1 GHANA BUILDING CODE PART 3 – USE AND OCCUPANCY TABLE OF CONTENTS 3.1 GENERAL 3 3.1.1 Scope 3 3.1.2 Definitions 3 3.2 CLASSIFICATION OF BUILDINGS OR PARTS OF BUILDINGS BY MAJOR OCCUPANCY 6 3.2.2 Building Size Determination 10 3.2.3 Provision of Compartment Walls and Compartment Floors 11 3.2.4 Fire Resistance of Elements of Structure 13 3.2.5 Fire Resistance of Floors in Conjunction with Suspended Ceilings 41 3.2.6 External Walls 42 3.2.7 Calculation of Permitted Limits of Unprotected Areas 43 3.2.8 Rules for Calculation by Reference to an Enclosing Rectangle 44 3.2.9 Separating Walls 57 3.2.10 Compartment Walls and Compartment Floors 60 3.2.11 Protection of Openings in Separating Walls, Compartment Walls and Compartment Floors 61 3.2.12 Fire Stopping 71 3.2.13 Restriction of Spread of Flame Over Surface of Walls and Ceilings 73 3.2.14 Roof Covering 76 3.2.15 Small Garages and Small Open Carports 81 3.2.16 Occupant Load 84

Upload: vasvuk

Post on 06-Feb-2016

675 views

Category:

Documents


127 download

TRANSCRIPT

Page 1: GHANA BUILDING CODE - PART 03.pdf

1  

          GHANA BUILDING CODE           PART 3 – USE AND OCCUPANCY              TABLE OF CONTENTS               3.1   GENERAL                                                                                                                    3 

 3.1.1  Scope      …      …        3 

 3.1.2 Definitions    …      …        3 

               3.2  CLASSIFICATION OF BUILDINGS OR PARTS OF BUILDINGS 

              BY MAJOR OCCUPANCY                                                                       6  

3.2.2  Building Size Determination       …        10  3.2.3  Provision of Compartment Walls and Compartment Floors      11  3.2.4  Fire Resistance of Elements of Structure   …        13  3.2.5 Fire Resistance of Floors in Conjunction with Suspended Ceilings     41 

               3.2.6      External Walls      …    …        42 

 3.2.7     Calculation of Permitted Limits of Unprotected Areas        43  3.2.8     Rules for Calculation by Reference to an Enclosing Rectangle      44 

 3.2.9  Separating Walls    …    …        57 

 3.2.10 Compartment Walls and Compartment Floors  …        60 

                3.2.11   Protection of Openings in Separating Walls, Compartment Walls  

and  Compartment  Floors      …        61  

3.2.12  Fire Stopping           …        71  3.2.13   Restriction of Spread of Flame Over Surface of Walls and Ceilings    73  3.2.14  Roof Covering          …        76  3.2.15  Small Garages and Small Open Carports    …        81  3.2.16  Occupant Load    …      …        84 

  

Page 2: GHANA BUILDING CODE - PART 03.pdf

2  

3.3  SAFETY REQUIREMENTS WITHIN FLOOR AREAS                                               86  3.3.1    Requirements Applying to all Floor Areas    …    86 

 3.3.2    Residential Occupancy    …      …    91  3.3.3    Institutional Occupancy   …      …    93  3.3.4    Business and Personal Services Occupancy    …    94  3.3.5    Mercantile occupancy    …      …    95  3.3.6    Industrial Occupancy    …      …    96 

                              3.3.7                    Assembly Occupancy                    …                   …                         98 

  

3.4  REQUIREMENTS FOR EXITS                                                                                   105  3.4.1    General Requirements    …      …    105  3.4.2    Number and Location of Exits from Floor Areas  …      106  3.4.3    Width and Height of Exits  …      …    109  3.4.4    Flame Spread Rating for Exits        …    112  3.4.5    Required Fire Separation for Exits       …    112  3.4.6    Exit Signs      …      …    114  3.4.7    Lighting for Exits    …      …    115  3.4.8    Types of Exit Facility    …      …    115 

  

3.5  HEALTH REQUIREMENTS                                                                                        121  3.5.1    Height and Area of Rooms  …      …    121  3.5.2    Windows      …      …    121  3.5.3    Ventilation       …      …    121  3.5.4    Plumbing Facilities    …      …    122 

              APPENDIX 1   REFERRED STANDARDS                                                                                        126 

Page 3: GHANA BUILDING CODE - PART 03.pdf

3  

PART 3 – USE AND OCCUPANCY  3.1  GENERAL 3.1.1 Scope: This part covers the requirements of fire protection of buildings and the health 

of the building environment, through the classification of buildings based on occupancy, type of construction, and their requirements. 

  3.1.1(1) This  part applies to all buildings of more than two storeys or whose total floor area exceeds          220m2.          (2) For buildings not listed in 3.1.1(1), requirements relating to use and occupancy will be found          in Part 7 of the Code.  3.1.2 Definitions 3.1.2.1           For the purpose of this part, the following definitions shall apply; and  in the case of storey levels, refer to the British system: 

 basement storey  ‐   means a storey which  is below the ground storey; or,  if there  is no ground storey, means a storey, the floor of which is situated at such a level or levels that some point on its perimeter is more  than  1.2m  below  the  level  of  the  finished  surface  of  the  ground  adjoining  the  building  in  the vicinity of that point. Fig. 3.1.2.1A  compartment  ‐   means any part of a building which  is separated  from all other parts by one or more compartment floors or by both such walls and floors and for the purposes of this part, if any part of the top  storey of a building  is within a  compartment,  the  compartment  shall also  include any  roof  space above such part of the top storey. Fig. 3.1.2.1B  compartment wall and compartment floor ‐  mean respectively, a wall and a floor which complies with sub‐section 3.2.8 and which is provided for the purposes of subsection 3.2.3 or to divide a building into compartments for any purpose in connection with subsection 3.2.4, 3.2.5 or 3.2.6.  door  ‐    includes any shutter, cover or other form of protection to an opening  in any wall or floor of a building, or  in the structure surrounding a protected shaft, whether the door  is constructed of one or more leaves.  element of structure  means – 

(a) any member  forming  part  of  the  structural  frame  of  a  building  or  any  other beam or column (not being member forming part of a roof structure only). 

(b) a floor, including a compartment floor, other than the lowest floor of a building. 

(c) an external wall 

(d) a separating wall 

(e) a compartment wall 

(f) structure enclosing a protected shaft 

(g) a load bearing wall 

Page 4: GHANA BUILDING CODE - PART 03.pdf

4  

(h) a gallery.  Fig. 3.1.2.1C externally non‐combustible  ‐   means externally  faced with, or otherwise externally consisting of non‐combustible materials.  fire stop ‐  means a barrier or seal which would prevent or retard the passage of smoke or flame within a cavity or around a pipe or duct where it passes through a wall or floor or at a junction between elements of structure.  ground storey  ‐   means a storey  the  floor of which  is situated at such a  level or  levels  that any given point on its perimeter is at or about, or not more than 1.2m below, the level of the finished surface of the g round adjoining the building in the vicinity of that point; or, if there are two or more such storeys, means the higher or highest of these. Fig. 3.1.2.1E 

 height of building ‐  has the meaning ascribed to it in subsection 3.2.2. 

 open carpot ‐  means a carpot of not more than one storey, which is open on two or more of its sides; and for the purpose of this definition a side which includes or consists of a door shall not for that reason be regarded as an open side. 

 permitted limit of unprotected areas ‐  means the maximum aggregate area of unprotected areas in any side or external wall of a building or compartment, calculated as prescribed in subsection 3.1.7.7. 

  

protected shaft  ‐   means a stairway,  lift, escalator, chute, duct or other shaft which enables persons, things or air to pass between different compartments and complies with subsection 3.1.10. 

 relevant boundary ‐  in relation to a side or external wall of a building or compartment, means that part of the boundary of the premises or of the notional boundary which is adjacent to that side or wall and either coincides with is parallel to or is at an angel of not more than 180o with that side or wall. Fig. 3.1.2.1D 

 separating wall ‐  means a wall or part of a wall which is common to two adjoining buildings.  unprotected area ‐  in relation to an external wall or side, of a building means – 

 (a) a window, door or other opening 

 (b) any part of the external wall which has fire resistance  less than that specified by this part 

for        that wall, and  

(c) any  part  of  the  external  wall  which  has  combustible  material  more  than  1  mm  thick            attached or applied to its external face, whether for cladding or any other purposes. 

 

Page 5: GHANA BUILDING CODE - PART 03.pdf

5  

 

Page 6: GHANA BUILDING CODE - PART 03.pdf

6  

(2) Any reference  in this part to a building shall,  in any case where two or more houses adjoin, he construed as reference to one of those houses. 

 (3) If any part of a building other than a single storey building – 

 (a) consists of ground storey only 

 (b) has  a  roof  to which  there  is  only  such  access  as may  be  necessary  for  the  purposes  of 

maintenance or repair; and  

(c) compartment wall or compartment walls  in the same continuous vertical plane, that part may be treated, for the purposes of this part, as a part of a single storey building.  Fig. 3.1.2.1F 

 (4) Any  reference  in  this  part  to  a  roof  of  a  specified  designation  shall  be  construed  as  a 

requirement that the roof or part of the roof shall be so constructed to the same specification, if exposed to test by fire in accordance with BS 476: Part 3: 1958, would comply with the relevant test criteria specified in relation to that designation. 

 Any roof or part of a roof shall be deemed to be of the specified designation if it conforms with   

  one of the specifications set out against that designation in Table 3.1.10.7B.   3.2 CLASSIFICATION OF BUILDING OR PARTS OF BUILDINGS BY MAJOR OCCUPANCY  3.2.1  (1)  Every building or part thereof, whether existing or hereafter erected, shall be classified 

  by  the  authority  having  jurisdiction,  as  belonging  to  one  of  the  following  groups   according  to  the  use  or  its  major  character  of  occupancy  and  as  described  and   exemplified in   Table 3.2.1A 

 (2)  The purpose of classification is to determine which requirements apply.  This part of the 

code  requires  classification  in  accordance  with  very major  occupancy  for  which  the building is used or intended to be used.  This gives the authority having jurisdiction the right to enforce regulations for every such occupancy. 

 (3)  Except as provided  in 3.2.1  (4) when a building  is divided  into compartments used or 

intended  to  be  used  for  more  than  one  major  occupancy,  the  occupancy  of  each compartment shall be determined separately. 

(4)             Where the whole or part of a building or compartment (as the case may be)  is used or    intended  to be used  for more  than one major occupancy only  the main occupancy of   that  building  or  compartment  shall  be  taken  into  account  in  determining  which   occupancy group it falls.       

Page 7: GHANA BUILDING CODE - PART 03.pdf

7  

Table 3.2.1A Forming part of Article 3.2.1 (1) 

 CLASSIFICATION BY GROUP OF TYPICAL OCCUPANCIES 

Group  Description Occupancies 

 Examples 

 

 

Residential  occupancies  used  for sleeping  accommodation  is  provided for normal residential purposes, with or without  cooking  or  dining  or  both facilities,  excluding  those  covered  in Group C occupancies, including: 

Apartments(flats) Boarding Houses Clubs, residential Convents Dormitories 1 or 2‐family private houses 

Hotels Lodging Monastries Motels   

  E 

 Educational  occupancies  where building  is  used  for  school,  college  or day‐care  purposes  involving  assembly for  instruction, education or recreation and which  is  not  covered  by Group  F, including:  

 Schools(residential) Colleges(residential)      

        

 Institutional occupancies in which: (i)  persons  are  detained  for  penal  or correctional  purposes,  or  for involuntary  detention,  or  whose liberties are restricted, including:    (ii)  persons  because  of  age, mental  or physical limitations require special care or treatment, including: 

 Jails Penitentiaries Police stations (1)      Minors correctional     centres (3) Convalescent homes (3) Hospitals  Infirmaries 

 Prisons  Psychiatric hospitals (1)  Reformatories(1)      Orphanages Psychiatric hospitals (2) Reformatories Sanitoria (2) 

Page 8: GHANA BUILDING CODE - PART 03.pdf

8  

 Business  and  personal  services occupancies  for  conducting  business and  rendering  professional  and personal services including: 

 Banks Barber  and  hair  dressing shops Beauty parlours Dental offices Dry cleaning,    self‐service    not employing    flammable or explosive     solvents or cleaners Fire stations 

Laundry   self‐service  Medical offices Offices Police station (2) Radio stations Small   tool     and  appliance   rental and    service Telephone    exchanges 

M   

Mercantile  occupancies  for displaying, or  selling  of  retail  goods  wares,  or merchandise, either wholesale or retail, including: 

Department  stores Exhibition halls Markets(area up to 500m2)  

 Shops Stores Supermarkets(with  area more than 500m2) Underground  shopping centres 

        F 

Factory  occupancies  in which  persons are  employed  in  any  process  for  or incidental to:  (a) making of any article or part of any article or  (b)  altering,  repairing  ornamenting, finishing,  cleaning  or  washing  or breaking up or demolition of any article  (c)  the adapting  for sale of any article, including:    

Factories Laboratories Power plants Assembly plants Dry cleaning plants Pumping stations Laundries Gas plants Refineries Saw‐mills  

           

 

    A 

 Assembly  occupancies  used  for  the attendance  of  persons  for  or  in connection  with  social,  amusement, recreational,  religious,  patriotic,  civil, travel,  educational,  business  or  other activities  and  not  comprised  within groups A to F including: 

Motion picture houses Theatres Places of worship Court rooms Dance halls Exhibition hall Arenas Reviewing stands Stadia Grand stands Passenger stations and terminals of air,  surface and marine  public transportation services 

           

Television studios    admitting  a  viewing   audience Lecture halls Lodge rooms Museums Libraries Gymnasia 

Page 9: GHANA BUILDING CODE - PART 03.pdf

9  

S  General Storage buildings or part of a building used primarily for;  

(i) the  storage  or  sheltering  of goods,  wares,  merchandise (except  those  that  involve highly combustible or explosive products or materials), vehicles or animals, including:(4)  

 

 

    Warehouses Cold Storage Freight depots Transit sheds Storehouses Grain elevators Barns Stables  

             

    Printing plants Truck  and  Marine  terminals Garages Hangers  (other  than aircraft repair hangers)    

H   High‐Hazard  Storage Buildings or part of a building used primarily for: 

 (ii) the storage, handling,     manufacture  or  processing  of   highly combustible or explosive   materials or products which are   liable  to  burn  with  extreme   rapidity  and/or  which  may   produce  poisonous  fumes  or   explosions;  for  storage,   handling,  manufacture  or   processing which involve highly   corrosive,  toxic  or  noxious   alkalis, acids or other  liquids or   chemicals  producing  flame,   fumes  and  explosive,   poisonous,  irritant or  corrosive   gases;  and  for  the  storage,   handling  or  processing  of  any   material  producing  explosive   mixtures  of  dust  which  will   result  in  the division of matter   into  fine  particles  subject  to   spontaneous  ignition,   including:  

                    Bulk plants for flammable    liquids Aircraft repair hangers Box factories Distilleries Rubber processing plants Manufacture of artificial     flowers,  synthetic leather,     ammunition, explosives      and fireworks.   

    

           

    Storage under pressure     of more than      0.1N/mm2 and in     quantities exceeding      70m3, of acetylene,     hydrogen,     illuminating and     natural gases,     ammonia, chlorine,     phosgene,  sulphur     dioxide, carbon     dioxide, methyloxide     and all gases subject      to explosion, fume or    toxic hazard,     cryogenic gases, etc. 

Page 10: GHANA BUILDING CODE - PART 03.pdf

10  

U  Utility and Miscellaneous  Includes  the  following  types  of buildings and structures: 

‐ Accessory building ‐ Miscellaneous  buildings  not 

classified in another category ‐ Aircraft  hangers  where 

accessory  is  to  a  1  or  2‐family residence 

‐ Grain  silos  where  accessory  is to a building in Occupancy class R 

Building types include:  

  Agricultural building Carports Fences(> 1.8m high) Greenhouses Livestock shelters Private garages Sheds Tanks Towers 

           

 

 Col.1 

 2 

 3 

  

 4 

 Notes to Table 3.1.2A 

(1) With detention quarters 

(2) Without detention quarters 

(3) Where the occupants are ambulatory and live as a single housekeeping unit in a dwelling unit with sleeping accommodation for not more than 10 people, the occupancy may be considered to be Group R 

(4) Storage properties are characterized by the presence of relatively small number of persons in proportion to the area. Any new use which increases the number of occupants to a figure comparable with other classes of occupancy shall change the classification of the building to that of the new use, for example, hangars used for assembly purposes, warehouses used for office purposes, garage buildings used for manufacturing. 

(5) Buildings not listed in one of the occupancy categories by the Code are to be assigned to the category with the most similar fire and other hazards. 

(6) A space with changeable occupancies must comply with the rules of all occupancies involved. (7) Buildings with more than one occupancy  must comply with mixed occupancy requirements. 

    

3.2.2 Building size determination  3.2.2 (1) In this part:  

(a) The height of a building, or  (where  relevant) of part of a building, means  the height of  such building or part, measured from mean level of the ground adjoining the outside of the external walls of the building to the level of half the vertical height of the roof of the building or part or top of the walls or of the parapet (if any) whichever is the higher. 

             Fig. 3.2.2A (b) (i) the area of any storey of a building or compartment shall be taken to be the total area of that 

storey bounded by the inner finished surfaces of enclosing walls or, on any side where there is no enclosing wall by the outermost edge of the floor on that side; 

 (ii) the area of any room or garage shall be taken to be the total area of its floor bounded by the        inner finished surfaces of the walls forming the room or garage. 

 

Page 11: GHANA BUILDING CODE - PART 03.pdf

11  

(iii)  the  area  of  any  part  of  a  roof  shall  be  taken  to  be  the  actual  visible  area  of  such  part  measured on a plane parallel to the pitch of the roof. Fig. 3.2.2B 

 (c) the cubic capacity of a building or compartment shall be ascertained by measuring the volume 

of space contained within –  

(i) the inner finished surfaces of the enclosing walls or, on any side where there is no enclosing wall, a plane extending vertically above the outermost edge of the floor on that side and 

              (ii) the upper surface of its lowest floor and 

 (iii) in the case of a building or of a compartment which extends to the roof the under surface of the roof or, in the case of any other compartment, the under surface of the ceiling of the highest storey within that compartment  including the space occupied by any other walls or any shafts, ducts or structure within the space to be measured.      Fig. 3.2.2C, Fig. 3.2.2D  

 3.2.3 Provision of Compartment Walls and Compartment Floors  3.2.3(1) Except as provided in 3.2.3(2) any building of an occupancy group specified in column (1) of                Table 3.2.3A which has:  

(a) any storey or floor area which exceeds that specified as relevant to a building of that occupancy  group  and  height  in  column  (3)  of  the  Table;  or  (b)  a  cubic  capacity  which exceeds  that  specified  in  column  (4) of  the  Table  shall be divided  into  compartments by means of a compartment walls or compartment floors or both so that; 

 (i) no such compartment has any storey the floor area of which exceeds the area 

specified as relevant to the building in column (3) of the Table; and  (ii) no  such  compartment  has  a  cubic  capacity  which  exceeds  that  specified  as 

relevant in column (4) of the Table.  3.2.3(2)  For  any building of occupancy  group D  fitted  throughout with  an  automatic  sprinkler 

system, the limits of dimensions specified in columns (3) and (4) of Table 3.2.3A shall be doubled. 

 

Page 12: GHANA BUILDING CODE - PART 03.pdf

12  

 

Page 13: GHANA BUILDING CODE - PART 03.pdf

13  

3.2.3(3) In any building which exceeds 28m in height, any floor which separates one storey from another               other than a floor which is                 (a) within a maisonette; or  

(b) above the ground storey but at a height not exceeding 9m above the adjoining ground shall       be constructed as a compartment floor.    Fig. 3.2.3A  

3.2.3(4) The following walls and floors shall be constructed as compartment walls or compartment               floors:‐               (a) any floor in a building of occupancy Group B; 

              (b) any wall or floor separating a flat or maisonette from any other part of the same building;                     Fig. 3.2.3B 

 (c) any wall or floor separating part of a building from any other part of the same building which  is used or  intended  to be used mainly  for an occupancy  falling within a different occupancy group in Table 3.2.3A; and 

              (d) any floor immediately over a basement storey if such a storey   

(i) forms part of a building of occupancy Group A which has three or more storeys or a                         building or compartment of occupancy group D; and (ii) has an area exceeding 100m2.  3.2.4 Fire resistance of elements of structure  3.2.4 (1)  In this sub‐section and Table 3.2.4A:  

(a) any reference to a building of which an element of structure forms part means the building or  (if a building  is divided  into  compartments) any  compartment of  the building of which   the element forms part; and 

 (b) reference to height means the height of a building not of any compartment in the building, 

but  if  any  compartment  is  completely  separated,  throughout  its  height  both  above  and below ground from all other parts by a compartment wall or compartment walls in the same continuous vertical plane, any reference to height in relation to that part means the height solely of that part.  Fig. 3.2.4A 

 3.2.4(2) Subject to the provisions of 3.2.4 (3), 3.2.4 (4) and 3.2.5 every element of structure shall have  

fire resistance of not less than the relevant period set out in Table 3.2.4A provided that:                (a) any external wall shall not have a fire resistance of less than one hour; 

               (b) any separating wall shall not have a fire resistance of less than one hour; 

 (c) any  compartment wall or  compartment  floor which  separates  a part of  a building  falling 

within  occupancy  group  other  than  occupancy  groups  R  ,  E  and  B  shall  not  have  a  fire resistance of less than one hour; 

Page 14: GHANA BUILDING CODE - PART 03.pdf

14  

 (d) any relevant of structure which forms part of more than one building or compartment shall 

be so constructed as  to comply with  the greater or greatest of  the  relevant  requirements specified in Table 3.2.4A; and 

 (e) any  relevant  of  structure  shall  not  have  fire  resistance  of  less  than  the minimum  period 

required by these provisions of the code for any element which it carries.  

Page 15: GHANA BUILDING CODE - PART 03.pdf

15  

   

 

Page 16: GHANA BUILDING CODE - PART 03.pdf

16  

Table 3.2.3A   (Dimensions of buildings and Compartments) 

Fig. 3.2.3C  

 Occupancy 

 Height of building 

 Limits of dimensions 

     

(1) 

    

(2) 

Floor area of storey building or 

compartment (in m2)  

(3) 

Cubic  capacity  of building  or compartment (in m3)  

(4)  

Part I – Buildings other than single storey buildings   

R  (Residential) 

Not exceeding 28m 

Exceeding 28m 

3000 

2000 

8500 

5500 

E and I 

(Educational/Institutional) 

Any height  2000  No limit 

B and M 

  (Business/Mercantile) 

Any height  2000  7000 

 F  (Industrial)  

Not exceeding 28m  Exceeding 28m 

No limit  

2000 

28000  

5500  S,H(General  and Hazardous Storage)   

Not exceeding 28m  Exceeding 28m 

No limit  

1000 

21000  

No limit 

 Part 2 – Single storey buildings 

 

R (Residential) 

E and I (Educational/ 

           Institutional) 

Any height 

 

Any height 

3000 

 

3000 

No limit 

 

No limit 

       

Page 17: GHANA BUILDING CODE - PART 03.pdf

17  

  3.2.4 (3)  Any compartment wall separating a flat or maisonette from any other part of the same 

building shall not be required to have fire resistance exceeding one hour unless –  

(a) The wall is a load bearing wall or a wall forming part of a protected shaft; or  

(b) The part of the building from which the wall separates the flat or maisonette is of a different purpose group and the minimum period of fire resistance required by the provisions of the subsection 3.2.4 for any element of structure  in that part  is one‐and‐a‐half hours or more.  

3.2.4 (4)  Provisions of 3.2.4 (2) shall not apply to –  

(a) Any part of an external wall which is non‐load bearing and which in accordance with subsection 3.2.6 may be considered an unprotected area; or  

(b) In the case of a single storey building or a building consisting of a ground storey and one or more basement  storeys, any element of  structure which  forms part of  the ground storey and consists of – 

 (i)   part  of  an  external  wall  which  does  not  support  a  gallery  and  which  may  in 

accordance with subsection 3.2.6 be an unprotected area; or  (iii) a  structural  frame  or  a  beam  or  column;  provided  that  any  beam  or  column 

which gives support to a wall or gallery shall have a fire resistance not less than the minimum period required by provisions of this code; or  

Page 18: GHANA BUILDING CODE - PART 03.pdf

18  

(iv) An internal load bearing wall or a load bearing part of a wall unless that wall or part is, or forms part of a compartment wall or a separating wall, or forms part of the structure enclosing a protected shaft or supports a gallery. 

  

Table 3.2.4A Minimum Periods of Fire Resistance 

Part 1:  Buildings Other than Single Storey Buildings  

  

Occupancy group    

(1) 

Maximum dimensions 

Minimum period of fire resistance (in hours) for 

elements of structure forming part of ‐ 

Height(in m) (2) 

Floor area(in m2) (3) 

Cubic capacity(in m3) (4) 

Ground storey upper storey 

(5) 

Basement storey (6) 

 

R  (Residential) 

Building having not more than two storeys 

No Limit  500  No Limit  ½  1  x 

Building having three storeys  No Limit 250 No Limit 1 (a)  1Building having any  number of storeys  28  3000  8500  1  1 ½ 

Building having any number of storeys  

No Limit  2000  5500  1 ½  2 

E and I (Educational/Institutional)   

28  

Over 28 

2000  

2000 

No Limit 

No Limit  

1  

1 ½ 

1 ½  2 

B   (Business and       Personal Service)  

7.5 7.5 15 28 

No Limit 

250500 

No limit 5000 

No Limit 

No LimitNo Limit 3500 1400 

No Limit 

 ½ 

1 (a) 1 1 ½ 

1 (b)  x1 1 1 ½ 2 

M(Mercantile) 

7.5 7.5 15 28 

No Limit 

150500 

No limit 1000 2000 

No LimitNo Limit 3500 7000 7000 

0 ½ 

1 (a) 1 2 

1 (b)1 1 2 

4 (y)   F (Industrial) 

7.5 7.5 15 28 28 

Over 28 

250No limit No limit No limit No Limit 2000 

No Limit1700 4250 8500 28000 5500 

0 ½ 

1 (a) 1 2 2 

1 (b)  1 1 2 4 4 

   

 

Page 19: GHANA BUILDING CODE - PART 03.pdf

19  

Table 3.2.4A – Part 1 (Cont’d.)  

 (1) 

  (2)   (3)   (4) 

  (5)   (6) 

 

 

A (Assembly) 

 

7.5 

7.5 

15 

28 

No Limit 

250 

500 

No limit 

5000 

No limit 

No Limit 

No Limit 

3500 

154000 

No limit 

 

½ 

1 (a) 

1 ½  

1  (b) 

1 ½ 

S,H (General and Hazardous 

      Storage) 

7.5 

7.5 

15 

15 

28 

28 

Over 28 

150

300 

No limit 

No limit 

No limit 

No Limit 

1000 

No Limit

No limit 

1700 

3500 

7000 

21000 

No Limit 

½ 

1 (a) 

1 (b)  

  

Notes to Table 3.2.4a – Part 1  (*)  A  floor which  is  immediately  over  a  basement  storey  shall  be  deemed  to be  an  element  of  structure 

forming part of a basement storey.  

(a) This period is reduced to half an hour in respect of a floor which is not a compartment floor except as to the beams which support the floor or any part of the floor which contributes to the structural support of the building as a whole. 

 (b) No  fire  resistance  is  required  if  the  elements  form  part  of  a  basement  storey which  has  an  area  not 

exceeding 50 m2.  

(x) The  items  thus marked  are  applicable  only  to  buildings,  not  to  compartments,  except  in  relation  to occupancy group R  

(y) If  the building  is  fitted  throughout with an automatic sprinkler system any maximum  limits specified  in columns (3) and (4) shall be doubled. 

