eye / face wash stations - pnr€¦ · pnr uk ltd 28a harris business park, stoke prior,...
TRANSCRIPT
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
EYE / FACE WASH STATIONS
Please see below for our range of emergency eye/face wash models. These
are the most popular items in this range. A full list of spares is available for each model please just ask.
We can also quote for other designs and HAWS / AXION models should you
be interested.
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7260B AXION MSR™ EYE / FACE WASH STATION
Wall mounted
1/2"G 1"G 3, 1 kg No CH Z535.1
• Wall mounted • AXION MSR™ eye / facewash head (SP65) • 11” catch basin made of ABS plastic (SP93) • Strainer (SP509) • Aluminium wall bracket (SP80) • stainless steel push flag with stay open ball valve (SP229) • Eye wash sign (SP175) • Test tag (SP170) • Axion flow control (SP37.5)
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7260B Axion Eye Wash
No.2080038/1
NOTE TO INSTALLER: please leave this information with the maintenance department.
Legally-stipulated dimensions:
1 Ensure that there is a minimum clearance of 150mm (6") with respect to the nearest wall or obstacle.
2 Height above floor level: 800mm - 1200mm (2' 7 1/2" - 3' 11 1/4").
Free access to the eywash station 7260B Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
Jeannine Ruf 7260B Axion 13.09.2011 1/4
SCALE 1:8
216 1
377 112
1" G Waste
1/2" G Supply
TÜV tested
THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")
974
2 37
824
http://www.haws.ch/http://www.hawsco.com/
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch
HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7260B Axion Eye Wash No.2080038/1
Shower location: The eyewash station 7260B Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6 BAR (30 - 90 PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is allso recommended.
Water quality: Eyewash stations require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 -95°F (but please ensure conformity with local regulations).
Volume flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eyewash station must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G conduit with female-thread adapter, while the outlet is a 1" G threaded conduit.
Regular inspection: The eyewash station 7260B Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2 BAR /
30 PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being correctly flushed out. Dismantle the T-piece, and clean the rubber flow-regulator.
3. Flow rate is not as specified The flow conduit may be blocked (for remedy see above). The eyewash station may not have been set up correctly.
4. Water does not discharge correctly Check the building's main drainage outlet. Note that it must have adequate capacity to handle the entire drainage system.
Jeannine Ruf 7260B Axion 13.09.2011 2/4
http://www.haws.ch/http://www.hawsco.com/
-
1 2 3 4 ITEM PART NU. DESCRIPTION
PARTS BREAKDOWN
A A
1
8 B B
SP65 EYE WASH ASSEMBLY
2 C
6
D 7 D
3
4
5 E E
PARTS
BREAKDOWN
BACHWEG 3
WHEN ORDERING T +41 (0)34 420 60 00 CH3401 BURGDORF
www.haws.ch
PARTS PLEASE F +41 (0)34 420 60 01 TITLE SWITZERLAND [email protected]
TÜV tested SPECIFY YOUR MODEL NUMBER
APPROVALS DATE DRAWN
7260B Axion Eye Wash
Jeannine Ruf F CHECKED
28.04.2010 MATERIAL F
ZONE REV
DESCRIPTION REVISIONS
ECN
DATE
Ralph Streit 31.03.2011
BY REVISED 13.09.2011
DRAW-NO.
SIZE PART NO.
REV. THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
ECN NO. A4
SCALE 1:7 2080038/1
SHEET 4 OF 4 1 2 3 4
C
1 SP65 Axion eye/face wash head 2 SP93 Bowl 3 SP509 Strainer 4 SP80 Bracket 5 SP229 Valve assembly 6 SP175 Eye wash sign 7 SP170 Test tag 8 SP37.5 Flow control
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7460B AXION MSR™ EYE / FACE WASH STATION
Wall mounted
1/2"G 1" 3,2 kg No CH Z535.1
• Wall mounted • AXION MSR™ eye / facewash head (SP65) • 11” catch basin made of stainless steel (SP90) • Strainer (SP509) • Aluminium wall bracket (SP80) • stainless steel push flag with stay open ball valve (SP229) • Eye wash sign (SP175) • Test tag (SP170) • Axion flow control (SP37.5)
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7460B Axion Eye Wash
No.2080055/2
NOTE TO INSTALLER: please leave this information with the maintenance department.
