fire protection legend - himmelman · pdf filesprinkler system piping ... all symbols may not...
TRANSCRIPT
CONNECT NEW TO EXISTING
# REFERENCE DRAWING NUMBER
* ISOMETRIC OR ELEVATION LETTER
ISOMETRIC OR ELEVATION BUBBLE
# REFERENCE DRAWING NUMBER
* SECTION OR ELEVATION LETTER
SECTION OR ELEVATION BUBBLE
REVISION NUMBER
REFERENCE BUBBLE # SHEET NUMBER * SECTION NUMBER
DRAWING NOTE
DEMOLITION NOTE
75 PSIG
NOT TO SCALE1
1. INFORMATION OBTAINED FROM ARVADA WATER DEPT. ON 07-08-2016.
STATIC PRESSURE RESIDUAL PRESSURE FLOW GPM
90 PSIG 1,500 GPM
FIRE PROTECTION WATER SUPPLY
FIRE DEPARTMENT CONNECTION
SPRINKLER SYSTEM PIPING
STAND PIPE SYSTEM PIPING
COMBINATION SPRINKLER/STANDPIPE PIPING
DRAIN PIPING
FLOW SWITCH
ISOLATION VALVE W/ TAMPER SWITCH
ANGLE VALVE
PRESSURE GAUGE
REDUCER
BALL VALVE
CHECK VALVE
SIAMESE
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
PENDANT SPRINKLER
EXISTING FIRE SPRINKLER
NEW FIRE SPRINKLER
NEW FIRE SPRINKLER RELOCATED TO NEW LOCATION
FIRE SPRINKLER TO BE REMOVED AND REPLACED IN THESAME LOCATION
ROOF MANIFOLD
ALL SYMBOLS MAY NOT BE USED
DESCRIPTIONSYMBOL
HORN AND STROBE
SPRINKLERBRANCHLINE
STAINLESS STEEL BRAIDEDSPRINKLER DROP
ADJUSTABLE HUB
CEILING TILE
SPRINKLER HEAD
SUSPENDED T-BAR GRID
MULTI-PORT CEILINGGRID MOUNTING
BRACKET
FIRE SPRINKLER SERVICE ENTRY DETAIL (EXISTING)
PIPE SADDLESUPPORT (TYP.)
(E) CAP
(E) FLOW SWITCH (TYP.)
(E) 2" ANGLE MAINDRAIN VALVE (TYP.)
(E) MANIFOLD MAINDRAINS & EXTEND TOFLOOR SINK
TO FDC
(E) FBFP
TO Z
ON
E #
1
TO Z
ON
E #
2
TO Z
ON
E #
3
(E) BUTTERFLY VALVE W/INTEGRAL TAMPERSWITCH (TYP.)
FINISHED GRADE
(E) ROD AND SLEEVEPER NFPA
5'-0"
FEBCO
FEBCO
FLOW TEST DATA
FIRE SPRINKLER GENERAL NOTES1. FIELD VERIFY BUILDING CONDITIONS PRIOR TO COMMENCING DESIGN
RELATED WORK.
2. COORDINATE FIRE SPRINKLER SYSTEM INSTALLATION WITH OTHER TRADES
AND BUILDING COMPONENTS PRIOR TO COMMENCING FABRICATION;
RELOCATE SPRINKLER SYSTEM COMPONENTS FOUND TO BE IN CONFLICT
WITH OTHER BUILDING SYSTEMS.
3. INSTALL SPRINKLER SYSTEM COMPONENTS AND PIPING TO ALLOW FOR
ACCESS TO CEILING CAVITY AND TO OTHER SYSTEMS EQUIPMENT MOUNTED
ABOVE CEILING.
4. PROVIDE ADDITIONAL OR MODIFY EXISTING SIGNAGE, LABELING AND
IDENTIFICATION AS REQUIRED BY NFPA AND LOCAL JURISDICTIONAL
AUTHORITY.
5. DESIGN AND INSTALLATION OF THE FIRE SPRINKLER SYSTEM SHALL COMPLY
WITH ALL APPLICABLE NFPA AND LOCAL JURISDICTIONAL REQUIREMENTS,
REVISE SPRINKLER SYSTEM INSTALLATION FOR FULL COMPLIANCE AS
REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
6. DRAIN AND TEST OUTLET CONNECTIONS SHALL BE DISCHARGED TO THE
BUILDING EXTERIOR OR TO A PROPERLY SIZED RECEPTOR WITHIN THE
BUILDING; DRAIN AND TEST OUTLET LOCATIONS SHALL BE IDENTIFIED ON
SHOP DRAWINGS FOR REVIEW AND APPROVAL.
7. COORDINATE ALL ELECTRICAL AND FIRE ALARM CONNECTIONS WITH EC
PRIOR TO INSTALLATION.
8. REFER TO PROJECT MANUAL FOR SPRINKLER TYPES AND INSTALLATION
REQUIREMENTS.
9. THE FIRE SPRINKLER SYSTEM INFORMATION CONTAINED ON THE PLANS IS
PROVIDED AS A GUIDE FOR THE FIRE SPRINKLER SYSTEM
DESIGNER/INSTALLER AND IS NOT INTENDED TO SHOW ALL REQUIRED
SYSTEM COMPONENTS; IT SHALL BE THE FIRE SPRINKLER SYSTEM
DESIGNER/INSTALLERS RESPONSIBILITY TO PROVIDE A COMPLETE,
APPROVED AND OPERATIONAL FIRE SPRINKLER SYSTEM IN ACCORDANCE
WITH NFPA AND THE LOCAL JURISDICTIONAL REQUIREMENTS.
10. COORDINATE INSTALLATION LOCATION OF ALL EXPOSED SPRINKLER SYSTEM
PIPING WITH ARCHITECT AND GENERAL CONTRACTOR PRIOR TO
INSTALLATION.
11. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF NFPA 13.
12. REFER TO PROJECT MANUAL FOR OCCUPANCY HAZARD CLASSIFICATIONS.
ALL AREAS OF THE BUILDING SHALL BE CONSIDERED LIGHT HAZARD
OCCUPANCY UNLESS REQUIRED OTHERWISE BY NFPA OR LOCAL
JURISDICTIONAL FIRE AUTHORITY.
DESCRIPTIONSYMBOL
GENERAL
#*
#
#*
#*
F
FDC
SP
ST
SP/ST
D
E
N
R
D
FIRE PROTECTION LEGEND
2 FLEXIBLE FIRE SPRINKLER HEAD DETAILNOT TO SCALE
REFER TOPLUMBING
PLANS
(E)S
T
(E)S
P
(E)S
P
(E)S
P
1
1
1
1
(E)FBFP
(E)B-1B-2
(E)GWH-1
(E)GWH-2
E.E E.F
E.2
E.3
E.4
(E)F
DC
DRAWING NOTES #
1. ADD SIGNAGE FOR ZONE ARRANGEMENT AT EXISTING FIRE RISERS.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
09 A
M
FP-001
FIRE PROTECTIONLEGENDS &SCHEDULES
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
1/4" = 1'-0"
ENLARGED FIRE PROTECTION PLAN - BOILER ROOM1
PLAN NORTH
REVISION DATE
1
FP-001
1 2 3 4
6
5
89 10
12
13
A
B
C
E
G
K
L
J
M
D
F
H
6.5
E.AE.B E.C E.D E.EE.FE.G E.H E.J
E.1
E.2
E.3E.4
E.5
E.6
E.7
E.8
E.9
E.10
7
SP
4
3
2
SP
SP
SPSP
(E) FDC
4
5
FDC
SPSP
SP
1
6
8
10
9
10
9
9
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
1 2 3
89 10
12
A
B
C
E
G
K
L
J
M
D
F
H
6
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
DRAWING NOTES #
1. FIRE SPRINKLER ZONE 2. EXTEND FIRE SPRINKLER PIPING THIS FLOOR.
2. FIRE SPRINKLER PIPING DOWN INTO ELEVATOR SHAFT, PROVIDE SIDEWALL SPRINKLERAT ELEVATOR PIT PER NFPA.
3. CONNECT TO EXISTING FIRE SPRINKLER PIPING STUBS ABOVE CEILING AND EXTEND TOZONES INDICATED.
4. MODIFY EXISTING FIRE SPRINKLER TO ACCOMMODATE NEW CEILING PER NFPA 13.
5. PROVIDE ISOLATION VALVE WITH TAMPER SWITCH AND FLOW SWITCH FOR ELEVATOR FIRE SPRINKLER, COORDINATE WITH FIRE ALARM SYSTEM INSTALLER FOR REQUIRED ALARM CONNECTION.
6. PROVIDE UPRIGHT SPRINKLERS WITH WIRE GUARDS IN ELECTRICAL ROOMS, COORDINATESPRINKLER PIPE ROUTING AND SPRINKLER LOCATIONS WITH E.C. PRIOR TO INSTALLATION.
7. FIRE SPRINKLER ZONE 3 MAIN UP TO FLOOR ABOVE, SEE PLAN AT LEFT FOR CONTINUATION.
8. PROVIDE INTERMEDIATE TEMPERATURE SPRINKLERS AT KILN ROOM, COORDINATE LOCATION OF SPRINKLERS WITH KILN AND ASSOCIATED HOOD LOCATIONS PRIOR TO INSTALLATION.
9. PROVIDE SPRINKLER COVERAGE BELOW EXPOSED STAIR, PROVIDE WIRE GUARDS WHERESPRINKLERS ARE LOCATED 8'-0" OR LESS ABOVE FINISHED FLOOR.
10. PROVIDE UPRIGHT SPRINKLERS WITH WIRE GUARDS IN STORAGE AREAS.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
14 A
M
FP-101
FIRE PROTECTIONPLANS
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLA
N N
OR
TH
PLAN NORTH
1" = 20'-0"
01.Fire Protection Level 1 - Overall1 1" = 20'-0"
02.Fire Protection Level 2 - Overall2
REVISION DATE
F
P
PLUMBING LEGENDALL SYMBOLS MAY NOT BE USED
DESCRIPTIONSYMBOL
PLUMBING GENERAL NOTES
DESCRIPTIONSYMBOL
GENERAL
STORM DRAIN, RAINWATER DRAINSD
OVERFLOW STORM DRAINOD
SUBSOIL DRAIN, FOOTING DRAINSSDSOIL, WASTE, OR SANITARY SEWERSAN
STORM / RAINWATER DRAIN BELOW FLOORSD
SOIL / WASTE / SANITARY SEWER BELOW FLRSAN
GREASE DRAINGDVENT
ACID WASTEAW
ACID VENTAV
INDIRECT DRAINDPUMP DISCHARGE LINEPD
COLD WATER
HOT WATER SUPPLY (140° F)
HOT WATER RECIRCULATING (140° F)TEMPERED HOT WATER (110° F)TW
TEMPERED HW RECIRCULATING (110° F)TWR
(CHILLED) DRINKING WATER SUPPLYDWS
(CHILLED) DRINKING WATER RECIRCULATINGDWRSOFT WATERSW
CONDENSATE DRAINCD
DISTILLED DRAINDI
DEIONIZED WATERDELAWN SPRINKLER SUPPLYLS
FIRE PROTECTION WATER SUPPLYF
GAS, LOW-PRESSUREG
GAS, MEDIUM-PRESSUREMGGAS, HIGH-PRESSUREHG
GAS VENTGV
FUEL OIL SUPPLYFOS
FUEL OIL RETURNFORFUEL OIL VENTFOV
LUBRICATING OILLO
LUBRICATING OIL VENTLOV
WASTE OILWOWASTE OIL VENTWOV
OXYGENOX
LIQUID OXYGENLOX
COMPRESSED AIRAMEDICAL COMPRESSED AIRMA
LABORATORY COMPRESSED AIRLA
VACUUMV
MEDICAL VACUUMMVSURGICAL VACUUMSV
LABORATORY VACUUMLV
NITROGENN
NITROUS OXIDENO²CARBON DIOXIDECO²
WET VACUUM CLEANINGWVC
DRY VACUUM CLEANINGDVC
ISOLATION VALVE
GLOBE VALVE
ANGLE VALVE
BALL VALVE
BUTTERFLY VALVE
GAS COCK, GAS STOP
COMBINATION FLOW MEASURINGDEVICE AND BALANCING VALVE
CHECK VALVE
PLUG VALVE
SOLENOID VALVE
S
MOTOR-OPERATED VALVE [SPECIFY TYPE]
M
PRESSURE REDUCING VALVE
PRESSURE-RELIEF VALVEP
TEMPERATURE-PRESSURE-RELIEF VALVET
HOSE BIBB
VALVE IN YARD BOX (VALVE TYPE SYMBOLAS REQUIRED FOR VALVE USE)
RECESSED-BOX HOSE BIBB ORWALL HYDRANT
UNION (SCREWED)
UNION (FLANGED)
STRAINER
PIPE ANCHOR
PIPE GUIDE
EXPANSION JOINT
FLEXIBLE CONNECTOR
TEE
CONCENTRIC REDUCER
ECCENTRIC REDUCER
AQUASTAT
FLOW SWITCH
PRESSURE SWITCH
WATER HAMMER ARRESTER
PRESSURE GAUGE WITH GAUGE COCK
THERMOMETER
VALVE IN RISERRISER DOWN (ELBOW)
RISER UP (ELBOW)
AIR CHAMBER
RISE OR DROP
BRANCH-TOP CONNECTION
BRANCH-BOTTOM CONNECTION
BRANCH-SIDE CONNECTION
CAP ON END OF PIPE
CLEANOUT PLUG
CIRCULATION PUMP
FLOOR CLEANOUT
WALL CLEANOUT
YARD CLEANOUT OR CLEANOUT TO GRADE
FLOOR DRAIN
FLOOR SINK
CONDUCTOR NOZZLE
DIRECTION OF FLOW
INDICATES PIPE SLOPE DOWN
NEW TO EXISTING CONNECTION
INDICATES ITEMS TO BE REMOVED
GAS TURRET
NOTE:
1. COORDINATE AND SCHEDULE WITH GAS SERVICE AND METER PROVIDER PRIOR TO COMMENCING WORK. LOW PRESSURE GAS (14" W.C.) REQUIRED
FROM THE METER TO THE BUILDING. CONTACT THE BUILDER CALL LINE PRIOR TO COMMENCING WORK.
