OUTLINE
System Basics - Recall Software and Hardware components HV Control Structure
HBD HV Control – Introduction Getting Started Features
Relay Board and Trip Detector Coming Up
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
HBD HV Control & Monitoring System Manuel Proissl Page 1 of 13
HV SYSTEM BASICS
HV Control is based on CS architecture (before: TS) System communicates ONLY with own HBD Server on va022 HBD server (/hbd/startHBD) sends CMDs and receives data from hvclient
robust and secure!
Two Modes: SA1 and HBD Expert Two User / Access Levels: STANDARD and SUPERUSER 3-Layer System has been used:
40 channels to serve (20 GEMs, 20 Meshs) Hardware: L1458HP mainframe, L1471Ns, Voltage Divider, Relay Boards HV Control is INDEPENDENT of Relay Board Installation!
Java GUI
Perl / SSH Client
C
via shell
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
HBD HV Control & Monitoring System Manuel Proissl Page 2 of 13
HV CONTROL STRUCTURE
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
ROOT Interface
Loop over channels
Check / Verify Stat. [every 5sec]
Respond to users
HV Server (va022) – Rackroom
HV
Clie
ntH
V Cl
ient
LeCroy 1458HPMainframe
LC 1
471
LC 1
471
40 modules. . . . . . . . . to serves . . . . . . . . .
16………
Voltage Divider
HV
Clie
nt
hvdb
HBD Server
8Trip Det.
Trip Det.
TS
PHENIX IR
Switch
8
behind PHENIX firewalle.g. trip settings
IBM eServer
HBD HV Control & Monitoring System Manuel Proissl Page 3 of 13
USER INTRO – GETTING STARTED
With HBD installation on December 1st, 2008 – the installer will become available for download from va022> /hbd/hvcontrol/hbdcontrol.exe Easy access through HBD website
Follow installation steps…. BNL Life No. and Serial required! After Reboot and Click on Desktop Icon:
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
Splash
Initializing interface… Checking network connection and speed First-time user??
System Activation Login: SA1 or Expert
YES NO
HBD HV Control & Monitoring System Manuel Proissl Page 4 of 13
USER INTRO – GETTING STARTED
HV System Activation is required for first-time users! You need… Locate Public Key on local disk Corresponding username
– same as to RSSH machines
16-digit activation code Unique code defining privileges Provided to every HBD group member
and one for shift crew (pre-inst.)
By clicking “Verify” - the system checks
in hvdb the code’s existence and
displays BNL ID and Name for
user verification of correct code pick-up By clicking “Activate System” – loads
HV Control privileges based on code
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
ActivationLogin to SA1 or Expert Mode
Window opens… Locate your public key on disk.
Window opens… Locate your public key on disk. BNL
UsernameBNL Username
Indicating if code is correct, wrong or unknown.
Indicating if code is correct, wrong or unknown.
HBD HV Control & Monitoring System Manuel Proissl Page 5 of 13
USER INTRO – GETTING STARTED
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
Activation
Window opens… Locate your public key on disk.
Window opens… Locate your public key on disk. BNL
UsernameBNL Username
Indicating if code is correct, wrong or unknown.
Indicating if code is correct, wrong or unknown.
THE PROTECTION SYSTEM– General Introduction –
Running Shift Mode means only ONE client at a time can login to HV Control, which is the specially authorized system in the counting room!
Activation code indicates user level:STANDARD or SUPERUSER
System in counting room has superuser privileges, meaning nobody else can login;
however, HBD experts can take over control at any time (notification for SA1..)
System NOT responding, superuser ID set free automatically
Use of Shift Mode outside of BNL prohibited by firewall
Expert Mode: no network restrictions!
HBD HV Control & Monitoring System Manuel Proissl Page 6 of 13
USER INTRO – GETTING STARTED
If your user access level, based on code, restricts you from running Expert Mode, a error window pops up – denying access!
