Slide 1
HVAC Systems
AP1000 Chilled Water System
Slide 2
Central Chilled Water SystemVWS Design Basis
– Containment Isolation: Safety-related, seismic, ASME III, 1E– Provides 40°F chilled water – VWS air-cooled chillers shall be designed for operation using
outdoor air with a maximum summer design temperature of 115°F dry bulb / 85.5°F wet bulb and a minimum winter design temperature of -40°F based on 0% exceedance
– VWS water-cooled chillers are designed for stable operation using Component Cooling Water System (CCS) water with a temperature range of 60 to 95°F.
Slide 3
Central Chilled Water System Sketch – High Capacity Subsystem
Slide 4
Central Chilled Water SystemSketch – Low Capacity Subsystem
Slide 5
Containment Recirculation System
Slide 6
Containment Recirculation System
Ductwork and Fan Coil Units
Slide 7
HVAC Systems – Containment Filtration
4,000 CFM EXHAUST UNIT A
4,000 CFM EXHAUST UNIT B
FUEL HANDLINGAREA
AUXILIARYBUILDING
ANNEXBUILDING
OUTSIDE AIR
OUTSIDE AIR
PLANTVENT
R
R
M C R
16"
36"36"
16"16"
4,000 CFM SUPPLY AHU A
OUTSIDE AIR
16"4,000 CFM SUPPLY AHU B
OUTSIDE AIR
CONTAINMENT
36" 36"
ILR
T
Slide 8
Radiologically Controlled Area Ventilation System
Fuel Handling Area Subsystem
50% CAPACITY
ELEVATORMACHINE
FUEL HANDLING AREA
RE50% CAPACITY SUPPLY AHU A
50% CAPACITY SUPPLY AHU B
INT
AK
E P
LE
NU
M
ROOM
RAILCAR BAY/FILTERSTORAGE AREA ANDSPENT RESIN ROOMS
OA
OA
EXHAUST FAN A
50% CAPACITYEXHAUST FAN B
PLANT VENT
VFS FILTEREDEXHAUST
Slide 9
Radiologically Controlled Area Ventilation System (VAS)
Aux/Annex Building Subsystem
50% CAPACITY
RE
50% CAPACITY SUPPLY AHU A
50% CAPACITY SUPPLY AHU B
INT
AK
E P
LE
NU
M
CONTAINMENTSTAGING AREAS
AND ADJAENT ROOMSOA
OA
EXHAUST FAN A
50% CAPACITYEXHAUST FAN B
PLANT VENT
VFS FILTEREDEXHAUST
AUXILIARYBUILDING
TO SUIT DUCT LAYOUT
VFS FILTEREDEXHAUST
ANNEXBUILDING RE