fire door control solutions · cao en mh tenest 5 es emany tel 021-2-0 a 021-2-0 -mal nfodtatode...

78
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Fire Door Control Solutions Contents Page 07.001.00 Subject to change without notice. Errors do not constitute claims for compensation for damages. Bracket for Magnets, Hand Switch, HLS Bolting, Door Sequence Selectors Electromagnets (Bar Magnets are to be found in chapter Access Control Systems) Power Packs Control of Signals Ex-Proof Hold-Open Systems Fire Door Control Solutions Pages 07.019.00 - 07.030.00 Counter Plates Pages 07.063.00 - 07.068.00 Pages 07.069.00 - 07.078.00 Smoke Detectors Pages 07.003.00 - 07.018.00 Pages 07.031.00 - 07.062.00

Upload: others

Post on 03-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Fire Door Control Solutions Contents

Page 07.001.00

Sub jec t to change wi thou t no t i ce . E r ro r s do no t cons t i t u t e c la ims fo r compensa t ion fo r damages .

Bracket for Magnets,Hand Switch, HLS Bolting,Door Sequence Selectors

Electromagnets(Bar Magnets are to be found in chapter Access Control Systems)

Power PacksControl of SignalsEx-Proof Hold-Open Systems

Fire Door Control Solutions

Pages 07.019.00

- 07.030.00

Counter Plates Pages 07.063.00 - 07.068.00

Pages 07.069.00 - 07.078.00

Smoke Detectors Pages 07.003.00- 07.018.00

Pages 07.031.00 - 07.062.00

Page 2: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1015

Hold-Open Systems

Page 07.002.00

Components Power pack Page 07.019.00 et sqq.

Smoke detectors Page 07.003.00 et sqq.

Electromagnets Page 07.031.00 et sqq.

Counter plates Page 07.063.00 et sqq.

Hand switch Page 07.071.00 et sqq.

Door sequence selector Page 07.075.00 et sqq.

Components of a Hold-Open System

State 01/2015

Page 3: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Smoke Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.003.00

Smoke DetectorRM 2000

RM 2000 smoke detectors are used in hold-open systems for fire protection doors. They have been tested according to the strict regulations of the European standard EN 54 (part 7).

The smoke detector is operated by a po-tential free relay contact when the smoke density in a room exceeds a certain level, or when the integrated temperature sensor records a rise in temperature of more than 65 °C. The relay contact can be used to control electromagnets, door closers and door drive units, thus enabling fire doors to be closed automatically. The additionally included temperature sensor in the smoke detector reacts to a temperature higher than 65 °C.

The alarm signal can be passed on through two separate potential free relay contacts. Additionally, a clearly visibly red diode on the smoke detector indicates the alarm system's operational situation.

The RM 2000 smoke detector has been approved for the use on hold-open systems by the Institute for Building Engineering in Berlin/Germany. (Approval No. Z-6.5-1903)

Supply voltage 24 VDC (+15 %, -10 %)

Power consumption 35 mA

Alarm signal level smoke unit 0.2 dB/m

Alarm signal level temperature sensor 65 °C

Current-carrying capacity relay contact 24 V/1.0 A

IP rating IP 42

Technical Data

Page 4: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Smoke Detectors

Page 07.004.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032

6 1

4 3

5 2

6 1

4 3

5 2

6 1

4 3

5 2

220 VAC

24 VDC

101 80 54

54

ø 4,5

•Model 040502: "b"closes upon alarm

If you require several smoke detectors to be wired in series, you need to place bridges at terminals 1 and 2 of the last smoke detector (see wiring diagram below).

Insert the smoke detector into the socket so that the light diode coincides with the mark in the socket. Then turn it to the right for about 15 mm until it snaps in. It is now ready for operation.

The hand switch can be mounted any-where on the feed line which is connec-ted to the electromagnet or the doorclo-ser.

Advice: Protect the smoke detector from dust, colour mist and moisture to prevent malfunction.

When using the smoke detector on fire protection doors please follow the gui-delines for hold-open systems set by the Institute of Building Engineering in Berlin.

The smoke detector is not equipped with a mains transformer so a direct voltage of 24 V is required at terminals 1 and 6 (see wiring diagram below).

A potential-free relay contact (contact "a") is available at terminals 2 and 3 which opens in event of alarm or power failure. An additional relay contact (contact "b") is provided at terminals 4 and 5 .

Contact "a" always opens, but contact "b" can either open or close, depending on the smoke detector model.•Model 040500: "b"opens upon alarm

Dimensions

Order Information RM 2000 smoke detector with integrated thermo sensor part no. 040500as no. 040500, but relay contact "b" closes upon alarm part no. 040502Socle for RM 2000 smoke detector part no. 040540Bracket for wall mounting part no. 04057024 VDC/450 mA power pack part no. 04054524 VDC/800 mA power pack part no. 040552 Hand release switch part no. 040005

Please see our special catalogues for DICTAMAT door operators and bar magnets.

Power supply

Electromagnet door closer

Connection Example

Installation

Hand release switch

Page 5: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Heat Detector WM 2000

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1093 Page 07.005.00

Heat Detector WM 2000WM 2000 heat detectors are used in hold-open systems for fire-protection doors, except for doors in escape routes where they are not allowed according to the directives of the German Institute of Building and Construction Engineering. The WM 2000 has been tested according to the European standard EN 54 (part 5) and approved by the above mentioned institute for the use in hold-open systems (certificate no. Z-6.5-1903).

The heat detector is equipped with a static alarm signal level at 60 °C. An additional survey mechanism with rate-of-rise perfor-mance guarantees a prompt and reliable response to rapidly increasing temperature. This offers significantly higher safety during fast spread of fire.

In case of alarm a potential free relay con-tact in the heat detector opens and cuts the power supply of connected electromagnets, door closers and door operators etc. The fire protection door closes automatically.

The alarm signal can be passed on through two separate potential free relay contacts. Additionally, a clearly visible red diode on the heat detector indicates the alarm system's operational situation.

Supply voltage 24 VDC (+15 %, -10 %)

Power consumption approx. 15 mA

Static alarm signal level 60 °C

Current-carrying capacity relay contact 24 V/1.0 A

IP rating IP 42

Class A1R

Technical Data

Page 6: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Heat Detector WM 2000

Page 07.006.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1093

6 1

4 3

5 2

6 1

4 3

5 2

6 1

4 3

5 2

220 VAC

24 VDC

101 80 54

54

ø 4,5

• Model 040512: "b"closes upon alarm

If you require several heat detectors to be wired in series, you need to place bridges at terminals 1 and 2 of the last heat detector (see wiring diagram below).

Insert the heat detector into the socket so that the light diode coincides with the mark in the socket. Then turn it to the right for about 1.5 cm until it snaps in. It is now ready for operation.

The hand switch can be mounted anywhere on the feed line which is connected to the electromagnets or the door closer.

Advice: Protect the heat detector from dust, colour mist and moisture to prevent malfunction.

When using the heat detector on fire pro-tection doors please follow the guide lines for hold-open systems set by the Institute of Building Engineering in Berlin.

The heat detector is not equipped with a mains transformer so a direct voltage of 24 V is required at terminals 1 and 6 (see wiring diagram below).

A potential-free relay contact (contact "a") is available at terminals 2 and 3 which opens in event of alarm or power failure. An additional relay contact (contact "b") is provided at terminals 4 and 5 .

Contact "a" always opens, but contact "b" can either open or close, depending on the heat detector model.

• Model 040511: "b"opens upon alarm

Dimensions

Order Information

Power supply

Electromagnet door closer

Connection Example

Installation

Hand switch

Heat detector WM 2000, contakt "b" opens on alarm part no. 040511

Heat detector WM 2000, contakt "b" closes on alarm part no. 040512

Socle for WM 2000 heat detector part no. 040540

Bracket for installation on the wall part no. 040570

Power pack 24 VDC / 450 mA part no. 040545

Power pack 24 VDC / 800 mA part no. 040552

Hand release switch part no. 040005

Further Accessories

Page 7: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+ Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.007.00

• Voltage supply 9 to 33 VDC

• Power consumption 25 mA at 24 V; 62 mA on alarm

• Operating temperature (smoke detector) -20 °C to +60 °C (prevent icing)

• Alarm temperature (heat detector) +60 °C; other temperatures on request

• Breaking capacity of contacts 1 A at 24 VDC

• Contact voltage 50 V (max)

• Contact current 1 A (non inductive)

• IP rating IP 54 (heat detector), IP 43 (RM 3000+)

DICTATOR RM 3000+ smoke detectors and WM 3000+ heat detectors are used in hold-open systems to automatically close fire protection doors in the event of alarm.

RM 3000+ optical smoke detectors work on the principle of photo-electric detection of scattered light without using any radio-activity. To ensure maximum reliability, three consecutive sensed alarm signals are needed to trigger alarm and to switch off the power supply to the hold-open magnets on the door.

The WM 3000+ heat detector comprises a pair of matched heat detectors. One of them is exposed and therefore responds quickly to changes in air temperature, whereas the second one is insulated and responds more slowly. The relay cuts off the power supply when a certain temperature is reached or in the event of a rapid increase in the temperature of the surrounding air.

The detectors of this series comply with the EN 54 directives. They have been tested and are approved together with DICTATOR electromagnets (certificate Z-6.5-1903).

Technical Data

with RS 3000 Relay Base for Hold-Open Systems

RM 3000+ Smoke Detector

Page 8: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.008.00

50

ø100

L1 out L1 in

Spare

L2-R

72

4,5

51

50ø100

DimensionsAll detectors in the 3000+ range fit into the RS 3000 relay base. If a smoke detector should prove unsuitable for a particular application (e.g. it is exposed to smoke or dust) it can simply be replaced with a heat detector from the 3000+ range. However, please observe the relevant regulations concerning the use of heat detectors in hold-open systems.

To protect the sensing chamber from pollution during construction work, all detectors are delivered with a red protection cap which must be removed when the hold-open system is put into operation.

To facilitate the installation of detectors in suspended ceilings, a special base with a mounting bar (part no. 040842) is available.

1. Optical Smoke Detector

2. Heat Detector

The two slots in the base make it very easy to install as precise fixing holes in the ceiling are not required.

The wide interior diameter of the bases in the 3000 range allows for ease of access to wires and the five terminals. Wiring is possible both from the back or from the side (knock-outs in the base).

The detector is plugged in by turning it clockwise. An anti-theft feature is included. A missing detector means alarm.

3. RS 3000 Relay Base

Page 9: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+ Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.009.00

230 VAC

24 VDC L2 -R

L1in

spare

L1out

230 VAC

24 VDC L2 -R

L1in

spare

L1out

L2 -R

L1in

spare

L1out

L2 -R

L1in

spare

L1out

Wiring Diagram for Single Detector

Connect the required number of smoke detectors (see relevant regulations) to one of our power packs. When choosing the power pack please make sure that the total power consumption of all connected detectors does not exceed the supply current of the power pack. These smoke detectors consume maximum 62 mA in the event of alarm.

The hand switch needs to be placed in the wiring to the first detector. The electrical hold-open magnets are connected to the last detector in the detector circuit. This allows for a simple, linear wiring.

Power pack

If you need to install more than 3 detectors, simply place them within the circuit. The power pack and hand switch must always be connected to the first detector, and the hold-open magnets must be wired to the relay base of the last detector in the circuit. DICTATOR electromagnets and door operators are provided with the necessary spark extinction diode as standard. If the base relay switchable load is not sufficient, you need to connect an additional relay. We will be happy to provide the necessary information.

Hold-open systems must be tested every month and require annual maintainance.

IMPORTANT: after an alarm a RESET is necessary. This can be done either by pressing the hand switch or by removing the detector from the relay base and screwing it back again.

Wiring Diagram for Three Detectors

Hold-open devices:Electromagnets, door closers or door operators

RM 3000+ or WM 3000+with RS 3000 relay base

Power pack

RM 3000+ or WM 3000+ with RS 3000 relay base

Hold-open devices:Electromagnets,door closers or door operators

Hand s

witch

RM 3000+ Smoke Detector, WM 3000+ Heat Detector Easy to Connect, with Integrated Relay

Hand s

witch

Page 10: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.0010.00

RM 3000+ Smoke Detector, WM 3000+ Heat Detector

Installation and Function

DICTATOR smoke detectors and DICTATOR heat detectors are equipped with an integrated relay in the base. This switches off electromagnets, door closers or door operators in the event of fire. The doors then close automatically.

