608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/11880 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Upload: others

Post on 30-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

319 W 9th St, Port Angeles, WA 98362 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/11880 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Page 2: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

Inspection Report Addendum

3/30/2018

Trees have been trimmed on the South and East sides.

The door hardware works, however the handle droops.

The roof leak has been repaired. The pipe has been caulked with roofing caulk / sealant.

The vent fan has been properly connected. Apparently the exhaust hose was never installed. A new 4”

hose and clamps have been installed.

TPR pipe has been installed on the hot water heater.

Junction boxes in the basement now have covers.

Missing outlet covers have been installed.

Page 3: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

Inspection Report

Provided by:

Phone: 360-775-0708

Email: [email protected]

Inspector: Tyson Zimmel

zimmelhomeinspections

Property Address:

319 W 9th St

Port Angeles, WA 98363

Page 4: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

Table Of Contents:

Section number:Section name:

Report Information 1

Report Summary Page 2

Grounds 3

Exterior 4

Roofing 5

Heating - Air 6

Electrical 7

Plumbing 8

Interiors 9

Kitchen 10

Bath(s) 11

Basement 12

Garage - Laundry 13

Foundation - Crawl Space 14

Page 5: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections

1 Report Information

Client Information

Client Name Christopher Ellis

Client Email [email protected]

Property Information

Approximate Year

Built

1937

Approximate Square

Footage

2,037

Number of Bedroom 4

Number of Bath 2.5

Direction House Faces South

Inspection Information

Inspection Date 3/21/2018

Inspection Time 3pm

Weather Conditions Dry

Outside Temperature 50 degrees

Price for Inspection $350

Sample Inspection Agreement

WITHIN THE SCOPE OF THE INSPECTION

The scope of this inspection and report is limited to a visual inspection of the systems and components

as listed below, in order to identify those, if any, which may need replacement or repair. See Standards

of Practice for a detailed description of the scope of inspection.

Exterior:

Landscaping, Retaining Walls, Gutters, Downspouts, Sidewalks and Driveways (both the condition of

and as they affect foundation drainage,) Roof, Chimney, Flashing, and Valleys, (for evidence of water

penetration and a description of materials,) Siding, Fascia, Soffit, Walls, Widows, Doors, Foundation,

Attached Porches/ Decks/ Balconies/ Patios/ Garages (both structural and condition of.)

Interior:

Plumbing System: Water Supply/Drains/Vents/Water Heaters/Fixtures, and Locating (But Not Testing)

Shut Off Valves; Electrical System: Service Drop, Service Panel, Ground Wire, GFCI Plugs, Switches,

Receptacles, Installed Fixtures, and Smoke Detectors; Heating/Cooling System: Permanent Systems,

Operating Controls/Filters/Ducts, Insulation, Vapor Barrier, and Ventilation; Bathrooms/Kitchen/Other

Rooms: Doors/Windows/Walls/Floors (as to general condition), Cabinets, Counter tops, and Installed

Fixtures; Structure: Ceilings/Walls/Floors, Stairs/Basements/Attic/Crawl Spaces (if readily accessible)

(as to evidence of water damage and general condition.)

- The scope of the inspection is limited to the description and the general condition of the above systems.

3 34/

Page 6: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections

OUTSIDE THE SCOPE OF THE INSPECTION

-Any area which is not exposed to view or is inaccessible because of soil, walls, floors, carpets, ceilings,

furnishings, lack of access or crawl spaces or any major system (water or electrical systems, heating

system, or air conditioner) that is not currently functional is not included in this inspection.

-The inspection does not include any destructive testing or dismantling. Client agrees to assume all the

risk for all conditions which are concealed from view at the time of the inspection. This is not a home

warranty, guarantee, insurance policy, or substitute for real estate disclosures which may be required by

law. Whether or not they are concealed, the following are outside the scope of the inspection;

- Building code or zoning ordinance violations - Thermostatic or time clock controls or Low Voltage

wiring systems - Geological stability or soils conditions - Water softener or water purifier systems or

solar heating systems - Structural stability or engineering analysis - Saunas, steam baths, or fixtures and

equipment - Building value appraisal or cost estimates - Pools or spa bodies or sprinkler systems and

underground piping - Radio-controlled devices, automatic gates, elevators, lifts, and dumbwaiters -

Furnace heat exchanger, freestanding appliances, security alarms or personal property - Specific

components noted as being excluded on the individual system inspection form - Adequacy or efficiency

of any system or component - Prediction of life expectancy of any item.

- The Inspector is a home inspection generalist and is not acting as an engineer or expert in any craft or

trade. If the Inspector recommends consulting other specialized experts, Clients do so at Client’s

expense.

