gunon-janus-novec1230 presentation r00
DESCRIPTION
Presentasi Novec1230 Janus Fire ProtectionTRANSCRIPT
PT. GUNON INTENATIONALTAMAN TEKNO H3 NO. 1-2BSD CITY – TANGERANG
INDONESIA 15134PHONE : +62 21 7562680 FAX : +62 21 7562685
[email protected]@gunon.com
1
PT. GUNON INTENATIONALWe are dealing in the Fire Protection and Detection System. Weprovide the systems based on Guideline Standards and ApprovalBodies :
2
PT. GUNON INTENATIONALWe are also a distributor and agent of famous brands in the worldas follows :
3
PT. GUNON INTENATIONALBased on the standard design guidelines, approval bodies,factory’s supports and our experiences, we provide :
* Consultation
* System Design
* Budget Estimation
* Sales
* Maintenance
* and after sales services
4
PT. GUNON INTENATIONALOn the markets :
* High Rise Building
* Telecommunication and Data Centre
* Industrial, Petrochemical and Power Plant
* Oil and Gas
5
PT. GUNON INTENATIONALProjects Reference
6
JANUS FIRE SYSTEMS®
YOUR GATEWAY TO A NEW KIND OF SERVICE
Established by four leading experts in the fire protection industry with a combinedexperience of over 120 years, Janus Fire Systems is based on the principle of offering
its clients superior products and services.
Address: 1102 Rupcich, Crown Point, IN 46307, United States
Phone:(219) 663-16007
JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :
8
JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :
9
JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :
10
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
Typical Clean Agent System Layout
11
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
When to use Clean Agents ?
* Protecting high value assets
- Energized electrical areas
- Artifacts and archived data
* Continuous operations must be
maintained
* Life safety is a concern
- Emergency communications
- Occupied or may be occupied
* Must be a clean agent
12
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
Typical areas of fire protection:
* Computer Rooms
* Data Storage Facilities
* Telecommunications
* Oil & Gas Petrochemical Facilities
* Museums
* Libraries and Archives
* Medical Facilities
* Manufacturing Facilities
* Storage Areas
13
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components:
* NovecTM 1230 Fire Protection Fluid
* Agent Storage Components and Accessories
*Agent Fluid Distribution Components
* Control Panels
* Detection and Alarm Devices
* Flow Calculation Software
14
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
What are Clean Agents?
Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave aresidue upon evaporation
(NFPA 2001, Sec. 3.3.6)
* Does not conduct electricity
* Gaseous
* Does not leave a residue behind
* Is not carbon dioxide
15
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 is a highly-efficient clean agent :
* Won’t Damage Equipment:
- Electrically non-conductive
- Non-corrosive
* No Downtime or Cleanup:
- Evaporates cleanly, leaving no residue
- Does not damage electronics
- Can be safely used on energized equipment,
helping to ensure continuity of operations
during a fire emergency16
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 is a highly-efficient clean agent :
17
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Designed to Provide a Large Margin of Human Safety
Clean agents fire suppression applications often include the presence of people, sosafety to human life is a critical issue when selecting a fire suppression product. 3M™Novec™ 1230 Fire Protection Fluid is a highly efficient fire extinguishant that's safe foruse in occupied spaces. The large margin between Novec 1230 fluid's useconcentration and "Non Observed Adverse Effects Level" provides the largest marginof safety relative to other chemical clean agents, CO2, and inert gas mixtures.
