ferraz shawmut

43
North American Power Fuses The most popular North American power fuses — to meet the most popular protection priorities. • Class RK5 / Tri-onic ® TR & TRS • DC-rated / Tri-onic ® TRS-RDC • Class J / Amp-trap ® HSJ • Class J / Amp-trap ® A4J • Class L / Amp-trap ® A4BY • Class L / Amp-trap ® A4BT • Class T / Amp-trap ® A3T & A6T • Class RK1 / Amp-trap ® A2K & A6K • Class RK1/Amp-trap ® HSRK • Class G / Amp-trap ® AG • Class CC / Amp-trap ® ATMR • Class K-5 / OT, OTN & OTS One-time • Class H / RF/RFS & RL/RLS Renewable Your problem: Today, you need a time-delay power fuse that can handle normal surges. Tomorrow, it’s a power fuse with a high interrupting rating and the added security of rejection dimen- sions. The day after that, one of those economical one-time power fuses will do the trick. But where can you turn for all three? Our solution: Ferraz Shawmut’s comprehensive power fuse offering covers a complete range of applications and a complete range of circuit-protection needs. Whether it’s the characteristics of our Tri-onic ® time-delay fuses. The high current-limiting capacity of our original Amp-trap ® power fuses. The cost-efficient protec- tion of our One-Time fuses. Or some other application-specific power fuse solution. Want more information fast? For more technical or application- specific information, please call our Power Fuse experts, at 978-462-6662; 416-252-9371 in Canada; or visit our website at us.ferrazshawmut.com. Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Upload: alan-jimenez

Post on 11-Mar-2016

236 views

Category:

Documents


2 download

DESCRIPTION

Catalogo Ferraz shawmut

TRANSCRIPT

Page 1: Ferraz shawmut

North American Power Fuses

The most popular North American power fuses — to meet the most popular protection priorities.

• Class RK5 / Tri-onic® TR & TRS

• DC-rated / Tri-onic® TRS-RDC

• Class J / Amp-trap® HSJ

• Class J / Amp-trap® A4J

• Class L / Amp-trap® A4BY

• Class L / Amp-trap® A4BT

• Class T / Amp-trap® A3T & A6T

• Class RK1 / Amp-trap® A2K & A6K

• Class RK1/Amp-trap® HSRK

• Class G / Amp-trap® AG

• Class CC / Amp-trap® ATMR

• Class K-5 / OT, OTN & OTS One-time

• Class H / RF/RFS & RL/RLS Renewable

Your problem: Today, you need a time-delay power fuse that can handle normal surges. Tomorrow, it’s a power fuse with a high interrupting rating and the added security of rejection dimen-sions. The day after that, one of those economical one-time power fuses will do the trick. But where can you turn for all three?

Our solution: Ferraz Shawmut’s comprehensive power fuse offering covers a complete range of applications and a complete range of circuit-protection needs. Whether it’s the characteristics of our Tri-onic® time-delay fuses. The high current-limiting capacity of our original Amp-trap® power fuses. The cost-efficient protec-tion of our One-Time fuses. Or some other application-specific power fuse solution.

Want more information fast? For more technical or application-specific information, please call our Power Fuse experts, at 978-462-6662; 416-252-9371 in Canada; or visit our website at us.ferrazshawmut.com.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 2: Ferraz shawmut

B �

Time Delay/Class RK5

TR aC: 1/10 to 600A 250VAC, 200kA I.R.

DC: 1/10 to 2 8/10A & 35 to 400A, 250VDC, 20kA I.R.; 3 to 30A & 450 to 600A, 160VDC, 20kA I.R.

TRs aC: 1/10 to 600A 600VAC, 200kA I.R.

DC: 1/10 to 12A, 600VDC, 20kA I.R.; 15 to 60A, 300VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R.

TRi-ONiC®

TR & TRs

Ratings

Features/Benefits

solid state smartspot indicatorTime delay for motor start-ups and transformer inrush currents without nuisance openingCurrent limiting for low peak let-thru currentRejection-style design prevents replacement errors (when used with recommended fuse blocks)easy-to-read label for quick recognition and replacementmetal-embossed date and catalog number for traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settingsHigh-grade silica filler ensures fast arc quenching and high current limitation

THe iNDusTRy’s mOsT pOpulaR Fuse FOR mOTOR CiRCuiT pROTeCTiON.

Tri-onic® SmartSpot® fuses now provide a visual open fuse indicator. With advanced material technol-ogy added to the existing product the TR and TRS current limiting time delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-onic proven time delay characteristic safely handles harmless starting currents and inrush currents associated with today’s motors and transformers.

UL Listed to Standard 248-12 File E2137

CSA Certified to Standard C22.2 No. 248.12

DC Listed to UL Standard 248 TRS only

approvals

appliCaTiONs:

Motor CircuitsMainsFeedersBranch CircuitsTransformersService Entrance EquipmentGeneral-purpose Protection

HiGHliGHTs:

Time DelayCurrent LimitingAC & DC Rated

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 3: Ferraz shawmut

B

B �

TR & TRs

TRi-ONiC®

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V

1/10 TR1/10R TRS1/10R 3-1/2 TR3-1/2R TRS3-1/2R 50 TR50R TRS50R

15/100 TR15/100R TRS15/100R 4 TR4R TRS4R 60 TR60R TRS60R

2/10 TR2/10R TRS2/10R 4-1/2 TR4-1/2R TRS4-1/2R 70 TR70R TRS70R

3/10 TR3/10R TRS3/10R 5 TR5R TRS5R 75 TR75R TRS75R

4/10 TR4/10R TRS4/10R 5-6/10 TR5-6/10R TRS5-6/10R 80 TR80R TRS80R

1/2 TR1/2R TRS1/2R 6 TR6R TRS6R 90 TR90R TRS90R

6/10 TR6/10R TRS6/10R 6-1/4 TR6-1/4R TRS6-1/4R 100 TR100R TRS100R

8/10 TR8/10R TRS8/10R 7 TR7R TRS7R 110 TR110R TRS110R

1 TR1R TRS1R 8 TR8R TRS8R 125 TR125R TRS125R

1-1/8 TR1-1/8R TRS1-1/8R 9 TR9R TRS9R 150 TR150R TRS150R

1-1/4 TR1-1/4R TRS1-1/4R 10 TR10R TRS10R 175 TR175R TRS175R

1-4/10 TR1-4/10R TRS1-4/10R 12 TR12R TRS12R 200 TR200R TRS200R

1-6/10 TR1-6/10R TRS1-6/10R 15 TR15R TRS15R 225 TR225R TRS225R

1-8/10 TR1-8/10R TRS1-8/10R 17-1/2 TR17-1/2R TRS17-1/2R 250 TR250R TRS250R

2 TR2R TRS2R 20 TR20R TRS20R 300 TR300R TRS300R

2-1/4 TR2-1/4R TRS2-1/4R 25 TR25R TRS25R 350 TR350R TRS350R

2-1/2 TR2-1/2R TRS2-1/2R 30 TR30R TRS30R 400 TR400R TRS400R

2-8/10 TR2-8/10R TRS2-8/10R 35 TR35R TRS35R 450 TR450R TRS450R

3 TR3R TRS3R 40 TR40R TRS40R 500 TR500R TRS500R

3-2/10 TR3-2/10R TRS3-2/10R 45 TR45R TRS45R 600 TR600R TRS600R

StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-TRFUSES 0-30 2 51 9/16 14 - - - - - - 31-60 3 76 13/16 21 - - - - - - 61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25 101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35 201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48 401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57 600V-TRSFUSES 0-30 5 127 13/16 21 - - - - - - 31-60 5-1/2 139 1-1/16 27 - - - - - - 61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25 101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35 201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48 401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57

