functional safety manual soliphant m with electronic ...€¦ · switch setting for the safety...

12
SD204F/00/en 71020793 Functional safety manual Soliphant M with electronic insert FEM52 Level Limit Measuring System Application Overfill protection or operating maximum detection of all types of solids in tanks to satisfy particular safety systems requirements to IEC 61508. The measuring device fulfils the requirements concerning for safety functions up to SIL 2 explosion protection by intrinsic safety or flameproof enclosure EMC to EN 61326 and NAMUR Recommendation NE 21. Your benefits For overfill protection up to SIL 2 Independently assessed (Functional Assessment) by exida to IEC 61508 No calibration Protected against outside vibration Easy commissioning

Upload: others

Post on 15-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

SD204F/00/en71020793

Functional safety manual

Soliphant M with electronic insert FEM52 Level Limit Measuring System

ApplicationOverfill protection or operating maximum detection of all types of solids in tanks to satisfy particular safety systems requirements to IEC 61508.

The measuring device fulfils the requirements concerning • for safety functions up to SIL 2 • explosion protection by intrinsic safety or flameproof

enclosure • EMC to EN 61326 and

NAMUR Recommendation NE 21.

Your benefits

• For overfill protection up to SIL 2– Independently assessed (Functional Assessment)

by exida to IEC 61508 • No calibration • Protected against outside vibration • Easy commissioning

Page 2: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

2 Endress + Hauser

Table of contents

SIL declaration of conformity. . . . . . . . . . . . . . . . . . . . 3

Functional Assessment Report. . . . . . . . . . . . . . . . . . . 4

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Structure of the measuring system with Soliphant M with FEM52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Level limit measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Safety function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Supplementary device documentation . . . . . . . . . . . . . . . . . . . . . . 6

Settings and installation instructions . . . . . . . . . . . . . . 6Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Settings for Soliphant M with FEM52 . . . . . . . . . . . . . . . . . . . . . . 7

Response in operation and failure . . . . . . . . . . . . . . . . 8

Failure rates of electrical components . . . . . . . . . . . . . 8

Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Recurrent function tests of the measuring system . . . . 8

Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Specific values and wiring options for the measuring system Soliphant M with FEM52 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

FMEDA Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Page 3: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

Endress + Hauser 3

SIL declaration of conformity

SIL05003b-en

Exam

ple

Page 4: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

4 Endress + Hauser

Functional Assessment Report

L00-FEM5xxxx-01-06-xx-en-001

Page 5: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

Endress + Hauser 5

Introduction

! Note! For general information about SIL please refer to: www.endress.com/sil

and in the Competence Brochure CP002Z "Safety in the Process Industry – reducing risks with SIL"

Structure of the measuring system with Soliphant M with FEM52

Level limit measuring system The measuring system is displayed in the following diagram (example).

L00-FTM5xxxx-16-06-xx-en-001

Soliphant M with electronics insert FEM52: three-wire DC connection (PNP) with transistor output

Safety function The safety function only applies to MAX safety (overfill protection).

The transistor output is blocked when:

• The switch point is exceeded (level exceeds response height) • A fault occurs • The mains voltage fails

The measuring range of Soliphant M depends on the medium, mounting location and fork length.

The detection range is within the length of the fork and depends on the weight of the medium and the resulting type of fork:

• Standard fork with a length of 155 mm (Density of medium ≥ 10 g/l) and• Short fork with a length of 100 mm (Density of medium ≥ 50 g/l)

Soliphant M

Electronic insert

Page 6: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

6 Endress + Hauser

Permitted versions of the Soliphant M with FEM52 for the safety function

The following combinations are permitted for the measuring system:

• FTM50-#####2#####• FTM51-#####2#####• FTM52-#####2#####

Permitted instrument types (# = all instrument versions permitted excepting 9 and Y)

• Valid FW version (firmware): V01.01.00 or higher• Valid HW version (hardware): V02.00 or higher

Safety function data

The mandatory settings and data for the safety function can be found in the Appendix (Page 9).

The measuring system reacts in ≤ 0.9 s.

! Note! MTTR is set at 8 hours under the condition that the electronics insert is on stock.Safety systems without a self-locking function must be monitored or set to an otherwise safe state after carrying out the safety function within MTTR.

Supplementary device documentation

The following must be available for the measuring system:

Settings and installation instructions

Installation instructions Please refer to the Operating Instructions (KA) for information regarding the correct installation ofSoliphant M with FEM52. Since the application conditions have an effect on the safety of the measurement, pay attention to the notes in the Technical Information (TI) and Operating Instructions (KA).

