AX Series I NTELLIGENT F IRE A LARM C ONTROL P ANEL F RONT P ANEL P ROGRAMMING M ANUAL

Upload: others

Post on 20-Dec-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Honeywell Fire Control Panel Front Programming Instructions

AX Series

L

INTELLIGENT FIRE ALARM CONTROL PANE FRONT PANEL PROGRAMMING MANUAL
Page 2: Honeywell Fire Control Panel Front Programming Instructions

Table of Contents

1 Introduction / Overview.........................................................................................4

1.1 Limitations of Fire Alarm Systems...............................................................................................4

1.2 General Installation Notes...........................................................................................................4

2 Programming .........................................................................................................5

2.1 Introduction..................................................................................................................................5 2.1.1 Access Levels...................................................................................................................................5 Memory Lock .......................................................................................................................................................6 2.1.2 Starting Point ....................................................................................................................................7

ZONES: Lists all zones in use by the system and allows text alterations............7

2.1.3 Program Menu Screens....................................................................................................................7 2.1.4 Navigating Through Menus ..............................................................................................................8 2.1.5 Changing Text Descriptions..............................................................................................................8 2.1.6 Numeric data entry .........................................................................................................................10

2.2 Recommended Programming Procedure .................................................................................10

2.3 PROGRAM Menu Functions .....................................................................................................11 2.3.1 Loops/SLC......................................................................................................................................12

2.3.1.1 Loops – View/Edit ..........................................................................................................................................12 2.3.1.1.1 Address Parameter ................................................................................................................................12 2.3.1.1.2 State Parameter.....................................................................................................................................12 2.3.1.1.3 Type .......................................................................................................................................................13 2.3.1.1.4 Value Parameter ....................................................................................................................................13 2.3.1.1.5 Zone Parameter .....................................................................................................................................13 2.3.1.1.6 Device Text Parameter ..........................................................................................................................13 2.3.1.1.7 Action Parameter ...................................................................................................................................13 2.3.1.1.8 Sensitivity Parameter .............................................................................................................................14 2.3.1.1.9 O/P Group..............................................................................................................................................17 2.3.1.1.10 Additional Info ........................................................................................................................................17 2.3.1.1.11 Detector Testing.....................................................................................................................................18

2.3.1.2 Loops – Auto Learn........................................................................................................................................18 2.3.1.2.1 Normal Procedure / Auto Learn .............................................................................................................18 2.3.1.2.2 Procedure if the Panel finds Devices Missing........................................................................................19 2.3.1.2.3 Procedure if the Panel finds Devices Added .........................................................................................20 2.3.1.2.4 Procedure if the Panel finds Devices Changed .....................................................................................20

2.3.1.3 Loop – Meter..................................................................................................................................................20 2.3.2 Zones .............................................................................................................................................21 2.3.3 Exit .................................................................................................................................................21 2.3.4 Outputs...........................................................................................................................................21

2.3.4.1 Default Output Settings..................................................................................................................................22 2.3.4.2 Cause.............................................................................................................................................................22 2.3.4.3 Style ...............................................................................................................................................................24

2.3.4.3.1 Delay......................................................................................................................................................24 2.3.4.3.2 Mode......................................................................................................................................................24 2.3.4.3.3 Wait........................................................................................................................................................24

2.3.4.4 Copying Output Settings to Multiple Zones....................................................................................................24 2.3.5 Positive Alarm Sequence Delays....................................................................................................25 2.3.6 Time and Date ................................................................................................................................25 2.3.7 View Options ..................................................................................................................................26 2.3.8 Passwords......................................................................................................................................26 2.3.9 Panel ..............................................................................................................................................26 2.3.10 PC Config .......................................................................................................................................27 2.3.11 Setup ..............................................................................................................................................27

2.3.11.1 Network..........................................................................................................................................................27 2.3.11.2 Panel Zone.....................................................................................................................................................27 2.3.11.3 ONBOARD NACs ..........................................................................................................................................27 2.3.11.4 Service Number .............................................................................................................................................27 2.3.11.5 Service Due Date...........................................................................................................................................27 2.3.11.6 Trace Logging Mode ......................................................................................................................................28

Page 2 of 30

Page 3: Honeywell Fire Control Panel Front Programming Instructions

2.3.11.7 Detector Blinking ........................................................................................................................................... 28 2.3.11.8 Ground Monitoring ........................................................................................................................................ 29 2.3.11.9 DACT ............................................................................................................................................................ 29 2.3.11.10 Resound........................................................................................................................................................ 29 2.3.11.11 Program Version ........................................................................................................................................... 29 2.3.11.12 CONFIG Data................................................................................................................................................ 29

3 Appendices.......................................................................................................... 30

3.1 Appendix 1 – Forgotten Level 3 Password............................................................................... 30

Page 3 of 30

Page 4: Honeywell Fire Control Panel Front Programming Instructions

1 Introduction / Overview This manual covers the programming of the AX Series Intelligent Fire Alarm Control Panels.

1.1 Limitations of Fire Alarm Systems An automatic fire alarm system can provide an early warning and notification of the development of a fire. It cannot, however, insure protection against loss of property or loss of life.

It is recommended that smoke and heat detectors as well as notification appliances, be located throughout the building in accordance with the requirements detailed in NFPA 72, any local / state codes and with the instructions supplied with the equipment.

The type(s) of detector (s) employed and their physical location must be chosen carefully to ensure that they detect the types of fires likely to occur in the protected area.

Even so, a number of factors may prevent the necessary levels of combustion products from reaching the sensing chambers and thus the system may not indicate an alarm condition.

Heat detectors protect property, not life.

Smoke detectors shall be installed in the same room(s) as the FACP, any equipment used for transmission of the alarm condition, and in locations where power supplies are mounted. Otherwise, a developing fire may damage the system and its ability to report the fire alarm condition. Refer to NFPA 72.

The system will not operate without power. Standby batteries shall be properly maintained and replaced regularly.

Regular maintenance will insure that the system is operating at its optimum performance. Arrange a maintenance agreement with the manufacturer’s local representative to insure that the system is maintained by a professional fire alarm installer in accordance with National and any local / state codes. Maintain a written record of all inspections and maintenance performed.

1.2 General Installation Notes WARNING: Disconnect all sources of power (AC and Battery) before installing components or servicing the system.

DO NOT install / remove circuit cards while the FACP is supplied with power (either AC or Battery).

ENVIRONMENT: INSTALL the equipment in a clean, dry environment.

The equipment meets the requirements for operation at 32°F - 120°F (0°C - 49°C) and relative humidity of 85% RH. However, standby battery life is drastically reduced at higher temperatures. The recommended room temperature for installation is 60°F - 86°F (15°C - 27°C).

WIRING: CHECK that the installation wire sizes are adequate to deliver the required load current and maintain compatibility with the specific device operating voltages.

USE an anti-static wrist strap whenever handling circuit cards.

STORE circuit cards in static suppressive packaging.

CAUTION: Acceptance / Re-acceptance Tests

Following installation, or after any system change (including changes to operating software or configuration settings), the system shall be tested in accordance with the requirements in NFPA 72 and any local / state codes.