Legally-stipulated dimensions:
1 Ensure that there is a minimum clearance of 150mm (6") with respect to the nearest wall or obstacle.
2 Height above floor level: 800mm - 1200mm (2' 7 1/2" - 3' 11 1/4").
Free access to the eywash station 7460B Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
Jeannine Ruf 7460B Axion 10.10.2011 1/4
SCALE 1:15
376 112
1/2" G Supply
1" Waste
TÜV tested
THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")
358
216 1
995
2
30
843
http://www.haws.ch/http://www.hawsco.com/
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch
HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7460B Axion Eye Wash No.2080055/2
Shower location: The eyewash station 7460B Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6 BAR (30 - 90 PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is allso recommended.
Water quality: Eyewash stations require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 -95°F (but please ensure conformity with local regulations).
Volume flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eyewash station must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G conduit with female-thread adapter, while the outlet is a 1" conduit.
Regular inspection: The eyewash station 7460B Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2 BAR /
30 PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being correctly flushed out. Dismantle the T-piece, and clean the rubber flow-regulator.
3. Flow rate is not as specified The flow conduit may be blocked (for remedy see above). The eyewash station may not have been set up correctly.
4. Water does not discharge correctly Check the building's main drainage outlet. Note that it must have adequate capacity to handle the entire drainage system.
Jeannine Ruf 7460B Axion 10.10.2011 2/4
http://www.haws.ch/http://www.hawsco.com/
-
1 2 3 4
PARTS BREAKDOWN
A
ITEM PART NU. DESCRIPTION 1 SP65 Axion eye/face wash head 2 SP90 Bowl 3 SP509 Strainer 4 SP80 Bracket A 5 SP229 Valve assembly 6 SP175 Eye wash sign 7 SP170 Test tag 8 VRKEWSTR Repair kit for SP509 9 SP37.5 Flow control
1 8 9
B B
SP65 EYE WASH ASSEMBLY 6
2 7
C C
3 D 4 D
5
E E
PARTS
BREAKDOWN
BACHWEG 3
WHEN ORDERING T +41 (0)34 420 60 00 CH3401 BURGDORF
www.haws.ch
TÜV tested PARTS PLEASE SPECIFY YOUR F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
MODEL NUMBER 7460B Axion APPROVALS
DRAWN Jeannine Ruf
F CHECKED
DATE
19.05.2011
Eye Wash
MATERIAL F
ZONE REV
DESCRIPTION
ECN
DATE
Jeannine Ruf 19.05.2011
BY REVISED REVISIONS
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
Jeannine Ruf DRAW-NO.
ECN NO.
10.10.2011 SIZE PART NO.
A4 SCALE 1:10
2080055/2
REV.
SHEET 4 OF 4 1 2 3 4
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7261 AXION MSR™ EYE / FACE WASH STATION Free standing / pedestal
1/2"G 1 1/4"G 8,4 kg No CH Z535.1
• Free standing pedestal • AXION MSR™ eye / facewash head (SP65) • 11” catch basin made of ABS plastic (SP93) • Strainer (SP509) • Floor flange (SP75) • Eye wash sign (SP175) • Test tag (SP170) • Foot control assembly (SP220) • Stainless steel push flag with stay open ball valve (SP229) • Axion flow control (SP37.5)
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7261 Axion Pedestal Eye Wash
No.2080043/4
NOTE TO INSTALLER: please leave this information with the maintenance department.
