full - ats - m2g - switchgear · 2020. 9. 17. · installation of remote indication boxes please...
TRANSCRIPT
-
ATSINSTRUCTIONS
MAINS TO GENERATOR
-
All items are sold under Switchgear Systems Limited standard terms and conditions, a copy of whichcan be found on our website (www.switchgear-systems.com).
It is the responsibility of the installer to ensure items are fitted to the requirements of BS 7671(Wiring Regulations) and best working practice.
Issue: 130918
-
INDEX
LAYOUT
SET-UP
02-03
04-05
06-07
14
15
16-23
24-31
32-33
34
35-36
08-09
10-11
12-13
Overview
Installation
Connection Diagram Key
4P M2G C331
4P M2G S331
2P M2G C330
Connecting to a generator
Front of enclosure
DS331 panel
DS330 panel
Remote add ons
Technical specs
Motor override switch
-
Installation and operation instructionsfor Mains to Generator ATS panels
This ATS is designed for use with a mains primary supply and a generator auxiliary supply. A constant DC power supply to the panel (either 12V or 24V depending on the model) is required at all times; this is normally taken from the GenSet battery but can also be fitted within the panel (as it may have been in this unit) or can be purchasedas a standalone unit. Please ensure you have the correct model of ATS for your application prior to installation. A full range of ATS panels for mains to mains is also available. Please visit www.switchgear-systems.com for more information. mmWe recommend local isolation of both supplies, immediately adjacent to the panel. Switchgear Systems Ltd have a comprehensive range of enclosed Load Break Isolators, Switch-Fuses and MCCBs which could be employed. We also supply a range of single line and dual line integrated ATS Bypass Switches for life safety systems.mmThis panel adheres to the European standard IEC60947-6-1 for transfer equipment. This panel is fully mains tested prior to leaving Switchgear Systems Ltd.
Test certificate number:
Signature:
The installer is responsible for ensuring that the installation conforms to the requirements of BS 7671 (Wiring regulations) and best safe working practice.
02
OVERVIEW
-
SPECIALREQUIREMENT?JUST ASK!
This system is designed to monitor the main supply in order to offer protection against phase failure, incorrect phase sequence and under/over voltage.
Features include:
• Voltage monitoring against pre-settable limits
• Status indication by LCD display
• Paired contactor switching mechanisms up to 160A and motorised
changeover switches from 200A and above
• Volt free N/O remote contacts for remote status indication
• All in one control interface giving external access to:
• Programming of settings
• Setting of operation condition
• Monitoring of supply condition
• Manual control
• On and Off load generator test facility
• The system monitors the primary supply and auxiliary supply for
stability
Switchgear Systems Ltd can also supply ATS systems
designed for use in circuits where both supplies are
coming from the mains or generator switches which
do not require a constant DC supply at the loss of
many of the setting options.
03
OVERVIEW
-
Installation Instructions
1. Before beginning the installation please ensure you have ordered the correct type of ATS unit. This panel is designed for use with mains primary and generator auxiliary power supplies. A DC supply is required to operate the control panel.2. You will require 2 cables from the GenSet to carry the positive and negative supplies (unless a remote power supply has been fitted). You will additionally need 1-2 cables for the remote start signal to the generator. Volt drop should be considered when deciding what cables to use but the current is nominal (less than an Amp) so 1.5mm will normally be suitable.3. The enclosure comes with 4 pre-drilled holes in the back for mounting, please see opposite page for dimension details for drilling. Alternatively wall mounting brackets are also available.4. Cables should be installed by a qualified electrician. Gland and make off cables to appropriate lengths being sure to adhere to the requirements set in BS7671. Please ensure you run sufficient control cables from the generator, normally this will be 3-4.5. Terminate and connect cables with appropriate ferrules and lugs where necessary. Torque settings are shown in the table on the opposite page. Please see the Connection Diagram key (pages 06-07) and appropriate Connection diagram (pages 08-14) for your unit, for details on where to terminate your cables.6. Alter the settings on the Deepsea control panel to the specifications of the site. Details about the operation and setting of these devices can be found on pages 16-31.7. If you need to fit remote indication please consult pages 07 and 32 for details.mmPlease note: Before commissioning ensure all terminals are tightened, including those factory fitted, as these may loosen during transit and storage. Maintenance of the IP ingress protection is the responsibility of the installer. All Panels are mains tested before leaving Switchgear Systems Ltd.
