Page 1: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

MultiboxFlush Individual Room Control

for Floor Heating Systems

To be precise.

Page 2: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

2

PageMultibox K, Multibox RTL and Multibox K-RTL

Description 3

Construction 3

Application 4

Temperature Setting 4

Function 5

Article Nos. 5

Multibox F

Description 6

Construction 6

Application 7

Temperature Setting 7

Function 8

Article Nos. 8

Multibox C/E and Multibox C/RTL

Description 9

Construction 9

Application 10

Temperature Setting 10

Function 11

Article Nos. 11

Pipe guide channel 12

Information

Planning 12

Thermal fluid 12

Functional heating 12

Accessories 13, 14

Equipment Overview 14, 15

Specifications 16, 17

Dimensional Sheet

Multibox K, RTL and K-RTL 18

Multibox F 19

Multibox C/E and C/RTL 20

Contents

Page 3: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

3

Multibox

K, RTL and K-RTL

HEIMEIER Multibox K, Multibox RTL andMultibox K-RTL flush box with frame,cover plate and fixing bars, for control-ling, for instance, floor heating systemswithout auxiliary power.

Multibox Kfor the individual room temperature con-trol with thermostatic valve of, forinstance, floor heating systems.

Multibox RTLfor maximum limitation of the returntemperature with return temperaturelimiter of, for instance, combinedfloor/radiator heating systems.

Multibox K-RTLfor the individual room temperature con-trol and maximum limitation of thereturn temperature with thermostaticvalve and return temperature limiter of,for instance, combined floor/radiatorheating systems.

All models optionally with cover and visible graduation cap in white RAL 9016or chrome-plated.

The flush box has an overall depth of 60 mm.

Flexible mounting thanks to variable spacing between flush box and cover ofup to 30 mm.

The cover can compensate for slantedmounting of the flush box of up to 6°on each side.

Thermostatic head K with liquid-filledthermostat. High actuating power, mini-mum hysterisis, optimum shutting time.Stable control properties even with smalldesign control differences (<1 K). Meets EnEV and/or DIN V 4701-10. Cue number 1-5. Anti-freeze protection.Temperature range 6° C - 28° C.

Return Temperature Limiter (RTL) withexpanding substance-filled thermostat.Cue number 1-5. Temperature range 10° C - 50° C.

Body made of gunmetal. Thermostaticinserts with stainless steel spindle anddouble O-ring seal. Outer O-ring can be replaced without system drainage.

All models are equipped with aventing/flushing valve.

Pipe-side G 3/4 adaptor with cone suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

For HEIMEIER valves, only use the corresponding, designated HEIMEIERcompression fittings (designation e.g. 15 THE).

Pipe guide channel for easy pipe/valveattachment – see Accessories.

Description

Construction• For out-of-true installation

offsetting up to 6° on each side

• Cover with concealed screw connection

• Small installation depth

• Designs with cover and visible graduation cap in white or chrome-plated

• Adjustable fitting for all wall structures, 30 mm depth compensation

• Pipe guide channel as accessory

• Valve chamber of corrosion-resistant gunmetal

• Universal connection possibilities

Multibox K

Multibox RTL Multibox K-RTL

� Flush box� Venting/flushing valve� Thermostatic head K� Frame� Cover plate� Fixing bar Valve chamber of corrosion

resistant gunmetal

Shutoff/regulating spindle� Return temperature limiter

(RTL)

�� � �

Page 4: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

4

Multibox K is used for the individualroom temperature control of, for instance,floor heating systems in association withlow temperature heating systems (seeinformation on Page 12). Multibox K is also used in wall heatingsystems. Use the shutoff/regulating spindle forhydraulic balancing.

ApplicationMultibox K

Multibox RTL is used for maximum limi-tation of the return temperature with,for instance, combined floor/radiatorheating systems for temperature controlof floor areas (see information on Page12). Only the return temperature is controlled. Use the shutoff/regulating spindle forhydraulic balancing.