Please observe the relevant regulations for hold-open systems in your country.

Important for maintenance services: the maximum allowable delay in responding of the detector are 39 seconds.

Important: the detectors must be protected from icing and condensation.

The relay base can directly be fitted to the ceiling. The detector is plugged into the base and secured by turning clockwise. When mounting it on a wall, a mounting bracket has to be used to make sure the detector is always in a horizontal position.

RM 3000+ smoke detector part no. 040800N

WM 3000+ heat detector (alarm temperature 60 °C) part no. 040820N

Heat detectors with other alarm temperatures (no approval) on request

Base with relay and evaluation electronics part no. 040841

Order Information

Accessories

Power packs (450 mA, 800 mA) see page 07.019.00

Electromagnets for installation on wall/ceiling/floor see page 07.031.00

Hand switch for manual release of door see page 07.071.00

Sequence controllers and pushing flap see page 07.075.00

Automatic and semi-automatic door operators see page 05.001.00

160 N or 320 N spring rope pulley or counterweight see page 05.047.00

Hydraulic radial dampers and final dampers see page 05.049.00

Further Accessories

Page 07.010.00

Page 11: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+ Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.0011.00

23

4,2

10

2

54

16

8,5

5,5

50

25

15 18 1,5

60

1112

34,2

54

1,5

448

500

15

Mounting Bracket for RM 2000, RM 3000+ and WM 3000+The mounting bracket (part no. 040570) allows DICTATOR smoke and heat detectors to be fixed to the wall without difficulty. The fixing holes are suitable for both the RM 2000 and RM 3000+/WM 3000+ range.

In certain cases the German Standard for door hold-open installations allows a smoke detector on the ceiling to be replaced by a detector on the wall. However, these detectors must be installed 500 mm from the wall. This can be achieved with the mounting bracket, part no. 040575. All fixing holes correspond to those of the bracket part no. 040570.

Dimensions Mounting bracket part no. 040570

Mounting bracketpart no. 040575

Order Information Bracket for installation on the wall (RM 2000/RM 3000+) part no. 040570

Bracket for installation on the wall, length of the arm 500 mm part no. 040575

Page 07.011.00

Page 12: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

RM 3000+ and WM 3000+Smoke and Heat Detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.0012.00Page 07.012.00

Page 13: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.013.00

Approval for Smoke Detectors RM 2000, RM 3000+ and Signal Control S400

Page 14: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032Page 07.014.00

h >1,0 m

ohne Unterdecke

nicht dichteUnterdecke

h >1,0 m

Brandmelder

h 1,0 m

brandschutztechnischklassifizierte bzw.

fugenlose Unterdecke

Excerpt from the Directions for Hold-Open Devices

The smoke detector must be installed on the ceiling, above the wall opening. It must be at least 0.5 m horizontally from the wall, and must be no higher than 2.5 m.

The smoke detector should be installed in the area of the ceiling where the highest concentration of smoke would first be expected in the event of fire. Fire protection ceilings are so thick that smoke spreads quickly over the surface, whereas decorative ceilings are generally permeable (see diagram 1).

Diagram 1: Heights of lintel

4. Mounting

4.1 Installing Smoke Detectors

4.1.1 Wall Openings

Non impermeableceiling Fireproof

ceiling

Fire detector

3.8 Electrical Installation of the Hold Open System

Exerpt from the General Approval of the Building Authorities (from November 2010)To prevent any disturbances by short circuit (unintended conductive connection) of the release contacts, there is required a separate wiring to the following devices (system components):

- fire detectors- hand release switches- supervising devices which can prevent the release.

In case the trouble-shooting or release of these devices (system components) is realized by lines (e.g. current change, data frames) or the devices (system components) are combined or contained in one casing, or the wiring of these devices is completely conducted in a cable protection tube or cable canal, a separate wiring is not required.

Withoutsuspended

ceiling

Page 15: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.015.00

B

h12,0 m

a10,5 m

a 2

2,0 m h 20,5 m

b 2b 1

B

Raum 1 Raum 2

A

A

a1

0,1 m

a 2

b 1; b 2

lichte Breitelichte Höhe

Diagram 2: Installation Instructions according to 4.1.1.

Section A - A Section B - B

The quantity and model of detectors, as well as the measurements between the ceiling and lintel, depend on the height of the ceiling at the points where the detectors are installed. If a lintel detector is required, it should be installed on the wall above the wall opening, maximum 0.1 m above the lintel.For the in stallation it is generally assumed that one detector can cover a range of 2 m to each side. If the opening width exceeds 4 m, additional detectors are required.

Usually one detector is placed on the ceiling in each of the adjoining rooms of the door and a third one directly on the lintel of the opening. However, if the ceiling in both rooms is no more than one metre above the opening, two detectors (one on each ceiling) are sufficient. A single detector on the lintel is sufficient on swing doors with an opening width up to 3 m.

Room 2Height

Line Height of ceiling Installation points Min. number of over opening lintel (b = b1 or b2) detectors required* 1 h1 and/or a1+ a2 + b 2 ceiling and h2 > 1.0 m 1 lintel detectors

2 h1and h2 a1+ a2 2 ceiling detectors ≤ 1.0 m

3 as line 2, b 1 lintel detector but swing door with door width up to 3.0 m * Depending on the door width more detectors may be necessary in lines 1 and 2.

WidthRoom 1

Page 16: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032Page 07.016.00

geschlossenen Decke

max.0,5m

max.0,5m

Deckenöffnungen

Deckenöffnung

Deckenöffnung

R=2m

R=2m

Ja

4.1.2 Ceiling Openings

According to regulations (10/1998) ceiling detectors may be replaced by wall detectors in exceptional cases.

Exceptions:

- Distance between ceiling and lintel is more than 5 m.- Wall detectors are installed at least 3.5 m above the lintel of the wall opening,

with brackets at least 0.5 m long.

If floors are joined through ceiling openings, these openings must have ceiling detectors. At least one ceiling detector must be installed on each floor, and they must be no further away from the edge of the ceiling opening than 0.5 m. If the ceiling above the opening is sealed, the detector must be installed vertically in the middle of the ceiling opening.

Sealed ceiling

Ceiling openings

4.1.1 Replacing Ceiling Detectors by Wall Detectors - cont.

Diagram 4: Installation areas according 4.1.2

If the ceiling opening has a diameter of more than 4 m, additional detectors are required.

No

Yes

1 lintel detector 2 ceiling + 1lintel detectors

NoCeiling on one or both sides more than 1.0 m over the upper edge of the opening?

2 ceiling detectors

Swing door width max. 3 m?

Diagram 3: Decision diagramm for 4.1.1

Yes

Page 17: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.017.00

Mounting devices used for hold-open systems must not interfere with the protection given by the door/gate.

You must not drill through fire protection doors/gates.

Counter plates for electromagnets should be mounted on swing doors in such a way that the screws are no more than 150 mm from the upper, lower, or vertical edge of the closing side. Rivet nuts with M5 oder M6 screws must be used on steel doors.

Once the hold-open system has been installed it is the operator's responsibility to ensure it is tested to make sure it functions correctly. This inspection must only be carried out by the manufacturer of releasing devices and hold-open systems or a specialist.The inspection must include the following points:

1. The hold-open system equipment must be authorised.

2. The reference numbers on the equipment must be authorised numbers.

3. All equipment must operate safely, as stated in the regulations. It must be possible to release the system by hand, or by simulating the detectors according to the type of fire.

4. It must be checked whether the system still closes automatically should it not be operating (e.g through lack of power or missing detector).

Once the inspection has been successful a 105 mm x 52 mm sign available from the hold-open system manufacturer must be displayed on the wall within the immediate vicinity of the system, with the following inscription:

Hold-Open SystemAuthorised by....(Company, month and year of inspection)

5. Final Inspection

4.2 Hand Release A manual hand release must be provided for every hold-open device. The hand switch must be installed within the immediate vicinity of the door and not be hidden by the door. It must be marked with "close the door".

4.5 Mounting Devices

Page 18: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Regulations

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032Page 07.018.00Page 07.018.00

Monthly Inspection

Date Date DateName NameName

6. Periodic Inspection

Date Date DateName NameName

Annual Inspection

The hold-open system must be tested by the operator on a monthly basis. In addition an annual maintenance service is required, which must only be carried out by a competent person.

Records of these monthly checks and annual maintenance must be kept by the operator (please see example below).

Page 19: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Power Packs

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.019.00

Power PacksThe DICTATOR power packs change an input voltage of 230 VAC into an electro-nically stabilised direct voltage of 24 VDC. This direct voltage is independent of the oscillations from the mains voltage. A green light just above the label indicates whether the power pack is working properly.

An integrated protective system protects the power pack in the event of a short circuit on the low-tension side.

DICTATOR power packs are available with two different capacities: 450 mA or 800 mA.

They have been tested and approved for the use on hold-open systems (approval no. Z-6.5-1903). The production quality of the power packs is surveyed by an accredited testing institute.

Technical Data 040545 040552Input voltage 230 VAC (+10 %, -10 %) / 50 Hz Power consumption max. 0.1 A 0.2 AOutput voltage 24 VDC (+10 %, -10 %)Output current max. 450 mA 800 mAOperating temperature -10° to +40 °CWeight 0.75 kg 1.2 kgIP rating (according to DIN 40050) IP 30 IP 20 Only for dry rooms!Protection class I Casing stainless steel white varnished sheet steel

Page 20: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Power Packs

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032Page 07.020.00

11

7

4

64

69

8

48

51

82

Energieversorgungsgerät E450prim. 230VAC (+10% /-10%)sek. 24VDC / max. 450mASchutzart IP 30Nur für trockene Räume.Vor dem Öffnen des GehäusesNetzspannung ausschalten !

Power

Dictator Technik GmbHGutenbergstr. 9D-86356 Neusäßwww.dictator.de

Art.-Nr. 040545

- - + +PE L1 N

105

134

160

5,5

85

55 4,5

Dimensions

The power packs are only suitable for dry rooms.

During service the power pack heats up. Therefore take care that air can penetrate the casing through the ventilation slots (e.g. do not mount the pack in a corner).

The connection to the 230 V mains and the commissioning and maintenance must be carried out by an accredited person.

Make sure the earthed conductor is connected

properly. Otherwise danger to life by electric shock!

Interior

Installation

Mains230 VAC

Order Information Power pack 24 VDC/450 mA part no. 040545

Power pack 24 VDC/800 mA part no. 040552

Mains230 VAC

Output24 VDC,max. 450 mA

Primary fuseT 0.1 A Output 24 VDC,

max. 800 mA

Primary fuseT 0.2 A

Power pack 040545

Power pack 040552

Power pack040545

Power pack040552

Page 21: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Power Packs

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.021.00

Technical Data

S400 Signal Control according to EN 14600:2005, point 4.9.2.1

The S400 signal control complies with the requirements of the EN 14600:2005, point 4.9.2.1. This norm requires the triggering of acoustic and optical warning signals during the closing of a fire protection door - even in case of power failure.

The S400 signal control disposes of an integrated power pack that changes the mains power of 230 VAC into 24 VDC to power hold-open devices and smoke detectors. In addition a battery back-up is integrated which serves only to power the acoustic and optical signallers. At a maximum two hazard warning flashers and one siren can be connected (for type please see following page).

The signallers are triggered the moment the hold-open system's power is cut and the door starts to close. By an integrated time control unit the signallers are switched off after an adjustable time.

Existing installations can be upgraded with the signal control.

