ferraz shawmut
DESCRIPTION
Catalogo Ferraz shawmutTRANSCRIPT
North American Power Fuses
The most popular North American power fuses — to meet the most popular protection priorities.
• Class RK5 / Tri-onic® TR & TRS
• DC-rated / Tri-onic® TRS-RDC
• Class J / Amp-trap® HSJ
• Class J / Amp-trap® A4J
• Class L / Amp-trap® A4BY
• Class L / Amp-trap® A4BT
• Class T / Amp-trap® A3T & A6T
• Class RK1 / Amp-trap® A2K & A6K
• Class RK1/Amp-trap® HSRK
• Class G / Amp-trap® AG
• Class CC / Amp-trap® ATMR
• Class K-5 / OT, OTN & OTS One-time
• Class H / RF/RFS & RL/RLS Renewable
Your problem: Today, you need a time-delay power fuse that can handle normal surges. Tomorrow, it’s a power fuse with a high interrupting rating and the added security of rejection dimen-sions. The day after that, one of those economical one-time power fuses will do the trick. But where can you turn for all three?
Our solution: Ferraz Shawmut’s comprehensive power fuse offering covers a complete range of applications and a complete range of circuit-protection needs. Whether it’s the characteristics of our Tri-onic® time-delay fuses. The high current-limiting capacity of our original Amp-trap® power fuses. The cost-efficient protec-tion of our One-Time fuses. Or some other application-specific power fuse solution.
Want more information fast? For more technical or application-specific information, please call our Power Fuse experts, at 978-462-6662; 416-252-9371 in Canada; or visit our website at us.ferrazshawmut.com.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �
Time Delay/Class RK5
TR aC: 1/10 to 600A 250VAC, 200kA I.R.
DC: 1/10 to 2 8/10A & 35 to 400A, 250VDC, 20kA I.R.; 3 to 30A & 450 to 600A, 160VDC, 20kA I.R.
TRs aC: 1/10 to 600A 600VAC, 200kA I.R.
DC: 1/10 to 12A, 600VDC, 20kA I.R.; 15 to 60A, 300VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R.
➤
➤
➤
➤
TRi-ONiC®
TR & TRs
Ratings
Features/Benefits
solid state smartspot indicatorTime delay for motor start-ups and transformer inrush currents without nuisance openingCurrent limiting for low peak let-thru currentRejection-style design prevents replacement errors (when used with recommended fuse blocks)easy-to-read label for quick recognition and replacementmetal-embossed date and catalog number for traceability and lasting identification Fiberglass body provides dimensional stability in harsh industrial settingsHigh-grade silica filler ensures fast arc quenching and high current limitation
➤
➤
➤
➤
➤
➤
➤
➤
THe iNDusTRy’s mOsT pOpulaR Fuse FOR mOTOR CiRCuiT pROTeCTiON.
Tri-onic® SmartSpot® fuses now provide a visual open fuse indicator. With advanced material technol-ogy added to the existing product the TR and TRS current limiting time delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-onic proven time delay characteristic safely handles harmless starting currents and inrush currents associated with today’s motors and transformers.
UL Listed to Standard 248-12 File E2137
CSA Certified to Standard C22.2 No. 248.12
DC Listed to UL Standard 248 TRS only
➤
➤
➤
approvals
appliCaTiONs:
Motor CircuitsMainsFeedersBranch CircuitsTransformersService Entrance EquipmentGeneral-purpose Protection
➤
➤
➤
➤
➤
➤
➤
HiGHliGHTs:
Time DelayCurrent LimitingAC & DC Rated
➤
➤
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �
TR & TRs
TRi-ONiC®
AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V
1/10 TR1/10R TRS1/10R 3-1/2 TR3-1/2R TRS3-1/2R 50 TR50R TRS50R
15/100 TR15/100R TRS15/100R 4 TR4R TRS4R 60 TR60R TRS60R
2/10 TR2/10R TRS2/10R 4-1/2 TR4-1/2R TRS4-1/2R 70 TR70R TRS70R
3/10 TR3/10R TRS3/10R 5 TR5R TRS5R 75 TR75R TRS75R
4/10 TR4/10R TRS4/10R 5-6/10 TR5-6/10R TRS5-6/10R 80 TR80R TRS80R
1/2 TR1/2R TRS1/2R 6 TR6R TRS6R 90 TR90R TRS90R
6/10 TR6/10R TRS6/10R 6-1/4 TR6-1/4R TRS6-1/4R 100 TR100R TRS100R
8/10 TR8/10R TRS8/10R 7 TR7R TRS7R 110 TR110R TRS110R
1 TR1R TRS1R 8 TR8R TRS8R 125 TR125R TRS125R
1-1/8 TR1-1/8R TRS1-1/8R 9 TR9R TRS9R 150 TR150R TRS150R
1-1/4 TR1-1/4R TRS1-1/4R 10 TR10R TRS10R 175 TR175R TRS175R
1-4/10 TR1-4/10R TRS1-4/10R 12 TR12R TRS12R 200 TR200R TRS200R
1-6/10 TR1-6/10R TRS1-6/10R 15 TR15R TRS15R 225 TR225R TRS225R
1-8/10 TR1-8/10R TRS1-8/10R 17-1/2 TR17-1/2R TRS17-1/2R 250 TR250R TRS250R
2 TR2R TRS2R 20 TR20R TRS20R 300 TR300R TRS300R
2-1/4 TR2-1/4R TRS2-1/4R 25 TR25R TRS25R 350 TR350R TRS350R
2-1/2 TR2-1/2R TRS2-1/2R 30 TR30R TRS30R 400 TR400R TRS400R
2-8/10 TR2-8/10R TRS2-8/10R 35 TR35R TRS35R 450 TR450R TRS450R
3 TR3R TRS3R 40 TR40R TRS40R 500 TR500R TRS500R
3-2/10 TR3-2/10R TRS3-2/10R 45 TR45R TRS45R 600 TR600R TRS600R
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-TRFUSES 0-30 2 51 9/16 14 - - - - - - 31-60 3 76 13/16 21 - - - - - - 61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25 101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35 201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48 401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57 600V-TRSFUSES 0-30 5 127 13/16 21 - - - - - - 31-60 5-1/2 139 1-1/16 27 - - - - - - 61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25 101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35 201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48 401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumberAmpere250V600V Rating 1Pole 3pole 1pole 3pole 0-30 20306R 20308R 60306R 60308R
31-60 20606R 20608R 60606R 60608R
61-100 21036R 21038R 61036R 61038R
101-200 22001R 22003R 62001R 62003R
201-400 24001R 24003R 64001R 64003R
401-600 2631R 2633R 6631R 6633R
RecommendedFuseBlocksWithBoxConnectorsForTri-onic®
ClassRK5Fuses
0-60A
61-600A
Note: Indicator not available (1/10 - 7) amps.
