halton hvac handbook chilled bean design guide

Upload: bzkizosbb

Post on 04-Jun-2018

232 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    1/44

    Care for Indoor Air

    Halton- Chilled Beam Design Guide

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    2/44

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    3/443

    1. Chilled beam system 5

    2. Target definition 6

    3. Active chilled beams

    3.1 Active chilled beam system 7

    3.2 Chilled beam system design 8

    3.3 System design strategies 9

    3.4 Design elements 10

    3.5 Chilled beam model selection 12

    3.6 Adaptable chilled beam concepts 14

    3.7 Chilled beam orientation and ventilation arrangements 22

    3.8 Operation range specification 24

    3.9 Product selection 25

    3.10 Indoor climate conditions design 26

    3.11 Management of room conditions 27

    3.12 Case study 30

    4. Passive chilled beams

    4.1 Passive chilled beam system 31

    4.2 Chilled beam system design 32

    4.3 Chilled beam model selection 33

    4.4 Chilled beam orientation and ventilation arrangements 35

    4.5 Operation range definition 37

    4.6 Pre-selection and selection 38

    4.7 Design of indoor climate conditions 40

    4.8 Management of room conditions 48

    5. Customised service beams

    5.1 Luminaires and other integrated technical services 42

    Contents Chilled Beam Design Guide

    Contents

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    4/444

    Chilled beam system

    Haltons chilled beam system is an air conditioning system

    for cooling, heating, and ventilation in spaces where good

    indoor climate and individual space control are appreciated.

    A chilled beam system provides comfortable thermal

    conditions with quiet and energy-efficient operation.

    The system can be realised with active or passive chilled

    beams, integrated multi-service chilled beams, or

    bulkhead-installed horizontal induction units.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    5/445

    Chilled beam system

    Haltons chilled beam system is an air conditioning

    system for cooling, heating, and ventilation in spaces

    where good indoor climate and individual space control

    are appreciated.

    A chilled beam system provides comfortable thermalconditions with quiet and energy-efficient operation.

    The system can be realized with active or passive chilled

    beams, integrated multi-service chilled beams, or

    bulkhead-installed horizontal induction units.

    Chilled beam system design

    A chilled beam system provides excellent indoor climate

    conditions and cost-efficient life-cycle costs when realization

    is managed properly from design to use of the building,

    covering:

    Definition of targets

    System design

    Product selection

    Room control

    Ductwork and pipework design

    Central systems design

    Eventual free cooling / heat pump applications

    Installation and commissioning

    Verification of indoor climate conditions

    Flexibility throughout the lifetime of the building

    Modern office buildings are designed to allow flexibility inuse of the spaces to meet the requirements of even high

    churn rates (percentage of people moving in the building

    in one year).

    The air conditioning system design can be carried out

    according to different strategies, for more limited to full

    flexibility:

    Traditional design

    AdaptableClimateconcept

    Flexibility requirements can affect the design, logistics in

    transport and at the site, and the tasks required when room

    layout or the use of space changes.

    Halton chilled beams

    Haltons chilled beam range includes many different types

    and models:

    Adaptable active chilled beams (ACC, ACE) for suspended-

    ceiling and exposed installation

    Active chilled beams for suspended-ceiling installation

    (ABC, ABD)

    Active chilled beams for exposed installation (ABE, ABH)

    Passive chilled beams for suspended-ceiling installation

    (APA)

    Passive chilled beams for exposed suspended-ceiling

    installation (APT)

    Customized active and passive service beams for both

    suspended-ceiling and exposed installations Compact, bulkhead-installed induction units with uni-

    directional horizontal air supply (AHH)

    Applications for different chilled beam types

    Active chilled beams. Active chilled beams are well suited

    to private and public office buildings, health care facilities,

    and hotel buildings in new construction as well as

    refurbishment projects.

    Active chilled beams are especially suitable for landscape

    and cell offices, patient care spaces, and hotel guest rooms.

    Adaptable active chilled beams are ideal for flexible office

    spaces, where office layouts are changed frequently and

    spaces are shifted often between office rooms and team,

    project and meeting rooms.

    Passive chilled beams. Passive chilled beams are used

    in the same applications as active chilled beams. There

    are, however, specific conditions favoring passive beam

    installations:

    Applications where ventilation rates are relatively high

    e.g., 0.7 0.9 cfm/ft2

    Refurbishment projects where the existing ventilationsystem is to be preserved for the most part

    Where ventilation is realized using a separate system

    e.g., an under-floor air distribution system

    Chilled beams with uni-directional air supply.Units with

    uni-directional air supply are used in spaces where most of

    the ceiling is left free of room unit installations. The units

    can be standard chilled beam units designed for

    performance with uni-directional supply or units dedicated

    to uni-directional air supply in exposed or bulkhead

    installations.

    Customized service beams.Active and passive

    customized service chilled beams are feasible for

    refurbishment projects in office and other public buildings.

    The benefits of customized service beam systems are:

    Effective installation of technical services and good total

    quality of installations due to off-site manufacturing and

    short construction process

    Selection of exposed or ceiling-integrated beams on the

    basis of a feasibility study for the building by consulting

    engineers

    The ability to create aesthetic interior

    1. Chilled beam system

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    6/446

    Target definition

    2. Target definition

    When the main targets for system operation and performance are set, indoor climate target values are specified.

    One of the key goals in designing good indoor climate conditions is to adjust the cooling and heating capacity to the

    level that meets both optimal comfort and energy-efficiency targets.

    In addition, module sizing and flexibility requirements are important factors influencing both design decisions and

    life-cycle cost management for the building. It is also important to take into account national and international

    standards and building codes.

    Indoor climate target levels according to CEN report 1752, on maximum values for thermal conditions.

    Indoor climate factor Classification

    Unit A B C

    Operative temperature Winter F 71 2 71 3.5 71 5

    Operative temperature Summer F 76 2 76 3 76 4Vertical temperature gradient 0.3 ft / 0.3 ft F 3 5 7

    Mean air velocity Winter fpm 30 35 40

    Mean air velocity Summer fpm 35 43 50

    Sound pressure level Office rooms NC 30 33 35

    Sound pressure level Landscape offices NC 35 38 40

    Ventilation rate Office rooms cfm/ft2 0.45 0.3 0.2

    Ventilation rate Landscape offices cfm/ft2 0.35 0.25 0.15

    Ventilation rate Meeting rooms cfm/ft2 1.3 0.9 0.5

    Design assumptions Occupancy:

    Clothing:

    office rooms 100 ft2per person

    landscape offices 70 ft2per person

    meeting rooms 50 ft2per person

    0.5 clo summer; 1.0 clo winter

    Indoor climate design conditions:

    Thermal conditions as specified in national or

    international standards or classifications

    Room air temperature or operative temperature

    Mean room air velocity or draught rate (DR)

    Internal surface temperatures and radiant

    asymmetry

    Air quality criteria as specified in national or

    international standards or classifications air qualityoften is indicated in terms of:

    Outdoor air flow rate

    CO2concentration

    Sound level requirement is expressed as:

    Noise Criterion NC

    Sound pressure level Lp(A)

    Typical space design data

    Room and module dimensions

    Space usage, internal load and occupancy levels

    Window and wall types, and solar shading

    Life cycle costs:

    Target system investment cost level ($/ft2)

    Energy-efficiency targets' levels can be expressed

    as specific level of consumption of heating energy

    and air conditioning and electric power (fan power).

    The building should be classified according to these

    consumption levels.

    Maintenance level targets indicate:

    Predicted service intervals

    Labor demand

    Accessibility of service points

    Need to replace parts / replacement interval

    (valve, filter, motor, and other parts.)

    Flexibility for change:

    Flexibility requirements can be characterized with

    the required tasks when layout or the use of space

    changes:

    Need for office / meeting room changes

    Need to relocate internal walls

    Need for installation / reconnection of terminal

    units or control units

    Adjustment of airflow rates

    Adjustment of water flow rates

    Other adjustments (e.g. personal requirements)

    Order delivery chain:

    Targets for order delivery indicate the versatility of

    the terminal unit in terms of their models, sizes and

    operation parameters.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    7/447

    Active Chilled Beams

    3. Active chilled beams

    3.1 Active chilled beam systemThe chilled beam system is an air/water system for high-

    temperature cooling and low-temperature heating that

    utilizes the excellent heat transfer properties of water

    and provides a good indoor climate energy-efficiently.

    Typically, a chilled beam system is realized as a dedicated

    outdoor air system with sufficient airflow rates to ensure

    good indoor air quality.

    Either the system employs a four-pipe system or a

    separate perimeter heating system is used. Even two-

    pipe application with system changeover between

    cooling and heating is used.