Input voltage 230 VAC (+10 %, -10 %) / 50 Hz Power consumption maximum 0.1 AOutput voltage for hold-open system 24 VDC, max. 400 mABattery back-up for signallers 20 VDC, max. 32 mA, max. 100 sec.Operating temperature -10° to +40 °CIP rating (according to DIN 40050) IP 30 / only for dry roomsProtection class ICasing stainless steelTime relay for switching off signallers adjustable 1 - 99 seconds/deactivatable

Page 22: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Power Packs

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032Page 07.022.00

DimensionsS400 Signal Control

Order Information S400 signal control part no. 700162

Signaller for S400 with red flashing light and siren, IP 65 part no. 700171

Signaller The only signaller tested and approved together with the S400 signal control is the signaller, part no. 700171. So you may use just this hazard warning flasher with integrated siren.

In case you use two units on one door, in one signaller the siren has to be deactivated.

Input voltage 24 VDC Power consumption 26 mA with activated siren 6 mA with deactivated sirenLoudness approx. 100 dBA, reducible by integrated potentiometerFlashing frequency 1 HzColour redIP rating IP 65 Dimensions D x H 97.5 x 104 mm

Technical Data Signaller

Page 23: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

Page 07.023.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064

DICTATOR Hold-Open Systems for Hazardous Areas

Products to be used in hazardous areas obviously have to meet special require-ments. In July 2003 the new European directive 94/9/EG (ATEX 100) has come into force making regulations more rigorous than before.

DICTATOR furnishes a hold-open system especially for hazardous areas that meets the requirements of the ATEX 100. The hold-open system has been tested and is approved by the Institute for Building Engi-neering in Berlin for the use on fire protection doors (approval no. Z-6.5-1646).

There are two types available:

- hold-open system without door operator

- hold-open system combined with a door operator for opening the door.

The central unit is installed outside the hazardous area.

The valid regulations and instructions must strictly be observed. The installation of the components and operating elements must assure that they cannot be damaged.

Technical Data Use hazardous areas

zones 1 and 2

Operating temperature 0 °C to +40 °C

Type of protection fire detector II 1G Ex ia II C T5 (at max. 40 °C)

only in combination with a safety barrier

Type of protection electromagnets II 2G EEx m II T6 or

II 2G EEx em II T6

Page 24: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064Page 07.024.00

11109

87

2143

+

1+8+

-

-

-

2-7-

+

+

1

2 34

LED-

COM-

IN+

OUT+

1

2 34

LED-

COM-

IN+

OUT+

1

2 34

LED-

COM-

IN+

OUT+

Components of a Hold-Open System without Door Operator

Fire protection doors, that are not kept closed all the time require a hold-open system. The smallest unit of such a hold-open system consists of a fire detector, a power supply, an electromagnet and a hand release switch. In case of fire or gas alarm the power supply to the electromagnet is interrupted, the door is set free and automatically closed by the built-in spring, a door closer or a counterweight. In case of hold-open systems in hazardous areas, according to German regulations, an additional gas warning system with a NC-contact is required to release the hold-open system as well. If the switching capacity of the potential-free contact of the gas alarm is not sufficient, an additional relay might be used that is fed by the power supply of the hold-open system.

The explosion-proof hold-open system is made up of maximum 10 smoke or heat de-tectors and up to 10 explosion-proof magnets. The explosion-proof magnet is available in 2 different forces and 2 different designs (with connection box or just with a 2 m ex-proof cable).

The TSZ 0400 central and the safety barrier (Zenerbarriere) are installed outside the hazardous area.

For the explosion-proof DICTATOR hold-open system with the following components a hazard analysis of the TÜV Süd (South) is existent. The cable recommended for the wiring within the hazardous area is an Ölflex cable 2x0,75 mm², max. length 100 m.

- TSZ 0400 central unit with power supply- Shunt safety barrier: Zenerbarriere Z928 - RM 3000IS EX smoke detector (or WM 3000IS EX heat detector) with base- Resistor 5.6 kΩ (to be placed in the last detector of the line)- Explosion-proof magnet- Hand release switch (part no. 700232)- Gas warning system

Components

Wiring Diagram

Shunt safety barrier Z928

Hand release switch 700232

Up to 10 intrinsically safe RM 3000IS EX smoke detec-tors or WM 3000IS EX heat detectors

Resistor placed in

the last detector of

the line

Up to 10 electromagnets EM GD 50 EX or EM GD 70 EX

Fuse*

Central unit TSZ 0400 Hazardous area

zones 1 - 2

Safe area

Gas

det

ecto

r

Screening(operational earth)

* Each Ex-magnet should be individually fused, with the fuse installed upstream of the magnet (i.e. between power supply and magnet).More information can be found in the manual of the magnets.

ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
Page 25: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

Page 07.025.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064

11109

87

2143

+

1+8+

-

-

-

2 -7 -

+

+

-+24

VDC

12

34

56

ResetReset

NCC

NO

AlarmAlarm

1

2 34

LED-

COM-

IN+

OUT+

1

2 34

LED-

COM-

IN+

OUT+

1

2 34

LED-

COM-

IN+

OUT+

The door operator used to open the fire protection door is not shown in the list of the components. Which door drive should be chosen depends on the type of door, the required forces, functions etc. Information on our explosion-proof door operators are to be found in the two chapters about door operators in our catalogue. The TSZ 0400 central unit, the shunt safety barrier and the AR 20 shut-off relay are installed outside the hazardous area.For the explosion-proof DICTATOR hold-open system with the following components a hazard analysis of the TÜV Süd (South) is existent. The cable recommended for the wiring within the hazardous area is an Ölflex cable 2x0,75 mm², max. length 100 m.- TSZ 0400 central unit with power supply- Shunt safety barrier: Zenerbarriere Z928- AR20 cutoff relay (completely cutting off the door operator control system in case of alarm) - RESET switch- RM 3000IS EX smoke detector (or WM 3000IS EX heat detector) with base- Resistor 5.6 kΩ (to be placed in the last detector of the line)- Explosion-proof magnet- Hand release switch (part no. 700232)- Gas warning system (to be provided by the customer)

Components of a Hold-Open System with Door OperatorIn order to open a fire protection door automatically an approved, explosion-proof door operator can be used. The magnets of explosion-proof hold-open systems are generally installed only in the OPEN position of the door and are not integrated in the door operator. In case of alarm, the AR 20 cutoff relay completely cuts off the door operator to make sure that the door does not stay open, even in case of an error of the control system. The door is closed mechanically.

Components

Wiring Diagram

Shunt safety bar-rier Z928

Central unit TSZ 0400

Cutoff relay AR20

Up to 10 electromagnets EM GD 50 EX or EM GD 70 EX

Up to 10 intrinsically safe RM 3000IS EX smoke detectors or WM 3000IS EX heat detectors Resistor

placed in the last detec-

tor of the line

Hand release switch700232 G

as d

e-te

ctor

Safe area

Hazardous area zones 1 - 2

If necessary 2 ex-proof CLOSE switches Fuse*

Screening(operational earth)

Powerinput230 VAC

Power output 230 VAC,supply of door drive control unit * Each Ex-magnet should be individually fused, with the fuse installed upstream

of the magnet. More information can be found in the manual of the magnets.

ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
ks
Schreibmaschinentext
Page 26: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064Page 07.026.00

TSZ 0400 Central Unit with Power Supply

Technical Data

Dimensions

TSZ 0400 central unit with power supply part no. 040580

Order Information

Installation

Functions of the TSZ 0400 central unit:- Power supply of the connected smoke detectors and electromagnets - Control and evaluation of the smoke detectors: in case of alarm or errors the integrated

relay contact interrupts the power supply to the magnet and the door closes- RESET: after each alarm the connected smoke detectors must be reactivated. This is done

either with the RESET switch on the front panel of the central unit or with a separate RESET-switch (obligatory in combination with the AR20 shut-off relay).

- Power supply of further consumers such as a warning siren or flash light - Additional potential-free contact

• Supply voltage 230 VAC ± 15 %, 50 Hz

• Power consumption (without load) about 50 mA

• Relay contact for hold-open system max. 30 VDC at 1 A

• Additional contact* change over contact, max. 30 VDC at 1 A

• Output voltage 24 VDC

• Output current max. 0.8 A

• Operating temperature 0 °C to 40 °C

• IP rating IP 42

• Material, colour of the casing plastic casing, RAL 9002

• LEDs on the front panel LED green "working" (ON) (normal operation)

LED red "alarm" (error or alarm)

• "Rückstelltaste" switch on the front panel hand release and RESET of the detectors

Up to 3 central units can be inter-connected using the integrated terminals. If one of the detectors connected to one central unit is released, this central unit switches the other connected central units to alarm.* Not available when an AR 20 cutoff relay is connected.

The TSZ 0400 central unit must be installed outside the hazardous area.

Page 27: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

Page 07.027.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064

60 (50*)

ø100

The wiring is done in the base S 3000IS EX. In the last detector the 5.6 kΩ resistor has to be installed between the clamps Com- and Out+. Intrinsically safe circuits (components marked light-blue) may enter hazardous areas - depending on the type of protection required. However, it has to be assured that each intrinsically safe circuit is safely separated from any not intrinsically safe circuit. The requirements of the EN 60079-14 standard have to be observed. In Germany addi-tionally applies the "National Preamble" of the DIN EN 60079-14/VDE 0165 part 1.On demand an additional parallel display can be connected to the RM/WM 3000IS EX smoke/heat detectors to faster locate the triggered detector or the seat of fire in case of alarm.

Smoke detector RM 3000IS EX with S 3000IS EX base part no. 040881SET

Heat detector WM 3000IS EX with S 3000IS EX base part no. 040886SET

Resistor 5.6 kΩ part no. 040891

Smoke and Heat Detectors RM 3000IS EX / WM 3000IS EX

Fire protection components installed in hazardous areas require in addition to the approval for fire protection a test and certificate confirming their compliance with the EN 94/9/EG (ATEX 100) standard. Both the smoke and heat detector RM 3000IS EX and WM 3000IS EX meet these requirements. The smoke detector RM 3000IS EX is a stray light detector with integrated thermo sensor.The smoke and heat detectors RM 3000IS EX and WM 3000IS EX are intrinsically safe. In hazardous areas they may only be used in combination with the shunt safety barrier described on the next page.

Dimensions

• Supply voltage 14 to 28 VDC

• Average quiescent current 85 µA at 24 VDC

• Starting current 105 µA at 24 VDC

• Alarm load 325 Ω in series with 1.0 V descent

• Operating temperature -40 °C to +60 °C (class T4)

-40 °C to +40 °C (class T5)

(Protect against condensation and icing!)

• Heat detector rate-of-rise detector

Reaction point class acc. EN 54-5:2000 AR1, max. room temperature 50 °C

• Ignition protection type II 1G EEx ia IIC T5 (at max. 40 °C)

• IP rating IP 23

• Indication of alarm red LED indicator on the detector

• Material / colour of the casing polycarbone / white

Technical Data

Order Information

Installation

*Height of the WM 3000IS EX

Page 28: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064Page 07.028.00

Dimensions

A shunt safety barrier, the Z928, must be placed in between the TSZ 0400 central unit and the intrinsically safe smoke detectors installed in the hazardous area. It restricts the transfer of energy from safe area equipment to the intrinsically safe smoke detectors, by the limitation of voltage and current.

The shunt safety barrier Z928 has been tested and is certified according to the require-ments of the 94/9/EG (ATEX 100) standard (approval no. BAS01ATEX7005).

Safety Barrier: Zenerbarriere Z928

Shunt safety barrier Z928 part no. 040584

CI-K casing for the safety barrier part no. 040585

Order Information

• Supply voltage max. 28 VDC

• Nominal power max. 93 mA

• Integrated resistor min. 300 Ohm

• EEx ia detectors to be connected max. 10 units

• IP rating IP 20 / casing IP 65

• Operating temperature 0 °C to +60 °C

• Material casing glassfiber reinforced polycarbonate

• Colour of the casing bottom black RAL 9005, upper part grey RAL 7035

Technical Data

The shunt safety barrier integrates several diodes. If the voltage in the safe area exceeds the maximum voltage admissible for these diodes, they start to conduct current and blow the fuse of the safety barrier. This way the transfer of too high energies to the hazardous area is prevented.

The safety barrier has to be installed outside the hazardous area.

If on site no suitable casing (with a top hat rail according to EN 50222) is available, we offer a separate casing with protection IP 65. The barrier is simply snapped onto the top hat rail in the casing.