All affected functions or devices shall be 100% tested. In addition, at least 10% of initiating devices not directly affected by the change shall also be tested.

Follow the recommendations of NFPA 72.

A secure dedicated ground connection is required. Although no system is immune to the effects of lightning strikes, a secure ground connection will reduce susceptibility. The use of overhead or outside aerial wiring is not recommended

General guidance for installation and trouble free operation.

Must beGrounded

ATTENTION OBSERVE PRECAUTIONS

FOR HANDLING ELECTROSTATIC

SENSITIVE DEVICES

Page 4 of 30

Page 5: Honeywell Fire Control Panel Front Programming Instructions

2 Programming

864

Where you see this symbol take note of any special UL 864 9th Edition precautions.

PCONLY

Where you see this symbol, there are additional enhanced features that can only be configured using the PC-NeT Configuration Tool

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES: This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems (UL 864, 9th Edition), certain programming features or options must be limited to specific values or not used at all as indicated below.

Program feature or option

Permitted in UL 864? Y/N

Possible Settings Settings permitted in UL 864

Section Ref.

Positive Alarm Sequence

Y Stage 1: 1-300 seconds Stage 2: 1-300 seconds

Stage 1: 15 seconds Stage 2: 180 seconds

See Installation and Operation Manual

Alarm Verification Y Fixed N/A

Multiple Detector Operation

Y Per Zone Per Zone 2.3.4

2.1 Introduction These instructions explain the configuration and programming of the AX Series Intelligent Fire Alarm Control Panel.

2.1.1 Access Levels Access to the panel’s control buttons and switches is restricted. A key must be used to unlock a secured cabinet door to gain access to the controls. The panel operation is further protected from inadvertent and erroneous misuse by means of four access levels. These levels are as follows: Level 1 Untrained User – Assigned by Level 3 User, allows restricted access to system controls. Level 2 Authorized User – Assigned by Level 3 User, allows full access to system controls. Level 3 PROGRAMMING – High level, factory authorized technician/engineer, permitting programming of

all system features and functions. Level 4 Firmware Upgrade – Highest level, factory authorized technician/engineer. Permits flash

programming of system software. Special Tools Required.

A level 3 PROGRAM password is required to enter all of the PROGRAMMING menus. For further details of Passwords, refer to Section 2.3.8.

Level 3 PROGRAM Password: If this password number is lost or forgotten, it is not possible to enter program/commission functions. Refer to 3.1 for further information.

Page 5 of 30

Page 6: Honeywell Fire Control Panel Front Programming Instructions

Memory Lock The configuration memory, which contains all programmed entries, may be protected against inadvertent change by means of a memory lock. The memory lock is J1 located to the far left of the main “Base Card” PCB.

Before making any programming/configuration data changes, ensure the jumper is in the OPEN (unlocked) position.

After all changes have been made, move the jumper back to the CLOSED (locked) position to protect the memory against inadvertent change.

Refer to the diagram opposite and below for position of jumper settings.

J1

J1

OPEN POSITION

CLOSED POSITION

USB

Dedicated AC Circuit

OUT OUT IN IN + - + -

Loop-1

OUT OUT IN IN + - + -

Loop-2

A+ A- B+ B-

NAC-1

A+ A- B+ B-

NAC-2

NC NO COM

FIRE NC NO COM

TROUBLE NC NO COM SUPERVISORY

NETWORK

A.C. MAINS!

AUX-1 AUX-2 0V V+ 0V V+

ANC PSU ANC FAULT PSU B A 0V V+

P-BUS B A B A

R EXTGND

SERIAL EXPANSION

BAT BAT - +

PROG

RUN

MASTER

PROGRAM

J2 LOCK MEM

J1

Page 6 of 30

S-232 RX TX

O/C OUTPUTS START FROM

BATTERY

Page 7: Honeywell Fire Control Panel Front Programming Instructions

2.1.2 Starting Point Upon power up, the panel display will show:

Press the Menu button on th7654, and press the ✔ buttobelow in section 2.1.3 will ap There are two main programfrom. They are as follows: LOOPS/SCL: Identify num

more. Open

ZONES: Lists all zon

OUTPUTS: Create “cau TIME/DATE: Change/set VIEW: View status PASSWORDS: Enter/chang PANEL: Lists all inte PC CONFIG: Enables con SETUP: Allows prog

device blink EXIT: Exits progra

2.1.3 Program Menu

[Program Menu 1 LOOPS/SLC OUTPUTS

[Program Menu 2 PASSWORDS

Selecting “Next Menu” altern

Advanced 12:00 AM NOV 26 2007 NORMAL PANEL OPERATION (Press Menu to View)

e keypad to begin. Next enter the factory default Level 3 programming code n to enter the code. You are now in Level 3 programming mode and the screen pear.

ming menu screens to choose from with up to 10 different sub-menus to choose

ber of SLC/LOOPS installed. Perform AUTO-LEARN, alter/enter device text, and s several sub-menus.

es in use by the system and allows text alterations.

se and effect” programming.

the time and date.

of the entire system. Opens several sub-menus.

e level 1,2,3 and 4 passwords.

rnal panel circuits and allows programming from default settings.

nection to a PC for use of PC-NeT Configuration Tool.

ramming of a number of system options including networking, service due date, ing and more.

m mode and returns to normal display/operation.

Screens

] Node 1

ZONES EXIT TIME/DATE VIEW Next Menu

] Node 1

PANEL PC-CONFIG SETUP Next Menu

ates between Program Menu 1 and 2.

Page 7 of 30

Page 8: Honeywell Fire Control Panel Front Programming Instructions

2.1.4 Navigating Through Menus

[Program Menu 1] Node 1 LOOPS/SLC ZONES EXIT OUTPUTS TIME/DATE VIEW Next Menu

When a Program Menu is displayed, use the buttons to highlight the required menu option and then press the ✔ button to select that option. More Program Menu options are available by selecting the “Next Menu” button. Press the ‘Esc’ button from within any menu option to return to the previous menu. The system can be returned to Normal Operation by pressing the ‘Esc’ button when at the top level Program Menu 1, or by not touching any buttons for 60 seconds (programming timeout). Note: The 60 second programming timeout can be disabled through the PC-NeT configuration programming Tool.

2.1.5 Changing Text Descriptions Various parameters can have a user defined text description. These include SLC Loop devices, zones, outputs, etc. The zone and device text descriptions are shown on the display when a status change occurs, providing a quick and clear indication of the source of the problem. Example: To add or change the device text associated to an addressable point, highlight the LOOPS/SLC in [Program Menu 1] and then press the ✔ button.

[Program Menu 1] Node 1 LOOPS/SLC ZONES EXIT OUTPUTS TIME/DATE VIEW Next Menu

Then, highlight the LOOP associated with the addressable point (i.e.: LOOP 1), then press the ✔ button. Note: The list of loops available will be adjusted automatically to show only those loops that have a loop driver installed. The below example is for an AX Series Intelligent Fire Alarm Control Panel with two loop drivers (2 SLC Loops) installed.