    Operation of the systemChilled beam systems are designed to use the dry

    cooling principle, operating in conditions where

    condensation is prevented by control applications.

    Chilled water can be produced by a dedicated chiller only

    for chilled beams or a common chiller for air handling units

    with a separate, flow-water-temperature-controlled loop for

    chilled beams, preferably connected via a buffer tank.

    Space temperature control is realized with variable water

    flow control using either on-off or proportional control

    principle.

    Ventilation

    Ventilation using active chilled beams is an efficient mixing

    ventilation application that results in uniform air quality.

    Supply air is discharged into the space through linear slots

    on either both sides or only one side of the chilled beam.

    Horizontal induction units have grilles for horizontal air

    supply. In demand-based ventilation applications, supply

    airflow can be increased by means of an integrated

    diffuser without affecting the heat transfer of the chilled

    beam.

    Cooling

    Active chilled beams use the primary air to induce and

    recirculate the room air through the heat exchanger of

    the unit, resulting in high cooling capacities and excellent

    thermal conditions in the space. High-temperature

    cooling enables the use of various free-cooling sources,like outdoor air, sea water and geothermal energy etc.

    Heating

    Integration of heating into chilled beams is

    recommended when the specific heating capacity of the

    chilled beam units is reasonably low (155 260 Btuh/ft),

    and the low heat transmission through the windows

    prevents a downdraught under the window.

    Low-temperature heating enables the use of various

    waste-heat sources. Alternatively to hydronic heating,

    electric heating can be integrated in chilled beam units.

    Schematic diagram of a chilled beam system with both cooling and heating functions.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    8/448

    Chilled beam system design

    3.2 Chilled beam system design

    A chilled beam system can be designed to fulfill requirements for sustainable, energy-efficient buildings that provide

    flexible use of space and a healthy and productive indoor climate. A chilled beam system can realize excellent indoor

    climate conditions in terms of thermal and acoustic properties throughout wide operation ranges and in many

    installation scenarios.

    There are several choices to be made, each having an influence on the performance, investments, operation, and

    maintenance costs. The tables below present the range of variation of the main design characteristics and typical

    ranges of operation for a chilled beam system.

    MAIN CHARACTERISTICS FOR CHILLED BEAM SYSTEM EVALUATION

    Indoor climate conditions

    AdaptableClimateconcept Traditional concept

    Good indoor climate conditions and efficient, practical operation

    with highly realistic design data for the building's whole life cycle.

    Reservations for performance at extreme capacity levels with high

    safety margins.

    Use of the space

    Changes in use of the space and layout changes with marginal

    churn costs.

    Optimized performance and unit cost for individual spaces with

    limitations in flexibility.

    Relatively high churn costs.

    Efficiency of logistics

    Effective design, installation, and commissioning processes;

    streamlined logistics with a uniform product range.

    Need for individual product identification in design, ordering,

    delivery, and installation.

    Life-cycle performance

    Higher investments in more efficient chilled beams (greater

    difference), enabling savings in pipework central units and lower

    operation costs.

    Lower investment costs for chilled beams and higher total

    investment and operating costs.

    TYPICAL INPUT VALUES AND OPERATION RANGES

    Room temperature, summer 73 77 F

    Room temperature, winter 68 72 F

    Supply air temperature 61 66 F

    Water inlet temperature, cooling 57 61 F

    Water inlet temperature, heating 95 104 F

    Target duct pressure level 0.3 0.5 in WC

    Target water flow rate, cooling 0.32 1.6 gpm

    Target water flow rate, heating 0.16 0.65 gpm

    Noise criteria NC 30

    Outdoor air flow rate / floor area, offices 0.33 0.55 cfm/ft2

    Outdoor air flow rate / floor area, meeting : 0.33 0.9 cfm/ft2

    Outdoor air flow rate / effective unit length 3.6 ... 9 cfm/ft

    Additional air flow rate in meeting rooms 0 ... 53 cfm per unit

    Cooling capacity / floor area 25 Btuh/ft2 38 Btuh/ft2*

    Cooling capacity / effective unit length 250 Btuh/ft 400 Btuh/ft *

    Heating capacity / floor area 4 Btuh/ft2 19 Btuh/ft2**

    Heating capacity / effective unit length 150 Btuh/ft 200 Btuh/ft **

    Note * It is reasonable to study the room air velocity conditions carefully

    Note ** It is reasonable to study the thermal conditions carefully

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    9/449

    System design strategies

    When a chilled beam system is designed and chilled beams are selected, there are several angles to be considered.

    The main target is to achieve excellent indoor climate conditions in spaces for the whole life cycle of the building,

    even if there is a continuous need to make changes in the space usage or layout. Through designing and selecting

    chilled beams according to an adaptable strategy, this target can be achieved.

    3.3 System design strategies

    Adaptable system design

    Adaptable system selection strategy provides benefits

    to the facility owner, who can modify spaces more

    quickly and with less cost over the facility's lifetime.

    Thermal condition management using Halton Velocity

    Control (HVC) and air quality control using Halton Air

    Quality (HAQ) provide continuously good indoor

    climate conditions.

    The design and installation teams can also benefit,

    because changes in the use or size of spaces during

    System design

    strategyAdaptableClimateconcept Traditional concept

    Indoor climate

    conditions

    Room air temperature 754 3.5 F 754 3.5 FRoom air velocity ... 50 fpm ...50 fpm

    ... 60 fpm temporarily during peak loadsRoom air quality

    CO2- concentration

    Ventilation rate

    900 ppm

    0.31 cfm/ft2

    (variable flow in meeting rooms)

    1000 ppm

    0.375 cfm/ft2

    (constant airflow in meeting rooms, or separate

    variable airflow application)Cooling capacity

    levels

    2025 Btuh/ft2 2040 Btuh/ft2

    Heating capacity 612 Btuh/ft2 620 Btuh/ft2

    Adaptable

    performance

    Halton Velocity Control (HVC) is designed at normal

    position (2).

    Adjustment in throttle (1) and full (3) position, when

    required.

    Adjustment of constant airflow rates and using Halton

    Air Quality (HAQ) control.

    Adaptation by increasing the number of terminal

    units.

    Chilled beam

    positioning

    Always perpendicular to perimeter wall Either parallel or perpendicular to perimeter wall

    Life cycle costs

    Flexibility Full flexibility in layout and application changes: no

    installation work during changes.

    Churn costs of 100130 $/ft2.

    Limited flexibility in layout and for changes in

    operation conditions.

    Churn costs of 7501000 $/ft2.Product cost Some extra cost for flexibil ity in room units, zones,

    and central system costs.

    Basic investment.

    Additional installations for variable flow application in

    meeting rooms.Focus in product

    selection

    Nozzle size, length, and effective length that are the

    same using adaptable active chilled beams.

    Various nozzle sizes, lengths, and effective lengths

    according requirements using basic active chilled

    beams.

    Water flow control and adjustment valves which are

    selected project- specifically and installed on siteChanges in space use

    and layout in the design

    and installation process

    No effect of changes in use or size of space on chilled

    beam selection

    Eventual reselection of chilled beams after significant

    changes of use or size of the spaces

    Commissioning Adjustment of chilled beams on site; no traditional

    commissioning needed.

    Constant-pressure control dampers in zones allow

    quick airflow rate adjustments and variable airflow in

    meeting rooms.

    Maximum limit flow valves allow quick adjustment of

    water flow rates without balancing need.

    Traditional commissioning comprising

    manual balancing of airflow rates using adjustment

    dampers

    manual balancing of water flow rates using

    adjustment valves

    Note: Typical design values. Check case by case.

    the design and construction process do not influence

    the beam selection.

    Traditional system design

    Designing and selecting chilled beams according to

    traditional strategy allows indoor climate targets to

    be met in the design conditions, but future changes in

    use or layout may influence the products

    performance.

    This strategy results in a lower investment cost, but

    changes during operation are more costly.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    10/4410

    Design elements

    A chilled beam system can realize excellent indoor climate conditions in terms of thermal, air quality, and acoustic

    conditions within wide ranges of operation and in various installation cases. Operation should, however, be

    designed with conditions in the occupied zone in all seasons (winter, summer, and intermediate season) taken into

    account. For the best result, the following technical issues should be considered also.

    3.4. Design elements

    Ventilation and air diffusion using chilled beams

    Primary air from the nozzles (3.5 9 cfm/ft) induces

    3 5 times the room air (depending on chilled

    beam type and operating conditions).

    A total airflow rate of 10 40 cfm/ft is discharged

    from one/two slots into the space.

    Make sure that airflow rates can be realized at actual

    chamber pressure levels.