Functioning

M and Q: 2 cable inlets (membrane) of max. ø16

Shunt safety barrier Z928 Casing CI-K

T: 2 cable inlets (membrane) of max. ø11

Page 29: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

Page 07.029.00© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064

105

13

4

16

0

5,5

85

55 4,5

AR 20 Cutoff Relay

The AR20 cutoff relay is required as a component in explosion proof hold-open systems when a door operator is used to open the door. In case of an alarm it completely cuts off the power supply to the control system of the door operator and the door is closed mechanically (door closer, closing spring or counterweight). After each alarm the shut-off relay has to be reactivated with a separate RESET switch. The AR 20 cutoff relay has to be installed outside the hazardous area.

• Control voltage 24 VDC ± 10 %

• Power comsumption max. 40 mA

• Switching capacity max. 3 A at 250 VAC

• Max. switchable motor power 0.37 kW

• Operating temperature 0 °C to 40 °C

• IP rating IP 20

• Material, colour of the casing sheet steel casing, RAL 9010

• Cable inlets of the casing 4 x Pg 9

• Indicator diode on the casing LED red = triggered (error or alarm)

Technical Data

Interior View Dimensions

Cutoff relay AR 20 part no. 040582

RESET switch to reactivate the cutoff relay part no. 700112

Order Information

Page 30: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Explosion-Proof Hold-Open Systems

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1064Page 07.030.00

Page 31: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1095

Electromagnets

Page 07.031.00

• Electromagnet with swivel head Page 07.033.00

• Electromagnet with connection terminal Page 07.037.00

• Electromagnet with connection terminal, IP 65 Page 07.039.00

• Electromagnet with connection terminal on the mounting plate Page 07.040.00

• Electromagnet with interrupter key plastic casing Page 07.041.00

• Ex-proof electromagnet for zones 2 and 22 with IP 65 protection Page 07.043.00

• Ex-proof electromagnets with IP 66 protection Page 07.045.00

• Electromagnet for flush mounting Page 07.049.00

• Electromagnet for floor mounting Page 07.051.00

• Electromagnet with feed-back contact Page 07.053.00

• Three pole heavy duty magnet (4350 or 5100 N) Page 07.057.00 (for further bar magnets see Access Control Systems)

• Bar magnet Page 07.059.00

Electromagnets - Summary

Page 32: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1095

Electromagnets

Page 07.032.00

DICTATOR Electromagnets

Customised Designs

Variations

Uses DICTATOR electromagnets are used in a variety of applications. One of the most impor-tant fields is fire protection and prevention. The electromagnets are used to keep fire protection doors open. Usually fire protection doors must always remain closed. However, this is not always possible due to organisational or practical reasons. Using an electromagnet to keep the door open is the perfect solution. In the event of fire the smoke detector, for example, automatically interrupts the power supply to the magnet, thus making sure the door closes. Electromagnets are also used on smoke vents and windows. These windows should normally be closed, and in the event of fire must open automatically. This is no problem for a DICTATOR electromagnet.

Bar magnets with very high holding forces are mainly used for security applications, such as the securing of emergency exits in escape routes.

Electromagnets are also used in machine construction. For example in machining centers, access doors or flaps must be closed before the machine is allowed to start. This requires information to be transferred from the door to the control system. DICTATOR electromagnets with feed-back contact provide the solution.

The versatility of DICTATOR electromagnets makes them the perfect solution for many different applications. However, on the following pages we will concentrate on our standard program for fire protection doors. If you have an application that cannot be solved with our standard models, please contact us.

DICTATOR electromagnets are produced in a variety of designs to enable us to offer solutions for special applications. Within our standard programme, the following tech-nical data can be varied:

Voltage 12 VDC to 230 VDC, 24 VAC to 250 VAC

Force 70 N to 5000 N

IP rating from IP 20 to IP 66

Electrical connection terminal, free leads etc.

Design casing, distance tube, flush mounting etc.

The most important features of DICTATOR electromagnets include lowest possible power comsumption and highest possible force. We have also attached great importance to a wide range of different models, offering optimal solutions for many different application and installation requirements.

Apart from the variation possibilities described above, we also offer customised designs e.g. the electromagnets with a permanent magnet. They usually work without current due to the permanent magnet. By feeding current to the magnet, the magnetism of the permanent magnet is momentarily neutralised, thus releasing the door or flap.

Please inform us of your application. We look forward to providing a solution for you.

Page 33: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.033.00

Electromagnet EM GD 60 EM GD 60 SVoltage 24 VDC ±10 % 24 VDC ±10 %Power consumption 67 mA (1.6 W) 79 mA (1.9 W)Duty cycle 100 % 100 %Operating temperature -20 °C to +60 °C -20 °C to +60 °CForce 700 N 1000 NRemanence / IP rating 0 N / IP 40 0 N / IP 40Finish zinc-plated / powder coated RAL 9010

DICTATOR electromagnets are used in combination with smoke detectors to keep fire protection doors open.The electromagnet with swivel head has a distance tube which is welded vertically onto a mounting plate.The magnet is supplied with its head in a straight position. To mount on the floor or ceiling the head position can be altered without having to interfere with any electri-cal connections (see diagram on the right).The tube is available in three different lengths. It can also be shortened to the required length if necessary.The mounting plate and tube are made of grey laquered steel and the magnet is zinc plated steel. The other parts are made of light grey plastics (RAL 7037). An inter-rupter key is integrated in the lower part of the tube. DICTATOR magnets are equipped with spark extinction diodes. In the event of faulty connection, the integrated polarity protection prevents the spark extinction diode from being destroyed. The GD 60 electromagnet has been tested according to EN 1155:2003 and together with the DICTATOR smoke detectors RM 2000 and RM 3000+ been approved by the German building supervision (approval no. Z-6.5-1903).

Electromagnet with Swivel HeadFor Installation on the Floor, Wall or Ceiling

Technical Data

Page 34: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032

Electromagnets

Page 07.034.00

ø 40

23

ø 60ø 48

67

107

ø 96

88

"L"

"M"

88

70

687

x 10

3 40

ø 1

8

Arr

etie

rsch

raub

e

You can either fix the electromagnet with swivel head to the floor, ceiling or wall. If you want to change the position of the head you need to loosen the locking screw and turn the head by 90°.

If you need to cut the distance tube, remove the head after loosening both grub screws which fix the head to the tube. Then pull out the wires connected to the interruption key.

An anchorplate needs to be fixed to the door as a counterpart to the magnet. A choice of different counter plates can be found later in this section.

The connection wires are inserted through an opening in the mounting plate. After the magnet has been properly mounted and wired, both plastic covers are pushed from the side over the mounting plate and clipped into position.

Please note:

It must be possible to release a fire protection door held open by an electromagnet with a hand switch which is not hidden by the opened door. (DICTATOR hand switch part no. 040005, see diagram on the left).

Installation

Order Information

Dimensions

Model Length "L" Height "M"

EM GD 60 S 175 magnet 175 mm 107 mm part no. 040111

EM GD 60 S 175 S magnet 175 mm 107 mm part no. 040164

EM GD 60 S 325 magnet 325 mm 257 mm part no. 040112

EM GD 60 S 475 magnet 475 mm 407 mm part no. 040113

Lock

ing s

crew

Page 35: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032 Page 07.035.00

70

234 x ø 4,5

55

55

ø 6

0

82

Order Information

Dimensions

Electromagnet for Installing on the Wall

The electromagnet with the plastic base is an aesthetical unit. It permits to compensate for larger distances between door and wall as with a normal electromagnet, without using a distance tube. The electromagnet is furnished both with and without interrupter key in the plastic base.

Fix the magnet to the wall and the anchor plate to the door. A selection of counter plates can be found later in this section.

The connection wires are inserted through an opening at the bottom of the base plate.

Please note: It must be possible to release a fire protection door held open by an electromagnet with a hand switch which is not hidden by the opened door. (DICTATOR hand switch part no. 040005).

with Plastic Base and Interrupter Key

EM GD 60 K 70 electromagnet force 700 N part no. 040223

EM GD 60 K 70 without interrupter key force 700 N part no. 040224

EM GD 60 K70 electromagnet with interrupter keyPart no. 040223

Page 36: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1032

Electromagnets

Page 07.036.00

Notes

Page 37: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1026

Electromagnets

Page 07.037.00

DICTATOR electromagnets are used in hold-open systems to keep fire protection doors open.

Electromagnets of the ranges R, RI and F include magnets with diameters of 40, 50, 60 and 70 mm. They differ in force, design and size. They are provided with a connection terminal to allow for an easy installation.

The magnets and the mounting plates are made of steel and are zinc-plated.

DICTATOR magnets are equipped with a spark extinction diode. In the event of faulty connection, the integrated polarity protection prevents the spark extinction diode being destroyed.

The electromagnets with connection terminal types EM GD 50 und 60 R 26 I can be connected to both 24 VDC and 24 VAC.

These electromagnets have been tested ac-cording to the EN 1155:2003 and in com-bination with DICTATOR smoke detectors RM 2000 and RM 3000+ are approved by the German building supervision (approval no. Z-6.5-1903).

Models R, RI, F

Electromagnets with Connection Terminal

Technical Data Voltage, standard configuration 24 VDC ± 10 %

Voltages, special configurations 24 VAC ± 10 % , 230 VAC, 230 VDC

Power consumption 67 mA to 142 mA

Duty cycle 100 %

Operating temperature -20 °C to +60 °C

Holding force 300 N to 2000 N

Remanence 0 N

Surface magnet, mounting plate zinc-plated

Page 38: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1026

Electromagnets

Page 07.038.00

ø k

a

b

l

i

ba

c

ø gfn

25

EM GD 50 R 26 electromagnet force 600 N part no. 040021

EM GD 60 R 26 electromagnet force 700 N part no. 040133

EM GD 60 R 26 S electromagnet force 1000 N part no. 040134

EM GD 70 R 39 electromagnet force 1450 N part no. 040023

EM GD 70 R 39 S electromagnet* force 1700 N part no. 040117

EM GD 70 R 39 R electromagnet* force 2000 N part no. 040118

All dimensions in mm.

Countersink DIN 74 Am

Dimensions

Order Information

The electromagnets of the R range are connected in the connection terminal fixed laterally to the magnet.

Technical Data

Electromagnets with Connection Terminal Model R

Electromagnet EM Voltage Power consumption Holding force

GD 50 R 26 24 VDC ±10% 67 mA ( = 1.6 W) 600 N

GD 60 R 26 24 VDC ±10% 67 mA ( = 1.6 W) 700 N

GD 60 R 26 S 24 VDC ±10% 79 mA ( = 1.9 W) 1000 N

GD 70 R 39 24 VDC ±10% 71 mA ( = 1.7 W) 1450 N

GD 70 R 39 S 24 VDC ±10% 142 mA ( = 3.4 W) 1700 N

GD 70 R 39 R 24 VDC ±10% 142 mA ( = 3.4 W) 2000 N

a b c f g i k l n

EM GD 50 R 26 55 44 27.5 5.5 ø 4.5 3 ø 50 26 18

EM GD 60 R 26 65 55 32.5 5 ø 4.5 3 ø 60 26 18

EM GD 70 R 39 75 60 37.5 7.5 ø 5.5 4 ø 70 39 18

Type

* These electromagnets are not approved by the building authorities.

Page 39: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1026

Electromagnets

Page 07.039.00

ø 70

120

98

60

75

39

50

60

75

22

35

4

i

d

b

b a

f

g

34

ø k

l

nm

37

(ø 70 : 32)

All dimensions in mm

The electromagnets of the RI range are connected in the waterproof plastic connection terminal. The EM GD 70 is also available with a Pg 13.5 inlet, especially for the use on ships with a larger cable diameter. In case the magnets are exposed to the sun, they are available with an UV resistant sealing compound. The electromagnets EM GD 50 and 60 are designed to be used with both 24 VDC and 24 VAC.

