319 W 9th St, Port Angeles, WA 98362 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.
You may view more detailed information for this home and can make an offer at
http://www.faira.com/listings/11880 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team
Inspection Report Addendum
3/30/2018
Trees have been trimmed on the South and East sides.
The door hardware works, however the handle droops.
The roof leak has been repaired. The pipe has been caulked with roofing caulk / sealant.
The vent fan has been properly connected. Apparently the exhaust hose was never installed. A new 4”
hose and clamps have been installed.
TPR pipe has been installed on the hot water heater.
Junction boxes in the basement now have covers.
Missing outlet covers have been installed.
Inspection Report
Provided by:
Phone: 360-775-0708
Email: [email protected]
Inspector: Tyson Zimmel
zimmelhomeinspections
Property Address:
319 W 9th St
Port Angeles, WA 98363
Table Of Contents:
Section number:Section name:
Report Information 1
Report Summary Page 2
Grounds 3
Exterior 4
Roofing 5
Heating - Air 6
Electrical 7
Plumbing 8
Interiors 9
Kitchen 10
Bath(s) 11
Basement 12
Garage - Laundry 13
Foundation - Crawl Space 14
zimmelhomeinspections
1 Report Information
Client Information
Client Name Christopher Ellis
Client Email [email protected]
Property Information
Approximate Year
Built
1937
Approximate Square
Footage
2,037
Number of Bedroom 4
Number of Bath 2.5
Direction House Faces South
Inspection Information
Inspection Date 3/21/2018
Inspection Time 3pm
Weather Conditions Dry
Outside Temperature 50 degrees
Price for Inspection $350
Sample Inspection Agreement
WITHIN THE SCOPE OF THE INSPECTION
The scope of this inspection and report is limited to a visual inspection of the systems and components
as listed below, in order to identify those, if any, which may need replacement or repair. See Standards
of Practice for a detailed description of the scope of inspection.
Exterior:
Landscaping, Retaining Walls, Gutters, Downspouts, Sidewalks and Driveways (both the condition of
and as they affect foundation drainage,) Roof, Chimney, Flashing, and Valleys, (for evidence of water
penetration and a description of materials,) Siding, Fascia, Soffit, Walls, Widows, Doors, Foundation,
Attached Porches/ Decks/ Balconies/ Patios/ Garages (both structural and condition of.)
Interior:
Plumbing System: Water Supply/Drains/Vents/Water Heaters/Fixtures, and Locating (But Not Testing)
Shut Off Valves; Electrical System: Service Drop, Service Panel, Ground Wire, GFCI Plugs, Switches,
Receptacles, Installed Fixtures, and Smoke Detectors; Heating/Cooling System: Permanent Systems,
Operating Controls/Filters/Ducts, Insulation, Vapor Barrier, and Ventilation; Bathrooms/Kitchen/Other
Rooms: Doors/Windows/Walls/Floors (as to general condition), Cabinets, Counter tops, and Installed
Fixtures; Structure: Ceilings/Walls/Floors, Stairs/Basements/Attic/Crawl Spaces (if readily accessible)
(as to evidence of water damage and general condition.)
- The scope of the inspection is limited to the description and the general condition of the above systems.
3 34/
zimmelhomeinspections
OUTSIDE THE SCOPE OF THE INSPECTION
-Any area which is not exposed to view or is inaccessible because of soil, walls, floors, carpets, ceilings,
furnishings, lack of access or crawl spaces or any major system (water or electrical systems, heating
system, or air conditioner) that is not currently functional is not included in this inspection.
-The inspection does not include any destructive testing or dismantling. Client agrees to assume all the
risk for all conditions which are concealed from view at the time of the inspection. This is not a home
warranty, guarantee, insurance policy, or substitute for real estate disclosures which may be required by
law. Whether or not they are concealed, the following are outside the scope of the inspection;
- Building code or zoning ordinance violations - Thermostatic or time clock controls or Low Voltage
wiring systems - Geological stability or soils conditions - Water softener or water purifier systems or
solar heating systems - Structural stability or engineering analysis - Saunas, steam baths, or fixtures and
equipment - Building value appraisal or cost estimates - Pools or spa bodies or sprinkler systems and
underground piping - Radio-controlled devices, automatic gates, elevators, lifts, and dumbwaiters -
Furnace heat exchanger, freestanding appliances, security alarms or personal property - Specific
components noted as being excluded on the individual system inspection form - Adequacy or efficiency
of any system or component - Prediction of life expectancy of any item.
- The Inspector is a home inspection generalist and is not acting as an engineer or expert in any craft or
trade. If the Inspector recommends consulting other specialized experts, Clients do so at Client’s
expense.