    Minimum supply chamber pressure is 0.2 0.3 in

    WC to ensure the correct supply air jet throw

    pattern.

    Check that the required throttle for balancing can be

    achieved with the adjustment damper at an

    acceptable sound level.

    The supply airflow rate is high enough to remove

    internal humidity loads.

    The supply air jet should stay attached to the ceiling

    (Coanda effect) and not fall directly into the occupied

    zone.

    Thermal loads in the occupied zone may influence

    the air jet direction and air distribution in the

    occupied zone.

    Analyze supply jet interaction with convective flows

    caused by a cold or warm window surface to ensure

    that it doesn't create a draught risk.

    When already detached from the ceiling, jets of two

    parallel chilled beams should not collide at a velocity

    level that results in a draught.

    The increase of airflow rate according to demand

    should not have a significant effect on the coil

    cooling capacity.

    Cooling using chilled beams

    The thermal properties of the external walls and

    window construction should be appropriate.

    The required cooling capacities should be max.

    20 25 Btuh/ft2.

    Chilled beam capacities (250 360 Btuh/ft) match

    supply airflow rates (3 9 cfm/ft) to provide good

    air distribution and draught-free conditions in the

    occupied zone.

    Water flow rates and pressure drops of chilled

    beams are in line with chilled water pipe work

    design and pumping cost target levels.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    11/4411

    Design elements

    Heating

    Proper system operation cannot be achieved by over-

    dimensioning the heating capacities. In a modern

    office building, 8 15 Btuh/ft2of floor area is typically

    sufficient heating capacity.

    The heating capacity of active beams is dependenton the primary airflow rate. This is why ventilation

    shall be in operation when heating is required.

    The heating capacity of active beams is typically

    160 260 Btuh/ft, and the inlet water temperature

    should be 95 115 F to create sufficient mixing

    between the supply air and room air.

    Both window draught due to radiation and

    downward convective air movement during cold

    seasons need to be eliminated.

    An efficient control system is used. It isrecommended to have room air temperature

    measurement integrated into a chilled beam, with

    heating control based on the room air temperature

    near the ceiling.

    Operation case study: Chilled beams parallel to the

    perimeter wall

    In this type of installation, it is especially important to

    have windows with adequate thermal properties for

    avoiding excessively high room air velocities inintermediate seasons.

    This study was performed using computational fluid

    dynamics (CFD) software. Air velocity is higher than

    50 fpm in the green areas.

    The images present the room air velocities in the

    same space in three seasons: summer (1), spring (2)

    and winter (3).

    1

    2

    3

    The images present the room air velocities in the same space in three seasons: summer (1), spring (2) and winter (3).

    Temperature conversion

    17.7 C = 64 F

    24 C = 75 F

    28 C = 82 F

    17 C = 62.6 F

    20.2 C = 68 F

    22 C = 71.6 F13 C = 55.4 F

    22 C = 71.6 F

    25.4 C = 77.7 F

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    12/4412

    Active chilled beam model selection

    The appropriate active chilled beam model is selected by

    taking into account the following factors:

    Architectural design

    Preferred appearance

    Desire for exposed installation or a solution integrated

    into a suspended ceiling

    Adaptation to the ceiling

    Positioning with respect to light fittings Integration of light fittings

    Room design grid dimensions and available space

    Requirements for flexibility and eventual partition

    wall locations

    Cooling capacity and ventilation rate requirements

    Building services integrated into chilled beams:

    Light fittings, controls, sensors, detectors, and cabling

    Adaptable active chilled beams are selected when the

    requirements for cooling capacities and ventilation rates need

    to be adjusted along with the space layout changes or when

    variable airflow is used for demand based ventilation.

    3.5. Active chilled beam model selection

    Active chilled beams in suspended ceiling installation

    Customized service beam.

    Active chilled beam in wall installation.

    Active chilled beam in exposed installation

    Active chilled beam in suspended ceiling installation

    Active chilled beam in bulkhead installation or

    in exposed installation.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    13/4413

    Active chilled beam model selection

    Active chilled beams in exposed installation

    Active chilled beams in wall installation

    Customized service beams in exposed installation.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    14/4414

    Adaptable chilled beam concepts

    Halton AdaptableClimatechilled beamsoffer unique flexibility from design through use. Their operation adapts easily

    to changes in space usage, layout, or user requirements throughout the buildings life cycle.

    Good indoor climate conditions are maintained with high energy-efficiency when an open-plan office is changed into

    cellular offices or meeting rooms.

    Chilled beams adapt thermal conditions to meet individual requirements, also in open-plan offices. Thus indoor

    climate conditions are optimal in all usage situations throughout the buildings life cycle.

    3.6. Adaptable chilled beam concepts

    Benefits of the Halton adaptable chilled beams:

    Wide operation range simplifies design and

    specification

    Good thermal comfort and indoor air quality

    Adjustable air flow rates

    Air velocity management

    Enhanced flexibility

    Free location of offices and meeting rooms

    Identical look of units for different

    spaces

    Air flow control that can be installed as

    needed

    Improved logistics

    Smooth order-to-delivery process

    Effective on-site handling

    Features:

    Primary air flow rate adjustment of 0.3 to 0.9 cfm/ft2

    in layout change from office room to meeting room

    using Halton Air Quality control (the air flow control

    does not affect the coil capacity, and thus over-

    chilling is avoided)

    Ability to achieve individual desired velocity

    conditions in the occupied zone even when partition

    walls are repositioned, by adapting the operation

    using Halton Velocity Control

    Integrated control and max. flow limiter valves for

    cooling and heating capacity allowing reset without

    influencing the water flows of other chilled beams

    (optional)

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    15/4415

    Adaptable chilled beam concepts

    Primary airflow rate

    Room Space type HVC position Nozzles qv1

    HAQ qv2

    Total qv1

    + qv2

    Total qv1

    + qv2

    left right cfm cfm cfm cfm/ft2

    1, 2, 3 Office 3 1 32 11 43 0.48

    4 Meeting room 2 2 32 0 ... 53 32 ... 85 0.9

    Management of ventilation rates using

    Halton Air Quality (HAQ) control

    The air flow rate of the chilled beam is dependent on

    Effective length, Leff

    Chilled beam chamber pressure, DPm

    Nozzle size, Dnoz

    Halton Air Quality control unit adjustment position,

    AQ

    The chamber pressure is adjusted by changing the

    position (a) of the airflow adjustment damper to match

    available duct pressure at the room branch.

    Four nozzle sizes are available, to enable attaining the

    minimum supply air flow rate of the chilled beam at

    the set pressure level in a typical room module.

    There is no need to change or plug nozzles of the

    chilled beam.

    Halton Air Quality control allows increasing the chilled

    beam airflow rate to meet the ventilation requirements

    of spaces such as:

    office spaces: 0.3 0.6 cfm/ft2

    meeting rooms: 0.7 0.9 cfm/ft2

    Air flow control

    The ventilation requirements of meeting and team

    rooms vary greatly according to the occupancy level.

    Demand-based ventilation control using, e.g., CO2

    sensors, contributes to a highly energy-efficient

    operation.

    In addition to manual adjustment damper operation,

    the HAQ damper can be equipped with an actuator

    controlled by a room controller.

    Factors influencing an active chilled beams air flow rate.

    Office rooms.

    Meeting room.

    By integrating the airflow control into the chilled beam

    unit, flexibility in use of the space is ensured.

    When rooms with constant and variable airflow rates

    are both served by the same distribution ductwork,

    constant pressure conditions are needed to guarantee

    the designed airflow rates.

    See the section Constant-pressure ductwork for

    efficiency for more information.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    16/4416

    Halton ACE with air quality control.The Halton Air

    Quality control unit is on the top of the chilled beam,

    supplying air upward. It is recommended to position

    the beam at a minimum distance of 2 ft from the wall

    and 4 in from the ceiling.

    The Halton Air Quality control unit is adjusted manually

    or, alternatively, controlled by an actuator connected to

    a room controller.

    The HAQ unit can be retrofitted later as required. Also

    the actuator can be mounted later, when changes in

    room layout are implemented.

    Total airflow rate of the chilled beam unit can be 4 to

    20 cfm/ft when equipped with HAQ control.

    The Halton Air Quality control unit does not increase

    the length of the chilled beam.

    Halton ACC with air quality control. In the Halton ACC

    solution, the air quality control unit is at the opposite

    end of the unit from the supply air connection. Thethrow pattern of the air quality control unit is

    bi-directional like that of the chilled beam.

    The effective length of a chilled beam equipped with

    air quality control unit (either manual or motorized

    version) is 2 ft shorter than the total length. The look

    of the Halton ACC unit is identical to that of the ABC

    chilled beam without HAQ unit.

