Genset Controller, GC-1F
DATA SHEET
• Engine control
• Generator monitoring
• Generator protection (ANSI)
• Mains monitoring
• Mains protection (ANSI)
• Engine monitoring
• Display panel
Document no.: 4921240310I
-
8/15/2019 Gen Set Controller Gc 1f 2
2/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 2 of 13
This data sheet includes the following versions:
GC-1F SW version 1.2x.xGC-1F/2 SW version 2.0x.x or later
-
8/15/2019 Gen Set Controller Gc 1f 2
3/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 3 of 13
Appl icat ionThe Gen-set Controller GC-1F is a microprocessor-based control unit containing all necessary functions forprotection and control of a diesel engine. Furthermore,it contains a three-phase AC voltage measuring circuit.The unit is equipped with an LCD display presenting allvalues and alarms. GC-1F is a compact all-in-one unit
designed for the following applications:
1. Automatic engine start/stop2. Engine protection3. Breaker control4. Generator protection5. Automatic Mains Failure6. Automatic Transfer Switch control*
GC-1F automatically carries out a cyclical self test. Ifany errors are found, the status relay output willdeactivate (normally closed). In order to save batterypower, the display can be set to switch off automaticallyafter a given period of time. The display will turn on
again, if events or alarms take place, or if one of thepush-buttons is activated.
SetupSetup is easily done via a PC Windows
® based utility
software (password-protected). A PC interface box isneeded for this operation (option J5). Option J5 isoptional equipment for GC-1F. The PC utility softwareoffers additional features such as monitoring of allrelevant information during commissioning, saving and
downloading of settings and downloading of softwareupdates. Furthermore, the most frequently usedsettings can be accessed via the display push-buttons(password-protected).
LanguageMaster language is English and furthermore, there arethree selectable languages. These are listed in theorder specification.
Translat ionThis function makes it possible to change all texts usedin the unit.
Opt ionsThe options selected by the customer will be integratedin the standard GC-1F, hereby securing the same userinterface unaffected by whether the application needs abasic or a more complex gen-set controller.
Terminals
Terminal Technical data Description
1 Power supply + Aux. supply
2 Power supply – GND
3-4Status out/configurable. Contact ratings 1 A 24V DC/V AC Resistive
General status output for marine approvals/only configurable inhw 1.05 and sw 2x.x.
9 Common Common for term. 10…1510 Digital input Start enable/configurable
11 Digital input Remote start/stop/configurable
12 Digital input Charge alternator D+ (running)/configurable
13 Digital input Configurable
14 Digital input Coolant temperature/configurable
15 Digital input Oil pressure/configurable
19 Common Common for emergency stop term. 20
20 Emergency stop and common for 21…23 Common for relays 1, 2 and 3 and input for emergency stop*
21 Relay output 21. Start prepare/configurable. Function NO
22 Relay output 22. Starter (crank)/configurable. Function NO
23 Relay output 23. Run coil/configurable. Function NO
24-25 Relay output 24. Horn/configurable. Function NO
26-27 Relay output 26. Alarm/configurable. Function NO
Multi-functional inputs
5 Common Common for term. 6…8
6 VDO1/0(4)...20 mA/binary input Fuel level/configurable
7 VDO2/0(4)...20 mA/binary input Oil pressure/configurable
8 VDO3/0(4)...20 mA/binary input Water temp./configurable
Tacho RPM input
16 RPM input Magnetic pick-up/tacho generator
17 RPM-GND Common for RPM input
18 RPM input W Magnetic pick-up. PNP, NPN or charge alternator W terminal
* Only possible with HW 1.05 and SW 2.2x.x.
-
8/15/2019 Gen Set Controller Gc 1f 2
4/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 4 of 13
3-phase generator voltage input
33 Gen. voltage L1
Generator voltage and frequency
34 Gen. neutral
35 Not used, must not be connected
36 Gen. voltage L2
37 Not used, must not be connected
38 Gen. voltage L3
3-phase generator current input 39 Gen. current L1, s1
Generator current
40 Gen. current L1, s2
41 Gen. current L2, s1
42 Gen. current L2, s2
43 Gen. current L3, s1
44 Gen. current L3, s2
3-phase mains voltage inputs
28 Mains voltage L1
29 Mains voltage neutral
30 Mains voltage L2
31 Not used, must not be connected
32 Mains voltage L3
Breaker relays
45 Relay R45. Generator circuit breaker/configurable, function NO (normallyopen)
46 Relay R45
Optional relay for closing mains breaker (option B3)
47Relay R47.
