Faulted Circuit Indicators Application Overview
Anthony PatenaudeApplication Engineer I - FIS
Schweitzer Engineering Labs
![Page 2: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/2.jpg)
Locating Distribution FeederFaults Is Challenging
![Page 3: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/3.jpg)
Operating Voltages
System Voltage Levels
Transmission 765 kV, 500 kV, 345 kV, 230 kV,169 kV, 138 kV, 115 kV
Subtransmission 138 kV, 115 kV, 69 kV, 33 kV, 27 kV
Primary distribution 33 kV, 27 kV, 13.8 kV, 4 kV
Secondary distribution 120/240 V, 120/208 V, 240/480 V
![Page 4: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/4.jpg)
FCIs Reduce Outage Time
Line Truck
![Page 5: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/5.jpg)
What Are FCIs and How Do They Work?
![Page 6: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/6.jpg)
Theory of Operation
• Sensor detects fault current greater than system load
• Larger amount of current flowing through conductor increases magnetic field
• FCI triggers display
I
B
–
+
![Page 7: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/7.jpg)
Sensor and Display
• FCI has two main components♦ Sensing unit
♦ Display
• Display is integral or remote
• Remote display allows indication from a distance
![Page 8: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/8.jpg)
Fixed Trip-Level FCIs
300
Time (Cycles)
40 A load
FCI trips when current exceeds trip rating and response time
500 A fault
5000
1 2 3
1.5 cycles
![Page 9: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/9.jpg)
Operating Energy
• Line powered♦ Current and/or voltage
• Battery powered♦ Microprocessor based
♦ Timed reset (typical)
♦ LED products
• Fault powered – no arming quantity necessary
![Page 10: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/10.jpg)
Backfeed Protection
• Back-feed currents can cause false tripping
• Backfeed protection option provides immunity from back-feed current surges faster than 24ms
• Sources of back-feed♦ Capacitor banks
♦ Motor spin down
♦ Inductive loads
![Page 11: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/11.jpg)
• Back-feed and discharge currents can cause
♦ False trips (over tripping)
♦ False reset
SOURCE CAPBANK
Backfeed Protection
![Page 12: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/12.jpg)
• Backfeed protection provides immunity from back-feed current surges faster than 1.5 cycles♦ Prevents false trips (over tripping)
♦ Prevents false reset
SOURCE CAPBANK
Backfeed Protection
![Page 13: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/13.jpg)
Advanced Fault Detection Using CT and Microprocessor
• Load current measurement algorithms
• Auto-adjusting trip ratings
• More dynamic FCIs
• Single self-configuring unit placed across entire system
![Page 14: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/14.jpg)
Applications - Overhead
![Page 15: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/15.jpg)
Application
• Single- and three-phase overhead conductors
• Midfeeder disconnect
• Unfused taps
• Underground transitions♦ Dips
♦ Risers
![Page 16: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/16.jpg)
Feeder Exit Riser Pole
Dead-End Riser
Underground FeederSubstation
![Page 17: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/17.jpg)
Quickly Determine Overhead Versus Underground Fault
Dead-End Riser
Underground FeederSubstation
![Page 18: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/18.jpg)
Closer Look at Fault in
Underground Cable
SourceSide
LoadSide
FCI identifieswhether fault is in
underground section or on overhead
system downstream
![Page 19: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/19.jpg)
SourceSide
LoadSide
FCI identifieswhether fault is in
underground section or on overhead
system downstream
Closer Look at Fault in Overhead Conductor
![Page 20: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/20.jpg)
Installation
![Page 21: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/21.jpg)
Reference “A”: Maximum recommended distance from pole of 6’-0”
Reference “B”: Minimum distance from pole of 3’-0”
Reference “C”: Minimum distance from energized hardware of 2’-0”
Minimum Installation Spacing Requirements
![Page 22: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/22.jpg)
Inrush Restraint Mechanism
![Page 23: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/23.jpg)
Example #1: Recloser Lock-out / Fault Downstream of FCIs
• Downstream fault – low impedance♦ Assume a 13.2 kV L-L system
– Line has been energized long enough to power up / arm the FCIs
– FCIs downstream of a 3 phase sectionalizing automatic recloser
To Source
To Load
![Page 24: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/24.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 25: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/25.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Fault
Time
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 26: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/26.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Recloser operates