Legally-stipulated dimensions:
1 Ensure that there is a minimum clearance of 150mm (6") with respect to the nearest wall or obstacle.
2 Height above floor level: 800mm - 1200mm (2' 7 1/2" - 3' 11 1/4").
Free access to the eywash station 7261 Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
Jeannine Ruf 7261 Axion 30.09.2011 1/4
Floor Flange Detail
244 1 375 110
1/2" G Supply
1 1/4" G Waste
TÜV tested
SCALE 1:10 THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")
2 93
5
39
161
794
http://www.haws.ch/http://www.hawsco.com/
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch
HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7261 Axion Pedestal Eye Wash No.2080043/4
Shower location: The eyewash station 7261 Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6 BAR (30 - 90 PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is allso recommended.
Water quality: Eyewash stations require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 -95°F (but please ensure conformity with local regulations).
Volume flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eyewash station must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G conduit with female-thread adapter, while the outlet is a 1 1/4" G threaded conduit.
Regular inspection: The eyewash station 7261 Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2 BAR /
30 PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being correctly flushed out. Dismantle the T-piece, and clean the rubber flow-regulator.
3. Flow rate is not as specified The flow conduit may be blocked (for remedy see above). The eyewash station may not have been set up correctly.
4. Water does not discharge correctly Check the building's main drainage outlet. Note that it must have adequate capacity to handle the entire drainage system.
Jeannine Ruf 7261 Axion 30.09.2011 2/4
http://www.haws.ch/http://www.hawsco.com/
-
1 2 3 4
PARTS BREAKDOWN A 1 7
10
SP65 EYE WASH ASSEMBLY
B 2
ITEM PART NU. DESCRIPTION 1 SP65 Axion eye/face wash head 2 SP93 Bowl 3 SP509 Strainer
A 4 SP75 Floor flange 5 SP229 Valve assembly 6 SP175 Eye wash sign 7 SP170 Test tag 8 SP220 Foot control assembly 9 SP185 Stripe tape
10 SP37.5 Flow control
B
C C
3
5
D D
6 8 9
4
E E
PARTS
BREAKDOWN
BACHWEG 3
WHEN ORDERING T +41 (0)34 420 60 00 CH3401 BURGDORF
www.haws.ch
TÜV tested PARTS PLEASE F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
SPECIFY YOUR MODEL NUMBER
APPROVALS DATE DRAWN
7261 Axion Pedestal Eye Wash
F
ZONE REV
DESCRIPTION REVISIONS
ECN
DATE
Jeannine Ruf CHECKED
BY REVISED
DRAW-NO.
02.10.2007
30.09.2011
MATERIAL
SIZE PART NO.
F
REV. THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
ECN NO. A4
SCALE 1:7 2080043/4
SHEET 4 OF 4 1 2 3 4
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7461 AXION MSR™ EYE / FACE WASH STATION Free standing / pedestal
1/2"G 1 1/4"G 8,9kg No CH Z535.1
• Free standing pedestal • AXION MSR™ eye / facewash head (SP65) • 11” catch basin made of stainless steel (SP90) • Strainer (SP509) • Floor flange (SP75) • Eye wash sign (SP175) • Test tag (SP170) • Foot control assembly (SP220) • Stainless steel push flag with stay open ball valve (SP229) • Axion flow control (SP37.5)
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7461 Axion Pedestal Eye Wash
No.2080056/5
NOTE TO INSTALLER: please leave this information with the maintenance department.
227 1
377 112
Floor Flange Detail
1/2" G Supply
11/4" G Waste
TÜV tested
MASSSTAB 1:10
THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")
Legally-stipulated dimensions:
1 Ensure that there is a minimum clearance of 150mm (6") with respect to the nearest wall or obstacle.
2 Height above floor level: 800mm - 1200mm (2' 7 1/2" - 3' 11 1/4").
Free access to the eywash station 7461 Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
Jeannine Ruf 7461 Axion 11.10.2011 1/4
2 93
4
33
161
796
http://www.haws.ch/http://www.hawsco.com/
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch
HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 7461 Axion Pedestal Eye Wash No.2080056/5
Shower location: The eyewash station 7461 Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6 BAR (30 - 90 PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is allso recommended.
Water quality: Eyewash stations require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 -95°F (but please ensure conformity with local regulations).