    Halton ACE with air quality control in a meeting room.

    Adaptable chilled beam concepts

    Halton ACC with air quality control in a meeting room.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    17/4417

    Adaptable chilled beam concepts

    Management of room conditions using

    Halton Velocity Control (HVC)

    Halton Velocity Control is used for adjusting room air

    velocity conditions either when room layout changes

    (e.g., in cases where the partition wall is located near

    the chilled beam) or when local, individual velocity

    conditions need to be altered.

    Halton Velocity Control does not affect the primary

    supply air rate, but it does have a slight effect on the

    cooling and heating capacities of the unit. The

    capacities and velocities can be studied using the HIT

    Design software.

    It is recommended to design the chilled beam in the

    normal position in order to allow both minimization

    (throttle) and maximization (full) functions later in the

    buildings life cycle.

    Halton Velocity Control dampers are divided into

    sections to enable the desired adjustment of velocity

    conditions in different parts of the occupied zone.

    Depending on the length of the beam, optimal lengths

    of HVC damper modules are used as follows:

    ABC or ACC 1 ft , 1 ft 8 in, and 2 ft 8 in

    ABE or ACE 1 ft, 2 ft, and 2 ft 8 in

    Halton Velocity Control provides manual velocity adjustment on both

    sides of the chilled beam, with three positions: 1 = throttle position, 2= normal position, and 3 = boost position.

    Adjustment of local velocity conditions is possible also in an

    open-plan office with Halton Velocity Control.

    Partition wall located close to the chilled beam. Halton

    Velocity Control is adjusted to position 1 on one side and

    position 3 on the other.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    18/4418

    Adaptable chilled beam concepts

    Halton Velocity Control is available for both exposed

    and ceiling-installed chilled beams.

    Halton Velocity Control in boost (3) and throttle (1) position in a

    Halton ACC chilled beam.

    Halton Velocity Control in boost (3) and throttle (1) position in a

    Halton ACE chilled beam.

    Case Study

    Flexibility for layout changes can be designed in with the HVC and HAQ concepts. Chilled beam installation adapts

    to different room sizes and layout, providing required capacities and maintaining good comfort level.

    Primary airflow rate

    Room Space type HVC position Nozzles qv1

    HAQ qv2

    Total qv1

    + qv2

    Total qv1

    + qv2

    left right cfm cfm cfm cfm/ft2

    1 Office 3 1 32 11 43 0.48

    2 Office 3 3 32 32 64 0.48

    3/Unit A Office 1 3 32 0 32 0.48

    3/Unit B Office 3 1 32 0 32 0.48

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    19/4419

    Constant-Pressure Air Distribution System

    Constant-pressure ductwork for efficiency

    In traditional active chilled beam systems, the ductwork

    is a proportionally balanced constant-air-flow distribution

    system. However, there are reasons it is beneficial or

    otherwise reasonable to arrange the airflow

    management using active constant-pressure control

    dampers. Among these are that

    chilled beams with pressure-dependent variable flow

    and constant flow are combined in the same

    ductwork sections and proper operation conditions

    are ensured

    frequent individual air flow adjustments of chilled

    beam units can be made without the need to balance

    the ductwork

    pressure control dampers allow zone ventilation

    operation hours locally, contributing to energy

    conservation in office buildings where tenants office

    hours tend to differ, for example

    Adaptable chilled beam concepts

    Combined pressure-dependent variable flow and constant flow.

    Ductwork is divided into constant-pressure zones,

    allowing individual adjustment of the air flow rates of

    each room and continuous air flow control according to

    demand in meeting rooms.

    The ductwork is sized using low velocities (< 1200

    fpm), taking into account the predicted max. flow rate

    in order to minimize pressure losses within the zone

    and to maintain the desired air flow accuracy and meet

    cooling capacity requirements.

    Ductwork balancing is not needed in constant-pressure

    duct systems when unitary airflow rates are adjusted

    (e.g., for office room space changes). Even constant

    airflow rates of office rooms can be integrated into the

    same ductwork as variable air flow rate control for

    meeting rooms.

    Typically, the use of units that are similar (in length or

    nozzle type), along with individual adjustment of airflow

    rates, allows effective commissioning of the system.

    Fan pressure control

    Fan speed control is typically used when variable flow

    is required. In small and symmetric low-velocity

    ductwork, the need for zone dampers is not evident,

    but larger duct systems shall be divided into sections,

    where duct pressure is kept constant by means of zone

    dampers.

    Adaptation to the variable operation conditions of a

    variable flow system can be realized with variable-speed

    drives controlled by frequency converters. The

    target is to maintain a duct pressure level that is as low

    as possible in order to save on fan power consumption.

    The pressure controller maintains a constant or

    optimized pressure level in the ductwork using a

    pressure sensor as feedback. The sensor measures the

    static pressure relative to prevailing pressure in the

    building.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    20/44

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    21/4421

    Zone balance arrangements

    When in the zone there are both units with constant

    and units with variable flows, the exhaust is liable to

    pressure deviations due to higher pressure losses in

    the main branch duct and lack of regaining static

    pressure. The air flow balance in spaces in meeting

    rooms with variable flow can be realized in different

    ways:

    Ducted exhaust using a variable flow control damper

    Continuous balanced ducted exhaust for constant

    flow

    Transfer air via a grille to the corridor

    Common zone exhaust tracking the variable

    common supply airflow

    Transfer air via a grille to the corridor

    Common zone exhaust tracking the common

    variable supply flow

    Adaptable chilled beam concepts

    Combination of ducted constant airflow exhaust and variable transfer

    to common exhaust.

    Ducted variable airflow exhaust using variable airflow control

    damper.

    Transfer air from spaces to common exhaust.

    The common exhaust can take care of the air exhaust

    of meeting rooms and eventual open office areas.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    22/4422

    Chilled beam orientation and ventilation arrangements

    3.7. Chilled beam orientation and ventilation arrangements

    Chilled beams can be installed either perpendicularly or parallel to the perimeter wall. However, perpendicular

    installation is recommended, as occupied zone velocities are thus lowest in all seasons. When chilled beams are

    installed parallel to the wall, intermediate-season conditions (cold window surface and internal heat loads) should be

    analyzed. Otherwise, cool supply air with a cold window can easily create increased velocities under windows.

    Perpendicular installation of chilled beams.

    Parallel installation of chilled beams.

    Selection of active chilled beam orientation Indoor climate conditions

    Capacity per chilled beam unit

    Residual velocities for occupied zone

    Supply air jet interaction with convective flows

    Suitability for room module dimensions

    Suitability in view of lighting fixture locations Flexibility for layout changes

    Minimum recommended distance between parallel

    beams

    Minimum recommended distance between chilled

    beam and wall/ceiling

    Sidewall installation of chilled beams.

    Bulkhead installation of horizontal induction units.

    Sidewall installations of chilled beams in a hotel guest room. Bulkhead installation of horizontal induction units in a hotel guest

    room.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    23/4423

    Chilled beam orientation and ventilation arrangements

    Exposed installation above a work area:

    symmetric throw pattern.

    Exposed installation close to wall:

    asymmetric throw pattern.

    Selection of active chilled beam air arrangements

    Active chilled beams should be positioned above workspaces to ensure comfortable velocity conditions. If the

    chilled beam is positioned close to a wall, an asymmetrical throw pattern is recommended. Minimum installation

    distances from walls and between parallel chilled beams are presented in the product data sheets.

    Exhaust air units have minor importance to the solutions operation.

    Suspended-ceiling installation above a work area: symmetric

    throw pattern.

    Wall installation in hotel guest room.

    Bulkhead installation in hotel guest room.

    Bi-directional air supply

    Perpendicular to exterior wall in offices (preferable),

    above the work area

    Parallel to exterior wall above work area

    Perimeter installation, with uni-directional supply

    Corridor installation limited application, depending

    on work area location and providing bi-directional

    supply horizontally and downward

    Uni-directional air supply

    Hotel guest rooms preferably above bed (above

    window as another option)

    Patient ward rooms preferably above bed either

    along side walls or parallel to exterior walls

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    24/4424

    Operation range specification

    3.8. Operation range specification

    A chilled beam systems operation range is determined on the basis of representative rooms. The selected rooms

    are studied to determine cooling and heating loads via dynamic energy simulation software. After assessment of

    load patterns in the representative rooms, chilled beam operation parameters are set. The design target values can

    be verified by a full-scale mock-up or computational fluid dynamics (CFD) simulation.