CONFIDENTIAL REPORT
-The written report to be prepared by the Inspector shall be considered the final and exclusive findings of
the Inspector/Inspection Company regarding the home inspection at the Inspection Address. The
inspection report to be prepared for the Client is solely and exclusively for the Client’s own information
and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the
inspection report and agrees not to disclose any part of it to any other person with the exception of the
seller and/or the real estate agents directly involved in this transaction. Client(s) or the inspector may
distribute copies of the inspection report to the seller and real estate agents directly involved in this
transaction, but neither the seller nor the real estate agent are intended beneficiaries of this Agreement or
the inspection report. Client agrees to indemnify, defend, and hold the Inspector/inspection Company
harmless from any third party claims arising out of the Client's or Inspectors distribution of the
inspection report.
DISPUTES
· Client understands and agrees that the Inspector/Inspection Company is not an insurer, that the price
paid for the subject inspection and report is based solely on the service provided. Client also agrees that
any claim of failure in the accuracy of the report shall be reported to the Inspector/Inspection Company
within five business days of discovery and that failure to notify the inspector within that time period
shall constitute a waiver of any and all claims. The Inspector/Inspection Company shall have five
business days to respond to the claim. If the Inspector/Inspection Company fails to satisfy the claim,
liability shall be limited to a refund of the price paid for the Inspection and Report.
Definition of conditions:
AS = Appears Serviceable: The item appeared to be in working or usable condition with no
major discrepancies noted.
4 34/
zimmelhomeinspections
R = Repair: The item was at or near the end of its useful lifespan. A certified professional
should be contacted for further evaluation and repair.
S = Safety Issue: The item is considered a safety hazard and can cause harm to people or
property. These items need to be repaired as soon as possible.
NI = Not Inspected: The item was not inspected during the inspection.
5 34/
zimmelhomeinspections
2 Report Summary Page
This is only a summary of the inspection report and is not a complete list of discrepancies.
CommentCondition#Section
Grounds 3 The trees on the south and east side of the home should be trimmed
back so they are not touching or overhanging the home.
Exterior 4 The deck railing is not supported using any support post. The entire
railing is built out of balusters. There should be a support post for the
railing every six feet.
The south support post have been added onto meaning the deck was
raised by stacking a 4x4 on top of the existing 4x4 post. These will
need to be either replaced or metal strapping added to hold them
together.
The south corner of the deck is sloping and some leveling may be
required. It is suggested that a "Licensed General Contractor" be
contacted for further evaluation and repair.
Exterior 7 The thermal pane window(s) at appear to have lost its / their thermal
seal at the south living room windows. Moisture, fogging, and hazing
are common signs of this condition. While mostly cosmetic, this
condition is generally not repairable. Correction would require
replacement of the window(s) or window pane(s). These windows
go all the way to the ground and will need to be a tempered window
when replaced.
The basement bathroom window is broken and will need replaced.
Exterior 8 The exterior north door out of the dining rooms hardware did not
work at time of inspection.
Roofing 11 The roof covering shows normal wear for its age and appeared to be
in serviceable condition at the time of the inspection.
On the south side of the roof there was some debris that need to be
removed.
Roofing 13 I recommend extending the gutters drain pipe that is draining off
under the deck. These are pouring out under the deck and can wash
out dirt that is supporting the support post.
Roofing 14 There is a roof leak around the plumbing stack on the west side of the
6 34/
zimmelhomeinspections
home over the master bedroom. There is also signs of moisture on
the sheathing on the west side of the attic over the master bedroom.
Upon further inspection the vent fan for the master bath does not vent
out and is putting moisture into the attic. It is suggested that a
"Licensed Roofing Contractor" be contacted for further evaluation
and repair.
Heating - Air 20 The AC was not tested due to the temperature outside. Testing below
65 degrees can cause harm to the system.
Plumbing 27 T P R (temperature pressure relief) valve overflow pipe was missing
at the time of the inspection. Recommend installation of an extension
pipe for increased safety. Client should consult a licensed plumber
for additional information. The water heater is from 2008.
Interiors 34 Reverse polarity was noted at outlet(s) located at the east living room,
basement bathroom and upstairs south bedroom. Reverse polarity,
(hot and ground / neutral reversed) are usually corrected by minor
wiring adjustments at the specified item. However, when a number
of these conditions are observed, client should consult a licensed
electrician.
Interiors 38 The gas fireplace pilot was not lit or fuel / gas was turned off. The
gas fireplace could not be fully inspected. Lighting of pilots or
adjustments of automatic ignition systems is not performed as part of
this inspection. Client is advised to obtain information from the
manufacturer regarding use, maintenance, and carbon monoxide risks,
if any.
Bath(s) 58 Cracked glass pane(s) were observed at basement bathroom.
Recommend repair as needed.
Bath(s) 60 GFIC (Ground Fault Interrupter Circuit) receptacle circuit (a safety
device for outlets near water) recommended at all bathroom outlets.
Bath(s) 62 Window vent only in the upstairs bathroom. I recommend adding a
vent fan.