Volume flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eyewash station must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G conduit with female-thread adapter, while the outlet is a 1 1/4" G threaded conduit.
Regular inspection: The eyewash station 7461 Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2 BAR /
30 PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being correctly flushed out. Dismantle the T-piece, and clean the rubber flow-regulator.
3. Flow rate is not as specified The flow conduit may be blocked (for remedy see above). The eyewash station may not have been set up correctly.
4. Water does not discharge correctly Check the building's main drainage outlet. Note that it must have adequate capacity to handle the entire drainage system.
Jeannine Ruf 7461 Axion 11.10.2011 2/4
http://www.haws.ch/http://www.hawsco.com/
-
1 2 3 4
PARTS BREAKDOWN 1
A 7 10
ITEM PART NU. DESCRIPTION
A
SP65 EYE WASH ASSEMBLY
2
C
6 C
3 9
5 D 8 4 D
E E
PARTS
BREAKDOWN
BACHWEG 3
WHEN ORDERING T +41 (0)34 420 60 00 CH3401 BURGDORF
www.haws.ch
TÜV tested PARTS PLEASE F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
SPECIFY YOUR MODEL NUMBER
APPROVALS DATE DRAWN
7461 Axion Pedestal Eye Wash
F
ZONE REV
DESCRIPTION REVISIONS
ECN
DATE
Jeannine Ruf CHECKED
BY REVISED
DRAW-NO.
15.02.2011
11.10.2011
MATERIAL
SIZE PART NO.
F
REV. THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
ECN NO. A4
SCALE 1:8.5 2080056/5
SHEET 4 OF 4 1 2 3 4
B B
1 SP65 Axion eye/face wash head 2 SP90 Bowl 3 SP509 Strainer 4 SP75 Floor flange 5 SP229 Valve assembly 6 SP175 Eye wash sign 7 SP170 Test tag 8 SP220 Foot control assembly 9 SP185 Stripe tape 10 SP37.5 Flow control
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7610 AXION EYE / FACE WASH STATION
Sink / countertop
1/2"O.D. slipjoint
4,2 kg No US Z358.1
• Sink or countertop fitted • AXION MSR™ eye / facewash head (SP65) • Eye wash sign (SP175) • Test tag (SP170) • Axion flow control (SP37.5) • VRK7650 Repair kit for 7650
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG � Bachweg 3 � CH-3401 Burgdorf � Switzerland � www.haws.ch HAWS Corporation � P.O.Box 2070 � 1455 Kleppe Lane � Sparks,Nevada 89431/USA �
Model 7610 Axion Eye/Face Wash No.2080067/2
7610 Axion 23.04.2012 1/2 Jeannine Ruf
NOTE TO INSTALLER: please leave this information with the maintenance department.
Legally-stipulated dimensions:
1 Ensure that there is a minimum clearance of 150mm (6") with respect to the nearest wall or obstacle.
2 Height above floor level: 800mm - 1200mm (2' 7 1/2" - 3' 11 1/4").
Free access to the eywash station 7610 Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
86 48
218 158
64
158 1
1/2" Supply
THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2") SCALE 1:15
949
2
463
47
http://www.haws.ch/http://www.hawsco.com/
-
7610 Axion 23.04.2012 2/2 Jeannine Ruf
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG � Bachweg 3 � CH-3401 Burgdorf � Switzerland � www.haws.ch HAWS Corporation � P.O.Box 2070 � 1455 Kleppe Lane � Sparks,Nevada 89431/USA �
Model 7610 Axion Eye/Face Wash No.2080067/2
Shower location: The eyewash station 7610 Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6 BAR (30 - 90 PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is allso recommended.
Water quality: Eyewash stations require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 -95°F (but please ensure conformity with local regulations).
Volume flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eyewash station must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G conduit with female-thread adapter.
Regular inspection: The eyewash station 7610 Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2 BAR /
30 PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being correctly flushed out. Dismantle the T-piece, and clean the rubber flow-regulator.
