Flow measurement with primary element

15/05/2018 Primary element flowrate measurement

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 2: Flow measurement with primary element

Flow measurement with DP transmitter

2

Measurement of a differential pressure: upstream and downstream of a primary element

Qv = V1S1 = V2S2

• Increase the speed (Qv)

• Increase the dynamical pressure

• Decrease of the static pressure

15/05/2018 Primary element flowrate measurement

Page 3: Flow measurement with primary element

C = pressure lost coefficient determined by experimental test

E = approach coefficient 𝐸 = 1/ 1 − 𝑏4

ε = expansion coefficient

d = internal primary element diameter

D = Internal pipe diameter

Primary Element

3

Volumetric flowrate is depending of the differential pressure square root made by the primary element

15/05/2018 Primary element flowrate measurement

HP LP

Page 4: Flow measurement with primary element

Flow type

4

LAMINAIRE TURBULENT

So it is necessary to ensure to have the right straight length

15/05/2018 Primary element flowrate measurement

Laminar Turbulent

Page 5: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

What are the Primary Element ?

15/05/2018 Primary element flowrate measurement

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 6: Flow measurement with primary element

Primary elements

15/05/2018 Primary element flowrate measurement6

Pitot Tube

Diaphragm

Venturi and micro-venturi Nozzles

V-ConeWedges

Orifice plate

Page 7: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Pitot Tube

15/05/2018 Pitot tube

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 8: Flow measurement with primary element

Principle

15/05/2018 Pitot Tube 8

Low cost solution for measurement in large diameter pipes or ducts

❖ Low permanent pressure lost – energy lost use is minimal

❖ Robust construction – long service life and virtually impossible to wear out

❖ Negligible wear – long term stability with Zero drift or degradation

Negative pressurePositive pressure

Flow direction

Average point for the

speed

Pitot tubes generates a differential pressure proportional

to the dynamic pressure

Page 9: Flow measurement with primary element

Pitot Tube

15/05/2018 Pitot Tube9

Single point 5 RB

Average 5RD

Pitot Tubes with FKC

for Flow measurement and corrected Flowrate (Nm3/h)

Page 10: Flow measurement with primary element

Pitot tube characteristics

• Rangeability: 10 : 1

• Accuracy ± 1 % of real flow rate

• Maxi Temperature: 500°c

• DN50 to DN1500

• 316 L

• Be careful with loaded fluids➔ fooling !

15/05/2018 Pitot Tube10

Page 11: Flow measurement with primary element

❖ 5RD Average

16/09/2015 Pitot Tube 11

What kind of fluids?

Water Gas Steam

❖ 5RD Single point

Gas

Page 12: Flow measurement with primary element

16/09/2015 Pitot Tube 12

What kind of pipe?

Circular pipe Rectangular pipe

To know the internal diameter

and the thickness of the pipeTo know the internal length, height and

thickness of the duct

IMPORTANT: Specify the pitot tube

localization: in the length or height

Be careful if the pipe has a thermal protection !!!

Page 13: Flow measurement with primary element

Pitot tube accuracy with the flowrate

15/05/2018 Pitot Tube13

Pitot tube only

Be careful to the minimal flowrate !!!

FKC11 and 22 Accuracy50-100% of output 0,10% span20-50 % of output 0,25% span10-20% of output 0,50% span

Pressure transmitter only

Page 14: Flow measurement with primary element

Straight length

15/05/2018 Pitot tube14

No straight length, degraded accuracy !!!

5RB pitot tube is more

sensitive ot the straight lenght

than 5RD pitot tube !! !

Page 15: Flow measurement with primary element

URV transmitter : 1,74

FKC11 et FKC22Flowrate DP Transmitter accuracy Measurement accuracy

T/h or m3/h mbar % Span mbar %1200 1,74 0,1 0,00174 0,1

900 0,98 0,1 0,00174 0,2

800 0,77 0,25 0,00435 0,6600 0,44 0,25 0,00435 1,0500 0,3 0,5 0,0087 2,9400 0,19 0,5 0,0087 4,6

