hvac vav select-ash

Upload: mohdnazir

Post on 03-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 HVAC Vav Select-Ash

    1/61

    Selecting VAV Terminals for

    Acceptable IAQ

    Selecting VAV Terminals for

    Acceptable IAQ

    Dan Int-HoutChief Engineer, Krueger

    Richardson, Texas

  • 7/28/2019 HVAC Vav Select-Ash

    2/61

    Where We Are Today:

  • 7/28/2019 HVAC Vav Select-Ash

    3/61

    The Rules

  • 7/28/2019 HVAC Vav Select-Ash

    4/61

    Air Distribution Device

    Selection Guidelines The ASHRAE fundamentals handbook, chapter 20 (Air

    Distribution), provides guidance on several methods of air

    distribution. Additional guidance can be found in the recently updated Air

    Distribution sections in Applications and SystemsHandbooks.

    Air distribution methods include overhead fully mixed, as well

    as fully stratified and partially mixed systems from below, andeven task /ambient personal air delivery systems.

    Described delivery systems include constant and variablevolume, UFAD, displacement ventilation and chilled beamsystems.

    All have advantages and disadvantages, which must beunderstood by the design engineer and architect.

  • 7/28/2019 HVAC Vav Select-Ash

    5/61

    Air Distribution Device

    Selection Guidelines

    For overhead well mixed systems, one should select a unitwith throw at max, and minimum, flow that meets ADPI

    guidelines based on diffuser spacing and T50 (throw to 50fpm).

    Additionally, select for maximum mixing: Noise can be good. Dirt on the ceiling is not bad.

    Air Distribution Effectiveness (ADE) is a new termdescribing room air mixing, and is a parameter with alldelivery methods.

    There is increasing evidence that typical loads in buildingsare far below those that used to require 1 cfm/sf in the past.

    I suspect most spaces only require about 0.4 cfm/sf, or less. Good design will require fewer diffusers, further apart, in

    order to provide adequate performance at these lower airflow rates.

  • 7/28/2019 HVAC Vav Select-Ash

    6/61

    Air Distribution, Poor Pattern

    Example

    THERMOSTAT

    POORLY ADJUSTED / SELECTED DIFFUSER

  • 7/28/2019 HVAC Vav Select-Ash

    7/61

    PROPERLY ADJUSTED DIFFUSER

    THERMOSTAT

    Good Pattern Example

  • 7/28/2019 HVAC Vav Select-Ash

    8/61

    Perforated 24X24, 10 inlet, 4 way, 20 Delta-T

    2

    4

    6

    8

    10

    12

    14

    16

    0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

    CFM/Sq.Ft.

    1/2UnitSepara

    tionDistance

    420

    350

    300250

    160

    Range

    Spacing for 80% ADPI

    NC=35

    CFM

  • 7/28/2019 HVAC Vav Select-Ash

    9/61

    ADPI and LEED Standard 55 requires air speed 80%, roomaverage air speed will be < 40fpm, andvertical stratification will be

  • 7/28/2019 HVAC Vav Select-Ash

    10/61

    ADPI and LEED

  • 7/28/2019 HVAC Vav Select-Ash

    11/61

    THERMOSTATCold

    Outside

    Window

    Common Overhead Heating Design

  • 7/28/2019 HVAC Vav Select-Ash

    12/61

    Perimeter Considerations:

    Maximum delta-t for effective mixing when heating,per ASHRAE handbook = ?.

    = 15F (90F discharge), continuous operation.

    Throw toward and away from glass.

    150 FPM should reach 4-5 feet from the floor.

    ASHRAE 62.1 requires that ventilation be increasedby 25% when heating, if the above rules are notfollowed.

    Typical perimeters require only 8F

    delta-t @ 1 cfm/sq.Ft.

  • 7/28/2019 HVAC Vav Select-Ash

    13/61

    Air Distribution Summary Diffuser selection should be based on throw and

    room size.

    Select at both max and minimum occupied flowrates. Rates are likely less than 0.5 cfm/sf.

    Noisy diffusers are good.

    Dirt on the ceiling aint all bad.

    Use good design when heating.

    Poor air distribution yields poor comfort, poor airquality, slow system response.

