fan-powered table of parallel · pdf filefan-powered parallel 76 vav-prc005-en model number...

26
Fan-Powered Parallel 75 VAV-PRC005-EN Model Number Description 76 Selection Procedure 77 - 79 General Data – Setting Guidelines 80 Performance Data – Pressure Requirements 81 Performance Data – Fan Curves 82 - 85 Performance Data – Hot Water Coil 86 - 87 Performance Data – Electrical Data 88 Performance Data – Acoustics 89 - 93 Dimensional Data 94 - 96 Mechanical Specifications 97 - 99 Table of Contents

Upload: lekhue

Post on 07-Mar-2018

220 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

75VAV-PRC005-EN

Model Number Description 76

Selection Procedure 77 - 79

General Data – Setting Guidelines 80

Performance Data – Pressure Requirements 81

Performance Data – Fan Curves 82 - 85

Performance Data – Hot Water Coil 86 - 87

Performance Data – Electrical Data 88

Performance Data – Acoustics 89 - 93

Dimensional Data 94 - 96

Mechanical Specifications 97 - 99

Table ofContents

Page 2: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN76

ModelNumberDescription

Parallel Fan-powered VAVTerminal UnitsThe features of the parallel fan-powered VAV terminal units aredescribed by the product categoriesshown below in bold. Within eachcategory the options availableare listed.

MODL Unit ModelVPCF Parallel fan-powered cooling-

only terminalVPWF Parallel fan-powered w/hot

water heatVPEF Parallel fan-powered w/

electric heat

DSEQ Design Sequence* Design sequence

INLT Primary Inlet – CFM6 6" inlet – 500 cfm08 8" inlet – 900 cfm10 10" inlet – 1400 cfm12 12" inlet – 2000 cfm14 14" inlet – 3000 cfm16 16" inlet – 4000 cfm

Fan Fan Size1 500 fan cfm2 615 fan cfm3 925 fan cfm4 1150 fan cfm5 1675 fan cfm6 2350 fan cfm7 2500 fan cfm

INSL Unit InsulationMT.5 1/2" matte-facedMT1 1" matte-facedFF.5 1/2" foil-facedFF1 1" foil-facedDW1 Double-wall w/ 1" matte-facedFBRF 3/8" closed cell

MTVT Motor Voltage115 115 motor voltage277 277 motor voltage208 208 motor voltage347 347 motor voltage

MTYP Motor TypeSTD Single-speed motor

CTRL Unit ControlPNON Shaft only – pneumatic

controls by othersENON Shaft only – DDC or analog

controls by othersDD00 Shaft w/ Trane actuatorDD01 DDC w/o remote heatDD02 N.C. on/off hot water

valve controlDD03 Proportional hot water

valve controlDD04 On/off electric heat controlDD05 Pulse-width modulation controlDD07 N.O. on/off hot water

valve controlFM00 Factory installation of other’s

actuator and controllerFM01 Factory installation of Trane’s

actuator and other’s controllerPN00 Pneumatic actuator onlyPN05 Pneumatic actuator w/ 3011EI05 Basic Operation w/ reheat

capability

CONN Controls & Heat Connection SideLeft Left sideHWCL Hot Water Coil1ROW One-row hot water coil2ROW Two-row hot water coilFUSE Power FuseWith Power fuseVOLT Electric Heater Voltage2081 208 Volt, 1-Phase2083 208 Volt, 3-Phase2401 240 Volt, 1-Phase2771 277 Volt, 1-Phase3471 347 Volt, 1-Phase4801 480 Volt, 1-Phase4803 480 Volt, 3-Phase5753 575 Volt, 3-PhaseSTGE Electric Heater Stage1 1 stage of heat2 2 stages of heat – equal3 3 stages of heat – equalHTKW Electric Heater Kilowatts0.5 0.5 kW1.0 1.0 kW1.5 1.5 kW2.0 2.0 kW2.5 2.5 kW3.0 3.0 kW3.5 3.5 kW4.0 4.0 kW4.5 4.5 kW5.0 5.0 kW5.5 5.5.kW6.0 6.0 kW6.5 6.5 kW7.0 7.0 kW7.5 7.5 kW8.0 8.0 kW9.0 9.0 kW10.0 10.0 kW11.0 11.0 kW12.0 12.0 kW13.0 13.0 kW14.0 14.0 kW15.0 15.0 kW16.0 16.0 kW17.0 17.0 kW18.0 18.0 kW20.0 20.0 kWCNTR Electric Heater ControlMAGN 24 volt magnetic contactorsMERC 24 volt mercury contactorsPEMA P.E. w/ magnetic contactorsPEME P.E. w/ mercury contactorsDISW Power Disconnect SwitchWITH Power disconnect switchAFSW Electric Heater Air flow SwitchWITH Electric heater airflow switch

VPCF

VPWF

VPEF

Page 3: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

77VAV-PRC005-EN

SelectionProcedure

This section describes the elementsand process required to properly selectparallel fan-powered VAV terminals,and includes a specific example. Theselection procedure is iterative innature which makes computerselection desirable.

Selection of fan-powered VAVterminals involves four elements:

�Air valve selection�Heating coil selection� Fan size and speed selection�Acoustics

Air Valve Selection

Provided in the performance datasection of the catalog is the Wide-OpenAir Pressure Drop vs. Airflow curve. Toselect an air valve, locate the requireddesign cooling airflow and find itsvertical intersection with the smallestair valve size that has air pressure dropequal to or lower than the maximumwide-open air pressure droprequirement.

Heating Coil Selection

Supply Air TemperatureThe first step required when selecting aheating coil is to determine the heatingsupply air temperature to the space,calculated using the heat transferequation. Air temperature difference isdefined as the heating supply airtemperature to the space minus thewinter room design temperature. Thezone design heat loss rate is denotedby the letter Q. Supply air temperatureto the space equals the leaving airtemperature (LAT) for the terminal unit.

Coil Leaving Air TemperatureOnce the terminal unit LAT isdetermined, the heating requirementsfor the coil can be calculated. Theleaving air temperature for the coil of aparallel fan-powered terminal unitvaries based on the type of unitinstalled heat being selected.

Electric coil LAT equals terminal unitLAT because the coil is located on theunit discharge. Hot water coils,however, are located on the enteringair side of the fan. In this case, coil LATis calculated using a mixing equation.Given the unit heating airflow and LAT,minimum primary airflow at its supplyair temperature, and the volume ofheated plenum air, the leaving airtemperature for the hot water coil canbe determined (see the unit selectionexample that follows for more details).

Coil Entering Air TemperatureThe entering air temperature (EAT) tothe coil also varies based on the coilposition on the unit.

Electric coil EAT equals thetemperature of blended primary airand plenum air because the coil is in ablow-thru configuration. The unit hotwater coil configuration is draw-thru,therefore, EAT equals the plenumair temperature.

Capacity RequirementOnce both coil EAT and LAT aredetermined, the heat transfer (Q) forthe coil must be calculated using theheat transfer equation. For electric heatunits, the Q value must be convertedfrom Btu to kW for heater selection.The required kW should be comparedto availability charts in the performancedata section for the unit selected. Forhot water heat units, reference thecapacity charts in the performance datasection for the required heat transfer Qand airflow to pick the appropriate coil.

Fan Size and Selection

Fan AirflowFan airflow is determined bycalculating the difference betweenthe unit design heating airflow andminimum primary airflow.

Fan External Static PressureFan external static pressure is the totalresistance experienced by the fan,

which may include downstreamductwork and diffusers, heating coils,and sound attenuators. As total airflowvaries so will static pressure, makingcalculation of external static pressuredependent on unit type.

In many applications of parallelterminals, a minimum primary airflowmust be maintained to meetventilation requirements. This primaryairflow contributes to the totalresistance experienced by the fan andshould be accounted for in allcomponents downstream of the fanitself, including electric coils. Hot watercoils are positioned on the fan inlet andare not affected by the additionalprimary airflow. The static pressureresistance experienced by the fan dueto the hot water coil is based on fanairflow only, not the totalheating airflow.

SelectionOnce fan airflow and external staticpressure are determined, reference thefan curves in the performance datasection. Cross plot both airflow andexternal static pressure on eachapplicable graph. If the point isbetween the high and low ranges forthe fan, that fan size will work.

It is common to identify more thanone fan that can meet the designrequirements. Typically, selectionbegins with the smallest fan availableto meet capacity. If this selectiondoes not meet acousticalrequirements, upsizing the fan andoperating it at a slower speed can bedone for quieter operation.

Acoustics

Air Valve Generated NoiseTo determine the noise generated bythe air valve, two pieces of informationare required; design airflow and designair pressure drop. The design airpressure drop is determined by takingthe difference between design inletand static pressure (the valve’s most

Page 4: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN78

SelectionProcedure

over-pressurized condition) and externalstatic pressure at design cooling flow.This represents a worst-case operatingcondition for the valve.

Fan Generated NoiseTo determine fan noise levels, fanairflow, external static pressure andspeed information is required.

Evaluation ElementsFor parallel fan-powered terminal units,the air valve and fan operation must beevaluated separately because theseoperations are not simultaneous.

Access the appropriate acousticstable(s) of the catalog and determinethe sound power and NC prediction forboth the discharge and radiated paths. Itis important to understand thatdischarge air noise is generally not aconcern with fan-powered terminals.Radiated noise from the unit casingtypically dictates the noise level ofthe space.

If the entire unit or any element of it isgenerating noise in excess of the NoiseCriteria requirements, the size of theappropriate portion of the terminalshould be increased. Because theselection procedure is iterative, careshould be taken by the designer toconfirm that the change in selectiondoes not affect other elements of theunit or system design.

Selection Example—

Parallel With Hot Water Heat

Air Valve SelectionRequired Information:

Design cooling airflow: 1000 cfmMaximum wide-openair pressure drop: 0.25 in. wg

Choose a size 10 air valve with wide-open air pressure drop of 0.05 in. wg

Heating Coil SelectionRequired Information:

Zone design heat loss: 20000 BtuUnit heating airflow: 600 cfmWinter room design temp.: 68ºFCoil entering water temp.: 180ºFMinimum primary airflow: 200 cfmPlenum temperature: 70ºFCoil flow rate: 2 gpmPrimary air temperature: 55ºF

Heat Transfer Equation (Btu)Q = 1.085 x Cfm x D Temperature

For the heating zone, the temperaturedifference is the zone supply airtemperature (SAT) minus the winterroom design temperature.

