hvac vav select-ash
TRANSCRIPT
-
7/28/2019 HVAC Vav Select-Ash
1/61
Selecting VAV Terminals for
Acceptable IAQ
Selecting VAV Terminals for
Acceptable IAQ
Dan Int-HoutChief Engineer, Krueger
Richardson, Texas
-
7/28/2019 HVAC Vav Select-Ash
2/61
Where We Are Today:
-
7/28/2019 HVAC Vav Select-Ash
3/61
The Rules
-
7/28/2019 HVAC Vav Select-Ash
4/61
Air Distribution Device
Selection Guidelines The ASHRAE fundamentals handbook, chapter 20 (Air
Distribution), provides guidance on several methods of air
distribution. Additional guidance can be found in the recently updated Air
Distribution sections in Applications and SystemsHandbooks.
Air distribution methods include overhead fully mixed, as well
as fully stratified and partially mixed systems from below, andeven task /ambient personal air delivery systems.
Described delivery systems include constant and variablevolume, UFAD, displacement ventilation and chilled beamsystems.
All have advantages and disadvantages, which must beunderstood by the design engineer and architect.
-
7/28/2019 HVAC Vav Select-Ash
5/61
Air Distribution Device
Selection Guidelines
For overhead well mixed systems, one should select a unitwith throw at max, and minimum, flow that meets ADPI
guidelines based on diffuser spacing and T50 (throw to 50fpm).
Additionally, select for maximum mixing: Noise can be good. Dirt on the ceiling is not bad.
Air Distribution Effectiveness (ADE) is a new termdescribing room air mixing, and is a parameter with alldelivery methods.
There is increasing evidence that typical loads in buildingsare far below those that used to require 1 cfm/sf in the past.
I suspect most spaces only require about 0.4 cfm/sf, or less. Good design will require fewer diffusers, further apart, in
order to provide adequate performance at these lower airflow rates.
-
7/28/2019 HVAC Vav Select-Ash
6/61
Air Distribution, Poor Pattern
Example
THERMOSTAT
POORLY ADJUSTED / SELECTED DIFFUSER
-
7/28/2019 HVAC Vav Select-Ash
7/61
PROPERLY ADJUSTED DIFFUSER
THERMOSTAT
Good Pattern Example
-
7/28/2019 HVAC Vav Select-Ash
8/61
Perforated 24X24, 10 inlet, 4 way, 20 Delta-T
2
4
6
8
10
12
14
16
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
CFM/Sq.Ft.
1/2UnitSepara
tionDistance
420
350
300250
160
Range
Spacing for 80% ADPI
NC=35
CFM
-
7/28/2019 HVAC Vav Select-Ash
9/61
ADPI and LEED Standard 55 requires air speed 80%, roomaverage air speed will be < 40fpm, andvertical stratification will be
-
7/28/2019 HVAC Vav Select-Ash
10/61
ADPI and LEED
-
7/28/2019 HVAC Vav Select-Ash
11/61
THERMOSTATCold
Outside
Window
Common Overhead Heating Design
-
7/28/2019 HVAC Vav Select-Ash
12/61
Perimeter Considerations:
Maximum delta-t for effective mixing when heating,per ASHRAE handbook = ?.
= 15F (90F discharge), continuous operation.
Throw toward and away from glass.
150 FPM should reach 4-5 feet from the floor.
ASHRAE 62.1 requires that ventilation be increasedby 25% when heating, if the above rules are notfollowed.
Typical perimeters require only 8F
delta-t @ 1 cfm/sq.Ft.
-
7/28/2019 HVAC Vav Select-Ash
13/61
Air Distribution Summary Diffuser selection should be based on throw and
room size.
Select at both max and minimum occupied flowrates. Rates are likely less than 0.5 cfm/sf.
Noisy diffusers are good.
Dirt on the ceiling aint all bad.
Use good design when heating.
Poor air distribution yields poor comfort, poor airquality, slow system response.
