    William Davis Ltd

    Proposed Housing Scheme,

    Shelford Road,

    Radcliffe-on-Trent

    Noise and Vibration Assessment

    December 2012

    Executive Park, Avalon Way, Anstey, Leicester, LE7 7GR

    Tel: +44 (0)116 234 8000

    Email: [email protected]

  • 8/13/2019 File 8 Noise Acoustic Report

    2/30

    www.wyg.com creative mindssafe hands

    Document Control

    Project: Proposed Residential Development, Shelford Road, Radcliffe-on-Trent

    Client: William Davis Ltd

    Job Number: A079137

    File Origin: O:\Acoustics Air Quality and Noise\Active Projects\A079137

    Document Checking:

    Prepared by:Graham DavisConsultant

    Signed:

    Contributor:Nathan Joe AllenGraduate Environmental Scientist

    Signed:

    Verified by:Nigel Mann

    Associate Environmental ScientistSigned:

    Issue Date Status

    1 03rdDecember 2012 First Issue

    2

    3

    4

  • 8/13/2019 File 8 Noise Acoustic Report

    3/30

    www.wyg.com creative mindssafe hands

    Contents Page

    1.0 Introduction.................................................................................................................................12.0 Assessment Criteria......................................................................................................................23.0 Assessment Methodology .............................................................................................................54.0 Site Survey ..................................................................................................................................95.0 Assessment of Key Effects..........................................................................................................126.0 Conclusions ...............................................................................................................................17

    Appendix Contents

    Appendix A Acoustic Terminology and AbbreviationsAppendix B Sketches

  • 8/13/2019 File 8 Noise Acoustic Report

    4/30

    Noise Assessment Report

    William Davis Ltd 1 A079137

    Proposed Residential Development December 2012

    1.0 Introduction

    1.1 Purpose of this Report

    This report presents the findings of a noise and vibration assessment for a proposed residential

    development, on Shelford Road, Radcliffe-on-Trent.

    A description of the existing noise environment in and around the site is provided. Noise surveys have been

    undertaken and the results used to verify predictions of the short-term and long-term effects of noise. The

    noise levels from the proposed development have been predicted at local representative receptors using

    CADNA noise modelling software which incorporates ISO 9613 and CRTN methodologies and calculations.

    A list of acoustic terminology and abbreviations used in this report is provided in Appendix A and a set of

    location plans and noise contour plots relevant to the assessment are presented in Appendix B.

    1.2 Legislative Context (England)

    PPG24 was replaced by NPPF on 27 March 2012. With regard to noise and planning NPPF contains the

    following 4 short statements (section 123):

    A. Avoid noise from giving rise to significant adverse impacts on health and quality of life as a result of

    new development;

    B. Mitigate and reduce to a minimum other adverse impacts on health and quality of life arising from

    noise from new development, including through the use of conditions;

    C. Recognise that development will often create some noise and existing businesses wanting to

    develop in continuance of their business should not have unreasonable restrictions put on them

    because of changes in nearby land uses since they were established; and

    D. Identify and protect areas of tranquillity which have remained relatively undisturbed by noise and

    are prized for their recreational and amenity value for this reason.

    Vibration is not specifically considered in the National Planning Policy Framework. However, it is considered

    that the relevant standards remain for guidance on human exposure to vibration in BS 6472:2008 and for

    buildings in BS 7385-2:1993.

  • 8/13/2019 File 8 Noise Acoustic Report

    5/30

    Noise Assessment Report

    William Davis Ltd 2 A079137

    Proposed Residential Development December 2012

    2.0Assessment Criteria

    2.1Internal Noise Assessment Criteria

    The criteria in BS 8233:1999 Sound insulation and noise reduction for buildings code of practice has

    been chosen as a suitable method for determining an adequate level of noise control to ensure that noise

    levels within existing properties, as a result of the proposed development, meet the following noise

    guideline values specified in the standard:

    Good Reasonable

    Living rooms LAeq= 30 - 40 dB

    Bedrooms LAeq= 30 - 35 dB, LAmax, night-time = 45 dB

    Gardens LAeq= 50 - 55 dB

    BS 8233:1999 suggests that a typical faade, regardless of construction, will offer a maximum of 15 dB

    sound insulation when windows are open. For the purposes of this assessment, the maximum external

    noise level from the source under consideration will be 45 dB(A) during the daytime, and 45 dB(A) during

    the night-time to ensure a maximum daytime LAeqof 30 dB, and a maximum night-time LAeqof 30 dB within

    habitable rooms are achieved.

    These levels are also comparable to the World Health Organisation Recommendations in their Guidelines

    for Community Noise (1999) publication which states that outdoor levels of 45 dB LAeq,Tfor open windows

    at night or internal levels of 30 dB LAeq,Tare guideline values to prevent sleep disturbance. Similarly

    outdoor levels of 60 dB LAmaxfor open windows at night or internal levels of 45 dB LAmaxare also maximum

    guideline values to prevent sleep disturbance.

    2.2 Vibration Assessment Criteria

    There are two applicable British Standards to describe vibration which are: BS 6472-2:2008, Guide to

    Evaluation of Human Exposure to Vibrations in Buildings (1 Hz to 80 Hz) and BS 7385-2:1993 Evaluation

    and Measurement for Vibration in Buildings Parts 1 (1990) and 2 (1993).

    2.2.1 Building Damage

    BS 7385-2:1993 Evaluation and Measurement for Vibration in Buildings provides guidance on acceptable

    values of transient vibration for avoidance of cosmetic damage to buildings as follows.