Time Delay/Class RK5 Fuses
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �
TimeinSeconds
Curr
enti
nAm
pere
s
Time Delay/Class RK5 Fuses TRi-ONiC®
TR1/10 TO 12
mel
ting
Tim
e –
Curr
ent
Data
, 250
V Fu
ses
TimeinSeconds
Curr
enti
nAm
pere
s
TR15 TO 600m
eltin
g Ti
me
– Cu
rren
t Da
ta, 2
50V
Fuse
s
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �
Time Delay/Class RK5 Fuses
TimeinSeconds
Curr
enti
nAm
pere
s
TRi-ONiC®
TRs1/10 TO 12
mel
ting
Tim
e –
Curr
ent
Data
. 600
V Fu
ses
TimeinSeconds
Curr
enti
nAm
pere
s
TRs15 TO 600m
eltin
g Ti
me
– Cu
rren
t Da
ta ,
600V
Fus
es
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �
Time Delay/Class RK5 Fuses TRi-ONiC®
AvailableCurrentinRMSSymmetricalAmperes
Max
imum
Inst
anta
neou
sPe
akL
et-T
hru
Ampe
res
AvailableCurrentinRMSSymmetricalAmperes
Max
imum
Inst
anta
neou
sPe
akL
et-T
hru
Ampe
res
peak let-Thru Current Data – TR30 to 600, 250 Volts aC
peak let-Thru Current Data – TRs15 to 600, 600 Volts aC
Note: See Application Information page L9 for All Motor and Transformer Tables.
TR & TRs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �
TRi-ONiC®
TRs-RDC
appliCaTiONs:
Mine CircuitsTrailing CablesPump MotorsRail Heaters
➤
➤
➤
➤
DC: 1 to 30A 300VDC, 20kA I.R. (Consult Factory for Availability)
DC: 35 to 400A 600VDC, 20kA I.R.
➤
➤
Ratings
Features/Benefits
DC rated for mine duty and other long time-constant applicationsTime delay for motor start-ups and high inrush loads without nuisance openingRugged glass melamine body for superior Reliability in harsh environments
➤
➤
➤
➤
DC RaTeD FOR TOuGH DC appliCaTiONs
The Tri-onic® DC fuse series is designed for DCcircuit protection in surface and underground mines. The TRS-RDC is MSHA approved and meets the industry’s most severe third party requirements for 600VDC rated fuses.
The TRS-RDC is a time-delay fuse with essentially the same time-current characteristic as thestandard Tri-onic®.
MSHA Approval No. 28-26-0
➤
approvalsHiGHliGHTs:
Time DelayDC Rated
➤
➤
Time Delay/DC RaTeD
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �
AMPERE CATALOG RATING NUMBER 1/10 TRS1/10RDC
15/100 TRS15/100RDC
2/10 TRS2/10RDC
3/10 TRS3/10RDC
4/10 TRS4/10RDC
1/2 TRS1/2RDC
6/10 TRS6/10RDC
8/10 TRS8/10RDC
1 TRS1RDC
1-1/8 TRS1-1/8RDC
AMPERE CATALOG RATING NUMBER 1-1/4 TRS1-1/4RDC
1-4/10 TRS1-4/10RDC
1-6/10 TRS1-6/10RDC
1-8/10 TRS1-8/10RDC
2 TRS2RDC
2-1/4 TRS2-1/4RDC
2-1/2 TRS2-1/2RDC
2-8/10 TRS2-8/10RDC
3 TRS3RDC
3-2/10 TRS3-2/10RDC
AMPERE CATALOG RATING NUMBER 3-1/2 TRS3-1/2RDC
4 TRS4RDC
4-1/2 TRS4-1/2RDC
5 TRS5RDC
5-6/10 TRS5-6/10RDC
6 TRS6RDC
6-1/4 TRS6-1/4RDC
8 TRS8RDC
9 TRS9RDC
10 TRS10RDC
AMPERE CATALOG RATING NUMBER 12 TRS12RDC
15 TRS15RDC
17-1/2 TRS17-1/2RDC
20 TRS20RDC
30 TRS30RDC
35 TRS35RDC
40 TRS40RDC
45 TRS45RDC
50 TRS50RDC
60 TRS60RDC
AMPERE CATALOG RATING NUMBER 70 TRS70RDC
80 TRS80RDC
90 TRS90RDC
100 TRS100RDC
125 TRS125RDC
150 TRS150RDC
175 TRS175RDC
200 TRS200RDC
250 TRS250RDC
300 TRS300RDC
400 TRS400RDC
Time Delay/600VDC Fuses TRi-ONiC®
StandardFuseAmpereRatings,CatalogNumbers
Dimensions
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm 0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
Curr
enti
nAm
pere
s
TimeinSeconds
0-60Amperes
61-400Amperes
TRs-RDC60 TO 400
mel
ting
Tim
e –
Curr
ent
Data
, 600
V Fu
ses
TRs-RDC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �
Features/Benefits
Optimized over-load capability for withstanding elevated levels of current during electronic motor controller starts
low i2t (low thermal energy)
excellent Cycling ability for frequent starts/stops without nuisance opening
➤
➤
➤
pROTeCT yOuR wiRiNG aND pOweR semi-CONDuCTORs wiTH a siNGle Fuse.
The new High Speed J (HSJ) combines the low I2t of a semiconductor fuse and the branch circuit performance of a Class J UL listed fuse. This fuse was designed for the starting characteristics of solid state motor controllers. The HSJ can provide branch circuit protection per NEC requirements, as well as very low I2t for protection of power semiconductors such as Diodes, SCR’s, GTO’s and SSR’s.
appliCaTiONs:
Branch CircuitsControl PanelsElectronic Motor ControllersPhase ControllersDrivesSoft-StartersSolid State Relays
➤
➤
➤
➤
➤
➤
➤
HiGHliGHTs:
Current-LimitingAC & DC RatingsLow l2tCompact Size
➤
➤
➤
➤
amp-TRap®
HsJ
aC: 1-600A 600VAC, 200kA I.R. 300kA I.R. Self Certified
DC: 15-600A 500VDC, 100kA I.R. L/R 10mS
➤
➤
Ratings
HsJ (15 TO 600a)UL Listed to Standard 248-8 File E2137
DC Listed to UL248
CSA Certified to Standard C22.2 No. 248.8
➤
➤
➤
approvals
HiGH speeD/Class J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 10
amp-TRap®
HiGH speeD/Class J HsJ
FuseCatalogNumber Ampere600VORLESS Rating 1Pole 3pole 0-30 US3J1I US3J3I
31-60 US6J1I US6J3I
61-100 61036J 61038J
101-200 62001J 62003J
201-400 64031J 64033J
401-600 6631J 6633J
RecommendedFuseBlocksWithBoxConnectorsforAmp-trap®ClassJFuses
A variety of pole configurations and termination provisions is available.
