1 Green Journey of Infosys High performance with low environmental impact & low cost Guruprakash Sastry Regional Head Infrastructure / Green Initiatives

Upload: others

Post on 30-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

1

Green Journey of InfosysHigh performance with low environmental impact & low cost

Guruprakash Sastry

Regional Head – Infrastructure / Green Initiatives

Page 2: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

2

Infosys Sustainability

Journey

1. Define unreasonable goals

2. Focused team of experts for driving initiatives

3. Innovations in infrastructure

4. Demonstrate commercial viability for each initiative

5. Measure performance continuously

Data driven new designs

Data driven retrofits

6. Success stories

Page 3: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

16%

3

Impact on energy bills &

Carbon footprint reduction

Savings of

2 Billion kWh of electricity

Savings of

$200 Million in electricity bills

1.7 Million Tons of CO2

emissions avoided

45+ Million square feet

across India

Increase in No. of

employees in India

since 2008

Absolute Increase in

energy consumption

since 2008159%

Page 4: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

4

New Ultra

Efficient

Buildings

Page 5: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

EPI of building - less than 75 kWh/m2/year

HVAC Goal Lighting Goal Water Goal

Max envelope heat gain 0.75 W/sqft

Total building @ 750-1000 sqft/TR

25 deg C, 55% RH

LPD of 0.45 W/sqft

90% of building to be day lit > 110 lux

No Glare throughout the year

Architects

Facade Specialists

IT Specialists

HVAC Engineers

Lighting Specialists

Architects

Facade Specialists

Lighting Specialists

Electrical Designers

PHE Engineers

Architects

Landscape Architects

Less than 25 LPD for office

building

Zero discharge

100% self sufficient

T

E

A

M

G

O

A

L

EPI: Energy Performance Index

Define clear goals

5

Page 6: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

6

Performance

Parameters in 2008-09

Building Energy (EPI):

200 kWh/m2/year

Average for software buildings

(incl. lights, AC, computers, etc.)

Lighting Design:

1.2 W/sqft

Average for software buildings

across campuses

AC Design:

350 sqft per TR

Average installed cooling capacity

across campuses

Electrical Design:

6.5 W/sqft

Total electrical load for software

buildings including chiller plant

* EPI – Energy performance index

Page 7: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

7

New design and

Performance Benchmarks in 2018-19

Building Energy (EPI):

75 kWh/m2/year

Average for software buildings

(incl. lights, AC, computers, etc.)

Lighting Design:

0.50 W/sqft

Average for software buildings

across campuses

AC Design:

750 sqft per TR

Average installed cooling capacity

across campuses

Electrical Design:

3.5 W/sqft

Total electrical load for software

buildings including chiller plant

63% Lower

58% Lower

54% Lower

46% Lower

* EPI – Energy performance index

Page 8: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

8

New Buildings

Practicing Energy Efficiency by Design

New buildings deliver an EPI of 75 kWh/m2/year

Building Shape &

OrientationInsulated Walls &

Roof

Ultra Efficient

system designSmart Building

Systems

Optimum Window-

wall ratioDay lit spaces with

efficient windows

Efficient technologies - Radiant

cooling is 30% more efficient

Page 9: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

Importance of building facade

9

Page 10: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

1

0

Importance of building facade

10

Page 11: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

11

New Buildings

Efficient Design at Lower Cost

• Campus based on sustainability principles from the concept design

• Efficient building facade avoids heat coming inside but lets in natural light

Page 12: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

12

Smart

Window Design

Day light pane

View pane

External shading

Smart glazing

Interior light shelf

Page 13: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

13

Impact of

Day Lighting

ImprovesEmployee health

& well being

Employee

Productivity

Page 14: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

Sl.

No.