  • 8/13/2019 File 8 Noise Acoustic Report

    6/30

    Noise Assessment Report

    William Davis Ltd 3 A079137

    Proposed Residential Development December 2012

    Table 2.1 Transient Vibration Guide Values for Cosmetic Damage

    Table 2.1 above shows the limits for transient vibration, above which cosmetic damage could occur. Minor

    damage is possible at vibration magnitudes which are greater than twice those given above and major

    damage to a building structure may occur at values greater than four times the tabulated values. PPV

    values of below 15 mm/s are unlikely to results in any damage to buildings.

    Damage is classified into the following categories:

    Table 2.2 Damage Classification

    2.2.2 Human Exposure

    BS 6472-2:2008 Guide to evaluation of human exposure to vibrations in buildings provides general

    guidance on human exposure to building vibration in the range of 1 Hz to 80 Hz and includes curves of

    equal annoyance for humans. It also outlines the measurement methodology to be employed.

    It introduces the concept of Vibration Dose Value (VDV) and estimated Vibration Dose Value (eVDV) for thebasis of assessment of the severity of impulsive and intermittent vibration levels, such as would be caused

    by a series of trains passing a given location.

    Human reaction to vibration depends on displacement, frequency, the duration (exposure time), point of

    application and direction of the vibration. It appears that the effect of vibration on the people within a

    building will be far more serious than the effect on the building itself. The units in which VDV and eVDV

    are measured are metres per second raised to the power of minus 1.75 (or ms -1.75).

    The Standard gives recommended vibration dose values above which various degrees of adverse comment

    may be expected in residential buildings, with a daily 16 hour VDV of 0.2 to 0.4 ms-1.75 likely to give low

    probability of adverse comment as shown in the following table.

    Peak Component Particle Velocity in

    frequency range of predominant pulseType of Building

    4 Hz to 15 Hz 15 Hz and above

    Residential of Light Commercial TypeBuildings

    15 mm/s at 4 Hz increasing to20 mm/s at 15 Hz

    20 mm/s at 15 Hz increasing to50 mm/s at 50 Hz and above

    Damage Description

    CosmeticThe formation of hairline cracks2 on drywall surfaces, or the growth of existing

    cracks in plaster or drywall surfaces; in addition, the formation of hairline cracks inmortar joints of brick/concrete block construction.

    MinorThe formation of large cracks or loosening and falling of plaster or drywall surfaces,

    or cracks through bricks/concrete blocks.

    MajorDamage to structural elements of the building, cracks in support columns, loosening

    of joints, splaying of masonry cracks, etc

  • 8/13/2019 File 8 Noise Acoustic Report

    7/30

  • 8/13/2019 File 8 Noise Acoustic Report

    8/30

    Noise Assessment Report

    William Davis Ltd 5 A079137

    Proposed Residential Development December 2012

    3.0 Assessment Methodology

    3.1 Noise Modelling Methodology

    Three dimensional noise modelling has been undertaken based on the monitoring data to predict LAeqand

    LAmaxnoise levels at a large number of locations both horizontally and vertically. CADNA noise modelling

    software has been used (as shown in Figure 3.1). This model is based on the Department of Transport

    Calculation of Road Traffic Noise (CRTN) and ISO 9613 noise propagation methodology and allows for

    detailed prediction of noise levels to be undertaken for large numbers of receptor points and different noise

    emission scenarios both horizontally and vertically.

    Figure 3.1 CADNA Noise Model

  • 8/13/2019 File 8 Noise Acoustic Report

    9/30

    Noise Assessment Report

    William Davis Ltd 6 A079137

    Proposed Residential Development December 2012

    The modelling software calculates noise levels based on the emission parameters and spatial settings that

    are entered. Input data, assumptions and model settings as given in the table below have been used.

    Table 3.1 Modelling Parameters Sources and Assumptions

    Parameter Source Details

    Horizontal distances around site Ordnance Survey Ordnance Survey

    Ground levels around site Ordnance Survey Ordnance Survey

    Ground levels other areasSite Observations and OrdnanceSurvey

    OS 1:25,000 contours and OS 1:10,000 spotheights.

    Traffic data, main surrounding roads WYGETraffic flows for local roads based on WYGEobservations and experience.

    Traffic data local roads WYGETraffic flows for local roads based on WYGEobservations and experience.

    Building heights around site WYGE Observations8 m height for two storey residential properties,and 4 m for Bungalows

    Barrier heights WYGE ObservationsAll existing barriers at 1.0 m with the exceptionof hedges and trees which are assumed to offerno noise protection.

    Receptor positions WYGE

    1 m from faade, height of 1.5 m for groundfloor, 4 m for first floor properties with groundfloor or bungalow dormer windows. 7 m fordormer windows on two storey properties. 1.5m height for model grid and monitoring

    locations for validation.

    Reflections WYGEFirst order reflections have been applied basedon mirror image sources

    Absorbent Ground CADNAFrequency dependant ground absorption hasbeen applied based on values specified in VDI2714/16 clause 6.3.

    Faade Correction CADNAFaade corrections have been incorporated intothe modelling

    Gradient CADNAGradient for each road has been calculatedfrom the height information using the calcslope of roads tool

    It is acknowledged that a number of these assumptions will affect the overall noise levels presented in this

    report. However it should be noted that certain assumptions made, as identified above, are worst case.

  • 8/13/2019 File 8 Noise Acoustic Report

    10/30

    Noise Assessment Report

    William Davis Ltd 7 A079137

    Proposed Residential Development December 2012

    3.2 Model Input Data

    3.2.1 Traffic Noise Data

    All roads expected to make a significant contribution, have been included within this assessment. Noise

    emissions from existing traffic flows have been derived from verification of the measured noise levels, along

    with observations made during the site survey and/or WYG Environment (WYGE) experience of similar road

    systems. Estimates of the vehicle speeds have been made based upon the speed restrictions currently in

    force in the area.