Dimensions

Fuse CatalogNumberAmpere250V600V Rating 1Pole 3pole 1pole 3pole 0-30 20306R 20308R 60306R 60308R

31-60 20606R 20608R 60606R 60608R

61-100 21036R 21038R 61036R 61038R

101-200 22001R 22003R 62001R 62003R

201-400 24001R 24003R 64001R 64003R

401-600 2631R 2633R 6631R 6633R

RecommendedFuseBlocksWithBoxConnectorsForTri-onic®

ClassRK5Fuses

0-60A

61-600A

Note: Indicator not available (1/10 - 7) amps.

Time Delay/Class RK5 Fuses

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 4: Ferraz shawmut

B �

TimeinSeconds

Curr

enti

nAm

pere

s

Time Delay/Class RK5 Fuses TRi-ONiC®

TR1/10 TO 12

mel

ting

Tim

e –

Curr

ent

Data

, 250

V Fu

ses

TimeinSeconds

Curr

enti

nAm

pere

s

TR15 TO 600m

eltin

g Ti

me

– Cu

rren

t Da

ta, 2

50V

Fuse

s

TR & TRs

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 5: Ferraz shawmut

B

B �

Time Delay/Class RK5 Fuses

TimeinSeconds

Curr

enti

nAm

pere

s

TRi-ONiC®

TRs1/10 TO 12

mel

ting

Tim

e –

Curr

ent

Data

. 600

V Fu

ses

TimeinSeconds

Curr

enti

nAm

pere

s

TRs15 TO 600m

eltin

g Ti

me

– Cu

rren

t Da

ta ,

600V

Fus

es

TR & TRs

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 6: Ferraz shawmut

B �

Time Delay/Class RK5 Fuses TRi-ONiC®

AvailableCurrentinRMSSymmetricalAmperes

Max

imum

Inst

anta

neou

sPe

akL

et-T

hru

Ampe

res

AvailableCurrentinRMSSymmetricalAmperes

Max

imum

Inst

anta

neou

sPe

akL

et-T

hru

Ampe

res

peak let-Thru Current Data – TR30 to 600, 250 Volts aC

peak let-Thru Current Data – TRs15 to 600, 600 Volts aC

Note: See Application Information page L9 for All Motor and Transformer Tables.

TR & TRs

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 7: Ferraz shawmut

B

B �

TRi-ONiC®

TRs-RDC

appliCaTiONs:

Mine CircuitsTrailing CablesPump MotorsRail Heaters

DC: 1 to 30A 300VDC, 20kA I.R. (Consult Factory for Availability)

DC: 35 to 400A 600VDC, 20kA I.R.

Ratings

Features/Benefits

DC rated for mine duty and other long time-constant applicationsTime delay for motor start-ups and high inrush loads without nuisance openingRugged glass melamine body for superior Reliability in harsh environments

DC RaTeD FOR TOuGH DC appliCaTiONs

The Tri-onic® DC fuse series is designed for DCcircuit protection in surface and underground mines. The TRS-RDC is MSHA approved and meets the industry’s most severe third party requirements for 600VDC rated fuses.

The TRS-RDC is a time-delay fuse with essentially the same time-current characteristic as thestandard Tri-onic®.

MSHA Approval No. 28-26-0

approvalsHiGHliGHTs:

Time DelayDC Rated

Time Delay/DC RaTeD

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 8: Ferraz shawmut

B �

AMPERE CATALOG RATING NUMBER 1/10 TRS1/10RDC

15/100 TRS15/100RDC

2/10 TRS2/10RDC

3/10 TRS3/10RDC

4/10 TRS4/10RDC

1/2 TRS1/2RDC

6/10 TRS6/10RDC

8/10 TRS8/10RDC

1 TRS1RDC

1-1/8 TRS1-1/8RDC

AMPERE CATALOG RATING NUMBER 1-1/4 TRS1-1/4RDC

1-4/10 TRS1-4/10RDC

1-6/10 TRS1-6/10RDC

1-8/10 TRS1-8/10RDC

2 TRS2RDC

2-1/4 TRS2-1/4RDC

2-1/2 TRS2-1/2RDC

2-8/10 TRS2-8/10RDC

3 TRS3RDC

3-2/10 TRS3-2/10RDC

AMPERE CATALOG RATING NUMBER 3-1/2 TRS3-1/2RDC

4 TRS4RDC

4-1/2 TRS4-1/2RDC

5 TRS5RDC

5-6/10 TRS5-6/10RDC

6 TRS6RDC

6-1/4 TRS6-1/4RDC

8 TRS8RDC

9 TRS9RDC

10 TRS10RDC

AMPERE CATALOG RATING NUMBER 12 TRS12RDC

15 TRS15RDC

17-1/2 TRS17-1/2RDC

20 TRS20RDC

30 TRS30RDC

35 TRS35RDC

40 TRS40RDC

45 TRS45RDC

50 TRS50RDC

60 TRS60RDC

AMPERE CATALOG RATING NUMBER 70 TRS70RDC

80 TRS80RDC

90 TRS90RDC

100 TRS100RDC

125 TRS125RDC

150 TRS150RDC

175 TRS175RDC

200 TRS200RDC

250 TRS250RDC

300 TRS300RDC

400 TRS400RDC

Time Delay/600VDC Fuses TRi-ONiC®

StandardFuseAmpereRatings,CatalogNumbers

Dimensions

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm 0-30 5 127 13/16 21 - - - - - -

31-60 5-1/2 139 1-1/16 27 - - - - - -

61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25

101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35

201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48

Curr

enti

nAm

pere

s

TimeinSeconds

0-60Amperes

61-400Amperes

TRs-RDC60 TO 400

mel

ting

Tim

e –

Curr

ent

Data

, 600

V Fu

ses

TRs-RDC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 9: Ferraz shawmut

B

B �

Features/Benefits

Optimized over-load capability for withstanding elevated levels of current during electronic motor controller starts

low i2t (low thermal energy)

excellent Cycling ability for frequent starts/stops without nuisance opening

pROTeCT yOuR wiRiNG aND pOweR semi-CONDuCTORs wiTH a siNGle Fuse.