CONFIDENTIAL REPORT

-The written report to be prepared by the Inspector shall be considered the final and exclusive findings of

the Inspector/Inspection Company regarding the home inspection at the Inspection Address. The

inspection report to be prepared for the Client is solely and exclusively for the Client’s own information

and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the

inspection report and agrees not to disclose any part of it to any other person with the exception of the

seller and/or the real estate agents directly involved in this transaction. Client(s) or the inspector may

distribute copies of the inspection report to the seller and real estate agents directly involved in this

transaction, but neither the seller nor the real estate agent are intended beneficiaries of this Agreement or

the inspection report. Client agrees to indemnify, defend, and hold the Inspector/inspection Company

harmless from any third party claims arising out of the Client's or Inspectors distribution of the

inspection report.

DISPUTES

· Client understands and agrees that the Inspector/Inspection Company is not an insurer, that the price

paid for the subject inspection and report is based solely on the service provided. Client also agrees that

any claim of failure in the accuracy of the report shall be reported to the Inspector/Inspection Company

within five business days of discovery and that failure to notify the inspector within that time period

shall constitute a waiver of any and all claims. The Inspector/Inspection Company shall have five

business days to respond to the claim. If the Inspector/Inspection Company fails to satisfy the claim,

liability shall be limited to a refund of the price paid for the Inspection and Report.

Definition of conditions:

AS = Appears Serviceable: The item appeared to be in working or usable condition with no

major discrepancies noted.

4 34/

Page 7: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections

R = Repair: The item was at or near the end of its useful lifespan. A certified professional

should be contacted for further evaluation and repair.

S = Safety Issue: The item is considered a safety hazard and can cause harm to people or

property. These items need to be repaired as soon as possible.

NI = Not Inspected: The item was not inspected during the inspection.

5 34/

Page 8: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections

2 Report Summary Page

This is only a summary of the inspection report and is not a complete list of discrepancies.

CommentCondition#Section

Grounds 3 The trees on the south and east side of the home should be trimmed

back so they are not touching or overhanging the home.

Exterior 4 The deck railing is not supported using any support post. The entire

railing is built out of balusters. There should be a support post for the

railing every six feet.

The south support post have been added onto meaning the deck was

raised by stacking a 4x4 on top of the existing 4x4 post. These will

need to be either replaced or metal strapping added to hold them

together.

The south corner of the deck is sloping and some leveling may be

required. It is suggested that a "Licensed General Contractor" be

contacted for further evaluation and repair.

Exterior 7 The thermal pane window(s) at appear to have lost its / their thermal

seal at the south living room windows. Moisture, fogging, and hazing

are common signs of this condition. While mostly cosmetic, this

condition is generally not repairable. Correction would require

replacement of the window(s) or window pane(s). These windows

go all the way to the ground and will need to be a tempered window

when replaced.

The basement bathroom window is broken and will need replaced.

Exterior 8 The exterior north door out of the dining rooms hardware did not

work at time of inspection.

Roofing 11 The roof covering shows normal wear for its age and appeared to be

in serviceable condition at the time of the inspection.

On the south side of the roof there was some debris that need to be

removed.

Roofing 13 I recommend extending the gutters drain pipe that is draining off

under the deck. These are pouring out under the deck and can wash

out dirt that is supporting the support post.

Roofing 14 There is a roof leak around the plumbing stack on the west side of the

6 34/

Page 9: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections

home over the master bedroom. There is also signs of moisture on

the sheathing on the west side of the attic over the master bedroom.

Upon further inspection the vent fan for the master bath does not vent

out and is putting moisture into the attic. It is suggested that a

"Licensed Roofing Contractor" be contacted for further evaluation

and repair.

Heating - Air 20 The AC was not tested due to the temperature outside. Testing below

65 degrees can cause harm to the system.

Plumbing 27 T P R (temperature pressure relief) valve overflow pipe was missing

at the time of the inspection. Recommend installation of an extension

pipe for increased safety. Client should consult a licensed plumber

for additional information. The water heater is from 2008.

Interiors 34 Reverse polarity was noted at outlet(s) located at the east living room,

basement bathroom and upstairs south bedroom. Reverse polarity,

(hot and ground / neutral reversed) are usually corrected by minor

wiring adjustments at the specified item. However, when a number

of these conditions are observed, client should consult a licensed

electrician.

Interiors 38 The gas fireplace pilot was not lit or fuel / gas was turned off. The

gas fireplace could not be fully inspected. Lighting of pilots or

adjustments of automatic ignition systems is not performed as part of

this inspection. Client is advised to obtain information from the

manufacturer regarding use, maintenance, and carbon monoxide risks,

if any.

Bath(s) 58 Cracked glass pane(s) were observed at basement bathroom.

Recommend repair as needed.

Bath(s) 60 GFIC (Ground Fault Interrupter Circuit) receptacle circuit (a safety

device for outlets near water) recommended at all bathroom outlets.

Bath(s) 62 Window vent only in the upstairs bathroom. I recommend adding a

vent fan.