2. GAS PIPE SIZING BASED UPON 200 LINEAR FEET OF GAS PIPING, LOW PRESSURE GAS (14"W.C.) AT 831 BTU/CF.
CONNECTED GAS LOAD SCHEDULE
1 (E)GWH-1 300,000 300,000 7"W.C. MECHANICAL ROOM EXISTING
6,435,000TOTAL CONNECTED LOAD
NO OF UNITS EQUIPMENT LOAD EACH (BTU/H) TOTAL LOADPRESSURE REQUIRED
MIN. / MAX.LOCATION REMARKS
1 (E)GWH-2 400,000 400,000 7"W.C. MECHANICAL ROOM
1 (E)B-1 2,000,000 2,000,000 7"W.C. MECHANICAL ROOM
1 (E)MAU-1 300,000 300,000 7"W.C. ROOF
1 (E)MAU-2 305,000 305,000 7"W.C. ROOF
EXISTING
EXISTING
EXISTING
EXISTING
1 B-2 3,000,000 3,000,000 7"W.C. MECHANICAL ROOM ADDED
1 MAU-3 130,000 130,000 7"W.C. ROOF ADDED
NOTES:
1. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL INSULATION REQUIREMENTS.
2. (ASTM E84) ALL INSULATION MATERIALS INSTALLED WITHIN THE PLENUM SHALL MEET THE FLAME/SMOKE REQUIREMENTS OF 25/50.
REMARKS:
1. FOR PIPING SMALLER THAT 1-1/2" INSTALLED WITHIN A BUILDING PARTITION WITHIN A CONDITIONED SPACE WITHIN A CONDITIONED SPACE. INSULATION
REDUCTION OF UP TO 1" BUT NOT LESS THAN 1" PER IECC TABLE C403.2.1, NOTE A.
DOMESTIC
COLD WATER
DOMESTIC
COLD WATER
DOMESTIC
HOT WATER & RECIRC.
DOMESTIC
HOT WATER & RECIRC.
STORM & OVERFLOW
DRAINAGE
ROOF & OVERFLOW
DRAIN BOWLS
INTERIOR
INTERIOR
(WITHIN PARTITION)
INTERIOR
INTERIOR
(WITHIN PARTITION)
INTERIOR
GLASS FIBER
WITH ASJ-SSL
GLASS FIBER
WITH ASJ-SSL
GLASS FIBER
WITH ASJ-SSL
GLASS FIBER
WITH ASJ-SSL
GLASS FIBER
GLASS FIBER
YES
YES
NONE
NONE
YES
YES
NONE
NONE
NONE
NONE
PVC
NONE
40 - 60
120 - 140
NA
NA
0.21 - 0.27 75
0.21 - 0.27 75
0.21 - 0.28 100
0.21 - 0.28 100
0.21 - 0.27 75
0.21 - 0.27 75
0.5 1 1 1 -
0.5 1 1 1 1
1 1.5 1.5 1.5 -
1 1.5 1.5 1.5 1
1 1 1 1 -
1 1 1 1 -
0.5
0.5
1
1
1
1INTERIOR
40 - 60
120 - 140
SERVICE
INSULATION CONDUCTIVITY
CONDUCTIVITY BTU * IN / (H * FT * °F )
LOCATIONINSULATION
MATERIAL
VAPOR
BARRIERJACKET
OPERATING
TEMPERATURE( ° F )
MEAN TEMP RATING ( ° F )
NOMINAL PIPE SIZE (IN)REMARKS
< 1 1 TO < 1-1/2 1-1/2 TO < 4 4 TO < 8 ≤ 8
PIPE INSULATION SCHEDULE
1. ALL INFORMATION SHOWN ON THESE DRAWINGS INCLUDING
LOCATION AND SIZES ARE BASED ON THE BEST INFORMATION
AVAILABLE. INFORMATION SHOWN IS TO INDICATE THE INTENT OF
THE PLUMBING SYSTEM WORK BUT MAY NOT REFLECT THE
EXACT ROUTING AND LOCATION. IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO FIELD VERIFY EXISTING EQUIPMENT,
PIPING, CONNECTIONS, STRUCTURE, ELECTRICAL, LIGHTING AND
ARCHITECTURAL INFLUENCES PRIOR TO INSTALLATION OF THE
NEW WORK TO AVOID ANY CONFLICTS WITH SYSTEMS
REQUIRING MODIFICATIONS. NOTIFY ENGINEER OF ANY
CONFLICTS, PRIOR TO PERFORMING WORK.
2. OFFSET ALL PIPING AS REQUIRED TO AVOID STRUCTURAL
MEMBERS, FLASHING, MECHANICAL AND ELECTRICAL EQUIPMENT.
3. DO NOT SCALE DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR
FINAL LOCATIONS OF ALL PLUMBING FIXTURES, GENERAL
PURPOSE FLOOR DRAINS, AND ADDITIONAL EQUIPMENT
REQUIRING PLUMBING CONNECTIONS.
4. COORDINATE SANITARY DRAINAGE UTILITY LOCATIONS AND
INVERT ELEVATIONS PRIOR TO COMMENCING WORK, NOTIFY
ARCHITECT IMMEDIATELY IF CONDITIONS DISCOVERED WILL NOT
ALLOW SYSTEM INSTALLATION AS DESIGNED.
5. SEE ISOMETRICS AND DIAGRAMS FOR BRANCH PIPE SIZES NOT
INDICATED IN PLAN.
6. COORDINATE PLACEMENT OF SLEEVES THROUGH FLOORS,
WALLS AND ROOF CONSTRUCTION PRIOR TO COMMENCING
WORK.
7. SEE ARCHITECTURAL PLANS AND DETAILS FOR MOUNTING
ELEVATIONS OF ALL PLUMBING FIXTURES.
8. MOUNT WALL HYDRANTS AND HOSE BIBBS AT 18" ABOVE
SURROUNDING GRADE OR FINISHED FLOOR ELEVATIONS UNLESS
SPECIFICALLY NOTED OTHERWISE.
9. FIELD VERIFY EXACT LOCATION OF ALL EXISTING UTILITIES AND
EQUIPMENT PRIOR TO COMMENCING WORK.
10. PROTECT EXISTING UTILITIES AND EQUIPMENT TO REMAIN
DURING ENTIRE CONSTRUCTION PERIOD; REPLACE DAMAGED
MATERIALS IMMEDIATELY AT NO ADDITIONAL COST TO THE
OWNER.
11. COORDINATE EXACT ROUGH-IN CONNECTION LOCATIONS AND
SIZES WITH EQUIPMENT SUPPLIER PRIOR TO COMMENCING
WORK ASSOCIATED WITH EQUIPMENT BEING FURNISHED BY
OTHERS.
12. SEE HVAC PLANS FOR FINAL LOCATION OF ALL HVAC EQUIPMENT,
COORDINATE PIPING SYSTEM CONNECTION PRIOR TO
INSTALLATION.
13. ALL WORK SHALL COMPLY WITH IPC 2015 AND IFGC 2015.
14. ALL MATERIALS IN THE PLENUM SPACE SHALL MEET THE FLAME
SPREAD AND SMOKE DEVELOPMENT INDEX PER
IMC/2015-SECTION 602.2.1. AND SHALL BE LISTED AND LABELED
FOR INSTALLATION WITHIN A PLENUM.
15. ALL EQUIPMENT AND MATERIALS USED IN THE DISTRIBUTION OF
DOMESTIC POTABLE WATER SHALL BE APPROVED AND TESTED
FOR SUCH APPLICATION WITH DOCUMENTED LISTINGS AND
LABELING IN ACCORDANCE WITH THE LATEST EDITION OF THE
INTERNATIONAL PLUMBING CODE, PUBLIC LAW 111-380 AND
ANSI/NSF-61, ANNEX G.
16. EXTEND ALL VENT TERMINATIONS THROUGH THE ROOF A
MINIMUM OF 20' FROM ALL OUTSIDE AIR INTAKES, AND OTHER
BUILDING OPENINGS.
CONNECT NEW TO EXISTING
REFERENCE BUBBLE
REVISION NUMBER
SECTION OR ELEVATION BUBBLE
DRAWING NOTE
DEMOLITION NOTE
* SECTION NUMBER# SHEET NUMBER#
*
#
#*
* SECTION OR ELEVATION LETTER
*#
ISOMETRIC OR ELEVATION BUBBLE
# REFERENCE DRAWING NUMBER
* ISOMETRIC OR ELEVATION LETTER# REFERENCE DRAWING NUMBER
#
#
DEMOLITION NOTE, ALTERNATEX
DRAWING NOTE, ALTERNATE#
ABOVEABV
AMERICANS WITH DISABILITIES ACTA.D.A.ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
ACID NEUTRALIZATION TANKANT
ACCESS PANELAPARCHITECT, ARCHITECTURALARCH
ACID VENT THROUGH ROOFAVTR
BACK FLOW PREVENTERBFP
BELOWBLWBALL VALVEBV
COMMONC
CUBIC FEET PER HOURCFH
CAST IRON PIPINGC.I.CEILINGCLG
COLUMNCOL
CONCRETECONC
CONNECTCONNCONTINUECONT
CONSTRUCT, CONSTRUCTIONCONST
COORDINATECOOR
CRAWLSPACECSCHECK VALVECV
DOWNDN
DISHWASHERDW
EXISTING(E)EACHEA
ELECTRICAL CONTRACTOREC
ELECTRIC, ELECTRICALELEC
ELEVATIONELEVELECTRIC WATER COOLEREWC
FAHRENHEITF
FLOORFLR
GENERAL CONTRACTORGC
GALLONS PER MINUTEGPM
HEADERHDR
HORIZONTALHORIZHORSEPOWERHP
INVERT ELEVATIONIE
INDIRECT WASTEIW
INTEGRALINTJOIST(S)JST(S)
KITCHEN EQUIPMENT CONTRACTORKEC
LOCATIONLOC
MANUFACTUREMANUFMAXIMUMMAX
THOUSAND BRITISH THERMAL UNIT PER HOURMBH
MECHANICAL CONTRACTORMC
MEDIUM PRESSURE GASMGMINIMUMMIN
MEMORY STOPMS
NEW(N)
NORMALLY CLOSEDNCNORMALLY OPEN / NUMBERNO
NOT TO SCALENTS
OUTSIDE AIROA
PLUMBING CONTRACTORPCPHASEPH
POINT OF CONNECTIONP.O.C.