The new High Speed J (HSJ) combines the low I2t of a semiconductor fuse and the branch circuit performance of a Class J UL listed fuse. This fuse was designed for the starting characteristics of solid state motor controllers. The HSJ can provide branch circuit protection per NEC requirements, as well as very low I2t for protection of power semiconductors such as Diodes, SCR’s, GTO’s and SSR’s.

appliCaTiONs:

Branch CircuitsControl PanelsElectronic Motor ControllersPhase ControllersDrivesSoft-StartersSolid State Relays

HiGHliGHTs:

Current-LimitingAC & DC RatingsLow l2tCompact Size

amp-TRap®

HsJ

aC: 1-600A 600VAC, 200kA I.R. 300kA I.R. Self Certified

DC: 15-600A 500VDC, 100kA I.R. L/R 10mS

Ratings

HsJ (15 TO 600a)UL Listed to Standard 248-8 File E2137

DC Listed to UL248

CSA Certified to Standard C22.2 No. 248.8

approvals

HiGH speeD/Class J

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 10: Ferraz shawmut

B 10

amp-TRap®

HiGH speeD/Class J HsJ

FuseCatalogNumber Ampere600VORLESS Rating 1Pole 3pole 0-30 US3J1I US3J3I

31-60 US6J1I US6J3I

61-100 61036J 61038J

101-200 62001J 62003J

201-400 64031J 64033J

401-600 6631J 6633J

RecommendedFuseBlocksWithBoxConnectorsforAmp-trap®ClassJFuses

A variety of pole configurations and termination provisions is available.

StandardFuseAmpereRatings,CatalogNumbers

15-30 2-1/4 57 13/16 21 - - - - - - - - - - - -

31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -

61-100 4-4/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7

101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7

201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10

401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13

AMPERERATING

A B C D E F G H In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm

DimensionsFig1

AMPERERATING

CATALOGNUMBER

OUTLINEFIGURE

AMPERERATING

CATALOGNUMBER

OUTLINEFIGURE

1 HSJ1 1 90 HSJ90 2

3 HSJ3 1 100 HSJ100 2

6 HSJ6 1 110 HSJ110 2

10 HSJ10 1 125 HSJ125 2

15 HSJ15 1 150 HSJ150 2

17-1/2 HSJ17-1/2 1 175 HSJ175 2

20 HSJ20 1 200 HSJ200 2

25 HSJ25 1 225 HSJ225 2

30 HSJ30 1 250 HSJ250 2

35 HSJ35 1 300 HSJ300 2

40 HSJ40 1 350 HSJ350 2

45 HSJ45 1 400 HSJ400 2

50 HSJ50 1 450 HSJ450 2

60 HSJ60 1 500 HSJ500 2

70 HSJ70 2 600 HSJ600 2

80 HSJ80 2

Fig2

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 11: Ferraz shawmut

B

B 11

amp-TRap®

HiGH speeD/Class J

1.0

.8

.6

.4

.2

00 100 200 300 400 500 600

110-600 AMP

15-100 AMP

Clearing i2t vs Operating Voltage

1.0

.8

.6

.4

.2

50 60 70 80 90 100

watts loss vs. % Rated Current

Corr

ectio

nFa

ctor

forI

2t

OperatingVoltage(ACRMSVolts) PercentRatedCurrent

I2tData-600VoltsAC,100kA

Corr

ectio

nFa

ctor

forW

atts

Los

s

Max Clearing I2t @ Max Clearing I2t @ WattsAmpere 600V AC 100kA 480V AC 100kA Loss atRating Pre-Arc 1 Fuse 2 in Series 1 Fuse 2 in Series Rated

(A) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103) Current15 0.02 0.36 0.15 0.23 0.12 2.6

17.5 0.03 0.45 0.19 0.29 0.15 3.520 0.04 0.58 0.24 0.37 0.19 3.725 0.08 1.2 0.50 0.77 0.40 430 0.16 2 0.84 1.3 0.66 4.135 0.16 1.5 0.63 0.96 0.50 5.340 0.27 2.3 1.0 1.5 0.76 5.545 0.32 3.3 1.4 2.1 1.1 650 0.44 5.5 2.3 3.5 1.8 6.860 0.72 8.0 3.4 5.1 2.6 8.470 1.2 12 5.0 7.7 4.0 1080 1.6 15 6.3 9.6 5.0 1190 2.3 21 8.8 13 6.9 13100 2.7 23 9.7 15 7.6 14110 2.3 21 10 13.9 8 18125 3.4 29 14 19 11 19150 5.1 41 20 27 16 22175 8.0 60 29 40 23 24200 14 92 44 61 35 26225 14 110 53 73 42 30250 16 130 62 86 49 36300 26 200 96 132 76 38350 37 290 139 191 110 40400 63 450 216 297 171 42450 67 500 240 330 190 58500 98 600 288 396 228 59600 141 900 432 594 342 68

HsJ

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 12: Ferraz shawmut

B 1�

peak let-Thru Data - HsJ15 to 600, 600Volts aC

Clearing i2t at 500 VDC 100ka, l/R = 10ms DC Voltage vs. Time Constant

DCV

olta

geC

apab

ility

L/RTimeConstant(mS)

amp-TRap®

HiGH speeD/Class J

AMPERE RATING

CLEARING I2t @ 500 VDC L/R = 10 ms (A2s X 103)

15 0.12 17.5 0.18 20 0.24 25 0.46 30 0.91 35 0.60 40 0.92 45 1.3 50 2.2 60 3.2 70 4.8 80 6.2 90 8.9

100 10 110 8.8 125 13 150 19 175 28 200 46 225 52 250 59 300 96 350 136 400 230 450 270 500 390 600 560

Max

imum

Inst

anta

neou

sPe

akL

et-T

hru

Ampe

res

AvailableCurrentinRMSSymmetricalAmperes

HsJ

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 13: Ferraz shawmut

B

B 1�

melting Time - Current Data, HsJ15 to 600, 600Volts aC

AvailableCurrentinRMSSymmetricalAmperes

Tim

ein

Sec

onds

Tim

ein

Sec

onds

amp-TRap®

HiGH speeD/Class J

AvailableCurrentinRMSSymmetricalAmperes

HsJ

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 14: Ferraz shawmut

B 1�

appliCaTiONs:

Capacitors LoadcentersPanelboardsSwitchboardsBus DuctFeeder CircuitsCircuit BreakersLighting, Heating, and General Loads

amp-TRap®

a4J

aC: 1 to 600A 600VAC, 200kA I.R.

DC: 1 to 600A 300VDC, 100kA I.R.

Ratings

Features/Benefits

High current limitation for low peak let-thru currentunique dimensions prevent replacement by other fuse classesFiberglass body provides dimensional stability in harsh industrial environmentseasy-to-read imprint label for quick recognition and replacement

FOR excellent CuRReNT limiTiNG pROTeCTiON

A4J Class J fuses deliver excellent current-limiting protection to a wide variety of applications. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings, interrupting ratings, or current-limiting capability.