Bath(s) 65 The bathtub faucet in the upstairs bath is dripping out of the handle

and I recommend caulking around where the shower head comes out

of the shower surround.

Basement 74 There are two open junction boxes at the ceiling in the basement and

an outlet that is missing its cover. All these should be covers

installed.

Foundation - Crawl

Space

81 The insulation has been pulled down by rodents and will need to be

fixed. I recommend a pest company remove all rodents before fixing

insulation.

7 34/

Page 10: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 3 Grounds

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

3 Grounds

Grading

Grading Slope The site is flat next to the foundation and slopes off to the west

Grading of the soil near the foundation appears to be in serviceable

condition. AS1) Grading Conditions

Driveways - Sidewalks - Walkways

Driveway Material Street parking

Sidewalk Material Concrete

The visible areas of the sidewalk appeared to be in serviceable condition

at the time of the inspection. AS2) Sidewalk Conditions

Vegetation

The trees on the south and east side of the home should be trimmed

back so they are not touching or overhanging the home. R3) Vegetation

Conditions

8 34/

Page 11: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 3 Grounds

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

9 34/

Page 12: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 4 Exterior

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

4 Exterior

Front - Back Entrance

Front Entrance Type Deck

The deck railing is not supported using any support post. The entire

railing is built out of balusters. There should be a support post for the

railing every six feet.

The south support post have been added onto meaning the deck was

raised by stacking a 4x4 on top of the existing 4x4 post. These will

need to be either replaced or metal strapping added to hold them

together.

The south corner of the deck is sloping and some leveling may be

required. It is suggested that a "Licensed General Contractor" be

contacted for further evaluation and repair.

R4) Front Entrance

Conditions

No support post in deck railing South corner is sloping

10 34/

Page 13: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 4 Exterior

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Back Entrance Type Deck

The visible and accessible areas of the deck appeared to be in

serviceable condition at the time of the inspection. AS5) Back Entrance

Conditions

Exterior Walls

Structure Type Wood frame

Exterior Wall Covering The visible and accessible areas of the exterior siding material are wood

shingles.

The visible and accessible portions of the exterior wall coverings

appeared to be in serviceable condition at the time of the inspection. AS6) Exterior Wall

Conditions

Exterior Windows - Doors

Window Type Sliding

Window Material Vinyl and aluminum

The thermal pane window(s) at appear to have lost its / their thermal

seal at the south living room windows. Moisture, fogging, and hazing R7) Window Conditions

11 34/

Page 14: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 4 Exterior

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

are common signs of this condition. While mostly cosmetic, this

condition is generally not repairable. Correction would require

replacement of the window(s) or window pane(s). These windows go

all the way to the ground and will need to be a tempered window when

replaced.

The basement bathroom window is broken and will need replaced.

The exterior north door out of the dining rooms hardware did not work

at time of inspection. R8) Exterior Door

Conditions

12 34/

Page 15: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 4 Exterior

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Exterior Water Faucet(s)

Faucet Location All sides of the home

The hose faucets appeared to be in serviceable condition at the time of

the inspection. These should be drained prior to freezing temperatures.

The water pressure at the home was 60psi, which is within normal

range.

AS9) Faucet Conditions

Exterior Electrical

Appears Serviceable AS10) Electrical

Conditions

13 34/

Page 16: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 5 Roofing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

5 Roofing

Roof Covering

Method of Inspection The roof was inspected by observing from a ladder placed at the edge of the

roof.

Roof Style Gable

Roof Covering

Material

Metal

Number of Layers One

The roof covering shows normal wear for its age and appeared to be in

serviceable condition at the time of the inspection.

On the south side of the roof there was some debris that need to be

removed.

R11) Roof Covering

Condition

14 34/

Page 17: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 5 Roofing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

The exposed flashings appeared to be in serviceable condition at the

time of inspection. AS12) Flashing Conditions

I recommend extending the gutters drain pipe that is draining off under

the deck. These are pouring out under the deck and can wash out dirt

that is supporting the support post.

R13) Gutter &

Downspout Conditions

15 34/

Page 18: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 5 Roofing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Attic Area

Attic Access Master bathroom and upstairs hall way

Method of Inspection Entered attic area.

Roof Frame Type The roof framing is constructed with truss framing over bedroom and rafter

framed over rest of home

There is a roof leak around the plumbing stack on the west side of the

home over the master bedroom. There is also signs of moisture on the

sheathing on the west side of the attic over the master bedroom. Upon

further inspection the vent fan for the master bath does not vent out and

is putting moisture into the attic. It is suggested that a "Licensed

Roofing Contractor" be contacted for further evaluation and repair.