PROVIDEPROV
PRESSURE REDUCING VALVEPRVPRESSURE PER SQUARE INCH GAUGEPSIG
PRESSURE AND TEMPERATURE RELIEFPTR
POLYVINYL CHLORIDE PIPINGPVC
RELOCATED(R)RETURN AIRRA
REFERENCERE
REQUIREDREQD
SUPPLY AIRSASANITARY PIPINGSAN
SHEETSHT
SQUARESQ
SIMILARSIMSAFETY RELIEF VALVESRV
STAINLESS STEELSS
TEMPERATURE CONTROLTCC
TYPICALTYPVENT PIPINGV
VERTICALVERT
VACUUM BREAKERVB
VENT THROUGH ROOFVTRWITHW
DESCRIPTIONSYMBOL
PLUMBING ABBREVIATIONS
FIELD VERIFYFV
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
15 A
M
P-001
PLUMBING CODESHEET
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
REVISION DATE
SYMMONS S-6080
LK-35ELKAYDRAIN STRAINER
1,31/2" 1/2"2"2"1-1/2"LRAD-1919
CHICAGOELKAY
FAUCET1-COMPT. CR SINK
S-1
1,21/2"--2"2"1 1/4"0355.012
0700J.R. SMITH
AM. STD.
SUPPORT CARRIERFAUCET
WALL HUNG LAVATORYL-2
HWCWCWVWREMARKS
TRAP
ROUGH-IN CONNECTIONSMODEL NOMANUFACTURERTAG DESCRIPTION
8
L-1 1 1/4" 2" 2" -- 1/2" 2
--1"2"2"INT.TUE1LN12CP0637
UT447E
J.R. SMITHTOTOTOTO
CARRIERFLUSH VALVEUR-1
WALL HUNG URINAL
S-22-COMPARTMENT SINK
FAUCETELKAY
CHICAGO 1-1/2" 2" 2" 1/2"1/2" 4
1/2"1-1/4" 2" 2" -- 1EWC-1J.R. SMITH
ELKAY VRCGRNTL8C0830
LRAD-3319
ELECTRIC WATER COOLERSUPPORT CARRIER
1/2" 1/2" -3" 3"FIAT
CHICAGOMSB-2424MOP SERVICE BASIN
MSB-1FAUCET
2"
1,8--1"2"2"INT.TUE1LN12CPUT447E
TOTOTOTO
CARRIERFLUSH VALVEUR-2
WALL HUNG URINAL
WALL. MTD. WATER CLOSET TOTO CT708EWC-1 FLUSH VALVE
SEATINT. 2"4" --1"TOTO TET1LN32#CP 9
WALL. MTD. WATER CLOSET TOTO CT708ELWC-2 FLUSH VALVE
SEATINT. 2"4" --1"TOTO TET1LN32#CP 1,9
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT ELEVATIONS OF ALL PLUMBING FIXTURES PRIOR
TO INSTALLATION.
2. PROVIDE ALL FIXTURES WITH CHROME PLATED CAST BRASS, ADJUSTABLE 'P' TRAPS WITH CLEANOUT PLUGS, TUBING OUTLETS AND WALL FLANGES
UNLESS FIXTURE IS FURNISHED WITH AN INTEGRAL TRAP OR IS PROVIDED ONE AS A STANDARD ACCESSORY.
3. PROVIDE ALL FIXTURES WITH CHROME PLATED SUPPLIES WITH ANGLE OR STRAIGHT PATTERN LOOSE KEY 1/4 TURN STOPS UNLESS FIXTURE IS
FURNISHED WITH INTEGRAL STOPS OR STOPS ARE PROVIDED AS STANDARD ACCESSORIES.
4. ALL LAVATORIES AND SINKS DESIGNATED TO BE IN COMPLIANCE WITH ANSI-A117.1 SHALL BE PROVIDED WITH OFFSET TAILPIECE CONNECTIONS AND
PROTECTIVE TRAP AND SUPPLY WRAPPING KITS, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5. FURNISH ALL BATTERY POWERED FAUCETS AND FLUSH VALVES WITH NEW SET OF BATTERIES FOLLOWING FINAL ACCEPTANCE OF THE PROJECT,
COORDINATE WITH THE OWNER'S DESIGNATED REPRESENTATIVE.
6. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION WHICH MAY NOT BE NOTED HERE.
7. ALL EQUIPMENT AND MATERIALS USED IN THE DISTRIBUTION OF DOMESTIC POTABLE WATER SHALL BE APPROVED AND TESTED FOR SUCH APPLICATION
WITH DOCUMENTED LISTINGS AND LABELING IN ACCORDANCE WITH THE LATEST EDITION OF THE INTERNATIONAL PLUMBING CODE, PUBLIC LAW 111-380
AND ANSI/NSF-61, ANNEX G .
REMARKS:
445897SRCXKCP
CHURCH 9500SSC
CHURCH 9500SSC
0637J.R. SMITH
SYMMONS S-60800355.012
0700J.R. SMITH
AM. STD.
SUPPORT CARRIERFAUCET
WALL HUNG LAVATORY
LK-35ELKAYDRAIN STRAINER
1,51/2" 1/2"2"2"SI-1LFRAD-191816
CHICAGOELKAY
FAUCET1-COMPT. ART SINK
S-3
S-42-COMPARTMENT ART SINK
FAUCETELKAY
CHICAGO SI-1 2" 2" 1/2"1/2" 6LRAD-3321
1100-GN2AE35-317ABLK-35ELKAYDRAIN STRAINER
WC-3SEAT
INT. 2"4" --1" 1,7FLOOR. MTD. WATER CLOSET 2282.010AM. STD.
FLUSH VALVE TOTO TET1LN32#CPCHURCH 9500SSC
BRONZE FINISH WITH WALL FLANGE.
CAST IRON ADJUSTABLE CLEANOUT WITH ROUND
BRONZE TOP AND ABS PLUG.
6" Ø STRAINER W/ VANDAL RESISTANT SCREWS.
PROVIDE WITH TRAP GUARD.
GALVANIZED FLANGED HOUSING WITH HEAVY DUTY
COVER, VANDAL RESISTANT SCREWS.
NO-HUB BOTTOM OUTLET, PVC OVERFLOW STANDPIPE
WITH UNDER DECK CLAMP, CAST IRON DOME STRAINER
NO HUB BOTTOM OUTLET, UNDER DECK CLAMP, CAST
IRON DOME STRAINER.
STAINLESS STEEL SHALLOW COVER, ROUND FACE W/
VANDAL RESISTANT CENTER SCREW.
1/2" INLINE DUAL CHECK VALVE ASSEMBLY. NSF-61.
BOX TYPE, 1/2" INLET, POLISHED CHROME
ON FLOOR TYPE 2" INLET/OUTLET CONNECTIONS
REMOVABLE SEDIMENT BUCKET, ALLOW 9-1/2" ABOVE
UNIT FOR BASKET REMOVAL
BOX TYPE, 3/4" INLET, POLISHED CHROME
COMPLETE WITH SERVICE ISOLATION VALVE
COMPLETE WITH SERVICE ISOLATION VALVE
COMPLETE WITH SERVICE ISOLATION VALVE
COMPLETE WITH SERVICE ISOLATION VALVE
TAG DESCRIPTION MANUFACTURER MODEL NO REMARKS
BFP-1 BACKFLOW PREVENTER FEBCO 510
CN-1 CONDUCTOR NOZZLE J.R. SMITH 1770
FCO-1 FLOOR CLEANOUT J.R. SMITH 4220
FD-1 FLOOR DRAIN (GENERAL) J.R. SMITH 2005Y
GCO-1 GRADE CLEANOUT J.R. SMITH 4880-U
HB-1 HOSE BIBB WOODFORD B75
OD-1 OVERFLOW ROOF DRAIN J.R. SMITH 1070Y-C-CID
SI-1 PLASTER TRAP ZURN Z1181-E-SS
RD-1 ROOF DRAIN J.R. SMITH 1010Y-C-CID
WCO-1 WALL CLEANOUT J.R. SMITH 4710-U
WH-1 WALL HYDRANT WOODFORD B67
WHA-1 WATER HAMMER ARRESTOR PPP SC-500A
WHA-2 WATER HAMMER ARRESTOR PPP SC-750B
WHA-3 WATER HAMMER ARRESTOR PPP SC-1000C
WHA-4 WATER HAMMER ARRESTOR PPP SC-1250D
BARRIER TRAP SEAL GUARD (ASSE 1072). PROVIDE SIZE
AS REQUIRED.
2" = 2692-02
3" = 2692-03
4" = 2692-04
TG-1 TRAP GUARD J.R. SMITH
WATER MIXING VALVE SCHEDULE
SYMBOL SERVICE MANUF. MODEL NUMBERINLETSIZE
OUTLETSIZE
INLETTEMPERATURE ( ° F )
OUTLETTEMPERATURE
( ° F )
MINIMUM FLOWGPM
REMARKS
TMV-1 LAVS/SINK BRADLEY S59-3080-B 1" 1-1/4" 40 110 2.0 1.2,3140
CW HW
REMARKS:
1. SURFACE MOUNTED, PROVIDE COMPLETE WITH WALL MOUNTING BRACKET; LEAD FREE DESIGN, INLET STRAINER CHECKSTOPS, INTEGRAL DIAL
THERMOMETER.
2. MINIMUM FLOW OF 0.5 GOM WITH OPERATIONAL CIRCULATION.
3. SINK AND LAVATORY TO MEET ASSE 1070.
PLUMBING EQUIPMENT SCHEDULE PLUMBING FIXTURE SCHEDULE
DOMESTIC WATER CIRCULATION PUMP SCHEDULE
MODEL NUMBERMANUF.SYMBOL REMARKS
CP-1 B&G NBF-25 1
REMARKS:
1. WATER TEMP 110F.
INLETSIZE
OUTLETSIZE
FLOW RATE
10.5 GPM3/4"3/4"
HEAD
10 FT.
WATTS RPM
2950125
ELECTRICALCHARACTER
115 VOLT / 1 PHASE
SERVICE
110F SERVICE
1. FIXTURE DESIGNATED TO BE IN COMPLIANCE WITH ANSI-A117.1.
2. WALL MOUNTED LAVATORY, BATTERY POWERED SENSOR FAUCET, 0.5 GPM, 4" CENTERS, PROVIDE WITH TMV-1.
3. STAINLESS STEEL SINGLE COMPARTMENT SINK, 6" DEEP. MANUAL FAUCET, 8" CENTERS, RIDGID GOOSENECK FAUCET, 2.2 GPM, WRISTBLADE HANDLES.
PROVIDE WITH TMV-1.
4. STAINLESS STEEL DOUBLE COMPARTMENT SINK, 6" DEEP, MANUAL FAUCET, 2.2 GPM, WRISTBLADE HANDLES. PROVIDE WITH TMV-1.
5. STAINLESS STEEL SINGLE COMPARTMENT SINK, 6" DEEP. TWO MANUAL FAUCETS, 8" CENTERS, RIDGID GOOSENECK FAUCET, 2.2 GPM, WRISTBLADE HANDLES.