04
INSTALLATION
-
21mm
21mm
21mm
21mm
A C
B
9mm Ø
Rating Max CableDimensionA
(Width)B
(Height)C
(Depth)
35mm cage35mm cage35mm cage70mm cage70mm cage
200mm200mm200mm200mm250mm
600mm600mm700mm700mm800mm
400mm400mm500mm500mm600mm
40-100A (2 Pole)40-63A (4 Pole)80-100A (4 Pole)
125A (4 Pole)160A (4 Pole)
Contactor Switching (C331/C330)
95mm² M8120mm² M10150mm² M10
250mm300mm300mm
800mm800mm800mm
600mm600mm600mm
200A (4 Pole)250A (4 Pole)400A (4 Pole)
Motorised Changeover Switching (S331)
Torque
3Nm3Nm3Nm6Nm6Nm
15…22Nm30…44Nm30…44Nm
240mm² M10300mm1000mm600mm630A (4 Pole) 30…44Nm300mm² M12300mm1000mm800mm800A (4 Pole) 50…75Nm300mm² M12300mm1200mm800mm1000A (4 Pole) 50…75Nm300mm² M12300mm1200mm800mm1250A (4 Pole) 50…75Nm
05
INSTALLATION
-
The following pages contain the connection diagrams, component details and
wiring diagrams for the mains to generator range of ATS panels. The supply
input and supply output cable terminals are labelled inside the panel and are
also indicated on the connection diagram pages. Please consult pages 08-13
for your specific device during installation and setup.
Components List
A - Primary supply L1 circuit protection fuseB - Primary supply L2 circuit protection fuseC - Primary supply L3 circuit protection fuseD - Auxiliary supply L1 circuit protection fuse E - Auxiliary supply L2 circuit protection fuseF - Auxiliary supply L3 circuit protection fuseG - Genset battery supply & circuit protection fuseH - 10A Remote primary power supply fuseI - Primary supply contactor control changeover relayJ - Auxiliary supply contactor control changeover relayK - Generator start signal control changeover relayL - Auxiliary switch on primary supplyM - Primary supply contactorN - Auxiliary supply contactorO - Auxiliary switch on auxiliary supplyP - Changeover switchQ - Motor unit for switching changeover switchR - Manual key switch box (page 34)
06
CONNECTION DIAGRAM KEY
-
If remote indication is required please use the remote indication terminals as
shown on the relevant connection diagram page. These are volt free contacts
for use with BMS or remote indication boxes. For more details about
installation of remote indication boxes please consult page 32.
Generator Control & Power Terminals (page 14)
1 - VDC negative battery in2 - VDC positive battery in3 - Negative start signal for Deepsea GenSet4 - Generator start signal terminal input5 - Generator start signal terminal output
Volt Free Status Indication Terminals (page 32)
6 - Primary supply closed remote indication terminal input7 - Primary supply closed remote indication terminal output8 - Auxiliary supply closed remote indication terminal input9 - Auxiliary supply closed remote indication terminal output
Remote Power Supply Terminals (pages 32-33)
10 - Remote primary power supply live - MAX 10A11 - Remote primary power supply neutral - MAX 10A12 - Remote auxiliary power supply live - MAX 2A13 - Remote auxiliary power supply neutral - MAX 2A
07
CONNECTION DIAGRAM KEY
-
O
08
4P M2G C331
-
Out
put S
uppl
y
Auxi
liary
Inco
min
gSu
pply L3 NL2 L1
Prim
ary
Inco
min
gSu
pply
L3 NL2 L1
Volt
free
prim
ary
supp
lyin
dica
tion
term
inal
s
Volt
free
star
tco
ntac
tte
rmin
als
Volt
free
auxi
liary
supp
lyin
dica
tion
term
inal
sNegative input terminal
Start signal terminalPo
sitiv
ein
put
term
inal
Primary relay open signal
Positive to controller
Auxiliary relay close signal
Auxiliary supply L3 monitoring line
Rem
ote
auxi
liary
pow
ersu
pply
Max
2A
Auxiliary supply L2 monitoring line
Auxiliary supply L1 monitoring line
Auxiliary supply N monitoring line
Primary supply L3 monitoring line
Primary supply L2 monitoring line
Primary supply L1 monitoring line
Primary supply N monitoring line
Rem
ote
prim
ary
pow
ersu
pply
Max
2A
GenSet start signal
Negative to controller
09
4P M2G C331
-
O
P
L
Q
A B C D E F G
R
K
10
4P M2G S331
-
Out
put S
uppl
yAu
xilia
ryIn
com
ing
Supp
ly L3 NL2 L1
Prim
ary
Inco
min
gSu
pply
L3 NL2 L1
Volt
free
prim
ary
supp
lyin
dica
tion
term
inal
s
Volt
free
star
tco
ntac
tte
rmin
als
Volt
free
auxi
liary
supp
lyin
dica
tion
term
inal
sNegative input terminal
Start signal terminalPo
sitiv
ein
put
term
inal
Primary relay open signal
Auxiliary relay close signal
Motor clockwise
Auxiliary supply L3 monitoring line
