ICC PRO V 4.4
OPC Server
2 ICC PRO - OPC Server v4.4
Legal Notice
DISCLAIMER
ICC Water Control Ltd makes no representations or warranties with respect to this
manual and, to the maximum extent permitted by law, expressly limits its liability for
breach of any warranty that may be implied to the replacement of this manual with
another.
Further, ICC Water Control reserves the right to revise this publication at any time
without incurring an obligation to notify any person of the revision.
COPYRIGHT
© Copyright 2018 ICC Water Control Ltd. All rights reserved.
TRADEMARKS
ICC Water Control has made every effort to supply trademark information about
company names, products and services mentioned in this manual.
IRRInet, IRRInet-XL, IRRInet-XM, IRRInet-M, IRRInet-ACE, Piccolo-XR, PIU,
Scorpio, Intrac are registered trademarks of Motorola Inc.
Windows, Windows 7, 8, 10, Windows Server 2008, 2012, 2016, SQL Server, SQL
Server 2008, SQL Server 2012 LocalDB and Microsoft are either registered
trademarks or trademarks of Microsoft Corporation in the United States and/or other
countries.
All other brands and products referenced in this document are acknowledged to be the
trademarks or registered trademarks of their respective holders.
GENERAL NOTICE
Some product names used in this manual are used for identification purposes only and
may be trademarks of their respective companies.
ICC PRO ICC PRO - OPC Server v4.4 3
Content
1. Introduction 4
Purpose 4
Audience 4
2. ICC PRO - OPC Server feature 5
General 5
Data available via OPC 5 Field Unit 6 Analog Input 7 Analog Output 7 Digital Input 8 Digital Output 8 External Flag 9 Fert Pump 9 Filter Program 10 Internal Flag 11 Irrigation Program 11 Logic Flag 15 Main Line 15 Meter 16 Sensor 17 Virtual Analog Input 17 Virtual Meter 18
3. Access from remote workstation 19
Distributed OPC Overview 19 DCOM 19 OPCEnum 19
Configuring DCOM 19 Adding a local user 19 Adding a group 20 Configuring OPC Server 21
Firewall settings 34
4 ICC PRO - OPC Server v4.4
1. Introduction
Purpose
This document guides the user how to configure and use ICC PRO - OPC Server.
The document describes the ICC PRO - OPC Server features and how to use it both
locally and on a network.
Audience
This document is for those who will configure ICC PRO - OPC Server for use with
third party clients and for users that want to connect a SCADA or other OPC client to
ICC PRO system via the OPC Server.
It is also important for administrators and for new users of ICC PRO.
ICC PRO ICC PRO - OPC Server v4.4 5
2. ICC PRO - OPC Server feature
ICC PRO - OPC Server allows any client OPC application to retrieve information
from ICC PRO and also modify data using the OPC standard protocol.
ICC PRO support OPC DA 2.0 and OPC DA 3.0.
Please refer to the ICC PRO installation manual for information about installing ICC
PRO and especially about installing the ICC PRO - OPC Server.
General
The OPC Server name is ICC_OPC_Server.1
If you install ICC PRO with the OPC Server option, the OPC Server is available after
installing ICC PRO and no special configuration is required.
To allow remote access (from an OPC client that is running on a remote workstation)
please refer to the chapter 3 Access from remote workstation
Data available via OPC
ICC PRO - OPC Server allows OPC clients to access real time data of the system.
You must define the elements in ICC before you can access them from an OPC client.
As soon as you define an element in ICC, it will be available to OPC clients without
any specific configuration in ICC.
The following elements are available via the OPC interface:
Field Unit
Analog Input
Analog Output
Digital Input
Digital Output
External Flag
Fert Pump
Filter Program
Internal Flag
Irrigation Program
Logic Flag
Main Line
Meter
Sensor
Virtual Analog Input
Virtual Meter
The available information for each element type is described in the following sections.