300 0,11 0,5 0,0087 7,9200 0,05 0,5 0,0087 17,4

100 0,01 0,5 0,0087 87,0

Exemple of accuracy

15/05/2018 15

Accuracy = Transmitter + Pitot + all element of the measurement chain

: Imprecision (Pitot (2%) + transmitter) : 10 % around at 300 m3/h

Pitot Tube

Page 16: Flow measurement with primary element

Application

• Biogaz

• Boiler

• Incineration plant

• Cogeneration plant

15/05/2018 Pitot Tube 16

• Compressor and HVAC

• Flow gas or atmospheric emission flue gas measurement

• Oxygenation of water treatment plant’s aerating tank

Page 17: Flow measurement with primary element

Measurement of steam flowrate with a pitot tube

17

Condensat

chamber

Pitot Tube

Pitot Tube 15/05/2018

Page 18: Flow measurement with primary element

Pitot tube with remote transmitter

18

Pitot tube with a remote

erection

Pressure transmitter

Differential pressure transmitter

15/05/2018 Pitot Tube

Page 19: Flow measurement with primary element

15/05/2018 Primary element flowrate measurement 19

Absolute

pressure XTR

Temperature

measurement

Differential

pressure XTR

Pitot tube

Biogaz flow measurement with Pitot tube

Page 20: Flow measurement with primary element

Automatic unclogging cabinet system – Pitot tube

15/05/2018 Pitot tube20

Air injection with programming time in the 5RD and 5RB pitot tubes

For loaded fluids

Page 21: Flow measurement with primary element

Velocity profile

15/05/2018 Pitot Tube21

Can be made by FEF

Standard NF X10-112

To determine the velocity profile

inside the pipe

Check and/or verify the

precise localization of the

pitot tube inside the pipe …

Page 22: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

V-Cone

15/05/2018 V-Cone

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 23: Flow measurement with primary element

Technical datasheet – V-Cone

15/05/2018 V-Cone23

❖ Liquid, gas and steam measurement

for high loaded and high viscosity

fluid. For example: waste water, oil…

❖ Straight length very low (3D/1D)

❖ Flow profile very stable, High accuracy

(< 1% of the flow) and reputability: 10:1

❖ No corrosion of the cone by abrasion

❖Many FCX working for « subsea »

flowrate measurement (oil&gas

application)

❖Measurement in 2 ways

Page 24: Flow measurement with primary element

Performance

15/05/2018 V-Cone24

• Accuracy: to +/- 0.5% of rate

• Turndown: from 10:1

• Repeatability: +/- 0.1%

Page 25: Flow measurement with primary element

Accuracy

15/05/2018 V-Cone25

❖ All and each V-Cones are supplied with standard water calibration.

❖ +/-0.5% Accuracy for all V-Cones calibrated over the total Re Range

of the application for a 10:1 turndown.

❖ +/-1.0% Accuracy for all V-Cones operated above 20,000 Re but not

calibrated over the total Re application range.

❖Meters operated below Re 8,000 may require a high viscosity

calibration.

❖ Stated accuracy is valid through all the Turndown of the meter.

Page 26: Flow measurement with primary element

Wafer-Cone

15/05/2018 V-Cone26

Page 27: Flow measurement with primary element

V-Cone

15/05/2018 V-Cone27

Page 28: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Orifice plate

15/05/2018 Orifice plate

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 29: Flow measurement with primary element

Technical specification: Orifice plate

15/05/2018 Orifice plate29

• Accuracy: 1,5 % or flow (ISO 5167)• Rangeability: 6 : 1• Excellent repeatability

• Connection clogging because of high loaded fluid

• High pressure lost

Page 30: Flow measurement with primary element

Integrated orifice

• Measurement of low flowrate (liquid or gas)

• Assembly with flange upon request

Orifice plate3015/05/2018

Page 31: Flow measurement with primary element

Orifice plate3115/05/2018

Steam flowrate with orifice plate

Page 32: Flow measurement with primary element

Corrected steam flowrate with orifice plate

15/05/2018 Orifice plate32

Be careful to the straight length !

Page 33: Flow measurement with primary element

Straight length: Orifice plate

15/05/2018 Orifice plate33

Straight length according to ISO 5167

Page 34: Flow measurement with primary element

34

Diaphragm installation

Orifice plate15/05/2018

Page 35: Flow measurement with primary element

Diaphragm installation

15/05/2018 Diaphragm35

Page 36: Flow measurement with primary element

Exemple of installation

36 Diaphragm15/05/2018

Page 37: Flow measurement with primary element

Exemple of installation

37 Diaphragm15/05/2018

Page 38: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Venturi and micro venturi

15/05/2018 Venturi and micro venturi

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 39: Flow measurement with primary element

Venturi & Micro-venturi, the difference

15/05/2018 Venturi and micro venturi39

Venturi Micro venturi

Page 40: Flow measurement with primary element

Technical datasheet - Venturi

15/05/2018 Venturi and micro venturi40

• Accuracy: 1,5% of maximal flow

• Rangeability: 6 : 1

• Low pressure lost

• Recommended for high viscosity and high loaded fluid

Page 41: Flow measurement with primary element

Straight length – Venturi

15/05/2018 Venturi and micro venturi41

Straight length according to ISO 5167

Page 42: Flow measurement with primary element

Technical datasheet - Micro venturi

• Rangeability: 6 : 1

• Accuracy: 1,5 % of flow

• Low pressure lost

15/05/2018 Venturi and micro venturi42

Page 43: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Nozzle

15/05/2018 Nozzle

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 44: Flow measurement with primary element