Multibox RTL

Multibox K-RTL is used for the individualroom temperature control and maximumlimitation of the return temperaturewith, for instance, combined floor/radiator heating systems (see informa-tion on Page 12).Multibox K-RTL is also used in wall heating systems.

Multibox K-RTL

Examples of use

� Manifold� Radiator� Floor heating area

Multibox K Multibox RTL

�� �

Multibox

K, RTL and K-RTL

Return temperature limiter (RTL)

Room temperature [°C]

Thermostatic head K

Cue number

Return temperature [°C]

Cue number

6

1

16

2 3

12 14

4 5

20 24 28

1 2 3 4 5

10 20 30 40 50

Temperature Setting

Multibox KMultibox K-RTL

Floor heating without central manifold with e.g. two equally long heating circuits per room andMultibox (see Planning Information on Page 12).

��

Multibox K-RTL

(Opening temperature)

Page 5: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

K, RTL and K-RTL

From the control aspect, the thermosta-tic valve integrated in Multibox K is aconstant proportional controller (P- con-troller) without any auxiliary power. Itdoes not need any electrical connectionor other outside power source.

The change of the room air temperature(controlled variable) is proportional to the change of the valve lift (correctingvariable). A rise in the room air tempera-ture e.g. from the sun's rays, results in an expansion of the liquid in the tempera-ture sensor and it acts on the bellows.By means of the valve spindle, this cutsback on the supply of water in the floorheating circuit. The procedure is reversedgiven a falling room air temperature.

Multibox K

From the control aspect, the thermo-static valve integrated in Multibox K-RTLis a constant proportional controller (P-controller) without any auxiliarypower. It does not need any electricalconnection or other outside powersource.

The change of the room air temperature(controlled variable) is proportional tothe change of the valve lift (correctingvariable). A rise in the room air tempera-ture e.g. from the sun's rays, results inan expansion of the liquid in the tempera-ture sensor of the thermostatic head andit acts on the bellows. By means of thevalve spindle, this cuts back on the supply of water in the floor heatingcircuit. The procedure is reversed given afalling room air temperature.

Multibox K-RTL is additionally providedwith a return temperature limiter (RTL)which stops the set return temperaturefrom being exceeded. The valve openswhen the set limiting figure is exceeded.

Multibox RTL Multibox K-RTL

From the control aspect, the return temperature limiter integrated in Multibox RTL is a constant proportionalcontroller (P-controller) without any auxiliary power. It does not need anyelectrical connection or other outsidepower source.

The temperature change of the fluid flowing through (controlled variable) isproportional to the change of the valvelift (correcting variable) and is transferredto the sensor by means of thermal con-duction. Any rise in the return tempera-ture due to, for instance, to loweredheating output of the floor heatingsystem as a result of outside thermaleffects causes the substance in the temperature sensor to expand and acton the diaphragm plunger. By means ofthe valve spindle, this cuts back on thesupply of water in the floor heating circuit. The procedure is reversed given afalling fluid temperature.

The valve opens when the set limitingfigure is exceeded.

Illustration Article Colour Art. No.

Multibox K Cover and thermostatic 9302-00.800with thermostatic valve head K white RAL 9016

Cover and thermostatic 9302-00.801head K chrome-plated

Article Numbers

Multibox RTL Cover and RTL thermostatic 9304-00.800with return temperature head white RAL 9016limiter (RTL)

Cover and RTL thermostatic 9304-00.801head chrome-plated

Multibox K-RTL Cover and thermostatic 9301-00.800with thermostatic valve head K white RAL 9016and return temperature limiter (RTL) Cover and thermostatic 9301-00.801

head K chrome-plated

Function

5

Page 6: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

6

Multibox

F

6

HEIMEIER Multibox F flush box withframe including thermostatic head, coverplate and fixing bars for the individualroom temperature control with thermo-static valve of, for instance, floor heatingsystems, without auxiliary power.