    3.2.2 Model Verification

    The model was verified by modelling the monitoring locations for the existing scenario. A daytime and

    night time LAeq and night time LAmaxscenario has been verified. The comparison between the monitoring and

    modelling results are shown in the tables below.

    Table 3.2 Modelled vs. Monitored Results LAeq; daytime 07:00 23:00

    Location Monitored LAeq Modelled LAeqDifference between

    Monitored and ModelledResults

    LT1 64.6 64.6 0.0

    LT2 60.9 60.9 0.0

    LT3 48.7 47.2 -1.5

    All values are sound pressure levels in dB re: 2x 10-5 Pa

    Table 3.3 Modelled vs. Monitored Results LAeq; night-time 23:00 07:00

    Location Monitored LAeq Modelled LAeqDifference between

    Monitored and ModelledResults

    LT1 54.6 54.6 0.0

    LT2 53.1 53.1 0.0

    LT3 42.0 39.6 -2.4

    All values are sound pressure levels in dB re: 2x 10-5 Pa

    Table 3.4 Modelled vs. Monitored Results LAmax; night-time 23:00 07:00

    Location Monitored LAmax Modelled LAmaxDifference between

    Monitored and ModelledResults

    LT1 86.0 85.5 -0.5

    LT2 91.2 91.3 0.1

    LT3 75.1 74.4 -0.7

    All values are sound pressure levels in dB re: 2x 10-5 Pa

    The verification points show a divergence between monitored and modelled results of no more than 3 dB.

    (15 minute night-time measurement), all models are assumed to be suitably verified.

  • 8/13/2019 File 8 Noise Acoustic Report

    11/30

    Noise Assessment Report

    William Davis Ltd 8 A079137

    Proposed Residential Development December 2012

    3.2.3 Sensitive Receptors

    Existing noise levels have been assessed at properties to the north, centre and south of the site with

    respect to direct noise from the existing ambient noise climate surrounding the site. An indicative site

    layout showing the locations of the proposed receptors is shown of SK02 of Appendix B.

    Table 3.5 Residential Receptor Locations

    Ref. Description Closest SourceApproximateDistance ToSource (m)

    Height (m)

    R1 Property to the north of site (western faade) Shelford Road 20.13 4.0

    R2 Property to the north of site (western faade) Shelford Road 17.19 4.0

    R3 Property to the north west of site (western faade) Shelford Road 23.19 4.0

    R4 Property to the north west of site (northern faade) Shelford Road 79.40 4.0

    R5 Property to the north west of site (western faade) Shelford Road 151.23 4.0

    R6 Property to the west of site (northern faade) Shelford Road 199.03 4.0

    R7 Property to the west of site (western faade) Clumber Drive 44.33 4.0

    R8 Property to the west of site (western faade) Clumber Drive 46.98 4.0

    R9 Property to the south west of site (western faade) Clumber Drive 45.70 4.0

    R10 Property to south west of site (southern faade) Clumber Drive 51.65 4.0

    R11 Property to southern of site (southern faade) Railway 50.30 4.0

    R12Property to the south east of the site (southernfaade)

    Railway 28.69 4.0

    R13 Property to the south east of site (eastern faade) Railway 67.78 4.0

    R14 Property to the east of site (eastern faade) Railway 168.90 4.0

    R15 Property to the east of site (eastern faade) Railway 256.88 4.0

    R16 Property to the east of site (eastern faade) Shelford Road 354.90 4.0

    R17 Property to the east of site (eastern faade) Shelford Road 276.47 4.0

    R18 Property to the north east of site (eastern faade) Shelford Road 149.90 4.0

    R19 Property to the north east of site (northern faade) Shelford Road 49.24 4.0

    Table 3.6 Garden Receptor Locations

    Co-ordinatesRef. Description

    X Y Height (m)

    G1 Plot to north of site 465529.5 340262.2 1.5

    G2 Plot to north west of site 465415.0 340140.2 1.5

    G3 Plot to north of site 465647.8 340094.8 1.5

    G4 Plot to north centre of site 465649.7 340044.3 1.5

    G5 Plot to centre of site 465621.9 339994.9 1.5

    G6 Plot to west of site 465495.7 339906.2 1.5

    G7 Plot to east of site 465789.7 339910.3 1.5

    G8 Plot to south west of site 465629.4 339752.4 1.5

    G9 Plot to south west of site 465565.2 339745.5 1.5

  • 8/13/2019 File 8 Noise Acoustic Report

    12/30

    Noise Assessment Report

    William Davis Ltd 9 A079137

    Proposed Residential Development December 2012

    4.0 Site Survey

    4.1 Noise Survey

    4.1.1 Noise Survey Methodology

    A monitoring survey was undertaken to characterise baseline ambient noise levels currently experienced on

    the site and to establish the relative local background and traffic noise levels.

    Equipment used during the survey included:

    B&K 2260 Environmental Noise Analyser (WYG1) s/n 2361273

    B&K 4231 Calibrator s/n 2176211Rion NL-32 Environmental Noise Analyser (WYG12) s/n 213442

    Rion NL-52 Environmental Noise Analyser (WYG13) s/n 620858

    Rion NL-52 Environmental Noise Analyser (WYG14) s/n 610212

    Norsonic 1251 Sound Calibrator s/n 31043

    The measurement equipment was checked against the appropriate calibrator at the beginning and end of

    the measurements, in accordance with recommended practice and no drift was observed. The accuracy of

    the calibrators can be traced to National Physical Laboratory Standards, calibration certificates for which are

    available on request.