    Typical input values and operation ranges (extreme target values in brackets)

    Room temperature for cooling 73 77 F

    Room temperature for heating 68 72 F

    Supply air temperature for cooling 61 66 F

    Supply air temperature for heating 61 66 F

    Water inlet temperature for cooling 57 61 F

    Water inlet temperature for heating 95 113 F

    Target duct pressure level for cooling 0.3 0.5 inWC

    Target water flow rate for cooling 0.32 1.6 gpm

    Target water flow rate for heating 0.16 0.65 gpm

    Outdoor air flow rate per unit floor area Offices: 0.33 0.55 cfm/ft2, meeting rooms: 0.33 0.9 (1.1) cfm/ft2

    Outdoor air flow rate over effective length 3.6 ... 9 cfm/ft

    Cooling capacity per unit floor area 25 (38) Btuh/ft2

    Cooling capacity / beams effective length 250 (400) Btuh/ft

    Heating capacity per unit floor area 4 (19) Btuh/ft2

    Heating capacity / beams effective length 150 (250) Btuh/ft

    Comfort / PMV -0.5 ... +0.5

    Draught rate (DR) < 15%

    Average room air velocity Cooling: 45 fpm

    Heating: 35 fpm

    Definition of design conditions and operation

    parameters

    Ventilation rates in spaces as rate per floor area

    (cfm/ft2)

    Ventilation rate in spaces as rate per person (cfm/

    person)

    Cooling capacity demand in spaces, in Btuh/ft2, and

    actual breakdown of loads Heating capacity demand in spaces, in Btuh/ft2, and

    actual breakdown of loads

    Model rooms and operational parameters

    Room temperature

    Supply air temperature

    Water inlet temperature

    Target duct pressure level

    Target water flow rate

    Maximum sound pressure levelVerification of target design values with full-scale mock-up and CFDsimulation

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    25/4425

    Product selection

    1. Design data in cooling

    Insert the supply air flow rate and temperature

    Specify the temperature difference between the

    inlet and outlet water of the beam, or, optionally,

    insert the inlet water temperature and target water

    flow rate.

    Calculate the coil capacity using HIT Design, and

    compare the coil capacity against the requirement.

    Note the capacities transferred by the coil and

    primary air.

    2. Chilled beam location and velocity control

    adjustment

    The location and number of chilled beams are

    specified (also, asymmetric positioning is possible).

    The HVC positions are set to allow adjusting the

    throw pattern in the space and providing the

    required velocity conditions in the occupied zone.

    To provide adaptability to load variations, use

    velocity control (HVC) position 2 (normal position).

    3. Air quality control adjustment

    Set the HAQ airflow rate to match the required

    room airflow rate.

    HAQ control can be used to adjust the airflow rate

    at a specified duct pressure level.

    4. Space results / unit performance Check the operation parameters against system

    operation conditions to verify that the operation

    parameters correspond to those of the system.

    5. Design data in heating

    Analysis is as in the cooling case.

    6. Space results / unit performance in heating

    Analysis is as in the cooling case.

    Design data window in Halton HIT Design selection.

    Room dimensions, occupied zone, and design criteria are specified in

    the Room window in Halton HIT Design.

    1, 5 2

    3

    4, 6

    3.9. Product selection

    Make your design process more efficient with the Halton HIT Design software design tool. Halton HIT Design

    enables product selection and performance simulation for the product(s) that addresses, e.g., air velocity, cooling

    and heating capacity, throw pattern, and sound level.

    Calculate the cooling and heating capacity of the selected chilled beam units by studying chilled beam performance

    in the chosen model rooms defined by yourself using desired operation parameters.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    26/4426

    Indoor climate conditions design

    4.2 m

    4.0 m

    v3

    Study the supply air throw pattern properties and

    room air velocities (in design case)

    Room air velocities in occupied zone within set limits

    (non-isothermal and isothermal cases)

    Temperature difference between air jet and room air

    Distance at which the jet detaches from the

    ceiling (Ld)

    Pressure loss lower than the available pressure in

    the duct (check that the noise level is within the

    limits set) Adjustability of the air flow rate

    In cases involving several units; check the impact of

    jet interaction on occupied zone boundary velocities

    (refer to Lmin

    in the leaflet's quick selection table).

    3.10. Indoor climate conditions design

    Simultaneously with the performance values, verify also that predicted the room conditions are acceptable,

    providing efficient air distribution but eliminating draught risks.

    Check supply air throw pattern in heating

    Simultaneously with the performance values, verify

    also that the predicted room conditions are

    acceptable, providing efficient air distribution:

    Supply air throw pattern and room air velocities (HVC

    position as in cooling)

    Supply jet adequately reaching occupied zone level

    Flow water temperature within recommended range Heating capacity

    Impact of the HVC arrangement

    Impact of the HAQ arrangement

    Study optional room modules

    Unit pressure drop (keep at the same level as

    before)

    Operation with optional room cooling load levels /

    room usage

    Impact of HVC in other positions (1 and 3) Impact of the HAQ arrangement

    Operation in optional room module configurations

    If targets for indoor climate condition are not met,

    change the length and/or

    beam properties, or even

    the beam type

    Halton HIT Design Performance view (2D).

    Halton HIT Design Performance view (3D).

    4.0 m

    v3

    CCE/A-3800-3500+AQ(0.0)2006.03

    Room: Room C

    Room size: 4.2 x 4.0 x 3.0 m

    Room air: 24.0 C / 50 %

    Heat gain: 0 W

    Instal lation height: 2 .9 0 m

    Inlet water temperature: 15.0 C

    Outlet water temperature: 20.1 C

    Wat er mas sf low: 0 .0 40 kg /s (2 x 0 .0 20 kg /s )

    Coil capacity: 858 W (2 x 429 W)

    Wat er p re ssur e d ro p: 0 .6 kPa

    To ta l sup ply a ir fl ow : 3 6 l/ s ( 2 x 1 8 l/ s)

    Supply air temperature: 18.0 C

    Prima ry ai r cap ac it y: 2 58 W ( 2 x 12 9 W)

    Tot al pr es sure dro p: 8 3 P a

    Total sound pressure level: 19 LpAre 10m2sab

    To ta l coo ling po we r: 1 11 6 W ( 2 x 5 58 W)

    Dew point temperature: 12.9 C

    HVC position side=1, middle=3

    Temperature d if ference: Tv3=1.2 C

    Ld: -

    vmax in occupied zone: v3=0.15 m/s v3(dt=0)=0.10 m/s

    vlim = 0.20 m/s

    Heat sources and their location may influence to the velocity and direction of the jet.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    27/4427

    Management of room conditions

    3.11. Management of room conditions

    Air flow measurement can be implemented accurately by measuring the chamber pressure of the chilled beam.

    Adjustment and balancing methods

    Traditional

    Proper operation conditions for chilled beams are

    ensured by adjustment of airflow and water flow

    rates.

    Airflow rates can be adjusted by balancing the

    ductwork by means of zone balancing dampers and

    the balancing damper of each chilled beam. The

    balancing damper can be integrated into the chilled

    beam or into the connecting branch. K factors and

    safety distances are presented in the HIT Design

    software package.

    Airflow measurement can be implemented accurately

    by measuring the chamber pressure of the chilled

    beam. Also, system-powered self-balancing dampers

    can be used. A self-balancing damper increases the

    total pressure drop to 0.16 0.6 inWC.

    Water flow rates can be adjusted via zone balancing

    valves and the balancing valve of each chilled beam.

    Halton Adaptable

    In constant-pressure zones, the unitary airflow rate

    adjustment does not affect the airflow rates of other

    chilled beams. Commissioning can be implemented

    very effectively. Furthermore, balancing is not needed

    when unitary airflow rates are adjusted, e.g., for office

    room space changes.

    Even constant airflow rates of office rooms can be

    integrated into the same ductwork as variable air flow

    rate control for meeting rooms.

    Water flow rates can be controlled using an automatic

    flow limiter and combined control valve for each chilled

    beam, enabling individual changes in water flow rates

    without the need for balancing.

    Additionally, in large systems, differential pressure

    valves in the pipework zones may be needed to

    ensure appropriate pressure conditions.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    28/4428

    Management of room conditions

    Shut-off valve

    Balancing valve

    Control and balancing valve

    Control valve with max flow limiter

    Pressure regulator valve

    Pressure control damper Duct balancing damper

    Adaptable air balancing and adjustment with constant duct

    pressure.

    Traditional balancing of ductwork.

    Adaptable control and maximum flow limiting valves. Traditional control and balancing valves.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    29/4429

    Management of room conditions

    Room control sequences

    Room thermal conditions typically are controlled by

    adjusting hot and chilled water flow rates in each

    chilled beam by means of two-way valves.