Electromagnets with Connection Terminal Model RI with Connection Terminal IP 65

Dimensions

Technical Data

ø 50/60: Pg 9ø 70: Pg 11

Model for connection cables up to ø 14 mm, e.g. on ships

Countersink DIN 74 Am

Type

Order Information EM GD 50 R 26 I, 24 VDC/AC 600 N part no. 040107

EM GD 60 R 26 I, 24 VDC/AC 700 N part no. 040131

EM GD 60 R 26 IS, 24 VDC/AC 1000 N part no. 040132

EM GD 60 R26 IS, 24 VDC/AC UV* 1000 N part no. 041014

EM GD 70 R 39 I, 24 VDC 1450 N part no. 040108

EM GD 70 R 39 I, 230 VDC 1450 N part no. 040208

EM GD 70 R 39 I, 230 VAC 1450 N part no. 040259

EM GD 70 R 39 I, PG 13.5, 24 VDC 1450 N part no. 040222

*The UV resistant sealing compound contains silikone! (Colour: grey)

Electromagnet EM GD 50 R 26 I GD 60 R 26 I GD 60 R 26 IS GD 70 R 39 I

Voltage 24 VDC/AC ±10 % 24 VDC ±10%

Power consumption 67 mA (1.6 W) 67 mA (1.6 W) 79 mA (1.9 W) 71 mA (1.7 W)

Holding force 600 N 700 N 1000 N 1450 N

a b d f g i k l m n

EM GD 50 R 26 I 55 44 100 5.5 Ø 4.5 3 Ø 50 26 14 25

EM GD 60 R 26 I 65 55 110 5 Ø 4.5 3 Ø 60 26 14 25

EM GD 70 R 39 I 75 60 118 7.5 Ø 5.5 4 Ø 70 39 20 35

Page 40: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1026

Electromagnets

Page 07.040.00

k

l

k

d

e

cd

e

i l ia b

ab

gf

f

EM GD 40 F 23EM GD 50 F 26

EM GD 60 F 26EM GD 70 F 39

Electromagnets of the range F include magnets with diameters of 40, 50, 60 and 70 mm. They differ in force and size (see technical data).The connection terminal is on the moun-ting plate of the magnet.

Dimensions

All dimensions in mm

EM GD 40 F 23 electromagnet force 300 N part no. 040085

EM GD 50 F 26 electromagnet force 600 N part no. 040106

EM GD 60 F 26 electromagnet force 700 N part no. 040049

EM GD 60 F 26 S electromagnet force 1000 N part no. 040163

EM GD 70 F 39 electromagnet force 1450 N part no. 040037

EM GD 70 F 39 S electromagnet* force 1700 N part no. 040115

EM GD 70 F 39 R electromagnet* force 2000 N part no. 040122

Order Information

EM GD Power consumption Force EM GD Power consumption Force 40 F 23* 75 mA (1.8 W) 300 N 70 F 39* 71 mA (1.7 W) 1450 N 50 F 26* 67 mA (1.6 W) 600 N 70 F 39 S 142 mA (3.4 W) 1700 N 60 F 26* 67 mA (1.6 W) 700 N 70 F 39 R 142 mA (3.4 W) 2000 N 60 F 26 S* 79 mA (1.9 W) 1000 N

Technical Data

Electromagnets with Connection Terminal Model F

* tested according to EN 1155

Type a b c d e f g i k l

EM GD 40 F 23 45 35 45 63 73 5 Ø 4.5 3 Ø 40 23

EM GD 50 F 26 55 44 51 74 83 4.5 Ø 4.5 3 Ø 50 26

EM GD 60 F 26 65 55 - 55 93 5 Ø 4.5 3 Ø 60 26

EM GD 70 F 39 75 60 - 60 103 7.5 Ø 5.5 4 Ø 70 39

* These electromagnets are not approved by the building authorities.

Page 41: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1125

Electromagnets

Page 07.041.00

Voltage 24 VDC ±10 %

Power consumption 67 mA (1.6 W)

Duty cycle 100 %

Operating temperature -20 °C to +60 °C

Force 700 N

Remanence 0 N

Finish magnet and mounting plate zinc-plated

Colour of casing white (plastic)

DICTATOR electromagnets are appropriate for the use in hold open systems on fire protection doors.

The magnets in plastic casing are available in two versions: with and without lateral Pg7 cable gland. Both types have an interrupter key on top of the casing. The magnet can therefore be used on both left and right ope-ning doors, as the interrupter key is always accessible. The plastic casing on the magnet meets high aesthetic requirements. Installing the magnet is very easy as the key is fixed to the mounting plate. The plastic casing can completely be removed for mounting.

DICTATOR magnets are equipped with a spark extinction diode as standard. In the event of faulty connection, the integrated polarity protection prevents the spark extinction diode being destroyed.

The electromagnets have been tested according to EN 1155:2003 and approved together with the DICTATOR smoke detectors RM 2000 and RM 3000+ by the German building supervision (approval no. Z 6.5-1903).

Technical Data

Electromagnet in Plastic Casewith Interrupter Key, for Surface Mounting

Page 42: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1125

Electromagnets

Page 07.042.00

26

251

55 555

57,5

84x

ø 4

,2

102

70

ø 6018

18

38

ø 2

0

24

251

55 5

555

7,5

84x

ø 4

,2

102

70

ø 6018

18

38

ø 2

0

24

Dimensions

Order Information

EM GD 60 F 26 T electromagnet force 700 N part no. 040097

EM GD 60 F 26 TK electromagnet force 700 N part no. 040045

Electromagnet EM GD 60 F 26 TK

Electromagnet EM GD 60 F 26 T

Page 43: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.043.00

Ex-Proof Electromagnetfor the Exclusive Use in Hazardous Zones 2 and 22

Technical Data

Hazardous areas are divided into different zones. As zones 2 (gas) or 22 (dust) are defined areas where ususally during nor-mal operation no dangerously hazardous atmosphere occurs or when only during a short period. The demands on devices used in these zones are minor to those applying to the ex-proof DICTATOR electromagnets, series EM GD Ex m (see page 07.045.00 and the following). Therefore, DICTATOR provides for the use in hazardous areas of the zones 2 and 22 an economic alternative, the EM GD 70 R39I Ex2 ex-proof magnet. The following three features distinguish it from the normal EM GD 70 R39I:- connecting terminal for the prescribed

equipotential bonding,- larger base plate,- special label for hazardous areas.The EM GD 70 R39I Ex2 is equipped as standard with spark extinction diodes and polarity protection.The electromagnets have been tested according to EN 1155:2003.

Electromagnet EM GD 70 R39I Ex2

Voltage 24 VDC ±15 % Power consumption (±15 %) 71 mA (1.7 W) Force / Remanence 1450 N / 0 N Ignition protection type II 3G Ex nC IIC T6 Gc X II 3D Ex nC IIIC T85°C Dc X Protection / Duty cycle IP 65 / 100 % Operating temperature -20 to +60 °C Connection connector box GDML 2011 GE 1 G, PG 11 Finish magnet and base plate zinc-plated

Page 44: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.044.00

.

The EM GD 70 R39 I Ex2 electromagnet may exclusively be used in hazardous areas of the zones 2 and 22.More conditions for the use in the zones 2 and 22: - The magnet must be protected against mechanical impact.- A protective earth connection is mandatory.- A fuse has to be connected upstream to the magnet.- All regulations for hazardous areas have to be observed.

EM GD 70 R39 I Ex2 electromagnet (zones 2 and 22), 1450 N part no. 040190

Fuse 5 x 20, semi-timelag, 200 mA part no. 040586

Fuse carrier with bayonet catch part no. 040587

Fuse carrier with pivoting retaining bracket part no. 040588

Order Information

Dimensions

Dimensions, Application, Accessories

Fuse, Fuse Carrier

To protect the magnet from a possible short circuit, a fuse T 200 mA with a minimum breaking capacity of 1500 A has to be connected upstream to the magnet.

The fuse carrier with the fuse is placed directly into the feeding line to the magnet. There are available two different types of fuse carriers.- Fuse carrier for solding directly into the feeding line, with bayonet catch Dimensions of the fuse carrier: L = 43.2 mm, ø = 14.2 mm Suitable for cables with a cross section up to max. 4 mm- Fuse carrier for mounting on top hat rails, with pivoting retaining bracket

Fuse 5x20, semi-timelagFuse carrier with bayonet catch

Fuse carrier with pivoting retaining bracket

Connection of equipotential bonding

Page 45: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.045.00

DICTATOR explosion-proof electro-magnets belong to group II of explosion-proof devices and are authorised for use in hazardous locations of classification zones 1 and 2 (according to the standard VDE 0165), with the exception of underground pits.

Explosion-proof magnets are produced with encapsulated protection (EEX m).

All explosion-proof magnets are equipped with diodes (spark extinction diodes) and polarity protection.

DICTATOR explosion-proof electro-magnets have been tested according to EN 1155:2005 and also the directive 94/9/EG (ATEX).

They are reg is te red under the t y p e - e x a m i n a t i o n c e r t i f i c a t e IBExU14ATEX1211X/PTB 03 ATEX 2174 X and the confirmation of the conformity to building class PTB 03 ATEX N060-4 at the PTB Institute, Braunschweig/Germany. In addition they have been approved by the building authorities.

Ex-Proof ElectromagnetWith Cable or Terminal Box

Electromagnet EM GD 50 Ex... m EM GD 70 Ex... m

Voltage ±15 % 24 VDC 24 VDC Max. permitted ripple 20 % 20 % Power consumption (±15 %) 67 mA (1.6 W) 70 mA (1.7 W) Force / Remanence 600 N / 0 N 1450 N / 0 N Ex-protection cable design II 2G EEx m II T6 II 2G EEx m II T6 Ex-protection terminal box II 2G EEx em II T6 II 2G EEx em II T6 Protection / Duty cycle IP 66 / 100 % IP 66 / 100 % Operating temperature -20 to +40 °C -20 to +40 °C Finish magnet zinc-plated, terminal box grey laquered

Technical Data

Page 46: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.046.00

Order Information

Dimensions

The economic DICTATOR explosion-proof electromagnets with connection cable are recommended when a distributing box is available; either a normal one outside the hazardous location, or an explosion-proof box within the area. The magnets are pro-vided with a 2 m connection cable or the length indicated with the part number. Other lengths can be supplied on request.

The magnet is fixed to a base plate. There are four holes provided in the base plate for easy and fast installation.

Explosion-Proof Electromagnet with Connection Cable

Installation

The DICTATOR explosion-proof magnet is fixed to the wall behind the door that needs to be kept open. The connection cable must be securely embedded and sufficiently protected from mechanical damage (e.g. by using a cable channel).

A counter plate needs to be fixed to the door as a counterpart to the magnet. A selection of counter plates can be found following the descriptions of the electromagnets. Make sure that the diameter of the counter plate is at least the same, or larger than that of the magnet.

Important: The encapsulated DICTATOR types "EMGD...Ex...m" can directly be con-nected to the DICTATOR power packs (see page 07.019.00). However each magnet must be protected by a fuse (G 200 mA type semi-timelag) of max. 3 x IB according to IEC 60127-2-1 (connected in series), which corresponds to its rated current. On the mounting plate of the magnet a terminal is provided to connect the equipotential bonding conductor of a minimum cross section of 4 mm2 to assure the equipotential bonding.

Advice: According to fire protection regulations a hand switch must be installed beside the fire protection door to release it (explosion-proof hand switch, part no. 700232). Please observe the relevant regulations for hazardous areas when mounting and con-necting the electromagnet.

The dimensions in brackets are valid for the EM GD 50 Ex 30 m model

Countersink AM 5 (4) DIN 74

EMGD50Ex30m EEx m II T6 connection cable 2 m part no. 040154

EMGD70Ex43m EEx m II T6 connection cable 2 m part no. 040156

EMGD70Ex43m EEx m II T6 connection cable 5 m part no. 040156-5

EMGD70Ex43m EEx m II T6 connection cable 10 m part no. 040156-10

EMGD70Ex43m EEx m II T6 connection cable 15 m part no. 040156-15

Page 47: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124 Page 07.047.00

EMGD50Ex85m electromagnet EEx m/e II T6 protection part no. 040157

EMGD70Ex99m electromagnet EEx m/e II T6 protection part no. 040159

Both models are supplied with connection box and a M 20 x 1.5 gland

Explosion-Proof Electromagnets with Terminal BoxDICTATOR EM GD...Ex...em electromagnets are provided with an explosion-proof terminal box with own binders. The magnets can therefore be connected directly and no further explosion-proof distributing boxes are required. The cable is inserted into the terminal box through a tested ATEX M20x1.5 conduit gland. The connection cable should have an outer diameter of 5 to 10 mm and a maximum wire cross section of 2.5 mm2. The EM GD...Ex...em electromagnet has "Encapsulation (m)" protection and the terminal box has "Increased safety (e)" protection.