    A baseline monitoring survey was undertaken at 7 locations (as specified in the following table and shown

    in SK01 of Appendix B) from Friday 19thOctober 2012 to Tuesday 23rdOctober 2012. Attended short term

    measurements were undertaken at four locations during the day, evening, peak and night-time periods with

    three additional locations being measured unattended over a 90 hour period. The raw data collected from

    the long term monitoring is available upon request.

    Measurements were taken in general accordance with BS 7445-1:2003 The Description and Measurement

    of Environmental Noise: Guide to quantities and procedures. Weather conditions during the survey period

    were observed as being dry with scattered showers. Anemometer readings confirmed that wind speeds

    were less than 5 ms-1at all times during the survey.

    Table 4.1 Noise Monitoring Locations

    Grid ReferenceRef Description

    X Y

    LT1 North eastern corner of site 465550.91 340355.96

    LT2 South eastern corner of the Site 465741.29 339713.83

    LT3 North western site boundary, to south west of Shelford Road Farm. 465457.12 340004.34

    ST1 Pavement of Shelford road, south of the Crown Cottages 465545.28 340368.95

    ST2 Corner outside 125 Shelford Road 465334.70 340133.21

    ST3 Corner of Haddon way / Clumber drive 465441.79 339812.49

    ST4 Pavement outside 37 Hudson Way 465815.05 339639.62

  • 8/13/2019 File 8 Noise Acoustic Report

    13/30

    Noise Assessment Report

    William Davis Ltd 10 A079137

    Proposed Residential Development December 2012

    4.1.2 Noise Survey Results

    Existing ambient noise levels around the site are dominated by traffic on Shelford Road to the north of the

    site, and the Nottingham to Skegness railway line to the south of the site.

    Ambient and background noise levels are usually described using the LAeqindex (a form of energy average)

    and the LA90 index (i.e. the level exceeded for 90% of the measurement period) respectively. Road traffic

    noise is generally described using the LA10 index (i.e. the level exceeded for 10% of the measurement

    period).

    The results of the statistical measurements and frequency measurements conducted during the survey are

    summarised in the following table. All values are sound pressure levels in dB (re: 2 x 10-5Pa).

    Table 4.2 Results of Baseline Noise Monitoring Survey (Average Levels)

    PeriodDuration

    (T)Monitoring Date and Times Location

    LAeq,T(dB)

    LAmax,T(dB)

    LAmin,T(dB)

    LA10,T(dB)

    LA90,T(dB)

    Day07:00 - 23:00

    77 hours18/10/2012 - 23/10/2012

    07:00 - 23:0064.6 96.5 25.1 66.3 43.6

    Night23:00 07:00

    40 hours18/10/2012 - 23/10/2012

    23:00 - 07:00

    LT1

    54.6 87.8 22.0 45.0 34.4

    Day

    07:00 - 23:00

    77 hours18/10/2012 - 23/10/2012

    07:00 - 23:00

    60.9 100.1 41.5 52.4 48.8

    Night23:00 07:00

    40 hours18/10/2012 - 23/10/2012

    23:00 - 07:00

    LT2

    53.1 91.2 40.7 49.4 46.1

    Day07:00 - 23:00

    77 hours18/10/2012 - 23/10/2012

    07:00 - 23:0048.7 89.4 27.4 47.7 42.1

    Night23:00 07:00

    40 hours18/10/2012 - 23/10/2012

    23:00 - 07:00

    LT3

    41.4 75.1 23.2 41.9 35.2

    15 Mins 22/10/2012 11:09 ST1 69.8 88.7 37.5 73.7 42.8

    15 Mins 22/10/2012 11:30 ST2 47.5 60.6 36.0 50.9 40.4

    15 Mins 22/10/2012 12:21 ST3 51.0 73.9 37.3 50.5 40.2

    Day07:00 - 19:00

    15 Mins 22/10/2012 13:11 ST4 50.9 71.2 42.4 51.1 45.7

    15 Mins 22/10/2012 19:35 ST1 67.0 85.5 30.3 67.8 33.8

    15 Mins 22/10/2012 21:34 ST2 60.1 82.1 29.5 59.0 33.1

    15 Mins 22/10/2012 21:13 ST3 36.7 52.5 29.5 39.0 32.5

    Evening19:00 - 23:00

    15 Mins 22/10/2012 20:22 ST4 47.8 69.6 33.1 49.1 39.3

    15 Mins 22/10/2012 23:00 ST1 62.1 87.7 24.2 45.3 25.7

    15 Mins 22/10/2012 23:18 ST2 57.8 80.6 28.5 54.1 31.5

    15 Mins 22/10/2012 23:35 ST3 41.6 68.6 28.6 38.5 31.5

    Night23:00 - 07:00

    15 Mins 22/10/2012 23:56 ST4 42.5 65.4 25.8 45.3 33.3

    All values are sound pressure levels in dB re: 2x 10-5 Pa

  • 8/13/2019 File 8 Noise Acoustic Report

    14/30

    Noise Assessment Report

    William Davis Ltd 11 A079137

    Proposed Residential Development December 2012

    4.2 Vibration Survey

    Existing vibration levels around the site are dominated by rail traffic using the Nottingham to Skegnessrailway line to south of the site.

    4.2.1 Vibration Survey Methodology

    Measurements were obtained using a Vibrock Digital Seismograph Type V901 fitted with a ground vibration

    transducer in continuity with a ground spike. The instrument measured Resultant, Displacement,

    Acceleration and Peak Particle Velocity (PPV) at a scanning duration of 30 seconds. Attended measurements

    were used to determine background levels and individual train passing events.

