gsec sf6 load-break switch-disconnector ppmv – product management
TRANSCRIPT
GSecSF6 load-break switch-disconnector
PPMV – Product Management
GSecThree position switch disconnector
Month DD, Year | Slide 2© ABB Group
Upper terminal
Lower terminalCapacitive dividers intergrated
SF6 line disconnectorInsulate busbar from cablesSF6 earthing switch
Grounds cable side
GSec
Upper part in epoxy resin and filled with SF6:
compact design
long-term protection against external environment
Sealed for life: 30 years
Lower part in stainless steel
Metallic partition (PM) between busbar and cable compartments
Safety for operators during maintenance activities
Lower bushings with integrated capacitive dividers:
Direct cable connection
Compact and safe structure
Month DD, Year | Slide 3© ABB Group
GSec
Line actuators:• Single spring mechanism
(1S – dead centre)• Double spring mechanism
(2S – stored energy)
Earth actuator:• Single spring mechanism
(1S – dead centre)
1. Line operating slot2. Earth operating slot3. Line diagram with indicators4. Pushbuttons (for 2S actuator)5. Voltage indicators6. Spring charged signal7. Fuse blown signal
Actuators
Month DD, Year | Slide 4© ABB Group
GSecActuators diagrams
Month DD, Year | Slide 5© ABB Group
Position of line contact (0 = open, 1 = closed)Spring status (0% = discharged, 100% = charged)Spring charging time- manual operation: depend on operator- automatic operation with motor = 3-4 s.
Tc Opening or closing time of the contact < 0,3 s.Tclose Total closing time < 5 s.Topen Total opening time < 5 s.
Ts1
Position of line contact (0 = open, 1 = closed)Springs status (0% = discharged, 100% = charged)Springs charging time- manual operation: depend on operator- automatic operation with motor = 3-4 s.
Tc Opening or closing time of the contact < 0,3 s.Tclose Total closing time < 0,3 s.Topen Total opening time < 0,3 s.
Ts2
1S – Single Spring 2S – Double Spring
time time
Actuation speed is independent from operator
GSec/T1
1S – Single spring mechanism
GSecTypical units
Month DD, Year | Slide 6© ABB Group
GSec/T2
2S – Double spring mechanism (stored energy)
GSecTypical units
Month DD, Year | Slide 7© ABB Group
GSec/IB
1S – Single spring mechanism
For panels with removable circuit breakers
Downstream earthing switch (interlocked)
GSec/T2F
2S – Double spring mechanism
Fuse tripping system
Fuse base
Fuse blown indicator
Downstream earthing switch (interlocked)
GSec
Line disconnector - Earthing switch
It is possible to close the earthing switch only if the line switch-disconnector is open
Earthing switch – Panel door
It is possible to open the door only if the earthing switch is closed
Mechanical interlocks for safety
Month DD, Year | Slide 8© ABB Group
(1) (2) (3)
Closed Open - Isolated Earth
GSecWide range of accessories
Month DD, Year | Slide 9© ABB Group
Line SwitchDisconnector
- Shunt opening release (T2/T2F)
- Shunt closing release (T2/T2F)
- Pushbutton protection (T2/T2F)
- Fuse blown contact (T2F)
- Motor closing spring charger
- Auxiliary contacts 4NC/4NO
- Key locks
- VPIS
- Manometer or pressure switch
Earthing switch
- Auxiliary contacts 4NC/4NO
- Key locks
GSecSafety and Compactness
Month DD, Year | Slide 10© ABB Group
Safety
- Metallic partition thanks to lower part in stainless steel
- Mechanical interlocks to prevent unsafe operations
- Separate operating seats for line and earth
Compactness
- Can fit 375mm wide panels
- No need for cross-beam with insulators and direct cables connection thanks to integrated capacitive dividers
Three positions load-break switch disconnector:
SF6 Load break switch
SF6 Disconnector
SF6 Earthing switch (cable side)
GSecSF6 three-positions LBS
Month DD, Year | Slide 11© ABB Group
Rated Voltage [kV] 12(1S / 2S)
17.5(1S / 2S)
24(1S / 2S)
Rated Current [A] 630 / 800 630 / 800 630
Short time current [kA] 16(3s) / 25(2s) 16(3s) / 20(3s) 16(3s) / 20(2s)
Mechanical class Line: M1 / M2 – Earth: M0
Electrical class Line: E3 – Earth: E2