PROVIDE WITH TMV-1.
6. 2 COMPARTMENT STAINLESS STEEL SINK, MANUAL FAUCET, 8" CENTERS, RIDGID GOOSENECK FAUCET, 2.2 GPM, WRISTBLADE HANDLES. PROVIDE WITH
TMV-1.
7. PRIMARY HEIGHT WATER CLOSET, BATTERY POWERED SENSOR FLUSH VALVE, 1.28 GPF.
8. BATTERY POWERED SENSOR FLUSH VALVE, 0.5GPF.
9. BATTERY POWERED SENSOR FLUSH VALVE, 1.28 GPF.
REMARKS:
1. CONTROLS CONTRACTOR TO CONNECT RELAY FOR PUMP TO DDC SYSTEM.
2. PROVIDE WITH OIL-MINDER CONTROL SYSTEM WITH VISUAL AND AUDIBLE ALARM. COORDINATE ALARM LOCATION WITH ARCHITECT.
SUMP PUMP SCHEDULE (ELEVATOR)
MODEL NUMBERMANUFACTURERSYMBOL REMARKS
ESP-1 STANCOR SE50 1, 2
OUTLET SIZE
2"
FLOW RATE
50 GPM
ELECTRICALCHARACTER
115V / 1 PHASE / 60 Hz
HEAD HP / WATTS
0.5 HP20 FT.
DRAIN STRAINER LK-35ELKAY
1100-G2E3-317AB
1100-GN2AE35-317AB
1100-GN2AE35-317AB
SIDE OUTLET, UNDER DECK CLAMP, CAST
IRON DOME STRAINER.RD-2 CANOPY DRAIN J.R. SMITH 1025-C-CID
12" Ø STRAINER W/ SLOTTED SEDIMENT BUCKET.
PROVIDE WITH TRAP GUARD.FD-2 FLOOR DRAIN (ART) J.R. SMITH 2240Y
VC-1 J.R. SMITHVENT CAP CAST IRON, VANDAL PROOF HOODED VENT CAP.1748
FS-1 FLOOR SINK (KITCHEN) J.R. SMITH12" SQ. 8" DEEP W/ ALUMINUM DOME BOTTOMSTRAINER AND 1/2 A.R.C. GRATE. PROVIDE WITHTRAP GUARD.
3430Y-PDBS-12
GDU-1 DISPOSER I.S.E. BADGER 5 120/1/60, 1/2 HP, 6.3 AMP., 1725 RPM
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
15 A
M
P-002
PLUMBINGSCHEDULES
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
REVISION DATE
(E)GD (E)GD
(E)G
D
(E)G
D
(E)SAN
(E)S
AN
(E)S
AN
(E)SAN (E)SAN
(E)S
AN
(E)S
AN
(E)S
AN
I.E. =93'-6"
(E)SAN
I.E. =93'-8"
(E)SAN(E)SAN (E)SAN
RE: CIVIL FORCONTINUATION
(E)SAN
(E)S
AN
(E)S
AN
I.E. =92'-2"
I.E. =94'-6"I.E. =94'-8"
(E) 2500 GALLONGREASEINTERCEPTOR
(E)PD
(E)D
(E)S
AN
1
6
5
13
E
K
L
J
M
F
H
6.5
4"
4"
2"
2"
4"
4"
2"
4"
6" 6"6"6"6"
2"
4"
2"4"
3"
3"
4"
4" 4"
2"
2"
2"
4"
2"
6"
4"
6"
3"4"
4"
6"
6"
6"
2"2"
2"
2"
3"
2"
2"
3"
2"
4"
4
E.A E.B E.C E.D E.E E.F E.G E.H E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
2
2
2
3
3
2
(E) G
(E) SP-1
PHASE 1B
6
5
13
E
K
L
J
M
F
H
6.5
E.A E.B E.C E.D E.E E.F E.G
E.H
E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
DEMOLITION NOTES #
1. (E) 6" SAN STUBBED FOR FUTURE CONNECTION, FIELD VERIFY EXACT LOCATION AND DEPTH PRIOR TO COMMENCING WORK.
2. DEMOLISH EXISTING PERFORATED PERIMETER DRAIN.
3. TEMPORARY CAP EXISTING PERFORATED PERIMETER DRAIN FOR RECONNECTION. REFER TO SHEET P-100A FOR NEW WORK.
4. (E) 4" SAN STUBBED AND CAPPED FOR FUTURE CONNECTION, FIELD VERIFY EXACT LOCATION AND DEPTH BEFORE COMMENCING WORK.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
52 A
M
PD-100A
UNDERFLOORPLUMBING
DEMOLITION PLAN- AREA A -
PHASES 1A & 1B
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTHPLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLAN 1/8" = 1'-0"
UNDERFLOOR PLUMBING DEMOLITION PLAN - AREA A1
REVISION DATE
DN
(E)UR
(E)UR
(E)WC
(E)2"FD
(E)2"FD (E)2"FD
(E)2"FD
(E)DF
(E)WC
(E)WC (E)WC
(E)WC
(E)WC
(E)WC
(E)WC
(E)LAV(E)LAV
(E)LAV(E)LAV
(E)LAV(E)DF
(E)MSB
(E)LAV
(E)LAV
(E)WC
(E)WC
(E)2"FD
(E)2"FD
(E)SINK (E)WB
(E)SINK
(E)SINK
(E)SH(E)LAV(E)WC(E)2"FD
(E)2"FD
(E)LAV
(E)LAV
(E)DF
(E)SCO (E)SCO(E)SCO
(E)SCO
(E)SCO
(E) 2500 GALLONGREASEINTERCEPTOR
(E)WCO
(E)WCO
(D)SINK
(E)SINK
(E)SINK
(E)4"FCO
(E)3"VTR
(E)S
D
TO (E)6"RD
(E)3"VTR
(E)3"VTR
(E)OD(E)OD
(E)O
D
TO (E)4"ODTO (E)6"OD
(E)3"VTR
(E)SD TO (E)4"RD(E)SD
(E)S
D
TO (E)6"RD
(E)6"FCO
(E)SD
TO (E)4"RD TO (E)4"RD
(E)SD
TO (E)4"RD
TO (E)3"RD
(E)S
D
(E)S
D
(E)S
D
2 GPM
(E)3"VTR
1 GPM
(E)WB
(E)SH
E.A E.B E.C E.D E.E E.F E.G E.H E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
3
2
KITCHENOFFICE
135A
COOLERS
135C
STORAGE &RECEIVING
136
UNISEX TOILET
135B
KITCHEN
135
STORAGE
106C
OUTDOORSTORAGE
107
CHAIRSTORAGE
106B
FACILITYMANAGER
OFFICE
101N
OFFICE
106A
MUSIC
105
PRINCIPAL
101A
CLOSET
101B
CLINIC
101L
UNISEX
101H
UNISEX
101M
STORAGE
101K
ASSIST.PRIN.
101G
RESOURCEROOM
101D
TEST
102A
TOILET
102B
MDF ROOM
143
CHALLENGE
102
STORAGE
102F
WORKROOM
102E
CORRIDOR
101J
CONFERENCE
102C
VESTIBULE
100
MECHANICAL
141
JAN.
139
VESTIBULE
142
ELECTRICAL
140STORAGE
134A
GIRLS
138
BOYS
137
CORRIDOR
103
TOILET
102D
RECEPTION
101
DRY STORAGE
135D
CORRIDOR
103A
CORRIDOR
103B
VESTIBULE
104
MULTI-PURPOSEGYMNASIUM
106
WORK ROOM
101E
PHASE 1B
1
DEMOLITION NOTES #
1. RE-CONFIGURE WATER SERVICE FOR IRRIGATION MODIFICATIONS. RE: 16/P-500.
2. DEMOLISH EXISTING SINK AND ALL ASSOCIATED PIPING AS SHOWN.
3. REMOVE AND HOLD EXISTING SINK AND ASSOCIATED ACCESSORIES FOR REINSTALLATIONDEMOLISH EXISTING ASSOCIATED PIPING AS SHOWN. REFER TO DRAWING P-101A FORE NEW WORK.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
54 A
M
PD-101A
FIRST FLOORPLUMBING
DEMOLITION PLAN- AREA A -
PHASES 1A & 1B
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLAN 1/8" = 1'-0"
FIRST FLOOR PLUMBING DEMOLITION PLAN - AREA A1
PLAN NORTH
REVISION DATE
(E)GD (E)GD
(E)G
D
(E)G
D
(E)SAN
(E)S
AN
(E)S
AN
(E)SAN (E)SAN
(E)S
AN
(E)S
AN
(E)S
AN
I.E. =93'-6"
(E)SAN
(E)SAN(E)SAN (E)SAN
RE: CIVIL FORCONTINUATION
(E)SAN
(E)S
AN
(E)S
AN
I.E. =92'-2"
I.E. =94'-6"I.E. =94'-8"
(E) 2500 GALLONGREASEINTERCEPTOR
(E)PD
(E)D
(E)S
AN
TO (E) PERIMETER DRAIN
(E) WATER ENTRY,RE: CIVIL FOR
CONTINUATION
(E) FIRE SERVICEENTRY,
RE: CIVIL FORCONTINUATION
(E)3" (E)6"
6
5
13
E
K
L
J
M
F
H
6.5
3"
12
3
(E)SAN
E.A E.B E.C E.D E.E E.F E.G E.H E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00
B
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00
B
2"
4
5GD
GD54 4
3"
3"
3"
77
7
3
2"
6
(E)4"
(E)2"
(E)4"
(E)2"
(E)6"
(E)6"
(E)3"
(E)4"
(E)6"
(E)4"
(E)4"
(E)4"
3"
3"
(E)4"
(E)6"
PHASE 1B
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
3" IRRIGATION. REFERTO CIVIL PLANS FORCONTINUATION.
CONNECT NEW 3"IRRIGATION TO (E) 3"IRRIGATION.
3"
3"
3"3"
DRAWING NOTES #
1. CONNECT 3" SANITARY LINE TO (E) 4" SANITARY LINE. FIELD VERIFY LOCATION AND ELEVATION.
2. 3" SANITARY UP TO FCO.
3. 2" SAN UP TO SINK ABOVE.
4. 3" GREASE DRAIN DOWN TO (E) GREASE DRAIN.
5. 3" GREASE DRAIN WITH P-TRAP UP TO FLOOR SINK.
6. CONNECT 2" SANITARY LINE TO (E) 2" SANITARY LINE.
7. 2" VENT RISE UP THRU FLOOR.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
17 A
M
P-100A
UNDERFLOORPLUMBING PLAN -AREA A - PHASES
1A & 1B
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLAN 1/8" = 1'-0"
UNDERFLOOR PLUMBING PLAN - AREA A1
PLAN NORTH
REVISION DATE
I.E. =93'-8"(E)6"
11
SANSAN
SA
N
SAN
SA
N
1 2 3 4
6
5
8 9 10 1213
E
G
K
L
J
M
D
F
H
6.5
E.A E.B
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00C
RE:
MATCHLINE
MATCHLINE
P-100C
6"
I.E.=97'-10"(5,441 SQ.FT.)RE: CIVIL FORCONTINUATION
I.E.=96'-4"(4,012 SQ.FT.)RE: CIVIL FORCONTINUATION
SD
6"
SANSAN
2" 3"
SA
N
3"
3"
2"
2"
4"
SAN
2"
2" 4"
2"
4" 6" 6"
4"
2"2"
2" 2"
4"
4"
SA
N
8
6"
1
3"
1
SA
N
SAN
SA
N
3"
3"
3"
1
2"
3
5' - 0"
5 4
6
3
2
4
3
1111
11
11
5
3
2
2"4"
1
1
8
3
52
6
1
14 2 2
2
14
2
13
5
3 12 3
14
8"
SD
3"
SD
SD
9I.E.=96'-4"(10,255 SQ.FT.)RE: CIVIL FORCONTINUATION
5' - 0"
7
I.E.=97'-10"(106 SQ.FT.)RE: CIVIL FORCONTINUATION
7
3"
SD
2"
17
17
4"
4"
4"
4"
4"
6"
163"
5
4
4
2"2"
PIPE SLEEVETYPICAL
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
1/8" / 1'-0"1/8" / 1'-0"
1/4" / 1'-0"
1/8" / 1'-0"
1/8
" / 1'-0"
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
1/8
" / 1'-0"
SA
N
1/8
" / 1'-0"
4
4
DRAWING NOTES #
1. 2" SAN UP TO SINK ABOVE.