    The vibration measurements were carried out at the following locations which are shown on SK01 of

    Appendix B.

    Table 4.3 Vibration Monitoring Locations

    Grid ReferenceRef. Description

    X Y

    V1 Adjacent to railway line to the south west of the site 465691.79 339672.85

    V2 Adjacent to railway line to the south east of the site 465817.24 339708.31

    4.2.2 Vibration Survey Results

    The following table shows the maximum Resultant, Displacement, Acceleration and Peak Particle Velocity

    (PPV) measured at each monitoring location during normal conditions (background) and train passing

    events.

    Table 4.4 Vibration Measurement Results

    LocationMax Resultant

    (mm/s)Max Displacement

    (mm)Max Acceleration (g)

    MaxPPV (mm/s)

    V1 - Background 0.200 0.001 0.17 0.175

    V1 Train Passing 1 0.225 0.002 0.17 0.200

    V1 Train Passing 2 0.550 0.002 0.36 0.225

    V1 Train Passing 3 0.225 0.001 0.27 0.200

    V1 Train Passing 4 0.225 0.001 0.20 0.200

    V2 Background 0.200 0.001 0.17 0.175

    V2 Train Passing 1 0.200 0.001 0.17 0.200

    V2 Train Passing 2 0.250 0.002 0.30 0.250

    V2 Train Passing 3 0.200 0.001 0.22 0.300

    V2 Train Passing 4 0.225 0.001 0.27 0.250

  • 8/13/2019 File 8 Noise Acoustic Report

    15/30

    Noise Assessment Report

    William Davis Ltd 12 A079137

    Proposed Residential Development December 2012

    5.0Assessment of Key Effects

    5.1 Noise Intrusion Assessment

    Internal noise levels within potential dwellings have been assessed both with windows open, where a

    reduction from a partially open window of 15 dB has been used, and with windows closed where an

    assumption of glazing with specification Rw30 dB (e.g 6/12/6mm double glazing or equivalent) has been

    used.

    The results presented in tables 5.1 5.3 below show the predicted noise intrusion levels at properties to

    the north, centre and south of the site. The recommended WHO/BS 8233 internal noise levels are

    generally met across the site during the daytime and night-time, assuming a windows-closed scenario.In order to achieve the recommended internal noise criteria, a range of mitigation measures are outlined in

    Section 5.3 of this report; SK06 in Appendix B shows the glazing and ventilation requirements for bedrooms

    and living rooms of the proposed development.

    Table 5.1 Daytime Noise Intrusion Levels LAeq 16 hour

    LocationExternal LAeq

    at 1m from facadeInternal LAeq with

    windows openInternal LAeq withwindows closed

    CriteriaInternal LAeq

    R1 57.6 42.6 27.6 30 - 40

    R2 57.4 42.4 27.4 30 - 40

    R3 55.2 40.2 25.2 30 - 40

    R4 48.8 33.8 18.8 30 - 40

    R5 40.9 25.9 10.9 30 - 40

    R6 39.2 24.2 9.2 30 - 40

    R7 37.4 22.4 7.4 30 - 40

    R8 37.8 22.8 7.8 30 - 40

    R9 41.0 26.0 11.0 30 - 40

    R10 47.9 32.9 17.9 30 - 40

    R11 52.8 37.8 22.8 30 - 40

    R12 55.6 40.6 25.6 30 - 40

    R13 50.9 35.9 20.9 30 - 40

    R14 47.9 32.9 17.9 30 - 40

    R15 46.4 31.4 16.4 30 - 40

    R16 46.1 31.1 16.1 30 - 40

    R17 45.4 30.4 15.4 30 - 40

    R18 48.8 33.8 18.8 30 - 40

    R19 55.2 40.2 25.2 30 - 40

    All values are sound pressure levels in dB re: 2x 10-5

    Pa.

  • 8/13/2019 File 8 Noise Acoustic Report

    16/30

    Noise Assessment Report

    William Davis Ltd 13 A079137

    Proposed Residential Development December 2012

    Table 5.2 Night-time Noise Intrusion Levels LAeq 8 hour

    LocationExternal LAeq

    at 1m from facadeInternal LAeq with

    windows openInternal LAeq withwindows closed

    CriteriaInternal LAeq

    R1 50.2 35.2 20.2 30

    R2 50.6 35.6 20.6 30

    R3 48.5 33.5 18.5 30

    R4 42.1 27.1 12.1 30

    R5 35.2 20.2 5.2 30

    R6 33.0 18.0 3.0 30

    R7 37.0 22.0 7.0 30

    R8 35.4 20.4 5.4 30

    R9 36.6 21.6 6.6 30

    R10 44.5 29.5 14.5 30

    R11 47.9 32.9 17.9 30

    R12 50.7 35.7 20.7 30

    R13 44.2 29.2 14.2 30

    R14 40.9 25.9 10.9 30

    R15 39.4 24.4 9.4 30

    R16 39.1 24.1 9.1 30

    R17 38.6 23.6 8.6 30

    R18 41.5 26.5 11.5 30

    R19 46.7 31.7 16.7 30

    All values are sound pressure levels in dB re: 2x 10-5

    Pa.