       

Page 20: GHANA BUILDING CODE - PART 03.pdf

20  

Table 3.2.4A – Part 2  ‐ Single storey buildings  

Minimum periods of Fire resistance  

  

Occupancy group  

(1) 

 Minimum floor area  

(in m2)  

(2) 

 Minimum period of fire resistance (in 

hours) for elements of structure 

(3) 

 

 

R (Residential)  3000  ½  z 

 E and I   (Educational/Institutional)  

3000  ½  z 

B  (Business and       Personal Service)  

3000 

No Limit 

½ 

1 z 

 M (Mercantile)  

2000 

3500 

No Limit 

½ 

 F (Industrial)  

2000 

3000 

No Limit 

½ 

 

G(Assembly) 

3000 

No limit 

½ 

1 z 

 S,H (General and Hazardous       Storage)  

500 

1000 

3000 

No Limit 

½ 

 Notes to Part 2: z,  See Article 3.2.6(4) (i)  

      

Page 21: GHANA BUILDING CODE - PART 03.pdf

21  

Table 3.2.4B  

National Periods of Fire Resistance  In this table:  

(a) “Class 1 aggregate” means  foamed  slag, pumice, blast  furnace  slag, pelleted  fly ash,  crushed brick  and  burnt  clay  products  (including  expanded  clay),  well‐burnt  clinker  and  crushed limestone.   “Class  2  aggregate”  means  flint  gravel,  granite  and  all  crushed  natural  stones  other  than limestone.  

(b) Any reference to plaster means:  

i)  in the case of an external wall 1m or more from the relevant boundary, plaster applied on the internal face only; 

 ii)   in the case of any other wall, plaster applied on both faces;   iii)  if to plaster of a given thickness on the external face of a wall, except  in the case of a 

reference to vermiculite – gypsum or perlite‐pypsum plaster, rendering on the external face of the same thickness; 

 iv)  if to vermiculite‐gypsum plaster, vermiculite‐gypsum plaster of a mix within the range of 

1 ½ to 2:1 by volume.  

(c) Load assumed to be on inner leaf only except for fire resistance period of four hours.                

Page 22: GHANA BUILDING CODE - PART 03.pdf

22  

A.  Masonry construction        Table 3.2.4B (cont’d.)   Part 1: Walls  

Construction and Materials  Minimum thickness excluding plaster (in mm) for period of fire resistance ofLoad‐bearing                                                                                           Non‐load bearing 

1. Reinforced concrete, minimum     concrete cover to main reinforcement of      25 mm.  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster  

4 hrs  2 hrs 1 ½ hrs 1 hr ½ hr 4 hrs 2 hrs 1 ½ hrs 1 hr ½ hr

 180 180 180 125 

 100 100 100 75 

 100 100 100 75 

 75 75 75 63 

 75 75 75 63 

2. Non‐fines concrete of Class 2 aggregate  a) 12.5mm cement – sand plaster b) 12.5mm gypsum‐sand plaster c) 12.5mm vermiculite‐gypsum plaster 

 150 150 150 

3. Bricks of clay, concrete or sand‐lime  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster  

 200 200 200 100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 170 170 170 100 

 100 100 100 100 

 100 100 100 100 

 75 75 75 75 

 75 75 75 75 

4.  Concrete blocks of Class 1 aggregate  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster  

 150 150 150 100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 150 100 100 75 

 75 75 75 75 

 75 75 75 62 

 75 75 75 50 

 50 50 50 50 

5. Concrete blocks of Class 2 aggregate  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster  

    

100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 100 100 100 100 

 150 150 150 100 

 100 100 100 75 

 100 100 100 75 

 75 75 75 75 

 50 50 50 50 

Page 23: GHANA BUILDING CODE - PART 03.pdf

23  

  Table 3.2.4B (cont’d.)   Part 1: Walls  (cont’d.)  Construction and Materials  Minimum thickness excluding plaster (in mm) for period of fire resistance of

Load‐bearing                                                                                           Non‐load bearing     6.   Autoclaved aerated  concrete blocks density 475 – 1200 kg/m3  

4 hrs  2 hrs 1 ½ hrs 1 hr ½ hr 4 hrs 2 hrs 1 ½ hrs 1 hr ½ hr

  

180  

  

100  

  

100  

  

100 

  

100 

  

100 

  

62 

  

62  

  50 

  

50 

7.  Hollow concrete blocks, one cell in wall       Thickness, of Class 1 aggregate  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster 

  

100 100 100 100 

  

100 100 100 100 

  

100 100 100 100 

  

100 100 100 100 

  

150 150 150 100 

  

100 100 100 75 

  

100 75 75 75 

  

100 75 75 62 

  

75 75 75 62 

8.  Hollow  concrete  blocks,  one  cell  in  wall thickness of class 2 aggregate  a)  unplastered b) 12.5mm cement‐sand plaster c) 12.5mm gypsum‐sand plaster d) 12.5mm vermiculite gypsum plaster  

  

150 150 150 125 

  

150 150 150 100 

  

125 125 125 100 

  

125 125 125 100 

  

125 100 100 75 

9.  Cellular clay block not less than 50% solid a) 12.5mm cement‐sand plaster b) 12.5mm gypsum‐sand plaster c) 12.5mm vermiculite gypsum plaster  

   

200 

   

100 

   

100 

 100 100 100 

 75 75 62 

    

Page 24: GHANA BUILDING CODE - PART 03.pdf

24  

  Table 3.2.4B (cont’d.)   Part 1: Walls (cont’d.)  Construction and Materials  Minimum thickness excluding plaster (in mm) for period of fire resistance of

Load‐bearing                     Non‐load bearing    10. Cavity wall with outer leaf of bricks or blocks or clay, composition, concrete or sand‐lime, not less than 100mm thick and  a)  inner  leaf  of  bricks  or  blocks  of  clay composition or sand‐lime  b) inner leaf of solid or hollow concrete bricks or blocks of class 1 aggregate  

4 hrs  2 hrs 1 ½ hrs 1 hr ½ hr  4 hrs 2 hrs 1 ½ hrs 1 hr ½ hr

      

100   

100 

      

100   

100 

      

100   

100 

      

100   

100 

      

100   

100 

      75   75 

      

75   

75 

      

75   

75  

      75   75 

      

75   

75 

11.  Cavity wall with  outer  leaf  of  cellular  clay blocks/9 above and  inner  leaf as of autoclaved aerated  concrete  blocks,  density  475  –  1200 kgm3.     

150  100  

100  

100  

100  

75  

75  

75  

75  

75  

 * Perlite‐gypsum plaster to clay bricks only          

Page 25: GHANA BUILDING CODE - PART 03.pdf

25  

Table 3.2.4B – (cont’d.) Part 1: Walls – (cont’d.) 

 B.  Framed and composite construction (non‐load bearing)  cont’d. 

  

Construction and Materials  

Periods of fire resistance in hours  

1.  Steel frame with external cladding of 16mm rendering on metal lathing  and  internal  lining  of  autoclaved  aerated  concrete blocks, density 480‐1120 kg/m3 of thickness of:                            50mm                           62 mm                           75mm 

    2 3 4 

2.  Steel  frame with external cladding of 100mm concrete blocks and internal lining of 16mm gypsum plaster on metal lathing 

 4 

3.  Steel frame with external cladding of bricks of clay, concrete or sand‐lime  100mm  thick  and  internal  lining  of  cement  pulp asbestos insulating board of thickness of 9mm 

 3 

4.  Steel frame with external cladding of 16mm rendering on metal lathing and internal lining of 9mm asbestos insulating board  16mm gypsum plaster on metal lathing 

 ½  1 

5.  Steel or timber frame with facings on each side of: 

(a) Metal  lathing with cement‐sand or gypsum plaster of thickness of:  

                                19mm                                12.5mm  

(b) Metal  lathing  with  vermiculite  gypsum  or  perlite‐gypsum plaster of thickness of: 

                                 25mm                                 19mm                                12.5mm  

(c) 9.5mm plasterboard with gypsum plaster of  thickness of 5mm 

(d) 9.5mm  plasterboard with  vermiculite  gypsum  plaster of thickness of  

                                25mm                                 16mm                                 10mm                                  5mm  

     1 ½     2 1 ½ 1   ½    2 1 ½ 1 ½  

Page 26: GHANA BUILDING CODE - PART 03.pdf

26  

Table 3.2.4B  ‐  Part 1: Walls – cont’d.  

B.  Framed and composite construction (non‐load bearing) cont’d.   

Construction and Materials  

Periods of fire resistance in hours  

  (e) 12.5mm plasterboard unplastered  with  gypsum  plaster  of  thickness  of 12.5mm  

(f) 12.5mm plasterboard with vermiculite gypsum plaster of thickness of:  

                          25mm                           16 mm                           10mm 

½   1     2 1½  1 

  (g) 19mm plasterboard  (or  two  layers of 9.5mm  fixed  to break joint) without finish  

(h) 19mm  plasterboard  (or  two  layers  of  9.5mm)  with vermiculite‐gypsum plaster of thickness of:  

                          16 mm           10mm 

 1     2 1½  

  (i) 12.5mm fibre  insulating board with gypsum plaster of thickness of 12.5mm  

(j) Cement  pulp  asbestos  insulating  board  not  less  than 9mm thick with 9mm fillets to face of studs 

 (k) Cement  pulp  asbestos  insulating  board  not  less  than 

12mm thick  

(l) 25mm  wood  wool  slabs  with  gypsum  plaster  of thickness of 12.5mm  

 ½    ½   ½    1  

 6. 

Compressed  straw  slabs  in  timber  frames  finished  on  both faces with gypsum plaster of thickness of 5mm 

 1 

 7.  Plasterboard 9.5mm cellular core partition:

 (a) Unplastered  (b) 12.5mm gypsum plaster (c) 22mm vermiculite‐gypsum plaster 

 

  ½  ½  2 

 8.  Plasterboard 19mm finished on both faces with 16mm gypsum 

plaster  1  

Page 27: GHANA BUILDING CODE - PART 03.pdf

27  

 Table 3.2.4B –  Part 1: Walls  (cont’d.) 

 B.  Framed and composite construction (non‐load bearing) cont’d. 

  

Construction and Materials  

Periods of fire resistance in hours  

 9. 

Plastered 12.5mm cellular core partition: 

(a) Unplastered   

(b) 12.5mm gypsum plaster  

(c) 16mm vermiculite‐gypsum plaster  

  ½   1  2 

  

10.  Plasterboard  12.5mm  bonded  with  neat  gypsum  plaster  to each side of 19mm plasterboard 

 

  

1 ½    

 11. 

Three  layers of 19mm plasterboard bonded with neat gypsum plaster 

 

 2 

  

12. Wood wool slab with 12.5mm render or plaster of thickness of:                             75mm                               50mm 

  2  1 

  

13.  Compressed  straw  slabs, with 75mm by 12.5mm wood  cover strips to joints, of thickness of 50mm 

  ½   

               

Page 28: GHANA BUILDING CODE - PART 03.pdf

28  

Table 3.2.4B – Part 1: Walls ( cont’d.)  

C.  External walls more than 1m from the relevant boundary (non‐load‐bearing)   

Construction and Materials  

Periods of fire resistance in hours  

 1. 

Steel  frame with external  cladding of non‐combustible  sheets and internal lining of:  

(a) 9mm cement pulp asbestos insulating board  

(b) 12.5mm  cement‐sand  or  gypsum  plaster  on  metal lathing  

(c) Sprayed cement pulp asbestos of thickness of 12.5mm   

(d) Two layers of 9.5mm plaster‐board  

(e) 9.5mm  plasterboard  finished with  gypsum  plaster  of thickness of 12.5mm 

 (f) 12.5mm  plastered  board  finished with  5mm  gypsum 

plaster  

(g) 50mm compressed straw slabs  

(h) 50mm  compressed  straw  slabs  finished  with  5mm gypsum plaster 

   4   4  4  ½    ½    ½   ½    1 

 2. 

 Timber frame with external cladding of 10mm cement sand or cement‐lime rendering and internal lining of:  

(a) 9mm cement pulp asbestos insulating board  

(b) 16mm gypsum plaster on metal lathing  

(c) 9.5mm  plasterboard  finished  with  12.5mm  gypsum plaster 

 (d) 50mm compressed straw slabs 

 (e) Aerated concrete block 

                                             50mm                                             62mm                                             75mm                                             100mm 

    1  1   1  1  1  3 4 4 4 

 

Page 29: GHANA BUILDING CODE - PART 03.pdf

29  

 Table 3.2.4B –  Part 1: Walls (cont’d.) 

 C.  External walls more than 1m from the relevant boundary (non‐load‐bearing) 

  

Construction and Materials  

Periods of fire resistance in hours  

 3. 

Timber  frame with external cladding of 100mm clay, concrete or sand – lime bricks or blocks finished internally with:  

(a) Cement pulp asbestos insulating board  

(b) 16mm gypsum plaster on metal lathing  

   4  4  

 *4. 

 Timber  frame with  external  cladding  of weather  boarding  or 9.5mm plywood and internal lining of:  

(a) 9mm cement pulp asbestos insulating board  

(b) 16mm gypsum plaster on metal lathing  

(c) 9.5mm  plasterboard  finished  with  12.5mm  gypsum plaster 

 (d) 12.5mm  plasterboard  finished  with  5mm  gypsum 

plaster  

(e) 50mm compressed straw slabs  

(f) 75mm wood wool slabs faced each side with asbestos cement 

 (g) Aerated concrete block 

                                             50mm                                              62mm                                              75mm                                              100mm  

    ½   ½   ½    ½   ½    2    3  4  4  4  

     

Page 30: GHANA BUILDING CODE - PART 03.pdf

30  

 Table 3.2.4B  ‐   (contd.) 

 Part II: Reinforced Concrete Columns 

 

Construction and Materials 

Minimum dimension of concrete column* without finish  (in mm) for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  

½ hr  

 1.  (a) Without plaster   

450  300  250  200  150 

      (b)  With 12.5mm cement‐sand of             gypsum‐sand plaster on mesh             reinforcement fixed around column  

300  225  150  150  150 

(c) Finished with 12.5mm encasement of vermiculite gypsum plaster  

275  200  150  120  120 

(d)  With  2.5mm  hard  drawn  steel wire  fabric,  of  maximum  pitch 150mm  in  each  direction,  placed in  concrete  cover  to  main reinforcement  

300  225  200  150  150 

 (e) With  limestone  or  light‐weight 

aggregate as coarse aggregate  

300  225  200  200  150 

 2.   Built into+ any separating wall, 

      compartment or external walls++   

(a)  Without plaster  

(b) Finished  with  12.5mm  of vermiculite‐gypsum plaster 

 

    

180   

125 

    

100   

75  

    

100   

75 

    

75   

63 

    

75   

63 

 *   The minimum dimension of a circular column is the diameter  

+    No part of column projecting beyond either face of wall 

++ Having not less fire resistance than that of the column and extending to the full height of, and not  

      less than 600mm on each side of the column 

 

Page 31: GHANA BUILDING CODE - PART 03.pdf

31  

Table 3.2.4B ‐   (contd.)  

Part III:  Reinforced Concrete Beams    

Construction and Materials 

Minimum dimension of concrete column* without finish (in mm) for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr  

 1.  (a) Without plaster   

63  45  35  25  12.5 

(b) finished with 12.5mm vermiculite        gypsum plaster 

 25  12.5  12.5  12.5  12.5 

(c) With 12.5mm cement–sand or gypsum‐sand  plaster  on  mesh  reinforcement fixed around beam  

50  30  20  12.5  12.5 

 

Table 3.2.4B‐   (contd.)  

Part IV: Prestressed Concrete Beams with Post Tensioned Steel  

Cover Reinforcement  Additional Protection 

Minimum concrete cover to tendons (in mm) for a fire 

resistance of 4 hrs 2 hrs  1 ½ hrs 1 hr

None 

(a) None      38

(b) Vermiculite  concrete  slabs  (permanent shuttering) 12.5mm thick    38  25  25 

(c) plaster  12.5mm  thick  on  mesh  reinforcement fixed around beam 

   50  38  25 

(d) vermiculite‐gypsum  plaster  12.5mm  thick  or sprayed cement pulp asbestos 10mm thick    38  25  25 

Light  mesh reinforcement (having  a minimum concrete  cover of  25mm)  to retain  the concrete  in position around the tendons 

(a) None  100  63  63   

(b) plaster 12.5mm thick on mesh reinforcement  90    (c) Vermiculite  concrete  slabs  (permanent 

shuttering) 12.5mm thick   75       

(d) Vermiculite  concrete  slabs  (permanent shuttering) 25mm thick  50       

(e) Vermiculite‐gypsum plaster 12.5mm thick 75    

(f) vermiculite‐gypsum plaster 25mm thick  50    

(g) Sprayed cement pulp asbestos 10mm thick 75    

(h) Sprayed cement pulp asbestos 19mm thick 50    

Page 32: GHANA BUILDING CODE - PART 03.pdf

32  

Table 3.2.4B ‐   (contd.)  

Part V: Structural Steel  

A.  Encased Steel Stanchions (mass per metre not less than 45kg)  

Construction and Materials 

Minimum thickness (in mm) of protection for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr 

 (A) Solid Protection* (unplastered) 

          1.  Concrete not leaner than C20 mix       with natural aggregates+ 

(a) Concrete not assumed to be  load‐bearing reinforced  50  25  25  25  25 

(b) Concrete  assumed  to  be  load‐bearing,  reinforced  in  accordance with BS 5950: Part 2: 2000β 

75  50  50  50  50 

 2. Solid bricks of clay, composition or sand‐    Lime 

75  50  50  50  50 

 3. Solid blocks of foamed slag or pumice     concrete reinforced+ in every horizontal     joint 

62  50  50  50  50 

4. Sprayed cement pulp asbestos of     density 140‐240    kg/m3  44  19  15  10  10 

5. Sprayed vermiculite cement    38  32  19  12.5 (B) Hollow Protection+   

 115 

  

50 

  

50 

  

50 

  

50 1. Solid bricks of clay, composition or sand      lime reinforced in every horizontal joint,     unplastered  2. Solid blocks of foamed slag or pumice     concrete reinforced in every horizontal      joint, unplastered 

75  50  50  50  50 

3. Metal lathing with gypsum or cement‐     lime plaster of thickness of  

 38δ  25  19  12.5 

4.  (a) Metal lathing with vermiculite‐             gypsum or perlite‐gypsum plaster of            thickness of 

50δ  19  16  12.5  12.5 

(b)  Metal  lathing  spaced  25mm  from  flanges with vermiculite‐gypsum or perlite‐gypsum plaster of thickness of 

44  19  12.5  12.5  12.5 

 

Page 33: GHANA BUILDING CODE - PART 03.pdf

33  

Table 3.2.4B  ‐   (contd.)  

Part V: Structural Steel  

A.  Encased Steel Stanchions (mass per metre not less than 45kg)  

Construction and Materials 

Minimum thickness(in mm) of protection for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr 

 (B) Hollow Protection ++ (contd.)  

         

 5. Gypsum plasterboard with 1.6mm wire      binding at 100mm pitch           

(a) 9.5mm  plasterboard with  gypsum of thickness of        12.5  12.5 

(b) 19mm  plasterboard  with  gypsum plaster of thickness     12.5  10  7  7 

 6. Gypsum plasterboard with 1.6mm     wire binding at 100mm pitch 

         

(a) 9.5mm  plasterboard  with vermiculite  gypsum    plaster  of thickness of 

  16  12.5  10  7 

(b) 19mm  plasterboard  with vermiculite  ‐  gypsum  plaster  of thickness of 

32 δ  10  10  7  7 

 

    *   Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in that casing made full and solid. 

 

+  Reinforcement  shall  consist  of  steel  binding wire  not  less  than  2.3mm  in  thickness,  or  a  steel mesh weighing not  less  than 0.48 kg/m2.    In concrete protection,  the spacing of  that  reinforcement shall not exceed 150mm in any direction. 

 ++  Hollow protection means that there  is a void between the protective material and the steel.   All hollow 

protection to columns shall be effectively sealed at each floor level.  δ Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads are used. 

 β   As read with BS5950:2000 and Eurocode 3  

   

Page 34: GHANA BUILDING CODE - PART 03.pdf

34  

Table 3.2.4B ‐  (contd.) Part V: Structural Steel (contd.) 

 A.  Encased steel stanchions (Mass per metre not less than 45kg) – contd.    

Construction and Materials 

Minimum thickness (in mm) of protection for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr 

(B) Hollow Protection *(contd.) 

44  19  15  10  10 7. Metal lathing with sprayed asbestos of       thickness of: 

8.  Vermiculite‐cement  slabs  of  4:1  mix reinforced  with  wire  mesh  and  finished with plaster skim.  Slabs of thickness of: 

63  25  25  25  25 

9. Cement pulp asbestos  insulating boards of  density  510‐880  kg/m3  (screwed  to 25mm thick cement pulp asbestos battens for ½ hour and 1 hour periods) 

‐  25  19  12  9 

 B.   Encased steel beams (Mass per metre not less than 30k)         

 Construction and Materials 

Minimum thickness (in mm) of protection for a fire resistance of 

4hrs  2hrs  1½hrs  1hr  ½hr 

(A) Solid Protection+ (unplastered)           1.    Concrete  not  leaner  than  1:2:4  mix (C20) with natural aggregates‐ 

(a) Concrete not assumed to be  load‐bearing, reinforced 

63  25  25  25  25 

(b) Concrete  assumed  to  be  load‐bearing,  reinforced  in  accordance with BS 5950/Eurocode 3 

75  50  50  50  50 

2.  Sprayed  cement  pulp  asbestos  of density 140‐240  kg/m3  44  19  15  10  10 

3. Sprayed vermiculite cement   ‐  38  32  19  12.5 

         +          Solid protection means a casing which is bedded close to the steel without intervening cavities and with all joints in 

that casing made full and solid. ++  Reinforcement shall consist of steel binding wire not less than 2.3mm in thickness, or a steel mesh weighing not less 

than 0.48 kg/m2.  In concrete protection, the spacing of that reinforcement shall not exceed 150mm in any direction.  *  Hollow protection means that there is a void between the protective material and the steel.  All hollow protection to 

columns shall be effectively sealed at each floor level. 

Page 35: GHANA BUILDING CODE - PART 03.pdf

35  

Table 3.2.4B ‐   (contd.) Part V:  Structural Steel (contd.) 

 B.  Encased steel beams (Mass per metre not less than 30kg) – contd.  

Construction and Materials 

Minimum thickness(in mm) of protection for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr (B) Hollow Protection* 1. Metal lathing  

(a) With  cement‐lime  plaster  of thickness of: 

(b) With  gypsum  plaster  of  thickness of: 

(c) With vermiculite‐gypsum or perlite gypsum plaster of thickness of: 

      

32 

  

38  

22  

12.5 

  

25  

19  

12.5 

  

19  

16  

12.5 

  

12.5  

12.5  

12.5 2. Gypsum plasterboard with 1.6mm wire       binding at 100mm pitch 

(a) 9.5mm  plasterboard with  gypsum plaster of thickness of: 

(b) 19mm  plasterboard  with  gypsum plaster of thickness of:  

       

12.5 

     

10 

   

12.5  7 

   

12.5  7 

3.  Plasterboard with  1.6mm wire  binding   at 100mm pitch 

(a) 9.5mm  plasterboard  nailed  to wooden  cradles  finished  with gypsum plaster of thickness of:  

(b) 9.5mm  plasterboard  with vermiculite‐gypsum  plaster  of thickness of: 

 (c) 19mm  plasterboard  with 

vermiculite‐gypsum  plaster  of thickness of:  

 (d) 19mm  plasterboard  with 

vermiculite‐gypsum  plaster  of thickness of:   

           

32+ 

       

16    

10    

12.5 

       

12.5    

10 

       

10    7 

    

12.5   7    7 

   

Page 36: GHANA BUILDING CODE - PART 03.pdf

36  

Table 3.2.4B (contd.) Part V: Structural Steel (contd.) 

 B.  Encased steel beams (Mass per metre not less than 30 kg) – contd.    

 Construction and Materials 

Minimum thickness (in mm) of protection for a fire resistance of 

4hrs  2hrs  1½hrs  1hr  ½hr 

4. Metal lathing with sprayed cement pulp asbestos  of  density  140‐240  kg/m3  and thickness of:  

44  19  15  10  10 

5. Cement pulp asbestos  insulating boards of  density  510‐880  kg/m3  (screwed  to 25mm thick cement pulp asbestos battens for ½ hour and 1 hour periods)  

  25  19  12  9 

6.  Vermiculite‐cement  slabs  of  4:1  mix reinforced  with  wire  mesh  and  finished with plaster skim.  Slabs of thickness of:  

63  25  25  25  25 

 7.    Gypsum  sand  plaster  12.5mm  thick applied  to  heavy  duty  (Type  B  as designated in B.S. 1105: 1963). Wood wool slabs of thickness of: 

  50  38  38  38 

  *  Hollow protection means that there is a void between the protective material and the steel.  All 

hollow protection to columns shall be effectively sealed at each floor level.  +  Light mesh reinforcement required 12.5mm to 19mm below surface unless special corner beads 

are used.                

Page 37: GHANA BUILDING CODE - PART 03.pdf

37  

Table 3.2.4B ‐  (contd.) Part VI: Structural Aluminium 

 Encased aluminium alloy stanchions and beams (Mass per metre not less than 16kg)  

Contruction and Materials 

Minimum thickness (in mm) of protection for a fire resistance of 

4 hrs  2 hrs  1 ½ hrs  1 hr  ½ hr 

(A) Solid Protection*  1.  Sprayed  cement  pulp  asbestos  of density 140 – 240  kg/m3 

 

2. Sprayed vermiculite‐cement  

   

 

48  32 

  

19  

44 

10 

(B) Hollow Protection +  1. Metal lathing with vermiculite‐gypsum     or perlite‐gypsum plaster of thickness     of:  2. Metal lathing finished with neat gypsum    plaster of thickness of:  3. Gypsum Plasterboard 19mm  thick with 1.6mm  wire  binding  at  100mm  pitch finished with gypsum – vermiculite plaster of thickness of:  4. Cement pulp  asbestos  insulating board of  density  510  –  880  kg/m3  (screwed  to 25mm thick cement pulp asbestos battens for the ½ hour period)  

             

    

32        

22        

    

22        

16     

34 

    

16   

19     

10     

21 

    

12.5   

12.5     

10     9 

     +   Solid protection means a casing which is bedded close to the alloy without  intervening cavities and with all joints in 

that casing made full and solid.  

*  Hollow protection means that there is a void between the protected material and the alloy.  All hollow protection to columns shall be effectively sealed at each floor level. 

     

Page 38: GHANA BUILDING CODE - PART 03.pdf

38  

 Table 3.2.4B (contd.) 

Part VII: Timber Floors  Construction and Materials  

Minimum thick (in mm) for fire resistance of: 

1 hr  ½ hr  Modified ½ hr ++ (A) Plain edge boarding on timber joists not less than 

38mm  wide with ceiling of:  

(i) Timber lath and plaster – thickness of plaster  

(ii) Timber lath and plaster with plaster of minimum       thickness of 16mm covered on underside with       plasterboard of thickness  

      (iii) metal lathing and plaster – thickness of plaster: (a) Gypsum (b) Vermiculite 

       (iv)  one layer of plasterboard of  thickness        (v)  one  layer  of  plasterboard  of  minimum  thickness   9.5mm finished with gypsum plaster of thickness      (vi)  one  layer  of  plasterboard  of  minimum  thickness   12.5mm finished with gypsum plaster of thickness      (vii)  two layers of plasterboard of total thickness      (viii)  two  layers  of  plasterboard  each  of  minimum   thickness 9.5mm finished with gypsum   plaster  of   thickness     (ix)  one  layer  of  fibre  insulating  board  of  minimum    thickness 12.5mm finished with gypsum plaster of   thickness      (x) one layer of asbestos insulating board of  minimum             thickness      (xi)wood wool slab 25mm thick finished with  gypsum            plaster of thickness 

        

12.5   

16 12.5        

12.5  

25    5       

12   5 

   

16          

12.5   

12.5     

19        

12.5 

 ++   The term “modified ½ hour” refers to the requirements specified in BS 476 Part 20‐23: 1987 and BS 476 Part 1:2004 

for floors of upper storey in small residential buildings which have 2 storeys.   

