how to reduce water & energy consumption in a cooling...

73
How to Reduce Water & Energy Consumption in a Cooling Tower? Gerry Van den Eynde Area Sales Manager

Upload: others

Post on 12-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

How to Reduce Water & Energy

Consumption in a Cooling Tower?

Gerry Van den Eynde – Area Sales Manager

Page 2: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

• Introduction

• History

• Product Lines

Agenda

Page 3: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Regional Energy Consumption

77% energy consumption

▪ Buildings

70% buildings energy

▪ Cooling

Page 4: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Madera Milford

Baltimore

South Africa

Italy

Belgium

Australia

Wholly owned (11)

Joint Ventures (1)

China Japan

Malaysia

Headquarter (1)

Korea

Licensees (1)

Global facilities & partners

Russia

UAE

India

Page 5: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

BAC Middle East Region Organization

5

15x direct BAC employees

35 x BAC representative employees

ME Sales (new projects)

ME After-Market (new & installed equipment)

Page 6: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Technology commitment

+100 patents technology

innovation.5000 m² R&D & test facility.

> 40 engineers

Page 7: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

1940 1960

Factory assembled evaporative condensers

and cooling towers

Industrial fluid coolerreplacing cooling

tower with heat exchanger

HISTORY

1980

Corrosion protectionmore than hot-dipgalvanized steel

Axial fan forced draftcounterflow coolers

or condensers

New coil and waterdistribution system design

1950 1970

Page 8: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

1980 1990

Baltibond CorrosionProtection System

Finned coilsDry operation

Ice thermal storage units

BACcount fill

HISTORY

2000

Combined flow technology – coil on fill

HXI hybrid cooler

Eurovent certification

Page 9: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

2000 2010

TrilliumSeriesAdiabatic coolers

Water saving evaporativecondensers - HXC

HFL - Water savingevaporative coolers

with remotecold water basin

Heat exchanger skid

HISTORY

New generationBaltibond hybrid coating

Eurovent certificationOpen cooling towers

CO2 condenser

Page 10: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

2015

HISTORY

OptiCoil PFI

Eurovent certificationClosed circuitcooling towers

TrilliumSeriesTVFC

Adiabatic cooler

2017 2018

NexusTM

Modular

hybrid cooler

PolairisTM

Evaporative

condenser

Page 11: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Product Line

Page 12: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Open

cooling towers

Water saving

hybrid wet-dry

BAC extensive product line

Closed circuit

Cooling towers

Thermal

storage units

Evaporative

condensers

Page 13: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Centrifugal fans

VT 0/1 VTL-E

Series 3000E Series 1500E PTE

Axial fans

Open Cooling towers

Page 14: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Centrifugal fans

Axial fans

VXI VFL

FXVS FXVTPFI

Closed circuit Cooling Towers

! NEXUS !

Radial fans

Page 15: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Axial fans

HXITrilliumSeries CoolerDFC SpartiumCooler

HFL VXI + PAC+ 3-way valve

Centrifugal fans

Dry ,Adiabatic and hybrid cooling

Page 16: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Axial fans

Centrifugal fans

VXC VCL

CXVE CXV-D PCE

Refrigerant Condensers

Radial fans

POLAIRIS

Page 17: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

How to Reduce Water & Energy

Consumption in a Cooling Tower?

Jai Kawrani - Application Manager

Page 18: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Agenda

Ways to Reduce Energy Consumption

• System Optimization

• Innovative Technologies

• System Efficiency & Reliability

Ways to Reduce Water Consumption

• Water Usage & Chemistry

• Cycle of Concentration & Bleed

• Advanced Materials of Construction

Value Pack

Page 19: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Industry Standards Evaluation

Page 20: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Owners Reduce Total Cost of Ownership

• More Energy Efficient Products Required

• Lower Operating Expenses

• Global Energy Codes and Regulations

Innovative Building Design and Operating Strategies

New Technologies

HVAC Industry Evolving

Page 21: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

ASHRAE 90.1-2013

Equipment Type 2010 Performance

Required

2013 Performance

Required

Open Loop Axial Fan

Cooling Towers

≥ 38.2 gpm/hp ≥ 40.2 gpm/hp

5% rating increase from 2010 to 2013 for Axial Fan Units

Page 22: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Ways to Reduce Energy Consumption

Page 23: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

System Optimization - Design for Lower Approach

Tower / Chiller Optimization

Reduce Approach

• Optimize Tower and Chiller Sizes with Energy Cost Estimates

• At least 2.5% Reduction in Energy Use per degree below 90°F

Page 24: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Range and Approach

Cooling Tower Controls the Approach

500 Ton Cooling Tower @ 1,500 gpm, Full Fan

• 95/85/78 (10 degree range) = 7.0°F Approach

• 102.6/87.6/78 (15 degree range) = 9.6°F Approach

• 86.8/81.8/78 (5 degree range) = 3.8°F Approach

› Reduces energy usage by 10%

Closer Approaches

• Colder condenser water increases higher efficiency

Page 25: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Chiller and Cooling Tower System Optimization