3. Flow rate is not as specified The flow conduit may be blocked (for remedy see above). The eyewash station may not have been set up correctly.
4. Water does not discharge correctly Check the building's main drainage outlet. Note that it must have adequate capacity to handle the entire drainage system.
http://www.haws.ch/http://www.hawsco.com/
-
3401 BURGDO
1 2 3 4
ITEM PART NU. DESCRIPTION 1 SP65 Axion eye/face wash head 2 SP175 Eye wash sign 3 SP170 Test tag
A A 4 SP37.5 Flow control
1 5 VRK7650 Repair kit for 7650
3 5
4
B SP65 EYE WASH ASSEMBLY B 2
C C
D D
E E
PARTS BREAKDOWN
WHEN ORDERING T +41 (0)34 420 60 00 CH BACHWEG 3
RF
www.haws.ch
PARTS PLEASE SPECIFY YOUR
F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
MODEL NUMBER APPROVALS DATE
DRAWN
7610 Axion Eye/Face Wash
Jeannine Ruf F CHECKED
30.06.2011 MATERIAL F
ZONE REV
DESCRIPTION
ECN
DATE
Jeannine Ruf 30.06.2011
BY REVISED REVISIONS
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
Jeannine Ruf DRAW-NO.
ECN NO.
23.04.2012 SIZE PART NO.
A4 SCALE 1:10
2080067/2
REV.
SHEET 1 OF 1 1 2 3 4
PARTS BREAKDOWN
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
7620 AXION™ EyePOD™
Faucet mounted
• Faucet mounted • Polished stainless steel, faucet-mounted eyewash
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSRUCTIONS
HAWS AG � Bachweg 3 � CH-3401 Burgdorf � Switzerland � www.haws.ch HAWS Corporation � P.O.Box 2070 � 1455 Kleppe Lane � Sparks,Nevada 89431/USA �
Model 7620 Axion Eye Wash No.2080031
7620 Axion 02.03.2012 1/2 Ralph Streit
NOTE TO INSTALLER: please leave this information with the maintenance department.
Free access to the eywash station 7620 Axion must be guaranteed all times. The operator is responsible for the observance of this requirement.
55/64-27 UNS-2B
12° 88.9
36
20
Eye wash closed Eye wash open
THESE DIMENSIONS MAY VARY +/- 6,4mm (1/4") SCALE 1:2
52
25
http://www.haws.ch/http://www.hawsco.com/
-
7620 Axion 02.03.2012 2/2 Ralph Streit
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG � Bachweg 3 � CH-3401 Burgdorf � Switzerland � www.haws.ch HAWS Corporation � P.O.Box 2070 � 1455 Kleppe Lane � Sparks,Nevada 89431/USA �
Model 7620 Axion Eye Wash No.2080031
TYPICAL APPLICATION
TURN ON FAUCET
ROTATE HEAD IN EITHER DIRECTION
EYEWASH MODE
http://www.haws.ch/http://www.hawsco.com/
-
3401 BURGDO
1 2 3 4 ITEM PART NU. DESCRIPTION
PARTS BREAKDOWN A
1 0000001717 13/16-27M x 55/64-27M adaptor 2 0000001715 15/16-27M x 55/64-27M adaptor 3 0000001719 13/16-24F x 55/64-27M adaptor A 4 0000087801 Faucet nozzle
1 4
B B
2
3 C
C
D D
E E
PARTS BREAKDOWN
WHEN ORDERING T +41 (0)34 420 60 00 CH BACHWEG 3
RF
www.haws.ch
PARTS PLEASE SPECIFY YOUR
F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
MODEL NUMBER APPROVALS DATE
DRAWN
7620 Axion Eye Wash
Ralph Streit F CHECKED
01.03.2012 MATERIAL F
ZONE REV
DESCRIPTION REVISIONS
ECN
DATE
Ralph Streit 01.03.2012
BY REVISED 02.03.2012
PART NO.
SIZE DRAW NO.
