firefinder xls system basics (12!10!04)1

28
Siemens Building Technologies Fire Products Division Company Confidential FireFinder XLS System Basics

Upload: comte6668991

Post on 27-Apr-2015

272 views

Category:

Documents


15 download

TRANSCRIPT

Page 1: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLSSystem Basics

Page 2: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

Fire Alarm System Basics

System & Processor

Inputs Outputs

An

nu

nc

iatio

n

& C

on

trol

Page 3: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

Inputs

Manual pull stations• HMS-S, HMS-D, HMS-SA, HMS-M, HMS-2S

Monitor points (Transmit-Receive Interface, or TRI)• HTRI-S, HTRI-D, HTRI-R, HTRI-M• Used for waterflow, tamper, security, damper• Relay output available

Conventional Zone Module – HZM Short circuit isolator – HLIM Intelligent LEDs

• ILED-HC, ILED-HW Detectors

• Bases – DB-11, DB-HR, ADBH-11, AD-11P, AD-HR• Detectors – HFP-11, HFPT-11

– FirePrint!

Inputs

Page 4: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

What is FirePrint?

A revolutionary fire detection method that distinguishes between a fire’s unique “fingerprint” and deceptive phenomena, and reports only real fires.

11 different selectable applications FirePrint is NOT a fancy form of “alarm

verification/confirmation”• Makes decisions based on obscuration/temperature/time

Siemens offers the No False Alarm Guarantee• If the system is designed and maintained properly, Siemens

will pay any fines associated with false alarms from FirePrint detectors

• No other manufacturer offers this guarantee

• Since 1997, total fines paid out equals $0!

Inputs

Page 5: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

DPU Device Programming Unit

Tests/addresses both MXL and FireFinder XLS devices• Not used for XL3 devices

Built in loop tester!• Have contractor test all loop wiring & devices before panel

gets there!• Indicates # & type of devices, and what device is at what

address• Finds multiple response addresses• Ground faults, activations indicated

Connection to label printer• Prints loop # & address• Multiple copies available

Inputs

Page 6: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

DLC – Device Loop Card

Plug-in card 252 devices on a loop! 1 or 2 loops per card

• T-tapped inside card• Total 252 total devices in any combination

50 cards/100 loops per system 2500 devices per system Non-twisted, non-shielded wire

• Great for retrofits! Wire is POLARITY INSENSITIVE (SureWire) Smart Degrade capability

• Loop accessories/outputs operate in Degrade

Inputs

Page 7: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

CDC-4 Conventional Detector Card

Plug-in card 4 conventional detection circuits Optional Alarm Verification Supports Siemens conventional detectors & circuit

closure devices Supports select COMPETITIVE conventional detectors

• Check the installation instruction in the Tech Support area of the website

Inputs

Page 8: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

PMI – Person/Machine Interface

Main operator interface & central processor Large graphics screen for events, details, icons &

bitmaps System event LEDs Large lighted buttons – prompts users through system

operation “More Info” button – users get to detail & map screens Touch screen for reports and maintenance

System Processor

An

nu

nc

iatio

n

& C

on

trol

Page 9: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

Lighted buttons to prompt user

Partial System Disable

Audible Status

-Large 6” display with touch screen

System Status LED’s

Menu Access

Navigation Controls

HELP

Page 10: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

MORE

INFO

Page 11: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

Page 12: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

Page 13: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

Enclosures

CAB1• Supports 1 row (4 module spaces) with PTB & batteries

CAB2• Supports 2 rows (8 module spaces) with PTB & batteries

CAB3• Supports 3 rows (12 module spaces) with PTB & batteries

Transponder enclosures• Same as CAB enclosures w/ grill outer doors

REMBOX2• Supports 2 inner door rows• No card cages

REMBOX4• Supports 4 inner door rows• No card cages

CAB-BATT Battery Box• For 55 AH, 100 AH batteries

System Processor

Page 14: FireFinder XLS System Basics (12!10!04)1

CAB1Small enclosure (one row) Ships complete:

• back box• inner door• outer door• module mounting plate

(CAB-MP)• door lens (OD-LP)

Options:• CAB1R (red version)• Tamper switch (HTSW-1)• Semi-flush trim kit (CAB1-TK)

Page 15: FireFinder XLS System Basics (12!10!04)1

CAB2 Medium

Enclosure (2 row)

CAB2 Ships complete:

• CAB2-BB• CAB2-BD• (2) CAB-MP’s• (1) OD-LP

Requires either (1):• OD-LP (lens)• OD-BP (blank)• OD-GP (grill)