Bath(s) 65 The bathtub faucet in the upstairs bath is dripping out of the handle
and I recommend caulking around where the shower head comes out
of the shower surround.
Basement 74 There are two open junction boxes at the ceiling in the basement and
an outlet that is missing its cover. All these should be covers
installed.
Foundation - Crawl
Space
81 The insulation has been pulled down by rodents and will need to be
fixed. I recommend a pest company remove all rodents before fixing
insulation.
7 34/
zimmelhomeinspections 3 Grounds
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
3 Grounds
Grading
Grading Slope The site is flat next to the foundation and slopes off to the west
Grading of the soil near the foundation appears to be in serviceable
condition. AS1) Grading Conditions
Driveways - Sidewalks - Walkways
Driveway Material Street parking
Sidewalk Material Concrete
The visible areas of the sidewalk appeared to be in serviceable condition
at the time of the inspection. AS2) Sidewalk Conditions
Vegetation
The trees on the south and east side of the home should be trimmed
back so they are not touching or overhanging the home. R3) Vegetation
Conditions
8 34/
zimmelhomeinspections 3 Grounds
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
9 34/
zimmelhomeinspections 4 Exterior
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
4 Exterior
Front - Back Entrance
Front Entrance Type Deck
The deck railing is not supported using any support post. The entire
railing is built out of balusters. There should be a support post for the
railing every six feet.
The south support post have been added onto meaning the deck was
raised by stacking a 4x4 on top of the existing 4x4 post. These will
need to be either replaced or metal strapping added to hold them
together.
The south corner of the deck is sloping and some leveling may be
required. It is suggested that a "Licensed General Contractor" be
contacted for further evaluation and repair.
R4) Front Entrance
Conditions
No support post in deck railing South corner is sloping
10 34/
zimmelhomeinspections 4 Exterior
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Back Entrance Type Deck
The visible and accessible areas of the deck appeared to be in
serviceable condition at the time of the inspection. AS5) Back Entrance
Conditions
Exterior Walls
Structure Type Wood frame
Exterior Wall Covering The visible and accessible areas of the exterior siding material are wood
shingles.
The visible and accessible portions of the exterior wall coverings
appeared to be in serviceable condition at the time of the inspection. AS6) Exterior Wall
Conditions
Exterior Windows - Doors
Window Type Sliding
Window Material Vinyl and aluminum
The thermal pane window(s) at appear to have lost its / their thermal
seal at the south living room windows. Moisture, fogging, and hazing R7) Window Conditions
11 34/
zimmelhomeinspections 4 Exterior
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
are common signs of this condition. While mostly cosmetic, this
condition is generally not repairable. Correction would require
replacement of the window(s) or window pane(s). These windows go
all the way to the ground and will need to be a tempered window when
replaced.
The basement bathroom window is broken and will need replaced.
The exterior north door out of the dining rooms hardware did not work
at time of inspection. R8) Exterior Door
Conditions
12 34/
zimmelhomeinspections 4 Exterior
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Exterior Water Faucet(s)
Faucet Location All sides of the home
The hose faucets appeared to be in serviceable condition at the time of
the inspection. These should be drained prior to freezing temperatures.
The water pressure at the home was 60psi, which is within normal
range.
AS9) Faucet Conditions
Exterior Electrical
Appears Serviceable AS10) Electrical
Conditions
13 34/
zimmelhomeinspections 5 Roofing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
5 Roofing
Roof Covering
Method of Inspection The roof was inspected by observing from a ladder placed at the edge of the
roof.
Roof Style Gable
Roof Covering
Material
Metal
Number of Layers One
The roof covering shows normal wear for its age and appeared to be in
serviceable condition at the time of the inspection.
On the south side of the roof there was some debris that need to be
removed.
R11) Roof Covering
Condition
14 34/
zimmelhomeinspections 5 Roofing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
The exposed flashings appeared to be in serviceable condition at the
time of inspection. AS12) Flashing Conditions
I recommend extending the gutters drain pipe that is draining off under
the deck. These are pouring out under the deck and can wash out dirt
that is supporting the support post.
R13) Gutter &
Downspout Conditions
15 34/
zimmelhomeinspections 5 Roofing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Attic Area
Attic Access Master bathroom and upstairs hall way
Method of Inspection Entered attic area.
Roof Frame Type The roof framing is constructed with truss framing over bedroom and rafter
framed over rest of home
There is a roof leak around the plumbing stack on the west side of the
home over the master bedroom. There is also signs of moisture on the
sheathing on the west side of the attic over the master bedroom. Upon
further inspection the vent fan for the master bath does not vent out and
is putting moisture into the attic. It is suggested that a "Licensed
Roofing Contractor" be contacted for further evaluation and repair.
