Fuel Cell Extended Runtime Stationary PowerDatacenter
Angelo MonteleoneBusiness Development ManagerNovember 2013
![Page 2: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/2.jpg)
SHIFT POWER | ENERGIZE YOUR WORLD
There is a power shift happening worldwide
• From fossil fuels to a blend of renewable, accessible alternatives
• From volatility to user-controlled supply management
• From excess waste and emissions to sustainable energy inventories and zero-emissions
• From single-resource dependence to multi-purpose energy architectures
• From thinking backward to rebuilding energy confidence in the future
2
CoverTel Power exists to accelerate this power shift by engineering and building the technologies needed to make it happen.
![Page 3: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/3.jpg)
Extended Run-time UPS with Fuel Cells
![Page 4: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/4.jpg)
Data Centre UPSIdeal Requirements
Compact, high-density power generators in the racks next to the loads
Unlimited energy storage, moved out of the data room
Modular, plug-in power generation units, easy installation, interface and commissioning with standard UPS models
Easy future upgrade for increased power by adding modules and racks
No decay* due to operation No decay* due to disuse (dormancy) No decay* due to start/stop cycling No periodic start-up requirement Safety requirements easily met Reduced or eliminated maintenance
requirements Lower overall costs than pure battery
solution Exactly predictable run-time Run-time easily further extended while
operating online
* - performance as well as reliability!
![Page 5: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/5.jpg)
Fuel Cell Extended Run UPS and Stand-by Power System
Rack Fuel Cells DC/DC’s Cooling HEX Ventilation System Controller Local LCD display
keypad user interface
19” Rack
Standard UPS APC Series
Smart-UPS VT or Symmetra PX
Grid connection Bridging power User
communication Inverters and
rectifiers
Fuel Cell Extended Run UPS / Stand-by System Rated 10, 20 or
30 kW N+1
redundancy capable
Fuel Cell Power Module(s)
Stack Air management H2 management FC Module Control CAN-Interface
10 kWnet
10 kWnet
10 kWnet
![Page 6: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/6.jpg)
Rack Arrangement
System Controller(2U)
DC/DC #1(3U)
DC/DC #2(3U)
DC/DC #3(3U)
FC #1(7U)
FC #2(7U)
FC #3(7U)
Cooling SystemHeat Exchanger
Water DrainH2 Supply
(10U)
Total 42U = 1.87 m
Upper Infrastructure interfaces
Ventilation and exhaust duct, with integrated H2 supply quick-connect.
Pre-installed power bus-bars, communications interfaces, cables
Quick-connect cooling
Heat exchanger, pump, manifolds, drain
![Page 7: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/7.jpg)
Fuel Cells combine the advantages of batteries and gensets
0 20 40 60 80 100 120 140 160 180 200
1
10
100
1000
10000
100000
0 20 40 60 80 100 120 140 160 180 200
SuperCapacitors
Lead acidSpirally wound
Ni-Cd Ni-MH
Li-ionHigh energy
LiM-Polymer
Ni-NiCQLeadacid
Li-ionVery highpower
Li-ionHigh power
300 400 500 600 7000 20 40 60 80 100 120 140 160 180 200
Energy Storage Energy Density vs. Power Density
Specific Energy, Wh/kg
Spe
cific
Pow
er,
W/k
g
A123
Thundersky -LFP
ZEBRA 12kW HD FCPM, 350 bar H2,270F Ultracap
EEStor“Claim”
A123,5kWhr Pack
Toshiba, SCiB StandardModule, TBP Series
![Page 8: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/8.jpg)
Runtime Diagram: Fuel Cell with One H2 Bundle andAPC Symmetra PX 96 kW 400 V (SY…96H-PD)