StandardFuseAmpereRatings,CatalogNumbers
15-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-4/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
AMPERERATING
A B C D E F G H In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
DimensionsFig1
AMPERERATING
CATALOGNUMBER
OUTLINEFIGURE
AMPERERATING
CATALOGNUMBER
OUTLINEFIGURE
1 HSJ1 1 90 HSJ90 2
3 HSJ3 1 100 HSJ100 2
6 HSJ6 1 110 HSJ110 2
10 HSJ10 1 125 HSJ125 2
15 HSJ15 1 150 HSJ150 2
17-1/2 HSJ17-1/2 1 175 HSJ175 2
20 HSJ20 1 200 HSJ200 2
25 HSJ25 1 225 HSJ225 2
30 HSJ30 1 250 HSJ250 2
35 HSJ35 1 300 HSJ300 2
40 HSJ40 1 350 HSJ350 2
45 HSJ45 1 400 HSJ400 2
50 HSJ50 1 450 HSJ450 2
60 HSJ60 1 500 HSJ500 2
70 HSJ70 2 600 HSJ600 2
80 HSJ80 2
Fig2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 11
amp-TRap®
HiGH speeD/Class J
1.0
.8
.6
.4
.2
00 100 200 300 400 500 600
110-600 AMP
15-100 AMP
Clearing i2t vs Operating Voltage
1.0
.8
.6
.4
.2
50 60 70 80 90 100
watts loss vs. % Rated Current
Corr
ectio
nFa
ctor
forI
2t
OperatingVoltage(ACRMSVolts) PercentRatedCurrent
I2tData-600VoltsAC,100kA
Corr
ectio
nFa
ctor
forW
atts
Los
s
Max Clearing I2t @ Max Clearing I2t @ WattsAmpere 600V AC 100kA 480V AC 100kA Loss atRating Pre-Arc 1 Fuse 2 in Series 1 Fuse 2 in Series Rated
(A) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103) (A2s x 103) Current15 0.02 0.36 0.15 0.23 0.12 2.6
17.5 0.03 0.45 0.19 0.29 0.15 3.520 0.04 0.58 0.24 0.37 0.19 3.725 0.08 1.2 0.50 0.77 0.40 430 0.16 2 0.84 1.3 0.66 4.135 0.16 1.5 0.63 0.96 0.50 5.340 0.27 2.3 1.0 1.5 0.76 5.545 0.32 3.3 1.4 2.1 1.1 650 0.44 5.5 2.3 3.5 1.8 6.860 0.72 8.0 3.4 5.1 2.6 8.470 1.2 12 5.0 7.7 4.0 1080 1.6 15 6.3 9.6 5.0 1190 2.3 21 8.8 13 6.9 13100 2.7 23 9.7 15 7.6 14110 2.3 21 10 13.9 8 18125 3.4 29 14 19 11 19150 5.1 41 20 27 16 22175 8.0 60 29 40 23 24200 14 92 44 61 35 26225 14 110 53 73 42 30250 16 130 62 86 49 36300 26 200 96 132 76 38350 37 290 139 191 110 40400 63 450 216 297 171 42450 67 500 240 330 190 58500 98 600 288 396 228 59600 141 900 432 594 342 68
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 1�
peak let-Thru Data - HsJ15 to 600, 600Volts aC
Clearing i2t at 500 VDC 100ka, l/R = 10ms DC Voltage vs. Time Constant
DCV
olta
geC
apab
ility
L/RTimeConstant(mS)
amp-TRap®
HiGH speeD/Class J
AMPERE RATING
CLEARING I2t @ 500 VDC L/R = 10 ms (A2s X 103)
15 0.12 17.5 0.18 20 0.24 25 0.46 30 0.91 35 0.60 40 0.92 45 1.3 50 2.2 60 3.2 70 4.8 80 6.2 90 8.9
100 10 110 8.8 125 13 150 19 175 28 200 46 225 52 250 59 300 96 350 136 400 230 450 270 500 390 600 560
Max
imum
Inst
anta
neou
sPe
akL
et-T
hru
Ampe
res
AvailableCurrentinRMSSymmetricalAmperes
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 1�
melting Time - Current Data, HsJ15 to 600, 600Volts aC
AvailableCurrentinRMSSymmetricalAmperes
Tim
ein
Sec
onds
Tim
ein
Sec
onds
amp-TRap®
HiGH speeD/Class J
AvailableCurrentinRMSSymmetricalAmperes
HsJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 1�
appliCaTiONs:
Capacitors LoadcentersPanelboardsSwitchboardsBus DuctFeeder CircuitsCircuit BreakersLighting, Heating, and General Loads
➤
➤
➤
➤
➤
➤
➤
➤
amp-TRap®
a4J
aC: 1 to 600A 600VAC, 200kA I.R.
DC: 1 to 600A 300VDC, 100kA I.R.
➤
➤
Ratings
Features/Benefits
High current limitation for low peak let-thru currentunique dimensions prevent replacement by other fuse classesFiberglass body provides dimensional stability in harsh industrial environmentseasy-to-read imprint label for quick recognition and replacement
➤
➤
➤
➤
FOR excellent CuRReNT limiTiNG pROTeCTiON
A4J Class J fuses deliver excellent current-limiting protection to a wide variety of applications. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings, interrupting ratings, or current-limiting capability.
UL Listed to Standard 248-8 File E2137
CSA Certified to Standard C22.2 No. 248.8
DC Listed to UL 248
IEC 269-2-1
➤
➤
➤
➤
approvalsHiGHliGHTs:
Fast ActingVery Current-LimitingDC Ratings
➤
➤
➤
FasT aCTiNG/Class J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 1�
ampeRe CaTalOG ampeRe CaTalOG ampeRe CaTalOG RaTiNG NumBeR RaTiNG NumBeR RaTiNG NumBeR
1 A4J1 50 A4J50 200 A4J200
3 A4J3 60 A4J60 225 A4J225
6 A4J6 70 A4J70 250 A4J250
10 A4J10 75 A4J75 300 A4J300
15 A4J15 80 A4J80 350 A4J350
20 A4J20 90 A4J90 400 A4J400
25 A4J25 100 A4J100 450 A4J450
30 A4J30 110 A4J110 500 A4J500
35 A4J35 125 A4J125 600 A4J600
40 A4J40 150 A4J150
45 A4J45 175 A4J175
StandardFuseAmpereRatings,CatalogNumbers
FasT aCTiNG/Class J Fuses
Fuse Catalog Number
ampere 600V OR less
Rating 1 pole 3 pole
0-30 US3J1I US3J3I
31-60 US6J1I US6J3I
61-100 61036J 61038J
101-200 62001J 62003J
201-400 64031J 64033J
401-600 6631J 6633J
RecommendedFuseBlocksWithBoxConnectorsforAmp-trapClassJFuses
A variety of pole configurations and termina-tion provisions are available. Refer to the fuse block section of this catalog for details.