The dimensions in brackets are valid for EM GD 50 Ex 85 m model.

Dimensions

Installation The DICTATOR explosion-proof magnet with terminal box is fixed to the wall behind the door that needs to be kept open. For a secure installation we recommend our mounting plate, part no. 205252 (see following page), to which the magnet is screwed with 2 M4 screws.A counter plate needs to be fixed to the door as a counterpart to the magnet. A selection of DICTATOR counter plates can be found following the descriptions of the electroma-gnets. Make sure that the diameter of the counter plate is at least the same, or larger than that of the magnet.

Important: The encapsulated DICTATOR types "EMGD...Ex...m" can be connected directly to the DICTATOR power packs (see page 07.019.00). However each magnet must be protected by a fuse (G 200 mA type semi-timelag) of max. 3 x IB according to IEC 60127-2-1 (connected in series), which corresponds to its rated current. On the outside of the terminal box a terminal is provided to connect the equi-potential bonding conductor of a minimum cross section of 4 mm2 to assure the equipotential bonding.

Advice: According to fire protection regulations a hand switch must be installed beside the fire protection door to release it (explosion-proof hand switch, part no. 700232). Please observe the relevant regulations for hazardous areas when mounting and con-necting the electromagnet.

Order Information

The positons of M4-threads on back of magnet can be found on the following page (dimensions of the mounting plate).

Page 48: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

Electromagnets

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.048.00

110

95

63

80

65

52

2xM4

5,5

t = 4 mm

Mounting plate for explosion-proof magnets part no. 205252

Fuse 5 x 20, semi-timelag, 200 mA part no. 040586

Fuse carrier with bayonet catch part no. 040587

Fuse carrier with pivoting retaining bracket part no. 040588

We recommend you to use a mounting plate when installing magnets EM GD 50 Ex 85 and EM GD 70 Ex 99 on a porose surface to ensure they are securely fixed to the wall.

The magnet is screwed to the mounting plate and fixed to the wall with 4 screws.

Each magnet must be protected by a fuse of max. 3 x IB according to IEC 60127-2-1 (connected in series) (fuse G 200 mA type semi-timelag). DICTATOR furnishes the required fuses type 5x20, semi-timelag and the corresponding fuse carrier.

Order Information

The DICTATOR mounting plate is screwed to the wall behind the door that has to be kept open by the magnet with 4 ø5 flat head screws. The magnet is then fixed to the mounting plate with two M4-screws.

Mounting Plate

Dimensions

Accessories: Mounting Plate, Fuse

Countersink DIN 4 Am 5

The fuse is placed with the fuse carrier directly into the feeding line to the ex-proof magnet. There are available two different types of fuse carriers.- Fuse carrier for solding directly into the feeding line, with bayonet catch Dimensions of the fuse carrier: L = 43.2 mm, ø = 14.2 mm Suitable for cables with a cross section up to max. 4 mm- Fuse carrier for mounting on top hat rails, with pivoting retaining bracket

Fuse, Fuse Carrier

Fuse 5x20, semi-timelagFuse carrier with bayonet catchFuse carrier with

pivoting retaining bracket

Page 49: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.049.00

ElectromagnetFor Flush Mounting

Technical Data

DICTATOR electromagnets are mainly used for hold-open systems on fire protection doors. Electromagnets for flush mounting are the perfect solution when there is not enough space between the door and wall or when the magnet should be installed in a less visible way.

For the f lush instal lat ion of the EM GD 50 U 35 a standard flush box is required. This makes the installation very easy. The magnet is inserted into the flush box which then is covered with the white front plate delivered along with the magnet.

The magnet is provided with free cable ends to be connected in the flush box. It is equipped with a spark extinction diode. In the event of faulty connection, the integrated polarity protection prevents the spark extinction diode being destroyed.

The EM GD 50 electromagnet has been tested according to the EN 1155:2003 standard and is approved in combination with the DICTATOR smoke detectors RM 2000 and RM 3000+ by the German building authorities (approval no. Z 6.5-1903).

Voltage 24 VDC ± 15 %

Power consumption 67 mA (1.6 W)

Force 600 N

Duty cycle 100 %

Operating temperature -20 °C to +60 °C

Remanence 0 N

Finish body of the magnet zinc-plated

Front plate white (plastic)

Page 50: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.050.00

EM GD 50 U 35 electromagnet force 600 N part no. 041011

Installation

Order Information

Dimensions

All dimensions are in mm

The EM GD 50 U 35 magnet is inserted into a standard flush box (see below) and than fixed along with the plastic cover plate to the flush box. The magnet is connected to the 24 VDC power supply inside the flush box by luster terminals.

Further information for the correct installation of the magnet is to be found in the installation instructions provided with the magnet.

A selection of corresponding counter plates can be found later in this section.

Please note: It must be possible to release a fire protection door held open by an electromagnet with a hand switch which is not hidden by the open door. (DICTATOR hand switch part no. 040005, see diagram on left).

The flush box required for the EM GD 50 U 35 magnet is not included in the delivery. The magnet has been designed for standard flush boxes with a minimum depth of 35 mm and a distance between the fixing holes of 60 mm (see drawing below)

Flush Box

Page 51: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.051.00

DICTATOR electromagnets are used in hold open systems on fire protection doors. The EM GD 60 FB is designed for the installation on the floor.Its casing, made of cast aluminium is rugged and solid. This is very important as due to its position on the floor it is bound to be hit or knocked at by cleaning machines, vacuum cleaners or even people. Or the floor is mopped frequently and the casing is quite often in contact with water. As the casing is made of aluminium it will not rust. The floor magnet can be furnished either with or without a red interruptor key on the back of the casing. DICTATOR magnets are equipped with a spark extinction diode. In the event of faulty connection, the integrated polarity protection prevents the spark extinction diode being destroyed.

The EM GD 60 electromagnet for the installation on the floor has been tested and is together with the DICTATOR smoke detectors RM approved by the German building authorities (approval no. Z-6.5-1903).

ElectromagnetFor Installation on the Floor

Technical Data

Voltage 24 VDC

Power consumption 67mA ( 1,6 W)

Duty cycle 100 %

Operating temperature -20 °C up to +60 °C

Force 700 N

Remanence 0 N

Colour of casing black, structured

Page 52: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.052.00

165

140

60

107

93

24

3

3 X

Ø 9

11

60

10

0

The cable for the electric connection (24 VDC) of the magnet is run in the floor to the position, where the magnet is going to be fixed. The exact position has to be determined by opening the door and placing the magnet behind the opened door. If you have selected the magnet with interruptor key please make sure it is easily accessible.

Drill the holes for the dowels into the floor, using the template delivered with the magnet.

Connect the cable to the binders of the magnet and then fix the magnet with 3 screws to the floor.

A counter plate needs to be fixed to the door as a counterpart to the magnet (use one of the series AP GD 60...).The diameter of the counterplate must match the diameter of the electromagnet. A selection of counter plates can be found later in this section.

Please note:

It must be possible to release a fire protection door held open by an electromagnet with a hand switch which is not hidden by the open door (DICTATOR hand switch part no. 040005, see illustration on left).

Order Information

Dimensions

EM GD 60 FB electromagnet force 700 N part no. 040370

EM GD 60 FB oT without interruptor key force 700 N part no. 040371

Installation

Page 53: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1076

Electromagnets

Page 07.053.00

Technical Data

DICTATOR electromagnets with feed-back contact are used when information as to whether the counter plate adheres to the magnet (i.e. that the door is opened or closed) is required elsewhere. This is necessary for fire protection doors integrated in complex transport systems in big stores, for central control and monitoring systems or even for machines. When the counter plate adheres to the magnet and if this is supplied with tension, this is registered by an integrated contact (NO) which passes on the information to the area required. There are two models of magnets with feed-back contact: - with connection terminal on the base plate

(model RM, see ill.)- with a 4-pole plug-in termination (model ST). The corresponding connector is available as accessory.

Model RM and ST electromagnets have been tested and are approved together with the DICTATOR smoke detectors RM by the German building authorities (approval no. Z-6.5-1903).

Electromagnet With Feed-Back Contact (Models ST/RM)

EM GD Electromagnet Model RM Model ST

Voltage 24 VDC ±15 % Power consumption ±10 % see information on the following pages Force 600 N - 1450 N Duty cycle / Remanence 100 % / 0N Operating temperature -20 °C to +60 °C Finish magnet and mounting plate zinc-plated IP rating IP 20 IP 53 Contact type 1 x NO Switchable load max. 180 V DC/AC; max 0.5 A DC/AC

Page 54: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1076

Electromagnets

Page 07.054.00

The RM electromagnets are equipped with a connection terminal on the base plate for the 24 VDC power supply and the feed-back contact (NO). Due to this type of connection terminal the protection is IP 20. If a higher protection is required we recommend to use the ST model (see next page).

The electromagnet covers a large range of admissible switching voltages and currents.

Information concerning the correct installation are to be found on the page next but one.

Order Information

Dimensions

Electromagnet with Feed-Back ContactModel RM

EM GD 50 F26 RM Electromagnet force 600 N part no. 040395

EM GD 60 F26 RM Electromagnet force 700 N part no. 040396

EM GD 70 F39 RM Electromagnet force 1450 N part no. 040397

Countersink DIN74 - Am4

Type

Technical Data EM GD Electromagnet 50 F26 RM 60 F26 RM 70 F39 RM

Voltage 24 VDC ±15 %

Power consumption ±10% 67 mA (1.6 W) 67 mA (1.6 W) 71 mA (1.7 W) Force 600 N 700 N 1450 N Duty cycle 100 % Operating temperature -20 °C to +60 °C Remanence 0 N IP rating IP 20 Contact type 1 x NO Rupturing capacity max. 10 VA (for each combination current/voltage) Switchable load max. 180 V DC/AC; max. 0.5 A DC/AC

All dimensions in mm

a b d e f g i k l n

EM GD 50 F26 RM 55 44 44 75 5.5 Ø 4.5 3 Ø 50 26 18

EM GD 60 F26 RM 65 55 55 85 5 Ø 4.5 3 Ø 60 26 18

EM GD 70 F39 RM 75 60 60 95 7.5 Ø 5.5 4 Ø 70 39 19

Page 55: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1076

Electromagnets

Page 07.055.00

The ST model electromagnets with feed-back contact are equipped with a 4-pole plug-in termination. We provide the corresponding connector as accessory. The plug-in connection reduces the installation time, avoids errors when connecting the magnet and increases the IP rating of the magnet with the connection cable plugged-in.

The electromagnet covers a large range of admissible switching voltages and currents.

Information concerning the correct installation is to be found on the next page.

Order Information

Dimensions

Electromagnet with Feed-Back Contact Model ST

EM GD 50 F26 ST Electromagnet force 600 N part no. 040152

EM GD 70 F39 ST Electromagnet force 1450 N part no. 040153

Circular connector M12x1with connection cable part no. 040187

Type

Technical Data EM GD Electromagnet 50 F26 ST 70 F39 ST

Voltage 24 VDC ±15 % Power consumption ±10 % 67 mA (1.6 W) 71 mA (1.7 W) Force 600 N 1450 N Duty cycle 100 % Operating temperature -20 °C to +40 °C Remanence 0 N IP rating IP 53 (with connection cable plugged in) Contact type 1x NO Breaking capacity max. 10 VA (for each combination current/voltage) Switchable load max. 180 V DC/AC; max 0.5 A DC/AC

All dimensions in mm

Countersink DIN 74 Am4

a b c d g i k l m n

EM GD 50 F26 ST 55 44 60 44 Ø 4.5 3 Ø 50 26 14.5 81

EM GD 70 F39 ST 75 60 80 60 Ø 5.5 4 Ø 70 39 19.5 102

Page 56: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1076

Electromagnets

Page 07.056.00

The magnet is fixed to the wall behind the door that needs to be kept open. In case of sliding doors it is installed in the position of the opened door. A counter plate needs to be fixed to the door as a counterpart to the magnet. Make sure that the counter plate completely covers the magnet and that it lies straight on the magnet. A selection of counter plates can be found later in this section.

