Basic data

    Material properties"teel grade& " %)!

    *ield stress&fy + %)!

    ,mm

    #ensity&a + )/!$kgm0

    Loads

    Permanent action&gk +

    12/ k,m

    3ariable action& qk + )2/k,m

  • 7/25/2019 Exemple Calcul Foc

    2/36

    The section is checked at 45" at normal temperature. The concrete slab is assumed to

    provide full lateral restraint to the beam6 therefore2 lateral-torsional instability does notneed to be taken into account.

    7ending moment resistance&

    "hear resistance&

    "erviceability 5imit "tate&

    Design in the fire situation

    Mechanical actions for the fire design situation

    The reduction factor for the design load level is e8ual to&

  • 7/25/2019 Exemple Calcul Foc

    3/36

    9here the : factor is taken as :2 + $2' for office buildings

    The section factor for the hot-rolled section is taken from "#$$1. The box section factor

    for an unprotected beam exposed on three sides is e8ual to&

    The exposed perimeter is indicated by the dashed line on Figure 3.

    The shadow effect is considered by modifying the section factor as follows&

    Verification in the time domain

    The adaptation factor + $2) is used for an unprotected beam exposed to fire on three

    sides. The adaptation factor %+ 2$ is used for simply supported beam.

    The fire resistance can be checked using the design data reproduced in Figure 4.

    The degree of utili;ation for the beam is given by&

    The critical temperature is given by&

    The fire resistance period predicted using

  • 7/25/2019 Exemple Calcul Foc

    4/36

  • 7/25/2019 Exemple Calcul Foc

    5/36

    EXAMPLE 2

    FIRE DESI! "F A! #!PR"$E%$ED IPE SE%$I"! &EAM EXP"SED

    $" $'E S$A!DARD $IME $EMPERA$#RE %#RVE

    The worked example illustrates the fire design of a simply supported non-

    composite beam. The transfer of heat into the beam is evaluated using a step-by-

    step calculation procedure. The structural resistance of the member at elevated

    temperature is evaluated using the simple calculation model for members sub=ect

    to bending given in E,>>'--%.

    ? beam made of hot-rolled IPE section is a part of the floor structure of an office

    building. The beam is loaded uniformly and restrained against lateral torsional

    buckling by a concrete slab. The beam is design to achieve a fire resistance rating

    of R!.

    Partial safety factor @

    A2fi

    + 2$$

    The design of the beam cross section and verifications at normal temperature is run inExample .

    E(aluation of gas temperature

    The standard temperature-time curve is used for the gas temperature&

    E(aluation of )eam temperature

    The dotted line on Figure 3 indicates the perimeter that is assumed to be exposed to

    fire. The section factor is calculated as follows&

    The correction factor for the shadow effect ksh

    for IPE-sections is given as&

  • 7/25/2019 Exemple Calcul Foc

    6/36

    where the BAmVCb is calculated from the box surrounding the section as

    indicated by dashed line on Figure 3.

    The increase of temperature of the steel section is calculated using an

    incremental calculation procedure to determine the increase in steel temperature

    given in E,>>'--% by the following e8uation&

    Time interval Dt + ! sec is used in the temperature calculation.

    The net heat flux is&

    m is the emissivity of the carbon steel BFm + $2) - E,>>'--% G%.%C

    Fr r is the emissivity of the fire BFr + 2$ H E,>>--% G'.C

    is the configuration factor B + 2$ H E,>>--% G'.C

    Jcc is the coefficient of the heat transfer for use with the standard temperature

    time curve Bgiven in E,>>--% G'.%. as Jc + %!2$ 9BmKCC

    L is the "tephan 7olt;mann constant BL + !2M) $-/ 9BmK1CC

    The steel temperature-time curve of the section is shown in Table and

  • 7/25/2019 Exemple Calcul Foc

    7/36

    ,ote&

    The temperature of the steel beam can be evaluated from "#$$1.

  • 7/25/2019 Exemple Calcul Foc

    8/36

    (lassification of the section at elevated temperature&

  • 7/25/2019 Exemple Calcul Foc

    9/36

    The slenderness of the flange in compression is&

    The limit for (lass is >F.

  • 7/25/2019 Exemple Calcul Foc

    10/36

    The adaptation factor + $2) is used for an unprotected beam exposed to fire on

    three sides2 and the adaptation factor % + 2$ is used for a simply supported beam.

    The design moment resistance at temperature a + M1O( is given by&

    The design shear resistance is given by&

    The section is satisfactory in the fire design situation.