Page 39: GHANA BUILDING CODE - PART 03.pdf

39  

 Table 3.2.4B – (contd.) 

Part VII: Timber Floors – (contd.)   

Construction and Materials  

Minimum thick (in mm) for fire resistance of: 

1 hr  ½ hr  Modified ½ hr ++ (B)    Tongued  and  grooved  boarding  of  not  less  than   16mm  (finished)  thickness*  on  timber  joists  not   less than  38mm wide with ceiling of: 

(j) timber lath and plaster – thickness of plaster  

(ii) timber lath and plaster with plaster of minimum       thickness of 16mm covered on underside with       plasterboard of thickness  

      (iii) metal lathing and plaster – thickness of plaster: (a) gypsum (b) vermiculite 

      (iv)  one layer of plasterboard of thickness       (v)  one  layer  of  plasterboard  of  minimum  thickness   9.5mm finished with: 

(a) gypsum plaster of thickness (b) vermiculite‐gypsum plaster of thickness 

     (vi)  one  layer  of  plasterboard  of  minimum  thickness   12.5mm finished with gypsum plaster of thickness      (vii) two layers of plasterboard of total thickness      (viii)  one  layer  of  fibre  insulating  board  of  minimum    thickness 12.5mm finished with gypsum plaster of   thickness      (ix)   one layer of cement pulp asbestos insulating board              of  minimum thickness      (x)  one layer of asbestos insulating board of minimum             thickness of 12mm  finished on  top with glass  fibre   or mineral wool of thickness      (xi)  wood wool slab 25mm thick finished with  

(a) gypsum plaster of thickness (b) vermiculite gypsum plaster of thickness 

 

          

22 12.5     

12.5                

25    

10 

       

9.5   

16 12.5    

12.5  

  5  

22      9        5 

   

16         

9.5            5 

 

*Or an equivalent thickness of wood chipboard 

Page 40: GHANA BUILDING CODE - PART 03.pdf

40  

 Table 3.2.4B (contd.) 

Part VII: Timber Floors  (contd.)   

Construction and Materials  

Minimum thick (in mm) for fire resistance of:

1 hr  ½ hr  Modified ½ hr ++ 

(C)  Tongued and grooved boarding of not less than       16mm  (finished) thickness* on timber joists not less        than 175mm deep by 50mm wide with ceiling of:        (i) Timber lath and plaster – thickness of plaster 

       (ii) metal lathing and plaster – thickness of plaster       (iii)  metal lathing and sprayed cement pulp asbestos to            thickness of        (iv)  one layer of plasterboard of thickness         (v)  one  layer  of  plasterboard  of  minimum  thickness    9.5mm finished with: 

(a) gypsum plaster (b) vermiculite – gypsum plaster of thickness 

       (vi) one layers of plasterboard of minimum thickness of            12.5mm finished with gypsum plaster of thickness      (vii)  two layers of plasterboard of total  thickness                  (viii)  one layer of fibre insulating board of thickness      (ix)   one layer of fibre insulating board of minimum             thickness of 12.5mm finished  with gypsum plaster   of  thickness      (x)    one layer of cement pulp asbestos insulating board              of thickness     (xi)   wood wool slab 25mm thick finished with:  

(a)   gypsum plaster of thickness  

(b) vermiculite‐gypsum plaster of thickness 

       19        

12.5                    10 

 

   16  16  

12.5       

12.5  

  5  19      

12.5   6    5   

          

9.5            

12.5      

 *   Or an equivalent thickness of wood chipboard 

++ The term “modified ½ hour” refers to the requirements specified  in BS 476   Part 20‐23: 1987 and BS 476 Part 1: 2004 for 

floors of upper storey in small residential building which have 2 storeys 

 

Page 41: GHANA BUILDING CODE - PART 03.pdf

41  

  

Table 3.2.4B (contd.) Part VIII:  Concrete Floors 

 

Construction and Materials 

Minimum thickness of solid substance including screed 

(in mm) 

Ceiling finish for a fire resistance

4 hours  2 hours  1 ½ hours 

Solid flat slab or filler joist floor.  Units of channel or T 

section 

90100 125 150 

25mmV or 25mmA19mmV or 19mmA 10mm V or 12.5mmA 

Nil 

10mmV or 12.5mmA7mmV Nil Nil 

10mmV or 12.5mmA7mmV Nil Nil 

Solid flat slab or filler joist floor with 25mm wood wool 

slab ceiling base 

90100 125 150 

 12.5mm G 

Nil 

 Nil Nil Nil 

12.5mm GNil Nil Nil 

Units of inverted U section with minimum thickness at 

crown 

6375 100 150 

  

Nil 

  

Nil Nil 

 Nil Nil 

Hollow block construction units of box or I section 

6375 100 150 

  

Nil 

  

Nil Nil 

 Nil Nil 

Cellular steel with concrete topping 

 63 

12.5mmV suspended on metal lathing or 12.5mmA (direct) 

12.5mmG suspended on metal lathing 

12.5mmG suspended on metal lathing 

  

“V” – Vermiculite‐gypsum plaster.   “A” – sprayed cement pulp asbestos     

  “G” – gypsum plaster   Note:   Where a column relating to ceiling finish contains no entry opposite a specification, the notional period of 

fire resistance specified in that column is not applicable.                 

Page 42: GHANA BUILDING CODE - PART 03.pdf

42  

3.2.5 Fire resistance of Floors in conjunction with Suspended Ceilings  3.2.5  (1)  This subsection is concerned only with the effect made by suspended ceilings to the fire  

resistance of  floors.    It  is not  related  to  the protection given by suspended ceilings  to structural steel work. 

 (2)  In  the  application of  subsection 3.2.4  to  floors, no  account  shall be  taken of  any  fire 

resistance  attributable  to  any  suspended  ceiling  other  than  a  suspended  ceiling constructed as described in Table 3.2.5A. 

   

Table 3.2.5A – Suspended Ceilings  

Height   

Type of floor   

Required fire resistance of floor 

 

Description of Suspended Ceiling 

  

Less than 15m 

 Non‐compartment 

 1 hour or less 

 

  Surface  of  ceiling  exposed within the cavity not  lower than class 1 Compartment 

 Less than 1 hour 

 

Compartment  1 hour 

Surface  of  ceiling  exposed within the cavity not  lower than Class O  supports and  fixings  for the ceiling non‐combustible 

15m or more  Any   1 hour or less 

Surface  of  ceiling  exposed within the cavity not  lower than Class  O  and  jointless,  supports and  fixings  for  the  ceiling  non‐combustible 

Any   Any   More than 1 hour 

Ceiling  of  non‐combustible construction  and  jointless; supports  and  fixings  for  the ceiling non‐combustible 

  3.2.6 External Walls  

(1) This subsection does not apply to small garages and small open car ports.  

(2) Any part of a roof shall be deemed to be part of an external wall or side of a building if it is pitched at an angle of 700 or more to the horizontal and adjoins a space within the building to  which  persons  has  access  not  limited  to  the  purposes  of  maintenance  and  repair.             Fig 3.2.6A 

Page 43: GHANA BUILDING CODE - PART 03.pdf

43  

 (3) If  a  building  is  to  be  erected  on  land which will  be  occupied  in  common with  another 

building and either the building to be erected or the other building is of occupancy group A then: 

 (i)   in the application of the provisions of this regulation to any side or external wall of the 

building  to  be  so  erected which  faces  a  side  of  external wall  of  the  other  building  a notional boundary shall be assumed to pass between those buildings. 

(ii)   such notional boundary shall be so situated as to enable the adjacent sides and external walls of both buildings to comply with the requirements of this part of the code. 

 (iii)  if that other building is an existing building it shall be treated as it were a new building 

of  the  same  occupancy  group  and  having  the  same  unprotected  areas  and  fire resistance as the existing building.   Fig. 3.2.6B 

 (4) Any external wall which  is situated within a distance of 1m  from any part on  the relevant 

boundary and any external wall of a building which exceeds 15m in height shall:  

(a) be  constructed of wholly of  incombustible materials apart  from any external cladding which complies with 3.2.6 (5) or internal lining which complies with 3.2.9 (6) and   

(b) be so constructed  that any  fire resistance required by  these regulations  is attained by the non‐combustible part alone. 

 (5) The requirements of 3.2.6 (4) shall not apply to: 

 (i)   An external wall of a building which is within the limits of size indicated by letter “X” in 

Part 1 of Table 3.2.4A or of a building which  is not divided  into compartments and  is within the limits of size indicated by “Z” in Part 2 of Table 3.2.4A provided the building does not exceed 15m in height. 

 (ii) an external wall of a building of occupancy group A which consists of flats or maisonettes 

if  that building has not more  than 3  storeys or  that part  is  separated as described  in 3.2.4 (1)b and has not more than 3 storeys:  or 

(iii)   an external wall of a part of a building  if  that wall  is  situated 1m or more  from  the relevant boundary and  that part  is  separated as described  in 3.2.4  (1)b and does not exceed 15m in height. 

 (6) Any  external  cladding which  is  situated within  a  distance  of  1m  from  any  point  on  the 

relevant boundary and any external cladding or a building which exceeds 15m in height shall have a surface complying with the requirements for class specified in 3.2.9.6 (1) (e). 

                       Fig. 3.2.6C  

(7) Any beam or column forming part of, and any structure carrying, an external wall which  is required to be constructed of non‐combustible materials shall comply with the provisions of 3.2.6 (4) and 3.2.6 (5) as to non‐combustibility. 

  

Page 44: GHANA BUILDING CODE - PART 03.pdf

44  

3.2.7 Calculation of Permitted Limits of Unprotected Areas 3.2.7.1  General rules applicable to this subsection:  

(1) The permitted limit of unprotected areas in any side of a building or compartment shall be calculated by reference to Table 3.2.7.1A and 3.2.7.1B.  

(2) In calculating  the size of unprotected areas or  the permitted  limit of unprotected areas, the following provisions shall apply:  (a) Where  any  part  of  an  external  wall  is  an  unprotected  area,  only  because  it  has 

combustible material attached to  it as cladding the size of unprotected area shall be deemed to be half the area of such cladding.  Fig. 3.2.7A  

(b) No account shall be taken of any of the following:    

(i)   except as provided in 3.2.7.1 (2)b (iii), an unprotected area which does not exceed 0.1m2 and which  is not  less  than 1.5m  from any other unprotected area  in  the same side of the building or compartment.. 

 (ii) one or more unprotected areas having an area (or  if more than one an aggregate 

area) not  exceeding 1m2 and not less than 4m from any other unprotected area in the same side of the building or compartment (except any such area as is specified in (i) above). Fig. 3.2.7B 

 (iii)  an  unprotected  area  in  any  part  of  an  external  wall  which  forms  part  of  a 

protected shaft.  (iv) an unprotected area in the side of a building not divided into compartments, if the 

area is not less than 28m above any ground adjoining the side of the building.                Fig. 3.2.7C   3.2.8  Rules for calculation by reference to an Enclosing Rectangle  3.2.8  (1)  The permitted limit of unprotected areas in any side of a building or compartment shall      be calculated by reference to the requirements of Tables 3.2.8A or 3.2.8B.  3.2.8  (2)  Definitions: For the purpose of this subsection:  

(a) plane of reference means any vertical plane which touches the side of some part of the side of a building or compartment, but which does not pass within the structure of such a building or compartment; and the relevant plane of reference shall in each case be  taken as  that most  favourable  in  that  respect  to  the person erecting  the building. Fig. 3.2.8A              

 

Page 45: GHANA BUILDING CODE - PART 03.pdf

45  

  

    

Page 46: GHANA BUILDING CODE - PART 03.pdf

46  

           

  

Page 47: GHANA BUILDING CODE - PART 03.pdf

47  

(a) enclosing rectangle means the smallest rectangle on the relevant plane of reference which would:  

  (i)      enclose all the outer edges of any unprotected areas of the building or, if the    building  is  divided  into  compartments  the  outer  edges  being  for  this 

purpose projected on the plane of common by  lines perpendicular to such plane; 

(ii)  have no horizontal sides; and  (iii)  have  height  and width  falling within  those  listed  in  Tables  3.2.8A  –  Fig. 

3.2.8B (c)  Unprotected  percentage  means  the  percentage  of  the  area  of  the  enclosing 

rectangle which  is  equal  to  the  aggregate  of  the  unprotected  areas  taken  into account in calculating the enclosing rectangle and as projected on it. 

 3.2.8  (3)  The conditions of this sub‐section shall be satisfied if a building or compartment is so  

    situated that no point on the relevant boundary  is either between the relevant plane of reference and the side of the building or compartment or at a distance from the relevant plane of reference which is less than the distance specified in Table 3.2.8A, according to  

                  the  purpose  group  of  the  building  or  compartment,  the  dimensions  of  the  enclosing rectangle and the unprotected percentage.   

        

Page 48: GHANA BUILDING CODE - PART 03.pdf

48  

       

Page 49: GHANA BUILDING CODE - PART 03.pdf

49  

 Table 3.2.8A – Buildings or Compartments of Purpose 

Groups R (Residential), I (Institutional), B (Office) and A (Assembly)   Width of 

rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 3m High3  1.0  1.0  1.0 1.5 1.5 1.5 2.0  2.0 2.06  1.0  1.0  1.5 2.0 2.0 2.0 2.5  2.5 3.09  1.0  1.0  1.5 2.0 2.5 2.5 3.0  3.0 3.512  1.0  1.5  2.0 2.5 2.5 3.0 3.0  3.5 3.515  1.0  1.5  2.0 2.5 2.5 3.0 3.5  4.0 4.018  1.0  1.5  2.0 2.5 2.5 3.0 3.5  4.0 4.021  1.0  1.5  2.0 2.5 3.0 3.0 3.5  4.0 4.524  1.0  1.5  2.0 2.5 3.0 3.5 3.5  4.0 4.527  1.0  1.5  2.0 2.5 3.0 3.5 4.0  4.0 4.530  1.0  1.5  2.0 2.5 3.0 3.5 4.0  4.0 4.540  1.0  1.5  2.0 2.5 3.0 3.5 4.0  4.0 5.0

No Limit  1.0  1.5  2.0 2.5 3.0 3.5 4.0  4.0 5.0 

  

   Enclosing Rectangle 6m High3  1.0  1.0  1.5 2.0 2.0 2.0 2.5  2.5 3.06  1.0  1.5  2.0 2.5 3.0 3.0 3.5  4.0 4.09  1.0  2.0  2.5 3.0 3.5 4.0 4.5  4.5 5.012  1.5  2.5  3.0 3.5 4.0 4.5 5.0  5.0 5.515  1.5  2.5  3.0 4.0 4.5 5.0 5.5  5.5 6.018  1.5  2.5  3.5 4.0 4.5 5.0 5.5  6.0 6.521  1.5  2.5  3.5 4.0 5.0 5.5 6.0  6.5 7.024  1.5  2.5  3.5 4.5 5.0 5.5 6.0  7.0 7.027  1.5  2.5  3.5 4.5 5.0 6.0 6.5  7.0 8.030  1.5  2.5  3.5 4.5 5.0 6.0 6.5  7.0 8.040  1.5  2.5  3.5 4.5 5.5 6.5 7.0  8.0 8.550  1.5  2.5  3.5 4.5 5.5 6.5 7.5  8.0 9.060  1.5  2.5  3.5 5.0 5.5 6.5 7.5  8.5 9.580  1.5  2.5  3.5 5.0 6.0 7.0 7.5  8.5 9.5100  1.5  2.5  3.5 5.0 6.0 7.0 8.0  8.5 10.0

No Limit  1.5  2.5  3.5 5.0 6.0 7.0 8.0  8.5 10.0 

     

Page 50: GHANA BUILDING CODE - PART 03.pdf

50  

Table 3.2.8A – (contd.)  Width of 

rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 9m High3  1.0  1.0  1.5 2.0 2.5 2.5 3.0  3.0 3.56  1.0  2.0  2.5 3.0 3.5 4.0 4.5  4.5 5.09  1.5  2.5  3.5 4.0 4.5 5.0 5.5  5.5 6.012  1.5  3.0  3.5 4.5 5.0 5.5 6.0  6.5 7.015  2.0  3.0  4.0 4.5 5.5 6.0 6.5  7.0 7.518  2.0  3.5  4.5 5.0 6.0 6.5 7.0  8.0 8.521  2.0  3.5  4.5 5.0 6.5 7.0 7.5  8.5 9.024  2.0  3.5  5.0 5.5 6.5 7.5 8.0  9.0 9.527  2.0  3.5  5.0 5.5 7.0 7.5 8.5  9.5 10.030  2.0  3.5  5.0 6.0 7.0 8.0 9.0  9.5 10.540  2.0  3.5  5.5 6.0 7.5 8.5 9.5  10.5 11.550  2.0  4.0  5.5 6.5 8.0 9.0 10.0  11.5 12.560  2.0  4.0  5.5 6.5 8.0 9.5 11.0  11.5 13.080  2.0  4.0  5.5 7.0 8.5 10.0 11.5  12.5 13.5100  2.0  4.0  5.5 7.0 8.5 10.0 11.5  12.5 14.5120  2.0  4.0  5.5 7.0 8.5 10.0 11.5  12.5 14.5

No Limit  2.0  4.0  5.5 7.0 8.5 10.6 12.0  12.5 15.0 

  

  Enclosing rectangle 12m high3  1.0  1.5  2.0 2.0 2.5 3.0 3.0  3.5 3.56  1.5  2.5  3.0 3.5 4.0 4.5 5.0  5.0 5.59  1.5  3.0  3.5 4.5 5.0 5.5 6.0  6.5 7.012  1.5  3.5  4.5 5.0 6.0 6.5 7.0  7.5 8.015  2.0  3.5  5.0 5.5 6.5 7.0 8.0  8.5 9.018  2.5  4.0  5.0 5.5 6.5 7.5 8.0  8.5 9.021  2.5  4.0  5.5 6.5 7.5 8.5 9.0  10.0 10.524  2.5  4.5  6.0 7.0 8.0 8.5 9.5  10.5 11.527  2.5  4.5  6.0 7.0 8.0 9.0 10.5  11.5 12.030  2.5  4.5  6.5 7.5 8.5 9.5 10.5  11.5 12.540  2.5  5.0  6.5 8.0 9.5 10.5 12.0  13.0 14.050  2.5  5.0  7.0 8.5 10.0 11.0 13.0  14.0 15.060  2.5  5.0  7.0 9.0 10.5 12.0 13.5  14.5 16.080  2.5  5.0  7.0 9.0 11.0 13.0 14.5  16.0 17.0100  2.5  5.0  7.5 9.5 11.5 13.5 15.0  16.5 18.0120  2.5  5.0  7.5 9.5 11.5 13.5 15.0  17.0 18.5

No Limit  2.5  5.0  7.5 9.5 12.0 14.0 15.5  17.0 19.0  

   

Page 51: GHANA BUILDING CODE - PART 03.pdf

51  

Table 3.2.8A – (contd.)  Width of 

rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 15m High3  1.0  1.5  2.0 2.5 2.5 3.0 3.5  3.5 4.06  1.5  2.5  3.0 4.0 4.5 5.0 5.5  5.5 6.09  2.0  3.0  4.0 5.0 5.5 6.0 6.5  7.0 7.512  2.0  3.5  5.0 5.5 6.5 7.0 8.0  8.5 9.015  2.0  4.0  5.5 6.5 7.0 8.0 9.0  9.5 10.018  2.5  4.5  6.0 7.0 8.0 8.5 9.5  10.5 11.021  2.5  5.0  6.5 7.5 8.5 9.5 10.5  11.0 12.024  3.0  5.0  6.5 8.0 9.0 10.0 11.0  12.0 13.027  3.0  5.5  7.0 8.5 9.5 10.5 11.5  12.5 13.530  3.0  5.5  7.5 8.5 10.0 11.0 12.0  13.5 14.040  3.0  6.0  8.0 9.5 11.0 12.5 13.5  15.0 16.050  3.5  6.0  8.5 10.0 12.0 13.5 15.0  16.5 17.560  3.5  6.5  8.5 10.5 12.5 14.0 15.5  17.0 18.080  3.5  6.5  9.0 11.0 13.5 15.0 17.0  18.5 20.0100  3.5  6.5  9.0 11.5 14.0 16.0 18.0  19.5 21.5120  3.5  6.5  9.0 11.5 14.0 16.5 18.5  20.5 22.5

No Limit  3.5  6.5  9.0 12.0 14.5 17.0 19.0  21.0 23.0 

  

  Enclosing rectangle 18m high3  1.0  1.5  2.0 2.5 2.5 3.0 3.5  4.0 4.06  1.5  2.5  3.5 4.0 4.5 5.0 5.5  6.0 6.59  2.0  3.5  4.5 5.0 6.0 6.5 7.0  8.0 8.512  2.5  4.0  5.0 6.0 7.0 7.5 8.5  9.0 10.015  2.5  4.5  6.0  7.0  8.0  8.5  9.5  10.5  11.0 18  2.5  5.0  6.5  7.5  8.5  9.5  11.0  12.0  13.0 21  3.0  5.5  7.0  8.0  9.5  10.5  11.5  12.5  13.0 24  3.0  5.5  7.5  8.5  10.0  11.0  12.0  13.0  14.0 27  3.5  6.0  8.0  9.0  10.5  11.5  12.5  13.5  14.5 30  3.5  6.5  8.0  9.5  11.0  12.0  13.5  14.5  15.5 40  4.0  7.0  9.0  11.0  12.0  13.5  15.0  16.5  17.5 50  4.0  7.0  9.5  11.5  13.0  15.0  16.5  18.0  19.0 60  4.0  7.5  10.0  12.0  14.0  16.0  17.5  19.5  20.5 80  4.0  7.5  10.0  13.0  15.0  17.0  19.0  21.0  22.5 100  4.0  7.5  10.0  13.5  16.0  18.0  20.5  22.5  24.0 120  4.0  7.5  10.0  14.0  16.5 19.0  21.0  23.5  25.5 

No Limit  4.0  8.0  10.0  14.0  17.0  19.5  22.0  24.0  26.5     

Page 52: GHANA BUILDING CODE - PART 03.pdf

52  

Table 3.2.8A – (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 21m High3  0.5  1.5  2.0 2.5 3.0 3.0 3.5  4.0 4.56  1.5  2.5  3.5 4.0 5.0 5.5 6.0  6.5 7.09  2.0  3.5  4.5  5.5  6.5  7.5  7.5  8.5  9.0 12  2.5  4.0  5.5  6.5  7.5  8.5  9.0  10.0  10.5 15  2.5  5.0  6.5 7.5 8.5 9.5 10.5  11.5 12.018  3.0  5.5  7.0 8.0 9.5 10.5 11.5  12.5 13.021  3.0  6.0  7.5  9.0  10.0  11.0  12.5  13.5  14.0 24  3.5  6.0  8.0  9.5  10.5  12.0  13.0  14.0  15.0 27  3.5  6.5  8.5  10.0  11.5  13.0  14.0  15.0  16.0 30  4.0  7.0  9.0  10.5  12.0  13.0  14.5  16.0  16.5 40  4.5  7.5  10.0  12.0  13.5  15.0  16.5  18.0  19.0 50  4.5  8.0  11.0  13.0  14.5  16.5  18.0  20.0  21.0 60  4.5  8.5  11.5  13.5  15.5  17.5  19.0  21.0  22.5 80  4.5  8.5  12.0  14.5  17.0  19.0  21.0  23.5  25.0 100  4.5  9.0  12.0  15.5  18.0  20.5  22.5  25.0  27.0 120  4.5  9.0  12.0  16.0  18.5  21.5  23.5  26.5  28.5 

No Limit  4.5  9.0  12.0  16.0  19.0  22.0 25.0  26.5  29.5  

  

 Enclosing rectangle 24m high 

 3  0.5  1.5  2.0 2.5 3.0 3.5 3.5  4.0 4.56  1.5  2.5  3.5 4.5 5.0 5.5 6.0  7.0 7.09  2.0  3.5  5.0 5.5 6.5 7.5 8.0  9.0 9.512  2.5  4.5  6.0 7.0 8.0 8.5 9.5  10.5 11.515  3.5  5.0  6.5  8.0  9.0  10.0  11.0  12.0  13.0 18  3.0  5.5  7.5  8.5  10.0  11.0  12.0  13.0  14.0 21  3.5  6.0  8.0  9.5  10.5  12.0  13.0  14.0  15.0 24  3.5  6.5  8.5  10.0  11.5  12.0  14.0  15.0  16.0 27  4.0  7.0  9.0  11.0  12.5  13.5  15.0  16.0  17.0 30  4.0  7.5  9.5  11.5  13.0  14.0  15.5  17.0  18.0 40  4.5  8.5  11.0  13.0  14.5  16.0  18.0  19.0  20.5 50  5.0  9.0  12.0  14.0  16.0  17.5  19.5  21.0  22.5 60  5.0  9.5  12.5  15.0  17.0  19.0  21.0  23.0  24.5 80  5.0  10.0  13.5  16.5  18.5  21.0  23.5  25.5  27.5 100  5.0  10.0  13.5  17.0  20.0  22.5  25.0  27.5  29.5 120  5.5  10.0  13.5  17.5  20.5 23.5  26.5  29.0  31.0 

No Limit  5.5  10.0  13.5  18.0  21.0  24.0  27.5  30.0  32.5    

Page 53: GHANA BUILDING CODE - PART 03.pdf

53  

Table 3.2.8A – (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 27m High3  1.0  1.5  2.0 2.5 3.0  3.5  4.0  4.0  4.5 

6  1.5  2.5  3.5 4.5 5.0  6.0  6.5  7.0  7.5 

9  2.0  3.5  5.0  6.0  7.0  7.5  8.5  9.5  10.0 

12  2.5  4.5  6.0  7.0  8.0  9.0  10.5  11.0  12.0 

15  3.0  5.5  7.0 8.5 9.5  10.5  11.5  12.5  13.5 

18  3.5  6.0  8.0 9.0 10.5  11.5  12.5  13.5  14.5 

21  3.5  6.5  8.5  10.0  11.5  13.0  14.0  15.0  16.0 

24  3.5  7.0  9.0  11.0  12.5  13.5  15.0  16.0  17.0 

27  4.0  7.5  10.0  11.5  13.0  14.0  16.0  17.0  18.0 

30  4.0  8.0  10.0  12.0  13.5  15.0  17.0  18.0  19.0 

40  5.0  9.0  11.5  14.0  15.5  17.5  19.0  20.5  22.0 

50  5.5  9.5  12.5  15.0  17.0  19.0  21.0  22.5  24.0 

60  5.5  10.5  13.5  16.0  18.5  20.5  22.5  24.5  26.5 

80  6.0  11.0  14.5  17.5  20.5  22.5  25.0  27.5  29.5 

100  6.0  11.0  125.5  19.0  21.5  24.5  27.0  30.0  32.0 

120  6.0  11.5  15.5  19.5  22.5  26.0  28.5  32.0  34.0 

No Limit  6.0  11.5  15,.5  20.0  23.5  27.0  29.5  33.0  35.0 

                  

Page 54: GHANA BUILDING CODE - PART 03.pdf

54  

Table 3.2.8B   –Buildings or compartment of purpose Groups M (Shop), F (Factory) and S, H (Storage and General Hazard) 

 