20000 Btu = 1.085 x 600 x (SAT - 68ºF)SAT = 98ºF

Because the hot water coil is on theplenum inlet of a parallel fan-poweredunit, the unit supply air temperature isequal to the mix of the heated plenumair from the fan and the minimumprimary airflow.

600 cfm x 98ºF =200 cfm x 55ºF +(600 cfm - 200 cfm) x Coil LAT

Coil LAT = 121ºF

For the heating coil, the temperaturedifference is the calculated coil LATminus the coil EAT (Plenum AirTemperature).Coil Q = 1.085 x 400 x (121-70) =

22134 Btu = 22.13 Mbh

Coil Performance TableSelection:Size 02 fan, 2-row coil with 2 gpm =30.02 Mbh

2-row coil with 2 gpm = 9.15 ft WPD

Fan SelectionRequired Information:

Design airflow: 400 cfmDownstream static pressureat design airflow: 0.25 in. wg

Fan external static pressure equalsdownstream static pressure (ductworkand diffusers) plus coil static pressure.The coil static pressure that the fanexperiences is at the fan airflow(400 cfm). The downstream staticpressure the fan experiences is at fanairflow plus minimum primary airflow.The sum of fan airflow and minimumprimary airflow (600 cfm) is less thandesign airflow (1000 cfm) and thereforethe 0.25 in. wg downstream staticpressure at design airflow must beadjusted for the lower heating airflow.

Using Fan Law Two:Heating Downstream Static Pressure =(600/1000)2 x 0.25 = .09 in. wg

A size 02 fan has the capability to deliverapproximately 650 cfm at 0.09downstream static pressure.

AcousticsRequired Information:

Design inlet static press.: 1.0 in. wgNC criteria: NC-35

The selection is a VPWF Parallel Fan-powered Terminal Unit, primary air valvesize 10, parallel fan size 02, with a 2-rowhot water coil.

Determine the casing radiated noiselevel because it typically dictates thesound level (NC) of the space. With aparallel unit, two operating conditionsmust be considered, design cooling anddesign heating.

Design Cooling (1000 cfm). The closesttabulated condition (1100 cfm at1.0 in.wg ISP) has the followingtabulated results:

Parallel Fan-Powered Unit withElectric Heat

Page 5: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

79VAV-PRC005-EN

Design Heating (200 cfm valve,400 cfm fan). The closest tabulatedcondition (390 fan cfm at 1.0 in. wg ISP)has the following tabulated results:

The predicted NC level for designcooling is NC-31 and for design heatingis NC-31. If the catalog path attenuationassumptions are acceptable, this unitmeets all of the design requirementsand the selection process is complete.Computer SelectionThe advent of personal computershas served to automate manyprocesses that were previouslyrepetitive and time-consuming. Oneof those tasks is the proper scheduling,sizing, and selection of VAV terminalunits. The Trane Company hasdeveloped a computer program toperform these tasks. The software iscalled the Trane Official ProductSelection System (TOPSS).The TOPSS program will take the inputspecifications and output the properlysized VariTrane VAV terminal unit alongwith the specific performance for thatsize unit.The program has several required fields,denoted by red shading on the TOPSSscreen, and many other optional fieldsto meet the criteria you have. Requiredvalues include maximum and minimumairflows, control type, and model. Ifselecting models with reheat, you willbe required to enter information tomake that selection also. The user isgiven the option to look at all theinformation for one selection on onescreen or as a schedule with the otherVAV units on the job.The user can select single-duct, dual-duct, and fan-powered VAV boxes withthe program, as well as most otherTrane products, allowing you to selectall your Trane equipment with onesoftware program.The program will also calculate soundpower data for the selected terminalunit. The user can enter a maximumindividual sound level for each octaveband or a maximum NC value. Theprogram will calculate acoustical datasubject to default or user suppliedsound attenuation data.

SelectionProcedure

Schedule ViewThe program has many time-saving features such as:� Copy/Paste from spreadsheets like Microsoft® Excel� Easily-arranged fields to match your schedule� Time-saving templates to store default settings

The user can also export the Schedule View to Excel to modify and put into a CADdrawing as a schedule.

Specific details regarding the program, its operation, and how to obtain a copy of itare available from your local Trane sales office.

Rearrange what fields you seeand in what order with a fewclicks of a button.

Required entry fields (in Redon TOPSS screen).

NOTE: Use the same procedures for selecting Low-Height Parallel Fan-PoweredUnits as used for selecting Parallel Fan-Powered Units

Octave 2 3 4 5 6 7 NCBand

Sound 67 58 56 53 48 44 20Power

Octave 2 3 4 5 6 7 NCBand

Sound 71 67 64 65 62 54 24Power

Page 6: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN80

General Data—SettingGuidelines

Primary Airflow Control Factory Settings – I-PControl Air Valve Cataloged Maximum Setting Minimum Setting Constant Volume

Type Size Cfm Cfm Cfm Cfm

6 500 60–500 0,60–500 60–5008 900 105–900 0,105–900 105–900

Direct Digital Control/ 10 1400 165–1400 0,165–1400 165–1400UCM 12 2000 240–2000 0,240–2000 240–2000

14 3000 320–3000 0,320–3000 320–300016 4000 420–4000 0,420–4000 420–40006 500 73–500 0,73–500 73–500

Pneumatic with 8 900 134–900 0,134–900 134–900Volume Regulator 10 1400 215–1400 0,215–1400 215–1400

12 2000 300–2000 0,300–2000 300–200014 2885 408–2887 0,408–2887 408–288716 3785 536–3789 0,536–3789 536–37896 500 120–500 0,120–500 120–5008 900 210–900 0,210–900 210–900

Analog Electronic 10 1400 328–1400 0,328–1400 328–140012 2000 470–2000 0,470–2000 470–200014 3000 640–3000 0,640–3000 640–300016 4000 840–4000 0,840–4000 840–4000

Primary Airflow Control Factory Settings – SIControl Air Valve Cataloged Maximum Setting Minimum Setting Constant Volume

Type Size L/s L/s L/s L/s

6 236 28–236 0,28–236 28–2368 425 50–425 0,50–425 50–425

Direct Digital Control/ 10 661 77–661 0,77–661 77–661UCM 12 944 111–944 0,111–944 111–944

14 1416 151–1416 0,151–1416 151–141616 1888 198–1888 0,198–1888 198–18886 236 35–236 0,35–236 35–236

Pneumatic with 8 425 63–425 0,63–425 63–425Volume Regulator 10 661 102–661 0,102–661 102–661

12 944 141–944 0,141–944 141–94414 1362 193–1363 0,193–1363 193–136316 1787 253–1788 0,253–1788 253–17886 236 57–236 0,57–236 57–2368 425 100–425 0,100–425 100–425

Analog Electronic 10 661 155–661 0,155–661 155–66112 944 222–944 0,222–944 222–94414 1416 303–1416 0,303–1416 303–141616 1888 397–1888 0,397–1888 397–1888

Note: Maximum airflow must be greater than or equal to minimum airflow.

Page 7: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

81VAV-PRC005-EN

PerformanceData—PressureRequirements

Inlet/Fan Airflow CoolingSize Cfm Only

Air Pressure Drop – in. wg (I-P)

Inlet/Fan Airflow CoolingSize Cfm Only

06–01 210 0.06300 0.12400 0.22500 0.35

08–01 210 0.01300 0.02400 0.04500 0.06

06–02 300 0.12375 0.19450 0.28500 0.35

08–02 300 0.02400 0.04500 0.06600 0.09

10–02 300 0.01400 0.01500 0.01615 0.01

08–03 500 0.08625 0.12750 0.17900 0.24

10–03 500 0.01725 0.02850 0.03925 0.04

12–03 500 0.01725 0.01850 0.01925 0.01

08–04 575 0.10700 0.15800 0.19900 0.24

10–04 575 0.01700 0.02900 0.041150 0.06

12–04 575 0.01700 0.01900 0.011150 0.01

10–05 1000 0.051150 0.061250 0.071400 0.09

12–05 1000 0.011200 0.011400 0.011675 0.01

14–05 1000 0.011200 0.011400 0.011675 0.01

12–06 1000 0.011300 0.011600 0.012000 0.01

14–06 1500 0.011800 0.012100 0.012300 0.01

16–06 1500 0.011800 0.012100 0.012300 0.01

14–07 1500 0.011900 0.012200 0.012500 0.01

16–07 1500 0.012000 0.012500 0.013000 0.01

Fan Airflow 1-Row HW 2-Row HW ElectricSize L/s Coil Only Coil Only Coil Only

01–02 100 3 4 3140 4 7 3190 5 10 3235 7 14 3285 10 20 3

03–07 235 4 8 3425 11 21 3625 21 40 3800 32 60 51000 48 86 111180 65 113 18

Air Pressure Drop – Pa (SI)Fan Airflow 1-Row HW 2-Row HW ElectricSize Cfm Coil Only Coil Only Coil Only

01–02 210 0.01 .02 .01300 0.02 .03 .01400 0.02 .04 .01500 0.03 .06 .01600 0.04 .08 .01

03–07 500 0.02 .03 .01900 0.04 .09 .011300 0.08 .15 .011700 0.13 .24 .022100 0.19 .34 .042500 0.26 .45 .07

Air Pressure Drop – in. wg (I-P)

Note: HW Coil Only pressure drops are just the heating coil.

