firefinder xls system basics (12!10!04)1
TRANSCRIPT
Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLSSystem Basics
Siemens Building Technologies Fire Products DivisionCompany Confidential
Fire Alarm System Basics
System & Processor
Inputs Outputs
An
nu
nc
iatio
n
& C
on
trol
Siemens Building Technologies Fire Products DivisionCompany Confidential
Inputs
Manual pull stations• HMS-S, HMS-D, HMS-SA, HMS-M, HMS-2S
Monitor points (Transmit-Receive Interface, or TRI)• HTRI-S, HTRI-D, HTRI-R, HTRI-M• Used for waterflow, tamper, security, damper• Relay output available
Conventional Zone Module – HZM Short circuit isolator – HLIM Intelligent LEDs
• ILED-HC, ILED-HW Detectors
• Bases – DB-11, DB-HR, ADBH-11, AD-11P, AD-HR• Detectors – HFP-11, HFPT-11
– FirePrint!
Inputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
What is FirePrint?
A revolutionary fire detection method that distinguishes between a fire’s unique “fingerprint” and deceptive phenomena, and reports only real fires.
11 different selectable applications FirePrint is NOT a fancy form of “alarm
verification/confirmation”• Makes decisions based on obscuration/temperature/time
Siemens offers the No False Alarm Guarantee• If the system is designed and maintained properly, Siemens
will pay any fines associated with false alarms from FirePrint detectors
• No other manufacturer offers this guarantee
• Since 1997, total fines paid out equals $0!
Inputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
DPU Device Programming Unit
Tests/addresses both MXL and FireFinder XLS devices• Not used for XL3 devices
Built in loop tester!• Have contractor test all loop wiring & devices before panel
gets there!• Indicates # & type of devices, and what device is at what
address• Finds multiple response addresses• Ground faults, activations indicated
Connection to label printer• Prints loop # & address• Multiple copies available
Inputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
DLC – Device Loop Card
Plug-in card 252 devices on a loop! 1 or 2 loops per card
• T-tapped inside card• Total 252 total devices in any combination
50 cards/100 loops per system 2500 devices per system Non-twisted, non-shielded wire
• Great for retrofits! Wire is POLARITY INSENSITIVE (SureWire) Smart Degrade capability
• Loop accessories/outputs operate in Degrade
Inputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
CDC-4 Conventional Detector Card
Plug-in card 4 conventional detection circuits Optional Alarm Verification Supports Siemens conventional detectors & circuit
closure devices Supports select COMPETITIVE conventional detectors
• Check the installation instruction in the Tech Support area of the website
Inputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
PMI – Person/Machine Interface
Main operator interface & central processor Large graphics screen for events, details, icons &
bitmaps System event LEDs Large lighted buttons – prompts users through system
operation “More Info” button – users get to detail & map screens Touch screen for reports and maintenance
System Processor
An
nu
nc
iatio
n
& C
on
trol
Siemens Building Technologies Fire Products DivisionCompany Confidential
Lighted buttons to prompt user
Partial System Disable
Audible Status
-Large 6” display with touch screen
System Status LED’s
Menu Access
Navigation Controls
HELP
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
MORE
INFO
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
Siemens Building Technologies Fire Products DivisionCompany Confidential
Enclosures
CAB1• Supports 1 row (4 module spaces) with PTB & batteries
CAB2• Supports 2 rows (8 module spaces) with PTB & batteries
CAB3• Supports 3 rows (12 module spaces) with PTB & batteries
Transponder enclosures• Same as CAB enclosures w/ grill outer doors
REMBOX2• Supports 2 inner door rows• No card cages
REMBOX4• Supports 4 inner door rows• No card cages
CAB-BATT Battery Box• For 55 AH, 100 AH batteries
System Processor
CAB1Small enclosure (one row) Ships complete:
• back box• inner door• outer door• module mounting plate
(CAB-MP)• door lens (OD-LP)
Options:• CAB1R (red version)• Tamper switch (HTSW-1)• Semi-flush trim kit (CAB1-TK)
CAB2 Medium
Enclosure (2 row)
CAB2 Ships complete:
• CAB2-BB• CAB2-BD• (2) CAB-MP’s• (1) OD-LP
Requires either (1):• OD-LP (lens)• OD-BP (blank)• OD-GP (grill)
Options:CAB2R (red version)CAB-2TK (semi-flush trim kit)
CAB-3 Large Enclosure
(3 row) CAB3 Ship Complete
• CAB3-BB • CAB3-BD• (3) CAB-MP’s• (1) OD-LP
Requires either (2):• OD-LP (lens)• OD-BP (blank)
• OD-GP (grill)
Options:CAB3R (red version)CAB-3TK (semi-flush trim kit)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Remote “Lobby” EnclosuresREMBOX2 and REMBOX4
REMBOX2• Space for (2) inner door
modules. • Typically LVM and up to
(4) SCM-8’s • Optional plate to mount
(4) OCM-16 or SIM-16• Local tamper switch
option (HTSW-1)• Semi-flush or surface
mounting. No trim kit needed.