-
7/28/2019 HVAC Vav Select-Ash
14/61
Thermal Comfort:
Latest THERMAL COMFORT STANDARD:
ASHRAE 55-2010 ASHRAE Fundamentals, Chapter 7
PMV - predicted mean vote - a single number
rating. Standard 55 mandates a maximum 5oF vertical
temperature stratification.
A program is available, based on a programlisting in ASHRAE 55, which allows plotting ofthe comfort envelope.
-
7/28/2019 HVAC Vav Select-Ash
15/61
Graphical Method, ASHRAE 55-2010
-
7/28/2019 HVAC Vav Select-Ash
16/61
Typical Executive Worker
Profile
-
7/28/2019 HVAC Vav Select-Ash
17/61
ASHRAE J ournal, J une 2008
Comfort Economics
-
7/28/2019 HVAC Vav Select-Ash
18/61
Design Issues:Diffuser Selection
Perimeter
Thermal Comfort
Acoustics
Ventilation & IAQ
LEED 09 ASHRAE Std. 55 Checklist
-
7/28/2019 HVAC Vav Select-Ash
19/61
Comfort Summary Thermal comfort is #1 reason for not renewing the
lease (dont fix the wrong thing).
Many IAQ and air distribution complaints can becured with temperature changes. The ratio of productivity to energy savings is
2000/1. First costs are minor compared toproductivity.
Internal heat loads cost 2X power consumption. Mandated designs and set points often waste
energy. People will make themselves comfortable!
Vertical Stratification requirement is often ignored Thermal comfort program available online!
-
7/28/2019 HVAC Vav Select-Ash
20/61
Acoustics:
AHRI 885-08 acoustical application standard.
AHRI 880-08 air terminal test standard. AHRI 260-01 ducted equipment except air terminals.
ASHRAE 70, air diffuser performance.
Acoustical quality suggests the use of RC (or newer
measures) rather than NC. Many acousticians areheading back to dBA!
LEED 2012 will include acoustical credits andrequirements.
A new ruling by AHRI will change everyonesdischarge sound ratings considerably.
-
7/28/2019 HVAC Vav Select-Ash
21/61
End Reflection Low frequency sound traveling down a duct willpartially reflect back when encountering a rapid
change in area. The smaller the duct, the greater the effect.
It can be as much as 10dB at 125Hz. It is much
less at higher frequencies. Since NC is usually set at 125Hz, reported NC
can go up as much as 10NC.
Most importantly, Specifying Engineers shouldbe modifying their discharge soundrequirements to reflect the new data.
-
7/28/2019 HVAC Vav Select-Ash
22/61
End Reflection
-
7/28/2019 HVAC Vav Select-Ash
23/61
End Reflection An end reflection happens when air travels from a main
to a branch duct, and especially when it enters a flex
duct connection. Another happens when a duct terminates at the room, at
the diffuser.
AHRI 885 includes one 8 end reflection in Appendix E.
This change only affects reported discharge soundpower levels.
Discharge sound is the same, but will be reported a bit
louder. Engineers will need to update their discharge sound
specifications.
-
7/28/2019 HVAC Vav Select-Ash
24/61
Sound Specifications
Should be based on clearly stated assumptions.
Should reflect real project needs, not anymanufacturers data and use currently accepted
application factors. Discharge sound specs need to be modified to account
for the louder reported sound power.
If duct lining is used requireNC shall be determinedin accordance with AHRI 885-08, Appendix E,otherwise specify octave band sound power.
Over-silencing increases both initial costs andoperating costs, and may hinder proper IAQperformance.
-
7/28/2019 HVAC Vav Select-Ash
25/61
Classroom Acoustics:
-
7/28/2019 HVAC Vav Select-Ash
26/61
LEED 2012 Proposed criteria
LEED for schools presently gives a point for soundlevels < 45 dBA (about 36 NC).
For 2012, it is proposed that 40 dBA be aprerequisite, with a point for achieving 35 dBA.
Instead of requiring resultant sound levels, the newcriteria says that calculated HVAC system noise
shall not exceed the specified values, using eitherthe ASHRAE Handbooks (which are inadequate) orAHRI 885.