First Cost Energy Cost

Cooling Tower ✓ ✓

Chiller ✓ ✓

Pump ✓ ✓

Condenser Water Piping ✓

Page 26: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Innovative Technology

Page 27: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Innovative Design Methods

EXTREME EFFICIENCY COOLING TOWERS

2 x the ASHRAE 90.1 energy ratings

HOW TO SELECT

• Increase heat transfer surface area

• Reduce CFM and HP

• Compare ASHRAE 90.1 GPM/HP ratings

EXAMPLE: 500 nom. tons (1,500 gpm 95/85/78)

• Model S3E-1020-07P, 40 HP fan motor

• Model XES3E-1424-07M, 20 HP fan motor

Page 28: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

500 TON SELECTION COMPARISON

Inputs:

• $0.12 / kW

• 2,500 hours

• 20 years

Series 3000 Cooling Tower

Page 29: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Extreme Efficiency Cooling Towers

Lowers operating cost

• Typical Payback in less than 2 years

• Energy reduction up to 75%

Reduced sound levels up to 5dB

Increases system reliability

• Less wear and tear on mechanicals

Helps contribute to energy and atmosphere LEED® credits

Page 30: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Innovative Technologies

Page 31: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

DIRECT DRIVE

• Highest reliability

• Superior energy

savings

• Lowest maintenance

costs

• Lowest total cost of

ownership

BE

ST

Drive System Selection Guide

GEAR DRIVE BELT DRIVE

• Common for larger

HP applications

• Highest maintenance

costs

• Highest potential for

downtime

• Proven and most

popular for HVAC

applications

• Quick service, lower

maintenance costs

GO

OD

BE

TT

ER

Both belt and gear have mechanical losses

Page 32: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Unmatched Reliability

• No misalignment issues

• No transmission components to fail

90% Reduction in Maintenance

• Up to 7 years between maintenance

• No more oil changes

Increased Thermal Performance

Page 33: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Direct Drive Technology

10% ENERGY SAVINGS

• No losses from Gears and Couplings

• No degradation over time

OPERATED BY VFD

• Additional Energy Reduction

Noise Elimination from Conventional Gear Drive Systems

Page 34: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

When to Consider Direct Drive

• Loss of Maintenance Staff

• Need More Capacity

• Eliminate Gear Misalignments

• Reduce Vibration Levels

Page 35: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

$750,000

$780,000

$810,000

$840,000

$870,000

$900,000

$930,000

$960,000

GEAR ENDURADRIVE FAN SYSTEM

TOTAL COST OF OWNERSHIPOver 20 Year Life

Energy Labor Materials

Direct Drive - TCO Analysis

*100 HP motor, $0.12 per kWh, 2,500 equivalent full-load hours, $10 per kW demand charge

GEAR DriveFan System

$118,927

Savings

Page 36: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Dubai Airport Free Zone Authority

Before After

Page 37: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Gloria Hotel, Dubai

Before After

Page 38: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Innovative Technologies

Page 39: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Ice Thermal Storage System

Page 40: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

System Efficiency & Reliability

Page 41: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

System Efficiency and Reliability

OPEN SYSTEM CHALLENGES

Fouling reduces efficiency, increases operating costs

Page 42: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

OPEN

COOLING TOWER

OPEN COOLING TOWER

+

CLOSED HEAT EXCHANGER

CLOSED CIRCUIT

COOLING TOWER

Water outlet =

Twb + Approach

Water outlet =

Twb + Approach + Δ THX

Water outlet = Twb + Approach

Page 43: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Closed Circuit Cooling Tower Advantages

Reduced fouling minimizes:

• Maintenance costs, energy costs, downtime

Can eliminate need for heat exchanger:

• Simplifies system

• Reduces installation cost

Greater layout and operation flexibility

Page 44: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Ways to Reduce Water Consumption

Page 45: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Water Usage in Cooling Towers

Drift

Evaporation

Blow Down

Blow down (via Cycles of Concentration) is the only significant

variable to control in Cooling Towers for reducing Water Usage

Page 46: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Total Water Usage in Cooling Towers

Evaporation66%

Blowdown33%

Drift1% Evaporation

83%

Blowdown16%

Drift1%

3 Cycles

(~2.7 gallons/ton)

6 Cycles

(~2.2 gallons/ton)

Cycles Gallons / Ton Evaporation Blowdown Drift

3 2.7 1.8 0.9 0.02

6 2.2 1.8 0.4 0.02

Page 47: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Water contains impurities

MINERALS

AIR

EARTH

CalciumMagnesium

SodiumIron

Oxygen

CarbonMonoxide

CarbonDioxide

Clay

Silt

Sand

Dissolved solids Dissolved gases Suspended matter

Page 48: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Critical Water Chemistry data

Total Dissolved Solids (TDS)

• Ca, Mg, Na, iron,..