Air Pressure Drop – Pa (SI)

Inlet/Fan Airflow CoolingSize L/s Only

06–01 100 15140 29190 55235 87

08–01 100 3140 5190 10235 16

06–02 145 31180 49215 72235 86

08–02 145 5190 10235 16280 23

10–02 145 3190 3235 3290 3

08–03 240 19300 30350 41425 60

10–03 240 3340 5400 8435 9

12–03 240 3345 3400 3435 3

08–04 275 26330 37380 48425 60

10–04 275 3330 5425 9540 15

12–04 275 3330 3425 3540 3

10–05 475 11525 14600 18660 22

12–05 475 3565 3660 3790 3

14–05 475 3565 3660 3790 3

12–06 475 3615 3755 3940 3

14–06 710 3850 3990 31085 3

16–06 710 3850 31000 31085 3

14–07 710 3900 31040 31180 3

16–07 710 3945 31180 31415 3

Inlet/Fan Airflow CoolingSize L/s Only

Page 8: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN82

PerformanceData—Fan Curves (I-P)

VPCF and VPEF maximum

Minimum

1 row coil maximum

2 row coil maximum

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

500 600 700 800 900 1000 1100 1200 1300

DSP(in. wg)

Airflow (cfm)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

100 200 300 400 500 600

DSP(in. wg)

Airflow (cfm)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

200 300 400 500 600 700

DSP(in. wg)

Airflow (cfm)

Parallel Fan Size 04

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

400 500 600 700 800 900 1000 1100

DSP(in. wg)

Airflow (cfm)

Parallel Fan Size 01 Parallel Fan Size 02

Parallel Fan Size 03

Page 9: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

83VAV-PRC005-EN

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

600 800 1000 1200 1400 1600 1800 2000

PerformanceData—Fan Curves (I-P)

VPCF and VPEF maximum

Minimum

1 row coil maximum

2 row coil maximum

DSP(in. wg)

Airflow (cfm)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

700 900 1100 1300 1500 1700 1900 2100 2300 2500

Parallel Fan Size 06

Airflow (cfm)

DSP(in. wg)

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Parallel Fan Size 07

DSP(in. wg)

Airflow (cfm)

Parallel Fan Size 05

Page 10: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN84

PerformanceData—Fan Curves (SI)

0

20

40

60

80

100

120

140

50 100 150 200 250 300

0

20

40

60

80

100

120

140

100 150 200 250 300 350

Parallel Fan Size 01 Parallel Fan Size 02

Airflow (L/s)

Airflow (L/s)

Airflow (L/s)

Airflow (L/s)

DSP(Pa)

DSP(Pa)

DSP(Pa)

DSP(Pa)

VPCF and VPEF maximum

Minimum

1 row coil maximum

2 row coil maximum

0

20

40

60

80

100

120

140

160

180

200

200 250 300 350 400 450 500 550

Parallel Fan Size 03

0

20

40

60

80

100

120

140

160

180

200

200 250 300 350 400 450 500 550 600 650

Parallel Fan Size 04

Page 11: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

85VAV-PRC005-EN

0

50

100

150

200

200 300 400 500 600 700 800 900

PerformanceData—Fan Curves (SI)

Parallel Fan Size 07

Airflow (L/s)

Airflow (L/s)

Airflow (L/s)

DSP(Pa)

DSP(Pa)

DSP(Pa)

VPCF and VPEF maximum

Minimum

1 row coil maximum

2 row coil maximum

0

20

40

60

80

100

120

140

160

180

200

300 400 500 600 700 800 900 1000 1100 1200 1300

0

20

40

60

80

100

120

140

160

180

200

500 600 700 800 900 1000 1100 1200 1300

Parallel Fan Size 05

Parallel Fan Size 06

Page 12: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN86

PerformanceData—Hot WaterCoil (I-P)

Fan Size 01, 02 (I-P)Water

Pressure Airflow (Cfm)Rows GPM Drop (ft) 215 250 300 350 400 450 500 550 590

1-Row 0.5 0.22 11.28 11.92 12.71 13.35 13.88 14.34 14.75 — —Capacity 1.0 0.77 13.71 14.62 15.75 16.73 17.61 18.40 19.19 19.91 20.45

MBH 2.0 2.67 15.22 16.37 17.83 19.13 20.30 21.39 22.40 23.36 24.083.0 5.57 15.80 17.05 18.64 20.07 21.38 22.59 23.73 24.81 25.644.0 9.43 16.10 17.41 19.08 20.58 21.96 23.25 24.46 25.61 26.495.0 14.22 16.29 17.63 19.35 20.90 22.32 23.66 24.92 26.11 27.03

2-Row 1.0 1.33 18.33 20.25 22.65 24.71 26.48 28.02 29.37 — —Capacity 2.0 4.47 19.85 22.26 25.40 28.23 30.79 33.11 35.23 37.17 38.60

MBH 3.0 9.15 20.36 22.94 26.35 29.47 32.34 34.99 37.43 39.70 41.404.0 15.29 20.61 23.28 26.83 30.10 33.14 35.95 38.58 41.03 42.875.0 22.79 20.76 23.48 27.12 30.49 33.62 36.54 39.28 41.84 43.78

Fan Size 03–07 (I-P)Water

Pressure Airflow (Cfm)Rows GPM Drop (ft) 500 700 900 1100 1300 1500 1700 1900 2100

1-Row 1.0 0.37 21.62 24.37 26.42 28.05 29.40 — — — —Capacity 2.0 1.25 25.93 29.84 33.07 35.97 38.49 40.72 42.70 44.50 46.13

MBH 3.0 2.59 27.75 32.32 36.19 39.56 42.56 45.35 47.93 50.29 52.464.0 4.35 28.75 33.71 37.96 41.71 45.08 48.17 51.01 53.68 56.225.0 6.52 29.39 34.60 39.11 43.11 46.74 50.08 53.17 56.06 58.766.0 9.07 29.83 35.22 39.91 44.10 47.91 51.43 54.71 57.78 60.677.0 12.03 30.16 35.68 40.51 44.83 48.78 52.44 55.86 59.07 62.10

2-Row 2.0 2.25 38.32 46.18 52.08 56.61 59.87 — — — —Capacity 3.0 4.59 40.84 50.35 57.87 63.92 68.88 73.04 76.57 79.61 82.26

MBH 4.0 7.63 42.13 52.56 61.05 68.02 73.87 78.85 83.14 86.89 90.205.0 11.33 42.92 53.93 63.03 70.63 77.08 82.63 87.47 91.74 95.536.0 15.67 43.44 54.86 64.40 72.44 79.32 85.29 90.53 95.18 99.337.0 20.66 43.82 55.53 65.39 73.76 80.97 87.26 92.81 97.75 102.18

Notes:1. Fouling Factor = 0.000252. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 140°F.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).4. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factors for

different entering conditions.

Temperature Correction Factors for Water Pressure Drop (ft)

Average Water Temperature 200 190 180 170 160 150 140 130 120 110Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (MBH)

Entering Water Minus Entering Air 40 50 60 70 80 90 100 110 120 130Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187

Coils–Water Weights

Internal Internal OperatingUnit Fan Coil Volume Volume WeightType Size Type (in.3) (gal.) (lbs)VPWF 01,02 1-Row 32.52 0.141 12.3VPWF 01,02 2-Row 57.90 0.251 16.8VPWF 03-07 1-Row 51.21 0.222 14.5VPWF 03-07 2-Row 89.27 0.386 20.1

LAT = EAT + MBH x 921.7CFM WTD = EWT - LWT = 2 x MBH

GPM(( ) )

Page 13: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

87VAV-PRC005-EN

PerformanceData—Hot WaterCoil (SI)

Notes:1. Fouling Factor = 0.000252. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 60°C.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factors for

different entering conditions.

Fan Size 01, 02 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 101 118 142 165 189 212 236 260 278

1-Row 0.04 1.02 3.31 3.49 3.73 3.91 4.07 4.20 4.32 — —Capacity 0.07 2.76 4.02 4.29 4.62 4.90 5.16 5.39 5.62 5.84 5.99

kW 0.13 7.97 4.46 4.80 5.23 5.61 5.95 6.27 6.57 6.85 7.060.19 16.65 4.63 5.00 5.46 5.88 6.27 6.62 6.96 7.27 7.520.25 28.19 4.72 5.10 5.59 6.03 6.44 6.81 7.17 7.51 7.760.32 42.48 4.77 5.17 5.67 6.13 6.54 6.93 7.30 7.65 7.92

2-Row 0.07 4.76 5.37 5.94 6.64 7.24 7.76 8.21 8.61 — —Capacity 0.13 13.36 5.82 6.52 7.44 8.27 9.02 9.70 10.33 10.89 11.31

kW 0.19 27.37 5.97 6.72 7.72 8.64 9.48 10.26 10.97 11.64 12.130.25 45.70 6.04 6.82 7.86 8.82 9.71 10.54 11.31 12.03 12.570.32 68.13 6.08 6.88 7.95 8.94 9.85 10.71 11.51 12.26 12.83

Fan Size 03–07 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 236 330 425 519 613 708 802 897 991

1-Row 0.07 1.32 6.34 7.14 7.74 8.22 8.62 — — — —Capacity 0.13 3.74 7.60 8.75 9.69 10.54 11.28 11.94 12.52 13.04 13.52

kW 0.19 7.73 8.13 9.47 10.61 11.60 12.47 13.29 14.05 14.74 15.380.25 12.99 8.43 9.88 11.13 12.23 13.21 14.12 14.95 15.73 16.480.32 19.47 8.61 10.14 11.46 12.64 13.70 14.68 15.58 16.43 17.220.38 27.14 8.74 10.32 11.70 12.93 14.04 15.07 16.04 16.94 17.780.44 35.96 8.84 10.46 11.87 13.14 14.30 15.37 16.37 17.31 18.20

2-Row 0.13 6.7 11.23 13.54 15.26 16.59 17.55 — — — —Capacity 0.19 13.73 11.97 14.76 16.96 18.73 20.19 21.41 22.44 23.33 24.11

kW 0.25 22.76 12.35 15.41 17.89 19.94 21.65 23.11 24.37 25.47 26.440.32 33.84 12.58 15.81 18.47 20.70 22.59 24.22 25.64 26.89 28.000.38 46.84 12.73 16.08 18.88 21.23 23.25 25.00 26.53 27.90 29.110.44 61.73 12.84 16.28 19.17 21.62 23.73 25.58 27.20 28.65 29.95

Coils - Water Weights

Internal Internal OperatingUnit Fan Coil Volume Volume WeightType Size Type (M3) (L) (kg)VPWF 01,02 1-Row 0.000533 0.533 5.6VPWF 01,02 2-Row 0.000949 0.949 7.7VPWF 03-07 1-Row 0.000839 0.839 6.5VPWF 03-07 2-Row 0.001463 1.463 9.1

Temperature Correction Factors for Water Pressure Drop (kPa)

Average Water Temperature 93 88 82 77 71 66 60 54 49 43Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (kW)

Entering Water Minus Entering Air 22 27 33 38 44 50 55 61 67 72Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187

)WTD = EWT - LWT =( kWLAT = EAT + (kW x 0.83(4.19)L/sL/s )

Page 14: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN88

PerformanceData—Electrical Data

VPEF Electric Coil kW Guidelines – Minimum to MaximumFan Single-Phase Voltage Three-Phase VoltageSize Stages 208V/240V 277V 347V 480V 208V 480V 575V