-
7/28/2019 HVAC Vav Select-Ash
27/61
Indoor Air Quality
Standing Standard ProjectCommittee 62.1
Residential Committee is 62.2
Current Standard is62.1-10, and all previous addendahave been incorporated (and nolonger available on the web).
Several additional Addenda havebeen approved and more are inprogress.
Addenda are now published 18months after the release of astandard.
-
7/28/2019 HVAC Vav Select-Ash
28/61
Terminal Units
-
7/28/2019 HVAC Vav Select-Ash
29/61
Single Duct
Retro-Fit Dampers
Bypass Dampers
Dual Duct
Parallel Fan Powered
Series Fan Powered
Terminal Units
-
7/28/2019 HVAC Vav Select-Ash
30/61
The Construction Specifier,
July 04
-
7/28/2019 HVAC Vav Select-Ash
31/61
Single Duct Terminal Units
-
7/28/2019 HVAC Vav Select-Ash
32/61
When to Use Single
Duct Terminals
Interior spaces Where only cooling is required. Heating not needed
due to climate and heating from perimeter areas.
Perimeter with reheat Cooling along outer walls with some small reheat on
the coldest days.
Interior with reheat to maintain ventilation minimums Only cooling is required but reheating for minimum
airflows
Supply return tracking Airflow measurement and control into and out of a
laboratory space.
Standard
Single Duct
-
7/28/2019 HVAC Vav Select-Ash
33/61
Retro-Fit Single Duct
Terminals
Retrofitting old terminal units. Mechanical constant volume dual duct dampers
for high pressure systems replaced with roundunits for measuring and controlling airflow.
Adding a control zone. Round units added to a round duct or square
ones to a square duct to measure and controlairflow in a new occupied zone monitored with
Tstat.
Replacing VVT-type zone dampers
replace existing high pressure, high velocity zone
controlled units with low pressure VAV units.
As a return damper Added to existing ductwork to measure and
control leaving airflow as required from controls.
Square Slip In Retro-Fit
Round Retro-Fit
-
7/28/2019 HVAC Vav Select-Ash
34/61
Dual Duct Terminal Units
Wh t U D l D t
-
7/28/2019 HVAC Vav Select-Ash
35/61
When to Use Dual Duct
Terminals
Perimeter Heating & Cooling
Positive ventilation control (measuredventilation to the zone)
Laboratories / Constant volume applications
Supply / Return tracking
Underfloor Air Conditioning Be sure you understand the mixing / control
requirements
Upstream vs. downstream flow sensing issues
N Mi i D l D t
-
7/28/2019 HVAC Vav Select-Ash
36/61
Non-Mixing Dual Duct
No Mixing
Two single duct Units J oined S&D Discharge
Inlet Sensing Only
Standard Dual Duct
2 Single
duct units
Joining Strip
Mi i D l D t
-
7/28/2019 HVAC Vav Select-Ash
37/61
Mixing Dual Duct
Attenuated Dual Duct
May have inlet or total flowdischarge sensing
Unequal inlet sizecombinations are available
Many types of linings are
available Mixing baffle can have up to
20:1 Mixing Ratio. Typically have high minimum
inlet pressure requirementPremium Dual Duct
-
7/28/2019 HVAC Vav Select-Ash
38/61
Opportunities for Dual Duct
Systems Dual Duct can meet the most stringent
requirements for classroom acoustics, aswell as 90.1 requirements.
Providing 100 OA (DOAS?) through oneinlet allows validation of ventilation rates
Supplemental heating and even sensible
cooling coils are being considered in somedesigns.
-
7/28/2019 HVAC Vav Select-Ash
39/61
Fan Powered Terminal Units
When to use fan powered
-
7/28/2019 HVAC Vav Select-Ash
40/61
When to use fan powered
terminals Originally designed for perimeter heating and
cooling - to avoid reheat
Constant volume applications have a fan nearthe discharge - series boxes
Series Boxes provide relatively constantinterior sound levels and air flow rates and areoften used in interior zones.