Mains circuit breaker/configurable, function NC (normally closed).48 Relay R47
Optional relay NO contact (option M19)
47Relay R47. Contact ratings 2 A 30V DC/250V AC(UL/cUL Listed: Contact ratings 2 A 30V DC/30V AC) Mains circuit breaker/configurable, function NO (normally open)
48 Relay R47
Optional Modbus RS485 interface (option H2)
49 B (-)GND A (+)
Modbus RS485 RTU or ASCII50
51
Optional CANbus #1 engine interface53 CAN-H
CAN-GNDCAN-L
CAN J1939 engine communication54
55
Optional CANbus #2 AOP-2 interface (option X4)
57 CAN-HCAN-GNDCAN-L
CAN communication line to AOP-258
59
Optional CANbus #2 ext. I/O interface (option H8)
57 CAN-HCAN-GNDCAN-L
CAN communication line to external I/O58
59
-
8/15/2019 Gen Set Controller Gc 1f 2
5/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 5 of 13
Avai lable option s
Option Description Type Note
B Generator protection
B3 Automatic Mains Failure and ATS control- Generator and mains breaker control- Change-over (no synchronisation)
Hardware option ATS mode is only availablein HW 1.05 and SW 2.2x.x.Option B3 must also beset.
G Breaker
G6 Front layout with generator breaker Hardware option
H Communication
H2 Modbus RS485 RTU or ASCII Hardware option
H5 CANbus J1939 CANbus #1 comm.- Detroit Diesel- John Deere- Deutz- Volvo Penta EMS- Volvo Penta EMS 2- Scania EMS- Scania EMS 2- MTU MDEC 302
- MTU MDEC 303- MTU ADEC- Cummins- Iveco- Perkins- Caterpillar
Hardware option
H8 External I/O CANbus #2 comm. Hardware option See supported modules inoption H8 documentation
J Cables
J5 PI-1 converter box kit (for PC connection) Hardware option
K Documentation
K1 Installation Instructions and Reference Handbook (hard copy) Other
K2 CD-ROM with complete documentation Other
L Gasket for IP65 Hardware option
L2 Heatfoil for display (display will operate down to -40°C) Hardware option Only HW 1.05 and ASW2.0x.x
M
M19 Mains circuit breaker/configurable, contact function NO (normallyopen)
Hardware option Only HW 1.05 and ASW2.2x.x
X Display
X4 Additional operator panel (AOP-2): 16 configurable LEDs, 8 con-figurable buttons and 1 status relay. CANbus #2 comm.
Hardware option Maximum of 2 AOP2s
Folio
Y2 Engine folio without generator symbol, generator and mains breaker Hardware option
Y10 Source – source folio with breaker symbols Hardware option Only HW 1.05 and ASW2.2x.x
-
8/15/2019 Gen Set Controller Gc 1f 2
6/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 6 of 13
Option B3 display layout
Optio n Y10 Source – Sourc e display layo ut
AUT TEST
ESC
-
8/15/2019 Gen Set Controller Gc 1f 2
7/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 7 of 13
Wiring, engin e interface
F: Fuse: Min. 2 A slow-blow.
It is possible to combine VDO inputs with binary and 0(4)…20 mA inputs in a mix.
-
8/15/2019 Gen Set Controller Gc 1f 2
8/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 8 of 13
Wiring, AC interface
Connection of the 3-phase voltage and current
The AC current grounding can be made as required to s1 or s2.
GB: Use a contactor. The ON output from the GC-1F is a constant signal. Remember to use free-wheeldiodes across the contactor coils, if DC voltage is used as supply for these.
Fuse for AC voltage: Max. 2 A slow-blow.
S2
S1
N L1
U L133
36 U L2
40 L1 s2
39 L1 s1
Generator
voltages
current
Generator
N L1
14 GB OFF feedback
Supply
Generator
GC-1F
GB ON command45
46
CONSUMER
GB
U L338
34 Neutral
L2
L2 L3
L3
L2 s141
L2 s242
S1
S2
S2 44 L3 s2
S1 43 L3 s1
-
8/15/2019 Gen Set Controller Gc 1f 2
9/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 9 of 13
Wiring, AMF (option B3)
The AC current grounding can be made as required to s1 or s2.
GB and MB: Use contactors. The ON outputs from the GC-1F AMF are constant signals. Remember touse free-wheel diodes across the contactor coils, if DC voltage is used as supply for these.
Fuse for AC voltage: Max. 2 A slow-blow.
14 GB OFF feedback
46
45GB ON command
Supply
GC-1F AMF
MB ON command47
48
MB OFF feedback
Consumers
U L230 voltages
MainsNeutral29
28 U L1L2
L2
MAINS
Generator
L1N
L1N
MB
15
GB
U L133
36 U L2Generator
voltage34 Neutral
S2
S1
42 L2 s2
41 L2 s1
Generator
current
L1 s139
L1 s240
S1
S2
L3
L3
U L332
38 U L3
S2
S1
44 L3 s2
43 L3 s1
-
8/15/2019 Gen Set Controller Gc 1f 2
10/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 10 of 13
The GC-1F can operate ATS switches in Gen – Mains and Source – Source applications.
Relay outputs can be configured for pulse or continues signals for 2 or 3 position ATS. Detailedinformation about different variants can be found in the option B3 manual.