R14) Attic Conditions
16 34/
zimmelhomeinspections 5 Roofing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Attach vent fan from master bath
Attic Ventilation Type Soffit vents Ridge Vents
Attic Ventilation
Conditions
Appears Serviceable
Attic Insulation Type Batt Insulation
The attic has fiberglass batt insulation. The approximate depth of the
insulation is 8 to 10 inches. This appears adequate. AS15) Attic Insulation
Conditions
17 34/
zimmelhomeinspections 6 Heating - Air
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
6 Heating - Air
Heating
Location of Unit Basement
Heating Type Heat Pump
Energy Source Electric
The heating system was operational at time of inspection. This is not an
indication of future operation or condition. I recommend this be
serviced annually.
AS16) Unit Conditions
Distribution Type The visible areas of the heat distribution system is duct work with registers.
The visible and accessible areas of the distribution system appeared to
be in serviceable condition at the time of inspection. AS17) Distribution
Conditions
The visible and accessible portion of the venting flue appeared to be in
serviceable condition at the time of the inspection. AS18) Ventilation
Conditions
The normal operating controls appeared to be serviceable at the time of
the inspection. AS19) Thermostat
Condition
Air Condition - Cooling
Type of Cooling System Split system
AC Unit Power 240V
The AC was not tested due to the temperature outside. Testing below
65 degrees can cause harm to the system. NI20) AC Unit Conditions
18 34/
zimmelhomeinspections 7 Electrical
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
7 Electrical
Service Drop - Weatherhead
Electrical Service Type The electrical service is overhead.
Electrical Service
Material
Aluminum
Number of Conductors Three
The main service entry appeared to be in serviceable condition at the
time of inspection. AS21) Electrical Service
Conditions
Main Electrical Panel
Main Disconnect
Location
At Main Panel
Electric Panel Location The main electric panel is located at the basement.
Panel Amperage Rating 200 amp
Circuit Protection Type Breakers
The main power cable is aluminum. The branch cables are copper. AS22) Wiring Methods
The main panel appeared to be in serviceable condition at the time of
the inspection. AS23) Electrical Panel
Conditions
19 34/
zimmelhomeinspections 7 Electrical
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
20 34/
zimmelhomeinspections 8 Plumbing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
8 Plumbing
Water Main Line
Main Shutoff Location The main valve is located at the basement.
Main Line Material The visible material of the main line / pipe appears to be copper.
The visible portion of the main pipe and valve appeared to be in
serviceable condition at the time of the inspection. AS24) Main Line & Valve
Conditions
Water Supply Lines
Supply Line Material The visible material used for the supply lines is copper.
The visible portions of the supply lines appeared to be in serviceable
condition at the time of inspection. All of the supply lines were not
fully visible or accessible at the time of the inspection.
AS25) Supply Line
Conditions
Drain - Waste Lines
Drain Line Material The visible portions of the waste lines are galvanized. The visible portions of
the waste lines are plastic.
The visible portions of the waste lines appeared to be in serviceable
condition at the time of inspection. All of the waste lines were not fully
visible or accessible at the time of the inspection.
AS26) Drain Line
Conditions
Water Heater(s)
Water Heater Type Electric
Water Heater Location Basement
Water Heater Capacity 50 Gallon
T P R (temperature pressure relief) valve overflow pipe was missing at
the time of the inspection. Recommend installation of an extension pipe
for increased safety. Client should consult a licensed plumber for
additional information. The water heater is from 2008.
R27) Water Heater
Conditions
21 34/
zimmelhomeinspections 8 Plumbing
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
22 34/
zimmelhomeinspections 9 Interiors
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
9 Interiors
Walls - Ceilings - Floors
The general condition of the walls appeared to be in serviceable
condition at the time of the inspection. AS28) Wall Conditions
The general condition of the ceilings appeared to be in serviceable
condition at the time of the inspection. AS29) Ceiling Conditions
The general condition of the visible and accessible portions of the floors
appeared to be in serviceable condition at the time of the inspection. AS30) Floor Conditions
Appears Serviceable AS31) Heat Source
Conditions
Windows - Doors
The sample of windows tested were operational at the time of the
inspection. AS32) Interior Window
Conditions
The interior doors appeared to be in serviceable condition at the time of
the inspection. AS33) Interior Door
Conditions
Electrical Conditions
Reverse polarity was noted at outlet(s) located at the east living room,
basement bathroom and upstairs south bedroom. Reverse polarity, (hot
and ground / neutral reversed) are usually corrected by minor wiring
adjustments at the specified item. However, when a number of these
conditions are observed, client should consult a licensed electrician.
R34) Electrical
Conditions
Appears Serviceable AS35) Lighting Conditions
Appears Serviceable AS36) Smoke Detector
Conditions
23 34/
zimmelhomeinspections 9 Interiors
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Appears Serviceable AS37) CO Detector
Conditions
Fireplace
Fireplace Location A fireplace is located at the living room.
Fireplace materials The fireplace is metal/pre-fabricated.