6 ICC PRO - OPC Server v4.4
Field Unit
OPC Tag Description Type R/W Remarks
ApplicationVersion The IRRInet
application
version
Decimal
R
FullDownloadOrUploadRequire Flag that
indicate if the
field unit
require an
upload or
download
Boolean
R
CommFail True if the
field unit is in
communication
failure status
Boolean
R
DailyAcc Daily
accumulation
in Liters
Double
R
WeeklyAcc Weekly
accumulation
in Liters
Double
R
MonthlyAcc Monthly
accumulation
in Liters
Double
R
YearlyAcc Yearly
accumulation
in Liters
Double
R
DailyFertAcc Daily Fert.
accumulation
in Liters
Double
R
WeeklyFertAcc Weekly Fert.
accumulation
in Liters
Double
R
MonthlyFertAcc Monthly Fert.
accumulation
in Liters
Double
R
YearlyFertAcc Yearly Fert.
accumulation
in Liters
Double
R
The full path for the tag is FieldUnits.[FIELD_UNIT_NAME].[TAG_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC and
[TAG_NAME] is one of the above tags.
ICC PRO ICC PRO - OPC Server v4.4 7
Analog Input
OPC Tag Description Type R/W Remarks
CommFailure
If set indicate a
communication
failure with the
element
Boolean R
HWFailure
If set indicate a
hardware failure in
the element
Boolean R
Sample
If set by the client,
ICC will sample the
value from the
IRRInet
Boolean W
Value
The current value of
the element in the
element
measurement units
Double R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].AnalogInputs.[ELEMENT_NAME].[TAG_NAM
E]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Analog Output
OPC Tag Description Type R/W Remarks
CommFailure
If set indicate a
communication
failure with the
element
Boolean R
HWFailure
If set indicate a
hardware failure in
the element
Boolean R
Sample
If set by the client,
ICC will sample the
value from the
IRRInet
Boolean W
Value
The current value of
the element in the
element
measurement units
Double R/W
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].AnalogOutputs.[ELEMENT_NAME].[TAG_NA
ME]
8 ICC PRO - OPC Server v4.4
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Digital Input
OPC Tag Description Type R/W Remarks
CommFailure
If set indicate a
communication
failure with the
element
Boolean R
HWFailure
If set indicate a
hardware failure in
the element
Boolean R
MomentaryStatus
The current status
of the digital input
regardless of the
stability time
Boolean R
RemainStabilityTime Remaining stability
time Integer R/W
Time in
seconds
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
StableStatus
The current stable
status of the digital
input
Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].DigitialInputs.[ELEMENT_NAME].[TAG_NAM
E]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Digital Output
OPC Tag Description Type R/W Remarks
CommFailure
If set indicate a
communication
failure with the
element
Boolean R
HWFailure
If set indicate a
hardware failure in
the element
Boolean R
ICC PRO ICC PRO - OPC Server v4.4 9
ManualStatus
The current manual
status of the digital
output
Boolean R/W
Write 1 to
manually
open or 0 to
manually
close
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
Status The current status
of the digital output Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].DigitialOutputs.[ELEMENT_NAME].[TAG_NA
ME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
External Flag
OPC Tag Description Type R/W Remarks
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
Status The current status
of the External Flag Boolean R/W
Write 1 to set
the flag or 0
to reset it
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].ExternalFlags.[ELEMENT_NAME].[TAG_NAM
E]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Fert Pump
OPC Tag Description Type R/W Remarks
ClearAlarm
If set by the client
the active alarm
will be cleared
Boolean W
Write 1 to
clear current
alarm
InUse
If set indicate that
the pump is used
by an irrigation
Boolean R
10 ICC PRO - OPC Server v4.4
program
Sample
If set by the client,
ICC will sample
the status from the
IRRInet
Boolean W
UncontrolAlarm
If set there is an
uncontrol alarm in
the fert pump
Boolean R
UnopenAlarm
If set there is an
unopen alarm in the