[Select Loop] Node 1 LOOP 1 LOOP 2 LOOP 3 LOOP 4 x x

Press the buttons to scroll through the list of Loops and then press the ✔ button to select the required loop.

Page 8 of 30

Page 9: Honeywell Fire Control Panel Front Programming Instructions

The display will then show a list of programming options for the specific loop selected, as follows:

[Loop 1] Node 1 VIEW/EDIT AUTO LEARN METER

Highlight the VIEW/EDIT programming option and then press the ✔ button. The display will be as follows:

[Loop 1 SLC] More> Address State Type Value 001.0 Normal PULL STATION 16 002.0 Normal MULTI.SENSOR 28 003.0 Normal PHOTO SMOKE 23 004.0 Normal SWITCH(MON) 16

Press the buttons to scroll to the required address point then press the button until you reach the “Device Text” column, press the ✔ button.

Note: If no previous Device Text has been programmed, Device Text location will be blank.

[Loop 1 SLC] More> Address Device Text Action 001.0 FIRE S 002.0 FIRE S 003.0 SUPERV 004.0 FIRE S

>R < KEY IN THE REQUIRED TEXT

The method of entering the characters is similar to the method employed on cell phones. The number buttons provide both their appropriate number and several letters of the alphabet. An example of the keypad is shown opposite.

MenuEsc 0

9wxyz7 pqrs

def31

tuv8

abc2

mno6jkl54 ghiFor example, Button 2 allows entry of the number 2 and letters A, B and C.

When a button is pressed, the number is first shown on the display at the current cursor position. If the button is pressed again within ½ second, the first character replaces the number. A further press displays the second available character and so on. After pressing the button to obtain the required character, wait for 1-second and the character will be entered and the cursor will move to the next character in the text description.

Pressing another button will immediately enter the previous character and move the cursor on to the next character.

Use the buttons to move backwards or forwards along the Device Text line. When you’ve completed entering the Device Text description, press the ✔ button.

Page 9 of 30

Page 10: Honeywell Fire Control Panel Front Programming Instructions

After completing all addressable point Device Text descriptions, press the ‘Esc’ button to return to the previous display.

The following table shows the numbers, characters and symbols assigned to each button on the keypad.

Button 1st Press 2nd Press 3rd Press 4th Press 5th Press Further Characters

1 1

2 A B C 2 Ä, Æ, Å, À, Á, Â, Ã, Ç

3 D E F 3 È, É, Ê, Ë, Đ

4 G H I 4 Ì, Í, Î, Ï

5 J K L 5

6 M N O 6 Ö, Ø, Ò, Ó, Ô, Õ, Ñ

7 P Q R S 7

8 T U V 8 Ù, Ú, Û, Ü

9 W X Y Z 9 Ý, Þ

0 Blank 0

Alternatively, press the buttons to scroll through a list of characters. Start by pressing the “up arrow” key. When the required character is shown, press the button to move on to the next character. The list of characters available and the order of presentation is as follows: Blank !“#$%&‘()*+,-./ 0123456789 :; ?@ ABCDEFGHIJKLMNOPQRSTUVWXYZ [‘]^_

2.1.6 Numeric data entry Numbers are entered by moving to the required field, and then typing in the required number, followed by the ✔ button. If the number is entered incorrectly, press the ‘Esc’ button to restore the previous number.

2.2 Recommended Programming Procedure ♦ Step 1 – SET-UP, Define General Set-up Information (Service Phone Numbers, etc.). ♦ Step 2 – PASSWORDS, Define User and Program Passwords as required. ♦ Step 3 – AUTO-LEARN, Let the panel learn the devices on the loop(s). ♦ Step 4 – VIEW DEVICES, Enter Zone Numbers, Location text and Change Group Assignments if

required. ♦ Step 5 – OUTPUTS, Program Output Groups as required. ♦ Step 6 – ZONES, Enter Zone Texts as required.

Page 10 of 30

Page 11: Honeywell Fire Control Panel Front Programming Instructions

2.3 PROGRAM Menu Functions The following table gives a list of the PROGRAM Menu Functions, the sub-functions available within each main function and a brief description for each function.

Step No./Main Menu Option

Sub Menus Comments

View/Edit View, test and configure the SLC loop devices.

Auto Learn Learn the devices present on all SLC loops.

4 3

LOOPS/SLC

Meter View information on the SLC loop voltages /currents.

6 ZONES -- Configure the Zones.

EXIT -- Cancel Level 3 Access and return to Level 2 Menu Options.

5 OUTPUTS -- Configure the Operating Characteristics of the Output Circuits.

TIME/DATE -- Change the Time and Date Settings.

Alarms View Zones and Inputs that are reporting an alarm condition.

View Zones, Inputs and Outputs that are reporting an off-normal condition. Off-Normal

Alarm, Pre-Alarm, Supervisory, Trouble, Disabled, etc.

Inputs View the current state of Zones and Inputs.

Outputs View the current operational condition of all output circuits.

Log View the Event Log.

Panel View the operational state, voltage & current loading of the panel I/O’s.

VIEW (Allows viewing of any programming changes and system status without exiting program mode.)

Network View Network Diagnostics

2 PASSWORDS -- Configure the Level 2 and Level 3 passwords.

PANEL -- Change the default zone assignments and output groups for all panel I/O’s.

PC-LINK -- Enable the PC Link for transfer of configuration data to and from the panel.

1 SETUP -- Configure General Operating Parameters.

Page 11 of 30

Page 12: Honeywell Fire Control Panel Front Programming Instructions

2.3.1 Loops/SLC Upon selecting the LOOPS/SLC option, the display will prompt for selection of the loop to be viewed / programmed.

[Loop 1] Node 1 LOOP 1 LOOP 2 LOOP 3 LOOP 4 x x

Note: The list of loops available will be adjusted automatically to show only those loops that have a loop driver installed. The above example is for an AX Series Intelligent Fire Alarm Control Panel with two loop drivers (2 SLC Loops) installed.

Press the buttons to scroll through the list of loops available and then press the ✔ button to select the loop required.

The display will then show a list of programming options as follows:

[Loop 1] Node 1 VIEW/EDIT AUTO LEARN METER

2.3.1.1 Loops – View/Edit The VIEW/EDIT option shows a list of the devices connected to the loop that were Auto-Learned by the panel. For example:

[Loop 1 SLC] More> Address State Type Value 001.0 Normal PULL STATION 16 002.0 Normal MULTI.SENSOR 28 003.0 Normal PHOTO SMOKE 23 004.0 Normal SWITCH(MON) 16

The first device on the loop is shown at the top of the list and is highlighted. Press the buttons to scroll through the list of devices.

Press the buttons to view additional information. The display highlights a particular parameter. If a highlighted field is modifiable and you’re not in view only mode, press the ✔ button and an additional option menu will be displayed.

2.3.1.1.1 Address Parameter Shows address of device on loop/SLC being viewed.

2.3.1.1.2 State Parameter This parameter shows the current operational status of the device. For example, this can show Normal, Alarm, Device Missing, etc.

This parameter cannot be changed.