Auxiliary supply L2 monitoring line
Auxiliary supply L1 monitoring line
Auxiliary supply N monitoring line
Primary supply L3 monitoring line
Primary supply L2 monitoring line
Primary supply L1 monitoring linePrimary supply N monitoring line
GenSet start signal
Negative to controller
Motor anti-clockwise
Rem
ote
auxi
liary
pow
ersu
pply
Max
2A
Rem
ote
prim
ary
pow
ersu
pply
Max
2A
Mot
orne
utra
l
Key
switc
h
Posi
tive
toco
ntro
ller
11
4P M2G S331
-
O
12
2P M2G C330
-
L N
Out
put S
uppl
yPr
imar
yIn
com
ing
Supp
ly
Auxi
liary
Inco
min
gSu
pply L N
Volt
free
prim
ary
supp
lyin
dica
tion
term
inal
s
Volt
free
star
tco
ntac
tte
rmin
als
Volt
free
auxi
liary
supp
lyin
dica
tion
term
inal
s
Negative input terminal
Start signal terminal
Posi
tive
inpu
tte
rmin
al
Primary relay open signal
Positive to controller
Auxiliary relay close signal
Auxiliary supply N monitoring line
Remote auxiliary power supply Max 2A
Auxiliary supply L monitoring line
Primary supply L monitoring line
Primary supply N monitoring line
Rem
ote
prim
ary
pow
ersu
pply
Max
2A
GenSet start signal
Negative to controller
13
2P M2G C330
-
Volt FreeGenerator
Start SignalTerminals *
Start Input
* Only one start signal required. Use either single cable negative start or twin cable volt free start. Positive and negative * is always required.
Negative Start Terminalfor DSE GenSet *
ATS Panel Genset
Star
t Out
put
Star
t Inp
utPositive Input
DSE
DSENegative Input
This ATS includes 2 volt free start terminals and one negative start terminal for connecting a generator. These terminals are a normally open contacts which close when mains fails and open again once power has returned to the mains and the generator cooldown timer has elapsed.
Typical connection example
14
CONNECTING TO A GENERATOR
-
WARNING LIVE TERMINALS ISOLATESUPPLY BEFORE REMOVING COVER
Tighten all connections, included thosefactory-fitted, before connecting mains supply.
DANGER!MIXED SUPPLIES PRESENT
ISOLATE ELSEWHERE
SwitchgearSystems Ltd
16 Woodside Park, Rugby, Warwickshire, CV21 2NPTel: 01788 577399 Fax: 01788 577899
Quarter turn
lock
Control Panel
(for 4P see pages 16-23)
(for 2P see pages 24-31)
15
FRONT OF ENCLOSURE
-
Info button Display Scroll Button Main Status Display Alarm Indicator
S1 Breaker Button Mode Select Button S2 Breaker Button
Operation of the panel
mm
•
mm
•
mm
•
The DSE331 controller on the front of the enclosure monitors the incoming
power supplies for under and over voltage, phase and power loss on both
the primary and auxiliary supplies. In the supplies are not within the limits
required by the settings it will not close the contactor responsible for
switching the supply load.mm
Pressing will cycle through monitoring screens showing the frequency,
individual phase voltages of each supply and battery supply voltage.mm
Pressing will cycle through the operational modes the ATS panel is
capable of running through. The mode description will flash; press to
lock in the desired mode. The details are on page 17.
16
DS331 PANEL
-
Modes
Start Inhibit - This mode prevents operation of the auxiliary (usually the generator) supply when the primary fails. It will close the
primary supply to load as long as it is available and will not
start or switch over to the generator. mm
Warning: This is the default mode of the panel; anytime the controller comes out of configuration mode or loses the DC supply powering it, it
will return to the start inhibit mode and must be reset to auto for normal
function.mm
Auto - This is the normal position the ATS should be set to for standard operation. It will send the GenSet start signal on
primary failure and switch the auxiliary to load. When the
primary is healthy again it will return the load to the
primary supply.mm
Manual - This gives the user manual control of the power supply; it will send the genset start signal to make both supplies
available. Pressing will close the primary supply to
load and pressing will close the generator to load.mm
Test - When the panel is in test mode it will send the start signal to the GenSet and switch the load to the generator and
continue to run that way until switched back to a different
mode.
17
DS331 PANEL
-
Setting up the panel
mm
1.
mm
2.
mm
3.
mm
4.
mm
5.
mm
6.