01 1 0.5–4.0 0.5–4.0 0.5–4.0 0.5–4.0 1.0–4.0 1.0–4.0 1.5–4.02 0.5–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 2.0–4.0 3.0–4.03** 1.0 - 4.0 1.0–4.0 1.5–4.0 1.0–4.0 1.5–4.0 3.0–4.0 —

02 1 0.5–6.0 0.5–6.0 0.5–6.0 0.5–6.0 1.0–6.0 1.0–6.0 1.5–6.02 0.5–6.0 1.0–6.0 1.0–6.0 1.0–6.0 1.0–6.0 2.0–6.0 3.0–6.03** 1.0 - 6.0 1.0–6.0 1.5–6.0 1.0–6.0 1.5–6.0 3.0–6.0 4.5–6.0

03 1 0.5–8.0 0.5–8.0 0.5–8.0 0.5–8.0 1.0–8.0 1.0–8.0 1.5–8.02 0.5–8.0 1.0–8.0 1.0–8.0 1.0–8.0 1.0–8.0 2.0–8.0 3.0–8.03** 1.0–8.0 1.0–8.0 1.5–8.0 1.0–8.0 1.5–8.0 3.0–8.0 4.5–8.0

04 1 0.5–8.0 0.5–9.0 0.5–9.0 0.5–9.0 1.0–9.0 1.0–9.0 1.5–9.02 0.5–8.0 1.0–9.0 1.0–9.0 1.0–9.0 1.0–9.0 2.0–9.0 3.0–9.03** 1.0–8.0 1.0–9.0 1.5–9.0 1.0–9.0 1.5–9.0 3.0–9.0 4.5–9.0

05 1 0.5–8.0 0.5–12.0 0.5–12.0 0.5–12.0 1.0–12.0 1.0–12.0 1.5–12.02 0.5–8.0 1.0–12.0 1.0–12.0 1.0–12.0 1.0–12.0 2.0–12.0 3.0–12.03** 1.0–8.0 1.0–12.0 1.5–12.0 1.0–12.0 1.5–12.0 3.0–12.0 4.5–12.0

06* 1 0.5–8.0 0.5–12.0 0.5–15.0 0.5–16.0 1.0–15.0 1.0–16.0 1.5–16.02 0.5–8.0 1.0–12.0 1.0–15.0 1.0–16.0 1.0–15.0 2.0–16.0 3.0–16.03** 1.0–8.0 1.0–12.0 1.5–15.0 1.0–16.0 1.5–15.0 3.0–16.0 4.5–16.0

07* 1 0.5–8.0 0.5–11.0 0.5–15.0 0.5–20.0 1.0–14.0 1.0–20.0 1.5–20.02 0.5–8.0 1.0–11.0 1.0–15.0 1.0–20.0 1.0–14.0 2.0–20.0 3.0–20.03** 1.0–8.0 1.0–11.0 1.5–15.0 1.0–20.0 1.5–14.0 3.0–20.0 4.5–20.0

* Not available with 240/1** Three stages of electric heat available only with pneumatic controls.

Notes:1. Coils available with 24-VAC magnetic or mercury contactors, load carrying P.E. switches, and P.E. switch with magnetic or mercury contactors.2. Available kW increments are by 0.5 from 0.5 kW to 8.0 kW, by 1.0 kW from 9.0 to 18.0 kW, and by 2.0 kW from 18.0 to 20.0 kW.3. Each stage will be equal in kW output.4. All heaters contain an auto thermal cutout and a manual reset cutout .5. The current amp draw for the heater elements is calculated by the formula below.

Notes:1. Electric Heat Units - Units with Primary Voltage of 208/60/1,

208/60/3, or 240/60/1 use 115 VAC fan motors.2. Electric Heat Units - Units with Primary Voltage of 277/60/1,

480/60/1 or 480/60/3 use 277 VAC fan motors.3. Electric Heat Units - Units with Primary Voltage of 347/60/1 or

575/60/3 use 347 VAC fan motors.4. Values are for standard, single-speed, permanent split capacitor

type motors. Consult factory for non-standard motorperformance.

Minimum Circuit Ampacity (MCA) Equation� MCA = (motor amps + heater amps) x 1.25

Maximum Overcurrent Protection (MOP) Equation� MOP = (2.25 x motor amps) + heater amps

General Sizing Rules:� If MOP = 15, then fuse size = 15

� If MOP = 19, then fuse size = 15 with one exception. If heateramps x 1.25 > 15, then fuse size = 20.

� If MOP £ MCA, then choose next fuse size greater than MCA.

� Control fusing not applicable.

� Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.

Fan Electrical PerformanceMaximum Fan Motor Amperage (FLA)

Fan Size HP 115 VAC 208 VAC 277 VAC 347 VAC

01 1/8 1.6 — 0.7 0.702 1/8 1.6 — 0.7 0.703 1/3 5.4 — 1.8 1.504 1/3 5.4 — 1.8 1.505 1/2 7.6 — 2.6 2.106 1/2 — 6.3 3.8 3.807 1 — 6.9 4.7 3.6

Example:

A model VPEF, electric reheat unit size 1005 has 480/3 phase, 12 kW electric reheatwith 2 stages and 277-Volt motor.

For MOP of fan-powered unit:

12 kW - 480/3 heater 12 x 1000 = 14.45 amps480 x 1.73

MCA = (2.6 + 14.45) x 1.25 = 21.31, MOP = (2.25 x 2.6) + 14.45 = 20.3.

Since MOP £MCA, then MOP = 25.

For total current draw of unit:

Electric Actuator = 0.17 ampsDDC UCM Control Board = 0.3312 kW—480/3 heater 12 x 1000 = 14.45

480 x 1.73Two heat outputs (2 stages) @0.5 amps max each = 1.00Motor amps: 277 V (Fan size 05) = 2.6

18.55 amps max

kW = 1214 x L/s x ATD

1famps = kW x 1000Primary Voltage

ATD = kW x 3145CFM

3145CFM x ATDkW =

3famps =kW x 1000

Primary Voltage x Ö 3

1214 x L/sATD = kW

Useful formulas:

Page 15: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

89VAV-PRC005-EN

PerformanceData—Acoustics

Discharge Sound Power (dB)Valve Only

Discharge Sound Power (dB)0.5" Inlet 1.0" Inlet 2.0" Inlet 3.0" Inlet

Fan Inlet Pressure (127 Pa) Pressure (254 Pa) Pressure (508 Pa) Pressure (762 Pa)Size Size Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

01 6 200 94 51 50 44 43 38 30 53 51 48 47 43 39 56 53 54 53 51 50 59 55 57 57 56 5602 300 142 56 52 49 48 44 35 58 55 54 53 50 43 60 57 57 56 54 50 62 59 61 59 57 55

400 189 58 53 49 47 42 36 63 59 58 57 54 46 64 61 60 61 58 52 65 63 63 63 60 56500 236 60 56 53 51 47 41 66 62 60 59 55 47 67 64 64 65 62 55 69 67 66 68 65 58

01 8 350 165 54 51 48 48 44 34 58 55 53 53 51 46 63 60 59 58 57 54 64 61 61 60 59 5702 520 245 59 55 53 53 51 41 63 59 57 57 55 47 67 64 62 63 61 56 69 66 65 65 64 59

700 330 64 59 57 57 55 46 66 63 61 62 60 51 70 66 65 66 64 57 73 70 69 70 68 62900 425 67 63 60 60 57 48 69 67 65 66 63 56 72 70 69 70 67 60 76 72 71 72 70 63

02 10 550 260 59 54 52 52 49 39 63 59 57 57 55 47 67 64 62 62 59 54 69 66 65 65 62 58820 387 62 57 56 56 54 44 67 63 61 61 59 51 72 69 67 67 65 58 74 71 70 70 67 611100 519 65 60 59 59 58 48 69 66 64 65 63 55 75 71 70 70 68 60 78 74 73 74 71 641400 661 67 64 62 62 60 51 72 69 67 67 65 57 78 74 72 73 71 63 81 77 76 76 74 67

03 8 350 165 54 52 48 48 45 35 57 55 53 52 50 44 61 59 58 57 56 53 63 60 61 60 60 5804 520 245 57 54 50 50 46 37 62 60 57 57 55 48 64 64 62 62 60 55 66 66 65 65 63 60

700 330 58 55 50 50 46 39 65 62 60 59 56 49 70 68 66 66 63 56 71 69 68 69 67 61900 425 59 57 53 53 47 43 65 62 59 58 54 50 73 71 69 68 65 58 76 73 72 72 70 63

03 10 550 260 57 53 52 52 49 40 60 58 56 57 55 49 65 64 62 63 61 56 67 66 65 65 63 5904 820 387 62 57 55 55 52 42 66 63 61 62 59 51 70 68 67 68 66 61 72 70 70 70 68 6305 1100 519 63 60 57 55 52 43 71 67 64 65 62 54 74 71 70 71 68 62 76 74 73 74 72 66

1400 661 65 62 59 56 51 44 73 69 66 65 62 54 78 75 73 73 71 63 80 77 76 77 75 6703 12 800 378 60 55 55 54 51 42 65 61 61 61 59 51 68 66 65 66 64 57 70 69 68 69 67 6004 1200 566 62 57 56 54 52 43 70 65 64 64 61 54 74 71 70 71 68 61 76 74 73 74 72 6505 1600 755 64 60 59 55 52 44 72 67 65 65 62 55 78 74 72 73 71 63 80 77 76 77 75 68

2000 944 66 62 61 55 52 46 73 69 67 65 63 55 81 76 74 74 71 64 83 80 78 78 77 6905 14 1100 519 58 55 55 55 53 45 65 62 61 62 60 53 72 69 68 68 66 60 75 72 72 72 70 64

1600 755 61 58 58 58 56 47 68 64 65 65 63 57 77 71 71 72 70 64 81 75 75 75 73 672100 991 64 61 61 59 58 48 69 66 66 66 64 58 77 73 72 73 71 65 82 77 77 77 75 693000 1416 68 65 66 61 59 52 73 70 70 68 65 60 79 76 76 76 74 67 82 79 79 79 78 71

06 12 800 378 55 52 51 49 46 37 59 57 56 54 52 47 64 63 62 59 57 52 66 67 66 62 60 561200 566 60 56 56 54 51 42 64 61 60 59 57 51 69 67 66 64 62 56 71 70 69 67 64 591600 755 63 60 60 57 54 45 68 65 64 63 60 54 72 70 69 68 65 59 75 73 72 71 68 622000 944 67 63 63 59 57 48 71 68 67 65 63 56 75 73 72 71 68 62 79 75 75 73 71 65

06 14 1100 519 57 53 53 51 48 41 62 59 58 57 54 48 66 65 64 61 60 55 70 70 69 64 62 5907 1600 755 61 57 56 55 52 45 66 63 62 61 58 52 71 69 68 66 64 59 74 72 71 69 67 62

2100 991 64 60 60 57 55 47 69 66 66 64 61 55 74 71 71 69 67 61 77 75 74 72 70 653000 1416 70 66 66 63 60 53 74 70 69 68 65 58 80 75 74 73 71 65 84 78 78 76 74 68

06 16 1400 661 59 56 54 54 51 43 64 62 61 60 57 52 69 69 67 65 62 57 72 74 72 67 65 6107 2100 991 61 59 58 56 54 46 68 65 63 62 60 55 73 72 71 69 67 62 75 75 74 72 70 65

2800 1321 64 62 61 59 56 49 70 67 66 65 62 57 77 73 72 71 69 64 80 77 76 75 73 684000 1888 70 67 67 64 61 55 74 71 70 68 65 60 81 76 75 74 71 66 86 79 78 77 75 70

Notes:1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.