UL Listed to Standard 248-8 File E2137

CSA Certified to Standard C22.2 No. 248.8

DC Listed to UL 248

IEC 269-2-1

approvalsHiGHliGHTs:

Fast ActingVery Current-LimitingDC Ratings

FasT aCTiNG/Class J

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 15: Ferraz shawmut

B

B 1�

ampeRe CaTalOG ampeRe CaTalOG ampeRe CaTalOG RaTiNG NumBeR RaTiNG NumBeR RaTiNG NumBeR

1 A4J1 50 A4J50 200 A4J200

3 A4J3 60 A4J60 225 A4J225

6 A4J6 70 A4J70 250 A4J250

10 A4J10 75 A4J75 300 A4J300

15 A4J15 80 A4J80 350 A4J350

20 A4J20 90 A4J90 400 A4J400

25 A4J25 100 A4J100 450 A4J450

30 A4J30 110 A4J110 500 A4J500

35 A4J35 125 A4J125 600 A4J600

40 A4J40 150 A4J150

45 A4J45 175 A4J175

StandardFuseAmpereRatings,CatalogNumbers

FasT aCTiNG/Class J Fuses

Fuse Catalog Number

ampere 600V OR less

Rating 1 pole 3 pole

0-30 US3J1I US3J3I

31-60 US6J1I US6J3I

61-100 61036J 61038J

101-200 62001J 62003J

201-400 64031J 64033J

401-600 6631J 6633J

RecommendedFuseBlocksWithBoxConnectorsforAmp-trapClassJFuses

A variety of pole configurations and termina-tion provisions are available. Refer to the fuse block section of this catalog for details.

Dimensions

amp-TRap®

a4J

ampeRe a B C D e F G H

RaTiNG in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm

1-30 2-1/4 57 13/16 21 - - - - - - - - - - - -

31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -

61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7

101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7

201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10

401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13

1-60A

61-600A

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 16: Ferraz shawmut

B 1�

FasT aCTiNG/Class J Fuses amp-TRap®

Curr

enti

nAm

pere

s

AvailableCurrentinRMSSymmetricalAmperes

Max

imum

Inst

anta

neou

sPe

akL

et-T

hru

Ampe

res

TimeinSeconds

a4J30 TO 600

mel

ting

Tim

e –

Curr

ent

Data

, 600

V Fu

ses

peak let-Thru Current Data – 30 to 600, 600 Volts aC

a4J

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 17: Ferraz shawmut

B

B 1�

amp-TRap®

a4By Class l

appliCaTiONs:

Mains, FeedersCircuit BreakersLoadcentersPanelboardsSwitchboardsMetering Centers

aC: 200 to 6,000A 600VAC,200kA I.R.

DC: 200 to 2500A 300VDC, 100kA I.R.

Ratings

Features/Benefits

unique dimensions prevent replacement by other fuse classes Blade stamped catalog numbers for permanent identification Glass melamine body and plated terminals provide superior reliability in harsh environments

COuNT ON THe HiGH iNTeRRupTiNG RaTiNG OF OuR most widely-used Class l Fuse

When it comes to protecting service entrance equipment, feeder circuits, and circuit breakers, A4BY fuses have been the industry’s favorite. The A4BY is a 100% rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500% rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.

UL Listed to Standard 248-10 (601-6000A) File E2137

CSA Certified to Standard C22.2 No. 248.10 (601-6000A)

Ferraz Shawmut Certified for DC per UL248 (601-6000A)

approvalsHiGHliGHTs:

Current-Limiting4-Second Time DelayDC RatingsUniform Characteristics in all Ampere Ratings

IndicatorsOptional built-in fuse indicators (-TI) are available. Consult factory.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 18: Ferraz shawmut

B 1�

Class l Fuses a4By

amp-TRap®

AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER RATING NUMBER

200 A4BY200 801 A4BY801 2000 A4BY2000

250 A4BY250 900 A4BY900 2001 A4BY2001

300 A4BY300 1000 A4BY1000 2200 A4BY2200

350 A4BY350 1100 A4BY1100 2500 A4BY2500

400 A4BY400 1200 A4BY1200 3000 A4BY3000

450 A4BY450 1201 A4BY1201 3001 A4BY3001

500 A4BY500 1350 A4BY1350 3500 A4BY3500

600 A4BY600 1400 A4BY1400 4000 A4BY4000

601 A4BY601 1500 A4BY1500 4001 A4BY4001

650 A4BY650 1600 A4BY1600 4500 A4BY4500

700 A4BY700 1601 A4BY1601 5000 A4BY5000

750 A4BY750 1800 A4BY1800 6000 A4BY6000

800 A4BY800

StandardFuseAmpereRatings,CatalogNumbers

200-800A 801-2000A

3001-4000A

2001-3000A

4001-6000A

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm

200-600 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61

601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61

801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88

1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88

1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88

2001-2500 10-3/4 273 4-1/2 114 3/4 19 3-1/2 89 3-15/32 88

2501-3000 10-3/4 273 5 127 3/4 19 4 102 3-15/32 88

3001-4000 10-3/4 273 5-3/4 146 3/4 19 4-3/4 121 3-15/32 88

4001-5000 10-3/4 273 6-1/4 159 1 25 5-1/4 133 3-15/32 88

5001-6000 10-3/4 273 7-1/8 181 1 25 5-3/4 146 3-15/32 88

Dimensions

safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 19: Ferraz shawmut

B

B 1�

Class l Fuses a4By amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

A4BY200to6000

Mel

ting

Tim

e–

Cur

rent

Dat

a,6

00V

Fuse

s

PeakLet-ThruCurrentData–A4BY300to6000,600VoltsAC

available Current in Rms symmetrical amperes

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 20: Ferraz shawmut

B �0

appliCaTiONs:

MotorsMotor ControllersTransformersMainsFeeders

amp-TRap®

a4BT Time Delay/Class l

aC: 200 to 2,000A 600VAC, 200kA I.R.

DC: 200 to 2,000A 500VDC, 100kA I.R.

Ratings

Features/Benefits

unique dimensions prevent replacement by other fuse classes.Blade-stamped catalog numbers for permanent identificationGlass melamine body and plated terminals provide superior reliability in harsh environments

wHeN yOuR heavier loads NeeDpROTeCTiON a4BT Fuses wON’T leT yOu DOwN

The high interrupting rating of A4BT current limiting fuses is ideally suited for protecting mains, feeders, and general circuits. The 10-sec-ond time delay at 500% of fuse rating is ideal for large motors and other loads with a high inrush. A4BT fuses are suitable for DC applications up to 500VDC. An A4BT fuse can be applied to normal loads up to its full ampere rating to allow 100% rating of equipment.

UL Listed to Standard 248-10 (601-2000A) File E2137

CSA Certified to Standard C22.2 No. 248.10 (601-2000A)

Ferraz Shawmut Certified for DC per UL248 (601-2000A)

approvalsHiGHliGHTs:

Current-LimitingFull 10-Second DelayDC RatingsUniform Characteristics in all Ampere Ratings

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 21: Ferraz shawmut

B

B �1

Time Delay/Class l Fuses a4BT amp-TRap®

AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER RATING NUMBER

200 A4BT200 601 A4BT601 1100 A4BT1100

250 A4BT250 650 A4BT650 1200 A4BT1200

300 A4BT300 700 A4BT700 1400 A4BT1400

350 A4BT350 750 A4BT750 1500 A4BT1500

400 A4BT400 800 A4BT800 1600 A4BT1600

450 A4BT450 900 A4BT900 1800 A4BT1800

500 A4BT500 1000 A4BT1000 2000 A4BT2000

600 A4BT600

StandardFuseAmpereRatings,CatalogNumbers

Dimensions

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm

200-600* 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61

601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61

801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88

1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88

1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88

safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.