System Description Units Conventional

practice

Efficient

design

Cost

savings in

INR Crores

Cost savings

in INR/sqft

01 Total electrical load MW 8.0 3.5 10 cr. 100

02 Transformer capacity MVA 10.0 4.5 1.0 cr. 10

03 DG set capacity MVA 12+2 4.5+1.5 12.0 cr. 120

04 HVAC system TR 2850 1350 3.0 cr. 30

05 Lighting system MW 1.2 0.45 1.5 cr. 15

06Annual energy

consumptionMillion kWh 25 8 10 cr. 100

Infrastructure required for 1 million sqft,

14

Benefit of efficient design on capital cost

Page 15: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

15

Innovations

HVAC system

1. Dual loop chilled water system – 8 deg C and 16 deg C

2. All equipment on variable speed drives – chillers, pumps, cooling towers, air system

3. Low velocity design for entire system

4. Efficient equipment - Magnetic chillers

5. Automatic tube cleaning system

6. Use of free cooling (through cooling tower) – economizer

7. STP recycled water for cooling tower makeup

8. Chiller plant efficiency : 0.42 kW/TR (annual avg. for a building in BLR)

Page 16: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

16

Efficient cooling system

Radiant Cooling

30% more efficient than most efficient conventional cooling

Requires 75% less air compared to conventional system

Frees up valuable real estate space, less equipments

Higher thermal comfort

Highest indoor air quality, fresh air circulation

Cost same as conventional air conditioning

100

3525

0

20

40

60

80

100

120

Standard Air-conditioning

Efficient Air-conditioning

Radiant cooling

Cooling energy consumption (kWh/m2/year)

Radiant slab

Air-conditioning Radiant Cooling

Page 17: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

17

Efficient cooling system

Radiant Cooling

Radiant panels developed by Infosys team

High cooling capacity

Quick installation

Cost effective

Patent pending – Europe, US and India

Radiant panels

Page 18: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

18

Ultra Efficient Engineering

Collaboration with global experts / academia

High Performance

Design

Minimal bends and

pressure drop

Page 19: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

19

Deep Green

Retrofits

Page 20: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

20

Key Drivers for

Deep Retrofits

Energy Efficiency

Technology Upgrade

Visual Comfort

Acoustic Comfort

End of Life Scenarios

Thermal Comfort

Indoor Air Quality

Changing Business Needs

Page 21: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

21

Re-engineered chiller plants

(Conversion to variable primary systems – 40 Central Plants)

Before Retrofit After Retrofit

Reduction in Energy

30%

Reduction in no. of Equipment

45%

Reduction in space

25%

Reduction in Maintenance Costs

Page 22: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

22

Data Centers: Cold aisle containment and

DX to chilled water conversion

Converted to water-cooled,

chilled water based system

– 50% reduction in energy

Cold aisle containment for

existing data centres

Page 23: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

23

Replacement of

Electric heaters/steam boilers with heat pumps

Air source heat pump, draws

heat from atmosphere

3.5 times more

efficient than electric

heating

2 MW of connected

load reduced across

campuses

550kL savings

in annual diesel

consumption

1kW electricity Electric Water Heater 0.95 kW of heating

1kW electricity Heat Pump 3.5 kW of heating

Page 24: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

24

Achievement on

Energy Efficiency

297

266

239 230

203

178167 160

150 145 139 133

0

50

100

150

200

250

300

350

2007-08 2008-09 2009-10 2010-11 2011-12 2012-13 2013-14 2014-15 2015-16 2016-17 2017-18 2018-19

Mo

nth

ly C

on

su

mption

in K

WH

/ E

mp

loye

e

On account of both – New buildings & retrofits

Page 25: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

25

Smart

Campuses

Page 26: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

26

Sustaining Performance through

Remote Performance Mgmt.

Review & Optimization of

Infosys Central Command Center

Thermal Comfort Indoor Air Quality Energy and Water use

Renewable Energy Building Assets Critical Operations

Central Utilities Alerts & Diagnostics Safety & Security

Optimizes operations across 16 Infosys campuses/ 26 million sqft in India

Page 27: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

27

Latest Data

Centers

Page 28: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

28

Ultra high efficiency

with Power UE of 1.12

Air entry at

room

temperature

Room neutral

air exiting the

RDHx coil

Cooling coil is positioned to

remove heat as soon as it is

produced by the server

Global average PUE of data centers is 1.8*

Best data centers in the world deliver a PUE of

about 1.08 (Facebook, Google) under cold

climate (Scandinavian countries)