Through a capillary tube, the temperaturesensor liquid of the thermostatic headacts on the bellows in the valve adaptor.There is therefore never any change inthe appearance of the cover with ther-mostatic head – irrespective of the instal-lation depth.

All models with cover and visible gradua-tion cap in white RAL 9016.

The flush box has an overall depth of 60 mm.

Adjustable mounting thanks to variable spacing between flush box and cover ofup to 30 mm.

The cover can compensate for slantedmounting of the flush box up to 6° oneach side.

Thermostatic head with liquid-filled thermostat. High actuating power, low

level of hysterisis, optimum shutting time. Stable control properties even with smalldesign control differences (<1 K). Meets EnEV and/or DIN V 4701-10. Cue number 1-5. Anti-freeze protection.Zero position (valve opens at approx. 0° C). Temperature range 6° C - 27° C.

Body made of gunmetal. Thermostaticinsert with stainless steel spindle anddouble O-ring seal. Outer O-ring can bereplaced without system draining.

Multibox F is provided with a ventingvalve.

Pipe-side G 3/4 adaptor with cone – suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

For HEIMEIER valves, only use the corre-sponding, designated HEIMEIER compres-sion fittings (designation e.g. 15 THE).

Pipe guide channel for easy pipe/valveattachment, see Accessories.

Description

Construction• No change in appearance

irrespective of installation depth

• Elegant and easy-to-clean graduation cap

• For out-of-true installation offsetting up to 6° on each side

• Cover with concealed screw connection

• Small installation depth

• Adjustable mounting for all wall structures, 30 mm depth compensation

• Pipe guide channel as accessory

• Valve chamber of corrosion-resistant gunmetal

• Universal connection possibilities

Multibox F

� Flush box� Thermostatic head with

capillary tube� Adaptor� Venting valve� Frame

� Cover plate Fixing bar Valve chamber of corrosion

resistant gunmetal� Shutoff/reg. spindle

��

Page 7: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Room temperature [°C]

Thermostatic head F

Cue number

6 1612 14 20 24 27

1 2 3 4 5

Temperature Setting

7

Application

Multibox

F

Multibox F is used for the individual roomtemperature control of, for instance, floorheating systems in association with lowtemperature heating systems (see infor-mation on Page 12). Multibox F is also used in wall heatingsystems. Use the shutoff/regulating spindle forhydraulic balancing.

Multibox F

Examples of use

� Manifold� Heating area

Multibox F

Multibox F

Floor heating without central manifoldwith e.g. two equally long heating circuits per room andMultibox (see also Planning information on Page 12).

Page 8: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

8

Multibox

F

Illustration Article Colour Art. No.

Multibox F Cover and thermostatic 9306-00.800with thermostatic valve head white RAL 9016

Article Numbers

Function

From the control aspect, the thermostaticvalve integrated in Multibox F is a con-stant proportional controller (P-controller)without any auxiliary power. It does notneed any electrical connection or otheroutside power source.

Change of the room air temperature(controlled variable) is proportional to thechange of the valve lift (correcting variable). A rise in the room air tempera-ture e.g. from the sun's rays, results in anexpansion of the liquid in the tempera-ture sensor and it acts through the capil-lary tube on the bellows in the valveadaptor. By means of the valve spindle,this cuts back on the supply of water inthe floor heating circuit. The procedure isreversed given a falling room air tempe-rature.

Multibox F

Page 9: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

9

Multibox

C/E and C/RTL

HEIMEIER Multibox C/E and MultiboxC/RTL flush box with frame, closed coverplate and fixing bars for controlling, forinstance, floor heating systems.

Multibox C/Efor individual room temperature controlof, for instance, floor heating systemswith thermal or motor actuators and/orwith remote dial thermostatic head F(see Equipment overview - Pages 14,15).

Multibox C/RTLfor maximum limitation of the returntemperature with return temperaturelimiter of, for instance, combinedfloor/radiator heating systems.

All models with closed cover in whiteRAL 9016.