Page 12 of 30

Page 13: Honeywell Fire Control Panel Front Programming Instructions

2.3.1.1.3 Type This parameter shows the type of device Auto Learned by the panel. For example, this can show Pull Station, Multi-Sensor, Photo Smoke, Heat, etc.

This parameter cannot be changed.

2.3.1.1.4 Value Parameter This parameter shows the analog value returned by the device. The number displayed will vary according to the type of device installed. An ‘H’ (High) and ‘L’ (Low) is shown for Switch (logic) inputs. The current sensitivity mode setting for AX intelligent smoke detectors is shown (a value based on sensitivity programming ranges 1 through 5). This parameter cannot be changed.

2.3.1.1.5 Zone Parameter This parameter shows the Zone to which this device has been assigned. Use the number keys to change the zone assigned to the device and press the ✔ button.

2.3.1.1.6 Device Text Parameter This parameter shows the 26-character location text assigned to this device. For guidance on how to change the text, refer to Section 2.1.5.

2.3.1.1.7 Action Parameter This parameter shows the action that will be performed when this device indicates an active (alarm) condition. For example:

[Loop 1 SLC] <More> Address Action Sensitivity O/P 001.0 FIRE SIGNAL DEFAULT 002.0 FIRE SIGNAL DEFAULT 003.0 FIRE SIGNAL DEFAULT 004.0 FIRE SIGNAL DEFAULT

Press the ✔ button to change the action assigned to this input device. A pop-up window is then shown on the display from which a different action can be selected.

[Select New Action] FIRE SIGNAL . PRE-ALARM FAULT SIGNAL ↓

Press the buttons to scroll through the list of Actions and then press the ✔ button to confirm the change. The display reverts to the device list showing the new action assigned to this device. Alternatively, press the ‘Esc’ button to cancel the changes and return to the device list display. The following Actions are available (Additional actions are available on a PC-NeT Configuration Tool)

Page 13 of 30

Page 14: Honeywell Fire Control Panel Front Programming Instructions

Action Description Fire Signal1 A Fire Alarm Condition will be generated whenever the input is active.

Supervisory A Supervisory Condition will be generated whenever the input is active.

Trouble Signal A Trouble Condition will be generated whenever the input is active.

Pre-Alarm A Pre-Alarm Condition will be generated whenever the input is active.

Key Lock Enables / Inhibits front panel controls (Disable, Acknowledge, Reset etc.)

Control Signal Allows control of Outputs without displaying “Trouble” or “Fire” or sounding the panel buzzer

- No Action is assigned to the input.

PPCCOONNLLYY

Other device actions can be configured using the PC-NeT Configuration Tool.

2.3.1.1.8 Sensitivity Parameter This parameter shows if the device sensitivity is set to its “DEFAULT” or “CUSTOM” settings. For example:

[Loop 1 Devices] <More>Address Sensitivity 001.0 DEFAULT 002.0 DEFAULT 003.0 CUSTOM 004.0 DEFAULT

Press the ✔ button to change the sensitivity assigned to an input device. When selected, a new screen displays the sensitivity settings assigned. For example, with an AX Series Intelligent Photoelectric Detector:

SENSITIVITY ADJUST MODE ( PHOTO SMOKE ) [ Alarm = 55 ][ Mode = 3 ][ Pre-Alarm= 45 ][ Sampling = 5s][ Min.Value= 8 ] [SAM/SSM]

Press the buttons to highlight the required menu option and then press the ✔ button to select it. Use the number buttons to enter the required value. Alternatively, press the ‘Esc’ button to cancel the changes.

The alarm thresholds are fixed for all devices. Sensitivity can only be changed for AX intelligent detectors using the Sensitivity Mode setting.

2.3.1.1.8.1 Mode

Each AX Series intelligent detector is capable of being field programmed for one of five response/sensitivity modes (see below). Response modes correspond to unique response behaviors of a detector and the type of environment it is protecting, which can be broadly related to the characteristics of a fire. The detector response modes relate to different combinations of smoke sensitivity characteristics and delay times, if utilized (see below). Response mode 1 is more sensitive than response mode 5. Detectors set to response mode 1 would be more suitable for environments in which sources of unwanted alarms are rare (i.e.: clean

Page 14 of 30

1 Fire Alarm Conditions are latched. By default, all other conditions are non-latching. The action for smoke and certain other detectors is always fire and cannot be changed.

Page 15: Honeywell Fire Control Panel Front Programming Instructions

rooms and computer rooms). Response mode 5 set detectors would be suitable for more dusty or smoky environments (i.e.: boiler rooms, loading dock areas). Response mode 3 (default programmed) would be the mid-sensitivity level used for most normal applications. Response mode setting and hysteresis of the individual detectors are stored within the detector’s memory. The storing of this critical information in the detector rather in the fire alarm control panel software allows the detector to maintain its programmed response settings and compensated values even when power is removed from the detector. If the detector is powered down or inadvertently replaced in another location, the detector response mode and clean values are not lost.

Clean Room, Computer

Room

Hotel Room, Apartment

Office, Hospital Ward,

Factory, Light Industry

Warehouse, Restaurant

Loading Dock, Parking Garage

Kitchen, Laundry(enclosed and

ventilated)

Boiler Room

Mode 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5

Photoelectric

Ionization

Multi-Sensor

Heat

1, 2, 3, 4, 5 = Response/Sensitivity Modes = Mode Suitable for Installation

Photoelectric Detector Multi-Sensor Detector

Response Mode

Sensitivity Characteristics

Delay Time

Response Mode

Smoke Sensitivity Characteristics

Temperature Sensitivity

Delay Time

1 1.7 %/ft 5 sec 1 1.7 %/ft High 0-20 sec

2 1.7 %/ft 30 sec 2 2.3 %/ft None 0-30 sec

3 2.3 %/ft 5 sec 3 2.7 %/ft Medium 0-20 sec

4 2.3 %/ft 30 sec 4 3.3 %/ft Medium 0-20 sec

5 2.9 %/ft 5 sec 5 None 1350F 0-30 sec

Ionization Detector Heat Detector

Response Mode

Sensitivity Characteristics

Delay Time

Response Mode

UL521 Temperature Rating (0F)

Sensitivity Characteristics

Spacing

1 .60 %/ft 5 sec 1 1350 Ordinary Static/Rate-of-Rise 70 ft

2 .60 %/ft 30 sec 2 1500 Ordinary Static/Rate-of-Rise 70 ft

3 .65 %/ft 5 sec 3 1500 Ordinary Static 70 ft

4 .65 %/ft 30 sec 4 2000 Intermediate Static/Rate-of-Rise 70 ft

5 .70 %/ft 5 sec 5 2000 Intermediate Static 70 ft

Page 15 of 30

Page 16: Honeywell Fire Control Panel Front Programming Instructions

2.3.1.1.8.2 Sampling

If the panel senses that a device may be in an alarm/active condition, it performs multiple samples to ensure that the alarm is a valid alarm. The value in this field defines the maximum time from first sensing a possible alarm to the final validated sample.

USE CAUTION WHEN SELECTING SAMPLINGVALUE

Detectors: Default 5 seconds. Maximum 10 seconds.

