GRID CODE TESTING BY VOLTAGE SOURCE CONVERTER ABSTRACT Safe and reliable operation of the wind turbines is important for an efficient operation of the power system. One important design criteria for wind turbines is the fulfillment of Grid Codes given by transmission system operators (TSO), they state how wind turbines/farms must behave when connected to the grid in normal and abnormal conditions. For this reason, the testing equipment which comprises the use of fully-rated Voltage Source Converter (VSC) in back- to-back configuration is proposed. Thanks to the full controllability of the applied voltage in terms of magnitude, phase and frequency, the use of VSC- based testing equipment, provides good flexibility. Here, test results of a 4 MW wind turbine and an 8 MW test equipment, located in Gothenburg, Sweden, are shown. Ola Carlson, Nicolás Espinoza R. [email protected] [email protected] Chalmers University of Technology Department of Electrical Engineering Division of Electric Power Engineering In every Grid Code it is specified a voltage dip profile that the wind turbine should ride through without tripping. In some cases, reactive current must be injected at the point of common coupling (PCC) in order to support the grid voltage when a voltage dip is detected. 0 0 1 0.4 0.6 0.2 System Voltage [pu] Time [s] 0.8 1 2 3 0.5 0.25 0.75 1.25 1.5 1.75 2.25 2.5 2.75 E.ON (Germany) Energnet.dk (Denmark) Red Eléctrica España (Spain) Svenska Kraftnät (Sweden) EirGrid (Ireland) National Grid (U.K.) ENTSO-E (Europe) PROPOSED VSC-based TESTING EQUIPMENT The test equipment is rated at 8 MVA, 10.5 kV, and the wind turbine is rated at 4 MW. The turbine-side VSC controls the applied voltage, The grid-side VSC delivers the wind turbine power to the grid. The tested system and its dynamic are decoupled from the AC grid. Grid-coupling Transformer VSC-based Testing Eq. LCL filter AC DC AC DC Control system WT-coupling Transformer LCL filter AC PCC In this example, the testing device is used to reproduce a voltage dip at the wind turbine terminals. The wind turbine reacts by injecting reactive power into the grid in order to support voltage restoration. It can also seen that the wind turbine generator is unaffected by the voltage dip and that the wind turbine keeps on running in a proper way. TESTING for FREQUENCY DEVIATION In this test, the applied frequency is varied upward emulating a frequency swell. The wind turbine reacts by disconnecting 5 seconds after the frequency reaches 52 Hz. IMPEDANCE CHARACTERIZATION of THE WIND TURBINE Finally, the testing device can also be used to characterize the input admittance of the wind turbine system , allowing the identification of frequency ranges in which the wind turbine can act passively (behaving as a resistor and dissipating the oscillation) or actively (injecting power at specific frequencies), evaluating the risk of interaction with other elements of the gird. CONCLUSIONS VSC-based testing equipment is flexible and allows for full characterization of the WT. It allows for testing not only Grid Codes but also future requirements. Input impedance of wind turbine system can also be measured by the testing device. Methodology validated by field test experiments. ACKNOWLEDGMENTS Big Glenn 4 MW wind turbine and the 8 MW HVDC-VSC station with filters and surge arresters REQUIREMENT for LOW VOLTAGE RIDE THROUGH (LVRT) and TESTING

Upload: others

Post on 18-May-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GRID CODE TESTING BY VOLTAGE SOURCE CONVERTER · 2017-06-01 · GRID CODE TESTING BY VOLTAGE SOURCE CONVERTER ABSTRACT ... EirGrid (Ireland) National Grid (U.K.) ENTSO-E (Europe)

GRID CODE TESTING BY VOLTAGE SOURCE CONVERTERABSTRACT

• Safe and reliable operation of the wind turbines is importantfor an efficient operation of the power system.

• One important design criteria for wind turbines is thefulfillment of Grid Codes given by transmission systemoperators (TSO), they state how wind turbines/farms mustbehave when connected to the grid in normal and abnormalconditions.

• For this reason, the testing equipment which comprises theuse of fully-rated Voltage Source Converter (VSC) in back-to-back configuration is proposed.

• Thanks to the full controllability of the applied voltage interms of magnitude, phase and frequency, the use of VSC-based testing equipment, provides good flexibility.

• Here, test results of a 4 MW wind turbine and an 8 MW testequipment, located in Gothenburg, Sweden, are shown.

Ola Carlson, Nicolás Espinoza [email protected]

[email protected]

Chalmers University of TechnologyDepartment of Electrical EngineeringDivision of Electric Power Engineering

In every Grid Code it is specified a voltage dip profile that the windturbine should ride through without tripping. In some cases,reactive current must be injected at the point of common coupling(PCC) in order to support the grid voltage when a voltage dip isdetected.

00 1

0.4

0.6

0.2

Sys

tem

Vol

tage

[pu]

Time [s]

0.8

1

2 30.50.25 0.75 1.25 1.5 1.75 2.25 2.5 2.75

E.ON (Germany)

Energnet.dk (Denmark)

Red Eléctrica España (Spain)

Svenska Kraftnät (Sweden)

EirGrid (Ireland)

National Grid (U.K.)

ENTSO-E (Europe)

PROPOSED VSC-based TESTING EQUIPMENTThe test equipment is rated at 8 MVA, 10.5 kV, and the wind turbine is rated at 4 MW. The turbine-side VSC controls the applied voltage, The grid-side VSC delivers the wind turbine power to the grid. The tested system and its dynamic are decoupled from the AC grid.

Grid-coupling Transformer

VSC-based Testing Eq.LCL

filterAC

DC AC

DC

Control system

WT-coupling Transformer LCL

filter

ACPCC

In this example, the testing device is used to reproduce a voltage dip at the wind turbine terminals. Thewind turbine reacts by injecting reactive power into the grid in order to support voltage restoration. It canalso seen that the wind turbine generator is unaffected by the voltage dip and that the wind turbinekeeps on running in a proper way.

TESTING for FREQUENCY DEVIATIONIn this test, the applied frequency is varied upward emulating afrequency swell. The wind turbine reacts by disconnecting 5seconds after the frequency reaches 52 Hz.

IMPEDANCE CHARACTERIZATION of THE WIND TURBINEFinally, the testing device can also be used to characterize the input admittance of the wind turbinesystem 𝑌𝑌𝑊𝑊(𝑗𝑗𝜔𝜔), allowing the identification of frequency ranges in which the wind turbine can actpassively (behaving as a resistor and dissipating the oscillation) or actively (injecting power at specificfrequencies), evaluating the risk of interaction with other elements of the gird.

CONCLUSIONS VSC-based testing equipment is flexible and allows for full characterization of the WT. It allows for testing not only Grid Codes but also future requirements. Input impedance of wind turbine system can also be measured by the testing device. Methodology validated by field test experiments.

ACKNOWLEDGMENTS

Big Glenn 4 MW wind turbine and the8 MW HVDC-VSC station with filtersand surge arresters

REQUIREMENT for LOW VOLTAGE RIDE THROUGH (LVRT) and TESTING