BNL ID and password only have to be set once by simply saving the settings
No access restrictions to Shift Mode
Troubleshooting, Q/A’s under “Help”
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
Login
Loading HV Control
HBD HV Control & Monitoring System Manuel Proissl Page 7 of 13
USER INTRO – GETTING STARTED
System Overview provides a quick
overview of the detector status Live-updated every 5sec (incl. parameters)
HV Control Panel represents the main
control for the SA1 – easy!
STANDBYSelect enabled modules + sethv to particular standby voltages from
HBD config file (saved locally from hvdb and updated every 5sec).
OPERATIONALSelect modules on standby + same procedure as for standby to op.
RECOVERYSelect tripped modules + disable + sethv (…) + enable
DISABLE / ENABLE>> Opens HBD Module Control window…
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
HV Control
Age: 0-5secAge: 0-5sec
OK + Trip + Call ExpertOK + Trip + Call Expert
HV ON/OFF + FB/RB + Report + Shell + Save + Switch to Detail…
HV ON/OFF + FB/RB + Report + Shell + Save + Switch to Detail…
HBD HV Control & Monitoring System Manuel Proissl Page 8 of 13
USER INTRO – GETTING STARTED
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
Toggle Button: Select and Deselect for Action.
Toggle Button: Select and Deselect for Action.
Modules in… GREEN: enabled, no trip RED: enabled, tripped (not clickable)
BLUE: disabled (not displayed)
By clicking on green module a blue border will indicate its selection; when done, click
“DISABLE MODULES” Blue border(s) blinking till changing to BLUE If clicking “ENABLE MODULES” – Error! (…)
By clicking on blue module a green border will indicate its selection; when done, click
“ENABLE MODULES” Green border(s) blinking till changing to GREEN If clicking “DISABLE MODULES” – Error! (…)
HBD HV Control & Monitoring System Manuel Proissl Page 9 of 13
USER INTRO – GETTING STARTED
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
Filter Parameter Listing.Filter Parameter Listing.
Parameter table… when running HV Control only.Parameter table… when running HV Control only.
HBD HV Control & Monitoring System Manuel Proissl Page 10 of 13
USER INTRO – ADD. FEATURES
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
For a complete detailed introduction toHBD HV Control V2.0, please refer todocumentation or online tutorials.
HBD HV Control & Monitoring System Manuel Proissl Page 11 of 13
RELAY BOARD AND TRIP DETECTOR
System has been used so far and hasn’t shown any issues, until now…. Indefinable problems occurred:
Having just the connection cable to trip detector hooked up, a “virtual trip” can be seen, meaning
the LED on the board indicates trip, however, after measuring it shows still same op. voltage. Having the relay board and L1471N SHVs and connection cable hooked up (operating case), we
see one relay trip causing multiple random LeCroy channel trips.
Even switching from the non-isolated RS485 to the isolated port didn’t help! Powering the board independently from mainframe didn’t help!
Possible explanation: airborne NOISE sparks Shielding Test: taking the relay board out of the mainframe, shielding the LeCroy
module all around seemed to solve the issue – problem almost disappeared
Next step: placing all 6 L1471Ns on right, relay boards on left side of mainframe and strong isolation in between… if this brings us back on track, we can use the relay board for Run9.
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
HBD HV Control & Monitoring System Manuel Proissl Page 12 of 13
COMING UP
Relay Board research will continue, but is independent from HV Control development!
Real-time simulation of all 40 channels (GEM and Mesh)
Major server software work necessary – making parameter settings via software possible and secure (file system not exposed!) Additional live-login to hvconfig without opening another tunnel Getting va022 ready for Run9 – auto-starts, hvclient, etc. (with Martin)
Switching from table to database (to design) for parameter setting
Online documentation and Introduction Tutorials (HBD website)
Upgrades For Run9 | PHENIX, BNL HBD HV Control System HBD Meeting :: September 30 th, 2008
HBD HV Control & Monitoring System Manuel Proissl Page 13 of 13