  • 8/13/2019 File 8 Noise Acoustic Report

    17/30

    Noise Assessment Report

    William Davis Ltd 14 A079137

    Proposed Residential Development December 2012

    Table 5.3 Night-time Noise Intrusion Levels LAmax

    LocationExternal LAmax

    at 1m from facadeInternal LAmax with

    windows openInternal LAmax with

    windows closedCriteria

    Internal LAmax

    R1 81.1 66.1 51.1 45

    R2 81.6 66.6 51.6 45

    R3 79.5 64.5 49.5 45

    R4 72.9 57.9 42.9 45

    R5 66.3 51.3 36.3 45

    R6 63.6 48.6 33.6 45

    R7 63.4 48.4 33.4 45

    R8 64.0 49.0 34.0 45

    R9 69.5 54.5 39.5 45

    R10 77.9 62.9 47.9 45

    R11 83.5 68.5 53.5 45

    R12 86.7 71.7 56.7 45

    R13 71.9 56.9 41.9 45

    R14 66.7 51.7 36.7 45

    R15 66.0 51.0 36.0 45

    R16 67.2 52.2 37.2 45

    R17 67.7 52.7 37.7 45

    R18 71.5 56.5 41.5 45

    R19 77.5 62.5 47.5 45

    All values are sound pressure levels in dB re: 2x 10-5 Pa.

  • 8/13/2019 File 8 Noise Acoustic Report

    18/30

    Noise Assessment Report

    William Davis Ltd 15 A079137

    Proposed Residential Development December 2012

    5.1.1 Garden Noise Levels

    Daytime noise levels in gardens and private external spaces of the proposed development have been

    assessed in the table below. The location of the garden receptor locations are shown on SK03 inAppendix B.

    Table 5.4 Garden Noise Levels LAeq,16hr

    RefExternal LAeq,16hr

    DaytimeBS 8233 Upper Limit

    Criteria LAeq

    G1 51.5 55.0

    G2 48.8 55.0

    G3 43.3 55.0

    G4 39.5 55.0

    G5 40.5 55.0

    G6 42.5 55.0

    G7 47.6 55.0

    G8 51.0 55.0

    G9 49.5 55.0

    All values are sound pressure levels in dB re: 2x 10-5 Pa.

    The results in the table above show that daytime LAeq noise levels within gardens are predicted to be

    within the BS 8233 upper limit (55 dB).

    5.2 Vibration Assessment

    5.2.1 Potential Building Damage

    The following table shows the maximum Peak Particle Velocity measured at the site for comparison with the

    BS 7385 criteria.

    Table 5.5 Vibration Assessment Building Damage

    LocationAverage Resultant

    (mm/s)Max

    Resultant (mm/s)Damage Criteria Within Criteria

    Foundations ofProposed Dwellings

    0.263 0.550 15.0 Yes

    The results in the table above show that the peak particle velocity (PPV) measured at a location

    representative of the foundations of the proposed development is typically 2.0 mm/s and up to a maximum

    of 3 mm/s. This is a positive indication that there is unlikely to be any building damage associated with

    vibration from the adjacent highway.

  • 8/13/2019 File 8 Noise Acoustic Report

    19/30

  • 8/13/2019 File 8 Noise Acoustic Report

    20/30

    Noise Assessment Report

    William Davis Ltd 17 A079137

    Proposed Residential Development December 2012

    6.0 Noise Mitigation

    6.1 Glazing and Ventilation Strategy

    The ventilation strategy provided in SK06 has been designed to achieve internal daytime LAeqof 35 dB, an

    internal night-time LAeq of 30 dB and an internal night-time LAmax of 45 dB in habitable rooms of the

    proposed development. It also highlights which areas would (in the absence of any alternative mitigation

    such as noise barriers) require enhanced glazing, or an alternative means of ventilation in order to meet

    both ventilation and internal ambient noise criteria. Alternative ventilation can be provided in several ways

    from acoustic trickle vents (which need to have a minimum sound reduction equal to or greater than the

    glazing), other passive ventilation systems or mechanical ventilations systems.

    It is recommended that any potential dwellings to the north of the site, within approximately 60 metres of

    Shelford Road, and to the south of the site, within approximately 100 metres of the railway line be taken

    into account in the site layout and design process. To reduce the impact of noise, enhanced glazing, the

    favourable orientation of dwellings, suitably located windows and gardens and effective internal layouts

    should be considered.

  • 8/13/2019 File 8 Noise Acoustic Report

    21/30

    Noise Assessment Report

    William Davis Ltd 18 A079137

    Proposed Residential Development December 2012

    7.0 Conclusions

    Noise and Vibration surveys have been undertaken in connection with the proposed new housing

    development on Shelford Road, Radcliffe-on-Trent.

    Noise

    NPPF 123 A & B

    In considering the NPPF test in section 123, points A & B. The proposed development is not expected to

    have an adverse impact on health or quality of life. Similarly, with regard to NPPF (123) point B, it is

    considered that all adverse impacts on health and quality of life (relating to noise) are mitigated by the use

    of appropriate mitigation.

    NPPF 123 C & D

    Given that nearby the site is surrounded by similarly residential properties to the north, west and the south,

    it is not considered that any existing businesses wanting to develop would be particularly restricted by the

    introduction of the new sensitive use of the proposed development.

    The development is situated in a CPRE Zone 4 area of tranquillity (Zone 1 being the least tranquil and Zone

    10 being the most tranquil), as such is not considered to be an area of Tranquillity.

    Glazing and Ventilation Strategy

    The recommended WHO/BS 8233 internal noise levels are generally met across the site during the daytime

    and night-time, assuming a windows-closed scenario. A glazing and ventilation strategy has been provided

    which achieves both ventilation and internal ambient noise level requirements of LAeq daytime35 dB, LAeq night-

    time of 30 dB and LAmax night-time of 45 dB in all residential bedroom and living spaces of the proposed

    development. The suggested glazing specifications are understood to be achievable. Standard double

    glazing is sufficient across the majority of the site in order to achieve the target internal noise levels whenwindows. Dwellings within approximately 60 metres of Shelford Road to the north, and 100 metres of the

    railway to the south would require enhanced glazing in order to meet internal target noise levels. All Garden

    receptors are below BS 8233 Upper Limit Criteria levels for LAeq.