The flush box has an overall depth of 60 mm.

Adjustable mounting from variable spacing between flush box and cover ofup to 30 mm.

The cover can compensate for slantedmounting of the flush box up to 6° oneach side.

Return temperature limiter (RTL) withexpanding substance-filled thermostatCue number 1-5. Temperature range 10° C - 50° C.

Body made of gunmetal. Thermostaticinserts with stainless steel spindle anddouble O-ring seal. Outer O-ring can bereplaced without system drainage.

All models are equipped with a venting/flushing valve.

Pipe-side G 3/4 adaptor with cone suitable for compression fittings for plastic, copper, precision steel and multi-layer pipe.

For HEIMEIER valves, only use the corre-sponding, designated HEIMEIER compres-sion fittings (designation e.g. 15 THE).

Pipe guide channel for easy pipe/valveattachment, see Accessories.

Description

Construction • Closed cover plate

• Multibox C/E suitable for actuatorsor remote dials

• For out-of-true installation offsetting up to 6° on each side

• Cover with concealed screw connection

• Small installation depth

• Adjustable fitting for all wall structures, 30 mm depth compensation

• Valve chamber of corrosion-resistant gunmetal

• Universal connection possibilities

Multibox C/E

� �

Multibox C/RTL

� Flush box� Thermostatic insert for

attachment of actuatorsor remote dials

� Venting valve� Frame� Cover plate

� Fixing bar Valve chamber of corrosion-

resistant gunmetal Shutoff/regulating spindle� Return temperature limiter

(RTL)

��

� �

Page 10: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

10

Return temperature limiter (RTL)

Return temperature [°C]

Cue number 1 2 3 4 5

10 20 30 40 50

Temperature Setting

Multibox C/E is used for the individualroom temperature control of, for instance,floor heating systems in association withlow temperature heating systems (seeinformation on Page 12). The individual room temperature is con-trolled by room thermostats in associa-tion with thermal or motor actuatorsand/or without auxiliary power with thethermostatic head F remote dial. Multibox C/E is also used in wall heatingsystems. Use the shutoff/regulating spindle forhydraulic balancing.

ApplicationMultibox C/E

Multibox C/RTL is used for maximum limi-tation of the return temperature with, forinstance, combined floor/radiator heatingsystems for the temperature control offloor areas (see Information on Page 12). Only the return temperature is controlled.Use the shutoff/regulating spindle forhydraulic balancing.

Multibox C/RTL

Multibox

C/E and C/RTL

Examples of uses

� Radiator� Floor heating area� Manifold� Thermostat P� Room thermostat

� Thermostat E Thermostatic head F,

Remote dial Empty pipe for cable

and/or cap. tube

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

9

6

3

1212

1212 618186

12121818

612

18

61212

1818 612

1818

61212

18186

1212

18184

6

7 1

23

3030

2525

1515

1010

5

C

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

CMultibox C/Ewith thermal actuator EMO T, EMOtec, motor actuator EMO1/3/EIB/LON or thermostatic head F(see Equipment Overview Pages 14, 15)

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

Multibox C/RTL

��

9

6

3

1212

1212 618186

12121818

612

18

61212

1818 612

1818

61212

18186

1212

18184

6

7 1

23

3030

2525

1515

1010

5

C

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

9

6

3

12

12 6186

1218

612

18

612

18 612

18

612

186

12

184

6

7 1

23

30

25

15

10

5

C

Multibox C/E

With e.g. two equally long heating circuits per roomand Multibox (see Planning information on Page 12).

(Opening temperature)

Page 11: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

11

Multibox

C/E and C/RTL

From the control aspect, the thermostaticvalve integrated in Multibox C/E – inassociation with the F thermostatic valve– is a constant proportional controller (P-controller) without auxiliary power. Itdoes not need any electrical connectionor other outside power source.