  • 7/28/2019 HVAC Vav Select-Ash

    14/61

    Thermal Comfort:

    Latest THERMAL COMFORT STANDARD:

    ASHRAE 55-2010 ASHRAE Fundamentals, Chapter 7

    PMV - predicted mean vote - a single number

    rating. Standard 55 mandates a maximum 5oF vertical

    temperature stratification.

    A program is available, based on a programlisting in ASHRAE 55, which allows plotting ofthe comfort envelope.

  • 7/28/2019 HVAC Vav Select-Ash

    15/61

    Graphical Method, ASHRAE 55-2010

  • 7/28/2019 HVAC Vav Select-Ash

    16/61

    Typical Executive Worker

    Profile

  • 7/28/2019 HVAC Vav Select-Ash

    17/61

    ASHRAE J ournal, J une 2008

    Comfort Economics

  • 7/28/2019 HVAC Vav Select-Ash

    18/61

    Design Issues:Diffuser Selection

    Perimeter

    Thermal Comfort

    Acoustics

    Ventilation & IAQ

    LEED 09 ASHRAE Std. 55 Checklist

  • 7/28/2019 HVAC Vav Select-Ash

    19/61

    Comfort Summary Thermal comfort is #1 reason for not renewing the

    lease (dont fix the wrong thing).

    Many IAQ and air distribution complaints can becured with temperature changes. The ratio of productivity to energy savings is

    2000/1. First costs are minor compared toproductivity.

    Internal heat loads cost 2X power consumption. Mandated designs and set points often waste

    energy. People will make themselves comfortable!

    Vertical Stratification requirement is often ignored Thermal comfort program available online!

  • 7/28/2019 HVAC Vav Select-Ash

    20/61

    Acoustics:

    AHRI 885-08 acoustical application standard.

    AHRI 880-08 air terminal test standard. AHRI 260-01 ducted equipment except air terminals.

    ASHRAE 70, air diffuser performance.

    Acoustical quality suggests the use of RC (or newer

    measures) rather than NC. Many acousticians areheading back to dBA!

    LEED 2012 will include acoustical credits andrequirements.

    A new ruling by AHRI will change everyonesdischarge sound ratings considerably.

  • 7/28/2019 HVAC Vav Select-Ash

    21/61

    End Reflection Low frequency sound traveling down a duct willpartially reflect back when encountering a rapid

    change in area. The smaller the duct, the greater the effect.

    It can be as much as 10dB at 125Hz. It is much

    less at higher frequencies. Since NC is usually set at 125Hz, reported NC

    can go up as much as 10NC.

    Most importantly, Specifying Engineers shouldbe modifying their discharge soundrequirements to reflect the new data.

  • 7/28/2019 HVAC Vav Select-Ash

    22/61

    End Reflection

  • 7/28/2019 HVAC Vav Select-Ash

    23/61

    End Reflection An end reflection happens when air travels from a main

    to a branch duct, and especially when it enters a flex

    duct connection. Another happens when a duct terminates at the room, at

    the diffuser.

    AHRI 885 includes one 8 end reflection in Appendix E.

    This change only affects reported discharge soundpower levels.

    Discharge sound is the same, but will be reported a bit

    louder. Engineers will need to update their discharge sound

    specifications.

  • 7/28/2019 HVAC Vav Select-Ash

    24/61

    Sound Specifications

    Should be based on clearly stated assumptions.

    Should reflect real project needs, not anymanufacturers data and use currently accepted

    application factors. Discharge sound specs need to be modified to account

    for the louder reported sound power.

    If duct lining is used requireNC shall be determinedin accordance with AHRI 885-08, Appendix E,otherwise specify octave band sound power.

    Over-silencing increases both initial costs andoperating costs, and may hinder proper IAQperformance.

  • 7/28/2019 HVAC Vav Select-Ash

    25/61

    Classroom Acoustics:

  • 7/28/2019 HVAC Vav Select-Ash

    26/61

    LEED 2012 Proposed criteria

    LEED for schools presently gives a point for soundlevels < 45 dBA (about 36 NC).

    For 2012, it is proposed that 40 dBA be aprerequisite, with a point for achieving 35 dBA.

    Instead of requiring resultant sound levels, the newcriteria says that calculated HVAC system noise

    shall not exceed the specified values, using eitherthe ASHRAE Handbooks (which are inadequate) orAHRI 885.