2. 2" SAN UP TO LAV ABOVE.
3. 4" SAN UP TO WATER CLOSET ABOVE.
4. 2" SAN WITH P-TRAP UP TO FLOOR DRAIN ABOVE.
5. 2" VENT UP TO FLOOR ABOVE.
6. 4" SAN UP TO CLEANOUT ABOVE.
7. 3" SD DOWN FROM ABOVE.
8. 6" SD DOWN FROM ABOVE.
9. 8" SD DOWN FROM ABOVE.
10. 4" SD UP TO FCO.
11. CONNECT 6" SANITARY LINE TO (E) 6" SANITARY LINE. APPROX. I.E.= XXXX, FIELD VERIFYPRIOR TO COMMENCING WORK.
12. 2" SAN UP TO URINAL.
13. 3" SAN UP TO MOP BASIN.
14. 2" SAN UP THRU FLOOR.
15. 4" SAN UP THRU FLOOR.
16. 3" SAN UP TO FLOOR DRAIN ABOVE.
17. CONNECT NEW 4" SOLID WALL PERIMETER DRAIN PIPE TO EXISTING TEMPORARY CAPPED PERFORATED PERIMETER DRAIN. FIELD VERIFY EXACT LOCATION AND ELEVATION.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
18 A
M
P-100B
UNDERFLOORPLUMBING PLAN -AREA B - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
UNDERFLOOR PLUMBING PLAN - AREA B1
REVISION DATE
SA
N
SA
N
1 2 3 4
8
910
12
A
B
C
E
G
D
SA
N
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
00B
RE:
MATCHLINE
MATCHLINE
P-100B
I.E.=97'-6"(3,584 SQ.FT.)RE: CIVIL FORCONTINUATION
6"
SD
I.E.=96'-4"(2,931 SQ.FT.)RE: CIVIL FORCONTINUATION
I.E.=96'-4"(2,942 SQ.FT.)RE: CIVIL FORCONTINUATION
I.E.=96'-4"(1,284 SQ.FT.)RE: CIVIL FORCONTINUATION
I.E.=97'-2"(1,900 SQ.FT.)RE: CIVIL FORCONTINUATION
I.E.=96'-10"(893 SQ.FT.)RE: CIVIL FORCONTINUATION
SD
SD
SD
SD
SD
4"
3"
4"
6"
6"
2"
2"
2"3"
2"
2"
4"
2"
2"
2"
SANESP-1
5' - 0"
5' - 0"
5' - 0"
5' - 0"
5' - 0"
5' - 0"
1
12
8
8
1
1
8
7
9
7
1
1
6
1
1
112"
SAN
10
3
12
1
1
2"
2"
3"
1
2" 2"
SAN
SA
N
SA
N
SAN
SAN
SAN
SAN
4"
1/8
" / 1'-0"
1/8" / 1'-0"
1/8" / 1'-0"
1/8
" / 1'-0"
1/8
" / 1'-0"
1/8" / 1'-0"
4
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
FINISHED FLOOR ELEVATION100'-0"
5643.30 USGS
5
1/8
" / 1'-0"
I.E.=5641.42'
I.E.=5640.15'
SA
N
1/8
" / 1'-0"
1/4" / 1'-0"
4
4
DRAWING NOTES #
1. 2" SAN UP TO SINK ABOVE.
2. 2" SAN UP TO LAV ABOVE.
3. 4" SAN UP TO WATER CLOSET ABOVE.
4. 2" SAN UP TO FLOOR DRAIN ABOVE.
5. 2" VENT UP TO FLOOR ABOVE.
6. 4" SAN UP TO CLEANOUT ABOVE.
7. 4" SD DOWN FROM ABOVE.
8. 6" SD DOWN FROM ABOVE.
9. 3" SD DOWN FROM ABOVE.
10. 4" SAN UP TO FLOOR ABOVE.
11. 2" SAN UP TO WATER COOLER.
12. 2" PUMPED DRAIN UP FROM ELEVATOR SUMP PUMP.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
8/3/
2016
2:4
1:34
PM
P-100C
UNDERFLOORPLUMBING PLAN -AREA C - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"1
UNDERFLOOR PLUMBING PLAN - AREA C
REVISION DATE
DN
(E)UR
(E)UR
(E)WC
(E)2"FD
(E)2"FD (E)2"FD
(E)2"FD
(E)DF
(E)WC
(E)WC (E)WC
(E)WC
(E)WC
(E)WC
(E)WC
(E)LAV(E)LAV
(E)LAV(E)LAV
(E)LAV(E)DF
(E)MSB
(E)LAV
(E)LAV
(E)WC
(E)WC
(E)2"FD
(E)2"FD
(E)SINK (E)WB
(E)SINK
(E)SINK
(E)SH(E)LAV(E)WC(E)2"FD
(E)2"FD
(E)LAV
(E)LAV
(E)SCO (E)SCO(E)SCO
(E)SCO
(E)SCO
(E) 2500 GALLONGREASEINTERCEPTOR
(E)WCO
(E)WCO
(E)SINK
(E)4"FCO
P-140
1
(E)3"VTR
(E)S
D
TO (E)6"RD
(E)2"
(E)2"
(E)3"VTR
(E)3"VTR
(E)OD(E)OD
TO (E)4"ODTO (E)6"OD
(E)4"(E)6"
(E)SD TO (E)4"RD(E)SDTO (E)6"RD
(E)3"(E)2"(E)1"
(E)6"FCO
(E)SD
TO (E)4"RD TO (E)4"RD
(E)SD(E)4"(E)4"
(E)6"
TO (E)4"RD
TO (E)3"RD(E)3"
(E)4"
(E)4"(E)4"
(E)S
D
(E)S
D
(E)S
D
2 GPM(E)1"(E)2"(E)2 1/2"
CWHW
HWC
(E)H
WC
(E)H
W(E
)CW
HWCHW
CW
(E)2"(E)1"
(E)3/4"
(E)3/4"
(E)2"
(E)4"
(E)2 1/2"
(E)2"(E)1"
(E)3"VTR
1 GPM
(E)WB
(E)1"(E)3/4"(E)3/4"
(E)1"(E)1"(E)3/4"
(E)3/4"(E)3/4"(E)3/4"
(E)SH
CWHW
HWC
CW
HW
HW
C
(E)1 1/2"(E)1"
(E)3/4"
6
5
13
K
L
J
M
F
H
6.5
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01
B
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01
B
(E)G(E)G
TO (E)MAU-2 ABOVE
4"FCO
1
1/2"
3/4"3/4"
1/2"
2
E.A E.B E.C E.D E.E E.F E.G E.H E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
G
1 1/4"
1/2"1/2"
2"3
(R)SINK
PHASE 1B
WAITING
101F
OFFICE
101E
KITCHENOFFICE
135A
COOLERS
135C
STORAGE &RECEIVING
136
UNISEX TOILET
135B
KITCHEN
135
STORAGE
106C
OUTDOORSTORAGE
107
CHAIRSTORAGE
106B
FACILITYMANAGER
OFFICE
101N
OFFICE
106A
MUSIC
105
PRINCIPAL
101A
CLOSET
101B
CLINIC
101L
UNISEX
101H
UNISEX
101M
STORAGE
101K
ASSIST.PRIN.
101G
RESOURCEROOM
101D
TEST
102A
TOILET
102B
MDF ROOM
143
CHALLENGE
102
STORAGE
102F
WORKROOM
102E
CORRIDOR
101J
CONFERENCE
102C
VESTIBULE
100
MECHANICAL
141
JAN.
139
VESTIBULE
142
ELECTRICAL
140STORAGE
134A
GIRLS
138
BOYS
137
CORRIDOR
103
TOILET
102D
RECEPTION
101
DRY STORAGE
135D
CORRIDOR
103A
CORRIDOR
103B
VESTIBULE
104
MULTI-PURPOSEGYMNASIUM
106
DRAWING NOTES #
1. CONNECT 1/2" CW, 3/4" HW & HWC TO EXISTING LINES AND RUN TO SINK AT LOCATION SHOWN.
2. 2" VENT UP TO STRUCTURAL SPACE, THEN TRANSITION TO 3" VTR IN VERTICAL STRUCTURALSPACE.
3. 2" VENT, 1/2" CW AND 1/2" HW DOWN TO SINK.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
22 A
M
P-101A
FIRST FLOORPLUMBING PLAN -AREA A - PHASES
1A & 1B
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLAN 1/8" = 1'-0"
FIRST FLOOR PLUMBING PLAN - AREA A1
PLAN NORTH
REVISION DATE
F.E
.C.
F.E.C.
F.E
.C.
(E)S
D
4"FCO
2 1/2"2"
3/4"
4
S-1
P-140
3
S-1S-1S-1
S-1S-1
S-1S-1
WC-3L-1
2 1/2"
WC-3
L-1S-1
S-1
S-1
P-140
2
2"
2 1/2"
3/4"
1 2 3 4
6
5
8 9 10 1213
E
G
K
L
J
M
D
F
H
6.5
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01C
RE:
MATCHLINE
MATCHLINE
P-101C
2
P-142
4" FCO-1
E.A E.B
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
ODSD
8"8"
4"SD
G
G
1 1/4"
1"1"
3/4"3/4"
3/4"
3/4"3/4" 1/2"
2"
1 1/2"
3/4"3/4"
1 1/4"
3/4"3/4"
1 1/2"
2"
1/2" 3/4"3/4"S-3
S-4
S-3
8
WH-1
3/4"
3/4"
3/4"
3/4"
9 9
9
1"1"
3/4"
3/4"
2"
2 1/2"
10
2"
2"2"
10
11
S-1
9
3/4"3/4"
1 1/4"
8
WH-1
WH-1
3/4"
3/4"3/4"
13
2"
2 1/2"
4" FCO-1
1/2"3/4"
2"1 1/4"
3/4"
9
9
9
9
9
9
99
141110
15
19
CN-1
2
15
1
16
15
6
9
123/4"
3/4"
3/4"
1 1/4"
3/4"
1 1/2"
3/4" 3/4"
1 1/2"
1"
4"4"
ODSD
8"8"
8"8"
18
CN-1
3" RD-2
106 S.F.
3" RD-2
52 S.F.
6" CN-1
20
17
OD
6"6"
SD
OD
OD
6"
6"
SD
8
8
8
2"
2"
2"
2"
2"
3"
6
21
21
22
2"
22
3" FD-2W/ TG-1
2"FD-1W/ TG-1 2"FD-1
W/ TG-1
22
1"1" 1 1/4"
2"
22
20
2"
2"
3/4"
2"
2 1/2"
2 1/2"
1 1/2"
3/4"
22
1 1/4"3/4"
3/4"
1"
9
FLEXCLASSROOM
113
CLASSROOM
126
BOYS
112
CLASSROOM
127
CLASSROOM
128
CLASSROOM
129
KINDERGARTEN
130
KINDERGARTEN
131 KINDERGARTEN
132
KINDERGARTEN
133
COMMONS
134
ART
108
STORAGE
130B
RR
130A
STORAGE
131B
RR
131A
STORAGE
132B
RR
132A
RR
133B
STORAGE
133A
LIBRARY MEDIACENTER
109
GIRLS
110
CUST.
111
CORRIDOR
103
OFFICE
109B
VESTIBULE
109A
STAIR 1
S1.1
STORAGE
108B
VESTIBULE
106D
KILN
108A
3
4
P-142
DRAWING NOTES #
1. 5" SD DOWN THRU FLOOR. RE: P-100B FOR CONTINUATION.