Dimensions
amp-TRap®
a4J
ampeRe a B C D e F G H
RaTiNG in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
1-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
1-60A
61-600A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 1�
FasT aCTiNG/Class J Fuses amp-TRap®
Curr
enti
nAm
pere
s
AvailableCurrentinRMSSymmetricalAmperes
Max
imum
Inst
anta
neou
sPe
akL
et-T
hru
Ampe
res
TimeinSeconds
a4J30 TO 600
mel
ting
Tim
e –
Curr
ent
Data
, 600
V Fu
ses
peak let-Thru Current Data – 30 to 600, 600 Volts aC
a4J
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 1�
amp-TRap®
a4By Class l
appliCaTiONs:
Mains, FeedersCircuit BreakersLoadcentersPanelboardsSwitchboardsMetering Centers
➤
➤
➤
➤
➤
➤
aC: 200 to 6,000A 600VAC,200kA I.R.
DC: 200 to 2500A 300VDC, 100kA I.R.
➤
➤
Ratings
Features/Benefits
unique dimensions prevent replacement by other fuse classes Blade stamped catalog numbers for permanent identification Glass melamine body and plated terminals provide superior reliability in harsh environments
➤
➤
➤
COuNT ON THe HiGH iNTeRRupTiNG RaTiNG OF OuR most widely-used Class l Fuse
When it comes to protecting service entrance equipment, feeder circuits, and circuit breakers, A4BY fuses have been the industry’s favorite. The A4BY is a 100% rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500% rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.
UL Listed to Standard 248-10 (601-6000A) File E2137
CSA Certified to Standard C22.2 No. 248.10 (601-6000A)
Ferraz Shawmut Certified for DC per UL248 (601-6000A)
➤
➤
➤
approvalsHiGHliGHTs:
Current-Limiting4-Second Time DelayDC RatingsUniform Characteristics in all Ampere Ratings
➤
➤
➤
➤
IndicatorsOptional built-in fuse indicators (-TI) are available. Consult factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 1�
Class l Fuses a4By
amp-TRap®
AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER RATING NUMBER
200 A4BY200 801 A4BY801 2000 A4BY2000
250 A4BY250 900 A4BY900 2001 A4BY2001
300 A4BY300 1000 A4BY1000 2200 A4BY2200
350 A4BY350 1100 A4BY1100 2500 A4BY2500
400 A4BY400 1200 A4BY1200 3000 A4BY3000
450 A4BY450 1201 A4BY1201 3001 A4BY3001
500 A4BY500 1350 A4BY1350 3500 A4BY3500
600 A4BY600 1400 A4BY1400 4000 A4BY4000
601 A4BY601 1500 A4BY1500 4001 A4BY4001
650 A4BY650 1600 A4BY1600 4500 A4BY4500
700 A4BY700 1601 A4BY1601 5000 A4BY5000
750 A4BY750 1800 A4BY1800 6000 A4BY6000
800 A4BY800
StandardFuseAmpereRatings,CatalogNumbers
200-800A 801-2000A
3001-4000A
2001-3000A
4001-6000A
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm
200-600 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61
601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61
801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88
1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88
1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88
2001-2500 10-3/4 273 4-1/2 114 3/4 19 3-1/2 89 3-15/32 88
2501-3000 10-3/4 273 5 127 3/4 19 4 102 3-15/32 88
3001-4000 10-3/4 273 5-3/4 146 3/4 19 4-3/4 121 3-15/32 88
4001-5000 10-3/4 273 6-1/4 159 1 25 5-1/4 133 3-15/32 88
5001-6000 10-3/4 273 7-1/8 181 1 25 5-3/4 146 3-15/32 88
Dimensions
safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B 1�
Class l Fuses a4By amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
A4BY200to6000
Mel
ting
Tim
e–
Cur
rent
Dat
a,6
00V
Fuse
s
PeakLet-ThruCurrentData–A4BY300to6000,600VoltsAC
available Current in Rms symmetrical amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �0
appliCaTiONs:
MotorsMotor ControllersTransformersMainsFeeders
➤
➤
➤
➤
➤
amp-TRap®
a4BT Time Delay/Class l
aC: 200 to 2,000A 600VAC, 200kA I.R.
DC: 200 to 2,000A 500VDC, 100kA I.R.
➤
➤
Ratings
Features/Benefits
unique dimensions prevent replacement by other fuse classes.Blade-stamped catalog numbers for permanent identificationGlass melamine body and plated terminals provide superior reliability in harsh environments
➤
➤
➤
wHeN yOuR heavier loads NeeDpROTeCTiON a4BT Fuses wON’T leT yOu DOwN
The high interrupting rating of A4BT current limiting fuses is ideally suited for protecting mains, feeders, and general circuits. The 10-sec-ond time delay at 500% of fuse rating is ideal for large motors and other loads with a high inrush. A4BT fuses are suitable for DC applications up to 500VDC. An A4BT fuse can be applied to normal loads up to its full ampere rating to allow 100% rating of equipment.
UL Listed to Standard 248-10 (601-2000A) File E2137
CSA Certified to Standard C22.2 No. 248.10 (601-2000A)
Ferraz Shawmut Certified for DC per UL248 (601-2000A)
➤
➤
➤
approvalsHiGHliGHTs:
Current-LimitingFull 10-Second DelayDC RatingsUniform Characteristics in all Ampere Ratings
➤
➤
➤
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �1
Time Delay/Class l Fuses a4BT amp-TRap®
AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER RATING NUMBER
200 A4BT200 601 A4BT601 1100 A4BT1100
250 A4BT250 650 A4BT650 1200 A4BT1200
300 A4BT300 700 A4BT700 1400 A4BT1400
350 A4BT350 750 A4BT750 1500 A4BT1500
400 A4BT400 800 A4BT800 1600 A4BT1600
450 A4BT450 900 A4BT900 1800 A4BT1800
500 A4BT500 1000 A4BT1000 2000 A4BT2000
600 A4BT600
StandardFuseAmpereRatings,CatalogNumbers
Dimensions
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm
200-600* 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61
601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61
801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88
1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88
1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88
safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
801-2000A200-800A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
Time Delay/Class l Fuses a4BT amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
available Current in Rms symmetrical amperes
Mel
ting
Tim
e–
Curr
entD
ata,
600
VAC
/500
VDC
Fus
es
A4BT200to2000
PeakLet-ThruCurrentData–A4BT300to2000,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
appliCaTiONs:
LoadcentersPanelboardsSwitchboardsCircuit BreakersMetering Centers
➤
➤
➤
➤
➤
amp-TRap®
a3T & a6T FasT aCTiNG/Class T
a3T aC:1 to 1200A 300VAC, 200kA I.R. DC: 1 to 1200A 160VDC, 50kA I.R.
a6T aC: 1 to 800A 600VAC, 200kA I.R. DC: 1 to 800A 300VDC, 100kA I.R.