Input Modules: Default 0 seconds. Maximum 10 seconds.

2.3.1.1.8.3 Alarm

The Alarm Level is the level of the analog value returned by the detector at which the panel will enter an alarm condition. The default value is 55. The alarm level cannot be adjusted.

2.3.1.1.8.4 Pre-Alarm

The Pre-Alarm Level is the level of the analog value returned by the detector at which the panel will enter a pre-alarm condition.

2.3.1.1.8.5 Minimum Value

If the detector analog output falls below the minimum value programmed, the panel will enter a fault warning (i.e.: dirty detector) condition. This parameter is normally left at a value of 8. Range is 4-20.

2.3.1.1.8.6 Special Sensitivity Mode SSM/Clock

In addition to the “SENSITIVITY ADJUST MODE”, an intelligent device can also run “SPECIAL SENSITIVITY MODE” (SSM) under time-clock control.

The AX Series Intelligent Fire Alarm Control Panels supports 10 independent, 7-day time clocks.

With the SAM/SSM Option highlighted, press the ✔ button to view the Special Sensitivity Mode settings. For example:

SPECIAL SENSITIVITY MODE (PHOTO SMOKE) [SSM/Clock = 2 ][ Alarm = 55 ][ Mode = 3 ][ Pre-Alarm= 45 ][ Delay = 5s][ Min.Value= 8 ] [SAM/SSM]

In the above example the panel is using special sensitivity mode 5 (and time clock number 2). Enter “0” in the SSM/Clock field to cancel Special Sensitivity Mode.

A number must be entered in the SSM/Clock field to select the appropriate SSM number and time clock. To view the time clock settings, highlight the SSM/Clock field, and press the ✔ button.

For example:

[Time Clock 2] DAY ON -> OFF ON -> OFF MON 00:00 00:00 19:00 00:00 TUE 00:00 06:30 00:00 00:00 WED 00:00 00:00 00:00 00:00 THU 00:00 00:00 00:00 00:00

The panel supports two independent times for each day of the week during which the SSM mode will be switched on (i.e. during which the Special Sensitivity Mode settings are active).

In the above example the SSM will be active between 19:00 (7:00 PM) on Monday and 06:30 (6:30 AM) on Tuesday (an example of use, would be a detector more sensitive during none occupied time periods). Page 16 of 30

Page 17: Honeywell Fire Control Panel Front Programming Instructions

Press the buttons to select the appropriate time field and use the number buttons to enter the required times. Press the ‘Esc’ button to return to the previous menu display.

Every type of device (the device type is shown in the top, right hand corner of the display) can support a unique SSM setting based on an SSM/Clock number. In the previous example the Special Sensitivity Mode settings have been defined for a PHOTO SMOKE that is using SSM/Clock number 2. If other intelligent smoke detectors on the same panel also require the same settings, then you only need to set them to the SSM/Clock 2 also. If a different time setting is required simply set another SSM/Clock number to meet its requirement.

2.3.1.1.9 O/P Group The O/P Group assignment is a group assigned to addressable NAC and Relay modules. These output groups determine the manner in which the outputs will operate when an alarm or other status event occurs within the system.

For example:

[Loop 1 Devices] <More>Address O/P Group 020.0 199 021.0 199 022.0 199 023.0 199

Use the number buttons to change the value of the O/P Group setting.

By default, all Loop Output devices are assigned to Output Group 199 (Common Alarm).

For detailed information and guidance on the programming and use of Output Groups, refer to Section 2.3.4

2.3.1.1.10 Additional Info This parameter shows additional information for the intelligent smoke detectors. For example:

[Loop 1 Devices] <More>Address Additional Info 001.0 AFSI 002.0 003.0 AFSI 004.0 AFSI

The panel can read any of the extended memory locations within the AX intelligent smoke detectors.

Highlight any “AFSI” family device, select VIEW EEPROM and then press the ✔ button to confirm. The display will prompt for entry of the required extended memory address. For example:

[Loop 1 Devices] <More>Address Additional Info

EEPROM ADDRESS=#

Enter the required address (# = all intelligent smoke detectors on that loop) using the number buttons and then press the ✔ button to confirm.

The panel will now read the extended memory locations for all AFSI intelligent detectors on the loop. When complete, the display will present the information as follows:

Page 17 of 30

Page 18: Honeywell Fire Control Panel Front Programming Instructions

[Loop 1 Devices] <More> Address Additional Info >001.0 EEP[ 1] = 23 002.0 003.0 EEP[ 1] = 21 004.0 EEP[ 1] = 22

2.3.1.1.11 Detector Testing Individual detectors can be tested to check the chamber response/operation and illuminate the detector LED.

While the address field is highlighted, press the buttons to scroll through the list of devices to the desired detector (or key in the address, and then press the ✔ button).

[Loop 1 SLC] <More> Address Action Sensitivity O/P 001.0 FIRE SIGNAL DEFAULT 002.0 FIRE SIGNAL DEFAULT 003.0 FIRE SIGNAL DEFAULT 004.0 FIRE SIGNAL DEFAULT

A menu will appear to confirm that you want “Test This Detector”.

TEST THIS DEVICE

Press the ✔ button to confirm or press the ‘Esc’ button to cancel.

Once selected, commands are sent to the intelligent smoke detector to turn on the detector LED and put the chamber into test. The “Test” LED lights up and the panel display returns to the list of devices.

After a few seconds the analog signal will rise, indicating the level of an alarm condition. If the detector is then left in the test condition, the Detector State will change to a “Fire Test” status.

The test is cancelled as soon as the display is scrolled up or down or when the ‘View Devices’ option is exited.

2.3.1.2 Loops – Auto Learn

2.3.1.2.1 Normal Procedure / Auto Learn The panel can automatically learn the presence or absence of devices at all addresses connected to the SLC loop(s) (Auto Learn is done on a per loop basis). When the Auto Learn option is selected, the panel starts searching the selected SLC loop for all associated addressable devices. A display is shown to indicate the progress of this procedure.

For example:

[Auto Learn Loop 1] AFSI Address 15 Devices found = 3

Page 18 of 30

Page 19: Honeywell Fire Control Panel Front Programming Instructions

When all addresses have been searched and all devices found the panel will display a summary screen showing the quantity of devices found for each type of device.

For example:

[Auto Learn Loop 1] AFSI Address 126 Devices found = 4

OPT ION MUL TMP PUL NAC I/O ZMU OTHERS 0 1 1 1 1 0 0 0 0

This summary provides a quick check to ensure that the panel has found all of the devices that should be connected to the SLC loop.

Press the ‘Esc’ button to return to the loop menu and press “Esc” again to go to the select SLC loop main menu.

Upon completion of the Auto Learn programming, all devices will be default programmed for general alarm:

NACs: activate on any alarm condition, silenceable

Relays: activate on any alarm condition, non silenceable

Smoke Detectors: default sensitivity (Mode 3) setting/level

Outputs = Relay

Inputs = Contact device input

2.3.1.2.2 Procedure if the Panel finds Devices Missing When the panel cannot communicate with a device previously programmed into the panel, the Auto Learn process is suspended and the display shows a pop-up window with options. For example:

KEEP THIS DEVICE . DELETE THIS DEVICE KEEP ALL MISSING DELETE ALL MISSING

! Address 002 DEVICE MISSING

If the missing device is kept (or all missing devices are kept), the panel remembers the programming for these devices. The panel will report a trouble condition until such time as the missing devices are reconnected.