18
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Designed to Provide a Large Margin ofHuman Safety
19
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 Fluid Performance
Don’t Just Manage a Fire. Extinguish It.3M™ Novec™ 1230 Fire Protection Fluid is a highly-effective clean agent firesuppressant, designed to extinguish a fire in its incipient stage before it has a chance tospread. It is applied as a gas, but is liquid at room temperature, and can be effectivelyused in streaming, flooding systems, or for use in inerting and explosion suppressionapplications. 20
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Novec 1230 Fluid Performance
Knocks down fires fast
Novec 1230 Fluid has a very low heat of vaporization, approximately 25 times less thanthat of water. This, along with a higher vapor pressure, causes Novec 1230 Fluid toevaporate more than 50 times faster than water. It also allows the clean agent totransition from a liquid to a gaseous state very rapidly when discharged through anozzle, and readily achieve vapor extinguishing concentrations in air. With highextinguishing efficiency and a wide margin of safety, Novec 1230 fluid is a greatalternative to water sprinkler systems, foam and dry chemicals due to:
* Low toxicity (no harm to personnel)
* Extinguishes fires in less than half the time of CO2 & inert gases
* No damage to sensitive equipment
* Not targeted for emission reduction or phaseout 21
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Sustainability :From its inception, 3M™ Novec™ 1230 Fire Protection Fluidwas designed to address the global demand for a sustainableclean agent. It is effective at extinguishing fires andis not targeted for emission reduction, phase-out orphase-down. Novec 1230 fluid offers the sustainable cleanagent properties you need, such as:* Zero ozone depletion potential (ODP)* An atmospheric lifetime of 5 days, compared to 65 years for halons* A global warming potential (GWP) of less than 1 – about the same as naturally-
occurring carbon dioxide 22
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : NovecTM 1230 Fire Protection Fluid
Sustainability :
23
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
Janus Fire Systems provides 500 Series Novec 1230 Clean Agent Cylinders.
Cylinders are charged with the clean agent to a maximum filling density of up to 70lb./ft.3 (1121 kg/m3) of cylinder volume.
Each cylinder is super-pressurized with dry nitrogen to 500 psi (34.48 bar)
All cylinders are equipped with an identification nameplate indicating the initial fillquantity of the clean agent.
24
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
Janus Fire Systems have 3 (three) cylinder series :
* Sv Series : filling capacity 10.00 - 59.40 kg
* Mv Series : filling capacity 57.20 – 191.40 kg
* Lv Series : filling capacity 137.9 – 453.6 kg
Sv Mv Lv
25
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
500 Series Novec 1230 Clean Agent Cylinders offer Enhanced Design Capabilitycompared with 360 psig (25 bars) cylinders :
* Less required Clean Agent
An additional Clean Agent required when the pressure and flow rate of agent in the pipeand nozzles has been met the limitation of Pipe Size and Flow Rate
* Smaller Size and Lower Quantity of Cylinders
Increasing Size and Quantity of Cylinders is required to get more pressure as thesmaller size and lower quantity of cylinders can not meet the requirement of listedsystem such as Discharge Time, Design Concentration, Flow Rate and Pressure at thedistribution pipe and nozzles
* Longer Pipe Length and Larger Pipe Network
* Smaller Pipe Diameters26
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Storage Components
* Other features provided and affixed to the cylinders :
- Cylinder Low Pressure Supervisory Switch
- Level Liquid Indicator
The features is designed to monitor Pressure and Agent are in good condition andready for used when it’s needed. With this features, no need to do daily inspectiontherefore more effective and efficient on maintenance purpose.
* Janus Fire Systems 500 Series offer more effective, efficienct
and flexibility
27
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components
28
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components
29
Cylinder Valve: Controls release of the clean agent Differential pressure operated valve Forged brass body and cap Shipped with anti-recoil safety plug installed in
the discharge outlet
Dip Tube: Extends from cylinder neck down to the bottom of
the cylinder
Cylinder Bracket One strap and rail with accompanying twirl nuts
and cap screws
Cylinder: Welded seam cylinder Manufactured to requirements of USDOT
(Department of Transportation) and TransportCanada for compressed gas
Designed for vertical mounting only
CylinderValve
Dip Tube
CylinderBracket
Cylinder
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Sv Series Agent Storage Components
30
Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator. Pressure Gauge (2) — Monitors
cylinder pressure.
Low-Pressure Supervisory Switch (3) — Mountedto cylinder valve. Monitor and annunciates lowcylinder pressure.
Rupture Disc (4) —Protects cylinderfrom over pressure.Rupture pointbetween 850 psi(58.6 bar) and 1000psi (68.9 bar)
Discharge Outlet (5)— Connects valve todischarge piping. 1-1/4 in (32 mm) femaleNPT connection.
Pilot Actuation Port(6) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. 3/8 in (10 mm)female NPTconnection.