    Control can be based on on/off, pulse-width-modulated

    (PWM), proportional, or proportional integral control.

    Demand-based control is based on remotely set setpoints determined by, e.g., schedulers, and settings

    can be adjusted locally by users according to their

    demands or by occupancy mode as detected by

    occupancy sensors.

    In meeting and team rooms, traditional temperature

    control can be complemented with an additional

    sequence for increasing outdoor airflow rate (Halton

    Air Quality control). This function responds rapidly to

    varying ventilation requirements.

    Proper heating operation can be ensured by using a

    combination of room and supply air temperature

    control in order to optimize the supplied air

    temperature to avoid an excessive vertical room

    temperature gradient.

    Condensation prevention can be arranged in two

    stages:

    System flow water temperature control based on

    room air dew point calculation for critical locations. Locally in the room, using condensate detection to

    close the chilled water valve.

    Control sequence for heating and cooling.

    Control sequence for heating, air quality (HAQ), and cooling.

    Room control applications

    Room control can be realized on the basis of

    functional requirements and the desired flexibility level

    using:

    A self-powered standalone controller

    An electric standalone controller

    A traditional communicative controller

    A temperature sensor, typically located in the

    wall-mounted user panel

    The control valve and actuator types are selected to

    match the required water flow rates and control

    sequences. The power supply (24 / 230 VAC) for

    controller, actuators, and sensors is supplied on the

    basis of the units selected.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    30/4430

    Case study

    WP1

    WP2

    HVC 3 HVC 1

    10 %

    20 %

    WP2

    WP1

    3.12 Case study: occupant comfort using chilled beams

    The International Centre for Indoor Environment and Energy of the Technical University of Denmark (DTU) has carried out

    a study measuring occupant comfort in an office environment where cooling and ventilation were provided by a ABC

    chilled beam equipped with Halton Velocity Control (HVC).

    Case 1

    Chilled beams are installed perpendicularly to the external

    wall. Velocity conditions are presented with a cooling

    capacity of 16 Btuh/ft2in two different cases: Halton Velocity

    Control in positions 3 and 1. Room air velocities were lower

    when induction through beams was lower, even though the

    cooling capacity was the same. The primary airflow rate was

    the same in both cases, and compensating cooling capacity

    was provided by increasing the water flow rate.

    Case 2

    Human responses were studied with chilled beams installed

    parallel to the external wall and two persons occupying the

    room. The number of people sensing a draught was clearly

    (by about 60%) reduced during the maximum cooling

    capacity period with HVC in the throttle position (1). While

    the person near the window surface (WP2) felt slightly

    warmer (PMV increased from 0.4 to 0.7) when HVC was

    used, the acceptability increased slightly.

    Case 1. Air velocities (fpm) in the occupied zone with Halton Velocity

    Control in full position.

    Thermal conditions (temperature and velocity) in theoccupied zone were measured in this study, along

    with human responses, using both thermal manikins

    and living people. The following conclusions were

    drawn after analysis of the measurement results:

    High quality of general thermal comfort can be

    achieved.

    Halton Velocity Control decreases velocities and the

    potential risk of draught discomfort.

    Increased heat load and supply flow rate togetherincrease the risk of local discomfort.

    Airflow interaction is an important factor affecting

    thermal comfort.

    The layout of chilled beams and workplaces should

    be carefully considered.

    Thermal flows from warm or cold windows are

    important factors in air distribution and occupants

    local thermal comfort.

    Case 1. Air velocities (m/s) in the occupied zone with Halton Velocity

    Control on in throttle position.

    Case 2 : Percentage of people sensing a draught (22 Btuh/ft2).

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    31/4431

    Passive chilled beam system

    4.1. Passive chilled beam system

    Chilled beam system description

    Haltons chilled beam system is an air conditioning

    system for cooling applications where good indoor

    climate and individual space control are appreciated.

    The passive chilled beam system utilises the excellent

    heat transfer properties of water and provides a good

    indoor climate energy-efficiently.

    Operation of the system

    Chilled beam systems are designed to use the dry

    cooling principle, operating in conditions in which

    condensation is prevented by control applications.

    Ventilation

    Ventilation in passive chilled beam systems typically is

    arranged using mixing ventilation with ceiling or wall

    diffusers. Alternatively, floor diffusers can be used.

    In passive-service chilled beams, a diffuser can be

    integrated into the beam unit for air supply.

    Cooling

    Chilled water circulates through the heat exchanger of

    the passive chilled beam unit, resulting in relatively

    high cooling capacities.

    Passive beam operation is based on free convection in

    the heat exchanger. Passive chilled beam units with a

    higher proportion of radiation also exist.

    Heating

    Heating generally is realised with a separate heating

    system.

    A separate heating system e.g., perimeter heating

    typically is used in passive chilled beam

    installations.

    Window draughts due to radiation and downward

    convective air movement during cold seasons need

    to be eliminated.

    Schematic diagram of a chilled beam system office floor installation.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    32/4432

    4.2 Chilled beam system design

    A passive chilled beam system can be designed to fulfil requirements for sustainable, energy-efficient buildings that

    provide flexible use of space and a healthy and productive indoor climate. A passive chilled beam system can realise

    excellent indoor climate conditions in terms of thermal and acoustic properties in a wide range of installation

    scenarios.

    TYPICAL INPUT VALUES AND OPERATION RANGES

    Room temperature, summer 73 77 F

    Room temperature, winter 68 72 F

    Water inlet temperature, cooling 57 61 F

    Target water flow rate 0.4 1.6 gpm

    Sound level NC 30

    Cooling capacity / floor area 25 Btuh/ft2 38 Btuh/ft2 *

    Cooling capacity / effective unit length 250 Btuh/ft 400 Btuh/ft *

    Separately for ventilation

    Supply air temperature 61 66 F

    Outdoor air flow rate/ floor area,

    offices 0.33 0.55 cfm/ft2

    meeting rooms 0.33 0.9 cfm/ft2

    Note * It is reasonable to study the room air velocity

    conditions carefully

    Note ** It is reasonable to study the thermalconditions carefully

    Ventilation and air diffusion arrangement

    The supply airflow rate shall be high enough to

    remove internal humidity loads.

    Cooling using chilled beams

    Required cooling capacities should be no more than

    19 25 Btuh/ft2. With well-dimensioned integrated

    applications, capacities as great as 38 Btuh/ft2can

    be realised.

    Thermal properties of the external walls and window

    construction should be reasonable.

    Airtight windows with effective solar shading are

    used.

    The cooling capacity of passive chilled beams is

    typically 150 250 Btuh/ft to avoid draughts in the

    occupied zone, especially underneath the unit.

    Operation shall be designed with conditions in the

    occupied zone in all seasons (winter, summer, and

    intermediate season) taken into account.

    The flow water temperature (typically above 57F)

    must be sufficiently high to avoid condensation in all

    operation conditions. If necessary, the inlet water

    temperature may be adjusted to compensate for

    outdoor or indoor conditions. A condensation sensor

    should be located in each zone.

    Water flow rates and pressure drops in chilled

    beams should be in line with chilled water pipework

    design and pumping cost target levels.

    Passive chilled beams installed in a suspended

    ceiling always require sufficiently large openings in

    the ceiling for the induced room air path.

    Location of chilled beams shall respect the minimum

    distances from walls and ceiling presented in the

    section Passive chilled beam orientation and

    ventilation arrangements.

    Passive chilled beam system design

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    33/4433

    The appropriate model of passive chilled beam unit is selected

    by taking into account the following factors:

    Architectural design

    Preferred appearance

    Exposed installation or flush mounting in suspended ceiling

    Hidden installation above perforated/grid ceiling

    Adaptation to ceiling

    Positioning in consideration of light fittings Integration of light fittings

    Unit dimensions

    Room design grid dimensions

    Requirements for flexibility and eventual partition wall locations

    Supply air diffuser integration

    Exhaust valve integration

    Cooling capacity requirements

    A passive beam can be integrated into a suspended ceiling via a

    ceiling plenum, allowing closed return air circulation.

    Building services can be integrated into chilled beams, creating

    an elegant and uniform ceiling appearance. Multi-service passive

    beams are a cost-effective and interesting concept especially for

    renovation projects where there is a desire to maximise ceiling

    height or existing ceiling appearance should be largely

    preserved.

    Common technical services for integration are:

    Light fittings, controls, sensors, detectors, and cabling

    4.3. Passive chilled beam model selection

    Passive beams in ceiling void

    Customised customized service beam.

    Closed passive chilled beam integrated into

    suspended ceiling.

    Passive chilled beam in exposed installation.

    Passive chilled beam in ceiling-void-mounted

    installation.