Page 16: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN90

PerformanceData—Acoustics

Radiated Sound Power (dB)Valve Only

Radiated Sound Power (dB)0.5" Inlet 1.0" Inlet 2.0" Inlet 3.0" Inlet

Fan Inlet Pressure (127 Pa) Pressure (254 Pa) Pressure (508 Pa) Pressure (762 Pa)Size Size Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

01 6 200 94 48 40 38 35 31 25 48 44 42 37 33 26 53 48 47 43 38 33 54 50 47 44 41 3702 300 142 51 45 42 35 29 24 54 49 46 39 33 26 57 51 50 44 38 32 60 55 53 48 42 37

400 189 54 48 46 38 32 25 58 53 49 42 35 26 61 55 52 47 40 33 63 57 55 49 43 37500 236 52 50 48 40 33 27 62 56 52 45 37 29 65 59 56 50 42 34 65 60 57 52 45 38

01 8 350 165 50 45 40 36 31 25 55 49 44 40 34 27 59 54 49 44 40 35 62 56 52 47 43 3902 520 245 54 49 43 38 32 24 59 54 48 43 37 27 64 58 53 48 42 35 66 61 56 51 46 40

700 330 59 54 48 43 36 26 62 58 51 47 40 30 67 61 56 51 44 36 70 64 59 54 48 40900 425 71 63 55 49 44 39 71 64 56 52 47 41 73 66 59 55 50 44 76 68 62 57 53 46

02 10 550 260 57 50 44 39 32 25 61 54 48 42 36 28 65 58 52 46 40 34 67 60 56 50 43 38820 387 59 52 46 41 34 25 64 58 52 46 40 31 69 63 56 51 44 37 71 66 60 54 47 401100 519 62 56 50 44 41 26 66 61 54 49 42 33 72 66 60 54 48 39 75 68 63 57 51 421400 661 65 60 53 47 44 30 68 64 57 52 45 36 74 69 63 57 50 41 77 71 66 60 53 44

03 8 350 165 53 47 42 37 33 25 55 50 44 39 34 27 60 54 47 43 38 33 62 56 50 46 41 3804 520 245 55 50 43 38 33 25 59 55 47 42 35 28 64 60 51 47 40 36 66 61 54 49 44 39

700 330 57 51 43 39 33 26 63 59 50 44 37 30 68 64 55 50 42 36 70 66 58 53 46 41900 425 59 54 47 42 35 30 64 60 51 45 37 32 72 67 59 53 45 39 73 68 62 56 49 42

03 10 550 260 54 48 42 40 33 23 57 52 46 42 36 29 63 58 50 46 40 33 65 60 53 49 43 3804 820 387 58 51 44 39 31 24 64 58 50 45 39 31 67 62 55 51 44 36 70 64 58 53 47 4005 1100 519 60 54 45 39 31 24 67 61 53 47 40 34 73 67 59 54 47 42 74 68 62 57 51 42

1400 661 62 57 47 42 33 26 70 64 55 49 41 35 76 69 62 56 49 43 78 72 65 60 53 4703 12 800 378 58 50 44 40 33 26 62 55 49 45 38 31 66 60 54 50 43 36 68 63 56 52 46 3904 1200 566 61 53 46 40 33 27 66 59 52 48 41 34 71 65 59 54 47 40 73 67 62 57 51 4305 1600 755 63 56 47 41 34 27 68 62 54 48 41 35 75 68 61 56 49 42 77 71 65 60 53 46

2000 944 65 58 49 47 36 31 70 63 55 50 42 35 77 70 62 57 50 43 79 73 67 61 55 4805 14 1100 519 57 52 47 43 37 28 63 58 52 47 40 34 69 64 58 54 47 40 72 68 61 57 50 45

1600 755 61 55 49 44 36 29 67 61 55 50 43 37 73 67 61 57 50 43 76 71 65 60 54 472100 991 64 57 51 45 37 30 69 63 58 52 45 39 75 69 64 59 52 46 78 72 67 62 55 503000 1416 68 62 57 49 41 33 72 66 60 54 45 38 77 71 65 60 52 47 80 75 69 64 57 51

06 12 800 378 53 47 42 37 31 25 57 52 45 41 35 31 62 58 50 45 39 33 65 62 53 48 42 371200 566 56 52 45 41 36 26 60 56 49 44 37 31 67 62 54 48 41 35 70 65 57 51 45 381600 755 60 56 48 43 39 29 64 60 52 47 40 34 71 65 57 51 44 37 74 68 60 54 48 412000 944 64 59 51 46 41 31 69 63 55 50 42 37 74 68 60 55 50 46 77 71 64 59 54 51

06 14 1100 519 56 49 44 40 32 25 61 55 48 44 38 30 66 61 54 49 43 36 69 66 57 51 45 4007 1600 755 59 53 47 42 35 27 65 59 52 48 41 33 70 64 58 53 46 39 74 68 61 55 49 42

2100 991 64 57 51 46 38 29 68 61 55 50 43 35 74 67 61 55 49 41 77 70 64 59 52 453000 1416 71 62 56 50 42 33 74 66 59 54 46 38 78 70 64 58 51 44 82 74 68 62 56 48

06 16 1400 661 63 54 48 41 36 29 67 59 53 46 42 35 70 66 58 52 48 40 72 70 61 54 50 4307 2100 991 66 57 51 44 39 32 71 63 56 49 45 38 75 69 63 56 52 44 77 72 66 59 55 47

2800 1321 68 60 54 46 41 34 73 65 59 51 47 40 79 72 66 59 54 47 81 75 69 62 58 514000 1888 73 66 60 56 52 50 78 70 63 56 50 45 83 75 70 62 57 50 85 78 72 65 60 53

Notes:1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.

Page 17: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

91VAV-PRC005-EN

PerformanceData—Acoustics

Notes:1. “–“ represents NC levels below NC 15.2. NC Values are calculated using ARI 885-98, Type 2 –

Mineral Fiber Insulation.

ARI 885-98 DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Small Box (< 300 cfm) -25 -28 -38 -53 -58 -31Medium Box (300-700 cfm) -27 -29 -39 -51 -53 -33Large Box (> 700 cfm) -29 -30 -40 -51 -51 -35Note: Subtract from terminal unit sound power to determine dischargesound pressure in the space.

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Type 1 – Glass Fiber -19 -19 -21 -25 -29 -35Type 2 – Mineral Fiber Insulation -18 -19 -20 -26 -31 -36Type 3 – Solid Gypsum Board -23 -26 -25 -27 -27 -28Note: Select the ceiling type which most closely represents theapplication. Next, subtract from terminal unit sound power to determineradiated sound pressure in the space.

Fan Only Sound PowerDischarge Sound Power (dB) Radiated Sound Power (dB)

Fan Outlet Fan Octave Bands Octave BandsSize Static Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7

01 200 94 52 49 47 44 38 32 58 51 51 47 42 340.25 240 113 55 50 50 47 42 38 60 52 52 49 44 37

(63 Pa) 280 132 59 52 52 50 45 42 66 59 57 53 48 43340 160 61 53 53 51 45 43 67 59 58 54 49 44400 189 63 54 55 53 47 45 68 60 58 54 49 46

02 280 132 60 53 52 49 44 39 64 56 54 51 45 400.25 330 156 61 54 53 51 45 41 66 58 55 52 47 42

(63 Pa) 390 184 63 55 54 52 47 43 67 58 56 53 48 44470 222 67 57 57 55 49 47 69 61 58 56 50 47550 260 69 59 58 57 51 50 73 63 60 58 52 50

03 400 189 58 53 51 47 42 39 66 56 53 52 46 420.25 480 227 59 54 52 49 44 42 67 57 54 54 48 44

(63 Pa) 560 264 61 55 54 51 46 45 70 59 56 55 50 47680 321 65 57 57 54 49 48 73 62 59 58 53 50800 378 69 61 60 58 54 53 76 65 61 62 57 54

04 530 250 56 53 53 50 45 43 62 62 55 55 50 440.25 630 297 58 54 55 51 47 45 64 64 57 56 52 46

(63 Pa) 740 349 60 56 58 54 50 49 65 64 58 58 54 49890 420 62 59 61 58 54 53 67 65 60 60 56 531050 496 64 61 63 61 58 57 69 68 63 63 59 56

05 680 321 58 56 53 50 45 41 68 62 55 52 48 430.25 810 382 60 57 55 52 48 45 69 63 57 55 50 46

(63 Pa) 950 448 61 58 57 53 50 47 70 64 59 56 52 481150 543 63 60 59 56 53 51 72 65 61 59 55 521350 637 65 62 62 60 57 56 74 66 63 62 58 55

06 930 439 62 56 55 56 47 46 67 60 57 55 46 440.25 1110 524 63 57 56 57 48 48 69 61 58 57 48 46

(63 Pa) 1300 614 66 60 59 58 52 52 71 62 60 57 50 491570 741 69 64 63 62 57 57 72 65 63 60 54 541850 873 72 68 66 65 61 61 76 69 66 63 58 58

07 1200 566 63 59 58 55 50 47 69 60 61 56 50 450.25 1440 680 66 63 61 58 55 52 72 63 63 58 53 49

(63 Pa) 1680 793 69 66 66 62 59 57 74 65 65 60 56 532040 963 72 70 69 66 63 61 77 70 69 64 60 572400 1133 74 72 71 68 65 64 80 72 72 68 64 61

Notes:1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.