Change of the room air temperature(controlled variable) is proportional to thechange of the valve lift (correcting variable). A rise in the room air tempera-ture e.g. from the sun's rays, results in anexpansion of the temperature sensorliquid and it acts through the capillarytube on the corrugated tube in the valveadaptor. By means of the valve spindle,this cuts back on the supply of water inthe floor heating circuit. The procedure is reversed given a falling room air temperature.

Together with thermal or motor actua-tors, room thermostats control individualroom temperature.

Multibox C/E Multibox C/RTL

From the control aspect, the return temperature limiter integrated in Multi-box C/RTL is a constant proportional con-troller (P controller) without any auxiliarypower. It does not need any electricalconnection or other outside power source.

Temperature change of the fluid flowingthrough (controlled variable) is proportio-nal to the change of the valve lift (correc-ting variable) and is transferred to thesensor by means of thermal conduction.Any rise in the return temperature dueto, for instance, to a lowered heatingoutput of the floor heating system as aresult of outside thermal effects causesthe substance in the temperature sensorto expand and act on the diaphragmplunger. By means of the valve spindle,this cuts back on the supply of water inthe floor heating circuit. The procedure is reversed given a falling fluid tempera-ture.

The valve opens when the set limitingfigure is exceeded.

Function

Illustration Article Colour Art. No.

Multibox C/E Cover white RAL 9016 9308-00.800with thermostatic insert for actuator or remote dial

Article Numbers

Multibox C/RTL Cover white RAL 9016 9303-00.800with return temperature limiter (RTL)

Page 12: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

12

- For all Multibox models, ensurethat the system supply tempera-ture is suitable for setting up the floor heating system.

- All Multibox models are to be connected to the return pipe at theend of the floor heating circuit. Heed direction of flow (see Examples of use).

- Depending on piping pressure loss, all Multibox models are suitable for heating areas up to approx. 20 m2.

- The length of 12 mm internal diameterpipe in any heating circuit should notexeed 100 m.

- With heating areas >20 m2 and/or pipe lengths >100 m, a T-piece, for instance, should be used to connecttwo equally long heating circuits to the Multibox. (see Examples of use).

- To ensure low-noise system operation, differential pressure over the valve should not exceed 0.2 bar.

- The floor heating pipe is to be laid spirally in the flooring screed (see Examples of use).

- The set value of the RTL should not be below ambient temperature - other- wise it will not open.

To stop any damage and scale in hotwater heating systems, the compositionof the thermal fluid is to conform to VDIDirective 2035. The VdTÜV instructionalleaflet 466/AGFW instructional leaflet5/15 is to be heeded in respect of indus-trial and district heating systems.

Mineral oil in the thermal fluid and/or allkinds of lubricants containing mineral oillead to considerable swelling and, in mostcases, to the failure of EPDM seals.

When using nitrite-free antifreeze andanti-corrosive based on ethylene glycol,technical advice – especially on additive

concentration – is to be taken from theanti-freeze/anti-corrosive manufacturer'sdocumentation.

Thermal fluid

Carry out functional heating of heatingscreed conforming to standards in keeping with EN 1264-4.

Earliest start for functional heating:

– Cement screed: 21 days after laying

– Anhydrite screed 7 days after laying

Begin 20 °C - 25 °C flow temperatureand maintain for 3 days. Then set maxi-mum design temperature and maintainfor 4 days. Flow temperature can beregulated by controlling the heat gene-rator. Turn the protective cap anti-clockwise to open valve or turn RTLhead to Position 5.

Refer to the screed manufacturer'sinformation!

Do not exceed maximum floor temperature at the heating pipes:– Cement and anhydrite screed: 55 °C– Poured asphalt screed: 45 °C – according to screed manufacturer`s

technical advice!

Functional heating

InformationPlanning

Pipe Guide ChannelPU pipe guide channel for easy moun-ting of all HEIMEIER Multibox modelsand for convenient pipe-valve attach-

ment. Mounting, for instance, in wallgaps or in front wall plumbing.