If the missing device is deleted (or all missing devices are deleted), the panel clears all previous programming for these devices. This includes any sensitivity threshold changes, text assignments, zone assignment, action, etc.

Press the buttons to highlight the required menu option and then press the ✔ button to confirm. The pop-up window will disappear and the panel will continue with the Auto Learn process.

If a single device is deleted and another missing device is subsequently registered, the display will once again show the pop-up window to keep or delete this device.

Page 19 of 30

Page 20: Honeywell Fire Control Panel Front Programming Instructions

2.3.1.2.3 Procedure if the Panel finds Devices Added When the panel finds a device not previously learned and programmed in the panel, the Auto Learn process is suspended and the display shows a pop-up window with options. For example:

ACCEPT NEW DEVICE . REJECT NEW DEVICE ACCEPT ALL NEW DEVICES REJECT ALL NEW DEVICES

! Address 002 NEW DEVICE

If the new device is accepted (or all new devices are accepted), the panel will configure the memory to register these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments, zone assignment, action, etc. for these devices.

If the new device is rejected (or all new devices are rejected), the panel does not program any default settings for these devices and will not attempt to communicate with the devices at these addresses.

Press the buttons to highlight the required menu option and then press the ✔ button to confirm. The pop-up window will disappear and the panel will continue with the Auto Learn process.

If a single device is accepted / rejected and another new device is subsequently registered, the display will once again show the pop-up window to accept or reject this device.

2.3.1.2.4 Procedure if the Panel finds Devices Changed When the panel finds a new type of device installed at an address previously learned and programmed in the panel, the Auto Learn process is suspended and the display shows a pop-up window with options. For example:

ACCEPT NEW DEVICE . KEEP OLD DEVICE ACCEPT ALL NEW DEVICES REJECT ALL NEW DEVICES

! Address 002 TYPE CHANGE

This situation could arise for example if a heat detector has been installed in place of a photoelectric smoke detector.

If the new device type is accepted (or all new device types are accepted), the panel will configure the memory to register these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments, zone assignment, action, etc. for these devices.

If the new device type is rejected (or all new device types are rejected), the panel remembers the programming for the original devices. The panel will report a fault condition until such time as the correct device types are reconnected.

Press the buttons to highlight the required menu option and then press the ✔ button to confirm. The pop-up window will disappear and the panel will continue with the Auto Learn process.

If a single device is accepted / rejected and another new device type is subsequently registered, the display will once again show the pop-up window to accept or reject this device.

2.3.1.3 Loop – Meter

Displays loop output and input voltages and loop loading. It also shows the revision of the loop driver software. A diagnostic display with automatic scanning of the loop to find devices with minimum and maximum communication pulse heights is available.

Page 20 of 30

Page 21: Honeywell Fire Control Panel Front Programming Instructions

2.3.2 Zones The Zones option lists all the zones in use by the panel and allows the zone text description to be changed.

[Commission Zones] Zone Location 0001 BASEMENT WEST 0002 RECEPTION 0015 EAST WING 0018 TOWER BLOCK

To change the location text assigned to the Zone, press the ✔ button when the Zone Location Text is highlighted. Refer to Section 2.1.5 for guidance on how to change text descriptions.

To select a different zone, use either the buttons (scroll up/down) or just type in the number of the required zone, followed by the ✔ button. Note that only zones in use are displayed.

2.3.3 Exit To exit the Programming Mode and return the panel to normal operation (User level 1 or 2), select the “Exit” option by selecting “Exit” then press the ✔ button or press “Esc”. The display will prompt for confirmation of the PROGRAM password. For example:

Please Enter Your Password

If the password is incorrect or if the password is not entered within 5-seconds, the display will revert to the PROGRAM Level Menu and User level-2 will not be entered.

After programming, the panel must always be returned to User level 2 (or level 1) to give normal alarm coverage.

2.3.4 Outputs The “Cause and Effect” programming is a schedule of actions that will turn on one or more outputs dependent upon a set of input events.

The Outputs Option provides the means to create simple or complex “cause and effect” programming within the panel. Delays can be introduced to allow a phased evacuation of a building (Note: this is different to “Positive Alarm Sequence” which is detailed in section 2.3.5).

This section describes the settings and options in detail for each parameter.

More complex “Cause and Effect” programming may be undertaken using the PC-NeT Configuration tool. When the OUTPUTS Option is selected, the display shows the cause and effect programming for Output Group 1. For example:

[Output Group 1] [ 3.9% Mem used]ZONE CAUSE STYLE=Delay->MODE 1 ANY FIRE 00 - On 2 ANY FIRE 00 - On 3 ANY FIRE 00 - On 4 ANY FIRE 00 - On

Page 21 of 30

Page 22: Honeywell Fire Control Panel Front Programming Instructions

To simplify the cause & effect programming, one or more outputs that will respond in the same way when the same set of input events occurs can be grouped together. This association of outputs is called an Output Group.

The panel can support up to 200 of these Output Groups. To select a different Output Group, highlight any group number and then enter the number of the output group required using the number buttons. The display always shows the Output Group in the top left corner.

Press the buttons to scroll through the list of zones.

Press the buttons to select the fields for a particular zone.

Press the ✔ button to select a particular field option to change its setting.

2.3.4.1 Default Output Settings On initial installation, or after clearing the configuration memory, all outputs are assigned to specific Output Groups and will turn on immediately if a single alarm occurs in any zone (any trouble condition for the systems defaulted trouble relay, any supervisory condition for the systems defaulted supervisory relay). The default assignments are as follows:

Output Device Output Group Cause and Effect On-board NAC 1 1 Any fire in any zone – no delay

On-board NAC 2 2 Any fire in any zone – no delay

On-board NAC 3 2 3 Any fire in any zone – no delay

On-board NAC 4 2 4 Any fire in any zone – no delay

On-board Relay 1 200 Any trouble in any zone – no delay

On-board Relay 2 199 Any fire in any zone – no delay

On-board Relay 3 198 Any supervisory in any zone – no delay

On-board Open Collectors 199 Any fire in any zone – no delay

All Loop Output Devices 199 Any fire in any zone – no delay

2.3.4.2 Cause Each Output Group can be programmed to respond in a unique way to events from each individual zone. An input event may be a fire alarm condition or it may be a trouble, disablement or other condition. A combination of criteria may also be applied to each zone. The Cause field determines what type of input event (or a combination of input events) will generate an output response for the selected input zone. To inspect or change the Cause, press the button to highlight the cause option. For example:

[Output Group 1] [ 3.9% Mem used]ZONE CAUSE STYLE=Delay->MODE Wait 1 ANY FIRE 00 - On 2 ANY FIRE+ 00 - On 3 ANY FIRE 00 - On 4 ANY FIRE 00 - On

Press the ✔ button to change the setting and a pop-up window will appear showing the options available. For example:

Page 22 of 30

2 AX-CTL-4 or AX-CTL2 + AX-NAC Only

Page 23: Honeywell Fire Control Panel Front Programming Instructions

[FIRE ] [SUPERVISORY] [PRE-ALARM]

✔ - - [TEST] [TROUBLE] - -

Press the buttons to highlight the required menu option and then press the ✔ button to change its

setting. An input action type is enabled when a ✔ is shown beneath the option. It is permitted to select multiple input types in which case a combination of input events will result in an output action. If there is a combination of input events, the CAUSE display above shows this extended programming by adding a ‘+’ to the text. For example, Zone 2 above shows that the basic event is ANY FIRE + other criteria.

