hitec power protection - injazat data center - tier iv solution

Upload: sonhuegli

Post on 03-Apr-2018

218 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    1/16

    Ride through systems Diesel UPS systems

    www.hitec-ups.com

    Injazat Data CentreAbu Dhabi

    Ride through systems Diesel UPS systems

    www.hitec-ups.com

    Injazat Data Centre

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    2/16

    Injazat Data Centre

    Injazat Data Centre Co-hosting Data Centre

    Provision of a managed, secure and environmentally controlled 2000m

    Data Hall for hosting mission critical servers and related IT equipment

    Timescales

    Commenced May 2007

    Construction Completion May 2008

    Operational December 2008

    Operating Environment Arid Desert, Remote Location 46 Degree Ambient

    Controlled Temperature

    Controlled Humidity

    Clean Room Conditions

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    3/16

    Injazat Data Centre

    Construction

    Two storey construction

    Plant rooms at ground floor level

    Data Centre at first floor level

    Physical separation of power and cooling systems

    Power Technology 6.6 MVA Building Load (5.4 MVA of Critical Load)

    Utility power from 2no dedicated primary supplies

    Fully redundant power distribution systems

    Simultaneous power from systems A & B

    System isolation until point of delivery

    DRUPS providing clean un-interrupted power supply Critical power requirements fully backed by DRUPS

    Stand alone capability for 72 hours

    Injazat Data Centre

    Tier IV Infrastructure

    Provision of secure, and redundant critical

    services to maintain 99.995% Data Hall uptime

    regardless of utility service failure or maintenance

    activities.

    Highest level of Data Centre Reliability

    First facility of its type in the Middle East

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    4/16

    May 2007

    March 2008

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    5/16

    Network Schematic SingleHV DRUPS System

    Network Schematic Downstream Load Distribution

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    6/16

    Normal Operation(Mains Available)

    MVDRUPS

    System B

    MVDRUPS

    System A

    Non-CriticalLoad

    Critical Cooling& Mech Load

    Critical IT &Server Load

    Low-Voltage

    O/P Bus O/P Bus

    ADWEASUPPLY

    A

    ADWEASUPPLY

    B

    Tier IV - 2 (N+1)Architecture

    (Medium Voltage)

    Emergency Operation(Supply A Fails)

    MVDRUPS

    System B

    MVDRUPS

    System A

    Non-CriticalLoad

    Critical Cooling& Mech Load

    Critical IT &Server Load

    Low-Voltage

    O/P Bus O/P Bus

    ADWEASUPPLY

    A

    ADWEASUPPLY

    B

    Tier IV - 2 (N+1)Architecture

    (Medium Voltage)

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    7/16

    MVDRUPS

    System B

    MVDRUPS

    System A

    Non-CriticalLoad

    Critical Cooling& Mech Load

    Critical IT &Server Load

    Low-Voltage

    O/P Bus O/P Bus

    ADWEASUPPLY

    A

    ADWEASUPPLY

    B

    Tier IV - 2 (N+1)Architecture

    (Medium Voltage)

    Emergency Operation(Supply B Fails)

    Emergency Operation(Supply A and B Fail)

    MVDRUPS

    System B

    MVDRUPS

    System A

    Non-CriticalLoad

    Critical Cooling& Mech Load

    Critical IT &Server Load

    Low-Voltage

    O/P Bus O/P Bus

    ADWEASUPPLY

    A

    ADWEASUPPLY

    B

    Tier IV - 2 (N+1)Architecture

    (Medium Voltage)

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    8/16

    Injazat Data Centre

    Plan View - DRUPS PlantRoom Layout

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    9/16

    Elevation Radiator Layout

    Deliveries and Offloading

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    10/16

    Specialist Plant Handling

    150 Ton Mobile Crane

    8 No. 28,000 kg lifts

    Zero Shock requirement

    Levelled Rails

    Hydraulic Rams

    Injazat Data Centre

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    11/16

    Remote Radiators

    Remote Radiators System A

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    12/16

    Two of Four Modules System A

    UTP LV to HV Step-upTransformers

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    13/16

    Service Fuel Tank andHeat Exchangers

    DRUPS Control Room System A

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    14/16

    BCP Panel and UCP Panel

    February 2009

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    15/16

    Injazat Data CentreFebruary 2009

    Injazat Data CentreFebruary 2009

  • 7/28/2019 Hitec Power Protection - Injazat Data Center - Tier IV Solution

    16/16

    Injazat Data CentreFebruary 2009