Width of rectangle in metres 

Distance in metres from relevant boundary for unprotected percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 3m High3  1.0  1.5  2.0 2.0 2.5 2.5 2.5  3.0 3.06  1.5  2.0  2.5  3.0  3.0  3.5  3.5  4.0  4.0 9  1.5  2.5  3.0  3.5  4.0  4.0  4.5  5.0  5.0 12  2.0  2.5  3.0  3.5  4.0  4.5  5.0  5.5  5.5 15  2.0  2.5  3.5  4.0 4.5  5.0  5.5  6.0  6.0 18  2.0  2.5  3.5 4.0 5.0  5.0  6.0  6.5  6.5 21  2.0  3.0  3.5 4.5 5.0 5.5  6.0  6.5  7.0 24  2.0  3.0  3.5 4.5 5.0 5.5  6.0  7.0  7.5 27  2.0  3.0  4.0 4.5  5.5  6.0  6.5  7.0  7.5 30  2.0  3.0  4.0 4.5  5.5 6.0  6.5  7.5  8.0 40  2.0  3.0  4.0 5.0  5.5 6.5  7.0  8.0  8.5 50  2.0  3.0  4.0 5.0 6.0  6.5  7.5  8.0  9.0 60  2.0  3.0  4.0 5.0 6.0  7.0  7.5  8.5  9.5 80  2.0  3.0  4.0 5.0 6.0 7.0 8.0  9.0  9.5 

No Limit  2.0  3.0  4.0 5.0 6.0 7.0 8.0  9.0  10.0 

   Enclosing rectangle 6m high 

3  1.5  2.0  2.5 3.0 3.0 3.5 3.5  4.0 4.06  2.0  3.0  3.5  4.0  4.5  5.0  5.5  5.5  6.0 9  2.5  3.5  4.5  5.0  5.5  6.0  6.5  7.0  7.0 12  3.0  4.0  5.0  5.5  6.5  7.0  7.5  8.0  8.5 15  3.0  4.5  5.5  6.0 7.0  7.5  8.0  9.0  9.0 18  3.5  4.5  5.5 6.5 7.0  8.0  9.0  9.5  10.0 21  3.5  5.0  6.0 7.0 8.0  9.0  9.5  10.0  10.5 24  3.5  5.0  6.0 7.0 8.5  9.5  10.5  10.5  11.0 27  3.5  5.0  6.5 7.5  8.5  9.5  10.5  11.0  12.0 30  3.5  5.0  6.5 8.0  9.0  10.0  11.0  12.0  12.5 40  3.5  5.5  7.0 8.5  10.0  11.0  12.0  13.0  14.0 50  3.5  5.5  7.5 9.0 10.5  11.5  13.0  14.0  15.0 60  3.5  5.5  7.5 9.5 11.0  12.0  13.5  15.0  16.0 80  3.5  6.0  7.5 9.5 11.5  13.0 14.5  16.0  17.5 100  3.5  6.0  8.0 10.0 12.0 13.5 15.0  16.5  18.0 120  3.5  6.0  8.0 10.0 12.0 14.0 15.5  17.0  19.0 

No Limit  3.5  6.0  8.0 10.0 12.0 14.0 16.0  18.0  19.0       

Page 55: GHANA BUILDING CODE - PART 03.pdf

55  

Table 3.2.8B (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for unprotected percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 9m High3  1.5  2.5  3.0 3.5 4.0 4.0 4.5  5.0 5.06  2.5  3.5  4.5 5.0 5.5 6.0 6.5  7.0 7.09  3.5  4.5  5.5  6.0  6.5  7.5  8.0  8.5  9.0 12  3.5  5.0  6.0  7.0  7.5  8.5  9.0  9.5  10.5 15  4.0  5.5  6.5  7.5  8.5  9.5  10.0  11.0  11.5 18  4.5  6.0  7.0  8.5  9.5  10.0  11.0  12.0  12.5 21  5.0  6.5  7.5  9.0  10.0  11.0  12.0  13.0  13.5 24  5.0  6.5  8.0  9.5  11.0  12.0  13.0  13.5  14.5 27  5.0  7.0  8.5  10.0  11.5  12.5  13.5  14.5  15.0 30  5.5  7.0  9.0  10.5  12.0  13.0  14.0  15.0  16.0 40  5.5  7.5  9.5  11.5  13.0  14.5  15.5  17.0  17.5 50  5.5  8.0  10.0  12.5  14.0  15.5  17.0  18.5  19.5 60  5.5  8.0  11.0  13.0  15.0  16.5  18.0  19.5  21.0 80  5.5  8.5  11.5  13.5  16.0  17.5  19.5  21.5  23.0 100  5.5  8.5  11.5  14.5 16.5 18.5 21.0  22.5  24.5 120  5.5  8.5  11.5  14.5 17.0 19.5 21.5  23.5  26.0 

No Limit  5.5  8.5  11.5  15.0 17.5  20.0  22.5  24.5  27.0    Enclosing rectangle 12m high 

3  2.0  2.5  3.0 3.5 4.0 4.5 5.0  5.5 5.56  3.0  4.0  5.0 5.5 6.5 7.0 7.5  8.0 8.59  3.5  5.0  6.0  7.0  7.5  8.5  9.0  9.5  10.5 12  4.5  6.0  7.0  8.0  9.0  9.5  11.0  11.5  12.0 15  5.0  6.5  8.0  9.0  10.0  11.0  12.0  13.0  13.5 18  5.0  7.0  8.5  10.0  11.0  12.0  13.0  14.0  14.5 21  5.5  7.5  9.0  10.5  12.0  13.0  14.0  15.0  16.0 24  6.0  8.0  9.5  11.5  12.5  14.0  15.0  16.0  16.5 27  6.0  8.0  10.5  12.0  13.5  14.5  16.0  17.0  17.5 30  6.5  8.5  10.5  12.5  14.0  15.0  16.5  17.5  18.5 40  6.5  9.5  12.0  14.0  15.5  17.5  18.5  20.0  21.0 50  7.0  10.0  13.0  15.0  17.0  19.0  20.5  23.0  23.0 60  7.0  10.5  13.5  16.0  18.0  20.0  21.5  23.5  25.0 80  7.0  11.0  14.5  17.0  19.5  21.5  23.5  26.0  27.5 100  7.5  11.5  15.0  18.0  21.0 23.0 25.5  28.0  30.0 120  7.5  11.5  15.0  18.5  22.0 24.0 27.0  29.5  31.5 

No Limit  7.5  12.0  15.5  19.0  22.5  25.0  28.0  30.5  34.0      

Page 56: GHANA BUILDING CODE - PART 03.pdf

56  

Table 3.2.8B (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for unprotected percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 15m High3  2.0  2.5  3.5 4.0 4.5 5.0 5.5  6.0 6.06  3.0  4.5  5.5 6.0 7.0 7.5 8.0  9.0 9.09  4.0  5.5  6.5  7.5  8.5  9.5  10.0  11.0  11.5 12  5.0  6.5  8.0  9.0  10.0  11.0  12.0  13.0  13.5 15  5.5  7.0  9.0  10.0  11.5  12.5  13.5  14.5  15.0 18  6.0  8.0  9.5  11.0  12.5  13.5  14.5  15.5  16.5 21  6.5  8.5  10.5  12.0  13.5  14.5  16.0  16.5  17.5 24  6.5  9.0  11.0  13.0  14.5  15.5  17.0  18.0  19.0 27  7.0  9.5  11.5  13.5  15.0  16.5  18.0  19.0  20.0 30  7.5  10.0  12.0  14.0  16.0  17.0  18.5  20.0  21.0 40  8.0  11.0  13.5  16.0  18.0  19.5  21.0  22.5  23.5 50  8.5  12.0  15.0  17.5  19.5  21.5  23.0  25.0  26.0 60  8.5  12.5  15.5  180  21.0  23.5  25.0  27.0  28.0 80  9.0  13.5  17.0  20.0  23.0  25.5  28.0  30.0  31.5 100  9.0  14.0  18.0  21.5 24.5 27.5 30.0  32.5  34.5 120  9.0  14.0  18.5  22.5 25.5 28.5 31.5  34.5  37.0 

No Limit  9.0  14.5  19.0  23.5  27.0  30.0  34.0  36.0  39.0    

  Enclosing rectangle 18m high 3  2.0  2.5  3.5 4.0 5.0 5.0 6.0  6.5 6.56  3.5  4.5  5.5 6.5 7.5 8.0 9.0  9.5 10.09  4.5  6.0  7.0  8.5  9.5  10.0  11.0  12.0  12.5 12  5.0  7.0  8.5  10.0  11.0  12.0  13.0  14.0  14.5 15  6.0  8.0  9.5  11.0  12.5  13.5  14.5  15.5  16.5 18  6.5  8.5  11.0  12.0  13.5  14.5  16.0  17.0  18.0 21  7.0  9.5  11.5  13.0  14.5  16.0  17.0  18.0  19.5 24  7.5  10.0  12.0  14.0  15.5  16.5  18.5  .19.5  20.5 27  8.0  10.5  12.5  14.5  16.5  17.5  19.5  20.5  21.5 30  8.0  11.0  13.5  15.5  17.0  18.5  20.5  21.5  22.5 40  9.0  12.0  15.0  17.5  19.5  21.5  23.5  25.0  26.0 50  9.5  13.0  16.5  19.0  21.5  23.5  26.0  27.5  29.0 60  10.0  14.0  17.5  20.5  23.0  26.0  27.5  29.5  31.0 80  10.0  15.0  19.0  22.5  26.0  28.5  31.0  33.5  35.0 100  10.0  16.0  20.5  24.0  28.0 31.0 33.5  36.0  38.5 120  10.0  16.5  21.0  25.5  29.5 32.5 35.5  39.0  41.5 

No Limit  10.0  17.0  22.0  26.5  30.5  34.0  37.0  41.0  43.5    

Page 57: GHANA BUILDING CODE - PART 03.pdf

57  

Table 3.2.8B (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for unprotected percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 21m High3  2.0  3.0  3.5 4.5 5.0 5.5 6.0  6.5 7.06  3.5  5.0  6.0 7.0 8.0 9.0 9.5  10.0 10.59  4.5  6.5  7.5  9.0  10.0  11.0  12.0  13.0  13.5 12  5.5  7.5  9.0  10.0  12.0  13.0  14.0  15.0  16.0 15  7.0  8.5  10.5  12.0  13.5  14.5  16.0  16.5  17.5 18  7.5  9.5  11.5  13.0  14.5  16.0  17.0  18.0  19.5 21  8.0  10.0  12.5  14.0  15.5  17.0  18.5  20.0  21.0 24  8.5  10.5  13.0  15.0  16.5  18.0  20.0  21.0  22.0 27  9.0  11.5  14.0  16.0  18.0  19.0  21.0  22.5  23.5 30  10.0  12.0  14.5  16.5  18.5  20.5  22.0  23.5  25.0 40  11.0  13.5  16.5  19.0  21.5  23.0  25.5  27.0  28.5 50  11.5  14.5  18.0  21.0  23.5  25.5  28.0  30.0  31.5 60  12.0  15.5  19.5  22.5  25.5  28.0  30.5  32.5  33.5 80  12.0  17.0  21.0  25.0  28.5  31.5  34.0  36.5  38.5 100  12.0  18.0  22.5  27.0 31.0 34.5 37.0  40.0  42.0 120  12.0  18.5  23.5  28.5 32.5 36.5 39.5  43.0  45.5 

No Limit  12.0  19.0  25.0  29.0  34.5  38.0  41.5  45.5  48.0      Enclosing rectangle 24m high 

3  2.0  3.0  3.5 4.5 5.0 5.5 6.0  7.0 7.56  3.5  5.0  6.0 7.0 8.5 9.5 10.0  10.5 11.09  5.0  6.5  8.0  9.5  11.0  12.0  13.0  13.5  14.5 12  6.0  8.0  9.5  11.5  12.5  14.0  15.0  16.0  16.5 15  6.5  9.0  11.0  13.0  14.5  15.5  17.0  18.0  19.0 18  7.5  10.0  12.0  14.0  15.5  16.5  18.5  19.5  20.5 21  8.0  10.5  13.0  15.0  16.5  18.0  20.0  21.0  22.0 24  8.5  11.5  14.0  16.0  18.0  19.5  21.0  22.5  24.0 27  9.0  12.5  15.0  17.0  19.0  20.5  22.5  24.0  25.5 30  9.5  13.0  15.5  18.0  20.0  21.5  23.5  25.0  26.5 40  11.5  14.5  18.0  20.5  23.0  25.0  27.5  29.0  30.5 50  12.0  16.0  19.5  22.5  25.5  27.5  30.0  32.0  33.5 60  12.5  17.0  21.0  24.5  27.5  30.0  32.5  35.0  36.5 80  13.5  18.5  23.5  27.5  31.0  34.5  37.0  39.5  41.5 100  13.5  20.0  25.0  29.5  33.5 37.0 40.0  43.0  45.5 120  13.5  20.5  26.5  31.0  36.0 39.5 43.0  46.5  49.0 

No Limit  13.5  21.0  27.5  32.5  37.5  42.0  45.5  49.5  52.0    

Page 58: GHANA BUILDING CODE - PART 03.pdf

58  

Table 3.2.8B – (contd.)  

Width of rectangle in metres 

Distance in metres from relevant boundary for percentage not exceeding

20  30  40  50  60  70  80  90  100 

  Enclosing Rectangle 27m High3  2.0  3.0  4.0 4.5 5.5  6.0  6.5  7.0  7.5 

6  3.5  5.0  6.5 7.5 8.5  9.5  10.5  11.0  12.0 

9  5.0  7.0  8.5  10.0  11.5  12.5  13.5  14.5  15.0 

12  6.0  8.0  10.5  12.0  13.5  14.5  16.0  17.0  17.5 

15  7.0  9.5  11.5 13.5 15.0  16.5  18.0  19.0  20.0 

18  8.0  10.5  12.5 14.5 16.5  17.5  19.5  20.5  21.5 

21  8.5  11.5  14.0  16.0  18.0  19.0  21.0  22.5  23.5 

24  9.0  12.5  15.0  17.0  19.0  20.5  22.5  24.0  25.5 

27  10.0  13.0  16.0  18.0  20.0  22.0  24.0  25.5  27.0 

30  10.0  13.5  17.0  19.0  21.0  23.0  25.0  26.5  28.0 

40  11.5  15.5  19.0  22.0  24.5  26.5  29.0  30.5  32.5 

50  12.5  17.0  21.0  24.0  27.0  29.5  32.0  34.5  36.0 

60  13.5  18.5  22.5  26.5  29.5  32.0  35.0  37.0  39.0 

80  14.5  20.5  25.0  29.5  33.0  36.5  39.5  42.0  44.0 

100  15.5  21.5  27.0  32.0  36.5  40.5  43.0  46.5  48.5 

120  15.5  22.5  28.5  34.0  39.0  43.0  46.5  50.5  53.0 

No Limit  15.5  23.5  29.5  35.0  40.5  44.5  48.5  52.0  55.5 

  3.2.9 Separating Walls  3.2.9  (1)  Except as provided in (2) any separating wall shall be imperforated and shall form a  

    complete vertical separation between any buildings separated (including any roof space therein). 

 (2)    Nothing in (1) shall prohibit. 

 (a) The  passage  through  a  separating  wall  of  a  pipe,  if  the  pipe  complies  with 

subsection 3.2.13 or FIG. 3.2.9A  

(b) an opening  in a separating wall which  is necessary as means of egress from fire,  if the opening is fitted with a door which – 

 

Page 59: GHANA BUILDING CODE - PART 03.pdf

59  

    (i) complies with the requirements of subsection 3.2.12; and  

    (ii) has fire resistance which is not less than the period required by subsection 3.2.4 for            the separating wall. 

       

 

Page 60: GHANA BUILDING CODE - PART 03.pdf

60  

(3) Except as provided in (4), any separating wall which forms a junction with a roof shall be carried above the upper surface of the covering of that roof to a distance of not less than 375mm (measured at right angles to such upper surface).  FIG. 3.2.9B 

 (4) A separating wall shall not be required to comply with the provisions of (3) 

 (a) if the buildings separated by the separating wall are so constructed that: 

     (i)   any part of the roof which is within 1.5m of the separating wall is designated AA,        AB and AC; and       (ii)  the deck of such part of the roof is of solid or hollow slab construction of non‐       combustible material; and  

    (iii)   the junction between the separating wall and such roof is fire‐stopped or  

(b) if –      (i)   each of the buildings separated by the separating wall is of occupancy group R,        B or A, and       (ii)  neither building exceeds 12.5m in height; and      (iii)  any part of the roof which is within 1.5m of the separating wall is covered with        non‐combustible material; and  

(v) the junction between the separating wall and the roof covering  is fire‐stopped. FIG. 3.2.9C 

 (5) If any external wall  is carried across the end of a separating wall, such external wall and 

separating  wall  shall  be  bonded  together  or  the  junction  of  such  walls  shall  be  fire‐stopped.  

(6) Any combustible material which is built into or carried through, across the end of or cover the top of a separating wall shall not be of such a type or used in such a way as wall render ineffective the resistance of that to the effects or spread of fire. FIG. 3.2.9D 

 (7) Except  as  provided  in  (8)  any  separating  wall  shall  be  constructed  wholly  of  non‐

combustible materials apart from any surface finish which complies with subsection 3.2.16 and the required fire resistance shall be attained  independently of any such combustible surface finish. 

 (8) The requirements of (7) shall not apply to: 

 (a) A wall separating buildings which are not divided  into compartments and are within 

the limits of size indicated  by the letter ‘X’ in Part 1 of Table 3.2.4A; or  

Page 61: GHANA BUILDING CODE - PART 03.pdf

61  

(b) A wall separating single storey buildings which are not divided into compartments and are within  the  limits  of  size  indicated  by  the  letter  ‘X’  in  Part  2  of  Table  3.2.4A  of subsection 3.2.4. 

 (9)  Any  beam  or  column  forming  part  of,  and  any  structure  carrying  a  separating wall  is 

required  to  be  constructed  of,  non‐combustible materials  shall  itself  comply  with  the requirements of (7) as to non‐combustibility. 

 3.2.10 Compartment Wall and Compartment Floors  3.2.10(1) Any compartment wall or compartment floor shall be imperforated with the exception       of any one or more of the following:  

(a) (i)   in the case of a compartment wall separating a flat or maisonette from any space in common  use  giving  access  to  that  flat  or maisonette,  an  opening  fitted with  a  door which complies with subsection 3.2.11 and has a fire resistance of not less than half an hour; 

   (ii)  in any other case, an opening fitted with a door which complies with the requirements 

of  subsection  3.2.11  and  has  fire  resistance  of  not  less  than  the  minimum  period required by subsection 3.2.4 for the wall or floor. FIG. 3.2.10A 

 (b) an opening for a protected shaft 

 (c) an opening for a ventilation duct  if any space surrounding the duct  is fire‐stopped and the 

duct is fitted with an automatic fire shutter where it passes through the wall or floor.                      FIG. 3.2.10B 

 (d) An opening for a pipe in conformance with subsection 3.2.11.3. FIG. 3.2.10C (e) An opening for a chimney, appliance ventilation duct 

 (f) An opening for a refuse chute 

   (2)   Where a compartment wall or floor joins any compartment wall, external wall or separating wall 

or any  structure enclosing a protected  shaft,  such  structures  shall be bonded  together at  the junction or the junction shall be fire‐stooped. FIG. 3.2.10D 

   (3)   Where any compartment wall forms a junction with a roof, such wall shall be carried above the 

upper  surface of  the  roof  covering  for a distance of not  less  than 375mm, measured at  right angles to the surface of the roof. 

   (4)  Any  combustible material  which  is  built  into  or  carried  through  or  across  the  ends  of  any 

compartment wall or  compartment  shall not be of  such a  type or used  in  such a way as will render ineffective the resistance of that wall or floor to the effect or spread of fire. 

   (5)  Any chimney, appliance ventilation duct or duct encasing one or more flue pipes which passes 

through a compartment floor or compartment wall shall be separated from that compartment 

Page 62: GHANA BUILDING CODE - PART 03.pdf

62  

floor or wall by non‐combustible construction having a fire resistance of not  less than half the minimum fire resistance required by subsection 3.2.4. 

   (6)  Any chimney, appliance ventilation duct or duct encasing one or more  flue pipes which  forms 

part of a  compartment wall  shall be  separated  from any  compartment adjoining  that wall by non‐combustible  construction  having,  at  any  level,  fire  resistance  of  not  less  than  half  the minimum  fire  resistance  required by  subsection 3.2.4  for  the  compartment wall  at  that  level  FIG. 3.2.10E 

   (7)  Any compartment wall or floor which  is required by subsection 3.2.4 to have fire resistance of 

one hour or more shall be constructed wholly of non‐combustible materials apart from:      (i)   any floor finish; or    (ii)   any  surface  finish  to  a  wall  or  ceiling  which  complies  with  the  requirements  of 

subsection 3.2.13;    (iii)  any  ceiling  which  complies  with  the  description  specified  in  the  Table  3.2.5A  to 

subsection 3.2.5 and, apart from any such ceiling, the required fire resistance of the wall or floor shall be obtained without assistance from any combustible material permitted in this subsection. 

 (8)  Any  beam  or  column  forming  part  of,  and  any  structure  carrying  any  compartment wall  or 

compartment floor which is required to be constructed of non‐combustible materials, shall itself comply with the provisions of subsection 3.2.10 (7) as to non‐combustibility. 

  3.2.11 Protection of opening in separating walls, compartment walls and compartment       floors 3.2.11.1 Protected shafts  3.2.11.1(1)         In this subsection, protecting structure means any wall or floor or other structure which                   encloses a protected shaft other than:  

(a) a wall which  forms  part of  an  external wall,  separating wall  or  compartment 

wall; or 

(b) a floor which is also a compartment or a floor laid directly on the ground; or 

(c) a roof.  FIG. 3.2.11A 

    (2)         No  protected  shaft  shall  be  constructed  for  use  for  any  purpose  additional  to  those specified in 3.1.2.1 other than the passage of pipe or duct or as sanitary accommodation or washrooms or both. 

     (3)  Subject  to  the  provisions  of  this  subsection,  any  protected  shaft  shall  be  completely 

enclosed.  

Page 63: GHANA BUILDING CODE - PART 03.pdf

63  

  

Page 64: GHANA BUILDING CODE - PART 03.pdf

64  

     (4)  Except as provided in (5) any protecting structure which is required by subsection 3.2.4 

to  have  fire  resistance  of  one  hour  or  more  shall  be  constructed  wholly  of  non‐combustible  materials  apart  from  any  surface  finish  which  complies  with  the requirements of 3.2.13. 

     (5)  The requirements of (4) shall not apply to protecting structure which  is situated within 

ground storey or an upper storey of a building or part of occupancy Group R consisting of flats or maisonettes if that building has three storeys. 

     (6)  Any beam or  column  forming part of, and any  structure  carrying protecting  structure 

which  is  required  to  be  constructed  of  non‐combustible materials  shall  itself  comply with the provisions of 3.2.11.1 (4). 

     (7)  Any wall,  floor or other structure enclosing a protected shaft but not being protecting 

structure may contain openings in conformance with other provisions of this part of the Code. 

     (8)  There shall be no opening in any protecting structure other than any one or more of the 

following:  

(i)   an opening for a pipe which complies with the provisions of 3.2.11.3  (ii)   an  opening  fitted  with  a  door  which  has  fire  resistance  complying  with  the 

provisions of 3.2.11.1 (9) and 3.2.11.2; (iii)    (if  the  protected  shaft  contains  a  lift),  an  opening which  complies with  the 

provisions of 3.2.11.1 (10); and  (iv)   (if  the protected  shaft  serves as or  contains a ventilation duct), an  inlet  to or 

outlet from that duct or an opening for that duct.    (9)  Any door fitted in an opening in a protecting structure shall have fire resistance for the 

following minimum period:  

(a) If  the protected  shaft  is  in a building of purpose group R,  I or  F and  is wholly or partly above the level of the adjoining ground, not less than half an hour; or  

(b) In any other case either not less than half the period required by other provisions of this part of the code for the protecting structure surrounding the opening or not less than half an hour (whichever is the greater). 

     (10)    Any protected shaft containing a lift or lifts:  

(a) shall  be  ventilated  to  the  external  air  by means  of  one  or more  permanent openings situated at the top of the shaft and having a total unobstructed area of not less than 0.1m2 for each lift in the shaft; and 

 (b) shall not contain any pipe conveying gas or oil or any ventilating duct; and  

Page 65: GHANA BUILDING CODE - PART 03.pdf

65  

(c) may have  an opening  in  its protecting  structure  for  the  passage of  the  cables operating  the  lift  into  the  room  containing  the  lift motor; provided  that  if  the opening is at the bottom of the shaft the opening shall be as small as practicable. 

 (11)  (a)  If a protected shaft serves as or contains a ventilating duct:  

(i) the duct shall be fitted  internally with automatic fire shutters so constructed at such intervals and in such positions as may be necessary to reduce so far as practicable  the  risk  of  fire  spreading  from  a  compartment  to  any  other compartment; 

 (ii)  the  duct  shall  not  be  constructed  of,  or  lined  with,  any  material  which 

substantially increases such risk.  

(b)   In addition,  in  the case of a protected shaft containing a ventilating duct,  the shaft shall be constructed with additional barriers to fire between the duct and the shaft as may be necessary  to  reduce, so  far as practicable,  the  risk of  fire spreading  from a compartment to any other compartment. 

   (12)   If a protected shaft consists of a stairway, it shall not contain any pipe conveying gas or oil 

or any ventilating duct. FIG. 3.2.11B    

3.2.11.2 Fire Resistant Doors  

(1) General:  

This subsection applies  to any door which  is  required by  the provisions of  this part of  the code to have a fire resistance. 

 (2) In this subsection: 

 “automatic self‐closing device” does not include rising butt hinges except as provided in (6): and “electric‐magnetic or electro‐mechanical device susceptible  to smoke”  refers only  to any such device which will allow the door held open by  it to close automatically upon the occurrence of each or any one of the following: 

 (i) detection of smoke by automatic apparatus suitable in nature, quality and location;  (ii) natural operation of a switch fitted in a suitable position  (iii) failure of a electricity supply to the device apparatus or switch;  (iv) if a fire alarm system is installed in the building, operation of that system. 

 

Page 66: GHANA BUILDING CODE - PART 03.pdf

66  

    (3) (a)  except  as  permitted  in  (8)  any  fire  resisting  door  shall  be  fitted with  an  automatic  self‐

  closing device  (b)  no means of holding any such door open shall be provided other than a fusible link or, if 

the  door  is  so  constructed  and  installed  that  it  can  readily  be  opened manually,  an electro‐magnetic or electro‐mechanical device susceptible to smoke. 

 (c)   no part of a hinge on which any such door is hung shall be made either of combustible 

material or of non‐combustible material having a melting point less than 8000C.  

(4) Except as provided in (5) any door fitted in an opening which is provided as a means of escape   in the event of fire shall be so constructed and installed that it can readily be opened manually   and  shall  not  be  held  open  by  any  means  other  than  an  electric‐magnetic  or  electro‐  mechanical device susceptible to smoke. 

 (5) A door which  is provided as a means of escape  in the vent of fire but which cannot readily be  

  opened manually may be installed if:  

(i)   such a door is fitted with an automatic self‐closing device and is held open by a fusible link; 

 

Page 67: GHANA BUILDING CODE - PART 03.pdf

67  

(ii)   the manually openable door has fire resistance of not less than half an hour; and,  

        (iii)  the required fire resistance is achieved by the two doors together.  