Refer to the following documentation for instructions on setting the instruments:

Technical Information Operating Instructions

Soliphant M FTM50, FTM51, FTM52TI392F/00

FTM50, FTM51KA229F/00

FTM52KA230F/00

Relevant contents Connection data, Installation instructions

Setting, configuration, remarks, function tests

Setting description in documentation

Soliphant M FTM50, FTM51KA229F/00

FTM52KA230F/00

Page 7: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

Endress + Hauser 7

Settings for Soliphant M with FEM52

Connectable load:

• Load switched via transistor and separate PNP connection, max. 55 V• Load current max. 350 mA (cyclical overload and short-circuit protection)• Residual current < 100 µA (with transistor blocked)• Capacitive load max. 0.5 µF at 55 V, max. 1.0 µF at 24 V• Residual voltage < 3 V (for transistor switched through)

Overvoltage protection FEM52: overvoltage category III

! Note! The SIL evaluation for the Soliphant M comprises the complete device, including the electronics insert,the tuning fork with piezo drive, the process connection and the internal wiring.

In applications with extremely strong external vibrations > 0.05 g2/Hz and light weight bulk solids < 600 gr/la functional test is recommended!

It is recommended to leave the switching elements following the overfill protection in the safe state until the alarm signal has been acknowledged.

" Caution! Changes to the settings at the electronic insert FEM52 after measuring system start-up can impair the safety function!

Switch setting for the safety function:

L00-FTM5xxxx-19-05-xx-xx-015

One switch for safety mode

MAX Overfill protection MIN Dry running protection

One switch for switching delay

0.5 s when covered, 1.5 s when uncovered (short fork 1 s)

5 s when covered, 5 s when uncovered

One switch for bulk density/density setting

≥ 50 g/l standard fork, ≥ 200 g/l short fork (high bulk density)

≥ 10 g/l standard fork, ≥ 50 g/l short fork (low bulk density)

One switch for diagnosis

OFF Diagnosis of abrasion and build-up switched OFF. ON Diagnosis of abrasion and build-up switched ON.

• For additional density setting to high bulk density:abrasion and build-up are indicated per LED at the electronic insert only

• For additional density setting to low bulk density:output of "signal on alarm" for abrasion and build-up

MAXMIN ON

OFF

Page 8: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

8 Endress + Hauser

Response in operation and failure

The response in operation and failure is described in the following documentation:

Failure rates of electrical components

The underlying failure rates of electrical components are specified for the useful lifetime according to IEC 61508-2 Section 7.4.7.4. Note 3.

Repair

If a SIL-marked device that has been operated in a functional safety application fails, the "Declaration of Hazardous Material and De-Contamination" form containing the appropriate information "Used as a SIL device in a Safety Instrumented System" must be enclosed with the defective device when it is returned.

Recurrent function tests of the measuring system

The operativeness of the overfill protection must be checked periodicaly if the PFDavg values given in the Appendix are used. The check must be carried out in such a way that it is proven that the overfill protection functions perfectly in interaction with all components. This is guaranteed when the response height is approached in a filling process. If it is not practical to fill to the response height, suitable simulation of the level or of the physical measuring effect must be used to make the level sensor respond. If the operativeness of the level sensor/transmitter can be determined otherwise (exclusion of faults that impair function), the check can also be completed by simulating the corresponding output signal.

" Caution! Note the following points for the function test: • Transistor output switching can be checked by using a hand multimeter at the terminals or by observing the

overfill protection elements (e.g. horn, adjuster). • As a positive test result, a covered tuning fork must be detected and trigger the alarm for overfill protection. • If fork covering is not detected during the recurrent test, the monitored process must be set to a

safe state by means of additional or other measures and/or kept in the safe state until the safety system is repaired.

Setting description in documentation

Soliphant M FTM50, FTM51KA229F/00

FTM52KA230F/00

Page 9: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

Endress + Hauser 9

Appendix

Specific values and wiring options for the measuring system Soliphant M with FEM52

The table show values and wiring options relevant to safety for the measuring system.