801-2000A200-800A

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 22: Ferraz shawmut

B ��

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

Time Delay/Class l Fuses a4BT amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

available Current in Rms symmetrical amperes

Mel

ting

Tim

e–

Curr

entD

ata,

600

VAC

/500

VDC

Fus

es

A4BT200to2000

PeakLet-ThruCurrentData–A4BT300to2000,600VoltsAC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 23: Ferraz shawmut

B

B ��

appliCaTiONs:

LoadcentersPanelboardsSwitchboardsCircuit BreakersMetering Centers

amp-TRap®

a3T & a6T FasT aCTiNG/Class T

a3T aC:1 to 1200A 300VAC, 200kA I.R. DC: 1 to 1200A 160VDC, 50kA I.R.

a6T aC: 1 to 800A 600VAC, 200kA I.R. DC: 1 to 800A 300VDC, 100kA I.R.

Ratings

Features/Benefits

extremely current limiting for low peak let-thru currentunique dimensions prevent replacement by other fuse classes

Blade-stamped catalog numbers for permanent identificationsmall physical size for greater design flexibility

THese small DimeNsiON Fuses aRe THe RiGHT FiT... FOR a TiGHT FiT

Fast acting A3T and A6T Class T fuses combine two highly desirable features -- high currentlimitation and a small physical size. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings or current limitingcapability. These fuses have glass melaminebodies for superior dimensional stability andcatalog numbers stamped into the blades forpermanent identification.

UL Listed to Standard 248-15 File E2137

CSA Certified to Standard C22.2 No. 248.15

DC Listed to UL Standard 248

approvalsHiGHliGHTs:

Fast ActingExtremely Current Limiting Small Physical SizeDC Ratings

RecommendedFuseBlocksWithBoxConnectorsforAmp-trapClassTFuses

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

AmpereRating

3060100200400600

1-pole30306T

30606T

31031T

32031T

34031T

36031T

3-pole30308T

30608T

31033T

32033T

34033T

1-pole60306T

60606T

61031T

62031T

64031T

66031T

3-pole60308T

60608T

61033T

62033T

CatalogNumber 300V 600V

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 24: Ferraz shawmut

B ��

FasT aCTiNG/Class T Fuses amp-TRap®

StandardFuseAmpereRatings,CatalogNumbers

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 300V 600V Rating 300V 600V Rating 300V 600V 1 A3T1 A6T1 60 A3T60 A6T60 300 A3T300 A6T300 3 A3T3 A6T3 70 A3T70 A6T70 350 A3T350 A6T350 6 A3T6 A6T6 80 A3T80 A6T80 400 A3T400 A6T400 10 A3T10 A6T10 90 A3T90 A6T90 450 A3T450 A6T450 15 A3T15 A6T15 100 A3T100 A6T100 500 A3T500 A6T500 20 A3T20 A6T20 110 A3T110 A6T110 600 A3T600 A6T600 25 A3T25 A6T25 125 A3T125 A6T125 700 A3T700 A6T700 30 A3T30 A6T30 150 A3T150 A6T150 800 A3T800 A6T800 35 A3T35 A6T35 175 A3T175 A6T175 1000 A3T1000 40 A3T40 A6T40 200 A3T200 A6T200 1200 A3T1200 45 A3T45 A6T45 225 A3T225 A6T225 50 A3T50 A6T50 250 A3T250 A6T250

AMPERE A B C D F G J RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm A3T 1-30 .88 22.4 .41 10.3 - - - - - - - - - - 31-60 .88 22.4 .56 14.1 - - - - - - - - - - 61-100 2.16 54.9 .81 20.6 .12 3.2 .75 19.0 1.56 39.6 .28 7.1 .82 20.8 101-200 2.44 62.0 1.06 26.9 .19 4.8 .88 22.4 1.70 43.2 .34 8.6 .83 21.1

201-400 2.75 69.8 1.33 33.8 .25 6.4 1.00 25.4 1.84 46.7 .41 10.4 .84 21.3 401-600 3.06 77.7 1.62 41.1 .31 7.8 1.25 31.8 2.03 51.6 .48 12.2 .84 21.3 601-800 3.38 85.8 2.08 52.8 .38 9.7 1.75 44.4 2.22 56.4 .55 14.0 .88 22.4 801-1200 4.00 102 2.52 64.0 .44 11.2 2.00 50.8 2.53 64.3 .61 15.5 1.03 26.2

A6T

1-30 1.50 38.1 .57 14.5 - - - - - - - - - -

31-60 1.57 39.9 .81 20.6 1.51 38.4 1.00 25.4 - - - - - -

61-100 2.95 75.0 .82 20.8 .12 3.2 .75 19.0 2.35 59.7 .28 7.1 1.58 40.1

101-200 3.26 82.8 1.07 27.2 .19 4.8 .88 22.4 2.51 63.7 .34 8.6 1.61 41.0

201-400 3.62 92.1 1.62 41.3 .25 6.4 1.00 25.4 2.72 69.1 .41 10.4 1.70 43.2

401-600 3.98 101.2 2.06 52.4 .31 7.9 1.25 31.8 2.95 75.0 .48 12.2 1.70 43.2

601-800 4.33 110.0 2.50 63.5 .37 9.5 1.75 44.4 3.17 80.5 .56 14.1 1.70 43.2

Dimensions

A3T1-60

A3T61-1200

A3T

A6T31-60

A6T61-800

A6T

A6T1-30

a3T & a6T

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 25: Ferraz shawmut

B

B ��

FasT aCTiNG/Class T Fuses a3T & a6T amp-TRap®

Curr

ent

in a

mpe

res

Time in seconds

A3T30to1200

Mel

ting

Tim

e–

Curr

entD

ata,

300

VFu

ses

PeakLet-ThruCurrentData–A3T30to1200,300VoltsAC

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 26: Ferraz shawmut

B ��

Time in seconds

FasT aCTiNG/Class T Fuses a3T & a6T

amp-TRap®

Curr

ent

in a

mpe

res

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

available Current in Rms symmetrical amperes

A6T1to800M

eltin

gTi

me

–Cu

rren

tDat

a,6

00V

Fuse

s

PeakLet-ThruCurrentData–A6T30to800,600VoltsAC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 27: Ferraz shawmut

B

B ��

appliCaTiONs:

LoadcentersPanelboardsSwitchboardsBus DuctFeeder CircuitsNon-inductive LoadsLighting Circuits

amp-TRap®

a2K & a6K Class RK1

a2K aC: 1 to 600A 250VAC, 200kAI.R. DC: 1 to 600A 250VDC, 200kA I.R.

a6K aC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.

