Section 14: Technical Specification for AC HT cables, LT Power Cables, DC Power cables and control cables, cable racks, supports, trays & accessories. Sr.No . Clause Comments of SJVN Replies after receipt from WAPCOS 1 14.1.1 (iii) As per tender drawing SLD, 11kV System is not provided at Dam site, in such case, requirement of 11kV Aerial Bunch cable (ABC) at Dam Site may be clarified. Ok. Kindly modify the relevant clause. 2 14.5.2 & 14.5.3 Armoring for cables has been elaborated in clause 14.3.7 but in these clauses the choice of Armoured/ unarmoured has been provided. Contradiction may be clarified. Ok. Kindly modify the relevant clause. 3 14.6.3 The incorporation of text as ‘In addition, “THPA- Bhutan” shall also be printed at every 3 meter run’ may be clarified. Ok. Kindly modify the relevant clause. 4 14.8 The supporting document shall be submitted for proposing the various kind of test to be performed for cables to be supplied. It is required to kindly submit the relevant standard. 5 14.10.4 As per the TS clause 14.4.1.3 straight through cable joints are to avoided whereas special clause has been elaborated for straight through cable joints, contradiction in the clauses shall be clarified. Ok 6 14.14 The necessity of this clause Ok. Kindly modify 1

Upload: balwantnegi7520

Post on 10-Dec-2015

213 views

Category:

Documents


0 download

DESCRIPTION

gf

TRANSCRIPT

Page 1: HT_LT Cables

Section 14: Technical Specification for AC HT cables, LT Power Cables, DC Power cables and control cables, cable racks, supports, trays & accessories.

Sr.No. Clause Comments of SJVN Replies after receipt from WAPCOS

1 14.1.1 (iii) As per tender drawing SLD, 11kV

System is not provided at Dam site, in

such case, requirement of 11kV Aerial

Bunch cable (ABC) at Dam Site may

be clarified.

Ok. Kindly modify the

relevant clause.

2 14.5.2 & 14.5.3 Armoring for cables has been

elaborated in clause 14.3.7 but in

these clauses the choice of Armoured/

unarmoured has been provided.

Contradiction may be clarified.

Ok. Kindly modify the

relevant clause.

3 14.6.3 The incorporation of text as ‘In addition, “THPA- Bhutan” shall also be printed at every 3 meter run’ may be clarified.

Ok. Kindly modify the relevant clause.

4 14.8 The supporting document shall be

submitted for proposing the various

kind of test to be performed for cables

to be supplied.

It is required to kindly

submit the relevant

standard.

5 14.10.4 As per the TS clause 14.4.1.3 straight

through cable joints are to avoided

whereas special clause has been

elaborated for straight through cable

joints, contradiction in the clauses

shall be clarified.

Ok

6 14.14 The necessity of this clause i.e.

WASTAGES shall be clarified as

bidder to provide all item in this

specification for completeness of

system.

Ok. Kindly modify the TS

accordingly.

7 14.21 (i) Schedule of Requirement envisages

optical fiber cable but there is no

clause in the specification & its usage.

Same shall be clarified.

It is required that the usage

and its specification shall be

added in the Technical

specification.