    Passive chilled beam model selection

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    34/44

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    35/4435

    4.4. Passive chilled beam orientation and ventilation arrangements

    Passive chilled beams can be installed either perpendicularly or parallel to the perimeter wall. The units should not

    be positioned directly facing work spaces, to ensure comfortable velocity conditions. Minimum recommended

    installation distances from walls and between parallel chilled beams shall be respected, for proper cooling

    performance.

    Side wall installation & ceiling diffuser.

    Ceiling diffuser between chilled beams.

    Selection of passive chilled beam orientation Indoor climate conditions

    Capacity per chilled beam unit

    Residual velocities for the occupied zone

    Convective plume interaction with supply air jet

    Suitability for room module dimensions

    Suitability for the lighting fixture locations

    Flexibility for layout changes

    Minimum distance between parallel beams

    Minimum distance between chilled beam and wall/

    ceiling

    Perimeter installation & ceiling diffuser.

    Side wall installation & wall diffuser.

    Side wall installation & floor diffuser. Side wall installation & low-velocity unit.

    Passive chilled beam orientation and ventilation arrangements

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    36/4436

    Passive chilled beam location

    Chilled beam units shall be installed respecting

    minimum recommended distances from walls and

    ceiling in order to ensure effective convection and

    proper operating conditions:

    H1 = min. 0.25 x W when S > W

    H2 = min. 0.5 x W when S < W

    Minimum distance between chilled beam units of L, to

    ensure effective operation:

    L = min. 3 x W

    When a passive chilled beam is installed above a

    perforated or grid ceiling, the following minimum

    distances should be respected:

    H3 = min. 1 in

    The open area percentage (OAP) of the suspended

    ceiling shall be sufficiently high to ensure proper

    functioning of the chilled beam.

    The minimum percentage of open area for perforation

    is 25%. The minimum hole diameter is 1/8 in.

    Side panel extensions can be used to improve

    buoyancy effect and thus cooling capacity.

    Use HIT Design for calculation of cooling capacity,

    taking installation above the perforated ceiling with or

    without side panel extensions into account.

    Exhaust air unit location

    In cases where chilled beams are installed above a

    suspended ceiling, exhaust units should not be

    installed above the suspended ceiling.

    Otherwise, exhaust unit position is of minor

    importance in the installation.

    Minimum distances for passive chilled beam installation.

    Passive chilled beam installed above a perforated or grid ceiling.

    Passive chilled beam orientation and ventilation arrangements

    Hsk, Correction factor, in

    4 1.19

    6 1.28

    12 1.40

    16 1.45

    Side panel extension effect on cooling capacity.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    37/4437

    Operation range definition

    4.5. Operation range definition

    Chilled beam operation range is defined on the basis of representative rooms. The selected rooms are studied to

    determine cooling and heating loads. After specification of load patterns in the representative rooms, chilled beam

    operation parameters are set. The design target values can be verified via a full-scale mock-up or computational fluid

    dynamics (CFD) simulation.

    Typical input values and operation ranges (extreme target values in brackets)

    Room temperature for cooling 73 77 F

    Water inlet temperature for cooling 57 61 F

    Target water flow rate for cooling 0.32 1.6 gpm

    Cooling capacity per unit floor area 25 (38) Btuh/ft2

    Cooling capacity / effective beam length 250 (400) Btuh/ft

    Comfort / PMV -0.5 ... +0.5

    Draught rate (DR) < 15%

    Local mean room air velocity Cooling: 45 fpm

    Heating: 35 fpm

    Definition of design conditions and operation

    parameters

    Cooling capacity demand in spaces, in Btuh/ft2, and

    actual breakdown of loads

    Heating capacity demand in spaces, in Btuh/ft2, and

    actual breakdown of loads

    Ventilation arrangement

    Diffuser type, size, and number Ventilation rates in spaces as rate per floor area, in

    cfm/ft2

    Ventilation rate in spaces as rate per person, in cfm/

    person

    Model rooms and operational parameters

    Room temperature

    Supply air temperature

    Water inlet temperature

    Target duct pressure level

    Target water flow rate Maximum sound pressure level

    Verification of target design values with full-scale mock-up and CFD

    simulation.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    38/4438

    Pre-selection and selection

    Pre-selection

    With the help of quick-selection tables, pre-select the

    chilled beam using the following parameters for the

    desired design conditions:

    Indoor climate conditions

    Cooling capacity

    Minimum distance between parallel units

    4.6. Pre-selection and selection

    Make your design process more efficient. Haltons design tools for the pre-selection and selection phase include

    brochure data sheets with quick-selection charts and the Halton HIT Design software. Halton HIT Design enables

    product selection and performance simulation for the product(s) that addresses, e.g., air velocity, cooling and

    heating capacity, throw pattern, sound level, and location of the units.

    APA cooling capacity, in Btuh/ft of

    effective length

    Water flow rate:

    1.27 gpm

    Difference between room air and water mean temperatures,

    degF

    Coil height (in) Coil width (in) 11 13 14 15 16 17 18 20

    3 12.4 91 116 132 147 163 176 190 232

    3 18.3 143 182 211 234 253 279 301 335

    3 24.2 190 241 283 303 322 362 401 465

    4 12.4 108 135 155 170 186 203 217 253

    4 18.3 177 220 258 284 310 335 358 4184 24.2 225 280 330 364 395 426 457 532

    Pre-selection example

    Room dimensions 8 x 13 x 9

    Room area 104 ft2

    Room temperature 75 F

    Ventilation rate 42 cfm

    Supply air temperature 64F

    Required total cooling capacity 22 Btuh/ft2

    Cooling capacity 2700 Btuh

    Cooling by ventilation 491 Btuh

    Coil cooling capacity 1931 Btuh Presumed temperature difference DT = 14 degF

    Select APA-4-153--1 159 Btuh/ft

    Chilled beam APA cooling capacity, in watts per metre of effective length for water flow rate 1.27 gpm

    CPA passive chilled beam quick-selection

    Cooling capacity over unit length (W/m) presented for

    water flow rate qmw

    = 1.27 gpm.

    Estimate the temperature rise in the chilled beam

    (typically 2 5 degF), and calculate the temperature

    difference between room air and water mean

    temperature.

    Temperature difference Tr- (T

    w1+ T

    w2)/2, degF

    Where

    Tr Room temperature, F

    Tw1

    Water flow temperature, F

    Tw2

    Water return temperature, F

    Check the temperature difference with the HIT Design

    software.

    Water flow rate

    qmw, gpm 0.024 0.32 0.40 0.48 0.55 0.63 0.71 0.79 0.87 0.95 1.27

    0.79 0.83 0.86 0.88 0.91 0.92 0.94 0.96 0.97 0.98 1

    Correction factor of cooling capacities for water flow rates deviating from 1.27 gpm flow rate.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    39/4439

    Pre-selection and selection

    1. Design data in cooling

    Specify the temperature difference between the

    inlet and outlet water of the beam or, optionally,

    insert the inlet water temperature and target water

    flow rate.

    Calculate the coil capacity using HIT Design, and

    compare the coil capacity against the requirement.

    You can also insert the supply air flow rate and

    temperature for total cooling capacity calculation.

    2. Chilled beam location and velocity control

    adjustment

    The location and number of chilled beams are

    specified (also, asymmetric positioning is possible).

    You can also add a person for evaluating the air

    velocity locally

    directly below the chilled beam

    in the vicinity of the beam at floor level

    further from the chilled beam at floor level

    3. Space results / unit performance

    Check operation parameters against system

    operation conditions to verify that the operation

    parameters respond to those of the system, as in

    the cooling case.

    Selection

    Calculate the cooling and heating capacity of the selected chilled beam units by studying chilled beam performance

    in selected model rooms with desired operation parameters, using Halton HIT Design.

    Design Data window in Halton HIT Design selection.

    Room dimensions, the occupied zone, and design criteria are

    specified in the Room window in Halton HIT Design.

    1 2

    3

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    40/4440

    Indoor climate conditions

    If indoor climate conditions targets are not met,

    then change

    the beam length or number of beams and/or

    beam properties or even

    beam type and

    diffuser type and/or location

    Study optional room modules

    Water flow rate (keep at the same level as before)

    Operation at optional room cooling load levels / room

    usage

    4.7. Design of indoor climate conditions

    Simultaneously with the performance values, verify also that the predicted room conditions are acceptable,

    particularly the air velocities entering the occupied zone created by the convective plume of the chilled beam. Take

    into consideration the interaction of the passive beam and the supply air distribution as well.