The gas fireplace pilot was not lit or fuel / gas was turned off. The gas
fireplace could not be fully inspected. Lighting of pilots or adjustments
of automatic ignition systems is not performed as part of this inspection.
Client is advised to obtain information from the manufacturer regarding
use, maintenance, and carbon monoxide risks, if any.
NI38) Fireplace
Conditions
24 34/
zimmelhomeinspections 10 Kitchen
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
10 Kitchen
Walls - Ceilings - Floors
The general condition of the walls appeared to be in serviceable
condition at the time of the inspection. AS39) Wall Conditions
The general condition of the ceilings appeared to be in serviceable
condition at the time of the inspection. AS40) Ceiling Conditions
The general condition of the visible and accessible portions of the floors
appeared to be in serviceable condition at the time of the inspection. AS41) Floor Conditions
Appears Serviceable AS42) Heat Source
Conditions
Windows - Doors
The sample of windows tested were operational at the time of the
inspection. AS43) Kitchen Window
Conditions
The interior doors appeared to be in serviceable condition at the time of
the inspection. AS44) Kitchen Door
Conditions
Electrical Conditions
Appears Serviceable AS45) Electrical
Conditions
Appears Serviceable AS46) Lighting Conditions
Kitchen Sink - Counter tops - Cabinets
The visible portion kitchen counters appeared to be in serviceable
condition at the time of the inspection. AS47) Counter Conditions
The kitchen cabinets appeared to be in serviceable condition at the time
of inspection. AS48) Cabinet Conditions
The kitchen sink appeared to be in serviceable condition at the time of
the inspection. The faucet appeared to be in serviceable condition at the
time of the inspection. The visible areas of the plumbing under the
kitchen sink appeared to be in serviceable condition at the time of the
inspection.
AS49) Sink Plumbing
Conditions
The sink disposal was operable at the time of the inspection. Client
should consult a licensed plumber, manufacturer, or disposal supply
company for information on proper usage and safety related concerns.
AS50) Garbage Disposal
Condition
Appliances
Stove - Range Type The oven is electric.
The oven was in operational condition at the time of the inspection.
This does not however guarantee future conditions after the time of
inspection.
AS51) Stove - Range
Condition
25 34/
zimmelhomeinspections 10 Kitchen
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
This is the style of hood fan that recirculates the air into the room.
Today's standards require the hood to be vented to the exterior. AS52) Hood Fan
Conditions
The dishwasher appeared to be in serviceable condition at the time of
the inspection. This does not however guarantee future performance or
conditions.
AS53) Dishwasher
Conditions
26 34/
zimmelhomeinspections 11 Bath(s)
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
11 Bath(s)
Walls - Ceilings - Floors
The general condition of the walls appeared to be in serviceable
condition at the time of the inspection. AS54) Wall Conditions
The general condition of the ceilings appeared to be in serviceable
condition at the time of the inspection. AS55) Ceiling Conditions
The general condition of the visible and accessible portions of the floors
appeared to be in serviceable condition at the time of the inspection. AS56) Floor Conditions
Appears Serviceable AS57) Heat Source
Conditions
Windows - Doors
Cracked glass pane(s) were observed at basement bathroom.
Recommend repair as needed. R58) Bathroom Window
Conditions
The interior doors appeared to be in serviceable condition at the time of
the inspection. AS59) Bathroom Door
Conditions
Electrical Conditions
GFIC (Ground Fault Interrupter Circuit) receptacle circuit (a safety
device for outlets near water) recommended at all bathroom outlets. R60) Electrical
Conditions
Appears Serviceable AS61) Lighting Conditions
Window vent only in the upstairs bathroom. I recommend adding a vent
fan. R62) Vent Fan
Conditions
Bathroom Sink
Appears Serviceable AS63) Counter - Cabinet
Conditions
27 34/
zimmelhomeinspections 11 Bath(s)
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
The sink appeared to be in serviceable condition at the time of
inspection in bath AS64) Sink Conditions
Shower - Tub - Toilet
The bathtub faucet in the upstairs bath is dripping out of the handle and
I recommend caulking around where the shower head comes out of the
shower surround.