The DS331 requires a constant DC supply, usually taken from the
battery on the GenSet controller (Another power supply can be used if
for some reason this is not possible; Switchgear Systems Ltd has a
range of units available on request). Unless otherwise requested it will
be 12Vdc up to 80A and 24Vdc from 100A and above, however it is
easy to change if necessary.mm
If the genset is also made by Deep Sea Electronics the ‘Negative start
signal’ terminal (page 07) in the ATS panel should be wired to the
‘negative start’ terminal on the genset. If the genset requires a volt free
contact or a + signal you can use the volt free gen start terminals
(page 07).mm
When the panel is first installed and when it loses DC power it will
default to ‘start inhibit’ and will need to be changed to ‘auto’ mode to
function as normal.mm
Configuration of the DS331 settings can be achieved through the
display on the front or by using the software found on the Deep Sea
Electronics website and connecting a computer to the Deep Sea panel
via the USB port on the back.mm
Editing a parameter through the display uses the configuration tables
on pages 20-23 of this booklet and is done by following the steps on
page 19.mm
Refer to the configuration tables on the pages 20-23 for details on the
adjustments that can be made.
18
DS331 PANEL
-
Editing the parameters
mm
• Press and hold the button until the configuration icon appears
on screen (a crossed spanner and hammer).
• Press to cycle forwards through the parameter options; to
cycle backwards through the parameter list press . Pressing
will cycle forwards through full parameter ‘pages’ to get to the
later parameters more quickly.
• When the screen displays the parameter you wish to change press
. The value will begin to flash allowing it to be altered.
• Press the and buttons to adjust the value to the desired
setting.
• Press the button again to save the current value; the value
should stop flashing to show it is saved.
• Press and hold the button when you have finished to exit
configuration mode; configuration icon should no longer be visible.
• Pressing and holding the buttons to adjust the value will cause it
to move faster for cycling large values, such as time, faster.
19
DS331 PANEL
-
Contrast101Display Mode102S1 Option103S1 Summary Screen Phase Display104S2 Option105S1 Summary Screen Phase Display106Lamp test at power up107Power Up In Auto108Enable Transfer By Buttons109Test Mode110
Breaker Type201Check Sync202Return To Programmed Transition203Display Mode204Open / Close S115Digital Input A Source301Digital Input A Polarity302Digital Input B Source303Digital Input B Polarity304Digital Input C Source305Digital Input C Polarity306Digital Input D Source307Digital Input D Polarity308
Digital Output A Source401Digital Output A Polarity402Digital Output B Source403Digital Output B Polarity404Digital Output C Source405Digital Output C Polarity406Digital Output D Source407Digital Output D Polarity408Digital Output E Source409Digital Output E Polarity410Digital Output F Source411Digital Output F Polarity412Digital Output G Source413Digital Output G Polarity414Digital Output H Source415Digital Output H Polarity416
Module (page 1)
Application (page 2)
Inputs (page 3)
Outputs (page 4)
000 (%)Icon Only (1), English (0)Generator (1), Mains (0)1 - 3Generator (1), Mains (0)1 - 3On (1), Off (0)On (1), Off (0)On (1), Off (0)On Load (1), Off Load (0)
Scheme B (1), Scheme A (0)On (1), Off (0)On (1), Off (0)Icon Only (1), English (0)
0 (Input Source List)0 (Input Polarity List)0 (Input Source List)0 (Input Polarity List)0 (Input Source List)0 (Input Polarity List)0 (Input Source List)0 (Input Polarity List)
0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)
Setting up the panel: Configurations tables for DS331
20
DS331 PANEL
-
S1 Transient Delay501Start Delay502Warming Time503S2 Fail Delay504Elevator Delay505Non-sync Transfer Time506Check Sync Tranfer Time507Breaker Close Pulse508
Timers (page 5)Breaker Trip PulseReturn DelayCooling TimeS2 Transient DelayFail To Stop EnableFail To Stop DelayLCD Page TimerLCD Scroll Timer
509510511512513514515516
S1 (page 6)Immediate S1 dropout601AC system602Under voltage enable603Under voltage trip604Under voltage return605Over voltage enable606Over voltage return607Over voltage trip608Under frequency enable609Under frequency trip610Under frequency return611Over frequency enable612Over frequency return613Over frequency trip614
S2 (page 7)Immediate S2 Dropout701Under voltage enable (Generator Option)702Under voltage trip (Generator Option)703Loading voltage (Generator Option)704Over voltage enable (Generator Option)705Over voltage trip (Generator Option)706Under frequency enable (Generator Option)707Under frequency trip (Generator Option)708Loading frequency (Generator Option)709Over frequency enable (Generator Option)710Over frequency trip (Generator Option)711Under voltage enable (Mains Option)712Under voltage (Mains Option)713Under voltage return (Mains Option)714