> 30 kW is problematic with battery-only solution above 3 h runtime> 40 kW is problematic with battery-only solution above 2 h runtime> 70 kW is problematic with battery-only solution above 1 h runtime
w/ (4) Battery Racks
w/ (3) Battery Racks
w/ (2) Battery Racks
w/ (1) Battery Rack
w/ Fuel Cell & (1) bundle
![Page 9: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/9.jpg)
FC Interfaces
Dry Cooler or Chiller
Dry Cooler or Chiller
Ventilation, Exhaust
Exhaust Blower
Water Drain
Coolant Supply
Coolant Return
Hydrogen StorageHydrogen Storage
H2 Feed Line
Communications
-192 V 0V
+192 V dc
Local Output380/400 V
50 Hz 3-Ph AC
Mains380/400 V
50 Hz 3-Ph AC
Fuel Cell-R10/20/30 Rack
APC SMART-UPS VTPor Symmetra PX
UPS Batteries
for “Bridging” power
and Step-loads
UPS Infra-structure (Local off-
grid “island”
Inverters)
Controller
DC-DC’s
Fuel Cells
3x 10 kW
Cooling
Grid Synchronized
Output400V 50 Hz
3-Ph AC
OPTIONAL
![Page 10: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/10.jpg)
Data Center Application References
![Page 11: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/11.jpg)
Reference Installations to 2009
End User Country Number of Modules
APC Kolding DK 1 X 10 kW BankInvest Copenhagen DK 1 x 10 kWUPS Systems Hungerford UK 1 x 10 kWWinton Capital Management,
KensingtonUK 3 x 10 kW
Comtec Enterprises, Surrey UK 3 x 10 kWMoD SLO 3 x 10 kWSwisscom / U. of Appl. Sc.
LucerneCH 1 x 10 kW
Interlink Toronto CA 2 x 10 kWNRCan Vancouver CA 3 x 10 kWAPC West Kingston US 1 x 10 kWUS Department of the Army US 3 x 10 kWUS National Weather Service US 1 x 10 kWTrue View Chicago US 2 x 10 kWTotals: 13 Systems 6 Countries 25 Modules,
250 kW
5 systems are fully populated with 3 modules
2 systems are with 2 modules 6 systems are with 1 module By Country:
• UK: 7 modules,
• US: 7 modules
• CA: 5 modules
• SLO: 3 modules
• DK: 2 modules
• CH: 1 module
13 modules in Europe 12 modules in North America
25 Modules 250 kW net 13 Systems 6 Countries
![Page 12: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/12.jpg)
APC HQ, West Kingston Rhode Island
PDU FCXR UPS H2 Storage
![Page 13: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/13.jpg)
Interlink Connectivity, Toronto
5th floor of a 21-story building in downtown Toronto built in the 1920s
• Battery bank option was too bulky and heavy
• Diesel generation installation was too costly 30 kW system
• air conditioning load
• and server load Fuel cell and UPS
in the server room Hydrogen storage located in
an adjacent room
![Page 14: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/14.jpg)
Swisscom, Lucerne Swisscom mobile
• R&D Partner and host site: Lucerne University of Applied Science
• Connected to APC DP310E UPS in an outdoor container – up to 10 kW
• Super-capacitors for bridging power• Up to 6 h of backup with antenna load of 2.4 kW, or 2 h at 10
kW• 256 simulations of grid-failure up to 8.5 kW loads in the first 2
year project• Project extended for a 2nd 2-year term
![Page 15: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/15.jpg)
Comtec Enterprises, Surrey
30 kW, 30 kVA ICT Communications Company,
Reigate, Surrey, UK Datacentre, 24/7 Network
Operations Centre “Eco-Structure” Web-Hosting
environment Winner of Datacentre 2007 Award
for Innovation in Micro-Datacentres
15
![Page 16: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/16.jpg)
16
Nukissiorfiit: Energy Utility, End Client H2Logic: System Integration &
Project Management
H2KT Project: Nuuk, Greenland
Controller
DC-DC’s
Fuel Cells
2 x 10 kW
Cooling
Local Inverters
Hybrid energy storage
GridInverters
Scope:
![Page 17: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/17.jpg)