2. 5" OD DOWN TO CONDUCTOR NOZZLE.
3. 6" OD DOWN FROM ABOVE CEILING, FIELD VERIFY EXACT LOCATION. PIPE TO LOCATIONINDICATED, DROP IN CHASE AND CONNECT TO 6" CN-1.
4. (E) 6" SD DOWN FROM ROOF. CONNECT TO NEW 6" SD AND ROUTE AS SHOWN.
5. 6" SD DOWN TO UNDERGROUND.
6. 1/2" CW AND 1/2" HW UP TO SINK ON FLOOR ABOVE AND 1/2" CW AND 1/2" HW DROP TO SINK.
7. REMOVE CAP AND CONNECT 2-1/2" CW, 2" HW, & 1" HWC TO EXISTING DOMESTIC WATER.
8. BALANCE CIRCUIT SETTER TO 0.5 GPM.
9. 2" VENT, 1/2" CW AND 1/2" HW DROP TO SINK.
10. 2" VENT RISE TO 3" VTR.
11. 4" SD AND 4" OD DOWN FROM ROOF DRAIN.
12. 2" SANITARY, 1/2" CW AND 1/2" HW UP TO SINK ABOVE.
13. 1-1/4" GAS RISE UP TO MAU-3 ON ROOF.
14. 5" SD AND 5" OD FROM DRAINS ABOVE, INCREASE TO 8" SD AND 8" OD AND OFFSET ABOVECEILING AS INDICATED.
15. 3/4" CW DOWN IN WALL TO WALL HYDRANT.
16. 6" SD DOWN THRU FLOOR. RE: P-100B FOR CONTINUATION.
17. 6" OD DOWN TO CONDUCTOR NOZZLE.
18. 8" SD DOWN THRU FLOOR. RE: P-100B FOR CONTINUATION.
19. 8" OD DOWN TO CONDUCTOR NOZZLE.
20. 3" SD DOWN THRU FLOOR. RE: P-100B FOR CONTINUATION.
21. 2" SANITARY DOWN FROM ABOVE.
22. 2" VENT RISE.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
25 A
M
P-101B
FIRST FLOORPLUMBING PLAN -AREA B - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
FIRST FLOOR PLUMBING PLAN - AREA B1
REVISION DATE
F.E
.C.
F.E.C.
S-1
P-140
4
S-1
S-1
S-1
S-1
1 2 3 4
8
910
12
A
B
C
E
G
D
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
01B
RE:
MATCHLINE
MATCHLINE
P-101B
6
P-142
7
9
3/4"3/4"
9
S-1
S-1
10
10
7
8
8
10
7
8
4" FCO-1
3/4"3/4"3/4"
3/4"3/4"
WH-1 3/4"
1 1/4"
3/4"
1 1/4"
3/4"3/4"3/4"
8
8910
1 1/4"
3/4"
1 1/4"
3/4"3/4"
3/4"3/4"
1"
3/4"
2"
3/4"
1 1/2"1 1/2"
1 1/2"1 1/2"
8
3/4"
1"
8
3/4"
1 1/2"
2"
3/4"
3/4"
2"
3/4"3/4"3/4"
EWC-1
14
4" CN-112
11
5" CN-1
2
1
2
1
5" CN-1
6" CN-1
6
5
3" CN-1
3
4
4" CN-1
11
12
15
WH-1
153/4"
7
9
9
10
7
7
9
13
16
18
17
10
3" RD-2
121 S.F.
3" RD-2
109 S.F.
S-1
9
107
3/4"3/4"3/4"
3/4"3/4"3/4"
S-1
9
10
7
1"
9
10
7
S-1
1"
1"
3/4"
1"
1"
3/4"
3
7
9
1"
CLASSROOM
119
CLASSROOM
118
CLASSROOM
117
CLASSROOM
116
CLASSROOM
122
CLASSROOM
120
CLASSROOM
123
CLASSROOM
115
RESOURCE
ROOM
125
TEACHER
WORK ROOM
121
STAFF RR
124
ELEC.
125A
STAIR 2
S2.1
VESTIBULE
114
FLEX
CLASSROOM
113
CLASSROOM
126
DRAWING NOTES #
1. 5" SD DOWN THRU FLOOR. RE: P-100C FOR CONTINUATION.
2. 5" OD DOWN TO CONDUCTOR NOZZLE.
3. 3" SD DOWN THRU FLOOR. RE: P-100C FOR CONTINUATION.
4. 3" OD DOWN TO CONDUCTOR NOZZLE.
5. 6" SD DOWN THRU FLOOR. RE: P-100C FOR CONTINUATION.
6. 6" OD DOWN TO CONDUCTOR NOZZLE.
7. 1/2" CW AND 1/2" HW UP TO SINK ON FLOOR ABOVE AND 1/2" CW AND 1/2" HW DROP TO
SINK.
8. BALANCE CIRCUIT SETTER TO 0.5 GPM.
9. 2" SANITARY DOWN FROM SINK ABOVE.
10. 2" VENT RISE.
11. 4" SD DOWN THRU FLOOR. RE: P-100C FOR CONTINUATION.
12. 4" OD DOWN TO CONDUCTOR NOZZLE.
13. 2" VENT DROP TO ELECTRIC WATER COOLER.
14. 2" PUMPED DISCHARGE FROM SUMP PUMP.
15. 3/4" CW DOWN IN WALL TO WALL HYDRANT.
16. 2" SANITARY UP TO ELECTRIC WATER COOLER ABOVE.
17. 1/2" CW UP TO ELECTRIC WATER COOLER ON FLOOR ABOVE
18. 1/2" CW DROP TO ELECTRIC WATER COOLER.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
8/3/
2016
2:4
7:51
PM
P-101C
FIRST FLOORPLUMBING PLAN -AREA C - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
Overall First Floor Plumbing Plan1
REVISION DATE
F.E.C.
F.E
.C.
LIBRARY MEDIACENTER
109
BOY'S
203
CLASSROOM
216
CLASSROOM
217
CLASSROOM
218
4TH GRADE
219
GIRLS
201
CUSTODIAL
202
CORRIDOR
200
STAIR 1
S1.2
P-140
6
S-1
S-1
S-1
1 2 3 4
6
5
8 9 10 1213
E
G
K
L
J
M
D
F
H
6.5
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
02C
RE:
MATCHLINE
MATCHLINE
P-102C
2
P-142
E.A E.B
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
4"4"
SD
OD
SD
OD
2
7
85
6
3
4
1
7
2" 2"
2"
2"
2"
2"
67
3" VTR
5
5
DRAWING NOTES #
1. 5" SD DOWN THRU FLOOR. RE: P-101B FOR CONTINUATION.
2. 5" OD DOWN THRU FLOOR. RE: P-101B FOR CONTINUATION.
3. 5" SD UP TO ROOF DRAIN.
4. 5" OD UP TO ROOF DRAIN.
5. 1/2" CW AND 1/2" HW UP TO SINK FROM BELOW.
6. 2" VENT RISE.
7. 2" SANITARY DOWN THRU FLOOR.
8. 2" VENT RISE TO 3" VTR.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
29 A
M
P-102B
SECOND FLOORPLUMBING PLAN -AREA B - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
SECOND FLOOR PLUMBING PLAN - AREA B1
REVISION DATE
F.E
.C.
F.E.C.
CLASSROOM
209
CLASSROOM
208
CLASSROOM
207
CLASSROOM
206
FLEXCLASSROOM
204
RESOURCEROOM
215
ELEC.
215A
CLASSROOM
213
CLASSROOM
212
CLASSROOM
210
TEACHERWORK ROOM
211
STAFF RR
214
STAIR 2
S2.2
P-140
5
S-1
S-1
S-1
CLASSROOM
205
S-1
S-1
S-1
S-1
S-1
S-1
1 2 3 4
8
910
12
A
B
C
E
G
D
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
02B
RE:
MATCHLINE
MATCHLINE
P-102B
6
P-142
EWC-1
OD
SD
OD
SD
5"5"
4"4"
5"5"
OD
SD
3"3"
OD
SD
4"4"
OD
SD
6"6"
4"4"
S-1
14
13
15
16
11
12
10
9
14
13
15
16
17
18
16
15
2
1
4
3
2
1
3
4
6
5
68
5
67
6 7
5
6
567
68
6 768
5
6 8
7
6 7
5
6
2"
2"
2"
6
5
6 7
2"
6
19
7
6 867
5
6 7
5
6
2"
6 8
567
5
DRAWING NOTES #
1. 5" SD DOWN THRU FLOOR. RE: P-101B FOR CONTINUATION.
2. 5" OD DOWN THRU FLOOR. RE: P-101B FOR CONTINUATION.
3. 5" SD UP TO ROOF DRAIN.
4. 5" OD UP TO ROOF DRAIN.
5. 1/2" CW AND 1/2" HW UP TO SINK FROM BELOW.
6. 2" VENT RISE.
7. 2" SANITARY DOWN THRU FLOOR.
8. 2" VENT RISE TO 3" VTR.
9. 3" SD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
10. 3" OD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
11. 3" SD UP TO ROOF DRAIN.
12. 3" OD UP TO ROOF DRAIN.
13. 4" SD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
14. 4" OD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
15. 4" SD UP TO ROOF DRAIN.
16. 4" OD UP TO ROOF DRAIN.
17. 6" SD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
18. 6" OD DOWN THRU FLOOR. RE: P-101C FOR CONTINUATION.
19. 1/2" CW UP TO WATER COOLER FROM BELOW.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
8/3/
2016
2:4
1:38
PM
P-102C
SECOND FLOORPLUMBING PLAN -AREA C - PHASE
1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
SECOND FLOOR PLUMBING PLAN - AREA C1
REVISION DATE
6
5
13
E
K
L
J
M
F
H
6.5
(E)6"RD (E)4"RD
(E)4"OD(E)6"OD
(E)4"RD (E)4"RD
(E)6"RD
(E)GAS VENT (E)3"VTR (E)3"VTR
(E)3"VTR
(E)3"VTR
(E)3"VTR
(E)6"RD
(E)3"VTR
(E)4"RD
(E)3"RD
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21
B
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21
B
(E)3"VTR
(E)4"RD
(E)GPR
(E)3/4"
(E)1"
RE: MECH
(E)G
(E)GPR
RE: MECH
(E)1"
(E)1 1/2"
(E)3"VTR
E.A E.B E.C E.D E.E E.F E.G E.H E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
1
PHASE 1B
6
5
13
E
K
L
J
M
F
H
6.5
E.A E.B E.C E.D E.E E.F E.G
E.H
E.J
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
E.10
RTU-7RE: MECH
EF-10RE: MECH
EF-9RE: MECH
1
3"RD-2
99 S.F.
1
DRAWING NOTES #
1. 3" ROOF DRAIN PIPING TO OFFSET TO EXTERNAL DOWNSPOUT.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
8/3/
2016
2:4
1:41
PM
P-121A
ROOF PLUMBINGPLAN - AREA A -PHASES 1A & 1B
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLAN 1/8" = 1'-0"
ROOF PLUMBING PLAN - AREA A1
PLAN NORTH
REVISION DATE
1 2 3 4
6
5
8 9 10 1213
E
G
K
L
J
M
D
F
H
6.5
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21
A
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21C
RE:
MATCHLINE
MATCHLINE
P-121C
5"OD-1
5"RD-1
4"RD-1
4"OD-11,450 S.F.
4,012 S.F.
4"OD-1
4"RD-12,468 S.F.
8"RD-1
8"OD-17,787 S.F.
E.A E.B
E.1
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
4"RD-1
4"OD-12,427 S.F.