➤
➤
Ratings
Features/Benefits
extremely current limiting for low peak let-thru currentunique dimensions prevent replacement by other fuse classes
Blade-stamped catalog numbers for permanent identificationsmall physical size for greater design flexibility
➤
➤
➤
➤
THese small DimeNsiON Fuses aRe THe RiGHT FiT... FOR a TiGHT FiT
Fast acting A3T and A6T Class T fuses combine two highly desirable features -- high currentlimitation and a small physical size. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings or current limitingcapability. These fuses have glass melaminebodies for superior dimensional stability andcatalog numbers stamped into the blades forpermanent identification.
UL Listed to Standard 248-15 File E2137
CSA Certified to Standard C22.2 No. 248.15
DC Listed to UL Standard 248
➤
➤
➤
approvalsHiGHliGHTs:
Fast ActingExtremely Current Limiting Small Physical SizeDC Ratings
➤
➤
➤
➤
RecommendedFuseBlocksWithBoxConnectorsforAmp-trapClassTFuses
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
AmpereRating
3060100200400600
1-pole30306T
30606T
31031T
32031T
34031T
36031T
3-pole30308T
30608T
31033T
32033T
34033T
–
1-pole60306T
60606T
61031T
62031T
64031T
66031T
3-pole60308T
60608T
61033T
62033T
–
–
CatalogNumber 300V 600V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
FasT aCTiNG/Class T Fuses amp-TRap®
StandardFuseAmpereRatings,CatalogNumbers
AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 300V 600V Rating 300V 600V Rating 300V 600V 1 A3T1 A6T1 60 A3T60 A6T60 300 A3T300 A6T300 3 A3T3 A6T3 70 A3T70 A6T70 350 A3T350 A6T350 6 A3T6 A6T6 80 A3T80 A6T80 400 A3T400 A6T400 10 A3T10 A6T10 90 A3T90 A6T90 450 A3T450 A6T450 15 A3T15 A6T15 100 A3T100 A6T100 500 A3T500 A6T500 20 A3T20 A6T20 110 A3T110 A6T110 600 A3T600 A6T600 25 A3T25 A6T25 125 A3T125 A6T125 700 A3T700 A6T700 30 A3T30 A6T30 150 A3T150 A6T150 800 A3T800 A6T800 35 A3T35 A6T35 175 A3T175 A6T175 1000 A3T1000 40 A3T40 A6T40 200 A3T200 A6T200 1200 A3T1200 45 A3T45 A6T45 225 A3T225 A6T225 50 A3T50 A6T50 250 A3T250 A6T250
AMPERE A B C D F G J RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm A3T 1-30 .88 22.4 .41 10.3 - - - - - - - - - - 31-60 .88 22.4 .56 14.1 - - - - - - - - - - 61-100 2.16 54.9 .81 20.6 .12 3.2 .75 19.0 1.56 39.6 .28 7.1 .82 20.8 101-200 2.44 62.0 1.06 26.9 .19 4.8 .88 22.4 1.70 43.2 .34 8.6 .83 21.1
201-400 2.75 69.8 1.33 33.8 .25 6.4 1.00 25.4 1.84 46.7 .41 10.4 .84 21.3 401-600 3.06 77.7 1.62 41.1 .31 7.8 1.25 31.8 2.03 51.6 .48 12.2 .84 21.3 601-800 3.38 85.8 2.08 52.8 .38 9.7 1.75 44.4 2.22 56.4 .55 14.0 .88 22.4 801-1200 4.00 102 2.52 64.0 .44 11.2 2.00 50.8 2.53 64.3 .61 15.5 1.03 26.2
A6T
1-30 1.50 38.1 .57 14.5 - - - - - - - - - -
31-60 1.57 39.9 .81 20.6 1.51 38.4 1.00 25.4 - - - - - -
61-100 2.95 75.0 .82 20.8 .12 3.2 .75 19.0 2.35 59.7 .28 7.1 1.58 40.1
101-200 3.26 82.8 1.07 27.2 .19 4.8 .88 22.4 2.51 63.7 .34 8.6 1.61 41.0
201-400 3.62 92.1 1.62 41.3 .25 6.4 1.00 25.4 2.72 69.1 .41 10.4 1.70 43.2
401-600 3.98 101.2 2.06 52.4 .31 7.9 1.25 31.8 2.95 75.0 .48 12.2 1.70 43.2
601-800 4.33 110.0 2.50 63.5 .37 9.5 1.75 44.4 3.17 80.5 .56 14.1 1.70 43.2
Dimensions
A3T1-60
A3T61-1200
A3T
A6T31-60
A6T61-800
A6T
A6T1-30
a3T & a6T
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
FasT aCTiNG/Class T Fuses a3T & a6T amp-TRap®
Curr
ent
in a
mpe
res
Time in seconds
A3T30to1200
Mel
ting
Tim
e–
Curr
entD
ata,
300
VFu
ses
PeakLet-ThruCurrentData–A3T30to1200,300VoltsAC
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
Time in seconds
FasT aCTiNG/Class T Fuses a3T & a6T
amp-TRap®
Curr
ent
in a
mpe
res
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
available Current in Rms symmetrical amperes
A6T1to800M
eltin
gTi
me
–Cu
rren
tDat
a,6
00V
Fuse
s
PeakLet-ThruCurrentData–A6T30to800,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
appliCaTiONs:
LoadcentersPanelboardsSwitchboardsBus DuctFeeder CircuitsNon-inductive LoadsLighting Circuits
➤
➤
➤
➤
➤
➤
➤
amp-TRap®
a2K & a6K Class RK1
a2K aC: 1 to 600A 250VAC, 200kAI.R. DC: 1 to 600A 250VDC, 200kA I.R.
a6K aC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
➤
➤
Ratings
Features/Benefits
THese Fast-actinG Fuses DeliVeR a HiGH DeGRee OF CuRReNT limiTaTiON wHeRe yOu NeeD iT mOsT
Current-limiting A2K and A6K fuses provideexcellent protection where high available shortcircuit currents exist. These fast-acting fuses are particularly good for branch/feeder circuits and back-up protection.