Ratings

Features/Benefits

THese Fast-actinG Fuses DeliVeR a HiGH DeGRee OF CuRReNT limiTaTiON wHeRe yOu NeeD iT mOsT

Current-limiting A2K and A6K fuses provideexcellent protection where high available shortcircuit currents exist. These fast-acting fuses are particularly good for branch/feeder circuits and back-up protection.

UL Listed to Standard 248-12 File E2137

CSA Certified to Standard C22.2 No. 248.12

Ferraz Shawmut Certified for DC per UL248

approvalsHiGHliGHTs:

Highly Current-LimitingFast ActingRejection Style

Rejection style design prevents replacement by other fuse classesFiberglass body provides dimensional stability in harsh industrial environmentseasy-to-read imprint label for quick recognition and replacementHigh degree of current limitation for low peak let-thru current

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 28: Ferraz shawmut

B ��

FasT aCTiNG/Class RK1 Fuses a2K & a6K

amp-TRap®

AMPERECATALOGNUMBER AMPERECATALOGNUMBER AMPERECATALOGNUMBER RATING 250V 600V RATING 250V 600V RATING 250V 600V

1 A2K1R A6K1R 35 A2K35R A6K35R 175 A2K175R A6K175R

3 A2K3R A6K3R 40 A2K40R A6K40R 200 A2K200R A6K200R

4 - A6K4R 45 A2K45R A6K45R 225 A2K225R A6K225R

5 A2K5R A6K5R 50 A2K50R A6K50R 250 A2K250R A6K250R

6 A2K6R A6K6R 60 A2K60R A6K60R 300 A2K300R A6K300R

8 - A6K8R 70 A2K70R A6K70R 350 A2K350R A6K350R

10 A2K10R A6K10R 80 A2K80R A6K80R 400 A2K400R A6K400R

12 A2K12R - 90 A2K90R A6K90R 450 A2K450R A6K450R

15 A2K15R A6K15R 100 A2K100R A6K100R 500 A2K500R A6K500R

20 A2K20R A6K20R 110 A2K110R A6K110R 600 A2K600R A6K600R

25 A2K25R A6K25R 125 A2K125R A6K125R

30 A2K30R A6K30R 150 A2K150R A6K150R

StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-A2KFUSES 0-30 2 51 9/16 14 - - - - - -

31-60 3 76 13/16 21 - - - - - -

61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25

101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35

201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48

401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57

600V-A6KFUSES 0-30 5 127 13/16 21 - - - - - -

31-60 5-1/2 139 1-1/16 27 - - - - - -

61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25

101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35

201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48

401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57

Dimensions

Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole

0-30 20306R 20308R 60306R 60308R

31-60 20606R 20608R 60606R 60608R

61-100 21036R 21038R 61036R 61038R

101-200 22001R 22003R 62001R 62003R

201-400 24001R 24003R 64001R 64003R

401-600 2631R 2633R 6631R 6633R

RecommendedFuseBlocksWithBoxConnectorsForAmp-trapClassRK1Fuses

A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.

0-60A

61-600A

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 29: Ferraz shawmut

B

B ��

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

FasT aCTiNG/Class RK1 Fuses a2K & a6K amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

available Current in Rms symmetrical amperes

A2K30to600

Mel

ting

Tim

e–

Curr

entD

ata,

250

VFu

ses

PeakLet-ThruCurrentData–A2K30to600,250VoltsAC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 30: Ferraz shawmut

B �0

FasT aCTiNG/Class RK1 Fuses a2K & a6K amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

available Current in Rms symmetrical amperes

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

A6K30to600

Mel

ting

Tim

e–

Curr

entD

ata,

600

VFu

ses

PeakLet-ThruCurrentData–A6K30to600,600VoltsAC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 31: Ferraz shawmut

AC: (70 to 600A) 600VAC, 200KA I.R.

300KA I.R. Self certified

Ratings

HiGH speeD RK1 (HsRK)

Protect your electrical power wiring and power semi-conductors with a single fuse.

The new HIGH SPEED RK1 (HSRK) combines semi-conductor fuse performance with NEC branch circuit compliance. The fuse was designed with two specific applications in mind: 1. To provide semiconductor fuse performance

to solid state drive applications but in the larger RK body sizes that have been typically installed in older systems.

2. To provide industrial power applications with the most current limiting fuse available, which in turn provides the best arc flash mitigation available to power systems using the larger RK size fuses.

HsRK (70 TO 600a)UL listed to 248-12 File E2137

CSA certified to C22.2 - No. 248.12

approvals

amp-TRap®

HsRK

Current LimitingLow I2tDrive protection in larger RK body sizes for older installationsFast acting

HiGHliGHTs:

Branch circuitsAC drivesSolid state controllersFeeder circuitsArc flash mitigation

appliCaTiONs:

Most current limiting RK1 availableProvides the best Arc flash mitigation for feeder and branch circuits (non motor load circuits)Excellent cycling ability for frequent drive starts and stops without nuisance openingExtremely Low I2t

Features/Benefits

HiGH speeD/Class RK1

B

B �1Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 32: Ferraz shawmut

B ��

Ampere Catalog# Ampere Catalog# Rating 600V Rating 600V

70 HSRK70R 200 HSRK200R

80 HSRK80R 225 HSRK225R

90 HSRK90R 250 HSRK250R

100 HSRK100R 300 HSRK300R

110 HSRK110R 350 HSRK350R

125 HSRK125R 400 HSRK400R

150 HSRK150R 450 HSRK450R

175 HSRK175R 500 HSRK500R

600 HSRK600R

StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm600V-HSRKFUSES 61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25

101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35

201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48 401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57

Dimensions

FuseCatalogNumber Ampere600V Rating 1pole 3pole

61-100 61036R 61038R

101-200 62001R 62003R

201-400 64001R 64003R

401-600 6631R 6633R

RecommendedFuseBlocksWithBoxConnectorsForAmp-trap®ClassRK1Fuses

A variety of pole configurations and ter-mination provisions are available. Refer to the fuse block section of this catalog for details.