Dimensions:180 mm x 575 mm x 70 mm (B x H x D).Also see Accessories Page 13.

Examples of mounting

1. 3.2.

Page 13: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

13

Multibox

Accessories

Compression fitting 10 1300-10.351for copper or precision steel pipe 12 1300-12.351brass. 14 1300-14.351With a pipe wall thickness of 0.8-1 mm 15 1300-15.351insert supporting sleeves. 16 1300-16.351Heed pipe manufacturer's technical advice. 18 1300-18.351

Support sleeves 18.5 10 1300-10.170for copper or precision steel pipe with 25.0 12 1300-12.170a 1 mm wall thickness. 25.0 14 1300-14.170Brass. 26.0 15 1300-15.170

26.3 16 1300-16.17026.8 18 1300-18.170

Compression fitting 12 x 2 1301-12.351for plastic pipe. 14 x 2 1301-14.351Brass. 16 x 2 1301-16.351

17 x 2 1301-17.35118 x 2 1301-18.35118 x 2,5 1302-18.35120 x 2 1301-20.35121 x 2,5 1301-21.351

Compression fitting 14 x 2 1330-14.351for multi-layer pipe. 16 x 2 1330-16.351Brass. 18 x 2 1330-18.351

L

Illustration Description L [mm] Ø Pipe Art. No.

Spindle extensionfor K thermostatic head with Multibox Kand Multibox K-RTLwhen maximum installation depth exceeded. Brass nickel-plated. 20 2201-20.700

30 2201-30.700Plastic, black 30 2002-30.700

Spindle extension 20 9153-20.700for RTL thermostatic head with Multibox RTLwhen maximum installation depth exceeded. Brass nickel-plated.

Pipe guide channel 9300-00.553made of PU, for easy mounting of all HEIMEIER Multibox models and convenient pipe-valve attachment. 180 mm x 575 mm x 70 mm (B x H x D).

12 1313-12.35114 1313-14.35115 1313-15.35116 1313-16.35118 1313-18.351

Compression fittingfor copper or precision steel pipe.Nickel plated brass.Soft sealed.

Page 14: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

14

AccessoriesIllustration Descriptiion Colour Art.-No.

Thermostatic head FFor connection to Multibox C/ERemote dial. 2.00 m 2802-00.500Cue number 1–5. 5.00 m 2805-00.500Liquid-filled thermostat. 8.00 m 2808-00.500High degree of control precision. 10.00 m 2810-00.500Setting range 6° C - 27° C. 12.00 m 2812-00.500

15.00 m 2815-00.500

For swimming pools medicinal baths 2.00 m 2822-00.500Setting range 15° C - 35° C. 5.00 m 2825-00.500

Frame and cover plate white RAL 9016 9300-00.800Replacement for Multibox K, chrome 9300-00.801Multibox RTL and Multibox K-RTL

Equipment overviewIllustration Description Capillary tube Art.No.

Special insert 9302-03.300for Multibox K and Multibox K-RTLfor reversed direction of flow with switched supply and return flow.

Special insert 9304-03.300for Multibox RTLfor reversed direction of flow with switched supply and return flow.

RTL insert and RTL thermostatic headspecially for converting Multibox K into Multibox K-RTL.

RTL insert and 9303-00.300RTL thermostatic head 6500-00.500

Frame and cover plate white RAL 9016 9300-03.800Replacement for Multibox C/RTL and Multibox C/E.

Page 15: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

15

230 V no-current closed (NC) 1831-00.50024 V no-current closed (NC) 1841-00.500

230 V no-current opened (NO) 1835-00.50024 V no-current opened (NO) 1845-00.500

230 V no-current closed (NC) 1807-00.50024 V no-current closed (NC) 1827-00.500

230 V no-current opened (NO) 1809-00.50024 V no-current opened (NO) 1829-00.500

Specifications catalogue EMO T and/or EMOtec

Thermal actuatorsSuitable for Multibox C/E.