R65) Shower - Tub
Conditions
The toilet appeared to be in serviceable condition at the time of
inspection in bath AS66) Toilet Conditions
28 34/
zimmelhomeinspections 12 Basement
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
12 Basement
Walls - Ceilings - Floors
The interior stairs appeared serviceable at the time of the inspection. AS67) Basement Stair
Conditions
The general condition of the walls appeared to be in serviceable
condition at the time of the inspection. AS68) Wall Conditions
The general condition of the ceilings appeared to be in serviceable
condition at the time of the inspection. AS69) Ceiling Conditions
The general condition of the visible and accessible portions of the floors
appeared to be in serviceable condition at the time of the inspection. AS70) Floor Conditions
Appears Serviceable AS71) Heat Source
Conditions
Windows - Doors
The sample of windows tested were operational at the time of the
inspection. AS72) Basement Window
Conditions
The interior doors appeared to be in serviceable condition at the time of
the inspection. AS73) Basement Door
Conditions
Electrical Conditions
There are two open junction boxes at the ceiling in the basement and an
outlet that is missing its cover. All these should be covers installed. R74) Electrical
Conditions
29 34/
zimmelhomeinspections 12 Basement
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
Appears Serviceable AS75) Lighting Conditions
30 34/
zimmelhomeinspections 13 Garage - Laundry
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
13 Garage - Laundry
Laundry Room
Location The laundry facilities are located in the basement and in the master bedroom
area
The visible and accessible portions of the laundry plumbing components
appeared to be in serviceable condition at the time of inspection. AS76) Laundry Room
Conditions
31 34/
zimmelhomeinspections 14 Foundation - Crawl Space
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
14 Foundation - Crawl Space
Foundation
Foundation Type Crawl Space
Foundation Material Concrete
Appears Serviceable AS77) Foundation
Conditions
Flooring Structure
Flooring Support Type The wood framing floor system was constructed of pre-fabricated truss joists.
The visible and accessible areas of the wood framing system appeared
to be in serviceable condition at the time of the inspection. AS78) Flooring Support
Conditions
Moisture Barrier - Venting - Insulation
Appears Serviceable AS79) Moisture Barrier
Conditions
Appears Serviceable AS80) Venting Conditions
The insulation has been pulled down by rodents and will need to be
fixed. I recommend a pest company remove all rodents before fixing
insulation.
R81) Insulation
Conditions
32 34/
zimmelhomeinspections 14 Foundation - Crawl Space
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
33 34/
zimmelhomeinspections 14 Foundation - Crawl Space
AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected
In the south crawl space there is an open junction box that needs a cover
installed. AS82) Crawl Space
Electrical
34 34/
ICN 10133AE019 WSDA INSPECTION CONTROL NUMBER
** This report is not valid without the above number**
WAC 16-228-2045 requires that a diagram be prepared for WDO Inspection Reports. A copy is available upon request.
Inspection Date: 3/21/2018 File No: 1 Time: 3pm Visit: 1
Inspection Firm: Zimmel Home Inspections
Address:172 East Arnette Rd
City: Port Angeles WA ZIP: 98362
Phone: 360-775-0708 E-mail: [email protected]
Structural Pest Inspector: Tyson Zimmel WSDA License # 87491
Structure Inspected: 319 W 9th St, Port Angeles, WA 98363
Client's Name: Christopher Ellis
NOTE: ONLY THE ABOVE NAMED CLIENT IS ENTITLED TO RELY ON THE CONTENTS OF THIS REPORT.
In accordance with the provisions of the Revised Code of Washington (RCW) 15.58.450, this report relates to a single sale, transfer, exchange, or refinance of a
property. It is not transferable to, and may not be relied upon, by parties involved in any subsequent sale, transfer, exchange, or refinance of the same property.
COMPLETE WOOD DESTROYING ORGANISM
INSPECTION REPORT SUMMARY OF FINDINGS YES NO*
VISIBLE EVIDENCE OF WOOD DESTROYING INSECTS [ ] [ x ]
VISIBLE EVIDENCE OF ACTIVE WOOD DECAY FUNGI [ ] [ x ]
VISIBLE EVIDENCE OF DAMAGE BY WOOD DESTROYING ORGANISMS [ x ] [ ]
VISIBLE EVIDENCE OF CONDITIONS CONDUCIVE TO WOOD DESTROYING ORGANISMS [ ] [ x ]
INACCESSIBLE AREAS [ ] [ x ]
* THERE IS REMAINING VISIBLE EVIDENCE OF INACTIVE: [ ]Carpenter Ants; [ ]Subterranean Termites; [ x ]Anobiid
Beetles; [ ]Moisture Ants; [ ]Dampwood Termites; [ ]Other Wood Boring Beetles; [ ]Past water events. Neither the inspector, nor
the inspecting firm, shall be liable for any corrective actions required by future inspections as a consequence of this evidence. See the
FINDINGS and DIAGRAM page(s) of, [ ]This report; [ ]Previous report(s) bearing the same ICN for details.
LIMITATION OF LIABILITY
The above inspecting firm and inspector endeavor to perform their services in a professional manner consistent with the care and skill ordinarily exercised by structural
pest inspection professionals. The inspecting firm will re-perform any services not meeting this standard without additional compensation. The inspecting firm's total
liability for the inspections made of the inspected structure shall be limited to the amount of financial responsibility prescribed under Washington State law. The
inspecting firm will not be liable for any special, incidental, punitive or consequential damages, whether foreseen or unforeseen, regardless whether liability is based on breach of contract, breach of express or implied warranty, negligence, strict liability, tort, or otherwise.