17
H2 Mini Grid System: Rotherham, Yorkshire
Hydrogen Mini-Grid System Yorkshire Forward’s
Advanced Manufacturing Park, Environmental Energy Technology CenterRotherham (Sheffield), Yorkshire
Environmentally-Efficient Building UPS Systems PLC: FC Integration,
Power Electronics and Control
FC Rack
Fuel Cell Modules(30 kW)
Hydrogenics Scope: Scope:
![Page 18: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/18.jpg)
(Herten, Germany)
Scope of supply:• Fuel Cell -R, 50kW Fuel Cell System• Fuel Cell -30 Electrolyzer, Indoor Version• Equipment delivered 2012-08
HySTAT™-30 electrolyzer
HyPM ™-R, 50kW fuel cell system
![Page 19: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/19.jpg)
Sir Samuel Griffith Center, Brisbane, Australia
Controller
DC-DC’s
Fuel Cells
6 x 10 kW
= 60 kW
Cooling
(2) Fuel Cells 30kW FC Racks
Electrolyzer30
Delivery Scheduled 2Q 2013
![Page 20: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/20.jpg)
Compact, high-density power generators in the racks next to the loads
Modular plug-in power generation
units, easily installed, interfaced and
commissioned with standard UPS
models
Ideal Spatial/Efficiency Attributes
Energy storage
moved out of the data
room
Easy power capacity
upgrade by adding modules
and racks
Valuable data center space is
saved for revenue-generating equipment (servers!)
![Page 21: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/21.jpg)
Ideal Performance Attributes
No decay due to
operationNo decay due to
dormancy
No decay due to
start/stop cycling
Reliable. Impervious,
Stable.Bankable.
Safe.
Safety requirements
easily met
No periodic start-up
requirement
Energy Certainty.
![Page 22: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/22.jpg)
Runtime easily
extended from Days to
Weeks
Extended-run Rack and Stand-by
Generator All-in-one
Runtime easily continued
online by tank hot-swap
Higher Efficiency than IC Engines
Run time is predictable with total accuracy
Extends UPS
runtime from Minutes to
Days
Ideal System Merits
![Page 23: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/23.jpg)
In ConclusionCombines the Advantages of Batteries and Gensets but without the
disadvantages
Less maintenance than batteries and gensets
No energy storage decay
as with batteries
More reliable than IC engine + Genset + ATS
combination
100% Clean and Sustainable with energy from
renewable sources Especially
well suited for pollution "non-
attainment" zones
![Page 24: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/24.jpg)
FC is more economical when: - Runtime > 2.5 h - Battery Racks > 3
Fuel Cell 30 kW
Ind
oo
r
SY32K48H-PD
Ind
oo
r SYCFXR48-9
SY32K48H-PD
6 Batt Racks2 UPS Racks
4 Batt Racks1 UPS Rack
3 Batt Racks1 UPS Rack
2 Batt Racks1 UPS Rack
1 Batt Rack1 UPS Rack
8 Batt Racks2 UPS Racks
1 FC Rack1 UPS Rack1 H2 Bundle
1 FC Rack1 UPS Rack2 H2 Bundles
…
…
Cost of Ownership vs Run-time: 30 kW
0 Batt Racks1 UPS Rack
Outdoor
Tota
l Cos
t of
Ow
ners
hip
Battery-only Solution
Fuel Cell Solution
![Page 25: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/25.jpg)
Fuel Cell Cabinet
Hydrogen Cylinder Shroud
Fuel Cell Cabinet Fuel Cell Cabinet Integrated with Storage
Note: There is capacity for 8 cylinders (4 shown)
Fuel Cell
5 or 8 kW each
![Page 26: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/26.jpg)
Product Testing (Mississauga)
![Page 27: Fuel Cell Extended Runtime Stationary Power Datacenter Angelo Monteleone Business Development Manager November 2013](https://reader035.vdocument.in/reader035/viewer/2022062511/551bce18550346c3588b52bd/html5/thumbnails/27.jpg)