We designed DC with a PUE of 1.12 at

Bangalore. Currently operating at about 1.18,

at partial loading

Uses free cooling from cooling towers

Unique Rear Door Heat Exchanger technology

Air entry Room Temperature- 27deg C

Air Exiting- 24deg C

*PUE – Power Utilization Effectiveness

Page 29: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

29

Renewable

Energy &

Green Power

Page 30: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

30

Green Power and

Renewable Energy

Currently 46% of our electricity is sourced from Green Power sources *

19 MW of captive roof top as well as ground mount installations

Commissioned 30 MW offsite Solar PV plant in Karnataka

In-house lab setup to test various PV technologies under same weather conditions

Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation

Infosys is the first Indian company to join

RE100 initiative in May 2015

100% Green Power by 2020

Page 31: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

31

Water

Management

Page 32: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

32

Water Efficiency by design

New Buildings

Software Development Blocks 25 liters/person 45 liters/person 45%

Food Courts 40 liters/seat 70 liters/seat 43%

Employee Care Centers 90 liters/person 135 liters/person 33%

Shower 6 liters/min 12-16 liters/min 50%

Taps 1.9 liters/min 6-9 liters/min 68%

Water Closet 3-6 liters/flush 6-9 liters/flush 50%

ImprovementInfosys Design

StandardsBuilding Type National Building

Code/UPCI

Specify flow rate along with design of fixtures

Page 33: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

33

Water Conservation in

Buildings

End Use Consumption Strategies

Low flow fixtures – Taps, Shower

heads, Health Faucets

Pressure Compensating Aerators

(PCA)Sensor controlled taps

Pressure regulating valves at

buildings

Landscape retrofits, Native

plantation

Root zone irrigation Employee awareness campaigns

Dual flush system

Artificial Grass at

Infosys MysoreSmart water metering

Page 34: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

New Buildings/Campuses Existing Buildings/Campuses

34

Water Recycling

100% of waste water is recycled and reused

100% of waste water is recycled

Efficient treatment technology - Membrane bio-

reactor (MBR) technology

Recycled water is used for irrigation, flushing and

air-conditioning

Retrofits to upgrade treated water quality in

line with new CPCB norms

Retrofits to reduce waste water treatment

cost

Dual piping system retrofits in existing buildings

100% Waste Water

from buildings

Sewage Treatment Plants

(STP)

Flushing

Irrigation

Air-conditioning

100% REUSE

Page 35: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

35

Rain water harvesting

Harvest 100% of on-site rain water

Natural and Artificial

lakes/ponds on campus to

harvest rain water

Roof top rain water

harvesting systems (New &

retrofits)

Deep well injection

system to recharge

ground water

35 lakes across campuses in India Roof top rain water harvesting 350+ deep well injection systems

(Holding capacity of ~330 million liters) (Recharge capacity of 17.5 million liters per day)

Page 36: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

3.28 3.3 3.32

3.07

2.47

2.17 2.15 2.21

1.921.77

1.411.31

0

0.5

1

1.5

2

2.5

3

3.5

4

2007-08 2008-09 2009-10 2010-11 2011-12 2012-13 2013-14 2014-15 2015-16 2016-17 2017-18 2018-19

Mo

nth

ly C

on

su

mption

in K

L / E

mp

loye

e

36

Achievement on

Water Efficiency

Page 37: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

37

Waste Management

Zero waste to landfills

Organic Waste

To be treated on campus

100% on-site treatment

of food waste

9 Automated biogas

producing 6800 LPG

cylinders/year

8 Composting plants

producing compost 400

tons/year

In-organic, Non-

Hazardous waste

To be recycled

Recycled through

authorized vendors

2400 Tons/year of waste

recycled

Treated through PCB

authorized vendors

500 Tons/year of

recyclable waste sent to

authorized recyclers

Hazardous waste

To be treated by certified recyclers only

Achieved 85% waste diversion from Landfills

Page 38: Green Journey of Infosys - NZEB...Tie-ups with NREL, ISES, IIT Bombay and IISC, Bangalore for research and innovation in Solar PV design, installation and operation Infosys is the

38

Achieving Sustainability in

Physical Infrastructure

1. Question every assumption

2. Push the boundaries

3. Use of technology

4. Focused efforts

5. Turn challenges to opportunities

6. Measure data, Monitor performance

Thank youFor more info: https://www.infosys.com/sustainability/Documents/infosys-