Page 1: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

HBD HV Controland Monitoring System

STATUS UPDATE

Manuel ProisslHBD Meeting 09/30/2008

Page 2: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

OUTLINE

System Basics - Recall Software and Hardware components HV Control Structure

HBD HV Control – Introduction Getting Started Features

Relay Board and Trip Detector Coming Up

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

HBD HV Control & Monitoring System Manuel Proissl Page 1 of 13

Page 3: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

HV SYSTEM BASICS

HV Control is based on CS architecture (before: TS) System communicates ONLY with own HBD Server on va022 HBD server (/hbd/startHBD) sends CMDs and receives data from hvclient

robust and secure!

Two Modes: SA1 and HBD Expert Two User / Access Levels: STANDARD and SUPERUSER 3-Layer System has been used:

40 channels to serve (20 GEMs, 20 Meshs) Hardware: L1458HP mainframe, L1471Ns, Voltage Divider, Relay Boards HV Control is INDEPENDENT of Relay Board Installation!

Java GUI

Perl / SSH Client

C

via shell

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

HBD HV Control & Monitoring System Manuel Proissl Page 2 of 13

Page 4: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

HV CONTROL STRUCTURE

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

ROOT Interface

Loop over channels

Check / Verify Stat. [every 5sec]

Respond to users

HV Server (va022) – Rackroom

HV

Clie

ntH

V Cl

ient

LeCroy 1458HPMainframe

LC 1

471

LC 1

471

40 modules. . . . . . . . . to serves . . . . . . . . .

16………

Voltage Divider

HV

Clie

nt

hvdb

HBD Server

8Trip Det.

Trip Det.

TS

PHENIX IR

Switch

8

behind PHENIX firewalle.g. trip settings

IBM eServer

HBD HV Control & Monitoring System Manuel Proissl Page 3 of 13

Page 5: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

With HBD installation on December 1st, 2008 – the installer will become available for download from va022> /hbd/hvcontrol/hbdcontrol.exe Easy access through HBD website

Follow installation steps…. BNL Life No. and Serial required! After Reboot and Click on Desktop Icon:

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

Splash

Initializing interface… Checking network connection and speed First-time user??

System Activation Login: SA1 or Expert

YES NO

HBD HV Control & Monitoring System Manuel Proissl Page 4 of 13

Page 6: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

HV System Activation is required for first-time users! You need… Locate Public Key on local disk Corresponding username

– same as to RSSH machines

16-digit activation code Unique code defining privileges Provided to every HBD group member

and one for shift crew (pre-inst.)

By clicking “Verify” - the system checks

in hvdb the code’s existence and

displays BNL ID and Name for

user verification of correct code pick-up By clicking “Activate System” – loads

HV Control privileges based on code

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

ActivationLogin to SA1 or Expert Mode

Window opens… Locate your public key on disk.

Window opens… Locate your public key on disk. BNL

UsernameBNL Username

Indicating if code is correct, wrong or unknown.

Indicating if code is correct, wrong or unknown.

HBD HV Control & Monitoring System Manuel Proissl Page 5 of 13

Page 7: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

Activation

Window opens… Locate your public key on disk.

Window opens… Locate your public key on disk. BNL

UsernameBNL Username

Indicating if code is correct, wrong or unknown.

Indicating if code is correct, wrong or unknown.

THE PROTECTION SYSTEM– General Introduction –

Running Shift Mode means only ONE client at a time can login to HV Control, which is the specially authorized system in the counting room!

Activation code indicates user level:STANDARD or SUPERUSER

System in counting room has superuser privileges, meaning nobody else can login;

however, HBD experts can take over control at any time (notification for SA1..)

System NOT responding, superuser ID set free automatically

Use of Shift Mode outside of BNL prohibited by firewall

Expert Mode: no network restrictions!

HBD HV Control & Monitoring System Manuel Proissl Page 6 of 13

Page 8: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

If your user access level, based on code, restricts you from running Expert Mode, a error window pops up – denying access!