Because of energy concerns, the ECM motor
has been employed in many applications. Texas A&M recently completed a study,
donated to ASHRAE and AHRI at the summermeeting in Montreal, on Series vs. Parallel, andECM vs PSC motors.
-
7/28/2019 HVAC Vav Select-Ash
41/61
The use of ECM motors can reduce the true energyconsumption of Fan Powered Terminals
An ECM motor is a brushless DC motor, with an
integral computer controlled inverter. At reduced rpm and load, an ECM motor can use as
little as 60% of the watts of a standard Permanent Split/ Capacitor Start (PSC) motor
An ECM motor can be programmed to be pressureindependent, resulting in true constant volumeperformance, easier balancing, and even DDC
controlled performance.
ECM Motors
-
7/28/2019 HVAC Vav Select-Ash
42/61
Some Cautions, however:An ECM motor can add $350 to the purchase
price of a Fan Powered Terminal.Power consumption CAN be greater than anequivalent PSC motor, and the connected load
requirement is usually higher because of this.There are issues with the power factor of thesetypes of devices which may cloud true energy
savings.
ECM Motors
-
7/28/2019 HVAC Vav Select-Ash
43/61
Series Fan Boxes
SERIES FAN POWERED BOXES
Fan is on discharge of unit - all air
goes through the fan (primary airflowcannot exceed fan airflow)
Fan runs at all times during occupancy
Fan must be started before primary airis supplied.
Note: there is no such thing as an anti-backward rotation device.
Radiated sound is critical soundapplication factor
Parallel Fan Boxes
-
7/28/2019 HVAC Vav Select-Ash
44/61
Parallel Fan Boxes
PARALLEL FAN POWERED BOXES
Fan is in parallel with VAV damper Fan airflow independent of primary
airflow
Fan is essentially first stage of heat Backdraft damper is standard
Discharge sound is criticalapplication factor
-
7/28/2019 HVAC Vav Select-Ash
45/61
Texas A&M Study Results
Data was generated for entire building
systems, not just terminals. Parameters were developed for detailed
full building energy analysis
Results are being presented in ASHRAEPapers, and full study results have been
donated to ASHRAE and AHRI.
-
7/28/2019 HVAC Vav Select-Ash
46/61
Texas A&M Study Results
The results showed that both system operation and climate had agreat effect on final energy use.
In general, however there were a few important observations:
ECM and PSC motors had the same building energy consumption withParallel boxes.
Parallel boxes could be more efficient than series boxes, except forback-draft damper leakage, which was found to be very significant.
Series boxes, with ECM motors, are the most energy efficient choice,
(at least until someone develops a leak proof parallel box). Series Boxes, with DDC system variable volume fan flow, are likely
more efficient than any other air distribution method, at low part loadoperation.
-
7/28/2019 HVAC Vav Select-Ash
47/61
Electric Reheat Options
120/208/240/277 single phase
208/3 phase (3-wire), 480/3 phase (4-wire)
1-3 Stages (most types) Side access - Leave clearance per NEC
Operation at minimum airflow is unlikely to provide comfort
Consider proportional electric heat with discharge temperature
control for maximum comfort
P ti l El t i R h t
-
7/28/2019 HVAC Vav Select-Ash
48/61
There are two types of proportional electricheat:
SCR Electric Heat Requires analog input
Somewhat expensive
Time Proportional Electric Heat 1 Stage only required
Infinite adjustment
Low cost
Silent
Allows for effective discharge temperature control
Many different control inputs
Proportional Electric Reheat
-
7/28/2019 HVAC Vav Select-Ash
49/61
Dedicated Outdoor Air Systems
DOAS D l D t
-
7/28/2019 HVAC Vav Select-Ash
50/61
DOAS Dual Duct
One inlet provides 100%outside air, dehumidified,typically cold.
Other duct provides 100%return air, either warm or cold,depending on the season.