Please note: It must be possible to release a fire protection door held open by an electromagnet with a hand switch which is not hidden by the open door. (DICTATOR hand switch part no. 040005).

Electrical Connection

Electromagnet with Feed-Back Contact Installation

The electrical connection of the RM and ST models is different. The RM model can be used in any case as it is provided with a connection terminal. Each terminal is marked in order to make the connection as easy as possible.

The ST models are equipped with a 4-pole plug-in termination directly at the magnet. To connect this magnet there is required a circular connector M12x1 (part no. 040187). The ST model will be used especially in large installations or when the magnet is already installed during production of the doors or e.g. complete conveying systems. Installation time is reduced considerably due to the plug-in connector and errors are avoided.

Circular Connector M12x1

Pin Assignment Model ST

Pin Assignment

Magnet Circular connector

Technical Data

IP rating IP 67 (screwed on)

Load capacity 4 A, max. 250 V

Length of cable 10 m

Coupler straight

with swivel nut

Connector Colour of cable Connection

1 brown Power supply 24 VDC

2 white Power supply 24 VDC

3 blue Feed-back contact (NO)

4 black Feed-back contact (NO)

Page 57: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1095

Electromagnets

Page 07.057.00

The DICTATOR EM FH 266.5x82x55 three pole heavy duty magnet is designed for applications where very high holding forces are necessary (e.g. large doors, conveying systems etc.).

It consists of three single EM GD 70 magnets which are arranged in a white powder-coated casing (RAL 9010). This makes the heavy duty magnet a very economic solution when high forces are required, and easy to install, too.

The heavy duty magnet can also be provi-ded with a feedback contact (RM model). The feedback functions by measuring the changing of the magnet field when the counter plate lies against the magnet or not.

Both types have differing holding forces (see table).

To achieve maximum force the AP FH counter plate should always be used with the heavy duty magnet.

The DICTATOR heavy duty magnet is equipped with a spark extinction diode. In the event of faulty connection the integrated polarity protection prevents the spark extinction diode being destroyed.

Technical Data

Three Pole Heavy Duty MagnetWith Very High Forces (4350 N or 5100 N)

Electromagnet EM FH 266.5x82x55 FH 266.5x82x55 RM

Voltage 24 VDC ± 10 %

Power consumption 438 mA (10.3 W) 355 mA (8.5 W)

Force 5100 N 4850 N

Duty cycle / Remanence 100 % / 0 N

Operating temperature -20 °C to +40 °C

Finish magnet zinc-plated, casing white powder coated

IP rating IP 20

Feedback contact no yes

Page 58: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1095

Electromagnets

Page 07.058.00

266,5

45,575,875,8

55

82

6,3575,83x

8x ø 5,5

50,6

28

21

8 x 5,5

20

475

235

7373 767

266,5

45,575,875,8

55

82

6,3575,83x

8x ø 5,5

50,6

28

21

When using the three pole heavy duty magnet for doors, the magnet is mounted on the wall behind the door that needs to be kept open. The AP FH counter plate 235x75x20 is fixed to the door as a counterpart to the magnet. To achieve the indicated force and have a feedback contact, make sure that the counter plate completely covers the single magnets and that it lies evenly.

Remove the magnet casing when installing and screw the mounting plate with the three magnets to the wall. A terminal is provided on the base plate for the electrical connection. The connection cable is introduced via a rubber funnel in the side of the casing. Screw the casing back on the base plate after mounting and wiring.

Installation

Dimensions

Order Information EM FH 266.5x82x55 electromagnet force 5100 N part no. 040270

EM FH 266.5x82x55 RM electromagnet force 4850 N part no. 040271RM

AP FH 235x75x20 counter plate part no. 040290

AP FH 235x75x20 Counter plate

EM FH 266.5x82x55 Electromagnet

Interior view with fixing dimensions of mounting plate

Page 59: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.059.00

Voltage 24 VDC ±10 % Power consumption 88 mA (2.1 W) Force 400 N Duty cycle 100 % Operating temperature -20 °C to +40 °C Remanence 4 N Finish zinc-plated IP rating IP 20 (DIN 400 50)

Bar MagnetHigh Holding Force - Small Size

Technical Data

The DICTATOR EM FH bar magnet 100x24x27 is the perfect solution when a normal (round) electromagnet with a comparable holding force does not fit. With a width of only 24 mm the narrow bar magnet can also be placed unobtrusively in applications with restricted space (e.g. in smoke vents in the window frame). Its 400 N holding force is very high and corresponds to that of a round electromagnet with a diameter of at least 40 mm.

The bar magnet is placed on a mounting plate along with a connection terminal. This facilitates installation and the electrical connection.

Due to its small, narrow dimensions the bar magnet is not provided with a release pin. However the remanence of the magnet is only 4 N.

The DICTATOR bar magnet is equipped with a spark extinction diode. In the event of faulty connection the integrated polarity protection prevents the spark extinction diode being destroyed.

Page 60: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.060.00

30

70

56

s = 5

4,5

6

3

27

18 23,5

1062

100

5

5

4,5

Senkung DIN 74 Am4

EM FH 100x24x27 bar magnet force 400 N part no. 040273

AP FH 70x30x5 counter plate part no. 040291

When using the bar magnet on windows it is fixed with 2 M4 screws in a recess of the frame. The AP FH 70x30x5 counter plate is mounted on the window as a counterpart to the magnet. Make sure that the counter plate completely covers the bar magnet and lies straight.

A two-channel terminal is provided on the mounting plate for the electrical connection to the 24 VDC power supply.

EM FH 100x24x27 Bar magnet

Installation

Dimensions

Order Information

AP FH 70x30x5 Counter plate Countersink ø 8.2x90°, 1 mm deep

Countersink DIN 74 Am4

Page 61: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.061.00

Voltage 24 VDC ± 10 %

Power consumption 67 mA (1.6 W)

Duty cycle 100 %

Operating temperature -20 °C to +60 °C

Force 130 N

Remanence max. 10 N

Finish zinc-plated

IP rating IP 20

Electrical connection cable, length 240 mm

The DICTATOR electromagnets go into the most different applications. Apart from magnets for the approved use on fire protection doors DICTATOR magnets are used amongst others in the machine construction sector (e.g. locking access doors to machining centres with feed-back contact) or the building sector (e.g. to keep windows or flaps locked/opened).

One of the most important features of the DICTATOR electromagnets is their low power consumption combined with the highest possible force.

The smallest magnet of the DICTATOR magnet line is the EM GD 20. Due to its very small dimensions ( 20 mm) it can be placed unobtrusively also in applications with restricted space. In order to facilitate its installation the magnet EM GD 20 is furnished in two designs: one with mounting plate and one without (this is provided with a threaded hole at the bottom of the magnet).

20 mm Electromagnets

Technical Data

with Free Leads, without Release Pin

Page 62: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Electromagnets

Page 07.062.00

3023 3

14,5

5,5

ø 2

9

30

24

ø 2,4Senkung Am DIN 74

30

23

26

22

330

4 x

ø 3

20

24

R 12

,3 5AA-A

A

20

M4

Dimensions

Order Information

All dimensions in mm

EM GD 20 A 24 electromagnet force 130 N part no. 040380

EM GD 20 B 26 electromagnet force 130 N part no. 040381

AP GD 25 G 15 counter plate part no. 040024

EM GD 20 A 24 Electromagnet

EM GD 20 B 26 Electromagnet

Counter plate AP GD 25 G 15

In order to achieve the maximum force of the magnet, the counter plate AP GD 25 has to be used together with the magnets. On demand it can also be supplied without its mounting plate. When fixing the counter plate make sure it completely covers the magnet.

Installation

Countersink DIN 74Am

Page 63: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.063.00

AP GD 40 G 14 counter plate Ø 44 part no. 040089

AP GD 50 G 16 counter plate Ø 54 part no. 040025

AP GD 60 G 16 counter plate Ø 64 part no. 040039

AP GD 60 G 30 counter plate Ø 64 part no. 040096

AP GD 60 G 60 counter plate Ø 64 part no. 040084

AP GD 70 G 20 counter plate Ø 74 part no. 040026

DICTATOR counter plates provide the safe and reliable connection between door and electromagnet.

Model G counter plates consist of a zinc- plated mounting plate, an elastic joint and a smooth, zinc-plated anchor plate.

To achieve maximum holding force the anchor plate should always have at least the same diameter as the electromagnet and lie flat against the magnet face.

The elastic joint between anchor and mounting plate compensates for an angle of up to 10° between door and magnet.

Model G flexible counter plates have been tested in combination with DICTATOR electromagnets.

Flexible Counter Plate With Elastic Joint (Model G)

Order Information

Page 64: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.064.00

QM

L

P

OO

N

K P

When fixing DICTATOR counter plates to the door make sure they completely cover the magnet.

It is important not to damage the surface of the counter plate (e.g. by scratches or pain-ting) as this would reduce the force of the magnet.

Important: It is imperative to follow the instructions given by the door manufacturer when installing the counter plates.

Installation

DimensionsCountersink Am DIN 74

All dimensions are in mm.

Counter plate K L M N O P Q

AP GD 40 G 14 Ø 44 14 5.5 3 50 40 Ø 4.5

AP GD 50 G 16 Ø 54 16 7 3 55 44 Ø 4.5

AP GD 60 G 16 Ø 64 16 7 3 65 55 Ø 4.5

AP GD 60 G 30 Ø 64 30 7 3 65 55 Ø 4.5

AP GD 60 G 60 Ø 64 60 7 3 65 55 Ø 4.5

AP GD 70 G 20 Ø 74 20 10 4 75 60 Ø 5.5

Page 65: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.065.00

AP GD 40 W 50 counter plate Ø 44 part no. 040072

AP GD 50 W 50 counter plate Ø 54 part no. 040027

AP GD 60 W 50 counter plate Ø 64 part no. 040070

AP GD 70 W 54 counter plate Ø 74 part no. 040068

Counter Plate

DICTATOR counter plates provide the safe and reliable connection between door and electromagnet.

Due to its angular joint the counter plate allows for an angle compensation between door and magnet of maximum 60° in both directions. The counter plate is fixed in the required position. Smaller angle deviations are compensated by an elastic element between plate and base.

To achieve maximum holding force the counter plate should always have at least the same diameter as the electromagnet and lie flat against the magnet face.

The flexible counter plates with angular joint have been tested in combination with DICTATOR electromagnets.

With Angular Joint

Order Information

Page 66: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.066.00

ø K

60ø 6,1

60 44

L

6M

60 60

K L M

AP GD 40 W 50 Ø 44 50 5,5

AP GD 50 W 50 Ø 54 51 7

AP GD 60 W 50 Ø 64 51 7

AP GD 70 W 54 Ø 74 54 10

Counter plate

Counter plate

Counter plate

Counter plate

Installation

Dimensions

When fixing DICTATOR counter plates to the door make sure they completely cover the magnet.

It is important not to damage the surface of the counter plate (e.g. by scratching or pain-ting) as this would reduce the force of the magnet.

Important: It is imperative to follow the instructions of the door manufacturer when installing the counter plates on fire protection doors.

Pivoting range

All dimensions are in mm.

Counter plate

Page 67: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.067.00

Telescopic Counter Plate

DICTATOR counter plates are used to provide the anchor for DICTATOR electromagnets. The integrated spring on telescopic counter plates dampens the impact of the doors on the magnet. They are therefore particularly recommended for big, heavy doors. They ensure the magnet remains on the counter plate even when the door hits the magnet at high speed and force. They also reduce unnecessary wear and tear on the door and magnet. The spring force is about 100 N on a stroke of 20 mm.

The new telescopic counter plates combine the advantages of both previous telescopic counter plates in one design: rugged and solid construction, a modern design and economic production.