70-600A

amp-TRap®

HiGH speeD/Class RK1 HsRK

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 33: Ferraz shawmut

B

B ��

amp-TRap®

HiGH speeD/Class RK1 HsRK

% Rated Currentworking Voltage (aC Rms Volts)

Corr

ectio

n Fa

ctor

for

l2 t

Corr

ectio

n Fa

ctor

for

wat

ts l

oss

AmpereRating(A)

Pre-arc(A2sX103)

MaxClearingI2t@600VAC

(A2sX103)

70 1.2 14

80 1.6 17

90 2.3 24

100 2.7 26

110 2.3 23

125 3.4 32

150 5.1 45

175 8.0 65

200 14 100

225 14 110

250 16 130

300 26 200

350 37 290

400 63 450

450 67 500

500 98 600

600 141 900

i2t vs working Voltage watts loss vs % Rated Current

i2t Data HsRK (amp Rating)R

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 34: Ferraz shawmut

B ��

prea

rcin

g Ti

me(

s)

AmpereRating(A)

WattsLossatRatedCurrent

70 10

80 11

90 13

100 14

110 18

125 19

150 25

175 26

200 27

225 35

250 43

300 45

350 47

400 53

450 62

500 63

600 83

amp-TRap®

HiGH speeD/Class RK1 HsRK

melting Time — Current Data HsRK70 — 600R, 600V aC

prearc Current (a Rms)±8% prearc Current (a Rms)±8%

prea

rcin

g Ti

me(

s)

max

imum

pea

k le

t-Th

ru C

urre

nt (

a)

60Hz Rms symmetrcal prosective Current (a)

peak let-Thru Data HsRK70 — 600R, 600V aCwatts loss Data HsRK70 — 600R, 600V aC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 35: Ferraz shawmut

B

B ��

amp-TRap®

aG Class G

amp-TRap aG Fuses FiT RiGHT iN TO a wide variety OF iNDusTRial appliCaTiONs

The Ferraz Shawmut Amp-trap AG fuse series is a complete line of Class G fuses. AG fuses safely fit a wide variety of applications. Class G fuses are made in four physical sizes and provide good branch-circuit protection for lighting, heating, and appliance circuits.

AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER 1/2 AG1/2 15 AG15

1 AG1 20 AG20 1-1/2 AG1-1/2 25 AG25 2 AG2 30 AG30 3 AG3 35 AG35

4 AG4 40 AG40

5 AG5 45 AG45

6 AG6 50 AG50

8 AG8 60 AG60

10 AG10

StandardFuseAmpereRatings,CatalogNumbers

Dimensions

AMPERE A B C RATING In. mm In. mm In. mm

1/2-15A 1.31 33.3 .406 10.3 .28 7.1

20A 1.41 35.8 .406 10.3 .28 7.1

25,30A 1.62 41.2 .406 10.3 .28 7.1

35-60A 2.25 57.2 .406 10.3 .50 12.7

Cross Reference:AG will replace the following fuses: Bussmann SC, Littelfuse SLC

Features/Benefits

Four unique sizes from ½-60 amperes do not allow inter-changeability with other fuse classesFiberglass bodies provide dimensional stability in harsh industrial settings

appliCaTiONs:

LightingHeating*AppliancesBranch Circuits

* Except in Canada, where fuses must be “P” or “D” type.

UL Listed to Standard 248-5 File E2137

CSA Certified to Standard C22.2 No. 248.5

approvalsHiGHliGHTs:

Current-LimitingTime Delay (above 5A)

Ratings

aC: 1/2 to 20A 600VAC, 100K A I.R. 25 to 60A, 480VAC, 100k A I.R.

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 36: Ferraz shawmut

B ��

Time Delay/Class G Fuses aG amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

Curr

ent

in a

mpe

res

Time in seconds

Mel

ting

Tim

e–

Curr

entD

ata,

480

VFu

ses

AG1to10

Mel

ting

Tim

e–

Curr

entD

ata,

480

VFu

ses

AG15to60

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

PeakLet-ThruCurrentData–AG1to60,480VoltsAC

available Current in Rms symmetrical amperes

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 37: Ferraz shawmut

B

B ��

appliCaTiONs:

Control CircuitsLightingGeneral LoadsBranch Circuit Protection

amp-TRap®

aTmR Class CC

aC: 1/10 to 30A 600VAC, 200kA I.R.

DC: 1/10 to 30A 600VDC, 100kA I.R.

Ratings

Features/BenefitsRejection style design prevents replacement errors when used with recommended fuse blocksVersatile design for individual component and branch circuit protection

small Fuse - BiG pROTeCTiONFOR GeNeRal CiRCuiTs

Amp-trap® ATMR fuses, in the Class CC family, are the smallest dimension 600VAC/DC fuses suitable for branch circuit protection. The ATMR is a popular choice for economical protection of control circuits and control circuit transformers where available short cir-cuit currents exceed 10,000 amperes. ATMR’s rejec-tion dimensions prevent substitution by lesser rated fuses. These fast acting fuses give current limiting protection to general circuits.

UL Listed to Standard 248-4 File E2137

CSA Certified to Standard C22.2 No. 248.4

DC Listed to ULStandard 248

approvalsHiGHliGHTs:

Fast ActingVery Current-Limiting

StandardFuseAmpereRatings,CatalogNumbers AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER 1/10 ATMR1/10 3-1/2 ATMR3-1/2

1/8 ATMR1/8 4 ATMR4

2/10 ATMR2/10 5 ATMR5

1/4 ATMR1/4 6 ATMR6

3/10 ATMR3/10 7 ATMR7

1/2 ATMR1/2 8 ATMR8

3/4 ATMR3/4 9 ATMR9

1 ATMR1 10 ATMR10

1-1/4 ATMR1-1/4 12 ATMR12

1-1/2 ATMR-1-1/2 15 ATMR15

2 ATMR2 20 ATMR20

2-1/2 ATMR2-1/2 25 ATMR25

3 ATMR3 30 ATMR30

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 38: Ferraz shawmut

B ��

CATALOGNUMBER ULTRASAFE™ ScrewConnector PressurePlate Numberof Indicating withDouble Connector CopperBox Poles FuseHolders QuickConnects withDouble Connector QuickConnects ADDER 30310R 30320R 30350R 1 USCC1I 30311R 30321R 30351R 2 USCC2I 30312R 30322R 30352R 3 USCC3I 30313R 30323R 30353R 3 USFMCCI

RecommendedFuseBlocksForAmp-Trap® ClassCCFuses

Refer to the Class CC Fuse Block section of this catalog for other details.

Dimensions

FasT aCTiNG/Class CC Fuses aTmR

amp-TRap®

Time in seconds

Curr

ent

in a

mpe

res

Mel

ting

Tim

e–

Curr

entD

ata,

600

VFu

ses

ATMR1/10to30

Current in amperes

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res PeakLet-ThruCurrentData–ATMR3/4to30,600VoltsAC

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 39: Ferraz shawmut

B

B ��

appliCaTiONs:

FeedersBranch CircuitsResistive HeatingResidential and Small Commercial Installations

ONe-Time

OT/OTN/OTs Class K-5

OT aC: 1 to 600A 250VAC, 50kA I.R. DC: 1 to 600A 250VDC, 20kA I.R.

OTN (Canada) aC: 15 to 60A 250VAC, 50kA I.R.

OTs aC: 1 to 600A 600VAC, 50kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.

Ratings

Features/Benefits

easy to read imprint label for quick recognition and replacementlow cost for high protection value

FOR versatility and economy, THeseGeNeRal puRpOse Fuses aRe HaRD TO BeaT

OT, OTN and OTS general purpose fuses provide low cost protection for feeder and branch circuitsserving lighting, heating, and other non-motor loads. OT, OTN and OTS fuses will safely interruptavailable short circuit currents up to 50,000 amperes in all ratings.

OT, OTN and OTS fuses are not rejection fuses – care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses.

OTN 15 through 60 satisfy the Canadian electrical code requirement for Type “P,” low melting-point, non-time delay fuses.