Supplemental reheat coilsand even a sensible coolingcoil have been considered
A good mixing baffle should
be employed (20:1 MixingRatio recommended)
Mixing Dual Duct
Fresh Air Terminal Unit
-
7/28/2019 HVAC Vav Select-Ash
51/61
Outside air can be supplied to a Series Fan Terminal through a secondducted system.
This requires two duct systems, but separates ventilation andrecirculated air.
The system allows monitoring of ventilation rates into each zone. A stand-alone Pressure Independent controller on the DOAS inlet,tied to the fan relay, will allow standard DDC zone controls.
Fresh Air Terminal Unit
PrimaryInlet
Fresh Air Inlet
Series FanPowered
Terminal Unit
Induced Air
Inlet
Chilled Fan Powered Terminal Unit
-
7/28/2019 HVAC Vav Select-Ash
52/61
100% Outside air can be supplied to a Series Fan Terminal througha ducted system, designed to handle ventilation and latent loads.
A sensible cooling coil, on the induced air inlet, cools plenum air foradditional sensible space cooling.
The system allows monitoring of ventilation rates into each zone. A stand-alone Pressure Independent controller for the DOAS inlet,
tied to the fan relay, will allow standard fan coil DDC zone controls.
Both Series and Parallel designs are currently being used dependingon the installation.
Chilled Fan Powered Terminal Unit
DOAS Air Inlet
Series Fan Powered Terminal UnitInduced Air Inlet
Sensiblecooling
coil
Chilled Box In The Interior
-
7/28/2019 HVAC Vav Select-Ash
53/61
C
Sensible Cooling Coil
Optional MERV 8 Filter
Standard Ceiling Diffusers
Series Fan Powered
Terminal Unit
Dedicated OutdoorAir Supply
Standard Reheat Options
Chilled Box at the Perimeter
-
7/28/2019 HVAC Vav Select-Ash
54/61
Series DOAS Unit
InteriorChilledBeams
DOAS Air Supply
Discharge Heating Coil
Perimeter Slot Diffusers
Chilled Parallel Box in a Laboratory
-
7/28/2019 HVAC Vav Select-Ash
55/61
Lab Pressure Supply Valve
Non Condensing Cooling Coil
Optional Merv-8 Filter
Laboratory Diffuser
y
Chilled Parallel Unit
-
7/28/2019 HVAC Vav Select-Ash
56/61
Dedicated Outdoor Air Duct
Active Chilled Beams
Parallel DOAS Unit
Secondary DOAS Duct
Supplying Chilled Beams
Chilled Box Summary
-
7/28/2019 HVAC Vav Select-Ash
57/61
Chilled Box Summary
Low first cost
Low system pressure requirement Safe location possible
Easily reconfigurable Minimal Contractor Training
Guaranteed Performance
Several LEED points possible
S
-
7/28/2019 HVAC Vav Select-Ash
58/61
Summary
LEED 2009 requires meeting Standard 62.1 Documented use of ADPI is the ONLY way to assure
compliance to 55 in the design phase.
Acoustics should be specified on the basis of needwith clear assumptions. Use AHRI 885
Reheat needs to be carefully considered in terms of
discharge temperatures and velocities. Software is available to assist in selecting the best mixof products.
The rules are dynamic - pay attention.
Engineers Checklist
-
7/28/2019 HVAC Vav Select-Ash
59/61
Engineer s Checklist
Are Specifications current? Real Manufacturers
Current Standards referenced Do we have clear acoustical requirements:
Inlet Ps defined?
Assumptions clearly defined?
Reheat: Sufficient airflow? Discharge Static?
3 or 4 wire 480V? Contactors? Stages?
gpm or btuh? (pick one)
Linings are acoustics and cost understood?
Accessories Transformers?
Filters?
Hanger brackets?
Fuses, Disconnects?
If specified
clearly, you mayget what youwant!
If unclear, youwill get what thelow bidder wants
you to get.
-
7/28/2019 HVAC Vav Select-Ash
60/61
ANY QUESTIONS?
-
7/28/2019 HVAC Vav Select-Ash
61/61
Contact
www.krueger-hvac.com
EXCELLENCE IN AIR DISTRIBUTION
KRUEGER