    Operation in optional room module configurations

    Study the velocities of the convective plume

    entering the occupied zones and room air

    velocities

    Plume velocities entering the occupied zones (in the

    design case)

    Room air velocities in the occupied zone

    Temperature difference between the plume and

    ambient room air

    Check the interaction of the falling convective

    plume of a chilled beam and supply air throw

    pattern

    Simultaneously with the performance values, verify

    that the predicted room conditions are acceptable,

    providing efficient air distribution.

    Supply jet adequately reaching the occupied zone

    level Supply air that is not directed directly to chilled

    beam air circulation

    Halton HIT Design Performance view (2D).

    Stationary person below and to the side of a chilled beam.

    Interaction of convective plumes of a chilled beam

    and a stationary person

    Note that the rising convective plume of a stationary

    Stationary person located directly below a chilled beam.

    person affects the flow pattern of a chilled beam and

    that the prevailing velocities above the person are

    lower than in undisturbed flow created by a chilled

    beam.

    2.5 m

    vop

    CPA-100-3900-315-1Cooling 2007.05

    Room:

    Room size: 2.5 x4.0 x2.8 m

    O ccu pi ed z on e: h =1 .8 m / dw =0 .5 m

    Room air: 24.0 C / 50 %

    Heat gain: 700 W

    P erf or at ed ce il in g: -

    I ns ta ll at io n he ig ht : 2 .7 0 m

    Inlet water temperature: 15.0 C

    Outlet watertemperature: 16.7 C

    Wa te r fl ow r at e: 0 .0 80 kg /s

    Coil capacity: 575 W

    155 W/m

    W at er p r es su re d r op : 5 . 6 k P a

    S up pl ya ir fl ow r at e 2 0 l /s

    2.0 l/(sm2)

    Supply ai r t emperature: 18.0 C

    J et outl et t emperature: 21.4 C

    P ri ma ry a ir c a pa ci ty : 1 4 3 W

    To ta l pr es su re d ro p: -

    Totalsoundpressurelevel: -

    T ot al c o ol in g c ap ac it y: 7 1 8 W

    72 W/m2

    Dewpoint t emperature: 12.9C

    Velocity control: -

    Velocity point

    v

    T

    vop

    ~0.15m/s

    vlim= 0.20m/s

    2.5 m

    v3

    vop

    CPA-100-3900-315-1Cooling 2007.05

    Room:

    Room size: 2.5 x4.0 x2.8 m

    O ccu pi ed z on e: h =1 .8 m / dw =0 .5 m

    Room air: 24.0 C / 50 %

    Heat gain: 700 W

    P erf or at ed ce il in g: -

    I ns ta ll at io n he ig ht : 2 .7 0 m

    Inlet water temperature: 15.0 C

    Outlet watertemperature: 16.7 C

    Wa te r fl ow r at e: 0 .0 80 kg /s

    Coil capacity: 575 W

    155 W/m

    W at er p r es su re d r op : 5 . 6 k P a

    S up pl ya ir fl ow r at e 2 0 l /s

    2.0 l/(sm2)

    Supply ai r t emperature: 18.0 C

    J et outl et t emperature: 21.4 C

    P ri ma ry a ir c a pa ci ty : 1 4 3 W

    To ta l pr es su re d ro p: -

    Totalsoundpressurelevel: -

    T ot al c o ol in g c ap ac it y: 7 1 8 W

    72 W/m2

    Dewpoint t emperature: 12.9C

    Velocity control: -

    Velocity point

    v

    T

    v3

    ~0.25m/s

    -2.6C

    vop

    ~0.15m/s

    vlim= 0.20m/s

    2.5 m

    v3

    vop

    CPA-100-3900-315-1Cooling 2007.05

    Room:

    Room size: 2.5 x4.0 x2.8 m

    O cc up ie d zo ne : h =1 .8 m / dw= 0.5 m

    Room air: 24.0 C / 50 %

    Heat gain: 700 W

    P er fo ra te d ce il in g: -

    I ns ta ll at io n he ig ht : 2 .7 0 m

    Inlet water temperature: 15.0 C

    Outlet watertemperature: 16.7 C

    Wa te r fl ow ra te : 0 .0 80 k g/ s

    Coil capacity: 575 W

    155 W/m

    W at er p r es su re d r op : 5 .6 k Pa

    S up pl y a ir f lo w ra te 2 0 l /s

    2.0 l/(sm2)

    Supply ai r t emperature: 18.0 C

    J et outl et t emperature: 21.4 C

    P ri ma ry a ir c a pa ci ty : 1 4 3 W

    To ta l pr es su re d ro p: -

    Totalsoundpressurelevel: -

    T ot al c o ol in g c ap ac it y: 7 1 8 W

    72 W/m2

    Dewpoint t emperature: 12.9C

    Velocity con trol: -

    Velocity point

    v

    T

    v3

    ~0.25m/s

    -2.6C

    vop

    ~0.05m/s

    vlim= 0.20m/s

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    41/4441

    Adjustment and balancing methods

    Proper operation conditions for chilled beams are

    ensured by correct water flow rates.

    Water flow rates can be adjusted via zone balancing

    valves and the balancing valve of each chilled beam.

    Water flow rates can also be controlled using an

    automatic flow limiter and combined control valve foreach chilled beam, enabling individual changes in

    water flow rates without the need for balancing.

    Additionally, in large systems, differential pressure

    valves in the pipework zones may be needed to

    ensure proper pressure conditions.

    4.8. Management of room conditions

    Water flow measurements can be implemented by measuring pressure drop over a balancing valve equipped with

    measurement taps.

    Room control

    Room thermal conditions typically are controlled by

    adjusting hot and chilled water flow rates in each

    chilled beam by means of two-way valves.

    Control can be based on on/off, pulse-width-modulated

    (PWM), proportional, or proportional integral control.

    Demand-based control is based on remotely setsetpoints determined by, e.g., schedulers, and settings

    can be adjusted locally by users according to their

    demands or by occupancy mode as detected by

    occupancy sensors.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    42/4442

    Customised service beams

    5. Customized service beams

    Traditional chilled beam installations include ventilation, cooling, and heating next to the equipment for other ceiling-

    based services. The customised service beam concept proposes an all-in-one solution for all ceiling-mounted

    accessories. The service beam concept is suitable for both suspended-ceiling and exposed installations. The

    product's appearance can be tailored to suit the interior.

    The concept offers benefits from the time of installation through a whole lifetime of use:

    An improved indoor climate is a result of excellent

    temperature conditions and silent, draught-free

    operation. Good conditions promote productivity and

    the health of users.

    Flexibility for different layouts, from open-plan to

    partitioned office space, is achieved efficiently.

    Assembly at the factory increases installation speed

    and quality while reducing costs. Rapid connections

    further reduce the commissioning time on-site.

    Having a single source of responsibility lowers risk

    and reduces the need for co-ordination.

    Luminaires can be integrated into chilled beams or

    installed as separate light fittings, regardless of chilled

    beam orientation. Chilled beams are available with

    direct and/or indirect luminaires.

    With fewer separate pieces of equipment fixed to

    the ceiling and walls, interior design better matches

    the architectural vision.

    The investment cost is more competitive than that of

    traditional systems and suspended-ceiling

    installations with separate building services.

    Competitive running costs are achieved with low

    maintenance demands and energy consumption.

    Room height is increased, as no suspended ceiling

    is needed.

    Luminaires

    Direct and indirect luminaires integrated into the

    bottom plate of the beam provide good contrast and

    visual comfort. Direct and indirect lighting can be

    implemented with separate light fittings or with one

    fitting for both. All lights can be equipped with built-in

    on/off or dimmable control and different connection

    options.

    Also, emergency lights can be integrated into the

    chilled beams.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    43/4443

    Customised service beams

    Detectors

    Occupancy sensors allowing for demand-based

    ventilation and other occupancy-related features, as

    well as daylight sensors and smoke detectors, can be

    integrated into the chilled beam.

    Controls

    Chilled beam delivery can include integrated two-way

    control valves with actuators and condensation

    sensors. When necessary, the beam structure can also

    include a room controller and the associated

    temperature sensor

    Space for sprinklers

    National building codes typically require sprinkler

    installations to be carried out on the site.

    However, the sprinkler pipes can be attached above

    the beams and the pipe connections for individual

    sprinkler nozzles, to an accessory space in the middle

    of the beam.

    Public address loudspeakers

    Public announcements or background music can be

    provided through built-in pre-wired speakers.

    Cable shelves

    Cables for various services can be laid on cable

    shelves, which can be integrated in the chilled beam

    design in order to complete the elegant installation.

  • 8/13/2019 Halton HVAC Handbook Chilled Bean Design Guide

    44/44

    www.haltoncompany.com