Time
Fault
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 27: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/27.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
TimeInrush Restraint Activated
Fault Recloser operates
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 28: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/28.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Recloser closes back inFault Recloser
operates
Inrush Restraint Activated
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 29: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/29.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Fault Recloser operates
Recloser closes back in
Inrush Restraint Activated
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 30: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/30.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Fault Recloser operates
Recloser closes back in
Recloser Lock‐out
Recloser Lock‐out
Inrush Restraint Activated
Example #1: Recloser Lock-out / Fault Downstream of FCIs
![Page 31: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/31.jpg)
Example #2: Recloser Lock-out / Fault Upstream of FCIs
• Upstream fault – low impedance♦ Assume a 13.2 kV L-L system
– Line has been energized long enough to power up / arm the FCIs
– FCIs downstream of a 3 phase sectionalizing automatic recloser
To Source
To Load
![Page 32: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/32.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 33: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/33.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 34: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/34.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
Time
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 35: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/35.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
TimeInrush Restraint Activated
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 36: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/36.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
TimeInrush Restraint Activated
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 37: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/37.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
TimeInrush Restraint Activated
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 38: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/38.jpg)
Trip Rating
Load
Trip Rating
Load
B&C Phases
A Phase
TimeInrush Restraint Activated
Recloser Lock‐out
Recloser Lock‐out
Example #2: Recloser Lock-out / Fault Upstream of FCIs
![Page 39: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/39.jpg)
Applications - Underground
![Page 40: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/40.jpg)
Live-Front Switchgear Air insulated
Cables terminated to exposed live bus
Cable termination uses voltage stress relief
No test point availability
Not applicable in subsurface applications
Install FCI units below stress relief
Install FCI with Snap-Action clamp onto terminal lug
![Page 41: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/41.jpg)
Three-Phase Live-Front Switchgear
![Page 42: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/42.jpg)
Four-Way Switch
Install FCIs at unfused outgoing feeds
Side view Top-down view
3 2
14IN
![Page 43: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/43.jpg)
Dead-Front Switchgear Designed with no exposed high-voltage parts
Pad-mount and subsurface applications
Uses standard connector system interface (Elbows & T-Bodies)
Connectors are shielded with semi-conductive rubber outer surface
Likely that test points are available
![Page 44: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/44.jpg)
Three-Phase Switchgear
![Page 45: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/45.jpg)
Three-Phase Switchgear
![Page 46: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/46.jpg)
Three-Phase Switchgear
LOAD
SIDE
![Page 47: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/47.jpg)
Concentric Neutral Training
Four Acceptable Options• Double Backed
• Braided
• Pulled Back (drain wire inside core)
• Pulled Back (drain wire outside of core)
![Page 48: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/48.jpg)
Tape-Shielded Cable and Adapter
![Page 49: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/49.jpg)
Fault Indicators Are a Good Value
• Meet needs of a large-scale deployment♦ Easy to Install
♦ Low cost
♦ Little to no maintenance
♦ Long service life (10+ years minimum)
• Reduce fault finding time by half
• Easy to spot and determine status in field
![Page 50: Faulted Circuit Indicators Application Overview · PDF file · 2017-06-01Faulted Circuit Indicators Application Overview ... Faults Is Challenging. Operating Voltages System Voltage](https://reader035.vdocument.in/reader035/viewer/2022070607/5aa9062f7f8b9a72188c5c92/html5/thumbnails/50.jpg)
Thank You for Your Time!Any Questions?