G
1 1/4"
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
1
1
1
1
1
1
22
P-500
1 2 3 4
6
5
7 8 9 10 11 1213
E
G
K
L
J
M
D
F
H
6.5
E.A E.B
E.2
E.3
E.4
E.5
E.6
E.7
E.8
E.9
RTU-6RE: MECH
RTU-7RE: MECH
EF-10RE: MECH
EF-9RE: MECH
EF-12RE: MECH
RTU-8RE: MECH
MAU-3RE: MECH
EF-11RE: MECH
1
DRAWING NOTES #
1. PROVIDE VENT CAP AT THE TERMINATION OF THE VTR.
2. 1-1/4" GAS PIPING FROM BELOW. ROUTE TO MAU-3.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
33 A
M
P-121B
ROOF PLUMBINGPLAN - AREA B -
PHASE 1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
ROOF PLUMBING PLAN - AREA B1
REVISION DATE
1 2 3 4
8
910
12
A
B
C
E
G
D
RE
:
MA
TC
HLIN
E
MA
TC
HLIN
E
P-1
21B
RE:
MATCHLINE
MATCHLINE
P-121B
4"RD-1
4"OD-1
5"OD-1
5"RD-1
5"OD-1
5"RD-1
4"OD-1
4"RD-1
4"OD-1
4"RD-1
3"OD-1
3"RD-1
2,134 S.F.
1,900 S.F.
893 S.F.
1,284 S.F.
2,942 S.F.
2,931 S.F.
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
1 2 3 4
78
910
11 12
A
B
C
E
G
D
RTU-9RE: MECH
RTU-10RE: MECH
EF-13RE: MECH
EF-14RE: MECH
1
1
1
1
1
1
1
DRAWING NOTES #
1. PROVIDE VENT CAP AT THE TERMINATION OF THE VTR.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
35 A
M
P-121C
ROOF PLUMBINGPLAN - AREA C -
PHASE 1A
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
PLAN NORTH
AREA 'A'EXISTINGBUILDING
AREA 'B'
AREA 'C'
KEYPLANPLAN NORTH
1/8" = 1'-0"
ROOF PLUMBING PLAN - AREA C1
REVISION DATE
(E)4"FS
(E)SINK
(E)SINK
(E)4"FS(E)SINK
(E)4"FS
(E)3"FS
(E)3"FS
(E)SINK(E)2"FD
(E)2"FD
(E)2"FD
(E)6"FS (E)4"FS(E)WC(E)2"FD
(E)LAV
(E)WB
(E)MSB
(E)4"FCO
(E)4"FCO
REFER TO FIREPROTECTIONPLANS
(E)PRV-1(E)PRV-2(E)PRV-3
(E)BFP-1(E)BFP-2
(E)D
(E)SD(E)SD(E)SD
(E)P
D(E)3"
(E)6"(E)6"
TO (E)6"RD(E)3"
(E)1 1/2"(E)3"(E)3/4"
TO (E)4"RD
(E)S
D
(E)HB
(E)G
(E)G
(E)G
(E)G
(E)GAS METER BY XCEL
(E)6"
(E)6"
(E)1 1/4"
(E)2"
(E)GWH-2
(E)GWH-1
(E)C
W
(E)6"
(E)B-1B-2
1
RE: MECH RE: MECH
G
(E)G
(E)G
(E)G
(E)C
W
(E)H
W
(E)H
WC
(E)3"V UPTO (E)3"VTR
(E)4" GASVTR
(E)3"V UPTO (E)3"VTR
(E)GPR
(E)G
(E)G
(E)G
(E)1 1/2"
(E)G
(E)G
(E)GPR
(E)HW
(E)HWC
(E)1 1/2"
E.C E.D E.E E.F
E.1
E.2
E.3
E.4
1 1/4"
1 1/4"
G
3"FS-1
G
2
42 40
2"
3"FS-1 3"FS-1
3
3
3939
3
1/2"
1/2"1/2"
1/2" 2"
41
4
4
41
4
CP-1 24
25
38
L-1L-1 L-1
L-1L-2
L-1L-1
L-1 L-1L-2
UR-1
UR-2
WC-1WC-1
WC-2
WC-1WC-1
WC-1WC-2
GIRL'S
110
BOY'S
112
CUSTODIAL
111
CORRIDOR
103
3
10
F
H
MSB-1
23
2"
1 1/2"
3/4"
26
26
26
2626
26
2" FD-1W/ TG-1
2" FD-1W/ TG-1
2" FD-1W/ TG-1
2" FD-1W/ TG-1
1"1"
1"1"
1"1"
2"
3/4"1 1/2"2 1/2"
12
6 30
36
12
37
12
33
3/4"3/4"3/4"
2"
HB-1
HB-1
31
31
21
21
35
29
21
21
376
29
29
29
2 1/2"
WC-2
L-2
S-2 W/GDU-1
STAFF RR
124
2ND GRADE
123
RESOURCEROOM
125
9
D
WCO-1
1 1/2"
2"
1" 3/4"
3/4"
4"
2"
12
1314
1615
6
6
17
18
2"
2" FD-1W/ TG-1
21
RR
132A
RR
131A
WC-3WC-3
2" FD-1W/ TG-1
2" FD-1W/ TG-1
WCO-1
L-1L-1
3/4"3/4"3/4"
6
18
19
20
1 1/2"
2"3/4"
WC-2
L-2
S-2 W/GDU-1
RESOURCEROOM
215
STAFF RR
214
CLASSROOM
213
9
D
WCO-1
2"
2"
2"
6
5
76
9
10
11
2" FD-1W/ TG-1
8
L-1L-1
L-1L-1
L-2
L-1L-1
L-1L-1
L-2
UR-1UR-2
WC-1
WC-1
WC-2
WC-1WC-1
WC-1WC-1
WC-2
GIRLS
201
BOY'S
203
CUSTODIAL
202
CORRIDOR
200
3
10
F
H
MSB-1
2"
2" 2926 26
26 26
22
28
27
SD
OD 4"
4"
4"4"
2"
SD
OD
2" FD-1W/ TG-1
2" FD-1W/ TG-1
2" FD-1W/ TG-1
2" FD-1W/ TG-1
8
33
HB-1
HB-11"
3/4"30
29
294" WCO-1
31
31
2"34
66
6
DRAWING NOTES #
1. CONNECT 4" GAS TO EXISTING 6" GAS FOR BOILER.
2. CONNECT 1-1/4" GAS TO EXISTING 6" GAS.
3. CONNECT 2" VENT TO EXSITING 3" VENT.
4. 2" VENT DROP IN WALL TO FLOOR SINK.
5. 1/2" CW AND 1/2" HW UP TO SINK FROM BELOW.
6. 2" VENT RISE.
7. 2" SANITARY DOWN THRU FLOOR.
8. 2" VENT RISE TO 3" VTR.
9. 1/2" CW AND 1/2" HW UP TO LAVATORY FROM BELOW. 2" SANITARY DOWN AND 2" VENT RISE FROM LAVATORY.
10. 4" SANITARY DOWN THRU FLOOR.
11. 4" SANITARY DOWN, 2" VENT RISE FROM WATER CLOSET. 1" CW RISE UP TO WATER CLOSET FROM BELOW.
12. BALANCE CIRCUIT SETTER TO 0.5 GPM.
13. 1/2" CW AND 1/2" HW DOWN TO LAVATORY. 2" SANITARY DOWN AND 2" VENT RISE FROM LAVATORY.
14. 1/2" CW AND 1/2" HW UP TO LAVATORY ABOVE. 2" SANITARY DOWN FROM LAVATORY ABOVE.
15. 1/2" CW AND 1/2" HW UP TO SINK ON FLOOR ABOVE AND 1/2" CW AND 1/2" HW DROP TO SINK.
16. 2" SANITARY DOWN FROM SINK ABOVE.
17. 1" CW UP TO WATER CLOSET ABOVE AND 1" CW DOWN TO WATER CLOSET.
18. 2" VENT RISE FROM WATER CLOSET.
19. 1" CW DOWN TO WATER CLOSET.
20. 2" VENT, 1/2" CW AND 1/2" HW DOWN TO LAVATORY.
21. 2" SANITARY WITH P-TRAP UP TO FLOOR DRAIN.
22. 2" VENT RISE FROM MOP BASIN. 1/2" CW AND 1/2" HW TO MOP BASIN FROM BELOW.
23. 2" VENT RISE FROM MOP BASIN. 1/2" CW AND 1/2" HW DOWN TO MOP BASIN.
24. REPLACE EXISTING CIRCULATION PUMP WITH NEW CP-1 FOR ADDED LOAD.
25. NEW 4" GAS LINE DROP TO SERVICE B-2.
26. 1/2" CW AND 1/2" HW TO LAVATORY. 2" SANITARY DOWN AND 2" VENT RISE FROM LAVATORY.
27. 4" SD UP TO ROOF DRAIN.
28. 4" OD UP TO ROOF DRAIN.
29. 4" SANITARY, 2" VENT AND 1" CW TO WATER CLOSET.
30. 2" SANITARY, 2" VENT AND 3/4" CW TO URINAL.
31. 1/2" CW TO HOSE BIBB.
32. WHA-2, PROVIDE ACCESS TO WATER HAMMER ARRESTOR.
33. WHA-4, PROVIDE ACCESS TO WATER HAMMER ARRESTOR.
34. 2-1/2" CW UP FROM FLOOR BELOW.
35. 2-1/2" CW UP TO FLOOR ABOVE.
36. 2" DRAIN FROM ELEVATOR SUMP PUMP TO DISCHAGE IN TO MOP BASIN WITH AIRGAP.
37. 3/4" HWC DOWN FROM LAVS ABOVE.
38. REFER TO DETAIL 15/P-500 FOR BYPASS OF PRV STATION FOR IRRIGATION SYSTEM.
39. 1/2" HW CONNECT TO EXISTING HW AS SHOWN.
40. 1/2" CW CONNECT TO EXISTING CW AS SHOWN.
41. 1/2" HW DOWN TO HOT FOOD WELL.
42. 1/2" CW AND 1/2" HW DOWN TO TILTING KETTLE.
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
47 A
M
P-140
ENLARGED PLANS
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - BOILER ROOM & KITCHEN1
PLAN NORTH
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - FIRST FLOOR RESTROOM GROUP2
PLAN NORTH
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - FIRST FLOOR STAFF RESTROOM4 1/4" = 1'-0"
ENLARGED PLUMBING PLAN - KINDERGARTEN RESTROOMS3 1/4" = 1'-0"
ENLARGED PLUMBING PLAN - SECOND FLOOR STAFF RESTROOM5
PLAN NORTHPLAN NORTH PLAN NORTH
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - SECOND FLOOR RESTROOM GROUP6
PLAN NORTH
REVISION DATE
WC-3
WC-3
L-1
L-1
1"
1"
1/2"
1/2"
3/4"
3/4"
1-1/2"
WCO-1
2"FD-1
W/ TG-1
2"FD-1
W/ TG-1
L-1
L-1
WC-3
WC-3
2"
2"
2"
2"
2"
2"2"
4"4"
4"
WC-2
L-2
L-2
S-2
W/ GDU-1
S-2
W/ GDU-1
WC-2
2"
1-1/2"
3/4"
3/4"
3/4"
3/4"
1"1/2"
1/2"1/2"
1/2"
1"
1"
WCO-1
WCO-1
WC-2
WC-2
2"FD-1
W/ TG-1
2"FD-1
W/ TG-1
L-2
L-2
S-2
W/ GDU-1
S-2
W/ GDU-1
4"
2"
2"
2"
2"2"
2"
2"2"
2"
4"
4" 4"
4"
2"
2"2"
2"
4"
4"
3"
S-1
HB-1
HB-1
3/4"3/4"
UR-1
UR-1
WC-1
WC-2
WC-2
WC-1
WC-1
1"
3/4"
3/4"
1"
1"1"
WC-1
WC-1
WC-1
3/4"3/4"
2 1/2"
2 1/2" 2"
1 1/2"
3/4"3/4"
3/4"3/4"3/4"
HB-1
HB-1
WC-2
WC-2
WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
L-1
L-2
L-1
L-1
L-1
1"
1/2"
3/4"
1"1/2"
1/2"
L-1
L-1
L-1
L-1
L-2
L-1
L-1
L-1
L-1
L-2
1/2"
3/4"
1"
1/2"
1/2" 1/2"
1/2"
1"1/2"
L-1
L-1
L-1
L-1
L-2
3/4"
L-1
L-1
L-1
L-1L-2
2"
2"
2"
2"2"
4"
2"
2"
S-1
FD-1
FD-1
FD-1
FD-1
FD-1
L-2
L-1
L-1
L-1L-1
3"
4"
4"
4"
2" 2"
2"4"
2"
4"
3"
2"
3"
2"
2"
2"
2"
2"
2"
2"
2"
2" 2"
2"
2"
2"2"2"
2"
2"
4"
4"
2"
2"
L-2
L-1
L-1
L-1
L-1
L-2
L-1
L-1
L-1
L-1
WC-1
WC-1
WC-2
WC-2
WC-1
WC-1
WC-2
WC-2
2"WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
WC-1
3"
2"
2"
2"
2"
2"2"
2"
2"
2"
2"
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
49 A
M
P-142
PLUMBINGISOMETRICS
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
1RESTROOM GROUP ISOMETRIC - DOMESTIC WATER
2RESTROOM GROUP ISOMETRIC - SANITARY & VENT
REVISION DATE
3RESTROOM GROUP ISOMETRIC - DOMESTIC WATER 131A & 132A
4RESTROOM GROUP ISOMETRIC - SANITARY & VENT 131A & 132A
5RESTROOM GROUP ISOMETRIC - DOMESTIC WATER 214 & 124
6RESTROOM GROUP ISOMETRIC - SANITARY & VENT 214 & 124
LOCKING NUT
SUPPORT NUT
NUT AND BOLT
180° GALVANIZED SHEET STEELSADDLE MIN. 9" LONG, RE: SPEC.