  • 7/25/2019 Exemple Calcul Foc

    11/36

    EXAMPLE *

    FIRE DESI! "F PR"$E%$ED IPE SE%$I"! &EAM

    EXP"SED $" PARAME$RI% FIRE %#RVE

    This worked illustrates the fire design of a simply supported non-composite beam. eat

    transfer into the section is calculated using the e8uation for protected members given in

    E,>>'--%2 which is evaluated using an iterative calculation procedure. The structural

    resistance is calculated using the simple calculation model for members in bending2given in E,>>'--%.

    ? steel beam forms part of a floor structure of an office building. The beam is uniformly

    load and restrained against lateral torsional buckling by a concrete slab. The beam is

    re8uired to achieve M$ minutes fire resistance and will be fire protected using sprayed

    vermiculite cement. The thermal actions will be determined using the parametric

    temperature - time curve.

    Data for fire calculation

    #ata for parametric fire curve&

    + !2)>1

    tmax + %% minutes

    x +

    Properties of fire protection material

    "prayed vermiculite cement

    thickness dp + $ mm

    densityp + !!$ kgm'

    specific heat cp + $$ QkgK

    thermal conductivityp + $2% 9mK

    The section is satisfactory at normal temperature Bsee Ex and %C.

    Design for the fire situation

    Mechanical actions for fire design situation

    4sing the simplified rule in E, >>-%2 actions in the fire situation may be

  • 7/25/2019 Exemple Calcul Foc

    12/36

    determined from actions in normal design. Bsee Ex. %C

    E(aluation of gas temperature

    The full calculation of a parametric fire curve is illustrated by worked example"$1%. The curve used in this example is based on the following parameters

    + !2)>12 tmax + %% min B$2'M) hourC andx + should be used. The modified

    time t* Bin hoursC is used in the parametric curve&

    The maximum gas temperature is reached at time t*max

    The heating part of the temperature curve is given&

    The maximal gas temperature in the fire compartment

    is&

    9hen t*max S %2 the curve in the cooling phase is given by&

    E(aluation of )eam temperatureThe section factor can be calculated as follows Bsee

  • 7/25/2019 Exemple Calcul Foc

    13/36

    The increase of temperature of the steel section is calculated using step-by-step

    procedure using the following formula&

    Time interval Dt + '$ sec is used in the temperature calculation.

    The maximum temperature reached due to exposure to the parametric fire is

    a2max + !/%O(. The steel

  • 7/25/2019 Exemple Calcul Foc

    14/36

  • 7/25/2019 Exemple Calcul Foc

    15/36

    Verification in the resistance domain

    %lassification of the section at ele(ated temperature

    The slenderness of the flange in compression is&

    The limit for (lass is >F.

  • 7/25/2019 Exemple Calcul Foc

    16/36

    The design moment resistance during fire exposure is givenby&

    The adaptation factor + $2/! is used for an unprotected beam exposed to fire on

    three sides.

    The adaptation factor % + 2$ is used for simply supported beam.

    The design moment resistance at the temperature

    a

    + !/%O( is&

    The design shear resistance is given by&

    The section is satisfactory in the at fire design situation.

    %omparison +ith design for standard fire resistance

  • 7/25/2019 Exemple Calcul Foc

    17/36

    EXAMPLE 4

    FIRE DESIGN OF A PROTECTED HEB SECTION COLUMNEXPOSED TO THE STANDARD TEMPERATURE TIME CURVE

    This worked example illustrates the fire design of a column that is continuous over

    two storeys. eat transfer into the section is evaluated using the E,>>'--%

    calculation procedure. The resistance of the column is evaluated using the simple

    calculation model for compression members given in E,>>'--%.

  • 7/25/2019 Exemple Calcul Foc

    18/36

    Data for fire calculation

    Aaterial properties of fire protectionH sprayed vermiculite cement

    - thickness dp + %$ mm

    - thermal conductivityp + $2% 9m-K-

    - densityp + !!$ kgm-'

    - specific heat cp + $$ Qkg-K-

    Mechanical actions at normal temperature

    The design value of the load in lower part of the column is&

    Design at normal temperature

    "ection E /$ 7 is designed to resist the applied load2 classified as (lass section.

    The buckling length of the column is e8ual to&

    7uckling perpendicular to ;-axis is critical.