EMO TThermal two-point actuator for heating, ventilation and air conditioning systems.With incorporated overvoltage protectionwith 230 V model.EMOtecThermal two-point actuator for floor heating systems. With position indicator given no-current closed (NC) model.

230 V 1932-00.50024 V 1942-00.500

1930-02.433

Specifications catalogue Thermostat P

230 V without temperature drop 1936-00.500230 V with temperature drop 1938-00.50024 V without temperature drop 1946-00.50024 V with temperature drop 1948-00.500

Specifications catalogue – Room thermostat

9

6

3

12

12 6186

1218

612

18

612

18 6 1218

612

186

12

184

6

7 1

23

30

25

15

10

5

C

30

25

15

10

5

C

Thermostat Pelectronic two-point room thermostat fortime-dependent control of room temperatu-re, with analogue 7-day switch clock, Pulse-Width Modulation output signal (PWM) andvoltage-free change-over contact.

Protective casinglockable, surface-mounted casing for thermostat P, transparent.

Room thermostatwith thermal return, controls room temperature together with thermal actuators.

Equipment overview

Motor actuatorsSuitable for Multibox C/E. EMO 1 1860-00.500

Proportional actuator 0-10 V DCOnly in conjunction with spindle extension, see below! EMO 3 1880-00.500

Three point actuator

EMO EIB Standardfor attaching directly to 1865-00.500the European with 2 binaryInstallation Bus inputs

1864-00.500

EMOLON 1867-00.500for use in LP variant

Specifications Catalogue EMO, EMO EIB LONWORKS®-Networks (FT variant and EMOLON on request)

Electronic room temperature controllerThermostat E 1 and Thermostat E 3 are Thermostat E 1 1960-01.500incorporated in conjunction with the EMO 1 Continuous controlleror EMO 3 electrical-motor actuators. For operating voltage supply (24 V AC) Thermostat E 3 1980-01.500use safety transformers meeting EN 60742, Three-point controllere.g. HEIMEIER transformer (Art. No. 1600-00.000). Specifications catalogue Thermostat E

Illustration Description Model Art. No.

Spindle extension plastic, black Length 30 mm 2002-30.700

Page 16: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

16

Multibox

K, K-RTL, F and C/ED

ruck

verlu

st Δ

p [k

Pa]

100503020105

Massenstrom ª [kg/h]

200 300 500 1000

300

200

100

50

30

20

10

5

3

2

1 Dru

ckve

rlust

Δp

[mba

r]

Dru

ckve

rlust

Δp

[mm

WS]

3000

2000

1000

500

300

200

100

50

30

20

10

30

20

10

5

3

2

1

0,5

0,3

0,2

0,1

Voreinstell-Umdrehungen [U]RegulierspindelMultibox K, F, C/E**)

2 3 5

kv-Wert 0,82

0,5 4

(Bei 2 K Regeldifferenz)

1

gilt auch für Multibox K-RTL

0,25

*) when RTL fully opened**) together with thermostatic head F

SpecificationsDiagram: Multibox K, K-RTL, F and C/E**)

Worked example

Controller withvalve body

DN 15

kv-figure [m3/h]Multibox K, F, C/E**)

Preset rotations [U] Regulating spindle

kvs-figure

[m3/h]

kv-figure [m3/h]Multibox K-RTL

0.25 0.5 1.0 2.0 3.0 4.0 5.0

Safe operatingtemp.TB[°C]

Safe ope-ratinggaugepressure

PB [bar]

Controldiff.Th. head[K]

1

2

0.43*)

0.82*)

1.35 90 10

0.10 0.17 0.21 0.28 0.32 0.39 0.43

0.11 0.18 0.23 0.33 0.40 0.59 0.82

To be found: Pressure loss Multibox K, F, C/E, K-RTLat 2 K control difference

Given: Thermal flux Q· = 1025 WTemperature spread Δ t = 8 K (44/36° C)