(6) Any door to which reference is made in 3.2.10 (1)a or 3.2.11.4(3)b shall be either single leaf door swinging  in one direction only or a double  leaf door each  leaf of which swings  in the opposite direction from the other leaf. FIG. 3.2.11.2A 

 (7) Any door which is fitted in protecting structure and is not required by the provisions of       

  3.2.11.1 (9) to have a resistance of more than half an hour may consist of any single or double      leaf door, other  than  a double  leaf door, both  leaves of which  swing  in one  and  the  same   direction and have rebated meeting stiles if:  

 (a) the door opens into a hall, lobby or corridor enclosed by walls or partitions having fire 

resistance of not less than  half an hour; and  

(b) the clearance between the leaf or leaves of any such doors and its frame and between the leaves is as small as is reasonably practicable. FIG. 3.2.11.2B 

 (8) A door which is not fitted with self‐closing device may be installed in an opening on the    

  structure which encloses a protected shaft containing exclusively a lift or lifts if either:  

(a) the door has  fire‐resistance  for a period of not  less  than half an hour and  there  is also  installed, so as to close the same opening, another door which is fitted with an automatic self‐closing device,  is held open by a  fusible  link and has  fire resistance  for a period not less than prescribed by the relevant provisions of this part of the code  for the structure surrounding the opening; or FIG. 3.2.11.2C   

(b)  (unless the opening  is  in compartment wall and  is one of two openings provided at  the same  level to allow access to a  lift  from different sides), the door has  fire resistance  for period not less than that prescribed by relevant provisions of this part of the code for the structure surrounding the opening. FIG. 3.2.11.2D 

  3.2.11.3  Penetrating of elements of structure by Pipes  

(1) In this subsection ‘Pipe’   

(a) excludes  flue pipes, ventilation pipes, ventilation ducts and any pipes which contains or convey heat or smoke.  

(b) includes vent pipe to drainage system, vent pipe to soil system, vent pipe to waste system and pipe fittings and accessories. 

(2) Subject to the provisions of (3) and (5) the nominal internal diameter of the part of  a pipe which passes through: (i)   an opening in a separating wall; or 

Page 68: GHANA BUILDING CODE - PART 03.pdf

68  

(ii)  an opening  in a compartment wall or compartment floor other than any such opening which is wholly enclosed within a protected shaft; 

(iii)  an opening in protecting structure shall not exceed the relevant dimensions prescribed in Table 3.2.11.3A.  FIG. 3.2.11.3A 

 (3) If on either side of the structure penetrated and within a distance of 1m  (measured along 

the  pipe)  from  the  point  of  penetration,  the  pipe  which  penetrates  the  structure  is  of specification  (a)  and  is  connected  to  a  pipe  of  specification  (b)  or  (c),or  the  pipe  is  of specification  (b)  and  is  connected  to  a  pipe  of  specification  (c),  the maximum  internal diameter of the pipe shall be determined as though it were of the same specification as the pipe to which it is connected.  

(4) Any opening shall be as small as  is reasonably practicable and shall be fire stopped around the pipe.  

(5) A  pipe  which  forms  part  of  an  above  ground  drainage  system  comprising  pipes  which comply with specification  (b)  in Table 3.2.11.3A and have a nominal  internal diameter not exceeding 150mm  in the case of a stack‐pipe or 100mm  in the case of a branch pipe may pass  through  an  opening  in  a  separating  wall  between  houses  or  an  opening  in  a compartment wall or compartment floor between flats or maisonettes if –  

 (a)  the pipe, being a stack pipe, is contained in each storey within an enclosure or, being a         

branch pipe, discharge into a stack pipe contained within an enclosure, formed in part by                  the wall penetrated by the branch pipe; 

                  (b)     any such enclosure: 

   (i)   extends,  in each storey,  from  the  floor  to  the ceiling of  that storey or,  if  the ceiling  is 

suspended beneath a floor, to that floor;   (ii)   has  each  side  formed  by  a  separating wall,  compartment wall  or  external wall  or  by 

casing;   (iii)  has  an  internal  surface,  excluding  any  supporting members, which  complies with  the 

requirements for class 0 specified in subsection 3.2.11.6;     (iv)  has no access panel situated in a bedroom or circulation space; and   (v)   is not used for any other purpose except to accommodate pipes conveying water; 

        (c)  any such casing‐   

   (i)   is  imperforate except for any opening made for the passage of a pipe or fitted with an 

access panel;   (ii)   consists of any material other than sheet metal; and   (iii)  (including any access panel) has a fire resistance of not less than half an hour, and  

             (d) any opening made for the passage of a branch pipe through a floor at the base or top of an                      enclosure (including in the case of a maisonette, any floor within the dwelling) is as small as                      reasonably practicable and is fire‐stopped around the pipe. Figs. 3.2.11.3B, 3.2.11.3C 

  

Page 69: GHANA BUILDING CODE - PART 03.pdf

69  

 

        

Page 70: GHANA BUILDING CODE - PART 03.pdf

70  

      

Page 71: GHANA BUILDING CODE - PART 03.pdf

71  

Table 3.2.11.3A Maximum Nominal Internal Diameter of Pipes 

  

Specification of Pipe  

Maximum nominal internal diameter of pipe  (in mm) 

 Pipe made of any non‐combustible material which if exposed to a temperature of 8000C will not fracture to such an extent as to permit flames or hot gases to pass through the wall of the pipe 

150 

Pipe made of lead or aluminum or alloy thereof; asbestos – cement pipe; or non plasticized polyvinyl chloride pipe complying with BS 4514: 2000/BS EN 1329 Part 1: 2000 

100 if it penetrates structure (other than a separating wall) enclosing a protected shaft not regularly used for the passage of people . 38 in all other cases 

 Pipe made of any other material 

 38 

   3.2.11.4 Stairways  

(1) Every stairway (including any landing thereof) which forms part of a building shall, whether the stairway is internal or external, be constructed of non‐combustible material except –  (a) an internal stairway which is situated – 

 (i)  within a maisonette; or  

                      (ii)  within any storey which comprises elements of structure for which the fire                   resistance required by this part of the code is less than one hour; or  

 (iii) within the ground storey or an upper storey of a building or part of occupancy group        A  which consists of flats or maisonettes if that building has not more than three       storeys or that part is separated as described in 3.2.4 (1)b and has not more than       three storeys; or  

                             (iv) within a building or compartment of occupancy group but not within a protected                                     shaft; or 

(b) an external stairway which  is situated between the ground and a floor or flat roof the level  of which  at  the  head  of  the  stairway,  is  not more  than  6m  above  the  finished surface of the ground adjoining the foot of the stairway. 

   (2)   The provisions of 3.2.11.4(1) shall not prohibit the addition of any combustible material to the 

upper surface of any stairway of landing. FIG. 3.2.11.4A   

Page 72: GHANA BUILDING CODE - PART 03.pdf

72  

  (3)   In any building of occupancy group A which has  three or more  storeys, any  internal  stairway (including any hall or landing associated therewith and any part of a floor which affords passage between  flights  of  the  stairway)  shall  be  separated  from  all  other  parts  of  the  building  by structure complying with the following requirements ‐ 

 (a) the structure shall have fire resistance for not  less than the minimum period required by 

subsection  3.2.4  for  elements  of  structure  forming  part  of  the  storey  in  which  it  is situated; and 

 (b) any opening in the structure which gives access to a habitable room or kitchen shall be fitted 

with a door which has a fire resistance of not less than ½ hour and complies with subsection 3.2.11.2. FIG. 3.2.11.4B 

 (4)   For stairways for physically challenged persons, reference is to be made to Appendix E of Part 4 of           this Code.  

 

  

3.2.12 Fire Stopping  

(1) This subsection applies to all types of construction unless otherwise specified.  

(2) Any fire stopping required by the provisions of this part of the Code shall be so formed and positioned as to prevent or retard the passage of flame. 

 (3) Fire  stops  shall  be  provided  at  floor,  ceiling  and  roof  levels  to  cut  off  completely  all 

concealed horizontal  and  vertical draft openings occurring between  storeys  and between top storeys and roof spaces including  

 (a) Every stud wall and partition at ceiling and floor levels 

 (b) Every stud wall and partition of combustible construction so that the maximum vertical 

dimension of any concealed space is not greater than 3m 

Page 73: GHANA BUILDING CODE - PART 03.pdf

73  

 (c) Every furred wall and partition so that concealed spaces between furring strips are fire 

stopped at the floor and ceiling levels. (d) At the bottom of the cove in every coved ceiling of combustible construction 

 (e) The top and bottom of each run of stairs at ceiling and floor levels, and 

 (f) The top and bottom of every expansion joint between floors and walls in heavy timber 

construction.  

(4) Where combustible floors are laid on wood sleepers on top of slabs in buildings required to be of non‐combustible construction,  the space between  the underside of  the  flooring and floor deck shall be filled with non‐combustible material or fire stopping shall be provided in such a manner that there is no open space in excess of 9m2 in area.  

(5) Where combustible ceiling  finishes are attached  to wood  furring strips  fastened  to a non‐combustible  backing  in  buildings  required  to  be  of  non‐combustible  construction  fire stopping shall be provided in such a manner that there is no open space in excess of 2m2 in between the ceiling finish and the backing. 

 (6) A concealed space erected by a suspended ceiling roof space or unoccupied attic space  in 

buildings of combustible  construction  shall unless  sprinkle  red, be  separated by  fire  stops into draft tight compartments not exceeding  (a) 560m2 in area or 60m in any dimension where materials having a flame‐spread rating of 

class 0 as defined in 3.2.13 are exposed in the space;  

(b) 280m2  in  the area or 18m  in any dimension where materials having a  flame –  spread rating greater than class 0 are exposed in the space. 

 (7) The  concealed  spaces  in  exterior  cornices  including  the  mansard  type,  balconies  and 

canopies  of  combustible  construction  shall  be  fire  stopped  from  the  point  where  such concealed spaces extend across the end of required fire separation.  

(8) Every fire stop shall:  (a) be constructed of: 

 (i)   cement pulp asbestos board, gypsum board or other non‐combustible material 

having a melting point above 7600C such as sheet steel  (ii)   solid lumber not less than 50mm in nominal thickness or  (iii)  12mm  thick plywood with  joints back with  like material or 50mm  thickness of 

lumber not  less  than 25mm nominal  in  thickness with  joints staggered, where the width or height of  the opening or  space  to be  stopped  is  such  that more than 1 piece of 50mm thick lumber is necessary, and  

     

Page 74: GHANA BUILDING CODE - PART 03.pdf

74  

(b) Conform to the appropriate requirements of the sub‐section.    

(9) Access openings through fire stops shall be protected with self‐closing draft‐tight closures of construction equivalent to the fire stop.  

(10)  Where fire stops are pierced by pipes, ducts or other elements or assemblies, the integrity of the fire stop shall be maintained. 

  

       3.2.13 Restriction of spread of flame over surfaces of walls and ceilings  

(1) For  the purposes of this subsection and Table 3.2.13A –  

(a) ‘ceiling’  includes  any  soffit  and  any  roof  light,  skylight, or other part of  a building which encloses and is exposed overhead within a room, circulation space or protected shaft;  

 “circulation space” means any place which  is solely, or predominantly used as a means of access between a room and a protected shaft or between either a room or a protected shaft and an exit from the building or compartment.    ‘small  room’ means a  room which  is  totally enclosed and has a  floor area not exceeding that  specified  in  column  (2)  of  Table  3.2.13A  according  to  the  occupancy  group  of  the building or compartment.  ‘trim’ means any architrave, cover mould, picture rail, skirting or similar narrow member, 

 (b) any  reference  to  the  surface  of  a  wall  shall  be  construed  as  a  reference  to  that  surface 

excluding  the  surface  of  any  other  door,  door  frame  window,  frame, mantel‐shelf,  fitted furniture or trim;  

(c) any  reference  to  the  surface  of  a  ceiling  shall  be  construed  as  a  reference  to  that  surface excluding the surface of the frame of any roof light or skylight; 

 (d) any part of a ceiling which slopes at an angle of 700 or more to the horizontal and is not part of 

a roof light or skylight shall be deemed to be a wall.  

(e) except as provided  in  (f) any  reference  to a surface being of class 0 shall be construed as a requirement that – 

 (i)  the material  of  which  the  wall  or  ceiling  is  constructed  shall  be  non‐combustible 

throughout; or     (ii)   the surface material (or if it is bonded, throughout to a substrate, the surface material 

in conjunction with the substrate) shall if tested in accordance with BS 476: Part 6: A1: 2009  have  an  index  of  performance  (i)  not  exceeding  12  and  sub‐index  (ii)  not exceeding 6; 

 

Page 75: GHANA BUILDING CODE - PART 03.pdf

75  

(f) the face of plastics material having a softening point less than 1200 if tested by method 102C of BS 2782 Part 1: 1978 shall not be regarded as a surface of class 0 unless – 

 (i)   the material is bonded throughout to a substrade which is not a plastics material and 

the material  in conjunction with the substrate satisfies the test criteria prescribed  in subsection e(ii) above; or 

        (ii)     the material satisfies the test criteria prescribed in (ii) above and is used as the lining                      of a wall so constructed that any surface which would be exposed if the lining were                   not present satisfies the said test criteria and is the face of a material other than                                  plastics having a softening point less than 1200C; 

 (g) any  reference  to  a  surface  being  of  a  class  other  than  class  0  shall  be  construed  as  a 

requirement that the wall or ceiling shall be so constructed that a specimen constructed to the same specification,  if exposed to test by fire  in accordance with BS 475: Part 7: 1971, would comply with the test criteria as to surface spread of flame specified in relation to that class.  

(h) the authority having jurisdiction may accept the results of tests based, on test standards other than as described in (g) provided he is satisfied that such alternate test standards will provide a flame spread rating or smoke developed classification comparable to that obtained in (g).  

(i)   in  relation  to a  requirement  that  surface  shall be of a class not  lower  than a  specified class, class 0 shall be regarded as the highest class followed in descending order by class 1, class 2, class 3 and class 4. 

               Class 1 ‐ a surface of very low flame spread          Class 2  ‐ a surface of low flame spread          Class 3  ‐ a surface of medium flame spread          Class 4  ‐ a surface of rapid flame spread  

    Class 0  ‐ an additional class which must comply with one of the                                 alternatives set out in (1) (e). 

 (2) Except as provided  in (3) and (4) the surface of a wall or ceiling  in a room, circulation space or 

protected shaft shall be of a class not lower than that specified in Table 3.2.13A.  

(3) Any part of the surface of a wall in a room may be of any class not lower than Class 3 if the area of that part (or, if there are more such parts, the total area of those parts) does not exceed the lesser of the following –  

(a) Half the floor area of the room; or  Fig. 3.2.13A  

(b) 20m2 in occupancy groups R,E and I;  

(c) 60m2 in occupancy groups B and to S and H. Fig. 3.2.13B 

Page 76: GHANA BUILDING CODE - PART 03.pdf

76  

 (4) Any part of the surface of a ceiling may be of any class not lower than Class 3 if that part of 

the  surface  is  the  face  of  a  layer  of material  the  other  face  of which  is  exposed  to  the external air and – (a) (i)    the ceiling is that of a room in a building or compartment of occupancy groups 

R,E,I,B,M or A or that of a circulation space in a building or compartment of any occupancy group and 

         (ii)   the area of that part does not exceed 2.5m2 and          (iii)  the distance between that part and any other such part is not less than 2.5m; or  

(b) (i)    the ceiling is that of a room in a building or compartment of occupancy group F,                 S or H; and (ii)  the area of that part does not exceed 5m2; and 

           (iii)  the distance between that part and any other such part is not less than 1.8m;            and          (iv)  that part and all other such parts are evenly distributed over the whole area of 

     the ceiling and together have an area which does not exceed 15% of the floor area of the room; or 

 (c) the  ceiling  is  that  of  a  balcony,  verandah,  open  carport,  covered way  or  leading  bay 

which has at least one of its longer sides wholly and permanently open; or  

            (d)  the ceiling is that of a garage, conservatory or out building which has a floor area not                      exceeding 40m2. Fig. 3.2.13C  

 Table 3.2.13A   – Spread of Flame over surface of Walls and Ceilings 

(Surfaces of Walls and Ceilings)  

Occupancy group of building or 

compartment   

(1) 

Maximum floor area of small rooms (in 

m2)   

(2) 

Class of surface for both walls and ceilings (except whereseparately specified) 

Small room(See Col.2) 

 (3) 

Rooms other than small rooms 

 (4) 

Circulation spaces and protected shafts

(5)  

R  4  3 1 0

E,I  4  1 (Wall)     0(Ceiling) 

0

B  30  3 1 0

M  30  3 1 0

F  30  3 1 0

A  30  3 1 0

S,H  30  3 1 0

Page 77: GHANA BUILDING CODE - PART 03.pdf

77  

   

 3.2.14 Roof covering  

Introductory Note (In  this  subsection  two  letters will  be  used  in  the  designation  of  each  roof.    The  first  letter relates to resistance to the penetration of fire as follows:   A – roofs which can withstand penetration for one hour B – roofs which can be penetrated between half‐an‐hour and one hour C – roofs which can be penetrated in less than half‐an‐hour D – roofs which are penetrated in the preliminary test.  The second letter relates to the spread of flame. A – roofs where there is no spread of flame B – roofs where there is not more than 533.4mm spread of flame 

Page 78: GHANA BUILDING CODE - PART 03.pdf

78  

C – roofs where there is more than 533.4mm spread of flame D – roofs which continue to burn for 5 minutes after withdrawal of the flame, or spread more           than 381 mm across the region of burning during the preliminary test).  

3.2.14(1)  No part of the roof of a building which: (a) Has a cubic capacity exceeding 1500m3; or 

(b) Is wholly or partly of occupancy group I,S or H; or 

(c) Is a house in a continuous terrace of more than two houses shall be so constructed as  to be  designated BD, CA, CB, CD, DA, DB, C, DC or DD or  to be  covered with thatch or wood shingles. 

 (2) Any part of a roof which is so designated BA, BB, or BC, shall not be less than 6m from any 

point on a boundary.  

(3) Any part of a roof which is so designated, AD, BD, CA, CB, CC or CD or is covered with thatch or wood shingles, shall be not less than 12m from any point on a boundary unless such part is: 

(a) of an area not exceeding 3m2, and  

(b) separated from any other part of the same roof which  is so designated or covered with  thatch or wood  shingles by an area of  roof which  is at  least 1.5m wide and which is covered by non‐combustible material in which case such designated part or part covered with thatch or wood shingles shall be not less than 6m from any such point. Fig. 3.2.14 

 (4) Any part of a roof which is so designated DA, DB, DC or DD shall be: 

 (a) not less than 22m from any point on a boundary; and 

 (b) of an area not exceeding 3m2; and 

 (c) separated from any other part of the same roof which is so designated by an area of 

roof which is at least 1.5m wide and covered with non‐combustible material. 

Page 79: GHANA BUILDING CODE - PART 03.pdf

79  

                               

Page 80: GHANA BUILDING CODE - PART 03.pdf

80  

Table 3.2.14A ‐ Permitted Roof Covering  

Type of Building  Distance from Boundary  

Designation of Covering  

Exceeding 1500m3  Within 6m  AA AB AC  

 More than 6m but less than 12m 

AA AB AC BA BB  BC (AD – with restriction)  

More than 12m  AA AB AC  AD BA BB BC 

 Terrace of more than 2 houses 

 Within 6m 

 AA AB AC  

 More than 6m but less than 12m 

AA AB AC  BA BB BC (AD – with restrictions) 

More than 12m AA AB AC AD BA BB  BC 

All other buildings 

 Within 6m 

 AA AB AC  

More than 6m but less than 12m 

AA AB AC BA BB BC With restrictions as to area  AO BD CA CB CC CD Thatch or shingles 

More than 12m but less than 22m 

AA AB AC AD BA BB BC BD CA CB CC CD Thatch or shingles 

More than 22m 

AA AB AC AD BA BB BC BD CA CB CC CD Thatch or shingles With restrictions as to area DA DB DC DD 

 * Note:  Table 3.2.14B lists various pitched and flat roof coverings in everyday use        

Page 81: GHANA BUILDING CODE - PART 03.pdf

81  

Table 3.2.14B  ‐ Notional Designation of Roof Covering  

Part I:  Pitched Roofs covered with Slates or tiles  

 Covering material  Supporting structure 

 Designation 

 1. Natural slates  2. Cement pulp asbestos slates  3. Clay tiles  4. Concrete tiles 

 1. Timber rafters with or without      underfelt, sarking, boarding,      wood wool slabs, compressed       straw slabs, plywood, wood or       fibre insulating board  

AA 

    Part II:  Pitched Roofs covered with Preformed Self‐supporting Sheets   Material  

 Construction 

 Supporting structure 

 Designation   

Corrugated sheets of:  (i) galvanized steel  (ii) aluminium  (iii) composite steel and         (iv) cement pulp asbestos   

1. Single skin without underlay     or with underlay of:  (i) cement pulp insulating board  (ii) plasterboard  (iii) fibre insulating board  (iv) wood wool slab  

   Structure  of  timber, steel or concrete 

   

AA 

(v) PVC coated steel   2. Double skin without underlay     or with underlay of:  i) resin‐bonded glass fibre  (ii) bitumen‐bonded glass fibre  (iii) mineral wool slab or    blanket  (iv) polysterene; or   (v) polyurethane  

   Structure  of  timber, steel or concrete 

   

AA 

  

Page 82: GHANA BUILDING CODE - PART 03.pdf

82  

  Part III: Pitched or Flat Roofs covered with Fully Supported Material  

 Covering material 

 Supporting structure 

 Designation 

  

1. Aluminium sheet 

2. Copper sheet 

3. Zinc sheet 

4. Lead sheet 

5. Mastic asphalt 

6. Vitreous enameled steel sheet 

1. Timber joists and:  (i) Tongued and grooved boarding or  (ii) Plain edged boarding 

  

AA 

2. Steel or timber joists with deck of:  (i) wood wool slab 

(ii) compressed straw slab 

(iii) wood or flax chipboard 

(iv) fibre insulating board 

(v) 9.5m plywood 

   

AA 

3.  Concrete  or  clay‐pot  slab  (cast  in situ  or  precast);  or  non‐combustible deck  of  steel,  aluminium  or  cement pulp  asbestos  (with  or  without insulation) 

  

AA 

  3.2.15 Small Garages and Small Open carports  

(1) Except as provided in (7) the following provisions shall apply to any garage which has a floor area not exceeding 40m2.  

(2) If such garage is a separate building and:  

(a) is not less than 2m from any boundary or any house within the boundary; or  Fig. 3.2.15A 

 (b) (being less than 2m from any boundary) complies with the requirement in (3); or 

 (a) (being  less  than  2m  from  any  house  within  the  boundary)  complies  with  the 

requirement of (4).                        It shall not be required to comply with any regulation in this subsection except subsection            3.2.14 and any other provisions expressly referred to in this subsection. 

 (3) Any such garage which  is  less  than 2m  from any boundary shall be so associated  that any 

part  of  an  external  wall  which  is  less  than  2m  from  the  boundary  is  externally  non‐

Page 83: GHANA BUILDING CODE - PART 03.pdf

83  

combustible  and  the  walls  of  the  garage  have  an  internal  surface  which  fulfils  the requirements for Class 0. Fig. 3.2.15B 

 (4) Any  garage which  is  less  than 2m  from  any house within  the  same boundary  shall be  so 

constructed  that  any  part  of  an  external wall which  is  less  than  2m  from  such  house  is externally non‐combustible and the walls of the garage have an internal surface which fulfils the  requirements  for Class 0 but  these  requirements  shall not  apply  if  every part of  any external wall of such house which is less than 2m from the garage – 

 (a) is externally non‐combustible 

(b) has resistance to external fire of not less than half an hour; and 

(c) has no unprotected area which exceeds 0.1m2 or  is  less than 1.5m from any other unprotected area in that part. Fig. 3.2.15C 

   (5) In  the  application  of  (3)  and  (4)  any  exposed  surface  of  a  frame member  forming  the 

structure of a wall shall not be deemed to be part of the internal surface of that wall.  

(6) If  a  garage  to which  (1)  applies  is  attached  to  or  forms  part  of  a  house,  it  shall  be  so constructed that: 

 (a) any floor  immediately over such garage has fire resistance of not  less than half‐an‐hour; 

and  

(b) any wall between such garage and such house has fire resistance of not less than half‐an‐hour; and  

(c) any opening in such wall is: (i)   at  its  lowest point,   not  less  than 100mm above  the  level of  the garage  floor; 

and (ii)  fitted with a door,  shutter or  cover which has  fire  resistance of not  less  than 

half‐an‐hour and which complies with the provisions of sub‐section 3.2.11.2.                      

Fig. 3.2.15D   

Page 84: GHANA BUILDING CODE - PART 03.pdf

84  

  

  

Page 85: GHANA BUILDING CODE - PART 03.pdf

85  

3.2.16 Occupant Load  3.2.16  (1)  The occupant load of every floor area, or part thereof, shall be:  

(a) The number of persons for which the floor area, or part thereof is designed, but  

(b) Unless  otherwise  approved,  not  less  than  the  number  of  persons  that  can  be accommodated on the floor area or part thereof as determined from Table 3.2.16A. 

 (2)            For the purpose of this subsection, mezzanines, tiers and balconies shall be regarded as     

          part of the floor area.  

(3)           Where a room or group of rooms is intended for 2 or more occupancies at different times,           the value to be used from Table 3.2.16A shall be the value which gives the greatest             number of persons for the occupancies concerned. 

  Table 3.2.16A – Forming part of 3.2.16(1)  

Item No.  Type of Use of Floor Area or Part thereof  

Area per Person m2 

   1 2    1 2 3    1 2    1  2  

R ‐ Residential uses:  Houses Dormitories  I ‐ Institutional uses:  Surgical and obstetrical suites Wards containing more than 2 beds Detention quarters  B ‐ Business and Personal Services uses:  Personal service shops Offices  M ‐ Mercantile uses:  Retail sales floors at ground, basement or cellar  Other floors 

(2)  

See Part 7 4.65    

11.61 4.65 11.61 

   

4.65 11.61 

   

2.79  

5.57  

   

Page 86: GHANA BUILDING CODE - PART 03.pdf

86  

Table 3.2.16A – (contd.)  

Item No.  Type of Use of Floor Area or Part thereof  

Area per Person m2 

  

 

 

10 

11 

12 

  

F – Factory (Industrial)  uses: 

Manufacturing or process rooms 

Storage garages 

Storage spaces (warehouse) 

Aircraft hangers 

 

A ‐ Assembly uses: 

Space with fixed seats 

Space with non‐fixed seats 

Stages for theatrical performance 

Space with non‐fixed seats and tables 

Standing space 

Stadia and grandstands 

Billiard rooms 

Classrooms 

School shops and vocational rooms 

Reading or writing rooms or lounges 

Dining, beverage and cafeteria space 

Laboratories in schools 

 U, S ‐ Other uses: 

Cleaning and repair of goods 

Kitchens  

Storage 

 

4.65 

46.45 

27.87 

46.45 

 

(1) 

(1) 

0.74 

0.74 

0.93 

0.37 

0.56 

9.29 

1.86 

9.29 

1.86 

1.11 

4.65 

  

4.65 

9.29 

46.45 

 Col.1 

 2  

 3 

 Notes to Table 3.2.16A 

(1) The occupant load shall be based on the number of seats provided  

(2) The occupant load for dwelling units shall be based on 2 persons per bedrooms or area provided for sleeping 

Page 87: GHANA BUILDING CODE - PART 03.pdf

87  

3.3 SAFETY REQUIREMENTS WITHIN FLOOR AREA   

    Interpretation  

(Section 3.3 regulates safety within floor areas including rooms or other spaces within a building with the exception of service rooms and service spaces that are regulated  in Section 3.5.   The regulations  are  grouped  according  to  the  occupancy  of  the  floor  area;  room  or  space.    The occupancy  of  these  floor  areas  and  other  spaces  is  not  necessarily  the major  occupancy  for which the building is classified.  For example, a building may be classified by major occupancy as an office building, and as such,  the provisions  for structural  fire protection  for office buildings prescribed  in  Section 3.2  apply.   Within  that building,  a  room or  floor  area may be used  for mercantile, institutional, business, residential, industrial or other occupancy.  Life safety for the occupants of any floor area  is dependent  in the first  instance on the use or occupancy of  that  floor area. The  risks  to  these occupants occur  in  the early  stages of a  fire.  These  risks  are  not  the  same  for  different  occupancies  and  must  be  regulated  differently.  Section 3.3 regulates these special life risks within floor areas and these apply regardless of the major occupancy, of the building that contains them.  For example, an assembly  room must  comply with  the  requirements  for assembly occupancy whether  it  is contained  in an office building, hospital, hotel,  theatre,  industrial or other major occupancy).   

