Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
DU-107-PP
![Page 2: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/2.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
PURPOSE The purpose of the Operations and Maintenance Training Program
is to train Operations and Maintenance Technicians in the operation of the Duke University Chiller and Steam Systems.
OBJECTIVES Trainees will demonstrate knowledge of
– Chilled Water Plant #2 (CHWP-2) Reclaim Water System Components
– CHWP-2 Reclaim Water System Components Operation– CHWP-2 Reclaim Water System Configuration– CHWP-2 Reclaim Water System Controls and Instrumentation
![Page 3: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/3.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
PURPOSE The purpose of CHWP-2 Reclaim Water is to:
– Reduce dependence on City of Durham water– Reduce costs– Reduce impact on the environment – Prevent loss of services during drought conditions
![Page 4: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/4.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
CHWP-2 RECLAIM WATER SYSTEM Reclaimed water supplies the CHPW-2 cooling tower basin. Reclaim
water comes from:– Air Handler Unit (AHU) cooling coil condensate– Wells– Creek– Storm drainage system and reclaim pond– Rainwater
The Control Room controls distribution of reclaim water to the cooling tower basin and irrigation system.
![Page 5: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/5.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
WHY RECLAIM WATER? In 2007 drought conditions in
Durham NC reached record low levels in water supplies. Duke helped lead the response.
Duke University growth from 2006 – 2010 of 7.4%.
Central Chiller System load increase from 2005 – 2010 of 60%.
Duke University is the largest user of water in the City of Durham.
![Page 6: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/6.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
At 30% of all water used, the Chilled Water System is the largest single consumer of water at Duke University.
CHWP-2 can use 100 million gallons of water per day.
![Page 7: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/7.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
HOW DUKE HAS RESPONDED October 2007, Duke University convened Water Conservation
Steering & Working Groups, which analyzed all potable water use on campus.
In 2009 CHWP-2 underwent major renovation, resulting in Leadership in Energy & Environmental Design (LEED) Gold certification
![Page 8: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/8.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
The reclaim water project supports the Governor Deval L. Patrick of North Carolina’s “Leading by Example” initiative (Executive Order 484).
As of 2010, 43 million gallons of water per year have been saved. When the Reclamation Pond is completed, an additional 100 million
gallons of water per year will be saved.
![Page 9: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/9.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAIM WATER PRINCIPLES Reclaimed water is used for makeup feedwater and irrigation. The CHWP-2 Reclaim System
– Reduces reliance on City of Durham water– Saves money– Reduces waste and impact on the environment
![Page 10: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/10.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
Water from the following sources is distributed through the CHWP-2 Reclaim Water System:– AHU cooling coil condensate– Two Wells– Creek – Storm Drainage System with Reclaim Pond(being constructed in-
stream during 2014)– Rainwater collected from the CHWP-2 rooftop
![Page 11: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/11.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow much of all water used at Duke is consumed by the
Chilled Water System?– 9%– 15%– 30%– 25%
![Page 12: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/12.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWER30% of all water used on campus is consumed by the Chilled
Water System.
![Page 13: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/13.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhat Gold level certification has CHWP-2 been awarded?
– EPA– LEED– Malcolm Baldrige– NOA
![Page 14: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/14.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWER In 2009 CHWP-2 underwent major renovation, resulting
in LEED Gold certification
![Page 15: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/15.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhat was the percentage of growth for Duke University from
2006 to 2010?– 14.7%– 17.4%– 7.4%– 4.7%
![Page 16: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/16.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERDuke University grew by 7.4% between 2006 and 2010.
![Page 17: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/17.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONThe reclaim water project supports which initiative of the
Governor of North Carolina?– Leading by Example– Keep North Carolina Green– Water Conservation Initiative– Esse Quam Videri
![Page 18: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/18.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERThe reclaim water project supports the Governor of
North Carolina’s “Leading by Example” initiative.
