EXTREME 200, 300 & 500 HIGH EFFICIENCY HOT WATER SYSTEMS wi th INJECTION DYNAMICS
H I G H E F F I C I E N C Y H O T W A T E R S Y S T E M S
extreme
I N T R O D U C T I O N
C O N T E N T S
Renowned for developing innovative products, Mikrofill has built its success
on quality, reliability and outstanding customer service.
Our rapidly expanding range of products include commercial condensing
boilers, hot water loading systems and pressurisation equipment.
Mikrofill’s hot water loading systems have been developed specifically to meet
the demands of modern commercial buildings. The Extreme is a domestic
hot water generator that combines the advantages of both an instantaneous
hot water heater and a storage system, creating perfect harmony between
a condensing boiler and a hot water cylinder.
Extreme 200, 300 & 500 4 -5
Technical Data 6
Dimensions 7
Efficiency Data 8 - 9
Example Installation 10
Ancillaries 11
H I G H E F F I C I E N C Y H O T W A T E R S Y S T E M S
extremeThe Extreme principle addresses and overcomes all of the disadvantages of the traditional coil type cylinder, whilst remaining simple and straightforward to install. In addition the operating principle ensures the efficiency of a condensing boiler is optimised during the production of domestic hot water.
Mikrofill’s uncompromising approach to quality materials, design flexibility and engineeringexcellence has resulted in the Mikrofill Extreme, the new standard in hot water generation.
Exceptional flow rates in excess of 2500 litres an hour at 60ºC
4
I N J E C T I O N D Y N A M I C S
Introducing ‘INJECTION DYNAMICS’, a breakthrough in domestic hot water technology. By utilising this revolutionary method of heating, the Extreme generates hot water faster, cleaner and more efficiently than ever before.
F E AT U R E S●Stainless Steel construction.
●Fully insulated, in excess of all current standards.
● Suitable for unvented and open vented systems.
●Available in 200, 300 and 500 litre versions.
●Maximum primary input of 120kw.
B E N E F I T S●Exceptional flow rates – up to 2570
litres an hour at 60°C.
●Injection dynamics – allowing hot water draw off in minutes.
●Optimises boiler cylinder efficiency – up to 94% with a condensing boiler.
●Positive stratification – greatly reduces the risk of Legionella proliferation.
●Design principle achieves 100% of cylinder capacity at 60°C enabling reduced storage requirement.
5
MODEL extreme 200 extreme 300 extreme 500
WEIGHT (EMPTY) 63kg 77kg 98kg
MAX WORKING PRESSURE 10 bar 10 bar 10 bar
MAX PRIMARY TEMPERATURE 90ºC 90ºC 90ºC
DHW FLOW CONNECTION 1” 1 1/4” 1 1/2”
DHW RETURN CONNECTION 1” 1” 1”
PRIMARY FLOW & RETURN CONNECTIONS 28mm 28mm 28mm
MCWS CONNECTION 1” 1 1/4” 1 1/2”
P&T VALVE SETTING 7 Bar & 90ºC
STANDING THERMAL LOSS 155 MJ per month 197 MJ per month 364 MJ per month
GLOBAL WARMING POTENTIAL 0 0 0
H I G H E F F I C I E N C Y H O T W A T E R S Y S T E M S
T E C H N I C A L D A T A
extreme 2 0 0 , 3 0 0 & 5 0 0
6
D I M E N S I O N S
2 0 0 , 3 0 0 & 5 0 0
A B
C
H
D
E
F
G
extreme 200 extreme 300 extreme 500
A 380mm 910mm 910mm
B 280mm 810mm 810mm
C 465mm 465mm 570mm
D 735mm 1260mm 1265mm
E 995mm 1530mm 1510mm
F 1305mm 1830mm 1810mm
G 710mm 710mm 735mm
H 300mm 300mm 300mm
DHW Flow
DHW Return
MCWS
Htg Return
Htg Flow P&T VALVE CONNECTION
7
H I G H E F F I C I E N C Y H O T W A T E R S Y S T E M S
extreme
10 min peak output @60°C
1st Hour continuous operation @60°C
extreme 500
extreme 300
extreme 200
All graphs are calculated using a 30º⁰∆T primary temperature.
litres per hour
2600
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
50030 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Heat Input kW
litres
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
20030 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Heat Input kW
8
F L O W C H A R A C T E R I S T I C S
Primary Flow Characteristics for the Extreme 200, 300 and 500
Primary Flow Rate
Continuous operation @60°C for the Extreme 200, 300 and 500
Primary Resistance
litres per hour
2100
2000
1900
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
030 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
Heat Input kW
All graphs are calculated using a 30º⁰∆T primary temperature.
litres per second kPa
1.0 50
0.9 45
0.8 40
0.7 35
0.6 30
0.5 25
0.4 20
0.3 15
0.2 10
0.1 5
030 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
0
Primary Heat Input kW
9
H I G H E F F I C I E N C Y H O T W A T E R S Y S T E M S
extreme
A schematic drawing of an Ethos wall mounted boiler installation, including a Mikrofill pressurisation package connected to an Extreme domestic hot water loading system.
IVIV IV
CondenseWaste
MIKROFILL
ExpansionVessel
LSV DOC
AAV
Heating Circuit
Mains/Boosted Cold Water Supply
DOC
IV
ServiceValve
ETHOS Boiler
ETHOSBoiler
MIK
ROVE
NT
10
E X T R E M E A N C I L L A R I E S
The Extreme is suitable for installation on both open and unvented domestic hot water systems and comes complete with a preinstalled pressure and temperature relief valve.
The unvented kit supplied includes the following items and is designed to work in conjunction with each Extreme cylinder.
●35 litre potable expansion vessel
●Pressure reducing valve (3.5 bar limit)
●Safety relief valve and tundish
●Check valve
●28mm 2 port valve (to provide a permanent means of isolation to the primary supply)
In addition each cylinder can be ordered with a factory fitted 3kW immersion heater.
11
Please note:- when operating on an “open vented” system additional filtration will be required.
Mikrofill Systems Ltd.11 Merse Road, North Moons Moat, Redditch, Worcestershire B98 9HL
T +44 (0)3452 60 60 20 F +44 (0)3452 60 60 21 E [email protected] www.mikrofill.com