Solution: Mass flow m· = Q· =1025

= 110 kg/hc·Δt 1.163 · 8Pressure loss as diagram Δpv = 18 mbar

also applies to Multibox K-RTLkv-figure 0.82

Preset rotations [U] in regulating spindleMultibox K, F, C/E**)

0.25 0.5

0.5

0.3

0.2

0.1

Mass flow rh (with 2 K control difference)

Pres

sure

loss

Δp

[kPa

]

Pres

sure

loss

Δp

[mba

r]

Pres

sure

loss

Δp

[mm

WS]

Page 17: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

17

Multibox

RTL and C/RTL

Dru

ckve

rlust

Δp

[kPa

]

100503020105

Massenstrom ª [kg/h]

200 300 500 1000

300

200

100

50

30

20

10

5

3

2

1 Dru

ckve

rlust

Δp

[mba

r]

Dru

ckve

rlust

Δp

[mm

WS]

3000

2000

1000

500

300

200

100

50

30

20

10

30

20

10

5

3

2

1

0,5

0,3

0,2

0,1

20,5 1 1,5 2,5 3 43,5 4,5Voreinstell-Umdrehungen [U]RegulierspindelMultibox RTL, C/RTL

kvs0,25

SpecificationsDiagram: Multibox RTL and C/R

Worked exampleTo be found: Preset figure Multibox RTL, C/RTL

Given: Thermal flux Q· = 1025 WTemperature spread Δ t = 8 K (44/36° C)Pressure loss Multibox RTL: Δpv = 22 mbar

Solution: Mass flow m· = Q· =1025

= 110 kg/hc·Δt 1.163 · 8Preset figure from diagram: 4

Controller withvalve body

DN 15

kv-figure [m3/h] Multibox RTL, C/RTL

Preset rotations [U] Regulating spindle

kvs-figure [m3/h]

0.25 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

Safe operatingtemp.TB[°C]

Safe operatinggaugepressure PB [bar]

1.35 90 100.13 0.20 0,25 0.30 0.35 0.39 0.44 0.54 0.74 1.06

Preset rotations [U]Control spindleMultibox RTL, C/RTL

0.25 0.5

0.5

0.3

0.2

0.1

Mass flow rh

Pres

sure

loss

Δp

[kPa

]

Pres

sure

loss

Δp

[mba

r]

Pres

sure

loss

Δp

[mm

WS]

Page 18: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

K, RTL and K-RTL

18

Dimensional Sheet

144

55,5

183

G 3/4

80

53

25,5

50

363

179

131

60

55,5

183

G 3/4

25,5

50

363

179

131

80

144

53

60

Multibox RTLMultibox K

Multibox K-RTL

175

220

600

- 30

10

Cover plate Frame

80

144

55,5

183

50

G 3/4

25,5

53

363

179

131

6025

.5

55.5 25

.5

55.5

25.5

55.5

Page 19: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

F

19

Dimensional Sheet

363

183

55,525

,5

G 3/4

50

179

131

60

144

Multibox F

Cover plate Frame

175

220

600

- 30

43

53

10

25.5

55.5

Page 20: Flush Individual Room Control for Floor Heating Systems · floor/radiator heating systems. Multibox K-RTL for the individual room temperature con-trol and maximum limitation of the

Multibox

C/E and C/RTL

Dimensional Sheet

Broc

hure

3.6

Prin

ted

on c

hlor

ine-

free

, bl

each

ed p

aper

.36

00-1

8.48

3/0

4.07

Subj

ect

to t

echn

ical

mod

ifica

tions

.

363

183

55,5

50

25,5

G 3/4

179

131

60

144

363

183

55,525

,5

G 3/4

50

179

131

60

144

Multibox C/RTLMultibox C/E

175

220

10

600

- 30

Cover plate Frame

Theodor Heimeier Metallwerk GmbHP.O. Box 1124, 59592 Erwitte, Germany Phone + 49 (0)2943 891-0Fax + 49 (0)2943 891-100www.heimeier.com

25.5

55.5

25.5

55.5