On (1), Off (0)0 (AC System)On (1), Off (0)0 V0 VOn (1), Off (0)0 V0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 Hz0.0 Hz
On (1), Off (0)On (1), Off (0)0 V0 VOn (1), Off (0)0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 HzOn (1), Off (0)0.0 V0.0 V
Over voltage enable (Mains Option)715Over voltage return (Mains Option)716
On (1), Off (0)0.0 V
21
DS331 PANEL
-
Input Source ListNot Used0Alarm Reset1Alarm Mute2Auto Restore Inhibit3Auto Start Inhibit4Auxiliary S2 Available5Auxiliary S1 Fail6S2 Load Inhibit7S2 Closed Auxiliary8Inhibit Scheduled Run9
Output Source ListNot Used0Audible Alarm1Battery High Voltage2Battery Low Voltage3Close S2 Output4Close S2 Output Pulse5Close S1 Output6Close S1 Output Pulse7Close to N Output8Close to N Output Pulse9
Over voltage trip (Mains Option)717Under frequency enable (Mains Option)718Under frequency (Mains Option)719Under frequency return (Mains Option)720Over frequency enable (Mains Option)721Over frequency return (Mains Option)722Over frequency trip (Mains Option)723
Plant Battery (page 8)Under voltage enable801Under voltage802Under voltage return803Under voltage delay804Over voltage enable805Over voltage return806Over voltage trip807Over voltage delay808
Enable scheduler901On or Off load902Start time903Day904Duration905
Scheduler (page 9)
Time of day1001Time of week1002Start time1003
Time (page 10)
0.0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 Hz0.0 Hz
On (1), Off (0)0.0 V0.0 V0.00.00On (1), Off (0)0.0 V0.0 V0.00.00
On (1), Off (0)On (1), Off (0)0:001-7 (Day, 1 = Monday)0:00
0:001-7 (Day, 1 = Monday)0:00
Parameters with multiple choices use the following identification tables for the parameter values:
22
DS331 PANEL
-
Input Polarity List
Input Alarming List
Input Action List
AC System
Lamp Test10Load Shedding11S1 Closed Auxiliary12S2 Load Inhibit13Open / Close S214Open / Close S115Panel Lock16Remote Start off-load17Remote Start on-load18Simulated S1 Available19Simulated S2 Available20
TypeIndex3 Phase 4 Wire0Single Phase 2 Wire13 Phase 3 Wire22 Phase 3 Wire (L1 - L2)32 Phase 3 Wire (L1 - L3)43 Phase 4 Wire (Delta)5
AlarmingIndexAlways0From Safety On1From Starting2Never3
ActionIndexElectrical Trip0Shutdown1Warning2
ActionIndexClose to Activate0Open to Activate1
Common Warning10Cooling Down11Digital Input A12Digital Input B13Digital Input C14Digital Input D15Elevator Control16Fail To Start17Fail To Stop18Fail To Reach Loading Voltage19Fail To Reach Loading Frequency20S2 Available21S2 Failure Latched22S2 Failure Unlatched23S2 In Limits24S2 Load Inhibited25S2 Ready26S1 Failure Unlatched27S1 Failure Latched28S1 High Frequency29S1 High Voltage30S1 In Limits31S1 Load Inhibited32S1 Low Frequency33S1 Low Voltage34Return Delay35Open S2 Output36Open S2 Output Pulse37Open S1 Output38Open S1 Output Pulse39Scheduled Run40Start And Run S241Start Delay42Waiting For S243Waiting For Manual Restore44Warming Up45
Output Polarity ListAlarmingIndexEnergise0De-energise1
23
DS331 PANEL
-
Display Scroll Button Main Status Display Alarm Indicator
S1 Breaker Button Mode Select Button S2 Breaker Button
Operation of the panel
•
mm
•
mm
•
The DSE330 controller on the front of the enclosure monitors the incoming
power supplies for under and over voltage and power loss on both the
primary and auxiliary supplies. In the supplies are not within the limits
required by the settings it will not close the contactor responsible for
switching the supply load.mm
Pressing will cycle through monitoring screens showing the frequency,
individual phase voltages of each supply and battery supply voltage.mm
Pressing will cycle through the operational modes the ATS panel is
capable of running through. The mode description will flash; press
again to lock in the desired mode. The details are on page 25.
24
DS330 PANEL
-
Modes
Start Inhibit - This mode prevents operation of the auxiliary (usually the generator) supply when the primary fails. It will close the
primary supply to load as long as it is available and will not
start or switch over to the generator. mm
Warning: This is the default mode of the panel; anytime the controler comes out of configuration mode or loses the DC supply powering it, it
will return to the start inhibit mode and must be reset to auto for normal
function.mm
Auto - This is the normal position the ATS should be set to for standard operation. It will send the GenSet start signal on
primary failure and switch the auxiliary to load. When the
primary is healthy again it will return the load to the
primary supply.mm
Manual - This gives the user manual control of the power supply; it will send the genset start signal to make both supplies
available. Pressing will close the primary supply to
load and pressing will close the generator to load.mm
Test - When the panel is in test mode it will send the start signal to the GenSet and switch the load to the generator and
continue to run that way until switched back to a different
mode.