COMMENTS
Rev: 2/1/2009 WSPMA Page 1 of ______ pages
WOOD DESTROYING ORGANISM INSPECTION STANDARDS of the
WASHINGTON STATE PEST MANAGEMENT ASSOCIATION
COMPLETE WOOD DESTROYING ORGANISM (WDO) INSPECTION REPORT.
This report is prepared from an inspection conducted by a Washington State Department of Agriculture licensed Structural Pest Inspector in accordance with
Washington Administrative Code 16-228-2005 through 16-228-2045. Opinions contained herein are based on conditions visible and evident at the time of the
inspection. This report does not warrant, represent, or guarantee that the structure reported on is free from evidence of WDO's, their damage, or conditions
conducive to WDO's; nor does it represent or guarantee that the total damage, infestation, or infection is limited to that disclosed in this report.
I. INSPECTION PROCEDURES
The inspector shall make a thorough inspection, using accepted methods and practices, of the subject to render an opinion on the presence of, or damage from WDO's as well an conditions conducive to such WDO's.
AREAS INSPECTED shall include: structural exterior (accessible both visibly and physically to an inspector at ground level); accessible structure interior; accessible
sub structural crawl space(s); garages, carports and decks which are attached to the structure. Deck inspection shall include; railings, wooden steps, and accessible
wooden surface materials, as well as deck substructures which are accessible (those with at least a 5 foot soil to joist clearance, or elevated decks which can be suitably
reached using a 6 foot step ladder). WOOD DESTROYING ORGANISMS shall include: subterranean termites; dampwood termites; carpenter ants; moisture ants; wood boring beetles of the family
Anobiidae; and wood decay fungus (rot). The inspector will not assume any responsibility for WDO's that were not detected during their dormant season. When
evidence of moisture ants, dampwood termites, wood infesting anobiids, or wood decay fungi is detected during a Complete WDO Inspection, the inspector must
identify and report the condition(s) conducive to such infestations. It must be stated in the report that such infestations may be eliminated by removal of all infested
wood and correction of any contributing conducive conditions. CONDUCIVE CONDITIONS, as determined by the inspector, shall include, but not be limited to: inadequate clearance; earth to wood contact; conducive debris in
the crawl space; inadequate ventilation; excessive moisture; vegetation contact with the structure; bare ground in the crawl space; existing or seasonal standing water in
the crawl space; failed caulking or grout in water splash areas; and/or non-functioning gutter systems.
II. LIMITATIONS OF INSPECTIONS
The inspecting firm shall not be held responsible by any party for any condition or consequence of WDO's which is beyond the scope of inspection. The scope,
defined in Section I, INSPECTION PROCEDURES, is limited as follows:
(a) INACCESSIBLE AREAS: Certain areas of a structure, which are inaccessible by their nature, may be subject to infestation by WDO's yet cannot be inspected
without excavation or unless physical obstructions are removed. Such areas include, but are not limited to: wall voids; spaces between floors; substructures concealed
by sub-floor insulation or those with inadequate clearance; floors beneath coverings; sleeper floors; areas concealed by furniture, appliances, and/or personal
possessions; and deck substructures with less that 5 foot clearance. (b) ROOF SYSTEMS AND ATTIC AREAS: Roof systems, roof coverings and attic areas are excluded from this report. This report may note, at the discretion of the
inspector, visual evidence of infestation and/or infections of WDO's in the portions of the eaves that are visible and accessible from the ground. Nor opinion is rendered
nor guarantee implied concerning the watertight integrity, the condition, or the future life of the roof system. Any comment(s) made regarding an obvious condition of
(a) component(s) of the roof system or attic space(s) shall not imply an extension to the scope of inspection. If a more qualified opinion is desired, the services of a licensed roof system professional should be obtained.
(c) SHEDS AND OUTBUILDINGS: Sheds, garages, carports, decks and other structures, which are not attached to the main structure by a roof system or foundation,
are excluded from this report unless specifically requested and noted. The inspecting firm reserves the right to charge additionally to inspect any unattached structures.
(d) CLIMATIC CONDITIONS: In certain geographical areas of Washington State where wet climate is common, and due to their construction and materials,
structures may be subject to conditions from normal weathering. Such conditions as cracking, checking, and/or warping of doors, window casings, siding, and non-supporting wooden members shall not be reported on inspection reports except at the discretion of the inspector. Inspectors are not required to report on any wood
destroying organism infestation, infection, or other condition that might be subject to seasonal constraints or environmental conditions if evidence of those constraints
or conditions is not visible at the time of the inspection.
(e) MOLD: Molds, mildews, and other fungal growth (except wood decay fungi) shall be reported on only to the extent that they indicate an excessive moisture
condition which may be conducive to WDO's. The inspector is not liable or responsible for determining the type of mold, mildew, or other fungi present, nor shall the inspector be liable or responsible for determining the possible health hazards associated with the presence of molds, mildews, or other fungi. This report is not, nor shall
the inspector perform a mold inspection or investigation. If a more qualified opinion is desired, the services of a toxicologist or certified industrial hygienist should be
obtained.