3.3.1  Requirements applying to all floor areas  

3.3.1.1 General (1) Where hazardous substances are used in connection with the activities of any occupancy other 

than as provided in subsection 3.3.7 for Groups S and H, the storage, handling and use of such substances shall be in accordance with the appropriate regulation in the fire prevention By‐law.  

(2) Every room or vault where hazardous substances are stored shall be separated  from all other occupancies by a 3‐hour compartment wall. 

 3.3.1.2 Means of Egress (Exits) 

(1)  A means of egress shall be provided from every roof which is intended     for occupancy, and from every podium, terrace, platform or contained open space. 

 (2)  Means  of  egress  to  exists  within  floor  areas  shall  conform  to  subsection  3.3.2  to  3.2.7  in 

addition to requirements of this subsection.  3.3.1.3(1)  Except as permitted in 3.3.2.2(1) each individually rented room or suite of rooms in a floor  

     area occupied by more than 1 tenancy and each dwelling unit shall have exterior doorway at             or near ground level, or a doorway leading to an exterior passage way open to the outdoors,              or to an interior corridor.  From the point where such doorway enters the exterior             passageway or interior corridor it shall be possible to go in opposite directions to each of 2             separate exists, except, as permitted in this section. 

Page 88: GHANA BUILDING CODE - PART 03.pdf

88  

(2) Except  as  otherwise  permitted  in  this  part,  public  corridors  shall  be  separated  from  the remainder of the building by a compartment wall having a fire resistance at least equal to one hour except that:  (a) the  fire‐resistance  need  not  exceed  ¾  hour when  the  fire‐resistance  rating  of  the  floor 

assembly is not required, to exceed ¾ hour; (b) no fire‐resistance rating is required when the floor area is sprinklered and the corridor does 

not serve Groups R,E and I occupancy.  3.3.1.3 Doorways required 

 (1) Any room or suite of rooms occupied by a single tenancy shall have 2 egress doorways placed in 

such  a manner  that  one  doorway  could  provide  egress  from  the  room  or  suite  of  rooms  as required  in 3.3.1.3  if  the other doorway becomes  inaccessible  to  the occupants due  to a  fire which might originate in the room or suite of rooms: (a) where the occupancy is classified as Groups S and H 

(b) which is intended for an occupant load of more than 60 persons; or 

(c) except  for  dwelling  units  where  area  of  a  room  or  suite  of  rooms  or  the  distance measured  from any point within a  room or  suite of  rooms  to  the nearest door opening onto a public corridor, a corridor used by  the public or a corridor serving classrooms or patients  bedrooms  or  opening  directly  to  an  exit  exceeds  the  values  shown  in  Table 3.3.1A. 

  

Table 3.3.1A   Forming part of sentence 3.3.1.3 (1) 

 

Occupancy of Rooms, Suite or Floor Area 

Maximum area of Room,  Suite or floor 

(m2) 

Maximum distance to  Egress Door 

(m) Group R  93 (1)  15 (1) 

Group E,I  70  11 

Group B  186  23 

Group M  139  11 

Group F  186  15 

Group A  139  15 

Group S,H  139  11 

 Column 1 

 2 

 3 

   *Note to Table 3.3.1A       (1) See sentence 3.3.4.2 (6) for dwelling unit.   

Page 89: GHANA BUILDING CODE - PART 03.pdf

89  

    (2)   Where a roof is used or intended for an occupant load of more than 60 persons at least 2  separate  means  of  egress  shall  be  provided  from  the  roof  to  stairs,  designed  in conformance with the requirements for exit stairs, located so that the distance between such stairs conform to the requirements in 3.4.2.2 for exists. 

     (3)  Where  a  podium,  terrace,  platform  or  contained  open  space  is  provided  egress 

requirements  shall  conform  to  the  appropriate  requirements  for  rooms  and  suite  of rooms in sentence (1). 

 3.3.1.5  The total minimum number of doorways from any room containing a high occupant  load shall 

be the same as the number of exits required for a floor area having the same occupant load as determined by Article 3.4.2.4 and such doorways shall be provided with exit signs as prescribed in Article 3.4.6.1. 

 3.3.1.6  (1) Corridors:  The minimum width of every public corridor shall be 1.10m.      (2)  Except as provided  in  sentence 3.3.1.7  (1)  the minimum unobstructed width of every 

corridor  used  by  public  and  every  corridor  serving  classrooms  or  patients  bedrooms shall be 1.10m. 

     (3)  Where a public corridor, corridor used by  the public or corridor serving classrooms or 

patients  bedrooms  contains  an  occupancy,  such  occupancy  shall  not  reduce  the unobstructed width of the corridor to less than its required width. 

     (4)  The minimum headroom clearance of every public corridor and every doorway  in such 

public corridor shall conform to Article 3.4.3.5.      (5)  Every  exit,  public  corridor,  corridor  providing  access  to  exit  for  the  public  or  serving 

patients  bedrooms  or  classrooms  shall  be  equipped  to  provide  illumination  to  an average  level  of  at  least  53.8  lux  at  floor  level  and  at  all  points  such  as  angles  and intersections at changes of level where there are stairs or ramps. 

 3.3.1.7  (1)  Doors:    Except  as provided  in  sentence  (4)  every door  that opens onto  a  corridor or 

other facility that provides access to exit from a room or suite of rooms shall swing on a vertical axis, and where such room or suite of rooms is used or intended for an occupant load  of more  than  60persons  or  for  a  group  of  S  or H  occupancy,  shall  swing  in  the direction of exit travel. 

     (2)  Every door that divides a corridor where such corridor is required to be separated from 

the remainder of the  floor area by separating wall shall swing on a vertical axis  in  the direction of exit travel. 

     (3)  Where  sliding doors are provided  in  locations described  in  sentence  (1),  they  shall be 

designed and  installed to swing on the vertical axis  in the direction of exit travel when pressure is applied.  Such doors shall be identified as a swinging door by means of a sign or decal affixed to the door. 

 

Page 90: GHANA BUILDING CODE - PART 03.pdf

90  

    (4)  In Group E occupancy, a sliding door may be used as an access to exit from a room or suite of rooms where persons are under legal restraint, provided locks are connected to releasing devices operated from a constantly supervised control station. 

 3.3.1.8  (1)  Every door that opens onto, or  is  located within a public corridor or other facility that 

provides access to exit from a room or suite of rooms occupied as a single tenancy, shall   

(a) be at least 810mm in width where there is only 1 door leaf;  

(b) have no single leaf in any multiple leaf door less than 600mm or more than 1200mm in width;  

(c) not open onto a step; and  

(d) be  readily openable without  the use of  keys  in  the direction of  travel  to  an  exit, except that this requirement does not apply to doors of rooms where persons are under legal restraint. 

 3.3.1.9  (1)  Except as provided in 3.3.1.9 (2), ramps, stairways, escalators and passageways used by 

the public as access to exit shall conform with the requirements in subsection 3.4.8.      (2)  Curved or spiral stairs          In a  stairway not  required as an exit, a curved or  spiral  stairway having  treads with a 

minimum average  run of 200mm and having  risers  in  conformance with 3.4.8.6  (1)  is permitted. 

 3.3.1.10 (1)  The Capacity of access to exits          The capacity of any public access to exit shall be based on the occupant load of the floor 

area  served  and  be  computed  on  the  basis  of  the  following  maximum  number  of persons  per  unit  width  as  determined  by  the  method  for  computing  exit  width  in 3.4.3.2. 

 (a) Except as provided in (c), doorways, corridors and passageways shall be assumed to 

accommodate not more than 90 persons per unit of exit width (550mm).  

(b) Except  as  provided  in  (c),  stairways,  ramps  and  escalators  shall  be  assumed  to accommodate not more than 60 persons per unit of exit width (550mm) and 

 (c) Access to exit from a floor area intended for the treatment or care of in firm persons 

shall be assumed to accommodate not more than 30 persons per unit of exit width (550mm). 

     

Page 91: GHANA BUILDING CODE - PART 03.pdf

91  

3.3.1.11 Flame spread rating in corridors  

(1)              The surface of a wall or ceiling of any public corridor or corridor serving classrooms, or          patients bedrooms, shall have a flame‐spread rating of a class not lower than Class 0        (see subsection 3.2.11). 

       (2)  Where a public corridor, a corridor used by the public or a corridor serving classrooms 

or patients bedroom contains an occupancy, the  interior finish materials used on walls or  ceilings  of  such  occupancy  shall  have  a  flame‐spread  rating  in  conformance with 3.3.1.11 (1). 

 3.3.1.12 Guards  

     (1)         A guard at least 1050mm in height shall be provided:  

(a) Around each roof to which access is provided for other than maintenance; (b) At  each  raised  floor, mezzanines,  balcony,  gallery  and  other  locations where  the 

difference in floor elevations is greater than 600mm.  

          (2)   Height of guards: The height of guards on stairs used by the public but not forming part of              a required exit shall be not less than 900mm measured vertically to the top of the guard              from a line drawn through the outside edges of the stair nosings and 1050mm around              landings. 

        (3)  Except  as  provided  in  3.3.1.12(2),  the  size  of  any  opening  through  a  required  guard 

serving a room, stairway or space to which the public is admitted or serving an exterior balcony shall be such as to prevent the passage of a spherical object having a diameter of 100mm  in residential occupancies and 200mm  in other occupancies unless  it can be shown to the satisfaction of the authority having  jurisdiction that the  location and size of openings that exceed these limits do not present a hazardous condition. 

 3.3.1.13   Transparent doorways and Panels  

(1)       Except  as  provided  in  3.3.1.13  (3),  every  glass  or  transparent  door  accessible  to  the   public shall be designed and constructed so that the existence and position of such door    is  readily  apparent  by  attaching  thereto  non‐transparent  hardware,  bare  or  other   permanent fixtures, and when constructed of glass shall be constructed of wired glass or   safety glass conforming to Part 7 of the code. 

       (2)  Except as provided  in 3.3.1.13  (3)  transparent panels used  in an access  to exit which 

because of their physical configuration or design could be mistaken as a means of egress shall be made inaccessible to occupants by barriers or railings. 

         (3)  Sliding  glass  partitions  which  separate  a  public  corridor  or  wall  from  an  adjacent 

occupancy  and  which  are  open  during  normal  working  hours  need  not  conform  to 3.3.1.13 (1) and (2) except that such partitions shall be suitably marked to indicate their existence and position. 

 

Page 92: GHANA BUILDING CODE - PART 03.pdf

92  

      (4)  Glass in doors and side lights that could be mistaken for doors within or at the entrance to dwelling units and in public areas shall conform to the requirements of Part 7 of this Code. 

 3.3.1.14  Exhaust Ventilation Required  

(1) Every building or part of a building in which there may be or may develop, by reason of use of occupancy, dust, fumes, gases, vapour or other various  impurities or contaminants that may  create  a  fire  or  an  explosion  hazard  shall  be  provided with  an  exhaust  ventilation system of approved design. 

       (2)  When substances or conditions that may create an explosion hazard are present as the 

result of the principal use of building space, such space shall be provided with approved explosion  relief devices  and  vents or other protective measures  shall be  taken which conforms to good engineering practice. 

       (3)  All‐explosion relief devices shall be of an approved type.  3.3.1.15  (1)  Except as provided in 3.3.1.15(2) and as otherwise required in this part of the code, the 

portions  of  a  floor  area  or mezzanine  that  do  not  terminate  at  an  exterior  wall,  a compartment wall or a vertical shaft, shall terminate at a vertical fire separation having a  fire‐resistance  rating  at  least  equal  to  that  required  for  the  floor  assembly  that terminates at the separation. 

       (2)  A mezzanine need not terminate at a vertical fire separation where the mezzanine:  

(a) Serves a Group F major occupancy  

(b) Is not considered as a storey  in calculating building height provided the mezzanine does not exceed 460m2 in area and does not contain a Group E occupancy. 

   3.3.2  Residential Occupancy  3.3.2.1    Scope: This subsection applies to floor areas or parts thereof used or intended for use as         residential occupancies.  3.3.2.1  (1)  Sleeping rooms occupied separately and not as suites, and suites or dwelling units in 

hotels and other residential buildings, shall be separated from adjacent rooms, suites and public  corridors  by  a  fire  separation  having  a  fire‐resistance  rating  of  at  least  1‐hour except  that  a  ½–hour  fire  resistance  rating  is  permitted  if  the  floor  assembly  is  not required to exceed ½–hour fire resistance rating (See Table 3.2.4A). 

     (2)   Except for hotels and motels, a door opening onto a public corridor which provides access 

to exit from individually rented rooms, suite of rooms or dwelling units shall be designed not to look automatically. 

 

Page 93: GHANA BUILDING CODE - PART 03.pdf

93  

    (3)   Trunk  rooms  and  storage  rooms  for  the  use  of  tenants  of  residential  occupancies  not forming part of an  individual dwelling unit or sleeping room occupied separately and not as  a  suite  shall be  separated  from  the  remainder of  the building by 1‐hour  separation, except that a ½  ‐hour fire separation  is permitted where the fire‐resistance rating of the floor assembly is not required to exceed ½ ‐hour. 

     (4)   Except as provided in (5) every dwelling unit containing more than 1 storey shall have an 

exit  or  public  access  to  exit  from  the  uppermost  storey  and  the  lowest  storey  of  the dwelling unit. 

     (5)   A single exit is permitted form a dwelling unit where the uppermost floor level is not more 

than 4.5m above the floor level adjacent to the exit provided such exit is an exterior door leading directly from a storey of the dwelling unit at or near ground level. 

  3.3.2.2 (1)  In buildings of  residential occupancy  and not more  than 3  storeys  in building height,  a 

doorway  from  a  habitable  room  is  permitted  to  open  directly  into  an  exit  stairway provided the provisions of 3.2.11.4 (3) are complied with.     

     (2)  A doorway from a dwelling unit may open onto an interior corridor served by a single exit, 

or an exterior balcony served by a single exit stairway, provided each dwelling unit has a second and separate means of egress. 

 3.3.2.3      Flame‐Spread‐Rating: Interior finish material used on the wall or ceiling of every room or 

space used or  intended  to be used  for  residential occupancy  shall have a  flame‐spread‐rating complying with the provisions of 3.2.13. 

 3.3.2.4           Dead‐end Corridors: Except for corridors served by a single exit as described in 3.3.2.2(2) a   

dead‐end public  corridor  is permitted only  if  it does not exceed 6m  in  length measured from the end of the corridor to the nearest exit.  Such dead‐end corridors shall contain no door  openings  except  entrance  doors  to  individually  rented  rooms,  suite  of  rooms  or dwelling units located so that it is not necessary to pass more than 2 doors in travelling to the nearest exit. 

  

 3.3.2.5    Partitions within dwelling units  

(1)   In every building required to be of non‐combustible construction, partitions of         combustible construction as described in 3.3.2.5 (2) may be used within dwelling units. 

   (2)    Partitions of combustible construction referred to in 3.3.2.5 (1) shall be limited to wood 

studs covered on both sides by non‐combustible cladding or gypsum wall board except that such cladding or wall board may be covered with paint. 

   (3)    Storage  lockers  in storage rooms shared by more than 1 tenant may be constructed of 

wood in building required to be of non‐combustible construction.  

Page 94: GHANA BUILDING CODE - PART 03.pdf

94  

3.3.2.6      Second Control: Walls and floors separating dwelling units shall be designed and            constructed to restrict sound transmission in conformance with Part 7 of this Code.  3.3.2.7      Guards: Guards around balconies in building of residential occupancy shall be designed so          that no member, attachment or opening located between 100mm and 900mm above the          balcony will facilitate climbing.   3.3.3  Institutional Occupancy  3.3.3.1  Scope: This subsection applies to floor areas or parts thereof used or intended for use as      institutional occupancies.  3.3.3.2    (1)    Except for sleeping rooms and patients bedrooms within a suite, sleeping rooms and  

patients bedrooms shall be separated from adjacent rooms or suites by a fire separating having a fire‐resistance rating of at least 1 hour. 

       (2)    Except  for  corridors  within  suites,  corridors  used  by  the  public  or  serving  patients 

bedrooms or sleeping rooms shall:  

(a) Be  separated  from  the adjacent  rooms or  suites by a  fire  separation having a  fire rating as required in 3.3.3.2 (1).  

(b) Having surface finishes with a flame spread rating conforming to Table 3.2.13A.  

(2) Access to exit from a room or suite may be by a dead‐end corridor provided the room or suite has a second and separate means of egress.  

 3.3.3.3   The fire separation required between institutional occupancy (Group C) and a repair garage                 shall have no openings.                 3.3.3.4  Flame‐spread rating: The interior finish of walls and ceilings shall have a flame‐spread rating               conforming to the provisions of subsection 3.2.13.   3.3.3.5  Separated Zones in Floor Areas  

(1) Every floor area used or intended to be used for patients in bed or inform persons shall be   divided  into 2 or more zones separated by a fire separation  in such a manner that the   occupants in every zone have access to 2 exits either directly or through adjacent zones. 

       (2)     Fire separations between zones shall have a fire resistance rating of at least 1 hour.        (3)    Doors  acting  as  closures  in  fire  separations  between  zones  shall  be  designed  and 

installed to retard the passage of smoke.  

Page 95: GHANA BUILDING CODE - PART 03.pdf

95  

      (4)     Every zone shall accommodate,  in addition to  its own occupants, the occupants of the largest adjacent zone in a floor area determined by the requirements for horizontal exits in subsection 3.4. 

       (5)    The  travel  distance  from  any  point  within  each  zone  to  an  adjacent  zone  shall  not 

exceed 30m.  3.3.3.6    Corridors  

(1) Every corridor in which it is necessary to move patients in beds shall be at least 2.4m wide.        (2)    Paired doors in corridors shall:  

(a) swing in opposite directions, the right‐hand door swinging in the direction of travel; and 

(b) be at least 1.1m wide and 2.1m high to permit movement of beds.  

 3.3.4  Business and Personal Services Occupancy  3.3.4.1  Scope: This subsection applies to floor areas or parts thereof used or intended for use as        business and personal services occupancies.  3.3.4.1  (1) Partitions: In every building required to be of non‐combustible construction, partitions of      combustible construction as described in (2) may be used within floor areas used or intended to      be used for a business or personal services occupancy where the partitions are not required      to act as fire separations. 

 (a) where the floor area is sprinklered; or  

 (b) within  spaces  having  an  area  not  more  than  1000m2  where  such  spaces  are 

separated from the remainder of the floor area by at least 1 hour fire separation of non‐combustible construction. 

       (2)  Partitions of combustible construction referred to in (1) shall be limited to: 

(a) wood  studs  covered  on  both  sides  by  non‐combustible  cladding  or  gypsum wall board, except that such cladding or wall board may be covered with paint; 

(b) glass in wood sash; or (c) solid lumber not less than 50mm thickness. 

 3.3.4.3  Frame Spread Rating: Interior finish material used on the wall of every room or space used or      intended to be used for business and personal services occupancy shall be of Class 0.  3.3.4.4  Dead‐end public corridors are permitted in Group B occupancies provided the areas      served by the corridor have a second and separate means of egress or provided:    

Page 96: GHANA BUILDING CODE - PART 03.pdf

96  

(a) the occupant load served by the dead‐end corridor does not exceed 30 persons;  

(b) door openings other  than entrance doors  to  individually  rental  rooms or  suites  are not, located in the dead‐end portion that serves as access to exit; 

 (c) the  travel  distance  from  the  most  remote  point  of  the  dead‐end  portion  to  the 

nearest exit does not exceed 9m in length;  

(d) the   doors  in  the dead‐end portions  are  located  so  that  it  is not necessary  to pass more than 2 doors in travelling to the nearest exit and; 

 (e) the doors  in the dead‐end portions are with self‐closing devices and designed not to 

lock automatically.   

3.3.5  Mercantile Occupancy  3.3.5.1  Scope: This subsection applies to floor areas or parts thereof used or intended for use as      mercantile occupancies.  3.3.5.2 Partitions 

(1) In  every  building  required  to  be  of  non‐combustible  construction,  partitions  of combustible construction as described  in  (2) may be used within  floor areas  intended  for mercantile occupancy where the partitions are not required to act as fire separations:  (a) where the floor area is sprinklered; or (b) where  a  floor  area  comprising  a  single  tenancy  does  not  exceed  1000m2  and  is 

enclosed by a 1 hour fire separation of non‐combustible construction.  

      (2)  Partitions of combustible construction referred to in (1) shall be limited to:  

(a) wood studs covered on both sides by non‐combustible cladding or gypsum wall board – except that such cladding or wall board may be covered with paint; 

(b) glass in wood sash; or (c) solid lumber not less than 50mm nominal thickness. 

  3.3.5.3    Flame Spread Rating: Interior finish used on the wall or ceiling of every room or space used or        intended to be used for mercantile occupancy shall have a flame‐spread rating of Class 0.  3.3.5.4    Posts or Turnstiles: In any mercantile occupancy no obstructions such as posts or turnstiles        shall be placed so as to restrict the width of a normal means of egress from a floor area or part       of a floor area to less than 750mm unless an alternative means of egress is provided adjacent        to and is plainly visible from the restricted egress.  3.3.5.5    Dead‐end public corridors are permitted in mercantile occupancies provided the areas served                   by such corridors have a second and separate means of egress.  

Page 97: GHANA BUILDING CODE - PART 03.pdf

97  

3.3.6  Factory (Industrial) Occupancy  3.3.6.1  Scope: This subsection applies to floor areas or parts thereof used or intended for use as      industrial occupancies.  3.3.6.2  Fire Separation: Every process room where hazardous substances are used or intended to be      used shall be separated from the remainder of the building by a 2‐hour fire separation.  The      authority having jurisdiction may waive the requirement for such separation where approved      fire extinguishing equipment is installed.  3.3.6.3 Spaces below grade:                  (1) Basements or cellars shall not be used for the storage, manufacture or handling of volatile               solids, liquids or gases that generate explosive air‐vapour mixtures or for processes that             involve explosive dusts.        (2)  Entrances  and  exists  to  basements  cellars  and  rooms  containing  building  services  in 

buildings  involving  the  storage,  manufacture  or  handling  of  volatile  materials  that generate explosive air‐vapour mixtures or processes that produce explosive dusts shall be separated form the other parts of the building.   Such basements, cellars and rooms shall be separated from other parts of the building with a vapour tight separation. 

 3.3.6.4 Exterior Wall Openings:  Where any storey of a building classified as Group S or H major              occupancy is required to be separated from the storey above or below a fire separation, every              opening in an exterior wall located vertically above another opening shall be separated by apron                or spandrel walls at least 90mm in height or by a canopy at least 90mm wide at each floor level               and such apron, spandrel or canopy shall have a fire‐resistance rating equivalent to the               construction required for the floor assembly and need not be greater than 1 hour.  3.3.6.5  Flame‐Spread Rating: Interior finish material used on the wall or ceiling of every room or space              used or intended to be used for industrial occupancy shall have a flame‐spread rating of Class 0.  3.3.6.6  Garages     (1)  Where access is provided from a storage garage to a stair tower or elevator lobby serving 

occupancies above the level of a storage garage, such access shall be through a vestibule conforming to 3.3.6.6 (13). 

     (2)  Mechanical  storage  garages  of  not more  than  4  storeys  in  building  height  where  no 

persons other  than parking attendants are permitted above  street  floor  level, need not have a fire separation between exits and the remainder of the building. 

     (3)  Every garage shall be provided with natural or mechanical ventilation in conformance with 

subsection 3.5.3 to prevent excessive accumulation of carbon monoxide, exhaust fumes or flammable and toxic vapours. 

     (4)   The clear height of every storey in a storage garage shall be at least 1.95m.  

Page 98: GHANA BUILDING CODE - PART 03.pdf

98  

    (5)  A continuous curb at  least 150mm  in height and a guard at  least 1050mm  in height shall be provided at every  floor opening and around  the perimeter of every  floor where  the exterior walls are omitted. 

     (6)   The  floor  finish  of  every  garage  shall  be  of  non‐combustible material,  asphalt  or  other 

approved material.      (7)   Only  3  exists  located  remote  from  each  other  need  be  provided  in  storage  garages 

provided persons other than attendants are not permitted above the street floor level.      (8)   Except for a basement in which the floor level is not more than 900mm below grade, or in 

which at least 25 per cent of the total area of the perimeter walls on each storey is open to  the  outdoors  and  distributed  to  provide  cross  ventilation,  every  storey  of  a  storage garage or repair garage located below grade shall be. 

 (9)      Repair garages: A repair garage shall be separated from other occupancies by at least 2‐            hour fire separation. 

              (10)  Storage garages: A storage garage shall be separated from other occupancies by at least a  1         ½ ‐ hour fire separation.              (11) Vestibule Required: Where access is provided through a fire separation between a storage           garage and a Group E or group A occupancy, such access shall be through a vestibule           conforming to 3.3.6.6 (13).              (12) In buildings exceeding 3 storeys in building height where access is provided through a fire‐ 

separation between a storage garage and a Group R or a Group A occupancy such access shall be thorough a vestibule conforming to 3.3.6.6. (13).  

            (13)  Vestibule Requirements: Where access is provided through a vestibule as required in                       sentences (1), (11), and (12), the vestibule shall: 

 (a) be at least 1.8m in length; (b) naturally ventilated to outside air in an approved manner, or mechanically ventilated 

at the rate required by article 3.5.3.3.; (c) have  the openings between  the vestibule and or adjoining occupancy provided with 

self‐closing doors having no hold‐open devices.  

3.3.6.7 Dispensing of Petrol  

(1) Facilities for the dispensing of petrol shall not be  installed above any space  intended for    occupancy. 

     (2)  Facilities for the dispensing of petrol shall not be installed in any building except that this 

requirement  does  not  apply  to  a  canopy which  is  open  on  at  least  75  percent  of  its perimeter, or, when approved, to a building of Group A occupancy. 

 

Page 99: GHANA BUILDING CODE - PART 03.pdf

99  

3.3.6.8      Rooms  or  spaces  involving  the  use  of  explosive  substances  shall  be  ventilated  in conformance with 3.3.1.14. 

 3.3.6.9  (1)  Access to exit from a room or suite of rooms containing an industrial occupancy with an 

      occupancy load of more than 30 persons or a high hazard industrial occupancy shall not be through a dead‐end corridor unless there is a second and separate means of egress. 

   3.3.7 Assembly Occupancy  

 3.3.7.1      Scope: This subsection applies to floor areas or parts thereof used or intended for use as 

assembly occupancies.  3.3.7.2    Fire separation required      (1)  Except  as  otherwise  provided  in  this  subsection,  different  occupancies  of  the  same 

occupancy classification, any one of which has an occupant  load exceeding 200 persons, shall be separated from each other by a fire separation having a fire resistance of at least 1 hour except that a fire separation having a fire resistance rating of ¾ ‐ hour may be used where the floor assembly is not required to have a fire resistance rating greater than ¾ ‐ hour. 

     (2)  Where  usable  space  exists  under  tiers  of  seats  in  arena‐type  buildings,  a ¾  ‐  hour  fire 

separation  shall  be  provided  between  such  space  and  the  seats  or  the  space  shall  be sprinklered. 

     (3)  An assembly occupancy shall be separated from a garage by a fire‐separation conforming 

to 3.3.6.6.  3.3.7.3           Flame‐Spread Rating: Interior finish materials used on the wall or ceiling of a room or space 

intended for assembly purposes shall have a flame‐spread rating of Class 0.  3.3.7.4          Fixed Seats  

(1)    Except  for  bench‐type  seats  as  provided  in  3.3.7.9;  3.3.7.11  and  3.3.7.12,  in  places  of    assembly with fixed seats, such seats shall be: 

 (a) attached or secured to the floor, platform or platform riser; 

(b) provided with arms and back; and 

(c) arranged  in  rows  having  an  unobstructed  passage  of  at  least  400mm  measured horizontally  between  plumb  lines  from  the  backs  of  the  seats  in  one  row  and  the edges  of  the  furthest  forward  projection  of  the  seats  in  the  next  row  in  the unoccupied position.  

