![Page 1: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/1.jpg)
Gas House
Safety
SATA 2009
![Page 2: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/2.jpg)
Gas House
Construction
1. 100 psf minimum or light weight vent design (NFPA 58 only)
2. Non combustible materials
a. Exception for relief panels, pneumatic tubing, etc
3. Openings to adjacent building protected by automatic closing door or damper – ducts, tunnels, doors
![Page 3: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/3.jpg)
Relief Panels
1. NFPA 58 - 1 square foot of panel per 50 cubic feet of room volume
2. NFPA 30B – 1 square foot of panel per 30 cubic of room volume
3. Relief panels must open at 20% of wall strength
eg: Walls 100psf – panels open 20psf
![Page 4: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/4.jpg)
Gas House
Location
1. 25 feet from tank farm
2. 15 feet from any ignition source
3. Exhaust vents should be at least
five feet from any opening into building*
* If adjacent building has tendency to hold vapors, duct fresh air inlets above roof
![Page 5: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/5.jpg)
Ventilation
1. NFPA 58 - 1 cfm per square foot of floor area.
2. NFPA 30 B – 1 air change per minute or CFM per formula
VR = (100 – LEL) (V)(R)
(DL)(LEL)
![Page 6: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/6.jpg)
Ventilation
Criteria
1. Type of filling equipment
a. TTV – low
b. UTC – potentially high
2. Anticipated product release
![Page 7: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/7.jpg)
![Page 8: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/8.jpg)
![Page 9: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/9.jpg)
Ventilation
Critical Checks
1. Air sweeps uniformly across floor
2. Gas House is negative to connecting room(s)
3.Establish schedule to replace air filters to maintain required air flow
4. Insure that high level is 1 ½ times minimum flow
![Page 10: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/10.jpg)
![Page 11: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/11.jpg)
GASSER ENCLOSURE
1. No Enclosure
2. Mesh Enclosure
3. Solid Enclosure
a. If used with Fenwal may require additional sensor and canister
![Page 12: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/12.jpg)
![Page 13: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/13.jpg)
![Page 14: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/14.jpg)
![Page 15: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/15.jpg)
Fenwal
1. Changes to system has added redundancy
2. Gas houses should be UV tight
a. Reflected light from tunnels
b. Walls/ceilings
c. Door openings
![Page 16: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/16.jpg)
Venting in Gas House
1. Venting into Gas House not allowed.*
*To safely vent, run tubing from vent valves into exhaust air duct.
![Page 17: Gas House Safety Point/Powerpoint pdfs... · 2015. 5. 28. · Gas House Location 1. 25 feet from tank farm 2. 15 feet from any ignition source 3. Exhaust vents should be at least](https://reader033.vdocument.in/reader033/viewer/2022060923/60af0aea0549fd5cf438c647/html5/thumbnails/17.jpg)
Expansion/Update
Checklist 1. Add DME as propellant, change electrical to
class C
2. Add additional gassers, may require increase in ventilation
3.Relief panels adequate for current requirements
4.Discharge from relief panels allow for safe venting
5.Disposal drum in or adjacent to gas house
6.Have added powder or other high static products
7.Grounding and bonding – replace polymer hoses with SS braid