R14) Attic Conditions

16 34/

Page 19: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 5 Roofing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Attach vent fan from master bath

Attic Ventilation Type Soffit vents Ridge Vents

Attic Ventilation

Conditions

Appears Serviceable

Attic Insulation Type Batt Insulation

The attic has fiberglass batt insulation. The approximate depth of the

insulation is 8 to 10 inches. This appears adequate. AS15) Attic Insulation

Conditions

17 34/

Page 20: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 6 Heating - Air

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

6 Heating - Air

Heating

Location of Unit Basement

Heating Type Heat Pump

Energy Source Electric

The heating system was operational at time of inspection. This is not an

indication of future operation or condition. I recommend this be

serviced annually.

AS16) Unit Conditions

Distribution Type The visible areas of the heat distribution system is duct work with registers.

The visible and accessible areas of the distribution system appeared to

be in serviceable condition at the time of inspection. AS17) Distribution

Conditions

The visible and accessible portion of the venting flue appeared to be in

serviceable condition at the time of the inspection. AS18) Ventilation

Conditions

The normal operating controls appeared to be serviceable at the time of

the inspection. AS19) Thermostat

Condition

Air Condition - Cooling

Type of Cooling System Split system

AC Unit Power 240V

The AC was not tested due to the temperature outside. Testing below

65 degrees can cause harm to the system. NI20) AC Unit Conditions

18 34/

Page 21: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 7 Electrical

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

7 Electrical

Service Drop - Weatherhead

Electrical Service Type The electrical service is overhead.

Electrical Service

Material

Aluminum

Number of Conductors Three

The main service entry appeared to be in serviceable condition at the

time of inspection. AS21) Electrical Service

Conditions

Main Electrical Panel

Main Disconnect

Location

At Main Panel

Electric Panel Location The main electric panel is located at the basement.

Panel Amperage Rating 200 amp

Circuit Protection Type Breakers

The main power cable is aluminum. The branch cables are copper. AS22) Wiring Methods

The main panel appeared to be in serviceable condition at the time of

the inspection. AS23) Electrical Panel

Conditions

19 34/

Page 22: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 7 Electrical

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

20 34/

Page 23: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 8 Plumbing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

8 Plumbing

Water Main Line

Main Shutoff Location The main valve is located at the basement.

Main Line Material The visible material of the main line / pipe appears to be copper.

The visible portion of the main pipe and valve appeared to be in

serviceable condition at the time of the inspection. AS24) Main Line & Valve

Conditions

Water Supply Lines

Supply Line Material The visible material used for the supply lines is copper.

The visible portions of the supply lines appeared to be in serviceable

condition at the time of inspection. All of the supply lines were not

fully visible or accessible at the time of the inspection.

AS25) Supply Line

Conditions

Drain - Waste Lines

Drain Line Material The visible portions of the waste lines are galvanized. The visible portions of

the waste lines are plastic.

The visible portions of the waste lines appeared to be in serviceable

condition at the time of inspection. All of the waste lines were not fully

visible or accessible at the time of the inspection.

AS26) Drain Line

Conditions

Water Heater(s)

Water Heater Type Electric

Water Heater Location Basement

Water Heater Capacity 50 Gallon

T P R (temperature pressure relief) valve overflow pipe was missing at

the time of the inspection. Recommend installation of an extension pipe

for increased safety. Client should consult a licensed plumber for

additional information. The water heater is from 2008.

R27) Water Heater

Conditions

21 34/

Page 24: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 8 Plumbing

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

22 34/

Page 25: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 9 Interiors

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

9 Interiors

Walls - Ceilings - Floors

The general condition of the walls appeared to be in serviceable

condition at the time of the inspection. AS28) Wall Conditions

The general condition of the ceilings appeared to be in serviceable

condition at the time of the inspection. AS29) Ceiling Conditions

The general condition of the visible and accessible portions of the floors

appeared to be in serviceable condition at the time of the inspection. AS30) Floor Conditions

Appears Serviceable AS31) Heat Source

Conditions

Windows - Doors

The sample of windows tested were operational at the time of the

inspection. AS32) Interior Window

Conditions

The interior doors appeared to be in serviceable condition at the time of

the inspection. AS33) Interior Door

Conditions

Electrical Conditions

Reverse polarity was noted at outlet(s) located at the east living room,

basement bathroom and upstairs south bedroom. Reverse polarity, (hot

and ground / neutral reversed) are usually corrected by minor wiring

adjustments at the specified item. However, when a number of these

conditions are observed, client should consult a licensed electrician.

R34) Electrical

Conditions

Appears Serviceable AS35) Lighting Conditions

Appears Serviceable AS36) Smoke Detector

Conditions

23 34/

Page 26: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 9 Interiors

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Appears Serviceable AS37) CO Detector

Conditions

Fireplace

Fireplace Location A fireplace is located at the living room.

Fireplace materials The fireplace is metal/pre-fabricated.

The gas fireplace pilot was not lit or fuel / gas was turned off. The gas

fireplace could not be fully inspected. Lighting of pilots or adjustments

of automatic ignition systems is not performed as part of this inspection.

Client is advised to obtain information from the manufacturer regarding

use, maintenance, and carbon monoxide risks, if any.