    Vibration

    An assessment of vibration levels has shown that maximum peak particle velocity (PPV) measured at a

    location representative of the foundations of the proposed development is 0.550 mm/s. This is a positive

    indication that there is unlikely to be any building damage associated with vibration from the existing use of

    the adjacent railway. Calculated eVDV levels at this location are 0.18 ms-1.75 indicating that there is a low

    risk of adverse comment.

  • 8/13/2019 File 8 Noise Acoustic Report

    22/30

    Noise Assessment Report

    William Davis Ltd A079137

    Proposed Residential Development December 2012

    Appendices

  • 8/13/2019 File 8 Noise Acoustic Report

    23/30

    Noise Assessment Report

    William Davis Ltd A079137

    Proposed Residential Development December 2012

    Appendix A Acoustic Terminology and Abbreviations

    Acoustic Terminology

    dB Sound levels from any source can be measured in frequency bands in order to provide detailed

    information about the spectral content of the noise, i.e. whether it is high-pitched, low-pitched, or

    with no distinct tonal character. These measurements are usually undertaken in octave or third

    octave frequency bands. If these values are summed logarithmically, a single dB figure is

    obtained. This is usually not very helpful as it simply describes the total amount of acoustic

    energy measured and does not take any account of the ears ability to hear certain frequencies

    more readily than others.

    dB(A) Instead, the dBA figure is used, as this is found to relate better to the loudness of the sound

    heard. The dBA figure is obtained by subtracting an appropriate correction, which represents the

    variation in the ears ability to hear different frequencies, from the individual octave or third

    octave band values, before summing them logarithmically. As a result the single dBA value

    provides a good representation of how loud a sound is.

    LAeq Since almost all sounds vary or fluctuate with time it is helpful, instead of having an instantaneous

    value to describe the noise event, to have an average of the total acoustic energy experienced

    over its duration. The LAeq, 07:00 23:00for example, describes the equivalent continuous noise level

    over the 12 hour period between 7 am and 11 pm. During this time period the LpA at any

    particular time is likely to have been either greater or lower that the LAeq, 07:00 23:00.

    LAmin The LAmin is the quietest instantaneous noise level. This is usually the quietest 125 milliseconds

    measured during any given period of time.

    LAmax The LAmax is the loudest instantaneous noise level. This is usually the loudest 125 milliseconds

    measured during any given period of time.

    Ln Another method of describing, with a single value, a noise level which varies over a given time

    period is, instead of considering the average amount of acoustic energy, to consider the length of

    time for which a particular noise level is exceeded. If a level of x dBA is exceeded for say 6

    minutes within one hour, then that level can be described as being exceeded for 10% of the totalmeasurement period. This is denoted as the LA10, 1 hr= x dB.

    The LA10index is often used in the description of road traffic noise, whilst the LA90, the noise level

    exceeded for 90% of the measurement period, is the usual descriptor for underlying background

    noise. LA1and LAmaxare common descriptors of construction noise.

    Rw The weighted sound reduction index determined using the above measurement procedure, but

    weighted in accordance with the procedures set down in BS EN ISO 717-1. Partitioning and

    building board manufacturers commonly use this index to describe the inherent sound insulation

    performance of their products.

  • 8/13/2019 File 8 Noise Acoustic Report

    24/30

    Noise Assessment Report

    William Davis Ltd A079137

    Proposed Residential Development December 2012

    Abbreviations

    CADNA Computer Aided Noise Abatement

    DMRB Design Manual for Roads and Bridges

    HGV Heavy Goods Vehicle

    PPG24 Planning Policy Guidance

    UDP Unitary Development Plan

    UKAS United Kingdom Accreditation Service

    WYGE WYG Environment

  • 8/13/2019 File 8 Noise Acoustic Report

    25/30

    Noise Assessment Report

    William Davis Ltd A079137

    Proposed Residential Development December 2012

    Appendix B Sketches

    SK01 Noise Monitoring Locations

    SK02 Indicative Site Layout and Receptor Locations

    SK03 Daytime LAeq,16hr

    SK04 Night-time LAeq,8hr

    SK05 Glazing and Ventilation Strategy

  • 8/13/2019 File 8 Noise Acoustic Report

    26/30

    She

    lford

    Ro

    ad

    LT 2

    LT 3

    ST1

    ST2

    ST3

    ST4

    V2

    V1

    LT 1

    A52

    Clum

    berD

    rive

    465350

    465350

    465400

    465400

    465450

    465450

    465500

    465500

    465550

    465550

    465600

    465600

    465650

    465650

    465700

    465700

    465750

    465750

    465800

    465800

    465850

    465850

    465900

    465900

    339500

    339550

    339600

    339650

    339700

    339750

    339800

    339850

    339900

    339950

    340000

    340050

    340100

    340150

    3

    40200

    340250

    340300

    340350

    340

    400

    340450

    340500

    340550

    Client:

    William Davis Ltd.

    Project:

    Shelford Road, Radcliffe

    Project Number:

    A079137

    Drawing Title / Scenario:

    Noise and VibrationMonitoring Locations

    Drawing Number:

    SK01

    Site Boundary:

    Scale : Not to scale

    WYGE Leicester 03.12.12

    This map is based upon Ordnance Surveymaterial reproducedbyWYG on behalf of Her Majesty's StationeryOffice, Crown Copyright. Unauthorised reproduction infringesCrown copyright and maylead to civil proceedings.