  • 7/28/2019 HVAC Vav Select-Ash

    27/61

    Indoor Air Quality

    Standing Standard ProjectCommittee 62.1

    Residential Committee is 62.2

    Current Standard is62.1-10, and all previous addendahave been incorporated (and nolonger available on the web).

    Several additional Addenda havebeen approved and more are inprogress.

    Addenda are now published 18months after the release of astandard.

  • 7/28/2019 HVAC Vav Select-Ash

    28/61

    Terminal Units

  • 7/28/2019 HVAC Vav Select-Ash

    29/61

    Single Duct

    Retro-Fit Dampers

    Bypass Dampers

    Dual Duct

    Parallel Fan Powered

    Series Fan Powered

    Terminal Units

  • 7/28/2019 HVAC Vav Select-Ash

    30/61

    The Construction Specifier,

    July 04

  • 7/28/2019 HVAC Vav Select-Ash

    31/61

    Single Duct Terminal Units

  • 7/28/2019 HVAC Vav Select-Ash

    32/61

    When to Use Single

    Duct Terminals

    Interior spaces Where only cooling is required. Heating not needed

    due to climate and heating from perimeter areas.

    Perimeter with reheat Cooling along outer walls with some small reheat on

    the coldest days.

    Interior with reheat to maintain ventilation minimums Only cooling is required but reheating for minimum

    airflows

    Supply return tracking Airflow measurement and control into and out of a

    laboratory space.

    Standard

    Single Duct

  • 7/28/2019 HVAC Vav Select-Ash

    33/61

    Retro-Fit Single Duct

    Terminals

    Retrofitting old terminal units. Mechanical constant volume dual duct dampers

    for high pressure systems replaced with roundunits for measuring and controlling airflow.

    Adding a control zone. Round units added to a round duct or square

    ones to a square duct to measure and controlairflow in a new occupied zone monitored with

    Tstat.

    Replacing VVT-type zone dampers

    replace existing high pressure, high velocity zone

    controlled units with low pressure VAV units.

    As a return damper Added to existing ductwork to measure and

    control leaving airflow as required from controls.

    Square Slip In Retro-Fit

    Round Retro-Fit

  • 7/28/2019 HVAC Vav Select-Ash

    34/61

    Dual Duct Terminal Units

    Wh t U D l D t

  • 7/28/2019 HVAC Vav Select-Ash

    35/61

    When to Use Dual Duct

    Terminals

    Perimeter Heating & Cooling

    Positive ventilation control (measuredventilation to the zone)

    Laboratories / Constant volume applications

    Supply / Return tracking

    Underfloor Air Conditioning Be sure you understand the mixing / control

    requirements

    Upstream vs. downstream flow sensing issues

    N Mi i D l D t

  • 7/28/2019 HVAC Vav Select-Ash

    36/61

    Non-Mixing Dual Duct

    No Mixing

    Two single duct Units J oined S&D Discharge

    Inlet Sensing Only

    Standard Dual Duct

    2 Single

    duct units

    Joining Strip

    Mi i D l D t

  • 7/28/2019 HVAC Vav Select-Ash

    37/61

    Mixing Dual Duct

    Attenuated Dual Duct

    May have inlet or total flowdischarge sensing

    Unequal inlet sizecombinations are available

    Many types of linings are

    available Mixing baffle can have up to

    20:1 Mixing Ratio. Typically have high minimum

    inlet pressure requirementPremium Dual Duct

  • 7/28/2019 HVAC Vav Select-Ash

    38/61

    Opportunities for Dual Duct

    Systems Dual Duct can meet the most stringent

    requirements for classroom acoustics, aswell as 90.1 requirements.

    Providing 100 OA (DOAS?) through oneinlet allows validation of ventilation rates

    Supplemental heating and even sensible

    cooling coils are being considered in somedesigns.

  • 7/28/2019 HVAC Vav Select-Ash

    39/61

    Fan Powered Terminal Units

    When to use fan powered

  • 7/28/2019 HVAC Vav Select-Ash

    40/61

    When to use fan powered

    terminals Originally designed for perimeter heating and

    cooling - to avoid reheat

    Constant volume applications have a fan nearthe discharge - series boxes

    Series Boxes provide relatively constantinterior sound levels and air flow rates and areoften used in interior zones.