L00-FTM5xxxx-05-06-xx-en-002

1oo1 architecture

Evaluated transmitter (FEM52)

L00-FEM5xxxx-14-06-06-xx-001

MAX

SIL SIL 2

HFT 0

SFF 90 %

PFDavg(low demand mode of operation)

0.025 x 10-2

λsd 39 FIT

λsu2 487 FIT

λdd 39 FIT

λdu 58 FIT

MTBF 158 years

Wiring scheme

L00-FTM5xxxx-04-06-xx-xx-002 PNP

Recurrent teste.g. approaching level

T1 (test interval) as required; see table below

CH1

Pro

bab

ility

PFDavg

0 1 2 3 4 5 6 7 8 9 10

0,300x10–2

0,250x10–2

0,200x10–2

0,100x10–2

0,050x10–2

0,000x10–2

0,150x10–2

Test interval[years]

1oo1 structure

Page 10: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

10 Endress + Hauser

FMEDA Report

L00-FEM52xxx-01-06-xx-en-002

L00-FEM52xxx-01-06-xx-en-001

© e

xida.c

om G

mbH

e+

h 0

3-0

3-2

2 r

030 v

1 r

1.0

.doc,

July

5,

2005

Ste

phan A

schenbre

nner

Page 2

of

3

Ma

na

ge

me

nt

su

mm

ary

Th

is r

ep

ort

su

mm

ari

ze

s t

he

re

su

lts o

f th

e h

ard

wa

re a

sse

ssm

en

t ca

rrie

d o

ut

on

th

e l

eve

l lim

it

sw

itch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

an

d s

oft

wa

re v

ers

ion

V0

1.0

0.0

0.

Th

e

ha

rdw

are

a

sse

ssm

en

t co

nsis

ts

of

a

Fa

ilure

M

od

es,

Eff

ects

a

nd

D

iag

no

stics

An

aly

sis

(F

ME

DA

). A

FM

ED

A i

s o

ne

of

the

ste

ps t

ake

n t

o a

ch

ieve

fu

nctio

na

l sa

fety

asse

ssm

en

t o

f a

d

evic

e p

er

IEC

61

50

8.

Fro

m t

he

FM

ED

A,

failu

re r

ate

s a

re d

ete

rmin

ed

an

d c

on

se

qu

en

tly t

he

S

afe

F

ailu

re F

ractio

n (S

FF

) is

ca

lcu

late

d fo

r th

e d

evic

e.

Fo

r fu

ll a

sse

ssm

en

t p

urp

ose

s a

ll re

qu

ire

me

nts

of

IEC

61

50

8 m

ust

be

co

nsid

ere

d.

Th

e f

ailu

re r

ate

s u

se

d i

n t

his

an

aly

sis

are

th

e b

asic

fa

ilure

ra

tes f

rom

th

e S

iem

en

s s

tan

da

rd

SN

29

50

0.

Acco

rdin

g t

o t

ab

le 2

of

IEC

61

50

8-1

th

e a

ve

rag

e P

FD

fo

r syste

ms o

pe

ratin

g i

n l

ow

de

ma

nd

mo

de

ha

s t

o b

e

10

-3 t

o <

10

-2 f

or

SIL

2 s

afe

ty f

un

ctio

ns.

A g

en

era

lly a

cce

pte

d d

istr

ibu

tio

n o

f P

FD

AV

G v

alu

es o

f a

SIF

ove

r th

e s

en

so

r p

art

, lo

gic

so

lve

r p

art

, a

nd

fin

al

ele

me

nt

pa

rt a

ssu

me

s

tha

t 3

5%

of

the

to

tal S

IF P

FD

AV

G v

alu

e is c

au

se

d b

y t

he

se

nso

r p

art

. F

or

a S

IL 2

ap

plic

atio

n t

he

to

tal

PF

DA

VG v

alu

e o

f th

e S

IF s

ho

uld

be

sm

alle

r th

an

1,0

0E

-02

, h

en

ce

th

e m

axim

um

allo

wa

ble

P

FD

AV

G v

alu

e f

or

the

se

nso

r p

art

wo

uld

th

en

be

3,5

0E

-03

.

Th

e l

eve

l lim

it s

witch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

is c

on

sid

ere

d t

o b

e a

T

yp

e B

1 c

om

po

ne

nt

with

a h

ard

wa

re f

au

lt t

ole

ran

ce

of

0.

Fo

r T

yp

e B

co

mp

on

en

ts w

ith

a h

ard

wa

re f

au

lt t

ole

ran

ce

of

0 t

he

SF

F s

ha

ll b

e >

90

% a

cco

rdin

g

to t

ab

le 3

of

IEC

61

50

8-2

fo

r S

IL 2

(su

b-)

syste

ms.