HANGER ROD
HEAVY DUTY CLEVIS HANGER
VAPOR BARRIER INSULATION, RE:SPEC
180° INSERT CALCIUM SILICATE INSULATION OFSAME THICKNESS AS PIPE INSULATION
METAL BOX FASTEN TO STUDS OR WALL
INTEGRAL WATER HAMMER ARRESTOR
1/4 TURN STOP VALVE
3/8" OUTLET CONNECTION
1/2" INLET CONNECTION
1/2"HW, SEE PLAN
1/2"TW TO LAVATORY/ SINK
1/2"CW TO LAVATORY/SINK
SERVICE UNION (TYP.)
TMV-1
1/2"CW, SEE PLAN
WALL CABINET AS SPECIFIED
ROUND SECURED CHROME COVERWITH VANDAL RESISTANT CENTERSCREW
WALL
WASTE
CLEANOUT PLUG
4"
SINK, SEEPLANS FORDESIGNATION
2" WCO-1
2"W & V WITHINWALL
1-1/2" WASTE TO WALLW/ ESCUTCHEON
INLET
OUTLETHO-HUBCOUPLING
1-1/2" THREADEDADAPTER
FINISHED FLOOR
BASE CABINETFLOOR
2" CHROMEPLATED WASTE
14" SPACE FORBASKET REMOVAL
SPACING DISTANCE TO EXISTINGROOF DRAIN. RE: ARCH CLAMPING RING RE: SPECS.
BALLAST
DRAIN RECEIVER CLIP
DRAIN RECEIVER
ROOF SYSTEM RE: ARCH.
UNDERDECK CLAMPROOF DRAIN CONDUCTOR
PIPING. RE: SPECS. RE: SPECS FOR INSTALLATIONCOORDINATE OPENING IN
EXISTING ROOF W/ ARCHITECTAND GENERAL CONTRACTOR
SLEEVE
GAS VENT
PATE PIPE SEAL
ROOF
GAS VALVE
GAS PIPE SUPPORTSTANDARD TYPE
UNION @ CONNECTION
ROOF LINE
DRIP LEG
1'-0" MIN.
GAS-FIRED
EQUIPMENT
SPACING DISTANCE TO EXISTINGROOF DRAIN. RE: ARCH
COORDINATE OPENING INEXISTING ROOF W/ ARCHITECTAND GENERAL CONTRACTOR
NEW CLAMPING RINGRE: SPECS.
EXISTING ROOF SYSTEMRE: ARCH.
ROOF DRAIN CONDUCTOR PIPING.RE: SPECS.
2" HIGH STANDPIPE.RE: SPECS.
OD-1
DRAIN RECEIVER
DRAIN RECEIVER CLIP
EXISTING BALLAST
NEW UNDERDECK CLAMP
MEDIUM PRESSURE GAS,SEE PLAN FOR CONT.
MANUAL GAS VALVE
SERVICE UNION
6" LONG DIRT LEGGAS PRESSURE REGULATOR
(GPR) SEE PLAN AND SCHEDULEFOR REQUIREMENTS
LOW PRESSURE GAS, SEEPLAN FOR CONTINUATION
INCREASER AS REQUIRED
PRESSURE GUAGE
(4) PIPE DIAMETERS
VENT TO ROOF FULL SIZEOF UNIT DISCHARGE W/
GOOSENECK
NOTE: SEE PLAN FOR PIPE
SIZES NOT INDICATED HERE.
2'-0" x 2'-0" x 6" CONCRETERETAINING RING BY P.C.
4" CAST IRONEXTENSION
4" - 45°ELBOW
BEDDING
45° WYEFITTING
SEWER, SEEPLANS CAST IRON SEWER FROM
BUILDING,RE: PLANS
FINISHEDGRADE
FLOW
CLEANOUT COVER, SEEPLUMBING EQUIPMENTSCHEDULE
GCO-1
STANCOR OIL-MINDER 115V, 1∅ CONTROL SYSTEM W/ BUILT IN AUDIBLE AND VISUALALARM WHEN PUMP DOESN'T RUN DUE TO OIL IN PIT, HIGH AMPERAGE OR HIGH
LIQUID CONDITION. PROVIDE SILENCING BUTTON FOR AUDIBLE ALARM BUILT INTOPANEL. PANEL SHALL HAVE ADDITIONAL CONTACT FOR A REMOTE ALARM LOCATION.
ELECTRICALOUTLET
POWERSUPPLY
MULTI-PIN CONNECTOR
MULTI-PIN CONNECTOR & CORD INCONDUIT LENGTHS AS REQUIRED
FLOOR
HIGH LIQUID ALARM FLOAT W/ CLAMP DEVICE TOMOUNT TO PUMP DISCHARGE PIPING
CHECK VALVE
SUMP PIT CAST IN PLACE COOR. W. G.C.
SUMP PUMP
COVER
GATE VALVE
OIL-MINDER POWER CABLE,PROBE CABLE & FLOAT CABLE
JUNCTION BOX PROVIDED W/ MULTI-PINCONNECTOR & CORD IN LENGTHS AS
REQUIRED
MULTI-PIN CONNECTOR
2"PD, SEE PLAN
WATER HAMMER ARRESTOR, SEE PLAN FORDESIGNATION, PROVIDE WITH ACCESSPANEL.
BALL VALVE
FULL SIZE OF SHOCK ABSORBER INLET
REDUCE IN VERTICAL AS INDICATED
WATER SUPPLY TO EQUIPMENT,SEE PLAN AND SCHEDULES
WATER HAMMER ARRESTOR,SEE PLAN FOR DESIGNATION,PROVIDE WITH ACCESS PANEL.
BALL VALVE
REDUCE IN VERTICAL ASINDICATED
WATER SUPPLY TO EQUIPMENT,SEE PLAN AND SCHEDULES
WATER HAMMER ARRESTOR,SEE PLAN FOR DESIGNATION,PROVIDE WITH ACCESS PANEL.
BALL VALVE
FINAL FIXTURE SERVED
CW HEADER WITHIN CHASE, SEEPLAN
WATER SUPPLY ABOVE CEILING, SEE PLAN
S.A. MAY BE POSITIONED ABOVE CEILING
FULL SIZE OF SHOCK ABSORBERINLET
FULL SIZE OF SHOCK ABSORBERINLET
5 PIPE
DIAMETERMINIMUM
BALL VALVE
CHECK VALVE
UNION
NEOPRENE ISOLATED CLAMP
IN-LINE CIRCULATION PUMP,
SEE PLAN FOR DESIGNATION
UNI-STRUT MOUNTED ON WALL
UNION
BALL VALVE
3/4" HWC FROM SYSTEM
(E)BFP
(E)BFP
(E) 3" TO IRRIGATIONWATER SYSTEMRE: PLANS
3" DOMESTIC CW FROMWATER SERVICE MAINRE: PLANS
(E)PRV
(E)PRV
(E)PRV
(E)BYPASS
FINISHED FLOOR
CONNECT NEW 3" CWTO EXSITING 3" CW TOBY-PASS PRV STATIONFOR IRRIGATIONMODIFICATIONS
CONNECT NEW 3" CWTO EXSITING 3"IRRIGATION BACKFLOWDEVICE
REPAIR CONNECTIONTO EXISTINGDOMESTIC BACKFLOWDEVICE
(E) 3" CW TODOMESTIC SYSTEM
(E)BFP
(E)BFP
(E) 3" TO IRRIGATIONWATER SYSTEMRE: PLANS
3" DOMESTIC CW FROMWATER SERVICE MAINRE: PLANS
(E)PRV
(E)PRV
(E)PRV
(E)BYPASS
FINISHED FLOOR
REMOVE EXISTING TEEFOR IRRIGATIONMODIFICATIONS.
(E) 3" CW TODOMESTIC SYSTEM
REMOVE SECTION OFRISER FORIRRIGATIONMODIFICATIONS.
1 CLEVIS HANGER DETAILNOT TO SCALE6 ICE MAKER BOX DETAIL
NOT TO SCALE10 THERMOSTATIC MIXING VALVE DETAILNOT TO SCALE13 WALL CLEANOUT DETAIL
NOT TO SCALE
11 PLASTER TRAP DETAIL (PT-1)NOT TO SCALE
7 ROOF DRAIN DETAILNOT TO SCALE 2 GAS PIPE ROOF PENETRATION DETAIL
NOT TO SCALE
3 ROOFTOP GAS CONNECTION DETAILNOT TO SCALE8 OVERFLOW ROOF DRAIN DETAIL
NOT TO SCALE
4 GAS PRESSURE REGULATOR PIPING DETAILNOT TO SCALE
5 GRADE CLEANOUT - EXTERIORNOT TO SCALE9 ELEVATOR SUMP PUMP DETAIL
NOT TO SCALE12 WATER HAMMER ARRESTOR DETAILSNOT TO SCALE
15 WATER ENTRY DETAIL (NEW)NOT TO SCALE
16 WATER ENTRY DETAIL (DEMO)NOT TO SCALE
14 CIRCULATION PUMP DETAILNOT TO SCALE
ENVIS
ION
MEC
HA
NIC
AL
EN
GIN
EER
S I
NC
.
9777 P
yramid
Court, S
uit
e 1
20
Engle
wood, C
O 8
0112
Tel-
303-6
88-0
223
Fax- 303-6
88-3
584
envis
ionengrs.c
om
Proje
ct #
Date
Drawn By
Checked By:
Project Number
Sheet Name
Copyright:
ALL DRAWN AND WRITTEN INFORMATIONAPPEARING HEREIN SHALL NOT BE
DUPLICATED, DISCLOSED OR OTHERWISEUSED WITHOUT THE WRITTEN CONSENT OF
MOA ARCHITECTURE
NOT FOR
CONSTRUCTION
AD
DIT
ION
S A
ND
RE
NO
VA
TIO
NS
016-0
09
7/29
/201
6 10
:38:
50 A
M
P-500
PLUMBINGDETAILS
SIE
RR
A E
LE
ME
NT
AR
Y S
CH
OO
L
JJR
08.04.16
16100.00
7771
Oak
St.
Arv
ada,
CO
800
05
BID SET
JCF
REVISION DATE