Press the ‘Esc’ button to return to the previous display.

The definition for each cause is as follows:

Cause Definition Fire Any single fire alarm.

Supervisory Any device in a supervisory condition

Pre-Alarm Any device in a pre-alarm condition.

Trouble Any device entering a trouble condition.

Test A 'Walk Test' fire in the zone.

PPCCOONNLLYY

Further enhanced cause and effects options can be programmed using the PC-NeT Configuration Tool.

[Output Group 1] [ 3.9% Mem used]ZONE CAUSE STYLE=Delay->MODE Wait 1 SPECIAL 00 - On 2 SPECIAL 00 - On 3 SPECIAL 00 - On 4 SPECIAL 00 - On

If the cause and effects programming is performed using the PC-NeT Configuration tool, the display shows “SPECIAL” and these group rules cannot be adjusted via the front panel menus.

864 Restrictions Apply

PPCCOONNLLYY

Multiple Detector Operation - Coincidence Detection.

The operation of the Coincidence Detection (Double Knock) feature is on a per zone basis.

At least two automatic devices shall be placed in the protected space. The spacing shall be as per NFPA 72 and shall be no more than 0.7 times the linear spacing for public mode notification uses.

Smoke Detectors employed in multiple detector operation must not be configured for Alarm Verification.

Page 23 of 30

Page 24: Honeywell Fire Control Panel Front Programming Instructions

2.3.4.3 Style The way in which an output turns on in response to a particular input event can be programmed. For example, an output may turn on immediately, it may turn on after a delay or it may pulse for a set time period and then turn on. This method of operation is called a “Style”. A style may have up to three different methods of operation. For example,

Delay Mode, Wait Mode, Wait Mode.

Style 00 is fixed to turn on immediately when an input event occurs.

Style 01 is fixed to pulse immediately when an input event occurs.

Styles 02 to 20 are programmable

Press the button to advance to the style field. Change the setting using numeric entry to select the required output style. If the style is already programmed elsewhere, the relevant style parameters are automatically entered into the appropriate fields.

2.3.4.3.1 Delay The delay field is the time from qualification of the input event to something happening at the output. The delay time can be set in intervals of 1 second up to a maximum of 250 seconds.

Press the button to advance to the delay field and change the setting using numeric entry.

2.3.4.3.2 Mode The mode field defines the method of operation of the output when it is first activated. This can be ON or PULSE.

Press the button to advance to the delay field and change the setting using the ✔ button.

PPCCOONNLLYY

In addition to the default ON and PULSE options, the outputs can be configured for additional ringing styles using the PC-NeT Configuration Tool. This includes the ANSI S3.41 (Temporal) Evacuation signal as well as simple on/off times (such as 2s ON / 3s OFF).

2.3.4.3.3 Wait The wait field is the time from first activation of the output to the next operational condition (mode) of the output. For example, the output could initially be delayed for 20 seconds and turn on in a pulsing mode. After a wait of a further 30 seconds it can be programmed to turn on differently such as steady ON. The wait time can be set in intervals of 1 second up to a maximum of 250 seconds.

Press the button to advance to the wait field and change the setting using numeric entry.

2.3.4.4 Copying Output Settings to Multiple Zones To save time in the entry of similar Output Group Settings for each zone, it is possible to copy information programmed for a particular zone to subsequent zones.

Press the button to highlight the required zone number and then press the ✔ button. The display shows a pop-up window prompting for the number of the zone to which to copy the information.

Use the number entry to select the required zone number. The Output Group programming for all of the zones from the currently selected zone to the zone number entered will be programmed with the same information as the currently selected zone.

Page 24 of 30

Page 25: Honeywell Fire Control Panel Front Programming Instructions

2.3.5 Positive Alarm Sequence Delays

PPCCOONNLLYY

In addition to the “Cause and Effect” programming described above, the panel also supports Positive Alarm Sequence which allows time for a building supervisor to investigate fire signals before turning outputs on. This mode can only be configured from the PC-NeT Configuration Tool.

864 Restrictions Apply

Maximum times restricted. Defaults are per UL864/NFPA72 requirements.

Smoke Detectors employed in Positive Alarm Sequence must not be configured for Alarm Verification.

There are two parts to this delay. The first stage is set relatively short (default 15 seconds). If the building supervisor does not acknowledge the alarm signal within the first stage, the delayed outputs will turn on. The second stage gives a longer period to investigate the alarm (default 180 seconds). This delay can be cancelled at any time by activating a manual pull station, or any other programmed overriding input device.

Note: If a second device alarm occurs Positive Alarm Sequence Delays are aborted.

First Stage Timer = maximum 300 seconds (NFPA 72 maximum time period 15 seconds).

Second Stage Timer = maximum 600 seconds (NFPA 72 maximum time period 180 seconds).

Each input and output device can be individually programmed to use the investigation delay from the PC-NeT configuration tool, together with the times appropriate to each stage of the delay. Refer to the Operation section of this manual for how the building occupier can turn the investigation delay feature on or off.

2.3.6 Time and Date This function allows the time and date in the panel to be changed. On entry to this function, the display will show the current time and date with confirmation of the day of the week on the bottom line.

Note: time change is in 12 hr [US – Standard] format with AM & PM or 24 hr [military format].

For example:

[SET TIME/DATE] TIME = 05:28 PM DATE = 04/15/06 SAT APR 15 2006

To change the settings, use the buttons to highlight the required option. Directly enter the new time or date using the number buttons. As soon as a number button is pressed, the display will clear the current setting and show the new value as it is entered. For example:

[SET TIME/DATE] TIME = 1-:-- AM DATE = 04/15/06 SAT APR 15 2006

Page 25 of 30

Page 26: Honeywell Fire Control Panel Front Programming Instructions

2.3.7 View Options The View Menu Options are identical to those available during Level-2 operation.

For further information on the View Options and the information that is presented, refer to the Operation section.

2.3.8 Passwords The panel provides up to 10 User Level-2 passwords and 2 Level-3 passwords. All of the passwords 3 can be field modified/changed.

Upon entry to the function, the display shows a list of the passwords. For example:

Password Access level User ID 15633 2 01 9988 2 02 13344 2 03 10000 2 04 10000 2 05

To change a password, use the buttons to highlight the required password and then enter the new password using the number buttons. When the required password is entered, press the ✔ button to confirm.