Options:CAB2R (red version)CAB-2TK (semi-flush trim kit)

Page 16: FireFinder XLS System Basics (12!10!04)1

CAB-3 Large Enclosure

(3 row) CAB3 Ship Complete

• CAB3-BB • CAB3-BD• (3) CAB-MP’s• (1) OD-LP

Requires either (2):• OD-LP (lens)• OD-BP (blank)

• OD-GP (grill)

Options:CAB3R (red version)CAB-3TK (semi-flush trim kit)

Page 17: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

Remote “Lobby” EnclosuresREMBOX2 and REMBOX4

REMBOX2• Space for (2) inner door

modules. • Typically LVM and up to

(4) SCM-8’s • Optional plate to mount

(4) OCM-16 or SIM-16• Local tamper switch

option (HTSW-1)• Semi-flush or surface

mounting. No trim kit needed.

REMBOX4• Space for (4) inner door

modules. Typically LVM and SCM-8’s.

• Optional plate to mount (8) OCM-16 or SIM-16

• Local tamper switch option (HTSW-1)

• Semi-flush or surface mounting. No trim kit needed.

System Processor

Page 18: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

CC-5/CC-2 Card cages

All wiring lands on removable terminal blocks All cards fit in the same card cage

• No separate Fire/Voice card cages Efficient card mounting

• 10 cards in 19”w x 14”h row– MXL – 6 cards in 19”w x 17”h row

• Less space required = less/smaller enclosures 60 pin bus between all cardcages

• Connected by 1 cable!

System Processor

Page 19: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

All cards same size and plug into CC-5/CC-2 cardcages

Thumb screws for handles & to keep cards in place

Page 20: FireFinder XLS System Basics (12!10!04)1

Power limited Field wiring (top)

Non-Power limited internal wiring

(bottom)

Power input to cards from PSC-12/PSX-12 or ZAC/ZAM

amplifiers

Out of enclosure to field devices or remote enclosures

60 pin bus - power, data, communications etc.

Removable terminal blocks (with covers)

Card guides removable for easy wiring access in enclosure - mounted with (2) captive screws each.

Labels to identify which card goes in which slot.

Page 21: FireFinder XLS System Basics (12!10!04)1
Page 22: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

PSC-12/PSX-12 Power Supplies

Filtered & Regulated 12 amp 24VDC supply• 5 amp continuous use

120 to 240 volt AC input, 50/60 Hz. PSC-12 – Battery charger for 100AH batteries

• New batteries – BTX-3 PSX-12 – Power only (no charger) to

extend power in cabinet Four 2-amp Form “C” relays built in

• Alarm, trouble, 2 programmable

System Processor

Page 23: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

ZIC-4A – Zone Indicating Card

Plug-in card Four Class A or B circuits Used as

• NAC – horn or strobe• Speaker circuit – 1 or 2 channel• Releasing circuit• Municipal Tie/Leased Line• Bell follower (NAC extender)

4 Amp capacity per circuit (96 Watts speaker)

Outputs

Page 24: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

CRC-6 Controllable Relay Card

Six independently controlled Form C relays 4 amps 30VDC/120VAC (resistive) 3.5 amps 120VAC (inductive @ 0.6 p.f.) Coils supervised Status and troubleshooting LEDs built in

Outputs

Page 25: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

SSD System Status Display

4 x 40 character LCD display Local sounder & scroll buttons Acknowledge/Silence/Reset capabilities on SSD-C

• Keyswitch activates control buttons Can be mounted in a larger enclosure

• Model SSD-C-REM Up to 32 on a system!

SSD-C

An

nu

nc

iatio

n

& C

on

trol

Page 26: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

RPM Remote Peripheral Module

Two serial ports & 1 parallel port Mounts in its own enclosure

• Can be mounted under desk Used for

• Printer connection (PAL-1)– No VDT connection available

• FSI connection• Apogee Insight Life Safety system connection

OutputsA

nn

un

cia

tion

& C

on

trol

Page 27: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLS – Module review (vs. MXL)

FireFinder XLS MXL PMI MMB-2, MMB-3, MKB-4 DLC ALD-2I ZIC-4A CSM-4 PSC-12/PSX-12 MPS-6/12 CC-5/CC-2 MOM-4/MOM-2 CAB1, CAB2, CAB3 MSE-2, MME-3, MLE-6 CRC-6 CRM-4 SSD, SSD-C RCC-1, RCC-2 RPM PIM-1, PIM-2

Page 28: FireFinder XLS System Basics (12!10!04)1

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLSSystems Basics

Thank You!Mark Pavlica

Product Manager

Siemens Fire Safety

[email protected]