REV. THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
ECN NO. A4
SCALE 1:1 2080031
SHEET 1 OF 1 1 2 3 4
http://www.haws.ch/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
8901 AXION EYE/FACE WASH Hand-held hose
1/2"G 1,8 kg No CH Z535.1
• Hand-held hose • AXION MSR™ eye / facewash head (SP65/1) • Single hand valve for double head/hose spray unit (SP247) • 250 psi hose with a chrome-plated swivel fitting (SP140) • Eye wash sign (SP175) • Test tag (SP170) • Wall bracket ABS black to 8901 (SP133) • Stainless steel push flag with stay open ball valve (SP229) • Axion flow control 4.2 GAL / 15.9 lt (SP37.6)
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
www.pnr.co.uk [email protected] +44(0)1527 579 066
PNR UK Ltd 28a Harris Business Park, Stoke Prior, Bromsgrove, B60 4DJ
www.pnr.co.uk | [email protected] | +44(0)1527 579 066 Co. Reg. 2306776 V.A.T. Reg. No. 488 0643 16
http://www.pnr.co.uk/mailto:[email protected]://www.pnr.co.uk/mailto:[email protected]
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 8901B Axion Eye/Face Wash and Body Spray No.2080191/3
NOTE TO INSTALLER: please leave this information with the maintenance departement.
Free acces to the eye/facewash & body spray 8901B Axion must be guaranteed at all times. The operator is responsible for the observance of this requirement.
Jeannine Ruf 8901B Axion
12.10.2011
1/4
57 81 85
1/2" G Supply 2.4m
TÜV tested
SCALE 1:18 THESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")
228
http://www.haws.ch/http://www.hawsco.com/
-
HAWS DRINKING FAUCET COMPANY INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HAWS AG • Bachweg 3 • CH-3401 Burgdorf • Switzerland • www.haws.ch
HAWS Corporation • P.O.Box 2070 • 1455 Kleppe Lane • Sparks,Nevada 89431/USA • www.hawsco.com
Model 8901B Axion Eye/Face Wash and Body Spray No.2080191/3
Shower location: The eye/facewash & body spray 8901B Axion must be installed in the vicinity of potential danger zones. It must be highly visible and easily accessible.
Connection conduit: You are recommended to use a 1/2" G conduit, capable of withstanding pressures of 2 - 6BAR (30 - 90PSI). The use of an inlet filter designed to prevent the entry of suspended particles and other impurities is also recommended.
Water quality: Eye/facewash & body spray require a supply of drinking water conforming to European standards or their equivalents in other countries.
Water temperature: The required water temperature should be determined by the user. The accepted ideal range is 15 - 35°C / 60 - 95°F (but please ensure conformity with local regulations).
Volum flow: A minimum flow rate of 6 litres / 1,6 US gallons per minute must be maintained. The eye/facewash & body spray must be capable of delivering this amount of water for at least 15 minutes.
Connection to plumbing system: The inlet consists of a 1/2" G male-threaded conduit.
Regular inspection: The eye/facewsh & body spray 8901B Axion should be inspected at weekly intervals. The inspection tag should be dated and signed after each check.
TROUBLESHOOTING Problem Repair-checklist 1. No flow Check the main shutoff valve. 2. Insufficient flow of water 1. Check the line pressure. This should be at least 2BAR /
30PSI (dynamic). 2. Blocked flow, possibly due to the conduit not being
correctly flushed out. Dismantle the spray element, and clean the rubber flow-regulator.
Jeannine Ruf 8901B Axion 12.10.2011 2/4
http://www.haws.ch/http://www.hawsco.com/
-
PARTS BREAKDOWN 1 2 3 4
ITEM PART NU. DESCRIPTION
A A
1 7
B B
6
4 C
C
2
D 3 D
5
E E
PARTS
BREAKDOWN
BACHWEG 3
WHEN ORDERING T +41 (0)34 420 60 00 CH3401 BURGDORF
www.haws.ch
TÜV tested PARTS PLEASE F +41 (0)34 420 60 01
TITLE
SWITZERLAND [email protected]
SPECIFY YOUR MODEL NUMBER
APPROVALS DATE DRAWN
8901B Axion Eye/Face Wash and Body Spray
Jeannine Ruf F CHECKED
03.03.2011 MATERIAL F
ZONE REV
DESCRIPTION REVISIONS
ECN
DATE
Jeannine Ruf 03.03.2011
BY REVISED 12.10.2011
DRAW-NO.