Level-3 Passwords. Care should be taken when changing the Level-3 password. If this new number is lost, it is not possible to enter programming/commission mode functions. Contact the factory for further information.

The factory default level 3 password is 7654

2.3.9 Panel The Panel Menu Option shows a list of the internal panel circuits and provides a means to change their default configuration settings.

Only use this menu if changes are to be made to the default settings for the panel’s internal circuits. Use the VIEW-PANEL Menu Option to view the state and operating condition of each circuit.

The display shows for example:

More>Address State Type Value >001.0 Normal VOLTAGE 5.6V 001.1 Normal VOLTAGE 5.6V 001.2 Normal CURRENT 5.6V 001.3 Normal CURRENT 5.6V

Use the buttons to scroll through the circuits. Use the buttons to view additional information. The zone and Output Group Assignments can be modified if required.

Page 26 of 30

3 The passwords can be further qualified using the PC-NeT CONFIG TOOL to provide permission / restriction to specific menu options. Refer to PC CONFIG TOOL Manual for further details.

Page 27: Honeywell Fire Control Panel Front Programming Instructions

2.3.10 PC Config The PC Link Option enables the connection of the PC-NeT Configuration Tool for retrieving configuration data from the panel and programming configuration data from a file on the PC.

For further information, refer to the PC-NeT Configuration Tool Manual.

2.3.11 Setup The Setup Options Menu enables the configuration of panel generic operating parameters. When the option is selected, the display shows a list of the available parameters. For example:

[Setup] THIS NETWORK NODE : . 0 . NEXT NETWORK NODE : 0 PANEL ZONE : 701 ONBOARD NACs : 2 Class B

Use the buttons to scroll through the list of options. The following will then be shown:

[Setup] SERVICE NUMBER : 5084539995 SERVICE DUE DATE : JAN 06 2011 10:00 TRACE LOGGING MODE : STANDARD More>DETECTOR BLINKING : NONE

2.3.11.1 Network This network node is set to 0 for a stand-alone non-networked panel. For panels in a networked application enter the required node number (i.e.: first network device = node 1, second = node 2, etc.) and next node number.

2.3.11.2 Panel Zone By default all the panel inputs are assigned to the Panel Zone. Alternatively the PC-NeT configuration tool allows individual inputs to have different zones if required.

2.3.11.3 ONBOARD NACs This is the programming area for the number of On Board NAC circuits and the circuit wiring type, Class A or Class B.

2.3.11.4 Service Number This Service Number is the telephone number that is shown on the status display whenever a trouble condition occurs. To change the number, press the ✔ button when the option is highlighted. The number is entered using the number buttons; refer to Section 2.1.5 for guidance on how to enter numbers.

2.3.11.5 Service Due Date The next service due date can be entered into the panel memory. When this date is reached, the panel will enter a trouble condition to alert the building owner that service is required. To change the due date, press the ✔ button when the option is highlighted. The display prompts for entry of the next service date. For example:

Page 27 of 30

Page 28: Honeywell Fire Control Panel Front Programming Instructions

[NEXT SERVICE DUE] TIME = 1-:-- AM DATE = 04/15/06 SAT APR 15 2006

Use the buttons to select between the time and date. Use the number buttons to enter the required time or date.

As soon as a new service date is entered, the panel will cancel any Service Due Trouble condition.

2.3.11.6 Trace Logging Mode The Trace Logging Option determines what type of information and to what level the information is stored in the Event Log.

There are three options:

STANDARD = Normal operating mode: logging alarm, trouble and warning conditions as they occur.

STANDARD + = Extended logging version of the standard operating mode where the removal of trouble and warning conditions are also logged.

DIAGNOSTIC = Full diagnostic logging of all conditions with greater depth to aid diagnosis of trouble conditions.

To change the option, press the ✔ button.

To erase the event log, press the button to view the additional command option as follows:

[Setup] TRACE LOGGING MODE : Erase Event Log DETECTOR BLINKING : GROUND MONITORING : DACT :

Press the ✔ button and the display will show that the event log is being erased by displaying the message “WORKING…” After the event log is erased, the display reverts to the Set-up Options screen.

2.3.11.7 Detector Blinking The Detector Blinking option determines whether the LED indicators on the devices will blink whenever the panel polls the device. To change the operation, press the ✔ button. The display presents a list of options. For example:

[Setup]

INDIVIDUAL ALL NONE

Use the buttons to scroll through the list of options and press the ✔ button to confirm the selection.

The device LED indicators will not blink if NONE is chosen or will blink if ALL is chosen.

If a device is changed it may be necessary to select and reconfirm the blinking command so that the new device will blink it’s LED.

Page 28 of 30

Page 29: Honeywell Fire Control Panel Front Programming Instructions

The INDIVIDUAL option should be chosen when it is required that only certain devices should blink their LED. The devices that shall blink their LED can only be programmed using the PC-NeT Configuration Tool.

2.3.11.8 Ground Monitoring This parameter determines whether a Ground Trouble is shown on the display during normal operation. To change the setting, press the ✔ button. The status changes from ✔ to X and vice versa.

2.3.11.9 DACT Not Used

2.3.11.10 Resound Default is RESOUND ON NEW DEVICE IN ALARM. Option can be set for RESOUND ON NEW ZONE IN ALARM. To change the setting, press the ✔ button.

2.3.11.11 Program Version The display shows the part number and version of the software installed in the panel. The version number is in the format AxCTL-XXX-YY where XXX is the major version and YY is a minor revision. Press the button to see the program checksum (8 digits).

2.3.11.12 CONFIG Data The CONFIG Data option shows the loop protocol selected and the checksum for the configuration data. A note of this number can be taken and then checked on the next service visit to see if any changes have been made to the configuration data.

[Setup] CONFIG DATA :AFSI More>

To view the Config Data Checksum (8 digits), press the button.

In addition, there is an option to erase the Configuration Data and set the panel back to factory settings. Press the button and press the ✔ button. A pop-up window will request confirmation to erase the configuration.

Page 29 of 30

Page 30: Honeywell Fire Control Panel Front Programming Instructions

Page 30 of 30

3 Appendices

3.1 Appendix 1 – Forgotten Level 3 Password

Should the PROGRAM Level 3 Password be forgotten, contact AFSI to obtain a temporary password number to regain access to the panel programming functions.

Customer Support will require a decryption key displayed by the panel. To obtain this number, attempt to gain access to the Programming Functions entering “1” when prompted for the password. As soon as the “Password Invalid” message is shown, press the “0” button and the display will show a decryption key. Make a note of the first part of this number.

For example:

[Level 2 Menu]

Please Enter Your Password 214728378

Customer Support will provide a temporary permit number that you can enter when prompted for the password. As soon as access has been regained to the Programming Functions, select the Passwords Menu Option and check / change the PROGRAM password. (Refer to Section 2.3.8 for further information).

Document Number: 682-002 [AEL] Revision: 01

34 Moorland Way, Nelson Park, Cramlington, NE23 1WE Tel: +44 1670 707 111 Fax: +44 1670 707 222 www.advel.co.uk Email: [email protected] ISO9001

R

MEMBER

ISO9001