-
8/15/2019 Gen Set Controller Gc 1f 2
11/13
Data sheet Gen-set Cont ro l ler GC-1F
DEIF A/S Page 11 of 13
Technical specif icat ions
Accuracy: Class 2.0To EN 60688
Operating temp.: -20…70°C (-4…158°F)-40…70°C (-40…158°F)
with option L2
(UL/cUL Listed: Max. 50°C ambient)
Storage temp.: -40…70°C (-40…158°F)
Heatfoil Display will operate(option L2): down to -40°C
Measuring inputvoltage: 50…480V AC (+20%)
Phase-to-phase
Short-circuit 3% of 350%*In (only available
protection: from HW 1.05 and 2.0x.x)
(UL/cUL Listed: 50…300V AC)
Load: 1.5 MΩ/phase
Frequency: 30…70 Hz
Measuring inputcurrent: 1 A or 5A AC from current
transformer
Current overload: 4 x In continuously20 x In, 10 sec. (max. 75 A)
80 x In, 1 sec. (max. 300 A)
Consumpt. max.: 0.3 VA/phase
(UL/cUL Listed: Use listed or R/C (XODW2.8)current transformers)
Pick-up inputvoltage: 2…70 V peak
Frequency: 10-10000 Hz
Aux. supply: 6-36V DC continuouslyMax. 8 W consumptionIncluding L2 heatfoil, max. 16 W
(UL/cUL Listed: 7.5…32.7V DC)
Passive binaryinput voltage: Bi-directional optocoupler
6…36V DC
Impedance: 4.7 kΩ
Dropout cranking: Able to survive 0 V for 50 ms at12V DC aux. supply before dropout
VDO inputs: Resistor inputs, internal 3 V supply
Analogue input: From active transducer
Current: (0)4…20 mA
Impedance: 50 Ω
Active binaryinput voltage: Dry contact inputs (see note)
3V DC supply, with cablesupervision
Relay outputs:
Impedance: 240 Ω ~ 16 mA
Relays 21-23: 30V AC/DC 2 A(UL/cUL Listed: 30V DC 1 A Resistive)
Relays 45, 47: 250V AC/30V DC 2 A(UL/cUL Listed: 30V DC 2 A Resistive)
Relays 24, 26: 30V AC/DC 8 A(UL/cUL Listed: 30V DC 6 A Resistive)
Status relay/config.: 24V DC 1 A Resistive
Response times:(Delay set to min.) Generator:
Reverse power < 400 msPower/overload < 400 msOvercurrent < 400 msOver-/undervoltage < 400 msOver-/underfrequency < 400 msFast overcurrent < 300 ms
Mounting: Panel-mounted
(UL/cUL Listed: For use on a flat surface of a type 1enclosure.Main disconnect shall be providedby installer)
Size: 160 x 220 mm (6.30” x 8.66”)
Climate: 97% RH to IEC 60068-2-30, test Db-20°C (-40°) to IEC 60068-2-1+70°C to IEC 60068-2-2
Display: 128 x 64 pixel backlight STN3 line views can max. show a valueof 9999
Safety: To EN 61010-1, UL508 andCSA22.2 No. 14-05Installation category (overvoltagecategory) III, 300V, pollution degree2
Protection: Front: IP52/NEMA type 1(IP65/NEMA type 1 with gasket,option L) Terminals: IP20/NEMA type 1To IEC/EN 60529
-
8/15/2019 Gen Set Controller Gc 1f 2
12/13
Data sheet Gen-set Con tro l ler GC-1F
DEIF A/S Page 12 of 13
EMC/CE: To EN 61000-6-1/2/3/4IEC 60255-22-1/EN 61000-4-18(PL3), IEC 60255-26
Material: All plastic materials are self-extinguishing acc. to UL94 (V1)
Plugconnections: AC voltage/current inputs:
3.5 mm2 (13 AWG) multi-strandedOther:1.5 mm2 (16 AWG) multi-stranded
(UL/cUL Listed: Wire size: AWG 30-12Use 60/75°C copper conductorsonly)
Tightening torque,min.: AC voltage input: 0.5Nm (5-7lb-in)
Other: 0.5Nm (5-7lb-in)
PC connection: RS232 converter box (option J5)
Weight: Approx. 0.9 kg (1.9lbs)
Installation: To be installed in acc. with theNEC (US) or the CEC (Canada)
Approval: CE & UL/cUL Listed
Add it ional operator panel AOP-2
Operating temp.: -20…70°C (-4…158°F)
(UL/cUL Listed: Max. 60°C ambient)
Storage temp.: -40…70°C (-40…158°F)
Aux. supply: 18…36V DC by external DC/DCconverter 12DCR24/5 suppliedfrom controlled Class 2 source
Terminals: Tightening torque: 0.4Nm (4lb-in)
Wiring: Size AWG 30-12Use 60/75°C copper conductorsonly
Mounting: Panel-mounted
(UL/cUL Listed: For use on a flat surface of type 1(IP54) enclosureMain disconnect must be providedby installer)
Installation:
(UL/cUL Listed: To be installed in acc. with theNEC (US) or the CEC (Canada)
Approval: CE & UL/cUL Listed
-
8/15/2019 Gen Set Controller Gc 1f 2
13/13
Data sheet Gen-set Con tro l ler GC-1F
DEIF A/S
Uni t dimensions in mm (inches)
AUT TEST
ESC
1 5 1 .
0 0
211.0
5 4 . 0
6 1 .
0
1 6 0 .
0
220.0
Order specif icat ions