Ride through systems Diesel UPS systems
www.hitec-ups.com
Telecommunication IndustryDatacenter Flevoland
Ride through systems Diesel UPS systems
www.hitec-ups.com
Contents
Key partners involved
Project design brief
Site lay-out
Single line
Project details
Project realization
End situation
Telecommunication industry - track record
-
Key partners involved
Project design brief
Fit to KPN data center philosophy
Data centre with modular build up
Phase 1: 2 x 2.500 sqm data floor, 2 x 2.500 sqm space
Phase 2: Add 2 x 2.500 sqm space to data floor
Phase 3: Expandable extra 2 x 5.000 sqm for future need
1.500 W/sqm, expandable to 2.000 w/sqm
N + 2 configuration
System to support 48 hours full load, emergency
operation
3 floor building, 1st floor no data floor (risk of flooding)
Noise level 35 dbA (at building front)
-
Site lay-out
Building design
-
UPS Single line
Project details
Units: 12 x 2.000 kVA (400 V, 50Hz)
MTU diesel engines
Hitec Power Protection Induction Couplings
Marelli LV alternators
Design: N+2
Isolated Redundant
Low Voltage
Step down transformers in building
Year of installation: 2008
-
Turn-key project
Project planning & management
Project engineering (concurrent)
Auxiliary equipment
Water cooling diesel engines including radiators
Fuel systems including daily fuel tank (2000 l p/unit)
Exhaust system including silencer
UPS room ventilation
Progress meetings
Documentation
Installation & commissioning
Service & support
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
Project realization
Project realization
-
End situation
End situation
-
End situation
End situation
-
End situation
End situation
In use since November 2008
-
Telecommunication industry -
track record
Hitec was worldwide the first to deliver a No-Break
system to the Royal Dutch Telecom company (now
KPN) in 1956.
Telecommunication industry today is more and more
shifting to data center applications. With that our
global installed base in industry is more than 185 units
supplying more than 265.000 kVA of UPS power.
Examples Units kVA
KPN 65 92.000
Verizon 14 21.000
British Telecom 3 6.000
Telecom Italia 4 6.800
De Teleinmobilien 3 4.800
Hanaro Telecom 15 15.000
MTN 26 42.900
Ride through systems Diesel UPS systems
www.hitec-ups.com
Discover the power of our systems
Ride through systems Diesel UPS systems
www.hitec-ups.com