Sound Noise Criteria (NC)Fan Only

Fan Fan Outlet Discharge RadiatedSize Cfm L/s Static NC Level NC Level

01 200 94 — 25240 113 0.25 — 26280 132 (63 Pa) — 32340 160 — 33400 189 15 33

02 280 132 — 29330 156 0.25 — 30390 184 (63 Pa) 15 31470 222 20 34550 260 22 39

03 400 189 — 30480 227 0.25 — 31560 264 (63 Pa) — 35680 321 15 39800 378 20 42

04 530 250 — 32630 297 0.25 — 35740 349 (63 Pa) — 35890 420 17 361050 496 21 39

05 680 321 — 32810 382 0.25 — 34950 448 (63 Pa) — 351150 543 16 371350 637 20 40

06 930 439 — 321110 524 0.25 — 341300 614 (63 Pa) 16 361570 741 21 381850 873 26 42

07 1200 566 15 361440 680 0.25 20 381680 793 (63 Pa) 24 402040 963 29 452400 1133 31 48

Page 18: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN92

PerformanceData—Acoustics

Notes:1. “–“ represents NC levels below NC 15.2. NC Values are calculated using ARI 885-98, Type 2 – Mineral Fiber Insulation..

ARI 885-98 DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Small Box (< 300 cfm) -25 -28 -38 -53 -58 -31Medium Box (300-700 cfm) -27 -29 -39 -51 -53 -33Large Box (> 700 cfm) -29 -30 -40 -51 -51 -35Note: Subtract from terminal unit sound power to determine dischargesound pressure in the space.

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Type 1 – Glass Fiber -19 -19 -21 -25 -29 -35Type 2 – Mineral Fiber Insulation -18 -19 -20 -26 -31 -36Type 3 – Solid Gypsum Board -23 -26 -25 -27 -27 -28Note: Select the ceiling type which most closely represents theapplication. Next, subtract from terminal unit sound power to determineradiated sound pressure in the space.

Sound Noise Criteria (NC)Valve Only

Discharge RadiatedNC Level NC Level

Fan Inlet 05" 1.0" 2.0" 3.0" 0.5" 1.0" 2.0" 3.0"Size Size Cfm L/s (127 Pa) (254 Pa) (508 Pa) (762 Pa) (127 Pa) (254 Pa) (508 Pa) (762 Pa)

01 6 200 94 — — — 19 — 15 21 2102 300 142 — — 15 18 15 20 24 27

400 189 — 17 20 22 20 23 26 30500 236 — 21 24 27 22 26 31 32

01 8 350 165 — — 18 21 — 17 23 2602 520 245 — 16 22 25 16 22 27 31

700 330 16 21 25 30 22 27 31 35900 425 21 26 30 32 36 36 39 42

02 10 550 260 — 15 21 24 19 24 29 31820 387 — 20 27 30 21 27 34 371100 519 16 24 30 34 25 31 37 411400 661 21 27 34 37 30 35 40 44

03 8 350 165 — — 17 22 15 17 22 2504 520 245 — 17 22 25 17 24 30 31

700 330 — 20 27 29 19 29 35 37900 425 — 20 31 34 22 30 38 39

03 10 550 260 — — 21 24 15 20 27 3004 820 387 — 20 26 29 20 27 32 3505 1100 519 16 25 30 34 22 31 39 40

1400 661 19 27 35 37 26 35 42 4503 12 800 378 — 17 24 27 20 25 30 3404 1200 566 — 22 30 34 24 30 36 3905 1600 755 16 25 34 37 26 32 41 44

2000 944 19 27 36 40 29 35 44 4605 14 1100 519 — 19 27 31 21 27 35 39

1600 755 — 21 30 35 24 31 39 422100 991 17 24 32 37 27 34 41 453000 1416 322 29 36 39 2 37 44 47

06 12 800 378 — — 20 25 15 20 27 321200 566 — 17 25 29 20 25 32 361600 755 16 22 29 32 25 30 36 402000 944 20 26 32 35 29 34 40 44

06 14 1100 519 — 15 22 29 17 24 31 3707 1600 755 — 20 27 31 21 29 35 40

2100 991 16 24 30 35 27 32 40 443000 1416 24 29 35 39 36 40 45 50

06 16 1400 661 — 19 27 34 26 31 37 4107 2100 991 15 22 31 35 30 36 41 44

2800 1321 19 25 32 37 32 39 46 494000 1888 25 30 36 41 39 45 52 55

Page 19: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

93VAV-PRC005-EN

PerformanceData—Acoustics

Radiated Sound Power (dB)Fan OnlyARI Conditions

Fan InletSize Size Cfm L/s 2 3 4 5 6 7

01 6,8 400 189 68 60 58 54 49 4602 6,8,10 550 260 73 63 60 58 52 5003 8,10,12 800 378 76 65 61 62 57 5404 8,10,12 1050 496 69 68 63 63 59 5605 10,12,14 1350 637 74 66 63 62 58 5506 12,14,16 1850 873 76 69 66 63 58 5807 14,16 2400 1133 80 72 72 68 64 61

Discharge Sound Power (dB)Fan OnlyARI Conditions

Fan InletSize Size Cfm L/s 2 3 4 5 6 7

01 6,8 400 189 63 54 55 53 47 4502 6,8,10 550 260 69 59 58 57 51 5003 8,10,12 800 378 69 61 60 58 54 5304 8,10,12 1050 496 64 61 63 61 58 5705 10,12,14 1350 637 65 62 62 60 57 5606 12,14,16 1850 873 72 68 66 65 61 6107 14,16 2400 1133 74 72 71 68 65 64

Notes:1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.

Discharge Sound Power (dB)Valve OnlyARI Conditions

Fan Inlet 1.5" Inlet Pressure (381 Pa)Size Size Cfm L/s 2 3 4 5 6 7

01 6 400 189 63 60 59 60 57 490201 8 700 330 68 65 63 64 62 540202 10 1100 519 68 66 64 64 61 5303 8 700 330 73 69 68 68 66 580403 10 1100 519 73 69 67 68 65 58040503 12 1600 755 75 71 69 69 67 60040505 14 2100 991 73 70 70 70 68 6306 12 1600 755 70 68 67 66 63 5706 14 2100 991 72 69 68 67 64 580706 16 2800 1321 74 70 69 68 66 6107

Radiated Sound Power (dB)Valve OnlyARI Conditions

Fan Inlet 1.5" Inlet Pressure (381 Pa)Size Size Cfm L/s 2 3 4 5 6 7

01 6 400 189 60 54 51 44 37 290201 8 700 330 65 59 54 49 42 330202 10 1100 519 70 64 58 52 45 3603 8 700 330 66 62 54 47 40 340403 10 1100 519 71 65 57 51 44 39040503 12 1600 755 73 65 58 53 46 40040505 14 2100 991 72 66 60 55 48 4306 12 1600 755 68 63 55 49 42 3606 14 2100 991 72 64 58 53 46 380706 16 2800 1321 76 69 62 55 51 4407

Page 20: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN94

DimensionalData

DISCHARGE OUTLETAIRFLOW

AIR

AIRFLOW

TOP VIEW

BACK VIEW

PARALLEL COOLING ONLY (VPCF)

400 (189)

560 (264)

800 (378)

1040 (491)

1360 (642)

1840 (868)

2400 (1133)

10" (254 mm)1004

10051205

1206

16061406

14071607

1204

16" (406 mm)

10" (254 mm)

12" (305 mm)

12" (305 mm)14" (356 mm)

14" (356 mm)16" (406 mm)

12" (305 mm)

INLET/FANSIZE

06010801

06020802100208031003

0804

INLET SIZE

10" (254 mm)

8" (203 mm)6" (152 mm)

6" (152 mm)

8" (203 mm)

8" (203 mm)10" (254 mm)

8" (203 mm)

(NOMINAL Ø)

1400 (661)

4000 (1888)

3000 (1416)

2000 (994)

2000 (994)1400 (661)

4000 (1888)

3000 (1416)

2000 (994)

21.50" (546 mm)

15.50" (394 mm)

CFM/LPS

900 (425)

1400 (661)900 (425)

900 (425)500 (236)

500 (236)900 (425)

1400 (661)

INLETFAN

40.00" (1016 mm)

H WDISCHARGE DIMENSIONS

14.00" (356 mm)

20.00" (508 mm)

30.00" (762 mm)

40.00" (1016 mm)

LA

19.25" (489 mm)

B

1203 12" (305 mm) 2000 (994)

1405 14" (356 mm) 3000 (1416)

VALVE

Wt

CUSTOMER NOTE:

1. Allow 6" (152 mm) clearance for plenum inlet.

2. Filter mounts in filter frame.

85 (39)

117 (53)124 (56)125 (57)

98 (44)99 (45)

115 (52)

116 (53)

86 (39)

100 (45)

76 (34)77 (35)78 (35)83 (38)84 (38)

84 (38)

85 (39)

76 (34)77 (35)

Lbs(kg)

20.00"(508 mm)

4.00"(102 mm)

L

6.50"(165 mm)

6.50"(165 mm)

W

H

5.50"(140 mm)

8.25"(210 mm) A

DISCHARGE

BDISCHARGE

ACTUATOR

FLOW RING TUBING

CONTROL BOXANALOG OR DDC/UCM

FAN CONTROL BOX

3. Fan and motor access is through plenum inlet.

4.00"(102 mm)

(356 mm x 508 mm x 25 mm)14" x 20" x 1"

Filter Size

20" x 20" x 1"(508 mm x 508 mm x 25 mm)

Fan Size

01 and 02

03 thru 07

2.00" (51 mm)SIZE 16 ONLY

Page 21: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

95VAV-PRC005-EN

DimensionalData

DISCHARGE OUTLETAIRFLOW

AIR

AIRFLOW

TOP VIEW

BACK VIEW

PARALLEL HOT WATER (VPWF)

40.00" (1016 mm)

INLET SIZE(NOMINAL Ø)

6" (152 mm)8" (203 mm)

8" (203 mm)6" (152 mm)

10" (254 mm)

10" (254 mm)8" (203 mm)

12" (305 mm)

10" (254 mm)

16" (406 mm)

10" (254 mm)12" (305 mm)

12" (305 mm)14" (356 mm)

12" (305 mm)

14" (356 mm)

16" (406 mm)14" (356 mm)

8" (203 mm)

INLET/FANSIZE

900 (425)1040 (491)1400 (661)

2000 (994)

2000 (994)1400 (661)

4000 (1888)3000 (1416)

2000 (994)

3000 (1416)

3000 (1416)4000 (1888)

1360 (642)

1840 (868)

2400 (1133)

INLET

500 (236)900 (425)500 (236)900 (425)

1400 (661)900 (425)1400 (661)2000 (994)

400 (189)

560 (264)

800 (378)

CFM/LPS

FAN

15.50" (394 mm)

21.50" (546 mm)

H

19.25" (489 mm)

DISCHARGE DIMENSIONS

40.00" (1016 mm)

30.00" (762 mm)

W L

20.00" (508 mm)

14.00" (356 mm)

A B

WATERCOIL

VALVE

1607140716061406120614051205100512041004

080412031003080310020802060208010601

WT

CUSTOMER NOTES.