![Page 19: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/19.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhat is LEED an acronym for?
– Land Environment Ecology Designation– Leading Ecologists to Energize our Destination– Leadership in Ecology and Energy Design– Leadership in Energy and Environmental Design
![Page 20: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/20.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERLeadership in Energy and Environmental Design
![Page 21: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/21.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
PURPOSE Systems that make up the CHWP-2 Reclaim Water System efficiently
and responsibly supply water for:– The CHWP-2 Cooling Towers basin to help cool the basin and
provide makeup feedwater– Irrigation on campus
![Page 22: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/22.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
SYSTEM COMPONENTS The Duke University CHWP-2 Reclaim Water System includes the
following equipment and locations:– Reclaim Water Supply– Reclaim Water Tanks– Reclaim Pumps – CHWP-2 Cooling Tower Basin– Irrigation System
![Page 23: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/23.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAIM WATER SUPPLYCreek and WellsAHU Cooling Coil CondensateStorm WaterReclamation PondRainwater
![Page 24: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/24.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
CREEK AND WELLS Reclaiming creek water saves 22 million gallons per year. Two wells save 1.5 million gallons per year
![Page 25: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/25.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
AHU COOLING COIL CONDENSATE Reclaiming condensate from air handler cooling coils saves 15
million gallons per year.
CONDENSATE DRAIN
![Page 26: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/26.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
STORM WATER Storm water runoff is collected in the storm drainage system. The storm drainage system consists of nearly 32 miles of storm
pipes and drainage ditches.
![Page 27: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/27.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAMATION POND The storm water reclamation pond is being constructed in-stream of
the storm drainage system. The pond will save approximately 100 million gallons of water per
year.
![Page 28: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/28.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RAINWATER Rainwater is collected from the CHWP-2 roof and piped to the
Reclaim Tanks in the basement. Rainwater collected from campus buildings saves 9 million gallons
per year.
![Page 29: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/29.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhat does reclaim water do in the cooling tower basin?
– Cools the basin and provides makeup feedwater– Preheats water in the basin and provides makeup feedwater– Reclaim water is not supplied to the basin– Rinses old feedwater from the basin and provides makeup
condensate
![Page 30: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/30.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERReclaim water cools the basin and provides makeup
feedwater.
![Page 31: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/31.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many millions of gallons of water may be saved annually
by the reclamation pond?– 22– 100– 15– 60
![Page 32: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/32.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERThe reclaim pond will save approximately 100 million
gallons of water per year.
![Page 33: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/33.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONApproximately how many miles of storm pipes and
drainage ditches are in the storm drainage system?– 100– 25– 32– 17
![Page 34: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/34.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERThe storm drainage system consists of nearly 32 miles of
storm pipes and drainage ditches.
![Page 35: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/35.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many millions of gallons of water are saved by
reclaiming rainwater?– 7.4– 22– 9– 14
![Page 36: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/36.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERRainwater collected from campus buildings saves 9
million gallons per year.
![Page 37: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/37.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many millions of gallons of water are saved by
reclaiming creek water?– 7.4– 22– 32– 1.5
![Page 38: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/38.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERReclaiming creek water saves 22 million gallons per
year.
![Page 39: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/39.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTION How many millions of gallons of water per year can be saved by
reclaiming condensate from AHU cooling coils?
– 22
– 32
– 9
– 15
![Page 40: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/40.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERReclaiming condensate from air handler cooling coils
saves 15 million gallons per year.
![Page 41: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/41.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAIM WATER TANKS Reclaim Water Tanks 1 and 2 are located in the basement of
CHWP-2.
![Page 42: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/42.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAIM PUMPS Reclaim Pumps P1 and P2 are located next to the Reclaim
Water Tanks.
![Page 43: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/43.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
RECLAIM PUMP CONTROLS Manual controls for Reclaim Pumps P1 and P2 are located to
the right of the pumps.