25
DS330 PANEL
-
Setting up the panel
1. The DS330 requires a constant DC supply, usually taken from the
battery on the genset controller (Another power supply can be used
if for some reason this is not possible; Switchgear Systems Ltd has
a range of units available on request). Unless otherwise requested it
will be 12VDC on all 2 pole ATS but it is easy to change if necessary.mm
2. If the genset is also made by Deep Sea Electronics the ‘Negative
start signal’ terminal (page 07) in the ATS panel should be wired to
the ‘negative start’ terminal on the genset. If the genset requires a
volt free contact or a + signal you can use the volt free gen start
terminals (page 07).mm
3. When the panel is first installed and when it loses DC power it will
default to ‘start inhibit’ and will need to be changed to ‘auto’ mode to
function as normal.mm
4. Configuration of the DS330 settings can be achieved through the
display on the front or by using the software found on the Deep Sea
Electronics website and connecting a computer to the Deep Sea panel
via the USB port on the back. mm
5. Editing a parameter through the display uses the configuration tables
on pages 28-31 of this booklet and is done by following the steps on
page 27.mm
6. Refer to the configuration tables on the pages 28-31 for details on the
adjustments that can be made.
26
DS330 PANEL
-
Editing the parameters
• Press and hold the button until the configuration icon appears
on screen (a crossed spanner and hammer).
• Press to cycle forwards through the parameter options; to
cycle backwards through the parameter list press . Pressing
will cycle forwards through full parameter ‘pages’ to get to the
later parameters more quickly.
• When the screen displays the parameter you wish to change press
. The value will begin to flash allowing it to be altered.
• Press the and buttons to adjust the value to the desired
setting.
• Press the button again to save the current value; the value
should stop flashing to show it is saved.
• Press and hold the button when you have finished to exit
configuration mode; configuration icon should no longer be visible.
• Pressing and holding the buttons to adjust the value will cause it
to move faster for cycling large values such as time.
27
DS330 PANEL
-
Setting up the panel: Configurations tables for DS330
Contrast101Display Mode102S1 Option103RESERVED104S2 Option105RESERVED106Lamp test at power up107Power Up In Auto108Enable Transfer By Buttons109Test Mode110
Breaker Type201RESERVED202RESERVED203Elevator Post Transfer204Open / Close S115Digital Input A Source301Digital Input A Polarity302Digital Input B Source303Digital Input B Polarity304
Digital Output A Source401Digital Output A Polarity402Digital Output B Source403Digital Output B Polarity404Digital Output C Source405Digital Output C Polarity406Digital Output D Source407Digital Output D Polarity408
Module (page 1)
Application (page 2)
Inputs (page 3)
Outputs (page 4)
000 (%)Icon Only (1), English (0)Generator (1), Mains (0)
Generator (1), Mains (0)
On (1), Off (0)On (1), Off (0)On (1), Off (0)On Load (1), Off Load (0)
Scheme B (1), Scheme A (0)
On (1), Off (0)
0 (Input Source List)0 (Input Polarity List)0 (Input Source List)0 (Input Polarity List)
0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)0 (Output Source List)0 (Output Source Polarity)
Display ph-ph111 On (1), Off (0)
S1 Transient Delay501Start Delay502Warming Time503S2 Fail Delay504Elevator Delay505Non-sync Transfer Time506RESERVED507Breaker Close Pulse508
Timers (page 5)
Breaker Trip Pulse509
28
DS330 PANEL
-
S1 (page 6)Immediate S1 dropout601AC system602Under voltage enable603Under voltage trip604Under voltage return605Over voltage enable606Over voltage return607Over voltage trip608Under frequency enable609Under frequency trip610Under frequency return611Over frequency enable612Over frequency return613Over frequency trip614
S2 (page 7)Immediate S2 Dropout701Under voltage enable (Generator Option)702Under voltage trip (Generator Option)703Loading voltage (Generator Option)704Over voltage enable (Generator Option)705Over voltage trip (Generator Option)706Under frequency enable (Generator Option)707Under frequency trip (Generator Option)708Loading frequency (Generator Option)709Over frequency enable (Generator Option)710Over frequency trip (Generator Option)711Under voltage enable (Mains Option)712Under voltage (Mains Option)713Under voltage return (Mains Option)714
On (1), Off (0)0 (AC System)On (1), Off (0)0 V0 VOn (1), Off (0)0 V0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 Hz0.0 Hz
On (1), Off (0)On (1), Off (0)0 V0 VOn (1), Off (0)0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 HzOn (1), Off (0)0.0 V0.0 V
Over voltage enable (Mains Option)715Over voltage return (Mains Option)716
On (1), Off (0)0.0 V