NI38) Fireplace

Conditions

24 34/

Page 27: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 10 Kitchen

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

10 Kitchen

Walls - Ceilings - Floors

The general condition of the walls appeared to be in serviceable

condition at the time of the inspection. AS39) Wall Conditions

The general condition of the ceilings appeared to be in serviceable

condition at the time of the inspection. AS40) Ceiling Conditions

The general condition of the visible and accessible portions of the floors

appeared to be in serviceable condition at the time of the inspection. AS41) Floor Conditions

Appears Serviceable AS42) Heat Source

Conditions

Windows - Doors

The sample of windows tested were operational at the time of the

inspection. AS43) Kitchen Window

Conditions

The interior doors appeared to be in serviceable condition at the time of

the inspection. AS44) Kitchen Door

Conditions

Electrical Conditions

Appears Serviceable AS45) Electrical

Conditions

Appears Serviceable AS46) Lighting Conditions

Kitchen Sink - Counter tops - Cabinets

The visible portion kitchen counters appeared to be in serviceable

condition at the time of the inspection. AS47) Counter Conditions

The kitchen cabinets appeared to be in serviceable condition at the time

of inspection. AS48) Cabinet Conditions

The kitchen sink appeared to be in serviceable condition at the time of

the inspection. The faucet appeared to be in serviceable condition at the

time of the inspection. The visible areas of the plumbing under the

kitchen sink appeared to be in serviceable condition at the time of the

inspection.

AS49) Sink Plumbing

Conditions

The sink disposal was operable at the time of the inspection. Client

should consult a licensed plumber, manufacturer, or disposal supply

company for information on proper usage and safety related concerns.

AS50) Garbage Disposal

Condition

Appliances

Stove - Range Type The oven is electric.

The oven was in operational condition at the time of the inspection.

This does not however guarantee future conditions after the time of

inspection.

AS51) Stove - Range

Condition

25 34/

Page 28: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 10 Kitchen

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

This is the style of hood fan that recirculates the air into the room.

Today's standards require the hood to be vented to the exterior. AS52) Hood Fan

Conditions

The dishwasher appeared to be in serviceable condition at the time of

the inspection. This does not however guarantee future performance or

conditions.

AS53) Dishwasher

Conditions

26 34/

Page 29: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 11 Bath(s)

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

11 Bath(s)

Walls - Ceilings - Floors

The general condition of the walls appeared to be in serviceable

condition at the time of the inspection. AS54) Wall Conditions

The general condition of the ceilings appeared to be in serviceable

condition at the time of the inspection. AS55) Ceiling Conditions

The general condition of the visible and accessible portions of the floors

appeared to be in serviceable condition at the time of the inspection. AS56) Floor Conditions

Appears Serviceable AS57) Heat Source

Conditions

Windows - Doors

Cracked glass pane(s) were observed at basement bathroom.

Recommend repair as needed. R58) Bathroom Window

Conditions

The interior doors appeared to be in serviceable condition at the time of

the inspection. AS59) Bathroom Door

Conditions

Electrical Conditions

GFIC (Ground Fault Interrupter Circuit) receptacle circuit (a safety

device for outlets near water) recommended at all bathroom outlets. R60) Electrical

Conditions

Appears Serviceable AS61) Lighting Conditions

Window vent only in the upstairs bathroom. I recommend adding a vent

fan. R62) Vent Fan

Conditions

Bathroom Sink

Appears Serviceable AS63) Counter - Cabinet

Conditions

27 34/

Page 30: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 11 Bath(s)

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

The sink appeared to be in serviceable condition at the time of

inspection in bath AS64) Sink Conditions

Shower - Tub - Toilet

The bathtub faucet in the upstairs bath is dripping out of the handle and

I recommend caulking around where the shower head comes out of the

shower surround.

R65) Shower - Tub

Conditions

The toilet appeared to be in serviceable condition at the time of

inspection in bath AS66) Toilet Conditions

28 34/

Page 31: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 12 Basement

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

12 Basement

Walls - Ceilings - Floors

The interior stairs appeared serviceable at the time of the inspection. AS67) Basement Stair

Conditions

The general condition of the walls appeared to be in serviceable

condition at the time of the inspection. AS68) Wall Conditions

The general condition of the ceilings appeared to be in serviceable

condition at the time of the inspection. AS69) Ceiling Conditions

The general condition of the visible and accessible portions of the floors

appeared to be in serviceable condition at the time of the inspection. AS70) Floor Conditions

Appears Serviceable AS71) Heat Source

Conditions

Windows - Doors

The sample of windows tested were operational at the time of the

inspection. AS72) Basement Window

Conditions

The interior doors appeared to be in serviceable condition at the time of

the inspection. AS73) Basement Door

Conditions

Electrical Conditions

There are two open junction boxes at the ceiling in the basement and an

outlet that is missing its cover. All these should be covers installed. R74) Electrical