![Page 44: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/44.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
COOLING TOWER BASIN The cooling tower basin is located below the cooling towers.
EAST CAMPUS STEAM PLANT
![Page 45: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/45.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
IRRIGATION SYSTEM Reclaim water reduces or eliminates reliance on City of Durham water for
landscape irrigation.
EAST CAMPUS STEAM PLANT
![Page 46: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/46.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhere are the Reclaim Water Tanks located?
– Below the cooling towers– Outside CHWP-2– Control Room– Basement of CHWP-2
![Page 47: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/47.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
AnswerReclaim Water Tanks 1 and 2 are located in the basement of
CHWP-2.
![Page 48: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/48.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhere are the Reclaim Pumps located?
– Below the cooling towers– Control Room– Next to the Reclaim Water Tanks– Mezzanine
![Page 49: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/49.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERReclaim Pumps P1 and P2 are located next to the Reclaim
Water Tanks.
![Page 50: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/50.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhere are the manual controls for the Condensate Reclaim
Pumps located?– Below the cooling towers– To the right of the pumps– Control Room– Outside CHWP-2
![Page 51: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/51.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERManual controls for the Condensate Reclaim Pumps P1 and P2
are located to the right of the pumps.
![Page 52: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/52.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
CHWP-2 RECLAIM WATER CONFIGURATION AND PROCESS FLOW
![Page 53: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/53.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
Reclaim water from AHUs, the creek, wells, and rainwater is collected in the Reclaim Water Tanks.
RECLAIM SUPPLY
RECLAIM WATER TANK 1 RECLAIM WATER TANK 2
![Page 54: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/54.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
When the water level in the tanks reaches 4 feet, the reclaim pumps turn on, sending water to the CWP2A and CWP2B cooling tower basins.
When the level drops below 2 feet, the pumps automatically shut off.
CWP2A CWP2B RECLAIM WATER
RECLAIM PUMP P-1
RECLAIM PUMP P-2
TOWER FILL VALVE
TOWER FILL METER
![Page 55: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/55.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
When the water level in the tanks reaches 4 feet, water is also pumped to the irrigation system.
IRRIGATION SYSTEM
IRRIGATION VALVE
IRRIGATION METER
![Page 56: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/56.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONAt what level do the reclaim pumps turn on?
– 4 feet– 7 feet– 2 feet– 5 feet
![Page 57: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/57.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERWhen the water level in the tanks reaches 4 feet, the reclaim
pumps turn on.
![Page 58: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/58.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONAt what level do the reclaim pumps automatically shut off?
– 4 feet– 7 feet– 2 feet– 5 feet
![Page 59: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/59.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERWhen the water level in the tanks reaches 2 feet, the reclaim
pumps automatically shut off.
![Page 60: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/60.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
AHU COOLING COIL CONDENSATE FLOW Moisture laden air passes through the chilled
water coil.
CONDENSATE DRAIN
ENTERING AIR
CHILLED WATER COIL
![Page 61: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/61.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
AHU COOLING COIL CONDENSATE FLOW The moisture condenses on the coil and is
captured in the drain pan.
CONDENSATE DRAIN
ENTERING AIR
CHILLED WATER COIL
CONDENSATE
DRAIN PAN
![Page 62: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/62.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
AHU COOLING COIL CONDENSATE FLOW The booster pump injects condensate into
the condenser water line to the cooling tower basin.
CONDENSATE DRAIN
ENTERING AIR
CHILLED WATER COIL
CONDENSATE
DRAIN PAN
BOOSTER PUMP
CONDENSER PUMP
COOLING TOWER BASIN
![Page 63: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/63.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
OPERATIONS MONITORING– Operation of the CHWP-2 Reclaim Water System is monitored through
the Control Room on the top floor of CHWP-2.– The Digital Control System (DCS) provides operators with information
on system operation and control over system parameters.