4. Water coil casing is non-symmetrical and

2. Allow 6" (152 mm) clearance for plenum inlet.

3. Filter is secured to front of coil with

1. Coil furnished with stub sweat connections.

thus cannot be rotated to obtain coil

filter clips.

connections on the other side.

97 (44)

130 (59)137 (62)138 (63)

102 (46)113 (51)128 (58)129 (59)

98 (44)99 (45)101 (46)

88 (39)

96 (44)97 (44)98 (44)

87 (39)88 (40)89 (40)

87 (39)

LBS(KGS)

5. Coils are provided without internal insulation.

(356 mm x 508 mm x 25 mm)14" X 20" X 1"

(508 mm x 508 mm x 25 mm)20" X 20" X 1"

Fan Size Filter Size

01 and 02

03 thru 07

ACTUATOR

6.50"(165mm)

6.50"(165 mm)

FLOW RINGTUBING

4.00"(102 mm)

PANEL SLIDES FORMOTOR ACCESS.

6.75"(171 mm)

FAN CONTROL BOX

CONTROL BOXANALOG OR DDC/UCM

8.25"(210 mm)

4.00"(102 mm)

L

20.00"(508 mm)

5.50"(140 mm) W

ADISCHARGE

BDISCHARGEH

sizes are 7/8" (22.2 mm) O.D.6. One and two-row coil connections for all fan

2.00" (51 mm)SIZE 16 ONLY

If the unit is to be installed in a location withhigh humidity, external insulation around theheating coil should be installed as required.

7. For motor access remove bottom screw on hangerbrackets to slide panel as shown in drawing.

Page 22: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN96

DimensionalData

DISCHARGE OUTLETAIRFLOW

AIR

AIRFLOW

TOP VIEW

BACK VIEW

PARALLEL ELECTRIC HEAT (VPEF)

40.00" (1016 mm)

INLET SIZE(NOMINAL Ø)

6" (152 mm)8" (203 mm)

8" (203 mm)6" (152 mm)

10" (254 mm)

10" (254 mm)8" (203 mm)

12" (305 mm)

10" (254 mm)

16" (406 mm)

10" (254 mm)12" (305 mm)

12" (305 mm)14" (356 mm)

12" (305 mm)

14" (356 mm)

16" (406 mm)14" (356 mm)

8" (203 mm)

INLET/FANSIZE

900 (425)1040 (491)1400 (661)

2000 (994)

2000 (994)1400 (661)

4000 (1888)3000 (1416)

2000 (994)

3000 (1416)

3000 (1416)4000 (1888)

1360 (642)

1840 (868)

2400 (1133)

INLET

500 (236)900 (425)500 (236)900 (425)1400 (661)900 (425)1400 (661)

2000 (994)

400 (189)

560 (264)

800 (378)

CFM/LPS

FAN

15.50" (394 mm)

21.50" (546 mm)

H

20.00" (508 mm)

DISCHARGE DIMENSIONS

40.00" (1016 mm)

30.00" (762 mm)

W L

20.00" (508 mm)

14.00" (356 mm)

A B

L

VALVE

Wt

CUSTOMER NOTES:

2. Inside duct dimensions equal outlet size (A x B).Allow 48" (129 mm) straight duct downstreamof unit before first runout.

3. Terminal box access door is side-hinged. Allowfor clearance. (Fan sizes 01 & 02 are 17" (432 mm)long x 14" (356 mm) high). (Fan sizes 03 thru 07are 16" (406 mm) long x 20" (508 mm) high).

5. Knockouts for power supply provided in top &bottom of terminal box.

duct flange.6. Flanged discharge outlet accepts up to a 1" (25mm)

HEATER TERMINAL BOX

4. Filter mounts in filter frame.

1. Allow 6" (152 mm) clearance for plenum inlet.

154 (70)153 (69)146 (66)145 (66)144 (65)129 (59)128 (58)127 (58)115 (52)114 (52)113 (51)114 (52)113 (51)112 (51)99 (45)98 (44)97 (44)98 (44)97 (44)

1607140716061406120614051205100512041004080412031003080310020802060208010601

FLOW RINGTUBING

6.25"(165 mm)

ACTUATOR

6.25"(165 mm)

FAN CONTROL BOX

CONTROL BOXANALOG OR DDC/UCM

ADISCHARGE

LBS

4.00"(102 mm)

20.00"(508 mm)

4.00"(102 mm)

6.00"(152 mm)

BDISCHARGE

5.50"(140 mm) W

H

Filter Size

14" x 20" x 1"(356 mm x 508 mm x 25 mm)

(508 mm x 508 mm x 25 mm)20" x 20" x 1"

Fan Size

01 and 02

03 thru 07

7. Fan and motor access if through the plenum inlet.

(KGS)

SIZE 16 ONLY2.00" (51 mm)

(210 mm)8.25"

heating coil should be installed as required.high humidity, external insulation around theIf the unit is to be installed in a location with

8. Coils are provided without internal insulation.

Page 23: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

97VAV-PRC005-EN

MechanicalSpecifications

MODELS VPCF, VPWF andVPEFParallel fan-powered terminalunits.

VPCF – Cooling Only

VPWF – With Hot Water Coil

VPEF – With Electric Coil

CASING22-gage galvanized steel. Hangerbrackets, side access, and filter whichis on the plenum inlet are providedas standard.

AGENCY LISTINGThe unit is UL and Canadian ULListed as a room air terminal unit.Control # 9N65.

ARI 880 Certified.

INSULATION

1/2" (12.7 mm) Matte-facedInsulation—The interior surface of theunit casing is acoustically andthermally lined with ½-inch, 1.75 lb/ft3

(12.7 mm, 28.03 kg/m3) compositedensity glass fiber with a high-densityfacing of 4.0 lb/ft3 (64 kg/m3). Theinsulation R-Value is 1.9. The insulationis UL listed and meets NFPA-90A andUL 181 standards. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Matte-facedInsulation—The interior surface of theunit casing is acoustically andthermally lined with 1 inch, 1.55 lb/ft3

(25.4 mm, 24.8 kg/m3) compositedensity glass fiber with a high-densityfacing of 4.0 lb/ft3 (64 kg/m3). Theinsulation R-Value is 3.85. Theinsulation is UL listed and meetsNFPA-90A and UL 181 standards. Thereare no exposed edges of insulation(complete metal encapsulation).

1/2" (12.7 mm) Foil-facedInsulation—The interior surface of theunit casing is acoustically andthermally lined with ½-inch, 2.0 lb/ft3

(12.7 mm, 32.04 kg/m3) density glassfiber with foil facing. The insulationR-Value is 2.2. The insulation is ULlisted and meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Foil-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 1-inch, 2.0 lb/ft3

(25.4 mm, 32.04 kg/m3) density glassfiber with foil facing. The insulation R-Value is 4.3. The insulation is UL listedand meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Double-wallInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with a 1-inch, 2.1 lb./ft3

(25.4 mm, 33.6 kg/m3) compositedensity glass fiber with high-densityfacing. The insulation R-value is 3.0. Theinsulation is UL listed and meets NFPA-90A and UL 181 standards. Theinsulation is covered by an interiorliner made of 26-gage galvanized steel.All wire penetrations are covered bygrommets. There are no exposededges of insulation (complete metalencapsulation).

3/8" (9.5 mm) Closed-cellInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 3/8-inch, 4.4 lb/ft3

(9.5 mm, 40.0 kg/m3) closed-cellinsulation. The insulation is UL listedand meets NFPA-90A and UL 181standards. The insulation has anR-Value of 1.4. There are no exposededges of insulation (complete metalencapsulation).

PRIMARY AIR VALVE

Air Valve Round—The primary airinlet connection is an 18-gagegalvanized steel cylinder sized to fitstandard round duct. A multiple-point,averaging flow sensing ring isprovided with balancing taps formeasuring +/-5% of unit catalogedairflow. An airflow-versus-pressuredifferential calibration chart is provided.The damper blade is constructed of aclosed-cell foam seal that ismechanically locked between two 22-gage galvanized steel disks. Thedamper blade assembly is connectedto a cast zinc shaft supported by self-lubricating bearings. The shaft is castwith a damper position indicator. Thevalve assembly includes a mechanicalstop to prevent over-stroking. At 4 in.wg, air valve leakage does not exceed1% of cataloged airflow.

FAN MOTORSingle-speed, direct-drive, permanentsplit capacitor type. Thermal overloadprotection provided. Motors will bedesigned specifically for use with anopen SCR. Motors will accommodateanti-backward rotation at start up.Motor and fan assembly are isolatedfrom terminal unit.

FAN SPEED CONTROL

Variable Speed Control Switch(SCR)—The SCR speed control deviceis provided as standard and allows theoperator infinite fan speed adjustmentso the fan output may be modified toachieve exact cfm requirements.

Air Valve/Fan Combinations Available:

Air Valve FanSize Airflow Airflow(in.) (cfm) Size (cfm)

06 500 01 50002 615

08 900 01 50002 61503 92504 1150

10 1400 02 61503 92504 115005 1675

12 2000 03 92504 115005 167506 2350

14 3000 05 167506 235007 2500

16 4000 06 235007 2500

Air Valve FanSize Airflow Fan Airflow

(mm) (L/s) Size (L/s)

06 (152) 236 01 23602 290

08 (203) 425 01 23602 29003 43704 543

10 (254) 661 02 29003 43704 54305 791

12 (305) 944 03 43704 54305 79106 1109

14 (356) 1416 05 79106 110907 1180

16 (406) 1888 06 110907 1180

Page 24: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN98

MechanicalSpecifications

TRANSFORMERThe 50-VA transformer is factory-installed in the fan control box toprovide 24 VAC for controls.