Conditions

29 34/

Page 32: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 12 Basement

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

Appears Serviceable AS75) Lighting Conditions

30 34/

Page 33: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 13 Garage - Laundry

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

13 Garage - Laundry

Laundry Room

Location The laundry facilities are located in the basement and in the master bedroom

area

The visible and accessible portions of the laundry plumbing components

appeared to be in serviceable condition at the time of inspection. AS76) Laundry Room

Conditions

31 34/

Page 34: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 14 Foundation - Crawl Space

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

14 Foundation - Crawl Space

Foundation

Foundation Type Crawl Space

Foundation Material Concrete

Appears Serviceable AS77) Foundation

Conditions

Flooring Structure

Flooring Support Type The wood framing floor system was constructed of pre-fabricated truss joists.

The visible and accessible areas of the wood framing system appeared

to be in serviceable condition at the time of the inspection. AS78) Flooring Support

Conditions

Moisture Barrier - Venting - Insulation

Appears Serviceable AS79) Moisture Barrier

Conditions

Appears Serviceable AS80) Venting Conditions

The insulation has been pulled down by rodents and will need to be

fixed. I recommend a pest company remove all rodents before fixing

insulation.

R81) Insulation

Conditions

32 34/

Page 35: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 14 Foundation - Crawl Space

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

33 34/

Page 36: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

zimmelhomeinspections 14 Foundation - Crawl Space

AS = Appears Serviceable | R = Repair | S = Safety | NI = Not Inspected

In the south crawl space there is an open junction box that needs a cover

installed. AS82) Crawl Space

Electrical

34 34/

Page 37: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

ICN 10133AE019 WSDA INSPECTION CONTROL NUMBER

** This report is not valid without the above number**

WAC 16-228-2045 requires that a diagram be prepared for WDO Inspection Reports. A copy is available upon request.

Inspection Date: 3/21/2018 File No: 1 Time: 3pm Visit: 1

Inspection Firm: Zimmel Home Inspections

Address:172 East Arnette Rd

City: Port Angeles WA ZIP: 98362

Phone: 360-775-0708 E-mail: [email protected]

Structural Pest Inspector: Tyson Zimmel WSDA License # 87491

Structure Inspected: 319 W 9th St, Port Angeles, WA 98363

Client's Name: Christopher Ellis

NOTE: ONLY THE ABOVE NAMED CLIENT IS ENTITLED TO RELY ON THE CONTENTS OF THIS REPORT.

In accordance with the provisions of the Revised Code of Washington (RCW) 15.58.450, this report relates to a single sale, transfer, exchange, or refinance of a

property. It is not transferable to, and may not be relied upon, by parties involved in any subsequent sale, transfer, exchange, or refinance of the same property.

COMPLETE WOOD DESTROYING ORGANISM

INSPECTION REPORT SUMMARY OF FINDINGS YES NO*

VISIBLE EVIDENCE OF WOOD DESTROYING INSECTS [ ] [ x ]

VISIBLE EVIDENCE OF ACTIVE WOOD DECAY FUNGI [ ] [ x ]

VISIBLE EVIDENCE OF DAMAGE BY WOOD DESTROYING ORGANISMS [ x ] [ ]

VISIBLE EVIDENCE OF CONDITIONS CONDUCIVE TO WOOD DESTROYING ORGANISMS [ ] [ x ]

INACCESSIBLE AREAS [ ] [ x ]

* THERE IS REMAINING VISIBLE EVIDENCE OF INACTIVE: [ ]Carpenter Ants; [ ]Subterranean Termites; [ x ]Anobiid

Beetles; [ ]Moisture Ants; [ ]Dampwood Termites; [ ]Other Wood Boring Beetles; [ ]Past water events. Neither the inspector, nor

the inspecting firm, shall be liable for any corrective actions required by future inspections as a consequence of this evidence. See the

FINDINGS and DIAGRAM page(s) of, [ ]This report; [ ]Previous report(s) bearing the same ICN for details.

LIMITATION OF LIABILITY

The above inspecting firm and inspector endeavor to perform their services in a professional manner consistent with the care and skill ordinarily exercised by structural

pest inspection professionals. The inspecting firm will re-perform any services not meeting this standard without additional compensation. The inspecting firm's total

liability for the inspections made of the inspected structure shall be limited to the amount of financial responsibility prescribed under Washington State law. The

inspecting firm will not be liable for any special, incidental, punitive or consequential damages, whether foreseen or unforeseen, regardless whether liability is based on breach of contract, breach of express or implied warranty, negligence, strict liability, tort, or otherwise.

COMMENTS

Rev: 2/1/2009 WSPMA Page 1 of ______ pages

Page 38: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

WOOD DESTROYING ORGANISM INSPECTION STANDARDS of the

WASHINGTON STATE PEST MANAGEMENT ASSOCIATION

COMPLETE WOOD DESTROYING ORGANISM (WDO) INSPECTION REPORT.