UL Listed to Standard 248-9 File E2137

CSA Certified to Standard C22.2 No. 248.9*

Ferraz Shawmut Certified for DC per UL248

*The Canadian ElectricalCode requires these fuses in ratings 15 through 60A to be of the low melting point design use OTN 15-60.

approvalsHiGHliGHTs:

VersatileLowest cost protection for circuits serving non-inductive loads

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 40: Ferraz shawmut

B �0

GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs ONe-Time

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V 1 OT1 OTS1 30 OT30, OTN30* OTS30 125 OT125 OTS125 2 OT2 OTS2 35 OT35, OTN35* OTS35 150 OT150 OTS150 3 OT3 OTS3 40 OT40, OTN40* OTS40 175 OT175 OTS175 4 OT4 OTS4 45 OT45, OTN45* OTS45 200 OT200 OTS200 5 OT5 OTS5 50 OT50, OTN 50* OTS50 225 OT225 OTS225 6 OT6 OTS6 60 OT60, OTN60* OTS60 250 OT250 OTS250 7 OT7 – 65 OT65 – 300 OT300 OTS300 8 OT8 OTS8 70 OT70 OTS70 350 OT350 OTS350 10 OT10 OTS10 75 OT75 OTS75 400 OT400 OTS400 12 OT12 OTS12 80 OT80 OTS80 450 OT450 OTS450 15 OT15, OTN15* OTS15 90 OT90 OTS90 500 OT500 OTS500 20 OT20, OTN20* OTS20 100 OT100 OTS100 600 OT600 0TS600 25 OT25, OTN 25* OTS25 110 OT110 OTS110

StandardFuseAmpereRatings,CatalogNumbers

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm 250V-OT,OTNFUSES 0-30 2 51 9/16 14 - - - - - -

31-60 3 76 13/16 21 - - - - - -

61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25

101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35

201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48

401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57

600V-OTSFUSES 0-30 5 127 13/16 21 - - - - - -

31-60 5-1/2 139 1-1/16 27 - - - - - -

61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25

101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35

201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48

401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57

Dimensions

Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole

0-30 20306 20308 60306 60308

31-60 20606 20608 60606 60608

61-100 21036 21038 61036 61038

101-200 22001 22003 62001 62003

201-400 24001 24003 64001 64003

401-600 2631 2633 6631 6633

RecommendedFuseBlocksWithBoxConnectorsForOne-TimeClassK-5Fuses

A variety of pole configurations and termination provi-sions are available. Refer to the fuse block section of this catalog for details.

61-600A

0-60A

* In Canada

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 41: Ferraz shawmut

B

B �1

max

imum

inst

anta

neou

s pe

ak l

et-T

hru

ampe

res

available Current in Rms symmetrical amperes

PeakLet-ThruCurrentData–OT,OTN&OTS30to600,250and600VoltsAC

GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs ONe-Time

Time in seconds

Curr

ent

in a

mpe

res

Mel

ting

Tim

e–

Curr

entD

ata,

250

VFu

ses

OT30to600;OTN30,60

Curr

ent

in a

mpe

res

Time in seconds

OTS30to600

Mel

ting

Tim

e–

Curr

entD

ata,

600

VFu

ses

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 42: Ferraz shawmut

B ��

appliCaTiONs:

General purpose loads where short circuits are 10,000 amperes or less

ReNewaBle

RF/RFs & Rl/Rls Class H

RF aC: 1 to 600A 250VAC, 10kA I.R.

RFs aC: 1 to 600A 600VAC, 10kA I.R.

Ratings

Features/Benefits

Knurledbushings for ease of disassembly

Ruggedconstruction for maximum service life

Precisiondie-cutrenewallinks renew quickly and give repeatable performance

TRaDiTiONal pROTeCTiON FOR CiRCuiTs wiTH less THaN 10,000a sHORT CiRCuiT CuRReNT

RF and RFS general purpose fuses are suitable for application where available short circuit cur-rents do not exceed 10,000 amperes. RF and RFS renewable fuses use matched RL and RLS die-cut zinc links from 1 to 600 amperes in 32 ratings.

UL Listed to Standard 248-7 File E2137

CSA Certified to Standard C22.2 No. 248.7

approvalsHiGHliGHTs:

Renewable32 Renewal Link Ratings

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 43: Ferraz shawmut

B

B ��B ��

61-600A

0-60A

ReNewaBle Class H Fuses/liNKs RF/RFs & Rl/Rls

AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V 1 RF1/RL1 RFS1/RLS1 45 RF45/RL45 RFS45/RLS45 225 RF225/RL225 RFS225/RLS225 2 RF2/RL2 RFS2/RLS2 50 RF50/RL50 RFS50/RLS50 250 RF250/RL250 RFS250/RLS250 3 RF3/RL3 RFS3/RLS3 60 RF60/RL60 RFS60/RLS60 300 RF300/RL300 RFS300/RLS300 5 RF5/RL5 RFS5/RLS5 70 RF70/RL70 RFS70/RLS70 350 RF350/RL350 RFS350/RLS350 6 RF6/RL6 RFS6/RLS6 80 RF80/RL80 RFS80/RLS80 400 RF400/RL400 RFS400/RLS400 10 RF10/RL10 RFS10/RLS10 90 RF90/RL90 RFS90/RLS90 450 RF450/RL450 RFS450/RLS450 15 RF15/RL15 RFS15RLS15 100 RF100/RL100 RFS100/RLS100 500 RF500/RL500 RFS500/RLS500 20 RF20/RL20 RFS20/RLS20 110 RF110/RL110 RFS110/RLS110 600 RF600/RL600 RFS600/RLS600 25 RF25/RL25 RFS25/RLS25 125 RF125/RL125 RFS125/RLS125 30 RF30/RL30 RFS30/RLS30 150 RF150/RL150 RFS150/RLS150 35 RF35/RL35 RFS35/RLS35 175 RF175/RL175 RFS175/RLS175 40 RF40/RL40 RFS40/RLS40 200 RF200/RL200 RFS200/RLS200

StandardFuseAmpereRatings,CatalogNumbers

Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole

0-30 20306 20308 60306 60308

31-60 20606 20608 60606 60608

61-100 21036 21038 61036 61038

101-200 22001 22003 62001 62003

201-400 24001 24003 64001 64003

401-600 2631 2633 6631 6633

RecommendedFuseBlocksWithBoxConnectorsForRenewableClassHFuses

A variety of pole configurations and termination provisions is avail-able. Refer to the fuseholder section of this catalog for details.

AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-RFFUSES 0-30 2 51 9/16 14 - - - - - -

31-60 3 76 13/16 21 - - - - - -

61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 18 1 25

101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35

201-400 8-5/8 219 2-1/16 54 1/4 6 1-5/8 41 1-7/8 48

401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57

600V-RFSFUSES 0-30 5 127 13/16 21 - - - - - -

31-60 5-1/2 139 1-1/16 27 - - - - - -

61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 18 1 25

101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35

201-400 11-5/8 295 2-9/16 67 1/4 6 1-5/8 41 1-7/8 48

401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57

Dimensions

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com