En

dre

ss+

Ha

use

r to

ge

the

r w

ith

exi

da.c

om p

erf

orm

ed

a q

ua

lita

tive

an

aly

sis

of

the

me

ch

an

ica

l p

art

s o

f th

e le

ve

l lim

it s

witch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

. T

his

an

aly

sis

wa

s

use

d b

y e

xida t

o c

alc

ula

te t

he

fa

ilure

ra

tes o

f th

e s

en

so

r e

lem

en

t u

sin

g d

iffe

ren

t fa

ilure

ra

te

da

tab

ase

s (

[N5

], [

N6

], [

N7

] a

nd

exi

da

‘s e

xp

eri

en

ce

d-b

ase

d d

ata

co

mp

ilatio

n)

for

the

diffe

ren

t co

mp

on

en

ts o

f th

e s

en

so

r e

lem

en

t (s

ee

[R

1])

. T

he

re

su

lts o

f th

e q

ua

ntita

tive

an

aly

sis

we

re u

se

d

for

the

ca

lcu

latio

ns d

escri

be

d in

se

ctio

n 5

.2.

Tab

le 1

Failu

re r

ate

s a

cco

rdin

g t

o IE

C 6

1508

sd

su

2

dd

du

SF

F

DC

S 3

D

CD 3

39

FIT

4

87

FIT

3

9 F

IT

58

FIT

9

0%

7

%

40

%

Tab

le 2

: S

um

mary

– P

FD

AV

G v

alu

es

T[P

roo

f] =

1 y

ea

r T

[Pro

of]

= 5

ye

ars

T

[Pro

of]

= 1

0 y

ea

rs

PF

DA

VG =

2,5

2E

-04

P

FD

AV

G =

1,2

6E

-03

P

FD

AV

G =

2,5

2E

-03

Th

e b

oxe

s m

ark

ed

in

g

ree

n (

)

me

an

th

at

the

ca

lcu

late

d P

FD

AV

G va

lue

s a

re w

ith

in th

e

allo

we

d r

an

ge

fo

r S

IL 2

acco

rdin

g t

o t

ab

le 2

of

IEC

61

50

8-1

an

d t

ab

le 3

.1 o

f A

NS

I/IS

A–

84

.01

–1

99

6 a

nd

do

fu

lfill

th

e r

eq

uir

em

en

t to

no

t cla

im m

ore

th

an

35

% o

f th

is r

an

ge

, i.e

. to

be

be

tte

r th

an

or

eq

ua

l to

3,5

0E

-03

.

Be

ca

use

th

e S

afe

Fa

ilure

Fra

ctio

n (

SF

F)

is a

bo

ve

90

% f

or

all

co

nsid

ere

d v

ers

ion

s,

als

o t

he

a

rch

ite

ctu

ral

co

nstr

ain

ts r

eq

uir

em

en

ts o

f ta

ble

3 o

f IE

C 6

15

08

-2 f

or

Typ

e B

su

bsyste

ms w

ith

a

Ha

rdw

are

Fa

ult T

ole

ran

ce

(H

FT

) o

f 0

are

fu

lfill

ed

.

1 T

yp

e B

co

mp

on

en

t:

“Co

mp

lex”

co

mp

on

en

t (u

sin

g m

icro

co

ntr

olle

rs o

r p

rog

ram

ma

ble

lo

gic

); fo

r d

eta

ils

see 7

.4.3

.1.3

of IE

C 6

1508-2

. 2 N

ote

th

at th

e S

U c

ate

go

ry in

clu

de

s fa

ilure

s th

at d

o n

ot ca

use

a s

pu

rio

us trip

3 D

C m

ea

ns th

e d

iag

no

stic c

ove

rag

e (

sa

fe o

r d

an

ge

rou

s).

The d

ocum

ent

was p

repare

d u

sin

g b

est

effort

. T

he a

uth

ors

make n

o w

arr

anty

of

any k

ind a

nd s

hall

not

be lia

ble

in

any e

vent

for

incid

enta

l or

consequential dam

ages in c

onnection w

ith t

he a

pplic

ation o

f th

e d

ocum

ent.

© A

ll rights

on t

he f

orm

at

of

this

technic

al re

port

reserv

ed.