    The elastic critical force for normal design is&

  • 7/25/2019 Exemple Calcul Foc

    19/36

    The non-dimensional slenderness at normal temperature is&

    The buckling reduction factor for hot-rolled I sections with hb ratio Y 2% is

    evaluated on curve c Bthe imperfection factor J + $21>C.

    7uckling resistance at 4ltimate 5imit "tate.

    The section is satisfactory at normal temperature.

    Design for the fire situation

    Mechanical actions for fire design situation

    4sing the simplified rule in E, >>-%2 actions in the fire situation may be determinedfrom actions in normal design.

    The accidental situation is used for the combination of mechanical actions during fire

    exposure2 where the : factor is taken as :%2 + $2' for office buildings. The reduction

    factor for the design load level is e8ual to&

    !&, The : factor is a nationally determined parameter. The value used in this example is

    the value recommended in E, >>--%

  • 7/25/2019 Exemple Calcul Foc

    20/36

    E(aluation of gas temperature

    The standard temperature-time curve is used for the gas temperature.

    E(aluation of column temperature

    The dotted line in Figure 3 indicates the perimeter of the section exposed to fire. The

    section factor is calculated as follows&

    The increase of temperature of the steel section is calculated by step-by-step procedure

    using&

    where&

    Time interval Dt + '$ sec is used in the temperature calculation.

    The steel and gas temperatures are shown in Table and Figure 4.

  • 7/25/2019 Exemple Calcul Foc

    21/36

  • 7/25/2019 Exemple Calcul Foc

    22/36

    $ minutes

    is a + !!1O(.

    ,ote&

    ?s an alternative2 the temperature of the steel column could be evaluated from "#$$!.

    m- and taking into account the properties of the fire

    protection material2 as follows.

    The steel temperature at t + >$ minutes2 is a + M$%O(

    The difference between the steel temperature calculated by the E,>>'--% step-by-step

    calculation and the steel temperature determined from "#$$! is caused by the assumption

    that $+Z

    Bi.e. neglecting the thermal capacity of the fire protection materialC in the design data givenin "#$$!. 4sing a design temperature from "#$$! will therefore lead to a conservative

    evaluation of the member resistance in fire.

    Verification in the resistance domain

    (lassification of the section at elevated temperature

    The slenderness of the flange in compression is&

    The limit for (lass is >F.

  • 7/25/2019 Exemple Calcul Foc

    23/36

    The limit is not exceeded. Therefore2 the flange is (lass .

    The slenderness of the web in compression is&

    The limit for (lass is ''F.

  • 7/25/2019 Exemple Calcul Foc

    24/36

    The buckling reduction factor is&

    The design resistance at temperature a + !!1O( is given by&

  • 7/25/2019 Exemple Calcul Foc

    25/36

    The elastic critical force at normal temperature is given as follows&

    In this case2 the calculation of2 [ should be based on the elastic critical load for a

    column buckling length of $.)L. The non-dimensional slenderness at normal

    temperature is given as follows&

    ,on-dimensional slenderness at temperature a is&

    The factor J is e8ual to&

    and the buckling reduction factor is&

    The design resistance at temperature a + M$%O( is calculated as&

  • 7/25/2019 Exemple Calcul Foc

    26/36

    Therefore2 the section is satisfactory for the fire design situation.

    !&, The conservative approximation of the steel temperature obtained from "#$$! hasresulted in a %!\ reduction in compressive resistance.

    %omparison +ith design using standard fire resistance and manufacturers/ data

    $ minutes exposure to the standard time temperature curve2 the thickness ofprotection re8uired can be determined using manufacturers design tables for

    vermiculite spray2 published in

  • 7/25/2019 Exemple Calcul Foc

    27/36

    EXAMPLE .

    FIRE DESI! "F A PR"$E%$ED 'E& SE%$I"! %"L#M! EXP"SED

    $" $'E PARAME$RI% FIRE %#RVE

    This worked example illustrates the fire design of a column that is continuous over

    two storeys. Transfer of heat into the section is calculated using the e8uation given in

    E,>>--%2 evaluated by step-by-step calculation procedure. The load bearing

    capacity of the column is calculated using the simple calculation model for

    compression members given in E,>>'--%.

    ? column made of hot-rolled E7 section supports two floors and is fire protected with

    gypsum boards. The column is re8uired to achieve M$ minutes fire resistance.