POWER DISCONNECTThe power disconnect is provided asstandard and allows the operator toturn the unit on or off by toggling tothe appropriate setting. This switchbreaks both legs of power to the fanand the electronic controls (ifapplicable)

OUTLET CONNECTION

Flanged Connection—A rectangularopening on the unit discharge toaccept a 90° flanged ductworkconnection.

FILTERA 1" (25 mm) filter is provided on theplenum inlet and attaches to the unitwith a filter frame.

ACCESS PANELInternal access to unit is achievedthrough plenum inlet for cooling andelectric units. For hot water units, thepanel opposite of control side slidesopen for access.

HOT WATER COIL

Parallel Water Coils—factory-installed on the plenum inlet.

The coil has 1-row with 144 aluminum-plated fins per foot (.305 m), and ifneeded 2-row with 144 aluminum-plated fins per foot (.305 m). Full fincollars provided for accurate finspacing and maximum fin-tubecontact. The 3/8" (9.5 mm) ODseamless copper tubes aremechanically expanded into the fincollars. Coils are proof tested at 450psig (3102 kPa) and leak tested at 300psig (2068 kPa) air pressure underwater. Coil connections are brazed withright-hand configuration.

ELECTRIC HEAT COILThe electric heater is factory-providedand installed, UL recognized resistanceopen-type heater. It also contains adisc-type automatic pilot duty thermalprimary cutout, and manual reset loadcarrying thermal secondary device.Heater element material is nickel-chromium. The heater terminal box isprovided with 7/8" (22 mm) knockoutsfor customer power supply. Terminalconnections are plated steel withceramic insulators. Heater control

access is on the discharge side ofthe unit.

ELECTRIC HEAT OPTIONS

ContactorsMagnetic Contactor—An electricheater 24-volt contactor for use withdirect digital control (DDC) or analog-electronic controls.

Mercury Contactor—An electricheater 24-volt contactor for use withdirect digital control (DDC) or analog-electronic controls.

P.E. Switch with MagneticContactor—This switch andmagnetic contactor is for use withpneumatic controls.

P.E. Switch with MercuryContactor—This switch andmercury contactor is for use withpneumatic controls.

Airflow Switch—An air pressuredevice designed to disable the heaterwhen the system fan is off.

Power Fuse—If power fuse is chosenwith a unit with electric heat, then asafety fuse located in the electricheater’s line of power to prevent powersurge damage to the electric heater.

Any electric heat unit with a calculatedMCA greater than or equal to 30 willhave a fuse provided.

Disconnect Switch—A factory-provided door interlockingdisconnect switch on the heater controlpanel disengages primary voltage tothe terminal.

UNIT CONTROLS SEQUENCE OFOPERATIONThe unit controller continuouslymonitors the zone temperature againstits setpoint and varies the primaryairflow as required to meet zonesetpoints. Airflow is limited byminimum and maximum position setpoints. For a parallel unit, the controllerwill intermittently start the fan upon acall for heat. Upon a further call forheat, any hot water or electric heatassociated with the unit is enabled.

1. Primary Airflow—The fan energizeswhen primary airflow drops belowthe fan setpoint airflow. The fanautomatically starts when the zonetemperature drops to the heatingtemperature setpoint.

2. Zone Temperature—The fanenergizes when the zone temperaturedrops to a selectable number ofdegrees above the heatingtemperature setpoint.

DIRECT DIGITAL CONTROLS

DDC Actuator—Trane 3-wire, 24-VAC,floating-point control actuator withlinkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.

Direct Digital Controller—Themicroprocessor-based terminal unitcontroller provides accurate, pressure-independent control through the useof a proportional integral controlalgorithm and direct digital controltechnology. The controller, named theUnit Control Module (UCM), monitorszone temperature setpoints, zonetemperature and its rate of change,and valve airflow using a differentialpressure signal from the pressuretransducer. Additionally, the controllercan monitor either supply duct airtemperature or CO2 concentration viaappropriate sensors. The controller isprovided in an enclosure with 7/8"(22 mm) knockouts for remote controlwiring. A Trane UCM zone sensoris required.

DDC Zone Sensor—The UCMcontroller senses zone temperaturethrough a sensing element located inthe zone sensor. In addition to thesensing element, zone sensor optionsmay include an externally-adjustablesetpoint, communications jack for usewith a portable edit device, and anoverride button to change theindividual controller from unoccupiedto occupied mode. The override buttonhas a cancel feature that will return thesystem to unoccupied. Wired zonesensors utilize a thermistor to vary thevoltage output in response to changesin the zone temperature. Wiring to theUCM controller must be 18- to 22-awg.twisted pair wiring. The setpointadjustment range is 50–88ºF (10–31°C).Depending upon the features availablein the model of sensor selected, thezone sensor may require from a 2-wireto a 5-wire connection. Wireless zonesensors report the same zoneinformation as wired zone sensors,but do so using radio transmittertechnology. Therefore with wireless,wiring from the zone sensor to theUCM is unnecessary.

Page 25: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

99VAV-PRC005-EN

MechanicalSpecifications

Digital Display Zone Sensor withLiquid Crystal Display (LCD)—The digital display zone sensor containsa sensing element, which sends a signalto the UCM. A Liquid Crystal Display(LCD) displays setpoint or spacetemperature. Sensor buttons allow theuser to adjust setpoints, and allow spacetemperature readings to be turned on oroff. The digital display zone sensor alsoincludes a communication jack for usewith a portable edit device, and anoverride button to change the UCM fromunoccupied to occupied. The overridebutton has a cancel feature, whichreturns the system to unoccupied mode.

The digital display zone sensor requiresseven wires.

System Communications—TheController is designed to send andreceive data from a Tracer Summit® orother Trane controllers. Current unitstatus conditions and setpoints may bemonitored and/or edited via this datacommunication feature. The networktype is a twisted wire pair shieldedserial communication.

ANALOG ELECTRONIC CONTROLSAnalog Actuator—A Trane 3-wire,24-VAC, floating-point control actuatorwith linkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.

Analog Electronic Controller—The controller consists of a circuitboard that offers basic VAV unitoperation and additional overridefunctions and operates using 24 VACpower. The controller uses a capacitivetype pressure transducer to maintainconsistent air delivery regardless ofsystem pressure changes. The enclosurehas 7/8" (22 mm) knockouts for remotecontrol wiring. A Trane electronic zonesensor is required.

Analog Electronic Thermostat—This single-temperature, wall-mountedelectronic device utilizes a thermistorto vary the voltage output in responseto changes in the zone temperature.Connections to the VAV unit circuitboard are made using standard three-conductor thermostat wire. The setpointadjustment range is 63–85ºF (17–29°C).The sensor is available in two models.One model has a concealed, internally-adjustable setpoint. The other modelhas an externally-adjustable setpoint.

PNEUMATIC CONTROLS

Normally Open Actuator –Pneumatic 3 to 8 psig (20 to 55 kPa)spring-range pneumatic actuator.

3011 Pneumatic Volume Regulator(PVR) – The regulator is a thermostatreset velocity controller, whichprovides consistent air delivery within5% of cataloged flow down to 18% ofunit cataloged cfm, independent ofchanges in system static pressure.Factory-calibrated, field-adjustablesetpoints for minimum and maximumflows. Average total unit bleed rate,excluding thermostat, is 28.8 scim at20 psig (7.87 ml/min at 138 kPa) supply.

UNIT OPTIONS

Power Fuse (VPCF, VPWF)—Optional fuse is factory-installed in theprimary voltage hot leg.

HOT WATER VALVES

Two-Position Valve—The valve is afield-adaptable, 2-way or 3-wayconfiguration and ships with a cap tobe field-installed when configured as a2-way valve. All connections areNational Pipe Thread (NPT). The valvebody is forged brass with a stainlesssteel stem and spring. Upon demand,the motor strokes the valve. When theactuator drive stops, a spring returnsthe valve to its fail-safe position.

Flow Capacity – 1.17 CvOverall Diameter – ½" NPTClose-off Pressure – 30 psi (207 kPa)

Flow Capacity – 3.0 CvOverall Diameter – 3/4" NPTClose-off Pressure – 14.5 psi (100 kPa)

Flow Capacity – 6.4 CvOverall Diameter – 1" NPTClose-off Pressure – 9 psi (62 kPa)

Maximum Operating FluidTemperature – 203ºF (95ºC)

Maximum system pressure – 300 psi(2067 kPa)

Maximum static pressure – 300 psi(2067 kPa)

Electrical Rating – 7 VA at 24 VAC,6.5 Watts, 50/60 Hz

8 feet (2.44 m) of plenum rated wirelead is provided with each valve.

Proportional Water Valve – The valveis a field-adaptable, 2-way or 3-wayconfiguration and ships with a cap overthe bottom port. This configures thevalve for 2-way operation. For 3-wayoperation, remove the cap. The valve isdesigned with an equal percentageplug. The intended fluid is water orwater and glycol (50% maximumglycol). The actuator is a synchronousmotor drive. The valve is driven to apredetermined position by the UCMcontroller using a proportional plusintegral control algorithm. If power isremoved, the valve stays in its lastposition. The actuator is rated forplenum applications under UL 94-5Vand UL 873 standards.

Pressure and Temperature Ratings –The valve is designed and tested in fullcompliance with ANSI B16.15 Class250 pressure/temperature ratings,ANSI B16.104 Class IV control shutoffleakage, and ISA S75.11 flowcharacteristic standards.

Flow Capacity – 7.30 Cv, 4.60 Cv, 1.80Cv, 0.79 Cv

Overall Diameter – ½" NPT, ¾" NPT(7.3 Cv)

Maximum Allowable Pressure – 345 psi(2415 kPa)

Maximum Operating FluidTemperature – 281ºF (138°C)

Maximum Close-off Pressure – 55 psi(379 kPa)

Electrical Rating – 4 VA at 24 VAC.

10 feet (3.05 m) of plenum rated22-gage wire for connection.Terminations are #6 stabs.

Page 26: Fan-Powered Table of Parallel · PDF fileFan-Powered Parallel 76 VAV-PRC005-EN Model Number Description ... calculation of external static pressure dependent on unit type. In many

Fan-PoweredParallel

VAV-PRC005-EN100