Failu

re M

od

es, E

ffects

an

d D

iag

no

sti

c A

naly

sis

Pro

ject:

Le

ve

l lim

it s

witch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

A

pp

lica

tio

ns w

ith

le

ve

l lim

it d

ete

ctio

n in

so

lids (

MA

X d

ete

ctio

n)

Cu

sto

me

r:

En

dre

ss+

Ha

use

r G

mb

H+

Co

. K

G

Ma

ulb

urg

G

erm

an

y

Co

ntr

act

No

.: E

+H

03

/03

-22

R

ep

ort

No

.: E

+H

03

/03

-22

R0

30

Ve

rsio

n V

1,

Re

vis

ion

R1

.0,

Ju

ly 2

00

5

Ste

ph

an

Asch

en

bre

nn

er

Page 11: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

Endress + Hauser 11

L00-FEM52xxx-01-06-xx-en-003

© e

xida.c

om G

mbH

e+

h 0

3-0

3-2

2 r

030 v

1 r

1.0

.doc,

July

5,

2005

Ste

phan A

schenbre

nner

Page 3

of

3

Th

e f

ailu

re r

ate

s lis

ted

ab

ove

do

no

t in

clu

de

fa

ilure

s r

esu

ltin

g f

rom

in

co

rre

ct

use

of

the

le

ve

l lim

it

sw

itch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

, in

pa

rtic

ula

r h

um

idity e

nte

rin

g t

hro

ug

h

inco

mp

lete

ly c

lose

d h

ou

sin

gs o

r in

ad

eq

ua

te c

ab

le f

ee

din

g t

hro

ug

h t

he

in

lets

.

Th

e lis

ted

fa

ilure

ra

tes a

re va

lid fo

r o

pe

ratin

g str

ess co

nd

itio

ns ty

pic

al

of

an

in

du

str

ial

fie

ld

en

vir

on

me

nt

sim

ilar

to I

EC

60

65

4-1

cla

ss C

(sh

elte

red

lo

ca

tio

n)

with

an

ave

rag

e t

em

pe

ratu

re

ove

r a

lo

ng

pe

rio

d o

f tim

e o

f 4

0ºC

. F

or

a h

igh

er

ave

rag

e t

em

pe

ratu

re o

f 6

0°C

, th

e f

ailu

re r

ate

s

sh

ou

ld b

e m

ultip

lied

with

an

exp

eri

en

ce

ba

se

d f

acto

r o

f 2

,5.

A s

imila

r m

ultip

lier

sh

ou

ld b

e u

se

d

if f

req

ue

nt

tem

pe

ratu

re f

luctu

atio

n m

ust

be

assu

me

d.

A u

se

r o

f th

e le

ve

l lim

it s

witch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

ca

n u

tiliz

e t

he

se

fa

ilure

ra

tes

in

a

pro

ba

bili

stic

mo

de

l o

f a

sa

fety

in

str

um

en

ted

fu

nctio

n

(SIF

) to

d

ete

rmin

e

su

ita

bili

ty in

pa

rt f

or

sa

fety

in

str

um

en

ted

syste

m (

SIS

) u

sa

ge

in

a p

art

icu

lar

sa

fety

in

teg

rity

le

ve

l (S

IL).

A f

ull

tab

le o

f fa

ilure

ra

tes is p

rese

nte

d in

se

ctio

n 5

.2 a

lon

g w

ith

all

assu

mp

tio

ns.

It i

s i

mp

ort

an

t to

re

aliz

e t

ha

t th

e “

no

eff

ect”

fa

ilure

s a

nd

th

e “

an

nu

ncia

tio

n”

failu

res a

re in

clu

de

d

in t

he

“sa

fe u

nd

ete

cte

d”

failu

re c

ate

go

ry a

cco

rdin

g t

o I

EC

61

50

8.

No

te t

ha

t th

ese

fa

ilure

s o

n its

o

wn

w

ill n

ot

aff

ect

syste

m re

liab

ility

o

r sa

fety

, a

nd

sh

ou

ld n

ot

be

in

clu

de

d in

sp

uri

ou

s tr

ip

ca

lcu

latio

ns.

Th

e f

ailu

re r

ate

s a

re v

alid

fo

r th

e u

se

ful

life

of

the

le

ve

l lim

it s

witch

So

liph

an

t M

with

tra

nsis

tor

(PN

P)

ou

tpu

t F

EM

52

, w

hic

h is e

stim

ate

d t

o b

e b

etw

ee

n 8

an

d 1

2 y

ea

rs (

se

e A

pp

en

dix

3).

Page 12: Functional safety manual Soliphant M with electronic ...€¦ · Switch setting for the safety function: L00-FTM5xxxx-19-05-xx-xx-015 One switch for safety mode MAX Overfill protection

Soliphant M + FEM52

International Head Quarter

Endress+Hauser

GmbH+Co. KG

Instruments International

Colmarer Str. 6

79576 Weil am Rhein

Deutschland

Tel. +49 76 21 9 75 02

Fax +49 76 21 9 75 34 5

www.endress.com

[email protected]

SD204F/00/en/01.06 71020793FM+SGML 6.0 ProMoDo

7711002200779933