Breaker Trip Pulse509Return Delay510Cooling Time511S2 Transient Delay512Fail to stop enable513Fail to stop delay514LCD Page timer515LCD Scroll timer516
29
DS330 PANEL
-
Input Source ListNot Used0Alarm Reset1Alarm Mute2Auto Restore Inhibit3Auto Start Inhibit4Auxiliary S2 Available5Auxiliary S1 Fail6S2 Load Inhibit7S2 Closed Auxiliary8Inhibit Scheduled Run9
Output Source ListNot Used0Audible Alarm1Battery High Voltage2Battery Low Voltage3Close S2 Output4Close S2 Output Pulse5Close S1 Output6Close S1 Output Pulse7Close to N Output8Close to N Output Pulse9
Over voltage trip (Mains Option)717Under frequency enable (Mains Option)718Under frequency (Mains Option)719Under frequency return (Mains Option)720Over frequency enable (Mains Option)721Over frequency return (Mains Option)722Over frequency trip (Mains Option)723
Plant Battery (page 8)Under voltage enable801Under voltage802Under voltage return803Under voltage delay804Over voltage enable805Over voltage return806Over voltage trip807Over voltage delay808
Enable scheduler901On or Off load902Start time903Day904Duration905
Scheduler (page 9)
Time of day1001Time of week1002Start time1003
Time (page 10)
0.0 VOn (1), Off (0)0.0 Hz0.0 HzOn (1), Off (0)0.0 Hz0.0 Hz
On (1), Off (0)0.0 V0.0 V0.00.00On (1), Off (0)0.0 V0.0 V0.00.00
On (1), Off (0)On (1), Off (0)0:001-7 (Day, 1 = Monday)0:00
0:001-7 (Day, 1 = Monday)0:00
Parameters with multiple choices use the following identification tables forthe parameted values:
30
DS330 PANEL
-
Input Polarity List
Input Alarming List
Input Action List
AC System
Lamp Test10Load Shedding11S1 Closed Auxiliary12S2 Load Inhibit13Open / Close S214Open / Close S115Panel Lock16Remote Start off-load17Remote Start on-load18Simulated S1 Available19Simulated S2 Available20
TypeIndex2 Phase 3 Wire (L1 - L2)02 Phase 3 Wire (L1 - L3)13 Phase 3 Wire23 Phase 4 Wire33 Phase 3 Wire (Delta)4Single phase 2 wire5
AlarmingIndexAlways0From Safety On1From Starting2Never3
ActionIndexElectrical Trip0Shutdown1Warning2
ActionIndexClose to Activate0Open to Activate1
Common Warning10Cooling Down11Digital Input A12Digital Input B13Reserved14Reserved15Elevator Control16Fail To Start17Fail To Stop18Fail To Reach Loading Voltage19Fail To Reach Loading Frequency20S2 Available21S2 Failure Latched22S2 Failure Unlatched23S2 In Limits24S2 Load Inhibited25S2 Ready26S1 Failure Unlatched27S1 Failure Latched28S1 High Frequency29S1 High Voltage30S1 In Limits31S1 Load Inhibited32S1 Low Frequency33S1 Low Voltage34Return Delay35Open S2 Output36Open S2 Output Pulse37Open S1 Output38Open S1 Output Pulse39Scheduled Run40Start And Run S241Start Delay42Waiting For S243Waiting For Manual Restore44Warming Up45
Output Polarity ListAlarmingIndexEnergise0De-energise1
31
DS330 PANEL
-
11 10
6 8
7 9
12 13
Connecting a remote indication box
The remote indication boxes supplied by Switchgear Systems Ltd come
complete with graphics and LED indicators which mirror those of the ATS
panels. As standard these are supplied with 240VAC lamps but alternative
voltages and DC versions are also available on special request. If using the
240VAC units, remote fused power supplies are available within the panel for
creating the circuit (terminals 10-13). The terminals are described on page 6
‘Customer connection diagram key’. Please see diagram below.
Please note: The supply must be available when the lamp is to be illuminated. As such the
Primary/Auxiliary remote supply should be used for the Primary/Auxiliary lamps respectively.
RemoteTerminals
PowerSupplyTerminals
LN230V AC
L N230V AC
32
REMOTE ADD ONS
-
Battery and charger
In some cases the battery on the GenSet may not be a convenient power
source for the ATS panel because of distance or access. In these cases a
local supply must be used. We offer a range of remote power supplies, either
in 12VDC or 24VDC to suit the ATS being used. The battery and charger can
also be installed directly into the panel at the time of manufacture.
This ATS may be fitted with a battery and charger; if it is, this will draw power
from the 10A remote primary supply built into the panel. If it is not and you
need to install a remote unit take the power supply from the 10A remote
primary supply as shown in the wiring diagram below:
Charger ATS Panel
VDC
neg
ativ
e ba
ttery
in
VDC
pos
itive
bat
tery
in
Rem
ote
prim
ary
pow
er s
uppl
y liv
e - M
AX 1
0A
Rem
ote
prim
ary
pow
er s
uppl
y ne
utra
l - M
AX 1
0A
33
REMOTE ADD ONS
-
Internal key switch for manual operation
Component R (200A and above panels which utilise motorised changeover switches only)
This unit can be manually operated by dis-engaging the motor and using the
enclosed loose handle to turn the shaft inside the panel by following these
steps:
• Inside the panel there is a key switch (Component R); turn this to the off
position. This will dis-engage the motor circuit and release the key.