UL Listed to Standard 248-12 File E2137
CSA Certified to Standard C22.2 No. 248.12
Ferraz Shawmut Certified for DC per UL248
➤
➤
➤
approvalsHiGHliGHTs:
Highly Current-LimitingFast ActingRejection Style
➤
➤
➤
Rejection style design prevents replacement by other fuse classesFiberglass body provides dimensional stability in harsh industrial environmentseasy-to-read imprint label for quick recognition and replacementHigh degree of current limitation for low peak let-thru current
➤
➤
➤
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
FasT aCTiNG/Class RK1 Fuses a2K & a6K
amp-TRap®
AMPERECATALOGNUMBER AMPERECATALOGNUMBER AMPERECATALOGNUMBER RATING 250V 600V RATING 250V 600V RATING 250V 600V
1 A2K1R A6K1R 35 A2K35R A6K35R 175 A2K175R A6K175R
3 A2K3R A6K3R 40 A2K40R A6K40R 200 A2K200R A6K200R
4 - A6K4R 45 A2K45R A6K45R 225 A2K225R A6K225R
5 A2K5R A6K5R 50 A2K50R A6K50R 250 A2K250R A6K250R
6 A2K6R A6K6R 60 A2K60R A6K60R 300 A2K300R A6K300R
8 - A6K8R 70 A2K70R A6K70R 350 A2K350R A6K350R
10 A2K10R A6K10R 80 A2K80R A6K80R 400 A2K400R A6K400R
12 A2K12R - 90 A2K90R A6K90R 450 A2K450R A6K450R
15 A2K15R A6K15R 100 A2K100R A6K100R 500 A2K500R A6K500R
20 A2K20R A6K20R 110 A2K110R A6K110R 600 A2K600R A6K600R
25 A2K25R A6K25R 125 A2K125R A6K125R
30 A2K30R A6K30R 150 A2K150R A6K150R
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-A2KFUSES 0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-A6KFUSES 0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole
0-30 20306R 20308R 60306R 60308R
31-60 20606R 20608R 60606R 60608R
61-100 21036R 21038R 61036R 61038R
101-200 22001R 22003R 62001R 62003R
201-400 24001R 24003R 64001R 64003R
401-600 2631R 2633R 6631R 6633R
RecommendedFuseBlocksWithBoxConnectorsForAmp-trapClassRK1Fuses
A variety of pole configurations and termination provisions are available. Refer to the fuse block section of this catalog for details.
0-60A
61-600A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
FasT aCTiNG/Class RK1 Fuses a2K & a6K amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
available Current in Rms symmetrical amperes
A2K30to600
Mel
ting
Tim
e–
Curr
entD
ata,
250
VFu
ses
PeakLet-ThruCurrentData–A2K30to600,250VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �0
FasT aCTiNG/Class RK1 Fuses a2K & a6K amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
available Current in Rms symmetrical amperes
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
A6K30to600
Mel
ting
Tim
e–
Curr
entD
ata,
600
VFu
ses
PeakLet-ThruCurrentData–A6K30to600,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AC: (70 to 600A) 600VAC, 200KA I.R.
300KA I.R. Self certified
➤
➤
Ratings
HiGH speeD RK1 (HsRK)
Protect your electrical power wiring and power semi-conductors with a single fuse.
The new HIGH SPEED RK1 (HSRK) combines semi-conductor fuse performance with NEC branch circuit compliance. The fuse was designed with two specific applications in mind: 1. To provide semiconductor fuse performance
to solid state drive applications but in the larger RK body sizes that have been typically installed in older systems.
2. To provide industrial power applications with the most current limiting fuse available, which in turn provides the best arc flash mitigation available to power systems using the larger RK size fuses.
HsRK (70 TO 600a)UL listed to 248-12 File E2137
CSA certified to C22.2 - No. 248.12
➤
➤
approvals
amp-TRap®
HsRK
Current LimitingLow I2tDrive protection in larger RK body sizes for older installationsFast acting
➤
➤
➤
➤
HiGHliGHTs:
Branch circuitsAC drivesSolid state controllersFeeder circuitsArc flash mitigation
➤
➤
➤
➤
➤
appliCaTiONs:
Most current limiting RK1 availableProvides the best Arc flash mitigation for feeder and branch circuits (non motor load circuits)Excellent cycling ability for frequent drive starts and stops without nuisance openingExtremely Low I2t
➤
➤
➤
➤
Features/Benefits
HiGH speeD/Class RK1
B
B �1Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
Ampere Catalog# Ampere Catalog# Rating 600V Rating 600V
70 HSRK70R 200 HSRK200R
80 HSRK80R 225 HSRK225R
90 HSRK90R 250 HSRK250R
100 HSRK100R 300 HSRK300R
110 HSRK110R 350 HSRK350R
125 HSRK125R 400 HSRK400R
150 HSRK150R 450 HSRK450R
175 HSRK175R 500 HSRK500R
600 HSRK600R
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm600V-HSRKFUSES 61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48 401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
FuseCatalogNumber Ampere600V Rating 1pole 3pole
61-100 61036R 61038R
101-200 62001R 62003R
201-400 64001R 64003R
401-600 6631R 6633R
RecommendedFuseBlocksWithBoxConnectorsForAmp-trap®ClassRK1Fuses
A variety of pole configurations and ter-mination provisions are available. Refer to the fuse block section of this catalog for details.
70-600A
amp-TRap®
HiGH speeD/Class RK1 HsRK
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
amp-TRap®
HiGH speeD/Class RK1 HsRK
% Rated Currentworking Voltage (aC Rms Volts)
Corr
ectio
n Fa
ctor
for
l2 t
Corr
ectio
n Fa
ctor
for
wat
ts l
oss
AmpereRating(A)
Pre-arc(A2sX103)
MaxClearingI2t@600VAC
(A2sX103)
70 1.2 14
80 1.6 17
90 2.3 24
100 2.7 26
110 2.3 23
125 3.4 32
150 5.1 45
175 8.0 65
200 14 100
225 14 110
250 16 130
300 26 200
350 37 290
400 63 450
450 67 500
500 98 600
600 141 900
i2t vs working Voltage watts loss vs % Rated Current
i2t Data HsRK (amp Rating)R
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
prea
rcin
g Ti
me(
s)
AmpereRating(A)
WattsLossatRatedCurrent
70 10
80 11
90 13
100 14
110 18
125 19
150 25
175 26
200 27
225 35
250 43
300 45
350 47
400 53
450 62
500 63
600 83
amp-TRap®
HiGH speeD/Class RK1 HsRK
melting Time — Current Data HsRK70 — 600R, 600V aC
prearc Current (a Rms)±8% prearc Current (a Rms)±8%
prea
rcin
g Ti
me(
s)
max
imum
pea
k le
t-Th
ru C
urre
nt (
a)
60Hz Rms symmetrcal prosective Current (a)
peak let-Thru Data HsRK70 — 600R, 600V aCwatts loss Data HsRK70 — 600R, 600V aC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
amp-TRap®
aG Class G
amp-TRap aG Fuses FiT RiGHT iN TO a wide variety OF iNDusTRial appliCaTiONs
The Ferraz Shawmut Amp-trap AG fuse series is a complete line of Class G fuses. AG fuses safely fit a wide variety of applications. Class G fuses are made in four physical sizes and provide good branch-circuit protection for lighting, heating, and appliance circuits.
AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER 1/2 AG1/2 15 AG15
1 AG1 20 AG20 1-1/2 AG1-1/2 25 AG25 2 AG2 30 AG30 3 AG3 35 AG35
4 AG4 40 AG40
5 AG5 45 AG45
6 AG6 50 AG50
8 AG8 60 AG60
10 AG10
StandardFuseAmpereRatings,CatalogNumbers
Dimensions
AMPERE A B C RATING In. mm In. mm In. mm
1/2-15A 1.31 33.3 .406 10.3 .28 7.1
20A 1.41 35.8 .406 10.3 .28 7.1
25,30A 1.62 41.2 .406 10.3 .28 7.1
35-60A 2.25 57.2 .406 10.3 .50 12.7
Cross Reference:AG will replace the following fuses: Bussmann SC, Littelfuse SLC
Features/Benefits
Four unique sizes from ½-60 amperes do not allow inter-changeability with other fuse classesFiberglass bodies provide dimensional stability in harsh industrial settings
➤
➤
appliCaTiONs:
LightingHeating*AppliancesBranch Circuits
* Except in Canada, where fuses must be “P” or “D” type.
➤
➤
➤
➤
UL Listed to Standard 248-5 File E2137
CSA Certified to Standard C22.2 No. 248.5
➤
➤
approvalsHiGHliGHTs:
Current-LimitingTime Delay (above 5A)
➤
➤
Ratings
aC: 1/2 to 20A 600VAC, 100K A I.R. 25 to 60A, 480VAC, 100k A I.R.
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
Time Delay/Class G Fuses aG amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
Curr
ent
in a
mpe
res
Time in seconds
Mel
ting
Tim
e–
Curr
entD
ata,
480
VFu
ses
AG1to10
Mel
ting
Tim
e–
Curr
entD
ata,
480
VFu
ses
AG15to60
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
PeakLet-ThruCurrentData–AG1to60,480VoltsAC
available Current in Rms symmetrical amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
appliCaTiONs:
Control CircuitsLightingGeneral LoadsBranch Circuit Protection
➤
➤
➤
➤
amp-TRap®
aTmR Class CC
aC: 1/10 to 30A 600VAC, 200kA I.R.
DC: 1/10 to 30A 600VDC, 100kA I.R.
➤
➤
Ratings
Features/BenefitsRejection style design prevents replacement errors when used with recommended fuse blocksVersatile design for individual component and branch circuit protection
➤
➤
small Fuse - BiG pROTeCTiONFOR GeNeRal CiRCuiTs
Amp-trap® ATMR fuses, in the Class CC family, are the smallest dimension 600VAC/DC fuses suitable for branch circuit protection. The ATMR is a popular choice for economical protection of control circuits and control circuit transformers where available short cir-cuit currents exceed 10,000 amperes. ATMR’s rejec-tion dimensions prevent substitution by lesser rated fuses. These fast acting fuses give current limiting protection to general circuits.
UL Listed to Standard 248-4 File E2137
CSA Certified to Standard C22.2 No. 248.4
DC Listed to ULStandard 248
➤
➤
➤
approvalsHiGHliGHTs:
Fast ActingVery Current-Limiting
➤
➤
StandardFuseAmpereRatings,CatalogNumbers AMPERE CATALOG AMPERE CATALOG RATING NUMBER RATING NUMBER 1/10 ATMR1/10 3-1/2 ATMR3-1/2
1/8 ATMR1/8 4 ATMR4
2/10 ATMR2/10 5 ATMR5
1/4 ATMR1/4 6 ATMR6
3/10 ATMR3/10 7 ATMR7
1/2 ATMR1/2 8 ATMR8
3/4 ATMR3/4 9 ATMR9
1 ATMR1 10 ATMR10
1-1/4 ATMR1-1/4 12 ATMR12
1-1/2 ATMR-1-1/2 15 ATMR15
2 ATMR2 20 ATMR20
2-1/2 ATMR2-1/2 25 ATMR25
3 ATMR3 30 ATMR30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
CATALOGNUMBER ULTRASAFE™ ScrewConnector PressurePlate Numberof Indicating withDouble Connector CopperBox Poles FuseHolders QuickConnects withDouble Connector QuickConnects ADDER 30310R 30320R 30350R 1 USCC1I 30311R 30321R 30351R 2 USCC2I 30312R 30322R 30352R 3 USCC3I 30313R 30323R 30353R 3 USFMCCI
RecommendedFuseBlocksForAmp-Trap® ClassCCFuses
Refer to the Class CC Fuse Block section of this catalog for other details.
Dimensions
FasT aCTiNG/Class CC Fuses aTmR
amp-TRap®
Time in seconds
Curr
ent
in a
mpe
res
Mel
ting
Tim
e–
Curr
entD
ata,
600
VFu
ses
ATMR1/10to30
Current in amperes
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res PeakLet-ThruCurrentData–ATMR3/4to30,600VoltsAC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��
appliCaTiONs:
FeedersBranch CircuitsResistive HeatingResidential and Small Commercial Installations
➤
➤
➤
➤
ONe-Time
OT/OTN/OTs Class K-5
OT aC: 1 to 600A 250VAC, 50kA I.R. DC: 1 to 600A 250VDC, 20kA I.R.
OTN (Canada) aC: 15 to 60A 250VAC, 50kA I.R.
OTs aC: 1 to 600A 600VAC, 50kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
➤
➤
➤
Ratings
Features/Benefits
easy to read imprint label for quick recognition and replacementlow cost for high protection value
➤
➤
FOR versatility and economy, THeseGeNeRal puRpOse Fuses aRe HaRD TO BeaT
OT, OTN and OTS general purpose fuses provide low cost protection for feeder and branch circuitsserving lighting, heating, and other non-motor loads. OT, OTN and OTS fuses will safely interruptavailable short circuit currents up to 50,000 amperes in all ratings.
OT, OTN and OTS fuses are not rejection fuses – care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses.
OTN 15 through 60 satisfy the Canadian electrical code requirement for Type “P,” low melting-point, non-time delay fuses.