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components
31
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components
32
Liquid Level Indicator: Nonmagnetic tube
containing a measurementtape attached to a magnet
As tape is removed, magnetengages at the liquid surfacewhere a floating metallic ballsits
Measurement can becompared with theappropriate chart in thedesign manual to determinethe current fill
DipTube
CylinderValve
CylinderBracket
Cylinder
LiquidLevelIndicator
Has features identical to SvSeries Cylinder Assembly
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Mv Series Agent Storage Components
33
Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator. Pressure Gauge Connection (2) — Attachment point for
pressure gauge
Low-Pressure SupervisorySwitch Connection (3) —
Attachment point for low-pressure supervisory switch.
Rupture Disc (4) —Protects cylinder fromover pressure. Rupturepoint between 850 psi(58.6 bar) and 1000 psi(68.9 bar)
Discharge Outlet (5)— Connects valve todischarge piping. 2 in(50 mm) groovedconnection
Pilot Actuation Port(6) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. ¼ in (8 mm)female NPTconnection
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components
34
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components
35
Rupture Disc: Protects cylinder from overpressure Rupture point is between 850 psi (58.6 bar)
and 1000 psi (68.9 bar)
CylinderValve
Dip Tube
CylinderBracket
Cylinder
Liquid LevelIndicator
Rupture Disc
Has features identical to Mv SeriesCylinder Assembly except:
Lv Series 1000 lb Cylinder notTransport Canada approved.
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Lv Series Agent Storage Components
36
Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator.
Pressure Gauge Connection (2) — Attachment point forpressure gauge
Low-Pressure SupervisorySwitch Connection (3) —
Attachment point for low-pressure supervisory switch.
Discharge Outlet (4)— Connects valve todischarge piping. 3 in(80 mm) groovedconnection.
Pilot Actuation Port(5) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. ¼ in (8 mm)female NPTconnection
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Multi Cylinders Application
Multi Cylinders application is provided for the enclosures with the volume is larger thancan be covered by single cylinder.
37
* Up to fifteen slave cylinders may be actuated from one primary cylinder* Maximum length of 100 ft (30.4 m) of pilot hose or ¼” (8 mm) copper
tubing on either side of the primary cylinder* Maximum length of 25 ft (7.62 m) of ¼” (8 mm) pilot piping on either
side of the primary cylinder
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Multi Cylinders Application
38
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Multi Zones Application
Multiple hazards can often be protected with a common set of cylinders by usingselector valves. Selector valves components are required in these specific cylinderarrangements that utilize selector valves to allow the protection of multiple hazards orhazard zones by one set of clean agent cylinder.
39
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Multi Zones Application
40
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Fluid Distribution Components
These components consist of the discharge nozzles used to atomize the liquid Novec1230 fluid and introduce it into a protected hazard along with the associated pipingsystem.
* Discharge Nozzle Ports : 4, 6, or 8 port (90°, 180°, 360°)
* Maximum nozzle height for a protected space is 18 ft 4 in (5.59 m) per tier of nozzles.
* Additional tiers are required for nozzle heights greater than 18 ft 4 in.
* Nozzles must be mounted within 4 ft 5 in (1.35 m) of the ceiling
41
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Components : Agent Fluid Distribution Components
42
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Component : Control Panel
* For systems requiring UL listing, the control panel must be UL listed and compatible
with the electrical valve actuator as indicated in the control panel manual.
* For systems requiring FM approval, the control panel must be FM approved and
compatible with the electric valve actuator as indicated in the control panel manual.
* The control panel should be located in an accessible area and installed in compliance
with NFPA 72 (National Fire Alarm Code).
43
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Component : Control Panel
44
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Component : Detection and Alarm Devices
* Detector selection is dependent upon hazard occupancy and environmental
conditions.
* Systems are designed to extinguish a fire rapidly in its incipient stage. The use of
smoke detectors of appropriate type must be considered to provide the earliest
possible indication of a fire detection with a low susceptibility to false alarms.
* For systems requiring UL listing, detectors must be UL listed and compatible with the
control panel as indicated in the control panel manual.
* Air sampling detection systems can also be utilized.
* In most applications, the detection devices are installed in a cross-zone (double
knock) or voting configuration. Cross-zoning of early warning detectors affords
stability yet provides early detection. 45
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Component : Detection and Alarm Devices
* Audible and visual devices may be utilized to indicate alarm conditions, system
status, or trouble conditions within the system.
* Audible alarm devices must be of a sufficient decibel level to be heard over the
maximum noise level in the protected hazard.
46
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
System Component : Flow Calculation Software
47
JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System
48