• Remove the key from the switch and insert the other key into the lock on
the enclosed handle. Press in the red button and turn the key to lock it in
position; this will allow the handle to fit over the Changeover switch shaft.
Please note: The two keys must remain together to prevent manual operation of the switch
whilst the motor is still engaged.
• To return to automatic mode simply turn and remove the key from the
handle, then use the other key to turn the key switch in the panel back to
engage the motor again.
34
MOTOR OVERRIDE SWITCH
-
AC-3 Utilisation Category
ATS Rated Current 40A 63A 80A 100A 125A 160A
Rated Operation Voltage (Ue)
Rated Frequency (Without De-rating)
Rated OperationalPower AC-3
Rated Making Capacity
Rated Breaking Capacity
Rated Short TimeWithstand Current Low
(at 40°C AmbientTemperature in free air
from a cold state)
Maximum BreakingCapacity (cos o = 0.45)I
Power Dissipation perPole
Max. Elec. SwitchingFrequency
240V
440V
240V
440V
AC-3
AC-3
1 S
10 S
30 S
1 min
15 min
440V
690V
AC-1
Ie/AC-1
Ie/AC-3
690V 690V 690V 690V 690V 690V
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
23.2A 40A 53A 53A 80A 116A
20A 40A 53A 53A 80A 116A
5.5kW 11kW 15kW 15kW 22kW 30kW
11kW 22kW 30kW
10 x Ie AC-3 acc. to IEC 60947-4-1
8 x Ie AC-3 acc. to IEC 60947-4-1
30kW 40kW 75kW
450A 1000A 1000A 1000A 1200A 1300A
300A 600A 600A 600A 780A 928A
225A 350A 350A 350A 450A 536A
150A 250A 250A 250A 300A 379A
55A 110A 110A 110A 140A 160A
- 950A 950A 950A 1100A 1200A
- 600A 600A 600A 750A -
1.6W 3W 6.3W 6.3A 8W 12W
0.42W 1W 1.7W 1.7W 3.2W -
600 cycles/h 300cycles/h
Contactor Ratings:
This includes the following ATS panels:
4P M2G C331 / 2P M2G C330
35
TECHNICAL SPECS
-
Motorised Switch Ratings:
This includes the following ATS panels:
4P M2G S331
A
AC21A-AC22A
AC23A
A.C.
690V
415V
690V
380V
1 s
415V
Number ofoperations
Number ofoperations
V
KV
A
A
A
Kvar
KAr.m.s
KApeak
W
200A
1000V
8KV
200A
200A
100A
80Kvar
10KA
20KA
4W
1000
8000
ATS Rated Current
Rated Voltage of Isolation
Impulse Withstand Voltage
Operational Current
Reactive Power
Rated Short-Time Withstand Current
Rated Short-Circuit Making Capacity
Mechanical Endurance
Electrical Life
Power Losses Per Pole
250A
1000V
8KV
250A
250A
125A
100Kvar
12.5KA
25KA
4.7W
1000
8000
400A
1000V
8KV
400A
400A
160A
150Kvar
15KA
30KA
11W
1000
5000
630A
1000V
8KV
630A
630A
200A
250Kvar
16KA
32KA
25W
1000
5000
800A
1000V
12KV
800A
800A
250A
300Kvar
30KA
63KA
22.5W
500
3000
1000A
1000V
12KV
1000A
1000A
315A
375Kvar
31.5KA
66KA
34W
500
3000
1250A
1000V
12KV
1250A
1250A
400A
450Kvar
35KA
73.5KA
53W
500
3000
36
TECHNICAL SPECS
-
Switchgear Systems Ltd.16 Woodside ParkWebb Ellis Industrial EstateRugby, WarwickshireCV21 2NP
T 01788 577399F 01788 577899E [email protected] www.switchgear-systems.com
Sheet Steel Enclosed Products
Sheet Steel Enclosed Double Break Switchfuses
Sheet Steel Enclosed Load Break Isolators
Sheet Steel Busbar Chambers
Sheet Steel Enclosed MCCBs & RCBOs
Sheet Steel Enclosed 4 Pole Contactors
Sheet Steel Enclosed Changeover Switches I-0-II
Sheet Steel Junctions Boxes & Generator Hook-Ups
Automatic Transfer Switch Panels
Sheet Steel Enclosed Bypass Switches
Panelboards & Section Boards
Power Rated Earth & Neutral Bars
PROVIDING A WIDE RANGE OFSWITCHGEAR PRODUCTS