Technical datasheet - Nozzle

15/05/2018 Nozzle44

❖ Recommanded for high Reynolds number > 50000, for exemple : steam with

high temperature. DO NOT USE THIS PRIMARY ELEMENT FOR SLUDGE

❖ Accuracy: 1,5 % of flow (ISO 5167)

❖ Rangeability: 6 : 1

Page 45: Flow measurement with primary element

Straight length - Nozzle

15/05/2018 Nozzle45

Straight length according to ISO 5167

Page 46: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Wedges

15/05/2018 Wedges

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 47: Flow measurement with primary element

Flowrate measurement with a wedges

15/05/2018 Wedges47

Measurement for high viscosity or high loaded fluid

Page 48: Flow measurement with primary element

Technical datasheet - Wedges

15/05/2018 Wedges48

❖ Accuracy: < 1% of maximal flow

❖ Repeatability: ± 0,2%

❖ Correct measurement with a low

Reynolds (<300)

❖ Low pressure lost

❖ Measurement for fluid with high

viscosity

❖ Dual measurement

Oil&Gas application

Page 49: Flow measurement with primary element

Straight length – Wedges

15/05/2018 Wedges49

Page 50: Flow measurement with primary element

Exemple of measurement with a wedges

15/05/2018 Wedges50

Page 51: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]

Conclusion

15/05/2018 Primary element flowrate measurement

Fuji Electric Corp. of America50 Northfield Avenue Edison, NJ

[email protected]

(732) 560-9410

americas.fujielectric.com

Page 52: Flow measurement with primary element

Some advises…

• DP transmitter must be in square root or the PLC

Do not put the square root function on both

• The range of the pressure transmitter is according to the primary element calculation so to the flowrate

The URV is link to the maximum flowrate calculated

• Caution during the installation of the primary element (for example not in the right direction)

• BE careful to the clogging of the primary element

5215/05/2018 Primary element flowrate measurement

Page 53: Flow measurement with primary element

53

Primary element comparison

DIAPHRAGM VENTURI NOZZLE PITOT

Pressure lost High pressure lost Low pressure lost Low pressure lost Low pressure lost

Accuracy According to a standard According to a standard According to a standardNo standard. Accuracy at 1,5%

(ISO 5167) arround 1,5% (ISO 5167) arround1,5% (ISO 5167) around 1,5%Very dependant of the flow

ErectionNeed to cut the pipe and weld the flange

Need to cut the pipe and weld the flange

Need to cut the pipe and weld the flange

Easy. No big works: No weld etc..

DN limitsAccording to the standard: DN> 50mm

According to the standard: DN between 200 mm and 1200 mm

According to the standard: DN between 50 mm and 630 mm

According to the standard: DN between 25mm and 6000 mm

Conclusion Frequent use due to its priceMedian use because of the cost of the erection

Rare. Very expensive for erection

Very often. Erection and price very interesting

Primary element flowrate measurement 15/05/2018

Page 54: Flow measurement with primary element

Primary element flowrate measurement 54

Nozzle Orifice plate (single hole)

Orifice plate (multi hole)

V-Cone Pitot Micro-venturi

Venturi

Price +++ ++ + ++++ + +++ +++

Efficiency on loaded fluid

+ + + +++ + ++ ++

Straight length +++ ++++ + + ++ + +++

High viscosity + + + ++++ + ++ +++

Erection parameters

++ ++ ++ ++ + +++ ++

Primary element comparison

+ Low

++++ High

15/05/2018

Page 55: Flow measurement with primary element

Straight length - Comparison

15/05/2018 Primary element flowrate measurement 55

Example: Pipe with 1 elbow downstream and upstreamBeta : 0,50

Primary Element

Pitot * Orifice plateSingle hole

Orifice plateMulti hole *

Venturi Micro venturi *

Nozzle Wedge V-Cone

Straightlength

7D/4D 22D/6D 2D/2D 9D/3,5D 3D/2D 14D/6D 12D/4D 3D/1D0D/0D1

* Not included to ISO51671 According to manufacturer McCrometer

Page 56: Flow measurement with primary element

Important technical point !!

• Technical information datasheet

• Minimum required technical data:

❖Internal diameter, thickness, thermal protection or other

❖Nominal Pressure

❖Nominal temperature

❖Fluid type

❖Maximal REAL flowrate !

❖Density if non standard

• Check straight length

• Check connection and erection

• DP pitot tube calculation note15/05/2018 Primary element flowrate measurement 56

Page 57: Flow measurement with primary element

15/05/2018 Primary element flowrate measurement 57

Selection table – Primary element

New table to be filled and

sent to FEF

Page 58: Flow measurement with primary element

Fuji Electric France S.A.S.46 rue Georges Besse - ZI du Brézet

63039 Clermont-Ferrand Cedex 02 - FranceTél. +33 (0)4 73 98 26 98 - Fax. +33 (0)4 73 98 26 99

WEB www.fujielectric.fr - Email [email protected]