This report is prepared from an inspection conducted by a Washington State Department of Agriculture licensed Structural Pest Inspector in accordance with

Washington Administrative Code 16-228-2005 through 16-228-2045. Opinions contained herein are based on conditions visible and evident at the time of the

inspection. This report does not warrant, represent, or guarantee that the structure reported on is free from evidence of WDO's, their damage, or conditions

conducive to WDO's; nor does it represent or guarantee that the total damage, infestation, or infection is limited to that disclosed in this report.

I. INSPECTION PROCEDURES

The inspector shall make a thorough inspection, using accepted methods and practices, of the subject to render an opinion on the presence of, or damage from WDO's as well an conditions conducive to such WDO's.

AREAS INSPECTED shall include: structural exterior (accessible both visibly and physically to an inspector at ground level); accessible structure interior; accessible

sub structural crawl space(s); garages, carports and decks which are attached to the structure. Deck inspection shall include; railings, wooden steps, and accessible

wooden surface materials, as well as deck substructures which are accessible (those with at least a 5 foot soil to joist clearance, or elevated decks which can be suitably

reached using a 6 foot step ladder). WOOD DESTROYING ORGANISMS shall include: subterranean termites; dampwood termites; carpenter ants; moisture ants; wood boring beetles of the family

Anobiidae; and wood decay fungus (rot). The inspector will not assume any responsibility for WDO's that were not detected during their dormant season. When

evidence of moisture ants, dampwood termites, wood infesting anobiids, or wood decay fungi is detected during a Complete WDO Inspection, the inspector must

identify and report the condition(s) conducive to such infestations. It must be stated in the report that such infestations may be eliminated by removal of all infested

wood and correction of any contributing conducive conditions. CONDUCIVE CONDITIONS, as determined by the inspector, shall include, but not be limited to: inadequate clearance; earth to wood contact; conducive debris in

the crawl space; inadequate ventilation; excessive moisture; vegetation contact with the structure; bare ground in the crawl space; existing or seasonal standing water in

the crawl space; failed caulking or grout in water splash areas; and/or non-functioning gutter systems.

II. LIMITATIONS OF INSPECTIONS

The inspecting firm shall not be held responsible by any party for any condition or consequence of WDO's which is beyond the scope of inspection. The scope,

defined in Section I, INSPECTION PROCEDURES, is limited as follows:

(a) INACCESSIBLE AREAS: Certain areas of a structure, which are inaccessible by their nature, may be subject to infestation by WDO's yet cannot be inspected

without excavation or unless physical obstructions are removed. Such areas include, but are not limited to: wall voids; spaces between floors; substructures concealed

by sub-floor insulation or those with inadequate clearance; floors beneath coverings; sleeper floors; areas concealed by furniture, appliances, and/or personal

possessions; and deck substructures with less that 5 foot clearance. (b) ROOF SYSTEMS AND ATTIC AREAS: Roof systems, roof coverings and attic areas are excluded from this report. This report may note, at the discretion of the

inspector, visual evidence of infestation and/or infections of WDO's in the portions of the eaves that are visible and accessible from the ground. Nor opinion is rendered

nor guarantee implied concerning the watertight integrity, the condition, or the future life of the roof system. Any comment(s) made regarding an obvious condition of

(a) component(s) of the roof system or attic space(s) shall not imply an extension to the scope of inspection. If a more qualified opinion is desired, the services of a licensed roof system professional should be obtained.

(c) SHEDS AND OUTBUILDINGS: Sheds, garages, carports, decks and other structures, which are not attached to the main structure by a roof system or foundation,

are excluded from this report unless specifically requested and noted. The inspecting firm reserves the right to charge additionally to inspect any unattached structures.

(d) CLIMATIC CONDITIONS: In certain geographical areas of Washington State where wet climate is common, and due to their construction and materials,

structures may be subject to conditions from normal weathering. Such conditions as cracking, checking, and/or warping of doors, window casings, siding, and non-supporting wooden members shall not be reported on inspection reports except at the discretion of the inspector. Inspectors are not required to report on any wood

destroying organism infestation, infection, or other condition that might be subject to seasonal constraints or environmental conditions if evidence of those constraints

or conditions is not visible at the time of the inspection.

(e) MOLD: Molds, mildews, and other fungal growth (except wood decay fungi) shall be reported on only to the extent that they indicate an excessive moisture

condition which may be conducive to WDO's. The inspector is not liable or responsible for determining the type of mold, mildew, or other fungi present, nor shall the inspector be liable or responsible for determining the possible health hazards associated with the presence of molds, mildews, or other fungi. This report is not, nor shall

the inspector perform a mold inspection or investigation. If a more qualified opinion is desired, the services of a toxicologist or certified industrial hygienist should be

obtained.