    Because of energy concerns, the ECM motor

    has been employed in many applications. Texas A&M recently completed a study,

    donated to ASHRAE and AHRI at the summermeeting in Montreal, on Series vs. Parallel, andECM vs PSC motors.

  • 7/28/2019 HVAC Vav Select-Ash

    41/61

    The use of ECM motors can reduce the true energyconsumption of Fan Powered Terminals

    An ECM motor is a brushless DC motor, with an

    integral computer controlled inverter. At reduced rpm and load, an ECM motor can use as

    little as 60% of the watts of a standard Permanent Split/ Capacitor Start (PSC) motor

    An ECM motor can be programmed to be pressureindependent, resulting in true constant volumeperformance, easier balancing, and even DDC

    controlled performance.

    ECM Motors

  • 7/28/2019 HVAC Vav Select-Ash

    42/61

    Some Cautions, however:An ECM motor can add $350 to the purchase

    price of a Fan Powered Terminal.Power consumption CAN be greater than anequivalent PSC motor, and the connected load

    requirement is usually higher because of this.There are issues with the power factor of thesetypes of devices which may cloud true energy

    savings.

    ECM Motors

  • 7/28/2019 HVAC Vav Select-Ash

    43/61

    Series Fan Boxes

    SERIES FAN POWERED BOXES

    Fan is on discharge of unit - all air

    goes through the fan (primary airflowcannot exceed fan airflow)

    Fan runs at all times during occupancy

    Fan must be started before primary airis supplied.

    Note: there is no such thing as an anti-backward rotation device.

    Radiated sound is critical soundapplication factor

    Parallel Fan Boxes

  • 7/28/2019 HVAC Vav Select-Ash

    44/61

    Parallel Fan Boxes

    PARALLEL FAN POWERED BOXES

    Fan is in parallel with VAV damper Fan airflow independent of primary

    airflow

    Fan is essentially first stage of heat Backdraft damper is standard

    Discharge sound is criticalapplication factor

  • 7/28/2019 HVAC Vav Select-Ash

    45/61

    Texas A&M Study Results

    Data was generated for entire building

    systems, not just terminals. Parameters were developed for detailed

    full building energy analysis

    Results are being presented in ASHRAEPapers, and full study results have been

    donated to ASHRAE and AHRI.

  • 7/28/2019 HVAC Vav Select-Ash

    46/61

    Texas A&M Study Results

    The results showed that both system operation and climate had agreat effect on final energy use.

    In general, however there were a few important observations:

    ECM and PSC motors had the same building energy consumption withParallel boxes.

    Parallel boxes could be more efficient than series boxes, except forback-draft damper leakage, which was found to be very significant.

    Series boxes, with ECM motors, are the most energy efficient choice,

    (at least until someone develops a leak proof parallel box). Series Boxes, with DDC system variable volume fan flow, are likely

    more efficient than any other air distribution method, at low part loadoperation.

  • 7/28/2019 HVAC Vav Select-Ash

    47/61

    Electric Reheat Options

    120/208/240/277 single phase

    208/3 phase (3-wire), 480/3 phase (4-wire)

    1-3 Stages (most types) Side access - Leave clearance per NEC

    Operation at minimum airflow is unlikely to provide comfort

    Consider proportional electric heat with discharge temperature

    control for maximum comfort

    P ti l El t i R h t

  • 7/28/2019 HVAC Vav Select-Ash

    48/61

    There are two types of proportional electricheat:

    SCR Electric Heat Requires analog input

    Somewhat expensive

    Time Proportional Electric Heat 1 Stage only required

    Infinite adjustment

    Low cost

    Silent

    Allows for effective discharge temperature control

    Many different control inputs

    Proportional Electric Reheat

  • 7/28/2019 HVAC Vav Select-Ash

    49/61

    Dedicated Outdoor Air Systems

    DOAS D l D t

  • 7/28/2019 HVAC Vav Select-Ash

    50/61

    DOAS Dual Duct

    One inlet provides 100%outside air, dehumidified,typically cold.

    Other duct provides 100%return air, either warm or cold,depending on the season.

    Supplemental reheat coilsand even a sensible coolingcoil have been considered

    A good mixing baffle should

    be employed (20:1 MixingRatio recommended)

    Mixing Dual Duct

    Fresh Air Terminal Unit

  • 7/28/2019 HVAC Vav Select-Ash

    51/61

    Outside air can be supplied to a Series Fan Terminal through a secondducted system.