• Measured by the Conductivity

Hardness (TH)

• Ca & Mg ions dissolved in water

• Typical Measure: Total Hardness

Alkalinity (TAC)

• Carbonate (CO3) or Bicarbonate (HCO3)

Chlorides and Sulfates

• Salts can be corrosive to metals at high levels

pH

Page 49: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Impact of Bleed on Cycle of Concentration

Constant Evaporation

6

5

4

3

2

1

6

5

4

3

2

Constant Evaporation

With Zero Bleed With Continuous Bleed

Maintaining Set Cycles

Tim

e >

Tim

e >

Solids build up

over time

Solids levels stay

balanced with

proper bleed

Page 50: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Cycles of Concentration vs Blow Down

Cycles of Concentration

Blow Down

/ Evap. Loss

EXPENSIVE0

1

2

3

4

5

6

7

1 2 3 4 5

CRITICAL

Page 51: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Advanced Materials of Construction

Page 52: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

• G235 Galvanized Steel : Low Cost / Higher Water Usage

• Special Hybrid Polymer Protection : Value for money / Less Water Usage

• Water Touched Stainless Steel: Medium Cost / Less Water Usage + High

protection to Chlorides

• Stainless Steel: High cost / Less Water Usage + Highest resistance against

Chlorides

• Evertough : Less Water Usage + Ultra strong & corrosion resistant basin

construction

Materials of Construction

Page 53: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Sump + Frame :

G235 with Special Hybrid Polymer

Casing : FRP

G235 with Special Hybrid Polymer + FRP

+ Less Water Usage

+ Value for money

+ Light Weight, Corrosion & UV resistant Casing

+ Equivalent to SS304 Water Usage

Page 54: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Baltibond Hybrid Coating

Page 55: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Frame :

G235 with Special

Hybrid Polymer

Casing :

FRP

Basin :

SST

Water touched Stainless Steel

+ Less Water Usage

+ High protection to Chlorides

- Medium Cost

Page 56: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Frame :

SST

Casing :

FRP

Sump : SST

Full Stainless Steel

+ Less Water Usage

+ High resistance against Chlorides

- High Cost

Page 57: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Stainless Steels: Differences Matter

301

304

316

Page 58: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Stainless Steels: Differences Matter

Page 59: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Stainless Steels: Differences Matter

Page 60: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

304 vs 316 at 30 deg C

316SS

Limits

304SS

Limits

Page 61: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

EVERTOUGH™ Construction

TriArmor® Cold Water

Basin

FRP Casing Panels

FRP Air Intake

Louvers

PFRP Hot Water

Basin with

Type 304 SST

Covers

Thermosetting Hybrid Polymer

Protected Structural Members

Strainer and other Submersible

Components are Constructed of 304 SST

+ Less Water Usage

+ Ultra strong construction

+ Strongest Cold Water Basin

Page 62: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Advanced Materials of Construction

• Thousands of Installations

• Eliminates Basin Leaks

• Protects Basin Surfaces

from corrosion and system

upsets

• Reduce Water usage

1. G-235 Heavy Galvanized

Steel

2. Thermosetting Hybrid

Polymer

3. Impermeable

Polyurethane Barrier

Page 63: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Galvanized Steel

2.35 oz of zinc/sq ft

2.35 oz of zinc/sq ft

Thermosetting Hybrid Polymer

Thermosetting Hybrid Polymer

Polyurethane Barrier

The Cold Water Basin

The TriArmor® Corrosion Protection System

Page 64: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Average Cold Water Basin Price

Page 65: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Material of construction = Water Quality & Water Consumption!

Page 66: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Value Pack

Page 67: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Cooling Towers are ‘Air Washers’!

Page 68: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Filtration Package & Sump Sweeper Piping

Sump Sweeper Piping

+ Matching Separator

THE

PERFECT

COMBINATION

Page 69: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Cyclonic Separator

Page 70: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Increased Water Agitation

Improved Filtration

Performance

Less Suspended Solids

Less Biological Growth

Sump Sweeper Piping

Page 71: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Automatic Dosage => BCP 3 D

• Minimize Water Usage

• Allow Consistent Water Quality

• Appropriate Dosage of Inhibitor - 1 & Biocides - 2

BCP Water Treatment Control Package

Page 72: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Product with

Innovative

Technology

Advanced

Material of

Construction

Expert

Maintenance

Services

Water

Treatment

Control

Package

Filtration

Package

Sump Sweeper

Piping

1 2

3

4

5 6

Page 73: How to Reduce Water & Energy Consumption in a Cooling Tower?ashraeqatar.org/uploads/3/4/5/4/34547927/how_to_reduce_energy__… · tower with heat exchanger HISTORY 1980 Corrosion

Q&A