New Product Release! Multi Split Air Conditioner FUJITSU GENERAL AIR CONDITIONING (UK) 2 Rooms Multi AOYG14KBTA2 AOYG18KBTA2 Space-saving installation Flexible installation Wide range of indoor units with various models High energy saving DC technology is used for compressor, indoor / outdoor fan motor and inverter controlling. Multiple indoor units can be connected to 1 outdoor unit, and long piping connection is also possible. Compared with single type, the outdoor unit can be installed in various places to for a space-saving installation solution. Up to max. piping length of 30m max. height difference of 15m can be supported. Multi type can be installed in large-size residence or buildings with multiple floors. 4 types 16 models are lined up in the capacity range from 2.0 kW to 4.0 kW class. Wide range of needs can be met from rooms of private homes to large shops and hotels. AOYG14KBTA2 AOYG18KBTA2 Highly Efficient DC Fan Motor Outdoor Unit DC Inverter Control Large Highly Efficient Heat Exchanger DC Twin Rotary Compressor SEER 8.7 (14 model) SCOP 4.7 A+++ Rank Cooling A++ Heating Models equipped with the New R32 Refrigerant Wall mounted type with sophisticated design Middle and small capacity models are available. This makes it easier to install at small spaces. Compact Cassette Mini Duct Slim Duct Simple setting Outdoor unit must have two Total Piping Length: 30 m Max. Height: 15 m Max. Height Total Piping Length Max. Piping Length (Each Unit): 20 m Max. Piping Length (Each Unit)

Upload: others

Post on 01-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: High energy saving - FUJITSU GENERAL

New Product Release ! Multi Split Air Conditioner

FUJITSU GENERAL AIR CONDITIONING (UK)

2 Rooms MultiAOYG14KBTA2AOYG18KBTA2

Space-saving installation Flexible installation

Wide range of indoor units with various models

High energy savingDC technology is used for compressor, indoor / outdoor fan motor and inverter controlling.

Multiple indoor units can be connected to 1 outdoor unit, and long piping connection is also possible. Compared with single type, the outdoor unit can be installed in various places to for a space-saving installation solution.

Up to max. piping length of 30m max. height difference of 15m can be supported. Multi type can be installed in large-size residence or buildings with multiple floors.

4 types 16 models are lined up in the capacity range from 2.0 kW to 4.0 kW class. Wide range of needs can be met from rooms of private homes to large shops and hotels.

AOYG14KBTA2 AOYG18KBTA2

Highly Efficient DC Fan Motor

Outdoor Unit

DC InverterControl

Large Highly Efficient Heat Exchanger

DC Twin RotaryCompressor

SEER

8.7(14 model)

SCOP

4.7

A+++

RankCooling

A++Heating

Models equipped with the New R32 Refrigerant

Wall mounted type withsophisticated design

Middle and small capacity models are available. This makes it easier to install at small spaces.

Compact Cassette Mini Duct Slim Duct

Simple settingOutdoor unit must have two

Total Piping Length:

30 m

Max. Height:

15 m

Max. H

eight

Total Piping Length

Max. Piping Length (Each Unit):

20 m

Max. Piping Length

(Each Unit)

Page 2: High energy saving - FUJITSU GENERAL

•Specifications and design are subject to change without notice for further improvement.•Actual products’ colors may be different from the colors shown in this printed material.

Distributed by :

FUJITSU GENERAL AIR CONDITIONING (UK) LTDUnit 150 Centennial Park, Centennial Avenue, Elstree, Herts. WD6 3SG

www.fujitsu-general.com/ukTel: +44 (0)208 731 3450 Fax: +44 (0)208 731 3451

Copyright© 2018 Fujitsu General Limited. All rights reserved. 3EFNP28-1812E

Specifications

AOYG18KBTA2

Fujitsu General (Thailand) Co., Ltd.

ISO 9001Certified number: 01 100 075229

ISO 14001Certified number: 01 104 9245

Model: AOYG14KBTA2 / AOYG18KBTA2

DimensionsAOYG14KBTA2 AOYG18KBTA2 (Unit : mm)

580 10933

0

353

Pitc

h of

bol

ts

for i

nsta

llatio

nPitch of bolts for installation

Top view

4-M10 hole

Side viewSide view Front view

799 68 29016

33 30

19

542

20

Airflow

Bottom view Side view (Valve part)

37

399Drain port Ø42

114

5710

4.4

150.119.7

Side viewSide view Front view

Bottom view Side view (Valve part)

Top view

580

79919 68 16 290

33 30

109

353

632

20

330

Pitc

h of

bol

ts

for i

nsta

llatio

n

Pitch of bolts for installation

4-M10 hole

Airflow

Drain port Ø4237

114

5710

4.4

399 150.119.7

580 109

330

353

Pitc

h of

bol

ts

for i

nsta

llatio

n

Pitch of bolts for installation

Top view

4-M10 hole

Side viewSide view Front view

799 68 29016

33 30

19

542

20

Airflow

Bottom view Side view (Valve part)

37

399Drain port Ø42

114

5710

4.4

150.119.7

Side viewSide view Front view

Bottom view Side view (Valve part)

Top view

580

79919 68 16 290

33 30

109

353

632

20

330

Pitc

h of

bol

ts

for i

nsta

llatio

n

Pitch of bolts for installation

4-M10 hole

Airflow

Drain port Ø42

37

114

5710

4.4

399 150.119.7

AOYG14KBTA2

Model No. AOYG14KBTA2 AOYG18KBTA2

Power Source Single-phase, ~230V, 50Hz

Rated Capacity(min-max)

CoolingkW

4.0 (1.4-4.6) 5.0 (1.7-5.8)

Heating 4.4 (1.1-5.5) 5.6 (1.8-7.0)

EER CoolingW/W

4.12 4.03

COP Heating 4.63 4.59

Sound Pressure Level(High)

Cooling

dB(A)

47 47

Heating 49 50

Sound Power Level(High)

Cooling 60 60

Heating 62 62

Airflow Rate Cooling/Heating m3/h 1,670/1,670 1,960/2,020

Net Dimensions H × W × D mm 542×799×290 632×799×290

Weight kg(lbs) 33 (73) 37 (82)

Connection Pipe DiameterGas

Inch3/8 × 2 3/8 × 2

Liquid 1/4 ×2 1/4 ×2

Max. Pipe Length Total / Each

m

30 / 20 30 / 20

Max. Height DifferenceBetween Outdoor Unitand Each Indoor Units. 15 15

Between Indoor Units. 10 10

Operation RangeCooling

°CDB-10 to 46 -10 to 46

Heating -15 to 24 -15 to 24

RefrigerantType (Global Warming Potential) R32 (675) R32 (675)

Charge kg(CO2eq-T) 0.9 (0.574) 1.02 (0.689)

Note: Specifications are based on the following conditions.Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.Heating : Indoor temperature of 20°CDB / 15°CWB, and outdoor temperature of 7°CDB / 6°CWB.