(f) STRUCTURAL ASSESSMENT: While it may be possible for the inspector to note damaged materials, neither the inspector nor the inspection firm is liable or

responsible in any way to determine the structural integrity of any building materials. If a more qualified opinion is desired, the services of a licensed, qualified contractor or structural engineer should be obtained.

(g) REMAINING EVIDENCE: In certain situations, it may not be practical to eliminate all evidence of previous WDO activity (e.g., carpenter ant frass, insect parts,

or subterranean termite scaling), or evidence of conducive conditions, (e.g., water staining). Although noted, this evidence may remain after corrections have been made

or if it is the inspector's opinion that the evidence is from inactive WDOs and no corrections are recommended. Neither the inspector nor the inspecting firm shall be

liable or responsible for any corrective action required by future inspections in regards to this remaining evidence. III. REPORTS

(a) WRITTEN REPORT: The inspecting firm shall not issue any complete wood destroying organism report unless a Washington State Department of Agriculture

licensed structural pest inspector from that firm has made a careful and thorough inspection of the structure in conformance with and subject to the limitations within

these standards. Reports shall include a diagrams and a description of the findings to help identify locations of the findings as well as inaccessible areas not identified in

section II (a) of these standards. IV. WORK RECOMMENDATIONS AND TREATMENTS

(a) NO WARRANTIES OF CORRECTIVE WORK: Neither the inspector nor the inspecting firm will evaluate or warranty the quality of workmanship, the

compliance with any applicable building codes, nor the suitability of use or any repairs, corrections, or treatments recommended within this report. Compliance with

Washington State pesticide application laws and applicable building codes (current revisions) is the responsibility of the property owner and those performing the work.

It is strongly recommended that those parties performing any corrections or treatments be licensed, bonded and qualified professionals providing warranted services. (b) CONDITIONS REVEALED DURING THE PERFORMANCE OF RECOMMENDATIONS: Should any WDO damage, or conducive condition be revealed

during the performance of any recommendations, whether performed by the owner, the purchaser, a contractor, or any other party of interest, the inspecting firm must

be notified of such, and be given a reasonable opportunity for re-inspecting and determining the need for any additional corrective measures before such conditions are

covered. The owner, purchaser, or any other person performing the work shall be responsible for notifying the inspector. Nothing contained herein shall prevent the

inspecting firm from assessing additional charges for each additional inspection.

NOTE: The Washington State Pest Management Association (WSPMA), as a service to inspection firms, has developed this form and these Standards of Practice. By

doing so, the WSPMA does not certify that the inspecting firm is a member of the WSPMA, or that the inspector is qualified to perform the inspection/. The WSPMA

shall not be a party to any claim or action by the buyer, seller, or other interested party against the inspecting firm solely by reason of making this report form and these

Standards of Practice available for use.

Rev: 2/01/2009

Page 39: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

Findings

Inactive Anobiid Beetle: Around the crawl space entrance on the north side of the

home there is some Anobiid beetle damage. This looks to be from an old

infestation and is inactive. This damage is not structural and was only seen in this

area.

Page 40: FAIRA TRANSPARENCY REPORTS 319 W 9th St, …...608 State St. South Kirkland, WA 98033 hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 319 W 9th St, Port Angeles, WA 98362

Important information about the attached

Complete Wood Destroying Organism Inspection Report.

Beginning January 1, 2004 the Washington State Pest Management Association has adopted a new

format for the Complete Wood Destroying Organism Inspection Report. This new format was

prompted, in part, by recent changes to Washington State Laws and Rules that pertain to Structural Pest

Inspections, (RCW 15.58.450 and WAC 16-228-2005 through 16-228-2045), and by changes in market

expectations. These changes were a cooperative effort involving members of all affected industries;

inspectors, real estate professionals, and lenders. This new inspection report format is easier to

understand, easier to enforce, and provides better protection for the consumer.

Washington State laws and rules do not recognize any difference between a “Preliminary Report” and a

“Final Report”. Therefore, this reporting format has been eliminated. There will only be one report: the

Complete Wood Destroying Organism Inspection Report. If you have questions regarding these changes,

contact the Washington State Pest Control Association (1-800-253-3836).

For your protection you are encouraged to have all findings corrected by licensed and bonded

contractors and to obtain and keep copies of all repair receipts. You may also elect to obtain a report

with “NO” findings. A report with “NO” findings does not indicate that the inspector is approving of

any work done to eliminate previously reported findings. It only indicates that there are no findings at

the time of the inspection. It must also be understood that remaining evidence may exist after all repairs

and corrections have been made. This evidence, while required to be reported, may be inconsequential.

The attached Washington State Pest Management Association Complete Wood Destroying

Organism Inspection Report Form has been reviewed by the Washington State Department of

Agriculture. The Department agrees that with an accurate inspection, and when filled out

properly, this form can meet the Wood Destroying Organism Inspection Reporting Criteria

found in WAC 16-228-2005 through 16-228-2045.