    This requires two duct systems, but separates ventilation andrecirculated air.

    The system allows monitoring of ventilation rates into each zone. A stand-alone Pressure Independent controller on the DOAS inlet,tied to the fan relay, will allow standard DDC zone controls.

    Fresh Air Terminal Unit

    PrimaryInlet

    Fresh Air Inlet

    Series FanPowered

    Terminal Unit

    Induced Air

    Inlet

    Chilled Fan Powered Terminal Unit

  • 7/28/2019 HVAC Vav Select-Ash

    52/61

    100% Outside air can be supplied to a Series Fan Terminal througha ducted system, designed to handle ventilation and latent loads.

    A sensible cooling coil, on the induced air inlet, cools plenum air foradditional sensible space cooling.

    The system allows monitoring of ventilation rates into each zone. A stand-alone Pressure Independent controller for the DOAS inlet,

    tied to the fan relay, will allow standard fan coil DDC zone controls.

    Both Series and Parallel designs are currently being used dependingon the installation.

    Chilled Fan Powered Terminal Unit

    DOAS Air Inlet

    Series Fan Powered Terminal UnitInduced Air Inlet

    Sensiblecooling

    coil

    Chilled Box In The Interior

  • 7/28/2019 HVAC Vav Select-Ash

    53/61

    C

    Sensible Cooling Coil

    Optional MERV 8 Filter

    Standard Ceiling Diffusers

    Series Fan Powered

    Terminal Unit

    Dedicated OutdoorAir Supply

    Standard Reheat Options

    Chilled Box at the Perimeter

  • 7/28/2019 HVAC Vav Select-Ash

    54/61

    Series DOAS Unit

    InteriorChilledBeams

    DOAS Air Supply

    Discharge Heating Coil

    Perimeter Slot Diffusers

    Chilled Parallel Box in a Laboratory

  • 7/28/2019 HVAC Vav Select-Ash

    55/61

    Lab Pressure Supply Valve

    Non Condensing Cooling Coil

    Optional Merv-8 Filter

    Laboratory Diffuser

    y

    Chilled Parallel Unit

  • 7/28/2019 HVAC Vav Select-Ash

    56/61

    Dedicated Outdoor Air Duct

    Active Chilled Beams

    Parallel DOAS Unit

    Secondary DOAS Duct

    Supplying Chilled Beams

    Chilled Box Summary

  • 7/28/2019 HVAC Vav Select-Ash

    57/61

    Chilled Box Summary

    Low first cost

    Low system pressure requirement Safe location possible

    Easily reconfigurable Minimal Contractor Training

    Guaranteed Performance

    Several LEED points possible

    S

  • 7/28/2019 HVAC Vav Select-Ash

    58/61

    Summary

    LEED 2009 requires meeting Standard 62.1 Documented use of ADPI is the ONLY way to assure

    compliance to 55 in the design phase.

    Acoustics should be specified on the basis of needwith clear assumptions. Use AHRI 885

    Reheat needs to be carefully considered in terms of

    discharge temperatures and velocities. Software is available to assist in selecting the best mixof products.

    The rules are dynamic - pay attention.

    Engineers Checklist

  • 7/28/2019 HVAC Vav Select-Ash

    59/61

    Engineer s Checklist

    Are Specifications current? Real Manufacturers

    Current Standards referenced Do we have clear acoustical requirements:

    Inlet Ps defined?

    Assumptions clearly defined?

    Reheat: Sufficient airflow? Discharge Static?

    3 or 4 wire 480V? Contactors? Stages?

    gpm or btuh? (pick one)

    Linings are acoustics and cost understood?

    Accessories Transformers?

    Filters?

    Hanger brackets?

    Fuses, Disconnects?

    If specified

    clearly, you mayget what youwant!

    If unclear, youwill get what thelow bidder wants

    you to get.

  • 7/28/2019 HVAC Vav Select-Ash

    60/61

    ANY QUESTIONS?

  • 7/28/2019 HVAC Vav Select-Ash

    61/61

    Contact

    [email protected]

    www.krueger-hvac.com

    EXCELLENCE IN AIR DISTRIBUTION

    KRUEGER