BNL ID and password only have to be set once by simply saving the settings

No access restrictions to Shift Mode

Troubleshooting, Q/A’s under “Help”

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

Login

Loading HV Control

HBD HV Control & Monitoring System Manuel Proissl Page 7 of 13

Page 9: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

System Overview provides a quick

overview of the detector status Live-updated every 5sec (incl. parameters)

HV Control Panel represents the main

control for the SA1 – easy!

STANDBYSelect enabled modules + sethv to particular standby voltages from

HBD config file (saved locally from hvdb and updated every 5sec).

OPERATIONALSelect modules on standby + same procedure as for standby to op.

RECOVERYSelect tripped modules + disable + sethv (…) + enable

DISABLE / ENABLE>> Opens HBD Module Control window…

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

HV Control

Age: 0-5secAge: 0-5sec

OK + Trip + Call ExpertOK + Trip + Call Expert

HV ON/OFF + FB/RB + Report + Shell + Save + Switch to Detail…

HV ON/OFF + FB/RB + Report + Shell + Save + Switch to Detail…

HBD HV Control & Monitoring System Manuel Proissl Page 8 of 13

Page 10: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

Toggle Button: Select and Deselect for Action.

Toggle Button: Select and Deselect for Action.

Modules in… GREEN: enabled, no trip RED: enabled, tripped (not clickable)

BLUE: disabled (not displayed)

By clicking on green module a blue border will indicate its selection; when done, click

“DISABLE MODULES” Blue border(s) blinking till changing to BLUE If clicking “ENABLE MODULES” – Error! (…)

By clicking on blue module a green border will indicate its selection; when done, click

“ENABLE MODULES” Green border(s) blinking till changing to GREEN If clicking “DISABLE MODULES” – Error! (…)

HBD HV Control & Monitoring System Manuel Proissl Page 9 of 13

Page 11: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – GETTING STARTED

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

Filter Parameter Listing.Filter Parameter Listing.

Parameter table… when running HV Control only.Parameter table… when running HV Control only.

HBD HV Control & Monitoring System Manuel Proissl Page 10 of 13

Page 12: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

USER INTRO – ADD. FEATURES

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

For a complete detailed introduction toHBD HV Control V2.0, please refer todocumentation or online tutorials.

HBD HV Control & Monitoring System Manuel Proissl Page 11 of 13

Page 13: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

RELAY BOARD AND TRIP DETECTOR

System has been used so far and hasn’t shown any issues, until now…. Indefinable problems occurred:

Having just the connection cable to trip detector hooked up, a “virtual trip” can be seen, meaning

the LED on the board indicates trip, however, after measuring it shows still same op. voltage. Having the relay board and L1471N SHVs and connection cable hooked up (operating case), we

see one relay trip causing multiple random LeCroy channel trips.

Even switching from the non-isolated RS485 to the isolated port didn’t help! Powering the board independently from mainframe didn’t help!

Possible explanation: airborne NOISE sparks Shielding Test: taking the relay board out of the mainframe, shielding the LeCroy

module all around seemed to solve the issue – problem almost disappeared

Next step: placing all 6 L1471Ns on right, relay boards on left side of mainframe and strong isolation in between… if this brings us back on track, we can use the relay board for Run9.

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008

HBD HV Control & Monitoring System Manuel Proissl Page 12 of 13

Page 14: HBD HV Control and Monitoring System STATUS UPDATE Manuel Proissl HBD Meeting 09/30/2008

COMING UP

Relay Board research will continue, but is independent from HV Control development!

Real-time simulation of all 40 channels (GEM and Mesh)

Major server software work necessary – making parameter settings via software possible and secure (file system not exposed!) Additional live-login to hvconfig without opening another tunnel Getting va022 ready for Run9 – auto-starts, hvclient, etc. (with Martin)

Switching from table to database (to design) for parameter setting

Online documentation and Introduction Tutorials (HBD website)

Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008