(f) STRUCTURAL ASSESSMENT: While it may be possible for the inspector to note damaged materials, neither the inspector nor the inspection firm is liable or
responsible in any way to determine the structural integrity of any building materials. If a more qualified opinion is desired, the services of a licensed, qualified contractor or structural engineer should be obtained.
(g) REMAINING EVIDENCE: In certain situations, it may not be practical to eliminate all evidence of previous WDO activity (e.g., carpenter ant frass, insect parts,
or subterranean termite scaling), or evidence of conducive conditions, (e.g., water staining). Although noted, this evidence may remain after corrections have been made
or if it is the inspector's opinion that the evidence is from inactive WDOs and no corrections are recommended. Neither the inspector nor the inspecting firm shall be
liable or responsible for any corrective action required by future inspections in regards to this remaining evidence. III. REPORTS
(a) WRITTEN REPORT: The inspecting firm shall not issue any complete wood destroying organism report unless a Washington State Department of Agriculture
licensed structural pest inspector from that firm has made a careful and thorough inspection of the structure in conformance with and subject to the limitations within
these standards. Reports shall include a diagrams and a description of the findings to help identify locations of the findings as well as inaccessible areas not identified in
section II (a) of these standards. IV. WORK RECOMMENDATIONS AND TREATMENTS
(a) NO WARRANTIES OF CORRECTIVE WORK: Neither the inspector nor the inspecting firm will evaluate or warranty the quality of workmanship, the
compliance with any applicable building codes, nor the suitability of use or any repairs, corrections, or treatments recommended within this report. Compliance with
Washington State pesticide application laws and applicable building codes (current revisions) is the responsibility of the property owner and those performing the work.
It is strongly recommended that those parties performing any corrections or treatments be licensed, bonded and qualified professionals providing warranted services. (b) CONDITIONS REVEALED DURING THE PERFORMANCE OF RECOMMENDATIONS: Should any WDO damage, or conducive condition be revealed
during the performance of any recommendations, whether performed by the owner, the purchaser, a contractor, or any other party of interest, the inspecting firm must
be notified of such, and be given a reasonable opportunity for re-inspecting and determining the need for any additional corrective measures before such conditions are
covered. The owner, purchaser, or any other person performing the work shall be responsible for notifying the inspector. Nothing contained herein shall prevent the
inspecting firm from assessing additional charges for each additional inspection.
NOTE: The Washington State Pest Management Association (WSPMA), as a service to inspection firms, has developed this form and these Standards of Practice. By
doing so, the WSPMA does not certify that the inspecting firm is a member of the WSPMA, or that the inspector is qualified to perform the inspection/. The WSPMA
shall not be a party to any claim or action by the buyer, seller, or other interested party against the inspecting firm solely by reason of making this report form and these
Standards of Practice available for use.
Rev: 2/01/2009
Findings
Inactive Anobiid Beetle: Around the crawl space entrance on the north side of the
home there is some Anobiid beetle damage. This looks to be from an old
infestation and is inactive. This damage is not structural and was only seen in this
area.
Important information about the attached
Complete Wood Destroying Organism Inspection Report.
Beginning January 1, 2004 the Washington State Pest Management Association has adopted a new
format for the Complete Wood Destroying Organism Inspection Report. This new format was
prompted, in part, by recent changes to Washington State Laws and Rules that pertain to Structural Pest
Inspections, (RCW 15.58.450 and WAC 16-228-2005 through 16-228-2045), and by changes in market
expectations. These changes were a cooperative effort involving members of all affected industries;
inspectors, real estate professionals, and lenders. This new inspection report format is easier to
understand, easier to enforce, and provides better protection for the consumer.
Washington State laws and rules do not recognize any difference between a “Preliminary Report” and a
“Final Report”. Therefore, this reporting format has been eliminated. There will only be one report: the
Complete Wood Destroying Organism Inspection Report. If you have questions regarding these changes,
contact the Washington State Pest Control Association (1-800-253-3836).
For your protection you are encouraged to have all findings corrected by licensed and bonded
contractors and to obtain and keep copies of all repair receipts. You may also elect to obtain a report
with “NO” findings. A report with “NO” findings does not indicate that the inspector is approving of
any work done to eliminate previously reported findings. It only indicates that there are no findings at
the time of the inspection. It must also be understood that remaining evidence may exist after all repairs
and corrections have been made. This evidence, while required to be reported, may be inconsequential.
The attached Washington State Pest Management Association Complete Wood Destroying
Organism Inspection Report Form has been reviewed by the Washington State Department of
Agriculture. The Department agrees that with an accurate inspection, and when filled out
properly, this form can meet the Wood Destroying Organism Inspection Reporting Criteria
found in WAC 16-228-2005 through 16-228-2045.