    Properties of fire protection material

    Wypsum board&

    - Total thickness dp + % mm6

    - thermal conductivityp + $2%$ 9m-K-

    - densityp + /$$ kgm'

    - specific heat cp + )$$ Qkg-K-

    Mechanical actions at normal temperature

    The design value of the load in the lower part of the column is

    Design at normal temperature

    "ection E /$ 7 is designed to resist the applied load2 classified as (lass section.

  • 7/25/2019 Exemple Calcul Foc

    28/36

    The buckling length of the column is e8ual to&

    7uckling perpendicular to ;-axis is critical.The elastic critical force for normal design is&

    The non-dimensional slenderness at normal temperature is&

    The buckling reduction factor for hot-rolled I sections with hb ratio Y 2% is

    evaluated on curve c Bthe imperfection factor J + $21>C.

    7uckling resistance at 4ltimate 5imit "tate.

    The section is satisfactory at normal temperature.

  • 7/25/2019 Exemple Calcul Foc

    29/36

    Design for the fire situation

    Mechanical actions for fire design situation

    4sing the simplified rule in E, >>-%2 actions in the fire situation may be determined

    from actions in normal design.

    The accidental situation is used for the combination of mechanical actions during fire

    exposure2 where the : factor is taken as :%2 + $2' for office buildings. The reduction

    factor for the design load level is e8ual to&

    !&, The : factor is a nationally determined parameter. The value used in this example is

    the value recommended in E, >>--%

    E(aluation of gas temperature

    The gas temperature is calculated on parametric temperature-time curve. The

    parameters of the curve in this example have been calculated as + 2')%2 tmax+ ''2M minutes B$2!M hourC andx + . ? full illustration of the calculation method

    for parametric fire curves is given in "$1%.

    The modified time t* Bin hoursC is used in the parametric curve

    The maximum gas temperature is reached at time t*max

    The heating part of the temperature curve is given by&

    The maximum gas temperature reached in the fire compartment is

  • 7/25/2019 Exemple Calcul Foc

    30/36

    9hen $2!Y t*max Y % the curve in the cooling phase is given by&

    E(aluation of column temperature

    The section factor is calculated as follows Bsee Figure 32 where the dotted line

    indicates the section perimeter exposed to fireC&

    The increase of temperature of the steel section is calculated by step-by-stepprocedure using&

    Time interval Dt + '$ seconds is used in the temperature calculation.

    The maximum steel temperature attained during this design fire occurs after ))

    minutes&

  • 7/25/2019 Exemple Calcul Foc

    31/36

  • 7/25/2019 Exemple Calcul Foc

    32/36

    Verification in the resistance domain

    %lassification of the section at ele(ated temperature

    The slenderness of the flange in compression is&

    The limit for (lass is >F.

  • 7/25/2019 Exemple Calcul Foc

    33/36

    The limit is not exceeded. Therefore2 the flange is (lass .

    The slenderness of the web in compression is&

    The limit for (lass is ''F.

  • 7/25/2019 Exemple Calcul Foc

    34/36

    The design resistance at temperature a2max + 1%)O( is given by&

    !&, #ue to relatively low design temperature and the reduction in effective

    length the buckling resistance is higher than the room temperature capacity.

  • 7/25/2019 Exemple Calcul Foc

    35/36

    Exemplul 2.

    Etapa II. Verifcarea la cald a stalpului

    Clasa de rezistenta R90: protectie cu mortar torcretat cu adaos de vermiculite de

    grosime di= cm.

    Caracteristicile stratului protector :

    i= !"0 #g$m! % i=0.0 &$m20C% pi= '% Ci= 200 ()$#g0C*

    +olicitarile pe setiune din grupare si din com,inatia la actiunea -ocului se vor

    considera: = /000 si respectiv = 9" #m

    1entru sectiunea de otel a stalpului : $3=40./ m5 % cs= "20 )$#g0C

    a6 +e determina : =7!"0x2006$72x"20x8"06=0.0"

    ,6 +e determina : $3=40./$70.0"x0.0/x40./6=".9c6 ;emperatura la -ata elementului din otel tre,uie sa corespunda clasei de

    rezistenta R90 :

    d??

    e?c?

    %

    %

    s

    +

    +=

    7 6

    unde :

    g?

    4

    c

    ?

    red

    =

    7 6

    fd

    $?

    i

    '

    % +=

    7 6

    3=7$.06".952.44="4.2/

    32= 70!0.0/6$0.".4/=/".4/

    s= 7"4.2/x29/".4/x0./"6$"4.2//".4/x0.46=!".20

    C

  • 7/25/2019 Exemple Calcul Foc

    36/36