SIZE PART NO.
REV. THIS DOCUMENT AND THE DATA DISCLOSED HEREIN OR HEREWITH IS NOT TO BE REPRODUCED, USED, OR DISCLOSED IN WHOLE OR IN PART TO ANYONE WITHOUT THE PERMISSION OF HAWS CORPORATION.
ECN NO.
A4 SCALE 1:10
2080191/3 SHEET 4 OF 4
1 2 3 4
1 SP65/1 Axion eye/face wash head 2 SP247 Valve assembly 3 SP140 Hose assembly 4 SP175 Eye wash sign 5 SP170 Test tag 6 SP133 Wall bracket , plastic 7 SP37.6 Flow control
http://www.haws.ch/mailto:[email protected]
emergency_eye-face_wash_cover_page.pdf7260B_Axion_wall_mounted_eye-face_wash_plastic_bowl.pdfEYE / FACE WASH STATIONHAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelEye WashNOTE TO INSTALLER: please leave this information with the maintenance department.Legally-stipulated dimensions:7260B Axion
HAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.chRegular inspection:ITEM PART NU. DESCRIPTION
SP65 EYE WASH ASSEMBLY63PARTS BREAKDOWNPARTS PLEASESPECIFY YOUR MODEL NUMBER2080038/1
7460B_Axion_eye-face_wash_wall_mounted_stainless_bowl.pdfEYE / FACE WASH STATIONHAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelEye WashLegally-stipulated dimensions:7460B Axion
HAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelEye WashRegular inspection:
5PARTS BREAKDOWNPARTS PLEASE SPECIFY YOURMODEL NUMBER2080055/2
7261_Axion_free_standing_ABS_plastic_bowl.pdfEYE / FACE WASH STATIONHAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelPedestal Eye WashLegally-stipulated dimensions:7261 Axion
HAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.chRegular inspection:
10SP65 EYE WASH ASSEMBLYITEM PART NU. DESCRIPTION4 SP75 Floor flange
6PARTS BREAKDOWNPARTS PLEASESPECIFY YOUR MODEL NUMBER2080043/4
7461_Axion_free_standing_stainless_bowl.pdfEYE / FACE WASH STATIONHAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelPedestal Eye WashTHESE DIMENSIONS MAY VARY +/- 12,7mm (1/2")Legally-stipulated dimensions:
7461 Axion
HAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.chRegular inspection:
10ITEM PART NU. DESCRIPTION
23 9PARTS BREAKDOWNPARTS PLEASESPECIFY YOUR MODEL NUMBER2080056/5
7610_Axion_eye-face_wash_sink_mounted.pdfEYE / FACE WASH STATIONLegally-stipulated dimensions:Regular inspection:4 SP37.5 Flow controlPARTS BREAKDOWNPARTS PLEASE SPECIFY YOURMODEL NUMBER
7610 Axion2080067/2
Axion_7620_eye_pod_faucet_mounted_eye_wash.pdfEyePOD™ Faucet mounted Polished stainless steel, faucet-mounted eyewash
MODEL NUMBER2080031
8901B_AXION_eye_face_hand_held_hose.pdfEYE/FACE WASHHAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelEye/Face Wash and Body Spray8901B Axion
HAWS DRINKING FAUCET COMPANYHAWS AG Bachweg 3 CH-3401 Burgdorf Switzerland www.haws.ch
ModelEye/Face Wash and Body SprayITEM PART NU. DESCRIPTION1 7625PARTS BREAKDOWN
TÜV testedPARTS PLEASESPECIFY YOUR MODEL NUMBER
8901B Axion2080191/3