 (2)       Aisles on the main floor and in the balconies and galleries shall be located so that there are  

  not more than 7 seats between any seat and the nearest aisle, except where: 

Page 100: GHANA BUILDING CODE - PART 03.pdf

100  

(a) a door or doorway  leading directly  to an access exit  is provided  for every 3  row of seats in which case such doors or doorways need not be provided with exit signs; and 

 (b) the number of seats in a row does not exceed 100. 

     (3)   Seating  arrangements  that  do  not  conform  to  the  requirements  of  3.3.7.4  (2) may  be 

approved provided the standard of safety is not reduced and the time required for egress is not increased. 

 3.3.7.5    Aisles      (1)  Except as required in 3.3.7.9, 3.3.7.11 and 3.3.7.12 aisles leading to exits shall be provided 

in places of assembly which contain fixed seats in conformance with 3.3.7.5 (2) and 3.3.7.5 (9). 

     (2)  The minimum clear width of aisle shall not be  less  than 1100mm except  that  the width 

may be reduced to not less than:  

(a) 750mm when serving 60 seats or fewer, and 

(b) 900mm when serving seats on 1 side only.      (3)   Except  in  the  case  of  bleacher  seats,  the minimum  clear width  of  aisles  referred  to  in 

3.3.7.5(2)  shall be measured at  the point  farthest  from an exit, cross aisle or  foyer and shall be  increased  in width 38mm for each 1.5m  in  length toward the exit, cross aisle or foyer. 

     (4)   Aisles shall terminate in a cross aisle, foyer or exit, and the width of such cross aisle, foyer 

or exit shall be at least the required width of the widest aisle plus 50 per cent of the total required width of the remaining aisle that it serves. 

     (5)   Dead‐end aisles shall be not more than 6m in length.      (6)   The length of travel to an exit door by an aisle shall not be longer than 45m.  

(7) Side aisles shall be at least 1100mm wide when seating is provided in conformance with    3.3.7.4 (2) (a) and (b)  

(8) The floor of every aisle shall have a gradient of not more than 1 to 8.  

(9) Steps shall not be placed in any aisle unless the gradient would exceed 1 to 8; such steps     shall conform to the following requirements:  (a) the  passageway  between  rows  of  seats  shall  be  level  at  right  angles  to  the  line  of 

travel; (b) the riser height shall be 115mm; 

Page 101: GHANA BUILDING CODE - PART 03.pdf

101  

(c) the riser height shall not exceed 200mm where not more than 1 riser is used between adjacent  seating platforms and  shall not exceed 200mm where more  than 1  riser  is used; 

(d) where variations in riser height occur;  

(i)    the heights of adjacent risers shall not vary more than 6mm; and  (ii)   treads or any part of a platform shall extend at least 425mm. 

 (e) the width of stair treads between platform shall conform to Article 3.4.8.7; 

 (f) aisle platform where  they extend at  least 425mm  in  the direction of exit  travel may 

slope 6mm in 300mm;  

(g) an  unobstructed  platform  at  least  800mm  square  shall  be  provided  adjacent  to  an aisle where a step is used at the entry to row of seats; and 

 (h) the  location  of  every  riser  is  made  apparent  from  both  directions  of  travel  by 

strategically placed light, contrasting marking stripes or other approved methods.  3.3.7.6  (1)   Corridors used by the public in assembly occupancies or serving classrooms as access to      exists shall:  

(a) be  separated  from  the  remainder of  the building by a  fire‐separation having a  fire‐resistance rating of not less than 1 hour except that;  (i) the  fire resistance need not be greater than ¾ hour where  the  floor assembly  is 

permitted to have a ¾ hour fire resistance rating;  (b) have  surface  finishes with  flame  spread  rating  conforming  to  the  requirements  in 

3.3.1.11 (1) for public corridors.    (2)  Access to exit used by the public or which serve classrooms in assembly occupancies may 

be by  a dead‐end  corridor provided  the  areas  served by  the dead‐end  corridor have  a second and separate means of egress. 

 3.3.7.7  (1)  Every door in a principal access to exit from a room, suite of rooms or floor area of Group 

A occupancy  containing  an occupant  load of more  than 100 persons  shall be equipped with an approved hardware that will release and allow the door to swing wide open when a force of 90N is applied to the device in the direction of the travel to the exit. 

   (2)  A  door  between  a  corridor  and  adjacent  classrooms  providing  access  to  exit  from  the 

classrooms need not be equipped with a self‐closing device where the building does not exceed 3 storeys in building height. 

 3.3.7.8    Access to exit from a room or suite of rooms of assembly occupancy shall not be through a 

dead‐end corridor unless there  is a second and separate means of egress from the room or suite of rooms. 

Page 102: GHANA BUILDING CODE - PART 03.pdf

102  

3.3.7.9    Fixed bench‐type seats without arms    (1)  Where fixed bench‐type seats without arms are provided the seats width per person shall 

be assumed to be 450mm.    (2)   The centre‐to‐centre  spacing between  rows of bench‐type  seats  shall be at  least 75mm 

where back rests are provided and at least 550mm where back rests are not provided.     (3)  There shall be a space of at least 300mm between the back of each seat and the front of 

the seat immediately behind it.    (4)   Except as provided in 3.3.7.4 (2) aisles shall be located so that there are not more than 7 

seats with backs or 20 seats without backs between every seat and the nearest aisle.    (5)   The width of every aisle – serving bench‐type seat shall conform to 3.3.7.5.    (6)   Steps shall not be placed in any aisle unless the gradient would exceed 1 to 8; such steps 

need to have hand rails when the adjacent seating is on the same level.    (7)   Seating  arrangements  that  do  not  conform  to  the  requirements  in  this Article may  be 

approved provided the standard of safety is not reduced and the time required for egress is not increased. 

 3.3.7.10    Height of Guards    (1)  Except  as  required  in  3.3.7.10  (2)  to  (4)  for bleacher  seats,  guards  shall be  installed  in 

outdoor places of assembly with fixed seats so that:  

(a) at the fascia of every box, balcony or gallery where the seats extend to the edge, the height of guards  is at  least 250mm  in  front of  the  seats and at  least 900mm when located at the end of the aisles or at the foot of steps;  

(b) the height or guards along every cross aisle other than those adjacent to the fascia of every box, balcony or gallery  is at  least 650mm except that such guards need not be provided where  the backs   of  the seats along  the  front side of  the aisle are at  least 600mm above the floor of the aisle; and 

 (c) where  the  seating  is  arranged  in  successive  tiers  and  the  height  of  rise  between 

platforms exceeds 450mm,  the height of guards  is at  least 650mm along  the entire row of seats at the edge of the platform. 

   (2)  The backs and ends of bleacher seats more than 1.2m above the ground or floor that are 

not adjacent to a wall shall be protected with a guard:  

(a) at least 1.05m in height above an adjacent aisle surface of foot rest; and  

(b) at least 0.9m in height above the centre of an adjacent seat board.  

Page 103: GHANA BUILDING CODE - PART 03.pdf

103  

  (3)  If  the  front  of  a  bleacher  is more  than  600mm  above  the  ground  or  floor,  it  shall  be protected with a guard at least 830mm in height above the front foot rest. 

     (4)   The size of any opening in a guard required in (2) and (3) shall be such as to prevent the        passage of a spherical object more than 300mm in size.  3.3.7.11     Outdoor Places of Assembly  

(1) Any outdoor places of assembly and each  tier or balcony  thereof  that has a capacity of    more than: 

   (a) 1000 persons shall have at least 3 separate exits, or 

(b) 4000 persons shall have at least 4 separate exits.  

(2)   In  every  outdoor  place  of  assembly,  every  seat  shall  be  located  so  that  the  travel    distance does not exceed 45m measured along the path of travel from the seat to: 

 (a) the ground, 

(b) an exit, 

(c) an opening to a passageway leading from the seating area, or 

(d) an opening through the seating deck structure such as a portal or vomitory. 

  (3)  Exits from outdoor stadia or grandstands shall be located not more than 22.5m apart. 

  (4)  The capacity of means of egress for outdoor places of assembly shall be based on: 

(a) 1 unit of exit width for each 300 persons for: 

(i) aisles,  (ii) stairs other than exit stairs, and  (iii) ramps and level passageways in vomitories and in exits, and 

 

(b)  1 unit of exit width for each 225 persons for exit stairs. 

  (5)  Aisle in outdoor places of assembly: 

(a) shall be located so that there are not more than 20 seats between any seat and the      nearest aisle.  (b) shall be at least 1.2m in width except that an aisle serving fewer than 60 persons may        be 0.75m in width, and  (c) shall not have steps unless the gradient of the aisle would exceed 1 in 8. 

   

Page 104: GHANA BUILDING CODE - PART 03.pdf

104  

  (6) Except as provided in 3.3.7.12 (1) and (2) where steps are provided in aisles, such steps      shall: 

(a) extend the full width of the aisles, 

(b) have risers not exceeding 230mm in height, and 

(c) have treads with a run of at least 250mm. 

 3.3.7.12    Bleachers  

(1) Where steps are provided in aisles of bleachers of the telescopic type such steps shall:  (a) have risers not exceeding 250mm, and 

(b) have risers with a run of at least 275mm.    (2)  When  the vertical distance between  seating platforms  in bleachers exceeds 275mm, an 

intermediate  step  shall  be  provided  the  full  width  of  the  aisle,  and  proportioned  to provide 2 equal risers between platforms and when the vertical distance between seating platforms exceeds 450mm, 2  intermediate  steps  shall be provided  the  full width of  the aisle so that there are 3 equal risers between platforms. 

   (3) Where  the passageway between  rows of  seats  is not a closed deck,  footboards  shall be 

provided so that:  

(a) the  total width  of  the  footboards  shall  be  not  less  than ¾  of  the  centre‐to‐centre spacing between rows of seats, and  

(b) the spacing between footboard members shall not exceed 25mm.  3.3.7.13    Libraries  

(1) Where a book storage room in a library exceeds 232.3m2 in area, or where the book stacks exceeds 9m in height or penetrate more than 1 storey:  (a) the book storage room shall be separated from the remainder of the building by a 2‐

hour fire separation, or  (b) the building shall be sprinklered. 

 (2) Open book shelves are permitted above and below a mezzanine floor, in a library building 

provided the height of such book shelves is not more than 2.10m or 75 percent of the floor to ceiling height of the space above or below the mezzanine floor assembly.  

3.3.7.14  Stages for theatrical Performance  

(1) Structural members supporting the floor of any stage for theatrical performances shall be   of  non‐combustible  construction  unless  the  building  is  permitted  to  be  of  combustible construction. 

 

Page 105: GHANA BUILDING CODE - PART 03.pdf

105  

  (2)  A  1‐hour  fire  separation  shall  be  provided  between  every  stage  for  theatrical performances and ancillary spaces, such as workshops, dressing rooms and storage areas. 

  (3)  Every  stage  for  theatrical  performance  and  ancillary  spaces,  such  as work  storage  and dressing rooms, shall be separated from the audience space by a 1‐hour fire separation, except for a proscenium opening which shall be protected with an approved: 

 (a) unframed asbestos fire curtain when the opening does not exceed 18.29m in width, or (b) semi‐rigid asbestos fire curtain when the opening is more than 18.29m in width. 

   (4)  Every  cement  pulp  asbestos  curtain  as  required  by  (3)  shall  be  operated manually  by 

remote control devices, one on the stage control panel and one on each side of the stage.    (5)  At least 2 vents for the purpose of venting fire and smoke to the outside of a building shall 

be provided  above  every  stage designed  for  theatrical performances  and  shall have  an aggregate area of at least 1/8 of the area of the stage behind the proscenium opening; 

 (a) where any  requirement of  (1)  to  (5)  is  incompatible with  the  function of  the  stage, 

other  fire  safety  measures  may  be  substituted  provided  the  authority  having jurisdiction is satisfied that the standard of safety is not reduced. 

 3.3.7.15  Motion Picture Projection Rooms    (1)  This part of the code does not apply to portable motion picture projectors.    (2)  Except  as  provided  in  (1),  every motion  picture  projector,  together with  all  associated 

electrical  devices,  shall  be  operated  within  a  projection  room  separated  from  the remainder of the building by a fire separation having a fire resistance rating of at  least 1 hour. 

   (3) A clear‐space of at  least 750mm shall be provided behind projection equipment  in every 

projection room.    (4) Every projection room shall have at  least 2 doorways with dimensions at  least 750mm  in 

width  and  2.03m  in  height.    Such  doorways  shall  be  separated  by  at  least  1/3  of  the perimeter of the room and shall lead to an access to exit. 

   (5) Doors  installed  in projection  rooms  shall be equipped with  self‐closing devices and  shall 

open outward.    (6) Every projection room shall be equipped with exhaust ventilation of sufficient capacity to 

provide 6 air charges per hour and shall be designed in conformance with good practice.    (7)  Every  shelf,  fixture  and major  item  of  fixed  equipment  in  a  projection  room  shall  be 

constructed of non‐combustible materials.       

Page 106: GHANA BUILDING CODE - PART 03.pdf

106  

 3.4   REQUIREMENTS FOR EXITS  3.4.1  General Requirements    3.4.1.1      (1)  Scope: Exit facilities complying with this section shall be provided to a public thoroughfare                     or   to an approved open space with access to a public thoroughfare from every floor area                     which is intended for occupancy.  

(2) Where more than 1 exit  is required from a floor area, each exit shall be separated from every other exit leading from that floor area. 

                   (3)  Access to exits shall conform to Section 3.3.  3.4.1.2  (1)  Unless otherwise indicated, the requirements of this section shall apply to new      construction.    (2)  Where alterations are made or changes of occupancy occur in an existing building:  

(a) exists  shall  conform  to  this  Part,  except  that  the  authority  having  jurisdiction may        permit  other  arrangements  when  in  his  opinion  safety  to  life  is  not  unduly endangered; and 

(b)  the authority having  jurisdiction may require any deficiency  in exits to be corrected, and may permit  fire escapes as described  in 3.4.8.14  for  this purpose provided such fire escapes serve floor areas. 

 (i) not more than 2 storeys above ground level in Group B occupancies, and  (ii) not more than 5 storeys above ground level for occupancies other than Group B. 

 3.4.1.3  Types of Exits: Subject to the requirements of this section, an exit from any floor area shall be     one of the following, used singly or in combination: 

 ‐ escalator that is capable of moving only in the direction of exit travel 

‐ exterior doorway 

‐ exterior passageway 

‐ exterior ramp 

‐ exterior stairway 

‐ fire escape 

‐ interior passageway 

‐ interior ramp 

‐ interior stairway 

‐ moving walkway that is capable of moving only in the direction of exit travel 

 

Page 107: GHANA BUILDING CODE - PART 03.pdf

107  

3.4.1.4  Restricted Use of Exits 

                 (1) A horizontal exit shall not be permitted as a required exit from a room or floor area having         a high occupant load.    (2)  Horizontal exits shall not comprise more than ½ of the required number of exits from any 

floor area.    (3)  A fire escape (emergency escape route) shall not be erected on any new building.    (4)  A fire escape (emergency escape route) shall not be erected on an existing building unless 

it  can be demonstrated  to  the  satisfaction of  the  authority having  jurisdiction  that  it  is impracticable to provide one or more of the exit facilities in 3.2.14. 

 (5) Glass and  transparent door assemblies accessible  to  the public,  transparent panels, side   

lights and windows  in exits, glass  in exit doors and side  lights  for doors, within and at  the entrance to dwelling units shall conform to the requirements in 3.3.1.13 for such assemblies in access exits. 

 3.4.2  Number and Location of Exits from Floor Areas      3.4.2.1  (1)  Minimum Number Required: Except as provided  in (2) and  in 3.3.2.1 (5), every floor area 

as regulated in 3.4.1.1 shall be served by not fewer than 2 exits.    (2)  Except for dwelling units  floor areas designed for an occupant  load of not more than 60 

persons  in buildings not exceeding 2  storeys  in building height may be  served by 1 exit provided the floor area requirements conform to Table 3.4.2A. 

   (3)  For the purpose of this subsection, travel distance means the distance from any point  in 

the floor area to an exit measured along the path of exit travel, except that when a floor area  is sub‐divided  into suites of rooms or rooms within suites and served by a corridor required to provide a fire separation from such adjacent rooms or suites of rooms or by an exterior passageway, the travel distance shall be measured from the door of such rooms or suites to the nearest exit. 

   (4)  Except for mezzanines, that are not enclosed and are of a size permitted in Table 3.3.1A to 

have a single egress, mezzanines shall be provide with exits on the same basis as required for floor areas in this section. 

          

Page 108: GHANA BUILDING CODE - PART 03.pdf

108  

Table 3.4.2A Forming part of sentence 3.4.2.1 (2) 

                    

 Notes to Table 3.4.2A 

(1) Single exit permitted when such exit is an exterior door or near ground level 

(2) See sentence 3.3.2.4 for dwelling units.  

3.4.2.2  Distance between Exits                   (1) Except where a floor area is divided by a fire separation so that it   is necessary to pass      through it to travel from one exit to another exit, the least distance between 2        required exits from a floor area shall be: 

                      (a) one‐half of the maximum diagonal dimension of the floor area but need not be more        than 9.1m for a floor area having a public corridor serving more than 1 tenant, or  

                       (b) one‐half the maximum dimension of the floor area, but not less than 9.1m for all other        floor areas.    (2)  The  minimum  distance  between  exits  referred  to  in  3.4.2.2  (1)  shall  be  the  shortest 

distance  that  smoke  would  have  to  travel  between  the  required  exits  assuming  that smoke will not penetrate an intervening fire separation. 

 3.4.2.3 Location of Exits  

 (1) Where more than 1 exit  is required from a floor area, such exits shall be  located so that  

  the travel distance to at least 1 exit as described in 3.4.2.1 (3) shall be not more than:  (a) 22.9m in any Group S or H occupancy 

Occupancy of Floor Area  Maximum Floor Area (m2)  

Maximum Travel Distance  

R  95 (1) (2)  15 

E,I  70 (1)  10 

B  185  25 

M  140  15 

F  140  10 

A  140  15 

S,H  185  25 

      

Page 109: GHANA BUILDING CODE - PART 03.pdf

109  

(b) 45.8m in any sprinklered floor area that contains an occupancy other than Group S or 

(c) 38.1m in any Group B occupancy, and 

(d) 30.5m in any other occupancy    (2)  Except for Group S or H occupancy, 3.4.2.3 (1) need not apply if exits are placed along the 

perimeter  of  the  floor  area  and  are  not more  than  61.0m  apart, measured  along  the perimeter provided each main aisle in the floor area leads directly to an exit. 

   (3)  Where more  than 1  exit  is  required,  every  exit  shall be  considered  as  contributing not 

more than ½ the required units of exit width.    (4)  Exits shall be  located and arranged so  that  they are clearly visible or  their  locations are 

clearly indicated and they are accessible at all times.    (5)  Where an assembly hall or theatre has more than 1 balcony or gallery, every exit stair or 

ramp leading from a balcony or gallery above the first balcony shall be separated from any other stairway and in a separate enclosure. 

 3.4.2.4  Except as provided in 3.3.7.11 for outdoor places of assembly, the number of exists from 

each floor area in which there is a high occupant load shall conform to Table 3.4.2B.   

 

Table 3.4.2B 

Forming part of Article 3.4.2.4 

 

Total Number of Persons  Minimum Number of Exits Required  

61 – 600  2 

691 – 1000  3 

Over 1000  4 

    

 

 

 

 

 

Page 110: GHANA BUILDING CODE - PART 03.pdf

110  

3.4.2.4 Exit for covered malls 

  (1)  Every covered mall shall:  

(a) be  served  by  at  least  2  exits  located  remote  from  each  other,  so  that  the  travel distance from any point within the covered mall to a mall exit does not exceed 61m, and  

(b) have  an  unobstructed  pedestrian  travel  space  at  least  3.7m  wide,  parallel  and adjacent to each connected building, and extending to each mall exit. 

   (2)  Exits  from  floor  areas  of  portions  of  buildings  considered  as  separate  buildings which 

adjoin a covered mall shall not comprise more than ½ of the required units of exit width from that floor area. 

   (3) Every  required exit  from a  storey above a  floor area adjoining a covered mall  shall  lead 

directly to the outdoors.    (4) Required exits from a covered mall shall not empty into another such covered mall.   3.4.3  Width and Height of Exits 

 3.4.3.1  Exit Width    (1)  The aggregate width of required exits shall be at least the value computed in accordance 

with 3.4.3.2 and 3.4.3.3.    (2)  Except as provided  in 3.4.3.1(3) to 3.4.3.1 (8) and  in 3.4.8.14(6), the clear width of every 

exit shall be at least 910m.    (3) The clear width of any corridor used as an exit shall be at least 1.12m.    (4) The clear width of any exit serving patients in bed shall be at least 1.12m.    (5) The width of an exit stair shall be at  least 1.12m where  the stair serves 1 or more  floor 

areas having a combined occupant load greater than 100 persons.    (6) Every door leaf in an exit doorway shall be:  

(a) not more than 1.22m in width, 

(b) not less than 610mm width where there is more than 1 leaf provided in the width of a 

doorway, and 

(c) not less than 810mm in width if there is only 1 leaf provided in the doorway.    

Page 111: GHANA BUILDING CODE - PART 03.pdf

111  

  (7) The aggregate width of doorways to exit stairways, exit ramps and doorways providing  direct access to the outside from a floor area shall be sufficient to provide the number of units of exit width required to serve the floor area from which they lead. 

   (8) Every doorway, leading from exit stairways and exit ramps in the direction of exit travel  

shall provide at least the number of units of exit width required for exit purpose, but shall not be less than ¾ of the width of the stairway or ramp it serves. 

          3.4.3.2     Width based on occupant load  

(1) For  the purpose of determining aggregate width of  required exits,  the occupant  load of   every  room  or  floor  area  of  the  building  to  be  considered  shall  be  determined  in   conformance with subsection 3.2.16. 

   (2)  The aggregate width of exits  from a  room or  floor area expressed as units of exit width 

(550mm) shall be determined by dividing the occupant  load of the room or floor area by the allowable number of persons per unit of exit width specified in 3.4.3.3. 

    (3)   In determining the width in units of an individual exit, the width of an exit in mm shall be 

divided by 550.   When  the  remainder  is  less  than 300mm,  it  shall not be considered as contributing to the number of units.  Where the remainder is 300mm or more, it shall be considered as  contributing ¼ unit of exit width  in  the  case of  stairs, and ½ unit of exit width in the case of other exit facilities.  

   (4)   Except  as  provided  in  (5)  and  (6),  the  required  units  of  exit width  shall  be  cumulative 

where 2 or more exits converge.      (5)   Except as provided in (6) where exit stair serves 2 or more floorways, one above the other, 

the required units of exit width are not cumulative.    (6)  The required units of exit width for exit stairs that serve 1 or more floor areas containing a 

high occupant load shall be increased by an amount required for the high occupant load, except  that  such  increase need not extend  to more  than 5  storeys beneath  the  storeys with the high occupant loads in high rise buildings. 

  3.4.3.3  Capacity per unit exit width    (1)  The aggregate width of  required exits  shall be  computed on  the basis of  the maximum 

number of persons per unit of exit width as specified in 3.4.3.3 (5).    (2)   The number of persons per unit of exit width shall be assumed to be 30 in determining the 

exit requirements from floor areas containing Group R or Group E occupancies.    (3)   Except as permitted in sentences (2) and (4), the number of persons per unit of exit width 

shall be 90 for exterior exit doors.  

Page 112: GHANA BUILDING CODE - PART 03.pdf

112  

  (4)   The number of persons per unit of exit width for outdoor places of assembly shall conform to Article 3.3.7.11. 

   (5)   Except as provided  in sentences  (2)  to  (4)  the number of persons per unit of exit width 

shall be 60.   3.4.3.4  Reduction of Exit Width    (1)  No  fixture,  turnstile,  or  construction  shall  project  into  or  be  fixed within  the  required 

width of any exit, except as permitted in sentences (2) to (5).    (2)   Exit doors shall be so hung and arranged that when opened they shall neither diminish nor 

obstruct the required width of exit by more than 50mm for each full unit of exit width.  

(3)     Swinging doors in their swing shall not reduce the effective width of exit stairs or landings    to  less than 760mm or reduce the effective width of an exit passageway to  less than the   minimum required width.  

  (4)   No hand rail or stair stringer shall project more than 90mm into the required width of an exit. 

  (5)  In places having a high occupant load where persons are admitted to the building and       allowed to wait until seats become available, special waiting areas shall be provided which         shall:  

(a) not encroach on the required exit width, 

(b) be separated from the required means of egress by partitions or guards not less than 

1070mm in height, and 

(c) be provided with an aggregate width of exit determined on  the basis of  subsection 3.2.16 and Article 3.4.3.3. 

 3.4.3.5  Headroom Clearance  

(1) Except as provided  in  sentence  (2)  to  (4) every means of egress  shall have a headroom   clearance of at least 2.15m. 

  (2)   The  headroom  clearance  for  stairways  measured  vertically  above  any  landing  or  the nosing of any stair tread shall be at least 2.10m. 

  (3)   The headroom clearance doorways shall be at least 2.05m.  

  (4)     No device such as a door closer shall be installed so as to reduce the headroom clearance             of a doorway to less than 2.0m.     

Page 113: GHANA BUILDING CODE - PART 03.pdf

113  

3.4.4  Flame Spread Rating for Exits  3.4.4.1  (1)  Except as permitted  in sentence (2) the flame spread rating of a wall or ceiling  in an exit 

shall be of designation Class 0.    (2)   The flame spread rating of any part of the surface of the wall finish of a lobby used as an 

exit as permitted in 3.4.5.1 (6) may be of any class not lower than class 3 if the area of that part (or,  if there are more such parts, the total area of those parts), does not exceed 25 per cent of the wall area. 

 3.4.5  Required Fire Separation for Exits  3.4.5.1  Grade of Separations      (1)  Except as provided in sentences (3) and (4) and in sentence 3.3.6.6(2), every exit shall be 

separated  from the remainder of the building  it serves by a  fire separation having a  fire resistance rating conforming to Table 3.4.5A for the grade of fire separation required for the  floor assemblies of  the storeys  through which  it penetrates or which  it serves.   This requirement  shall  not  be  deemed  to  prohibit  unprotected  openings  in walls  of  an  exit enclosure that are not fire separations. 

   (2)   Except  as provided  in  sentence  (3), not more  than  1  required  exit  from  any  floor  area 

above  or  below  the  first  storey  shall  not  lead  through  a  lobby,  including  the  foyer  or sentence hall of another floor at ground level. 

  

Table 3.4.5A Forming Part of Sentence 3.4.5.1 (1) 

     Grade of fire separation required for floor 

assemblies (hr) 

Minimum fire‐resistance rating for fire‐separation of exit 

(hr) Less than ¾  ¾ 

¾  ¾ 

1  ¾ 

1 ½  1 

2  1 ½ 

3  2 

4  3 

  

  

 

Page 114: GHANA BUILDING CODE - PART 03.pdf

114  

3.4.5.1  (3)  Exit leading through a lobby: Not more than 1 required exit from any floor area may lead through a lobby where, 

 (a) the lobby floor is more than 4.57m above grade, 

(b) the path of travel through the lobby does not exceed 15.24m, 

(c) the lobby conforms in all aspects with the requirements for exits, except that, 

(i) rooms other than garbage rooms, incinerator rooms and janitors storage rooms      may open onto the lobby,  (ii) the fire separation between the lobby and a room used for the sole purpose of      control and supervision of the building need not have a fire‐resistance rating, and     

                       (iii) the fire separation between the lobby and adjacent occupancies that are                         permitted to open onto the lobby need not have a fire‐resistance rating when the                  lobby and the adjacent occupancies are sprinklered.  (4)    The requirements in sentence (1) do not apply to an exterior passageway that is designed    as an exit facility provided the passageway is open to the outdoors and is served by an exit   stair at each end of the passageway. 