![Page 64: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/64.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
PLANT ROUNDS– During an Operator’s routine shift, Rounds are accomplished to
record key information and visually assess Chilled Water System operation.
– Each Plant has a Rounds Sheet to be filled out by the Operator.– Each plant has different requirements for plant rounds.– The information is recorded, not only for the current status, but
also to record system trends.
![Page 65: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/65.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
CHWP-2 DAILY ROUNDS– The following is recorded, during operator rounds, specifically
for the CHWP-2 Reclaim Water System:• Tank #1 Level (inches)• Tank #2 Level (inches)• Reclaim Pump P-1 (ON/OFF)• Speed (HZ/Amps)• Reclaim Pump P-2 (ON/OFF)• Speed (HZ/Amps)• Suction PSI• Discharge PSI
![Page 66: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/66.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
EXAMPLE CHWP-2 ROUNDS SHEET (front and back)
![Page 67: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/67.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
TYPICAL PROBLEMS ASSOCIATED WITH CHWP-2 RECLAIM WATER– Reclaim pumps leaking
• Most likely cause is packing failure.– Failed Flow Meters
• Most likely cause is failure or clogging of meter.– Flooding of basement
• Most likely cause is sump pump has failed or drain is clogged.
– Failed Flow Control Valves• Most likely cause is clogged valve or failed actuator
![Page 68: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/68.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhere does Operations Monitoring take place?
– Control Room in each steam plant– Control Room in West Campus Steam Plant– Control Room in CHWP-2– Control Room in CHWP-1
![Page 69: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/69.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWER In the Control Room in CHWP-2
![Page 70: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/70.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhy is it necessary to reclaim water?
– Reduce dependence on city water– Reduce costs– Reduce impact on the environment– All of the above
![Page 71: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/71.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERAll of the above. The purpose of CHWP-2 Reclaim Water
is to reduce the dependence on city water, reduce costs, reduce impact on the environment.
![Page 72: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/72.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONReclaim water supplies what and irrigation?
– Hospital– Reclamation pond– Creek– Cooling tower basin
![Page 73: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/73.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERReclaim water supplies the cooling tower basin as
makeup.
![Page 74: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/74.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many millions of gallons of water can CHWP-2 use in a
day?– 7.4– 100– 15– 60
![Page 75: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/75.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERCHWP-2 can use 100 million gallons of water per day.
![Page 76: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/76.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many water reclaim tanks are located in CHWP-2?
– 4– 1– 2– 10
![Page 77: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/77.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERTwo water reclaim tanks are located in CHWP-2.
![Page 78: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/78.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow many water reclaim pumps are located in CHWP-2?
– 4– 1– 2– 10
![Page 79: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/79.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERTwo water reclaim pumps are located in CHWP-2.
![Page 80: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/80.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTION In which year did drought conditions in Durham NC reach
record low levels and stimulate Duke’s response?– 2006– 2007– 1998– 2001
![Page 81: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/81.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWER In 2007 drought conditions in Durham NC reached
record low levels in water supplies. Duke helped lead the response.
![Page 82: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/82.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONHow much did the Central Chiller System’s load increase
between 2005 to 2010?– 30%– 15%– 60%– 7.4%
![Page 83: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/83.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERBetween 2005 and 2010 Central Chiller System load
increased 60%.
![Page 84: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/84.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
QUESTIONWhere is the Reclamation Pond being constructed?
– Under the cooling towers– In-stream of the storm drainage system– In the basement– Eno River State Park
![Page 85: Facilities Management Utilities & Engineering Services Duke CHWP-2 RECLAIM WATER DU-107-PP](https://reader035.vdocument.in/reader035/viewer/2022062515/56649c905503460f9494a8bd/html5/thumbnails/85.jpg)
Facilities ManagementUtilities & Engineering ServicesDuk
e
CHWP-2 RECLAIM WATER
ANSWERThe Reclamation Pond, is being constructed in-stream of
the storm drainage system.