The casing is made of fiberglass reinforced plastic. Due to the flexible joint below, the armature plate itself can compensate for angles up to 10° between magnet and counter plate. A spring integrated in the casing damps the impact of the door on the magnet. This prevents the door from springing back.

The counter plates have been tested in combination with DICTATOR electro-magnets.

with Damping

Material of the casing PA 66, glass-fiber reeinforced

Colour of the casing anthracite

Armature plate zinc-plated steel

Damping force 100 N on a stroke of 20 mm

Technical Data

Page 68: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Counter Plates

Page 07.068.00

AP GD 50 T 80 Ø 54 80 7

AP GD 60 T 80 Ø 64 80 7

AP GD 70 T 84 Ø 74 84 10

L

M

20

ø 8

2

ø 7

8

4xø 4,5

55

55

ø K

AP GD 50 T 80 counter plate Ø 54 part no. 040071

AP GD 60 T 80 counter plate Ø 64 part no. 040028

AP GD 70 T 84 counter plate Ø 74 part no. 040029

The telescopic counter plate casing is fixed to the door with 4 M4 countersunk head screws. When fixing the telescopic counter plate, make sure that the surface of the plate lies flat against the magnet face and covers it completely. To achieve maximum holding force, the diameter of the counter plate must be at least the same as that of the magnet.

The surface of the counter plate must not be damaged (e.g. by scratching and painting) as this would reduce the holding force of the magnet.

Important: it is imperative to follow the instructions of the door manufacturer when moun-ting the counter plate on fire protection doors.

Installation

Dimensions

All dimensions in mm

Counter plate K L M

Order Information

Page 69: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Accessories Electromagnets

Page 07.069.00

Brackets for ElectromagnetsFor Easier Mounting

Technical Data

DICTATOR offers a distance bracket for the wall or floor and a telescopic bracket for fixing electromagnets. In certain situations they make mounting electromagnets much easier and faster.

The two different types characterize as follows:

- Distance bracket for floor and wall mounting. The head can be swiveled up to 180° and thus can adapt to the most different hitting angles of the door. The height of the console can be adjusted up to 70 mm. The base plate of the magnet is screwed to the bracket (4 Allen head screws are included in the delivery). When choosing the appropriate console for the base plate of the electromagnet you have to consider the distance between the borings and their diameter.

- Telescopic bracket The telescopic bracket allows to easily ad-

apt the mounting position of the magnet on site. It offers a very large adjusting range and is extremely robust. That predestines it especially for heavy duty applications (e.g. in schools).

Floor/wall distance bracket

Telescopic bracket

Adjusting range head can be swiveled up to 180°

inclination of arm 90 - 136°

Adjustability of height 145 - 215 mm 388 - 520 mm

Hole pattern designed for EM GD 50 and 60 EM GD 50, 60 and 70

Material/Finishing sheet steel, powder-coated in white (RAL 9010)

Page 70: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

AccessoriesElectromagnets

Page 07.070.00

DimensionsDistance Bracket

Distance bracket white, fixing measures 44x44 mm/M4 part no. 040124

Distance bracket white, fixing measures 44x44 mm/M5 part no. 040126

Distance bracket white, fixing measures 55x55 mm/M4 part no. 040127

Telescopic bracket white, oblong fixing holes part no. 040147

Order Information

Dimensions and Part Numbers

Allen head screw "a"

Swivel range 180°

All dimensions in mm

Bracket a Dimension b appropriate for magnets (e.g.)

040124 M4 44 mm EM GD 50 R26, R26I, F26

040126 M5 44 mm special types as EM GD 50 F25T

040127 M4 55 mm EM GD 60 R26, R26I, F26

All dimensions in mm

Dimensions Telescopic Bracket

Page 71: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124

Accesso-

Page 07.071.00

German fire protection regulations state that a switch with an appropriate inscription is obligatory for hold-open systems on fire protection doors.

The DICTATOR hand switch meets these demands. The fire-protection door is released by pressing the hand switch.

The hand switch is also available for flush mounting.

In hold-open systems with DICTATOR RM 3000+ smoke or WM 3000+ heat detectors and DICTATOR electromagnets, connect the hand switch to the first smoke or heat detector.

The hand switch should be mounted beside the door in a clearly visible position when the door is open.

Order Information

Hand Switch for Hold-Open Systems

Hand switch for surface mounting part no. 040005

Rocker red without print for hand switch no. 040005 part no. 040005WRN

Rocker white without print for hand switch no. 040005 part no. 040005WWN

Hand switch for flush mounting part no. 040053

Page 72: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1124Page 07.072.00

Accessories

DimensionsHand switch for surface mounting

Hand switch for flush mounting

Elec

trica

l con

nec-

tions

Page 73: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • Email [email protected] • 1124

Accessories Fire Protection HLS-Catch Temperature Bolt

Page 07.073.00

Technical Data

Perfectly functioning fire and smoke protection doors are an indispensable requirement for preventing and limiting damage. Especially with hinged doors, the great heat of a fire might cause the door to distort. This could produce a dangerous gap through which the fire could spread further, in spite of the fire protection door.

The Hot-Locking-Safe temperature bolt offers protection for life and material in a simple and unobtrusive way. The temperature bolt is installed in the frame or the door at those places where there is the highest danger of a gap occurring. Normally the bolt is retracted in the casing and locked there by the soldered strut. Only when the surrounding temperature rises to about 600 °C and the HLS bolting has reached about 65 °C the soldered strut melts and the spring in the back of the cylinder can push out the bolt. This fixes the door securely to the frame and the door leaf cannot distort.

IMPORTANT: The HLS-catch temperature bolt may only be installed in accordance with the respective door producer.

HLS-Catch Temperature BoltSafely Closed Fire Protection Doors - Without Gap

Material casing zinc-plated steel

Material soldered strut Hotmelt

Melting point at a surrounding temperature of 600 °C

Spring force approx. 11 N

Application area hinged fire protection doors T30 and T60

Door types timber and steel doors with timber or steel frames

Test DIN EN 1634-1:2000

Page 74: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • Email [email protected] • 1124

Accessories Fire ProtectionHLS-Catch Temperature Bolt

Page 07.074.00

DimensionsTV2003-50

HLS-catch TV2003-50, Hotmelt, 23 mm stroke part no. 710715

Installation Example

Order Information

Usually the HLS-catch temperature bolt is installed in the frame. However, it is also possible to fit it into the door leaf. The number and the position have to be decided upon together with the door manufacturer.

It is very important that both HLS-catch and its counter plate are installed exactly opposite each other.

Casing with internal spring Counter plateFront plate

Stroke = 23 mm

Page 75: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1045 Page 07.075.00

Door Sequence Selector

Door Sequence Selectors For double-leaf hinged fire and smoke protection doors it is mandatory to be equipped with a door sequence selector. The tested DICTATOR door sequence selectors make sure that the door leaves close in the right order and thus reliably prevent the spreading of fire and smoke.

DICTATOR provides two different door sequence selector models:

- SR 90 door sequence selector with usual lever arm and support brackets as an economic model.

- SR 2000 door sequence selector with or without electromagnetic locking of the lever arms. The SR 2000 is designed especially for two-leaved hinged fire doors meeting high aesthetic requirements. The SR 2000 can be mounted unobtrusively below the door frame behind both door leaves. Model SR 2000 E is provided with an electromagnet keeping both arms of the selector folded in, unless one of the connected smoke detectors switches to alarm and cuts the power supply to the magnet.

The DICTATOR door sequence selectors have been tested and approved on hinged fire protection doors with two leaves according to DIN EN 1158.

Product Overview SR 90 door sequence selector door sequence selector with 2 support brackets

SR 2000 door sequence selector compact unit without support brackets,

with/without locking of the integrated arms

Material zinc-plated steel

Page 76: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1045Page 07.076.00

Door Sequence Selector

(1)

(2)

The DICTATOR SR 90 door sequence selector remains unfolded when only the finally locking leaf is opened. Every time both door leaves are opened the telescopic arm of the door sequence selector SR 90 is automatically set in an upright position by the integrated leg spring.

The door sequence selector controls the correct closing sequence of both door leaves:

The door leaf to close finally (locking door leaf) hits the door sequence selector's telescopic arm with the pin of the support bracket and is kept in this position ...

until the latch leaf with support bracket moves laterally across the door sequence selector's telescopic arm and...

during closing takes the telescopic arm back with it to its closed position. When the telescopic arm lies flat against the door frame, the locking leaf is released and ...

can now close.

Operation SR 90

Operation

Operation SR 2000

selector. This also folds in the telescopic arm (1) and sets the active leaf free. Then the active leaf can also close.If only the active leaf is opened, both SR 2000 door sequence selector arms remain folded in.The SR 2000 E model will unfold its arms only after an alarm of one of the connected smoke detectors.

As soon as both door leaves open, the SR 2000 door sequence selector's telescopic arm is acti-vated by the integrated traction spring. During closing the active (locking) door leaf, which is required to close last, hits the door sequence selector's telescopic arm (1) with its back and stays in this position until the closing passive leaf (latch leaf) touches the release roller of the small arm (2) and folds in the small arm of the door sequence

Page 77: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1045 Page 07.077.00

Door Sequence Selector

20

45,5

60

120

535

ø22

ø189

304

47

max. 72°min. 30°

45

40

50

25

50

4580

113

23

80

ø16

8,1

20

45,5

60

120

535

ø22

ø189

304

47

max. 72°min. 30°

45

40

50

25

50

4580

113

23

80

ø16

8,1

Door Sequence Selector SR 90 Dimensions, Technical Data

Dimension A

Door leaf

Bm8 DIN 74 countersink

M8x20 with hexagon socket SW 4

Dimensions SR 90

Order Information

Technical Data

The SR 90 door sequence selector has a telescopic arm which automatically sets itself in an upright position when both door leaves are opened. As counter piece a support bracket has to be mounted on both door leaves.

Detailed information on mounting is given in the mounting instructions. There is also explained how to determine the dimension A shown in the dimensioned drawing.

Components Included

M8 DIN 439 SW 13 nut

Door frame

SR 90 door sequence selector, zinc-plated, with accessories part no. 500420P

Weight of door leaf max. 160 kg per door leaf

Width of door leaf up to 1.60 m per door leaf

Space required above the door min. 30 mm

Setting up angle 30° to 70°

SR 90 door sequence selector with telescopic arm

2 support brackets with pin and polyamid tube

1 cylinder head stud M8 x 16 DIN 7984

5 hexagon socket screws M8 x 16 DIN 7991

Page 78: Fire Door Control Solutions · CAO en mH tenest 5 es emany Tel 021-2-0 a 021-2-0 -mal nfodtatode 1015 Holdpen Sstems ae 000200 Components Power pack Page 07.019.00 et sqq. Smoke detectors

© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • GermanyTel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 1045Page 07.078.00

Door Sequence Selector

m

ax.115

L466 / 866139

R 100

45

40 14

R2002x ø 5,5

20

S

The SR 2000 door sequence selector (see the illustration on the left) doesn't need any separate support brackets. In particular the model with integrated electromagnet fits absolutely unobtrusively in the appearance of the door.

Door Sequence Selector SR 2000 Dimensions, Technical Data

Dimensions SR 2000

Technical Data

15.0 x 1.5 mm washers

Type Dimension L

L 1050

K 650

Order Information

Passive leaf

Active leaf

Weight of door leaf max.160 kg per door leaf

Width of door leaf 0.75 m to 1.50 m per door leaf

Space required below the door frame 20 mm

Setting up angle max. 115°

Electromagnet (only with SR 2000 E model) 24 VDC/42 mA

SR 2000 L door sequence selector (long version) part no. 500430

SR 2000 EL door sequence selector (with magnetic hold-open) part no. 500431

SR 2000 K door sequence selector (short version) part no. 500435

SR 2000 EK door sequence selector (with magnetic hold-open) part no. 500436

Supervision of Rotation Angle

If the SR 2000 E door sequence selector with electromagnet is used together with a door closer or a door operator which has an integrated hold-open, these devices have to include a so-called supervision of the rotation angle. This makes sure the power supply of the electromagnet is switched off as soon as the active leaf is closed manually. Then the telescopic arm is activated and can support the active leaf.