UL Listed to Standard 248-9 File E2137
CSA Certified to Standard C22.2 No. 248.9*
Ferraz Shawmut Certified for DC per UL248
*The Canadian ElectricalCode requires these fuses in ratings 15 through 60A to be of the low melting point design use OTN 15-60.
➤
➤
➤
approvalsHiGHliGHTs:
VersatileLowest cost protection for circuits serving non-inductive loads
➤
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B �0
GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs ONe-Time
AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V 1 OT1 OTS1 30 OT30, OTN30* OTS30 125 OT125 OTS125 2 OT2 OTS2 35 OT35, OTN35* OTS35 150 OT150 OTS150 3 OT3 OTS3 40 OT40, OTN40* OTS40 175 OT175 OTS175 4 OT4 OTS4 45 OT45, OTN45* OTS45 200 OT200 OTS200 5 OT5 OTS5 50 OT50, OTN 50* OTS50 225 OT225 OTS225 6 OT6 OTS6 60 OT60, OTN60* OTS60 250 OT250 OTS250 7 OT7 – 65 OT65 – 300 OT300 OTS300 8 OT8 OTS8 70 OT70 OTS70 350 OT350 OTS350 10 OT10 OTS10 75 OT75 OTS75 400 OT400 OTS400 12 OT12 OTS12 80 OT80 OTS80 450 OT450 OTS450 15 OT15, OTN15* OTS15 90 OT90 OTS90 500 OT500 OTS500 20 OT20, OTN20* OTS20 100 OT100 OTS100 600 OT600 0TS600 25 OT25, OTN 25* OTS25 110 OT110 OTS110
StandardFuseAmpereRatings,CatalogNumbers
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm 250V-OT,OTNFUSES 0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-OTSFUSES 0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole
0-30 20306 20308 60306 60308
31-60 20606 20608 60606 60608
61-100 21036 21038 61036 61038
101-200 22001 22003 62001 62003
201-400 24001 24003 64001 64003
401-600 2631 2633 6631 6633
RecommendedFuseBlocksWithBoxConnectorsForOne-TimeClassK-5Fuses
A variety of pole configurations and termination provi-sions are available. Refer to the fuse block section of this catalog for details.
61-600A
0-60A
* In Canada
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B �1
max
imum
inst
anta
neou
s pe
ak l
et-T
hru
ampe
res
available Current in Rms symmetrical amperes
PeakLet-ThruCurrentData–OT,OTN&OTS30to600,250and600VoltsAC
GeNeRal puRpOse/Class K-5 Fuses OT/OTN/OTs ONe-Time
Time in seconds
Curr
ent
in a
mpe
res
Mel
ting
Tim
e–
Curr
entD
ata,
250
VFu
ses
OT30to600;OTN30,60
Curr
ent
in a
mpe
res
Time in seconds
OTS30to600
Mel
ting
Tim
e–
Curr
entD
ata,
600
VFu
ses
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B ��
appliCaTiONs:
General purpose loads where short circuits are 10,000 amperes or less
➤
ReNewaBle
RF/RFs & Rl/Rls Class H
RF aC: 1 to 600A 250VAC, 10kA I.R.
RFs aC: 1 to 600A 600VAC, 10kA I.R.
➤
➤
Ratings
Features/Benefits
Knurledbushings for ease of disassembly
Ruggedconstruction for maximum service life
Precisiondie-cutrenewallinks renew quickly and give repeatable performance
➤
➤
➤
TRaDiTiONal pROTeCTiON FOR CiRCuiTs wiTH less THaN 10,000a sHORT CiRCuiT CuRReNT
RF and RFS general purpose fuses are suitable for application where available short circuit cur-rents do not exceed 10,000 amperes. RF and RFS renewable fuses use matched RL and RLS die-cut zinc links from 1 to 600 amperes in 32 ratings.
UL Listed to Standard 248-7 File E2137
CSA Certified to Standard C22.2 No. 248.7
➤
➤
approvalsHiGHliGHTs:
Renewable32 Renewal Link Ratings
➤
➤
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
B ��B ��
61-600A
0-60A
ReNewaBle Class H Fuses/liNKs RF/RFs & Rl/Rls
AmpereCatalogNumber AmpereCatalogNumber AmpereCatalogNumber Rating 250V 600V Rating 250V 600V Rating 250V 600V 1 RF1/RL1 RFS1/RLS1 45 RF45/RL45 RFS45/RLS45 225 RF225/RL225 RFS225/RLS225 2 RF2/RL2 RFS2/RLS2 50 RF50/RL50 RFS50/RLS50 250 RF250/RL250 RFS250/RLS250 3 RF3/RL3 RFS3/RLS3 60 RF60/RL60 RFS60/RLS60 300 RF300/RL300 RFS300/RLS300 5 RF5/RL5 RFS5/RLS5 70 RF70/RL70 RFS70/RLS70 350 RF350/RL350 RFS350/RLS350 6 RF6/RL6 RFS6/RLS6 80 RF80/RL80 RFS80/RLS80 400 RF400/RL400 RFS400/RLS400 10 RF10/RL10 RFS10/RLS10 90 RF90/RL90 RFS90/RLS90 450 RF450/RL450 RFS450/RLS450 15 RF15/RL15 RFS15RLS15 100 RF100/RL100 RFS100/RLS100 500 RF500/RL500 RFS500/RLS500 20 RF20/RL20 RFS20/RLS20 110 RF110/RL110 RFS110/RLS110 600 RF600/RL600 RFS600/RLS600 25 RF25/RL25 RFS25/RLS25 125 RF125/RL125 RFS125/RLS125 30 RF30/RL30 RFS30/RLS30 150 RF150/RL150 RFS150/RLS150 35 RF35/RL35 RFS35/RLS35 175 RF175/RL175 RFS175/RLS175 40 RF40/RL40 RFS40/RLS40 200 RF200/RL200 RFS200/RLS200
StandardFuseAmpereRatings,CatalogNumbers
Fuse CatalogNumber Ampere250V600V Rating 1Pole 3pole 1pole 3pole
0-30 20306 20308 60306 60308
31-60 20606 20608 60606 60608
61-100 21036 21038 61036 61038
101-200 22001 22003 62001 62003
201-400 24001 24003 64001 64003
401-600 2631 2633 6631 6633
RecommendedFuseBlocksWithBoxConnectorsForRenewableClassHFuses
A variety of pole configurations and termination provisions is avail-able. Refer to the fuseholder section of this catalog for details.
AMPERE A B C D E RATING In. mm In. mm In. mm In. mm In. mm250V-RFFUSES 0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 18 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 54 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-RFSFUSES 0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 18 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 67 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Dimensions
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com