  3.4.5.2  Integrity of Exits  

(1) There shall be no openings  in any  fire separation, separating exits except exit doorways    and openings for standpipes. 

   (2)   Exit  stairways  that  are  continuous  such  as  scissors  stairs  shall  be  separated  from  each 

other by a smoke‐tight fire separation having a fire‐resistance rating at least equal to that required for the floor assembly through which they pass. 

   (3)   Fire  separations  separating  continuous  stairs  in  sentence  (2)  shall  not  be  pierced  by 

doorways, duct work or any other openings that affect the continuity of the separation.    (4)   An exit shall not be used as a plenum for ventilating air‐conditioning system    (5)   An exit shall be designed  for no purpose other  than  for exiting, except  that an exit may 

also serve as an access to a floor area.    (6)   Service rooms such as furnace and incinerator rooms and ancillary rooms such as storage 

rooms, washrooms,  toilet  rooms,  garbage  rooms  and  laundry  rooms  should  not  open directly into an exit. 

     

Page 115: GHANA BUILDING CODE - PART 03.pdf

115  

3.4.6  Exit (Means of Egress) Signs  3.4.6.1  (1)  Every exit door other than the main entrance to a room or building shall have an exit sign      placed over it when the exit serves:  

(a) a building exceeding 2 storeys in building height; 

(b) a building having an occupant load greater than 150; 

(c) a room with a high occupant load of more than 60 except as provided in 3.3.7.4(2)(a);  

(d) a room or floor area that has a fire escape as part of the required means of egress; or 

(e) a  corridor  exceeding  22.9m  in  length  and  serving  patients  or  inmates  bedrooms  in Groups E and I occupancies. 

 (2) Every exit sign required in sentence (1) shall: 

 (a) be visible from the exit approach; 

(b) have the word EXIT displaced in plain legible letters; 

(c) be designed to be illuminated continuously while the building is occupied; 

(d) be connected to an electrical circuit separate from other electrical circuits; and (e) be designed to be illuminated by an emergency power supply as described in sentence 

3.4.7.1(1) and (2).  

  (3)   Letters on exit signs shall be:  

(a) white  letters on contrasting background of green at  least 114mm high with 19mm stroke spelling EXIT, when the sign is internally illuminated,  

(b) white  letters  on  green  background  at  least  150mm  in  height  with  19mm  stroke spelling EXIT, when the sign is externally illuminated. 

             (4)   The minimum size of exit sign letters f or viewing distances shall be as given in Table 3.4.6  

Table 3.4.6: Size of exit sign letters  

Viewing distance  Letter height Less than 20m  50mm 

20‐30m  75mm 30‐40m  100mm 

More than 40m  125mm  

(5)   Where necessary, signs shall be provided to indicate the direction of egress in public             corridors and passageways and shall have the word EXIT with a suitable arrow or pointer            indicating the direction of egress and the size of lettering shall conform to sentence (3).   

Page 116: GHANA BUILDING CODE - PART 03.pdf

116  

 (6)  No mirrors shall be placed in or adjacent to any exit in such a manner as to confuse the        direction of exit. 

 3.4.7  Lighting for Exits  3.4.7.1  (1)  Every exit, public corridor, corridor providing access to exit for the public or serving  

patients bedrooms or classrooms shall be equipped to provide illumination to an average level and at least 54 lux at floor level and at all points such as angles and intersections at changes of level where there are stairs or ramps.   

  (2)   Emergency  lighting shall be provided to average  levels of at  least 11  lux at floor or tread level in: 

 (a) exits and corridors used by the public and principal routes providing access to exit  in 

an open floor area where such exits, and corridors and routes that are below grade or are window less, 

(b) underground walkways, and (c) covered malls. 

  3.4.8  Types of Exit Facility  3.4.8.1  Scope:  Except  when  stated  otherwise  the  requirements  apply  to  both  interior  and  exterior     exits.  3.4.8.2 Stairs and ramps            (1) The finish for treads and landings of interior and exterior stairs and ramps                 accessible to the public shall have non‐skid finish or be provided with non‐skid strips.              (2) Every flight of interior stairs shall have at least 3 risers.             (3)(i)  No flight of stairs shall have a vertical rise of more than 3.7m between floors or  

    landings,  except  the  flights  of  stairs  serving  as  exits  from  rooms  intended  for  infirm persons, or having a high occupant  load shall have a vertical rise of not more than 2.4m between floors or landings. 

    (ii)  The  length and width of  landings  shall be at  least  the width of  stairways  in which  they occur, except that in a straight run the length of a landing need not exceed 1.12m. 

 3.4.8.3 Handrails           (1) Every exit ramp or stairway shall have a handrail on at least 1 side, and where 1.12m or more in     width shall have handrails on both sides.           (2)  Where the required width of a ramp or flight of stairs exceeds 2.22m, 1 or more intermediate                   handrails between landings shall be provided and the number and position of these                  intermediate handrails shall be such that there will be not more than 1.68m between                   handrails.          (3)  Handrails shall be constructed so that there will be no obstruction on or above them which will      break a hand hold. 

Page 117: GHANA BUILDING CODE - PART 03.pdf

117  

        (4)  Handrails on stairs and ramps shall be not less than 810mm and not more than 910mm in      height, measured vertically from a line drawn through the outside edges of stair nosing, except      that handrails not meeting these requirements are permitted provided they are installed in        addition to the required handrails. 

        (5)  A clearance of at least 38mm shall be provided between every handrail and any wall to which it              is fastened.         (6)  Windows in exit stairways that extend to less than 1.07m above the landing shall be protected               by a barrier or railing located approximately 1.07m above such landing.   3.4.8.4 Guards               (1)     Every exit such as a ramp stairway or passageway shall have a wall or a wall‐secured                         guard on each side.    (2)   Except as provided in sentence (3), the height of guards on exit stairs shall not be less than 

915mm  in height measured vertically to the top of the guard from a  line drawn through the outside edges of the stair nosings and 1.07ma round landings. 

   (3)   The height of  guards on  exterior  stairs  and  landings, more  than  10.7m  above  adjacent 

ground level shall not be less than 1.52m measured vertically to the top of the guard from a line drawn through the outside edges of the stair nosings.  

   (4)   The size of any openings through guards for exits shall be such as to prevent the passage 

of a  spherical object having a diameter of 100mm  in buildings of  residential occupancy and 200mm in buildings of other occupancy, unless it can be shown to the satisfaction of the authority having jurisdiction that the location and size of the openings that exceed this limit do not present a hazardous condition. 

 3.4.8.5  Sign for Basement Stair:  In buildings over 2 storeys in building height, any part of an exit, ramp               or stair that continues past the exit door at ground level to a basement or cellar shall be clearly                marked by a sign indicating it does not lead to an exit.  3.4.8.6 Ramp Gradient and Landings   (1) The maximum gradient of ramps shall be: 

(a) 1 in 10 in any Group A, B or C occupancy, (b) 1 in 6 in rooms or floor areas classified as Group M or Group S or  H occupancy, (c) 1 in 8 from any other floor area and, (d) 1 in 10 for every exterior ramp. 

                (2)  Where a doorway or stairway empties onto a ramp through a side wall, there shall be a level                        area extending across the full width of the rampway, and for a distance of 300mm on either                         side of the wall opening, excepting one side when it abuts on an end wall. 

   (3)   Where a door or stairway empties through an end wall onto a ramp, there shall be a level 

area across the full width of a ramp and along its length for at least 915mm.    

Page 118: GHANA BUILDING CODE - PART 03.pdf

118  

3.4.8.7 Stair Treads and Risers    (1)    Treads and risers in every exit stair, except a fire escape stair shall be proportioned so that               the product of the rise and run in mm shall not be less than 1750 and not more than 1900;             risers shall have a maximum rise of 200mm and a minimum rise of 130mm, treads shall             have a minimum runoff 230mm exclusive of nosing.  

(2)   Treads and risers in every exit stair, except a fire escape stair, shall have uniform run and rise in any one flight and shall not alter significantly in run and rise in successive flights in any stair system. 

 (3)   Where the run of any tread in an exit stair is less than 250mm; a nosing of at least 25mm 

shall be provided beyond the face of the riser or an equivalent back slope on the riser shall be provided. 

 (4)   The front edge of stair treads in exits and public access to exits shall be at right angles to 

the direction of exit travel.  3.4.8.8  Curved Stairs Prohibited: No winders or curved stairs shall be used in a required exit.  3.4.8.9 Escalators and Moving Walks    (1) Any escalator of the horizontal tread‐type enclosed in accordance with the requirements of          this part, and any moving walks enclosed in accordance with this part and designed in             accordance with the provisions for ramps in this part may be considered as an exit provided           it conforms to this article.    (2)   An  escalator  or moving walkway  that  pierces  a  required  fire  separation  and  serves  as 

required exit shall be enclosed in the same manner as exit stairs.    (3)   Where  any  escalator  serves  as  a  required  exit,  the width of  the  tread  shall be  at  least 

900mm,  the  rise  shall not exceed 220mm and  the  run  shall be at  least 4000mm;  there shall  be  a  clear  width  of  at  least  1.12m  at  the  handrails,  and  the  escalator  may  be considered to have 2 units of exit width. 

   (4)   No escalator or inclined moving walkway shall have a vertical travel of more than 1 storey.    (5)   Every  escalator  or  inclined  moving  walkway  shall  have  top  and  bottom  landings  as 

required herein for stairs.  3.4.8.10 Horizontal Exits                (1) The floor area or each side of a horizontal exit shall be sufficient to accommodate the             occupants of both floor areas, allowing not less than 0.5m2 of clear floor space per person,           except that 1.50m2 shall be provided for persons in wheel chairs and 2.25m2 for bedridden             patients.    (2)   Where vestibules, enclosed balconies or bridges are used as part of any horizontal exit, 

their clear width shall be at least that of the exit doorways opening into them, except that handrails may not project into this clear width more than 90mm. 

 

Page 119: GHANA BUILDING CODE - PART 03.pdf

119  

  (3)   In any horizontal exit where there is a difference in level between connected floor areas, gradients not exceeding those specified in 3.4.8.6 may be used. 

   (4)   No stair or steps shall be used in horizontal exit.    (5)   Every opening used as a horizontal exit  shall be protected by a closure consisting of an 

approved self‐closing door or doors that swing in a vertical axis.      (6)   Where 2 doors are provided in a horizontal exit they shall:  

(a) be mounted adjacent to each other,  

(b) be mounted  in  separate  opening  or mounted  in  1  opening  and meet  on  a mullion unless otherwise approved, 

 (c) swing in opposite directions and have signs on each side of the wall to indicate as the 

exit the door that swings in the direction of travel from that side.     (7)  Bridges and Balconies as Horizontal Exits           (a)  Where buildings are connected by a walkway, each building shall be separated from           walkway by at least ¾ ‐ hour fire separation. 

           (b)   A walkway shall be of non‐combustible construction when connected to a building           required to be of non‐combustible construction, except that where at least 50 percent                   of the area of the enclosing perimeter walls of walkways at or near ground level are                   open to the outdoors, such walkways may be, made of heavy timber construction.  

 (8) Guards shall be at  least 1.20m  in height and the  least dimension of any opening through 

  the guard shall not exceed 100mm.    3.4.8.11   Passageways: Passageways and stairways shall be designed so as to keep the length of travel            to a minimum. 3.4.8.12(1)     Access to exterior passageways from a floor area shall be through exit doors at the floor             level.   (2)  Every exterior passageway which has a drop of more than 500mm on any side shall have 

guards on the open sides at least 1.07m high.  3.4.8.13   Doors                (1)     No exit doors shall open immediately onto a flight of stairs, but shall open onto a landing              at least 300mm wider and longer than the width of such door.    (2)   No riser of any flight of stairs shall be located within 300mm of an exit door.  

Page 120: GHANA BUILDING CODE - PART 03.pdf

120  

  (3)   Exit doors shall be clearly  identifiable and no hangings or draperies shall be placed over exit doors to conceal or obscure any exit. 

    (4)   No mirrors shall be placed  in or adjacent to any exit  in such a manner as to confuse the 

direction of exit.    (5)   No exit door shall open directly onto a step.    (6)   Every  door  shall  open  in  the  direction  of  exit  travel  except  for  doors  serving  a  single 

dwelling unit and shall swing on its vertical axis.   (7)   (a) Every exit door  that  is normally  required  to be kept closed  shall be provided with a 

reliable self‐closing mechanism, and shall not at any time be secured in an open position except as specified in (b); 

 (b) Where the safety of the occupants  is not endangered thereby, and with the approval of  the  authority  having  jurisdiction,  approved  hold‐open  devices may  be  installed  on closures that are required to be self‐closing other than closures on vestibules required  in Article 3.3.6.6 and on exit shafts. 

   (8)   Sliding doors:  Exit doors leading directly to outdoors at ground level may be sliding doors,      provided they conform to sentence 3.3.1.7 (3).  

(9) Revolving doors:  Where revolving doors are used they shall:  

(a) be approved collapsible revolving doors, 

(b) have hinged doors providing equivalent units of exits width located adjacent to them, 

(c) not be used at the foot of any stairway, and 

(d) not be used as an exit for floor areas containing a high occupant  load or Group E or Group S or H occupancies.  

             (10)  A revolving door may be considered to provide not more than ½ unit of exit width.    (11)   Approved hardware that will release and allow the door to swing wide open when a force 

of 90N is applied to the hardware in the direction of exit travel shall be installed on:  

(a) every exit door from a floor area containing a Group F occupancy having an occupant load of more than 100 persons,  

(b) every door  leading  to an exit  lobby  from an exit stair shaft, and every exterior door leading from an exit stair shaft in buildings having an occupant load of more than 100 persons, and 

 (c) every exit door from a floor area containing a Group S or H occupancy. 

 

Page 121: GHANA BUILDING CODE - PART 03.pdf

121  

  (12)   Every exit door shall be designed and installed so that when the latch is released the door will open in the direction of exit travel under a force of not more than 90N applied at the knob or other latch releasing device. 

   (13)   Fastenings on any required exit door shall be such that the door may be readily opened 

from the inside without the use of keys except that this requirement shall not apply to the doors of rooms where persons are under legal restraint. 

 3.4.8.14 Emergency (Fire) Escapes routes                (1)   Emergency (fire) escapes shall be installed in conformance with sentence 3.4.1.2 (2) and  

sentence  3.4.1.4  (3)  and  (4)  and  shall  be  of  metal  or  concrete,  of  the  stair  type,      extending    to ground  level,  constructed  throughout  in a  strong  substantial manner and securely fixed to the buildings, except that wooden fire escapes may be used on buildings of combustible construction if all posts and brackets are at least 100mm in their least    nominal  dimension  and  all  other  woodwork  is  at  least  50mm  in  its  least  nominal    dimension. 

   (2)   Access to emergency escapes shall be from corridors through doors at floor  level, except 

that  access  from  a  dwelling  unit  may  be  through  a  casement  window  having  an unobstructed opening of not less than 1.07m high by 560mm wide with a sill height of not more than 900mm above the inside floor. 

   (3)   Stairs shall be  inclined at an angle of not more than 45 degrees with  the horizontal and 

shall have risers of not more than 210mm in height and treads of not less than 220mm in width exclusive of nosing. 

   (4)   Stairway  headroom  shall  not  be  less  than  1.95m  plus  height  of  one  riser  measured 

vertically above the nosing of any tread or platform.    (5)   Where doors open onto fire escape balconies, such balconies shall have a clear area of not 

less than 8.60m2.      (6)  The width of an emergency escape shall conform to sentence 3.4.3.1 (1) except that the 

width of an emergency escape shall be at least 550mm when serving:  

(a) not more than 3 storeys, and 

(b) not more than 15 persons.    (7)   The open  sides of every platform, balcony and stairway shall be protected by guards at 

least 900mm in height measured vertically above the nosing of any tread or platform.    (8)   Two equally  spaced  rails not more  than 450mm apart, parallel  to  stair  stringers and  to 

platform edges shall be the minimum protection provided, and the top rail may serve as a handrail if free from obstructions which could break a hand hold. 

   (9)   A wall handrail shall be installed where the fire escape is more than 550mm in width.  

Page 122: GHANA BUILDING CODE - PART 03.pdf

122  

(10) Unless otherwise approved, the flight of stairs  leading to the ground at the foot of a fire escape shall be fixed in position.  Where such flight of stairs is not fixed in position, it shall be held  in  the  ‘up’ position without a  latch or  locking device, and  shall be  fitted with an approval counter balancing device  that will permit  it  to be easily and quickly brought  into position for use.  

  3.5  HEALTH REQUIREMENTS  3.5.1  Height and Area of Rooms  3.5.1.1 (1)  The height of every room and space shall be such that adequate light and air         may be provided for the intended occupancy, and that no obstruction to movement or           activities below is caused by the ceiling or ceiling fixtures.            (2)   The unobstructed height in dwelling units shall conform to Part 7 of the code. 

           (3)  The clear height above and below a mezzanine floor assembly shall be at least 2.15m unless          otherwise approved.  3.5.2  Windows  3.5.2.1  Unless otherwise approved every room used for sleeping in any building, and every principal    room such as living room, dining room or combination thereof in dwelling units, shall be      provided with windows in conformance with Part 7 of this Code.  3.5.3  Ventilation   3.5.3.1  Air Contaminants: Air contaminants released within buildings shall be removed in so far as    possible at their points of origin, and shall not be permitted to accumulate in unsafe    concentrations.  3.5.3.2  Room Ventilation           (1)  All rooms and spaces shall be ventilated in conformance with sentences (2) and (3).           (2)   The ventilation of rooms or spaces by natural methods in Group A occupancies shall conform                  to Part 7 of this Code.           (3)  The ventilation of rooms and spaces in occupancies other than residential occupancies by     natural methods shall be permitted in lieu of mechanical ventilation when the authority having       jurisdiction is satisfied that such ventilation will provide sufficient air change to provide        healthful conditions in that occupancy.  3.5.3.3  Ventilation for explosive substances          (1) Except as provided in sentences (4) and (5), an enclosed storage, garage and repair areas in a       garage shall have a ventilation system designed to limit the average concentration of carbon       monoxide to not more than 100 parts per million parts of air for periods longer than 1 hour    

Page 123: GHANA BUILDING CODE - PART 03.pdf

123  

   with a maximum concentration at any time of not more than 400 parts of carbon monoxide per      million parts of air when measured between 900mm and 1.2m from the floor. 

         (2)  The requirement in sentence (1) is considered to be met by a system designed to provide a      continuous supply of fresh air at a rate equal to at least 0.23m3 of air per minute for each m2 of   floor area. 

        (3)  Mechanical  ventilation  systems  provided  in  accordance  with  sentence  (1)  shall  include   automatic ventilating  fan control by means of approved carbon monoxide monitoring devices,   or by other approved means located so as to provide full protection for the occupancy. 

        (4)  In garages subject  to  the  requirements of sentences  (1),  (2) and  (3) where motor vehicles are   parked by mechanical means the ventilation requirements may be reduced by one half. 

        (5)  Storage garages with a total capacity of  less than 20 motor vehicles need not have mechanical   ventilating system  if  the downward slope of  the  floor  to  the outside door  is 1  in 120 and  the   garage floor is above outside ground level. 

        (6)  The requirements of sentences (1) to (5) shall not apply to any storage garage provided: 

              (a) at least 25 percent of the total area of the perimeter walls on each storey is open to the        outdoors and distributed to provide cross ventilation,              (b) no portion of any floor of the garage is more than 900mm below the adjacent ground          level, and                (c) no tarpaulins, glass or other materials are used to close the required exterior openings at any        time.  3.5.4  Plumbing Facilities 3.5.4.1  Systems Required            (1) Each building situated on property that abuts on a street in which a public or       municipal water main is located shall be provided with or have accessible to its occupants a         plumbing system including a portable water supply, a sanitary drainage system and toilet       fixtures.            (2) When the installation of a sanitary drainage system is not possible because of the absence of a       water supply, sanitary privies, chemical closet or other approved means for the disposal of      human waste shall be provided.           (3) Plumbing systems shall be designed and installed in accordance with Part 9.6 of this Code.   3.5.4.2  Minimum Number of Fixtures           (1) Water closets shall be provided for each sex in accordance with the anticipated      proportion of each sex in the occupancy when this can be determined with reasonable          accuracy, except that when each determination cannot be made with reasonable accuracy, it        may be assumed that the occupancy, is equally divided between the sexes.            (2) Where more than 2 water closets are required in this subsection, urinals may be substituted for    2/3 of the required number of water closets and may be counted as water closets.           (3) Except as provided in sentence (4), at least 1 lavatory shall be provided in a room containing 1  

Page 124: GHANA BUILDING CODE - PART 03.pdf

124  

   or 2 water closets or urinals, and at least 1 additional lavatory shall be provided for each    additional 2 such fixtures.           (4) Wash fountains in circular form may be provided in lieu of lavatories required in sentence (2)    provided each 500mm, of its circumference is considered to be equivalent of 1 lavatory.           (5) The number of water closets required for Group A occupancies and for auditoria, gymnasia,    lecture halls, secondary schools, non‐residential colleges and similar occupancies shall conform    to Table 3.5.4A.         (6)  The number of water closets required for Group B occupancies and for restaurants,    non‐residential clubs, community halls, lodge rooms, passenger stations and depots, art    galleries, exhibition halls, libraries, museums, court rooms and similar occupancies shall    conform to Table 3.5.4B.        (7)   The number of water closets required for primary schools and day‐care centres shall be at least    1  fixture for each 30 males and 1 fixture for each 25 females.  

 Table 3.5.4A  

Forming Part of Sentence 3.5.4.2 (5)  

Number of Persons 

 Minimum Number of Water Closets 

 Male  Female 

1 – 50  1  2 

51 – 100  2  4 

101 – 200  4  6 

201 – 400  6  8 

Over 400 6 plus 1 for each additional 200 

males over 400 

8 plus 1 for each additional 150 

females over 400 

  

  

  

    3.5.4.2(8) The number of water closets required for places of worship and undertaking premises shall 

be at least 1 fixture for each 150 persons of each sex.      (9) The number of water  closets  required  for  institutional occupancies  shall  conform  to good 

practice and shall be subject to the approval of the authority having jurisdiction.      

Page 125: GHANA BUILDING CODE - PART 03.pdf

125  

Table 3.5.4B   Forming Part of Sentence 3.5.4.2 (6) 

  

Number of Persons  

 Minimum Number of Water Closets for each Sex 

 1 – 25 

 1 

 26 – 50 

 2 

Over 50 

 2 plus 1 for each additional 50 persons of each sex over 50  

 3.5.4.2(10) The number of water closets required for residential occupancies shall be at least 1 

      fixture for each 10 persons of each sex, except that dwelling units shall conform to       requirements in Part 7 of this Code. 

            (11)  The number of water closets required for mercantile occupancies shall be at least 1 fixture      for each 300 males and 1 fixture for each 150 females.     

             (12) The number of water closets required for industrial occupancies shall conform to   Table 3.5.4C. 

     Table 3.5.4C Forming 

 Part of Sentence 3.5.4.2 (12)  

 Number of Persons of each sex 

 

 Minimum Number of Water Closets for each sex 

1 – 10  1 

11 – 25  2 

26 – 50  3 

51 – 75  4 

76 – 100  5 

Over 100  5 plus 1 for each additional 30 persons of each sex over 100 

   

 

 3.5.4.3    Glass, other than safety glass, shall not be used for a shower or bathtub enclosure. 

 

Page 126: GHANA BUILDING CODE - PART 03.pdf

126  

APPENDIX 1 Referred Standards 

 STANDARD  TITLE  ASTM  SABS 

BS EN 13168:2001 

Thermal insulation products for buildings. Factory made wood wool (WW) products. Specification 

ASTM C390 ‐ 08e1 Standard Practice for Sampling and Acceptance of Thermal 

Insulation Lots 

SANS 1381‐4 Materials for thermal insulation of 

buildings  

BS 476 PART 

20:1987 

Fire tests on building materials and structures. Method for determination of the fire resistance of elements of construction (general principles), 

ASTM E119 ‐ 12 Standard Test Methods for Fire Tests of Building Construction and 

Materials 

SANS 10177‐2 Fire testing of materials, 

components and elements used in 

buildings Part 2: Fire resistance test for building elements SANS 10177‐1 

Fire testing of materials, components and elements used in 

buildings Part 1: General introduction to the methods of test 

BS 476 PART 

21:1987 

Fire tests on building materials and structures. Methods for determination of the fire resistance 

of loadbearing elements of construction 

ASTM E119 ‐ 12 Standard Test Methods for Fire Tests of Building Construction and 

Materials 

SANS 10160‐1 Basis of structural 

design and actions for buildings and industrial structures Part 1: Basis of structural design 

BS 476 PART 

22:1987 

Fire tests on building materials and structures. Methods for determination of the fire resistance of non‐loadbearing elements of construction 

ASTM E119 ‐ 12 Standard Test Methods for Fire Tests of Building Construction and 

Materials 

 

BS 476 PART 

23:1987 

Fire tests on building materials and structures. Methods for determination of the contribution of components to the fire resistance of a structure 

ASTM E84 ‐ 12 Standard Test Method for Surface Burning Characteristics of Building 

Materials 

SANS 10177‐8 Fire testing of materials, 

components and elements used in 

buildings Part 8: Surface burning characteristics of building materials 

BS 5950 PART 5:1987 

Structural use of steelwork in building. Code of practice for design of cold formed thin gauge 

section 

ASTM A992 / A992M ‐ 11 Standard Specification for Structural Steel Shapes 

 

Page 127: GHANA BUILDING CODE - PART 03.pdf

127  

BS 2782 PART 1 

Methods of testing plastics. Thermal properties. Plastic yield 

ASTM D6108 ‐ 09 Standard Test Method for Compressive 

Properties of Plastic Lumber and Shapes 

ASTM F725 ‐ 03(2008)e1 Standard Practice for Drafting Impact Test Requirements In 

Thermoplastic Pipe And Fittings Standards 

 

SANS 4898  Rigid cellular plastics ‐ Thermal insulation 

products for buildings ‐ Specifications 

BS 476 PART 6 + A1:2009 

Fire tests on building materials and structures. Method of test for fire propagation for products 

ASTM E119 ‐ 12 Standard Test Methods for Fire Tests of Building Construction and 

Materials 

SANS 10177‐10  Fire testing of materials, components and elements used in buildings Part 10: Surface burning characteristics of 

building materials using the inverted channel 

tunnel test  

BS EN 1329 PART 1:200 

Plastics piping systems for soil and waste discharge (low and high temperature) within the 

building structure. Unplasticized poly (vinyl chloride) (PVC‐U). Specifications for pipes, fittings 

and the system 

ASTM D2852 ‐ 95(2008) Standard Specification for Styrene‐Rubber (SR) Plastic Drain Pipe and Fittings 

ASTM F2648 / F2648M ‐ 11 Standard Specification for 2 to 

60 inch [50 to 1500 mm] Annular Corrugated Profile Wall 

Polyethylene (PE) Pipe and Fittings for Land Drainage 

Applications 

SANS 9852 Unplasticized poly(vinyl chloride) (PVC‐U) pipes ‐ 

Dichloromethane resistance at specified temperature (DCMT) ‐ 

Test method SANS 967  Unplasticized 

poly(vinyl chloride) (PVC‐U) soil, waste and vent pipes and pipe 

fitting BS 476 PART 3 :2004 

Fire tests on building materials and structures. Classification and method of test for external fire 

exposure to roofs 

ASTM E108 ‐ 11 Standard Test Methods for Fire Tests of Roof 

Coverings