Ground Fault Protection
Earthing systems (ES): Diagram 1a (left) - "TN-S system"; Diagram 1b (right) - "TN-C
system"
Safety and installation standards
The IEC 60364 standard defines 3 types of earthing systems (ES) :
TN system
TT system
IT s ystem
Earthing systems (ES) characteristics are:
1. An insulation fault has varying consequences depending on the system used:
Fault that is dangerous or not dangerous for persons
Strong or very weak fault current.
2. If the fault is dangerous, it must be quickly e liminated
3. The PE is a conductor.
The TT system combined with Residual Current Devices (RCD) reduces the risk of fire.
Defined by installation standards, basic principles for the protection of persons against the risk of electrical
shocks are:
1. The earthing of exposed conductive parts of equipment and electrical loads
2. The equipotentialit y of simultaneously a ccessible exposed conductive parts tha t tend to eliminate touch
voltage
3. The automatic breaking of electric power supply in case of voltage or dangerous currents caused by a live
insulation fault current.
The IEC 60364 standard
Since 1997, IEC 364 is identified by a no.: 60 XXX, but its content is exactly the same.
Earthing systems (ES)
The IEC 60364 standard, in § 3-31 and 4-41, has defined and developed 3 main types of earthing systems (ES).
The philosophy of the IEC standard is to take into account the touch voltage (Uc) value resulting from an
insulation fault in each of the systems.
Protection using an Residual Current Device – RCD
Residual current device (RCD) - Wiring diagram
Residual Curren rDevices RCDs with a sensitivity of 300 mA up to 30 A must be used in the TT system.
Complementary protection using an RCD is not necessary for the TN or IT systems in which the PE is carried
out using a conductor. For this reason, the type of protection using an RCD must be:
High Sensitivity (HS) for the protection of persons and against fire (30 mA / 300 mA)
© 2013 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy Powered by CsanyiGroup
Low Sensitivity (LS) up to 30 A for the protection of belongings.
This protection can be carried out by using specific measuring toroids that cover all of the live conductors
because currents to be measured are weak. At the supply end of an installation, a system, which includes a
toroid that measures the current in the PE, can even be carried out using high sensitivity RCDs.
AUTHOR: Schneider Electric experts
Title:Schneider Electric Low voltage expert guides n° 2 - Ground Fault
Protection
Format: PDF
Size: 6.9MB
Pages: 60
Download: Please login first | Get Download Updates | Get Technical articles
Recommended EE articles
Subscribe to Monthly Download Updates
Get EEP's updates without having to keep checking up on the
portal to see if there is anything new. New FREE technical
articles, electrical books, guides, software and other exclusive
content you will receive via email. Pretty simple!
Subscribe here:
Email Address:
Subscribe
Page edited by E.C. ( Google ).
Become EEP's Contributor and introduce yourself to 70k+ of our readers all across the web.
TOP