    Licence Number AL 553611

    Executive ParkAvalon WayAnsteyLeicestershireLE7 7GRTel 0116 234 8000

    WYG Environment

  • 8/13/2019 File 8 Noise Acoustic Report

    27/30

    She

    lford

    Ro

    ad

    A52

    ClumberD

    rive

    R1

    R2

    R3R4

    R5

    R6

    R7

    R8

    R9

    R10R11

    R12

    R13

    R14

    R15

    R16

    R17

    R18

    R19

    A52

    G1

    G2

    G3

    G4

    G5

    G6 G7

    G8G9

    465350

    465350

    465400

    465400

    465450

    465450

    465500

    465500

    465550

    465550

    465600

    465600

    465650

    465650

    465700

    465700

    465750

    465750

    465800

    465800

    465850

    465850

    465900

    465900

    339500

    339550

    339600

    339650

    339700

    339750

    339800

    339850

    339900

    339950

    340000

    340050

    340100

    340150

    3

    40200

    340250

    340300

    340350

    340

    400

    340450

    340500

    340550

    Client:

    William Davis Ltd.

    Project:

    Shelford Road, Radcliffe

    Project Number:

    A079137

    Drawing Title / Scenario:

    Proposed Layout& Receptor Locations

    Drawing Number:

    SK02

    Key:

    Site Boundary:

    Scale : Not to scale

    WYGE Leicester 03.12.12

    This map is based upon Ordnance Surveymaterial reproducedbyWYG on behalf of Her Majesty's StationeryOffice, Crown Copyright. Unauthorised reproduction infringesCrown copyright and maylead to civil proceedings.

    Licence Number AL 553611

    Executive ParkAvalon WayAnsteyLeicestershireLE7 7GRTel 0116 234 8000

    WYG Environment

  • 8/13/2019 File 8 Noise Acoustic Report

    28/30465350

    465350

    465400

    465400

    465450

    465450

    465500

    465500

    465550

    465550

    465600

    465600

    465650

    465650

    465700

    465700

    465750

    465750

    465800

    465800

    465850

    465850

    465900

    465900

    339500

    339550

    339600

    339650

    339700

    339750

    339800

    339850

    339900

    339950

    340000

    340050

    340100

    340150

    3

    40200

    340250

    340300

    340350

    340

    400

    340450

    340500

    340550

    Client:

    William Davis Ltd

    Project:

    Shelford Road, Radcliffe

    Project Number:

    A079137

    Drawing Title / Scenario:

    Existing DaytimeLAeq,16hr Noise Levels

    Drawing Number:

    SK03

    Key:

    0.0 - 55.0 dB55.0 - 63.0 dB63.0 - 72.0 dB72.0 - 90.0 dB

    Site Boundary:

    Scale : Not to scale

    WYGE Leicester 03.12.12

    This map is based upon Ordnance Surveymaterial reproducedbyWYG on behalf of Her Majesty's StationeryOffice, Crown Copyright. Unauthorised reproduction infringesCrown copyright and maylead to civil proceedings.

    Licence Number AL 553611

    Executive ParkAvalon WayAnsteyLeicestershireLE7 7GRTel 0116 234 8000

    WYG Environment

  • 8/13/2019 File 8 Noise Acoustic Report

    29/30465350

    465350

    465400

    465400

    465450

    465450

    465500

    465500

    465550

    465550

    465600

    465600

    465650

    465650

    465700

    465700

    465750

    465750

    465800

    465800

    465850

    465850

    465900

    465900

    339500

    339550

    339600

    339650

    339700

    339750

    339800

    339850

    339900

    339950

    340000

    340050

    340100

    340150

    3

    40200

    340250

    340300

    340350

    340

    400

    340450

    340500

    340550

    Client:

    William Davis Ltd

    Project:

    Shelford Road, Radcliffe

    Project Number:

    A079137

    Drawing Title / Scenario:

    Existing NightLAeq,16hr Noise Levels

    Drawing Number:

    SK04

    Key:

    0.0 - 45 dB45.0 - 57.0 dB57.0 - 66.0 dB66.0 - 90.0 dB

    Site Boundary:

    Scale : Not to scale

    WYGE Leicester 03.12.12

    This map is based upon Ordnance Surveymaterial reproducedbyWYG on behalf of Her Majesty's StationeryOffice, Crown Copyright. Unauthorised reproduction infringesCrown copyright and maylead to civil proceedings.

    Licence Number AL 553611

    Executive ParkAvalon WayAnsteyLeicestershireLE7 7GRTel 0116 234 8000

    WYG Environment

  • 8/13/2019 File 8 Noise Acoustic Report

    30/30

    Clum

    berD

    rive

    She

    lford

    Road

    465350 465400 465450 465500 465550 465600 465650 465700 465750 465800 465850 465900

    39550

    339600

    339650

    339700

    339750

    339800

    339850

    339900

    339950

    340000

    340050

    340100

    340150

    340200

    340250

    340300

    340350

    340

    400

    340450

    340500

    340550

    Client:

    William Davis Ltd

    Project:

    Shelford Road, Radcliffe

    Project Number:

    A079137

    Drawing Title / Scenario:

    Glazing and VentilationStrategy

    Drawing Number:

    SK05

    Key:

    Site Boundary:

    Alternative VentilationRequired:

    Enhanced Glazing andAlternative VentilationRequired:

    WYGE Leicester 03.12.12

    This map is based upon Ordnance Surveymaterial reproducedbyWYG on behalf of Her Majesty's StationeryOffice, Crown Copyright. Unauthorised reproduction infringesCrown copyright and maylead to civil proceedings.

    Licence Number AL 553611