REMBOX4• Space for (4) inner door
modules. Typically LVM and SCM-8’s.
• Optional plate to mount (8) OCM-16 or SIM-16
• Local tamper switch option (HTSW-1)
• Semi-flush or surface mounting. No trim kit needed.
System Processor
Siemens Building Technologies Fire Products DivisionCompany Confidential
CC-5/CC-2 Card cages
All wiring lands on removable terminal blocks All cards fit in the same card cage
• No separate Fire/Voice card cages Efficient card mounting
• 10 cards in 19”w x 14”h row– MXL – 6 cards in 19”w x 17”h row
• Less space required = less/smaller enclosures 60 pin bus between all cardcages
• Connected by 1 cable!
System Processor
Siemens Building Technologies Fire Products DivisionCompany Confidential
All cards same size and plug into CC-5/CC-2 cardcages
Thumb screws for handles & to keep cards in place
Power limited Field wiring (top)
Non-Power limited internal wiring
(bottom)
Power input to cards from PSC-12/PSX-12 or ZAC/ZAM
amplifiers
Out of enclosure to field devices or remote enclosures
60 pin bus - power, data, communications etc.
Removable terminal blocks (with covers)
Card guides removable for easy wiring access in enclosure - mounted with (2) captive screws each.
Labels to identify which card goes in which slot.
Siemens Building Technologies Fire Products DivisionCompany Confidential
PSC-12/PSX-12 Power Supplies
Filtered & Regulated 12 amp 24VDC supply• 5 amp continuous use
120 to 240 volt AC input, 50/60 Hz. PSC-12 – Battery charger for 100AH batteries
• New batteries – BTX-3 PSX-12 – Power only (no charger) to
extend power in cabinet Four 2-amp Form “C” relays built in
• Alarm, trouble, 2 programmable
System Processor
Siemens Building Technologies Fire Products DivisionCompany Confidential
ZIC-4A – Zone Indicating Card
Plug-in card Four Class A or B circuits Used as
• NAC – horn or strobe• Speaker circuit – 1 or 2 channel• Releasing circuit• Municipal Tie/Leased Line• Bell follower (NAC extender)
4 Amp capacity per circuit (96 Watts speaker)
Outputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
CRC-6 Controllable Relay Card
Six independently controlled Form C relays 4 amps 30VDC/120VAC (resistive) 3.5 amps 120VAC (inductive @ 0.6 p.f.) Coils supervised Status and troubleshooting LEDs built in
Outputs
Siemens Building Technologies Fire Products DivisionCompany Confidential
SSD System Status Display
4 x 40 character LCD display Local sounder & scroll buttons Acknowledge/Silence/Reset capabilities on SSD-C
• Keyswitch activates control buttons Can be mounted in a larger enclosure
• Model SSD-C-REM Up to 32 on a system!
SSD-C
An
nu
nc
iatio
n
& C
on
trol
Siemens Building Technologies Fire Products DivisionCompany Confidential
RPM Remote Peripheral Module
Two serial ports & 1 parallel port Mounts in its own enclosure
• Can be mounted under desk Used for
• Printer connection (PAL-1)– No VDT connection available
• FSI connection• Apogee Insight Life Safety system connection
OutputsA
nn
un
cia
tion
& C
on
trol
Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLS – Module review (vs. MXL)
FireFinder XLS MXL PMI MMB-2, MMB-3, MKB-4 DLC ALD-2I ZIC-4A CSM-4 PSC-12/PSX-12 MPS-6/12 CC-5/CC-2 MOM-4/MOM-2 CAB1, CAB2, CAB3 MSE-2, MME-3, MLE-6 CRC-6 CRM-4 SSD, SSD-C RCC-1, RCC-2 RPM PIM-1, PIM-2
Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLSSystems Basics
Thank You!Mark Pavlica
Product Manager
Siemens Fire Safety