fert pump
Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].FertPumps.[ELEMENT_NAME].[TAG_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Filter Program
OPC Tag Description Type R/W Remarks
FlushingCounter
Number of
flushes since
last reset
Integer R
FlushingCounterResetTime
The flushing
counter reset
time
Date R
RemainingDelayBeforeStartFlushing
Remaining
time before
start flushing
Integer R/W Seconds
RemainingDelayBetweenFilterValves
Remaining
time to wait
between
closing the
last flashing
valve and
open the
next valve
Integer R/W Seconds
RemainingFlushingTime
Remaining
time to flush
with the
current valve
Integer R/W Seconds
RemainingIntervalBetweenFlushes
Remaining
time or
quantity
until starting
Integer R/W
Minutes
for time
based
filter or
ICC PRO ICC PRO - OPC Server v4.4
11
a new
flushing
cycle
pulses for
quantity
based
filter
Sample
If set by the
client, ICC
will sample
the status
from the
IRRInet
Boolean W
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].FilterPrograms.[ELEMENT_NAME].[TAG_NA
ME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Internal Flag
OPC Tag Description Type R/W Remarks
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
Status The current status
of the Internal Flag Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].InternalFlags.[ELEMENT_NAME].[TAG_NAM
E]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Irrigation Program
OPC Tag Description Type R/W Remarks
Activate
Activate or
Deactivate the
program
Boolean W
Write 1 to
activate the
program or 0 to
deactivate the
program
Active True if the
program is active Boolean R
ActualFlow The program
actual flow Double R
Actual Flow in
meter flow units
12 ICC PRO - OPC Server v4.4
ClearAlarm
Reset the
program active
alarm
Boolean W Write 1 to clear
the active alarm
CyclesInDay Cycles in day Integer R/W
Applicable only
for the first
program in a
group
DaysInterval Interval between
irrigation days Integer R/W
Applicable only
for the first
program in a
group
ExpectedFlow Program
expected flow Double R/W
In meter flow
units
HighFlowAlarm Program high
flow alarm Boolean R
True if there is
high flow alarm
in the program
IrrigateByDaysInterval
True if the
program is
irrigating by days
interval.
False if irrigating
by week days
Boolean R/W
Write 1 to
irrigate by days
interval
IrrigateByWeekDays
True if the
program is
irrigating by
week days.
False if irrigating
by days interval
Boolean R/W
Write 1 to
irrigate by week
days
IrrigateNow Irrigate now
command Boolean W
Write 1 to
irrigate now the
group.
Applicable only
to the first
program in a
group
IrrigateNowSelected
Irrigate now
selected
command. Must
mark the selected
program before
setting this.
Boolean W
Write 1 to
irrigate now
selected the
group.
Applicable only
to the first
program in a
group
IrrigateNowSelectedDebt
Irrigate now
selected debt
command. Must
mark the selected
Boolean W
Write 1 to
irrigate now
selected debt the
group.
ICC PRO ICC PRO - OPC Server v4.4
13
program before
setting this.
Applicable only
to the first
program in a
group
IrrigateToday Irrigate today
command Boolean W
Write 1 to
irrigate today the
group.
Applicable only
to the first
program in a
group
IrrigateTodaySelected
Irrigate today
selected
command. Must
mark the selected
program before
setting this.
Boolean W
Write 1 to
irrigate today
selected the
group.
Applicable only
to the first
program in a
group
IrrigateTodaySelectedDebt
Irrigate today
selected debt
command. Must
mark the selected
program before
setting this.
Boolean W
Write 1 to
irrigate today
selected debt the
group.
Applicable only
to the first
program in a
group
IrrigationBasis Program
Irrigation basis Byte R/W
1 – Time
3- Quantity
IrrigationDays Irrigation week
days Integer R/W
Two week
irrigation days.
Bit pattern.
First week
Sunday is bit 1
and Saturday on
week two is bit
14.
LowFlowAlarm Program low
flow alarm Boolean R
True if there is
low flow alarm
in the program
RemainingCyclesInDay Remaining cycles
in day Integer R/W
Applicable only
for the first
program in a
group
RemainingDaysInterval
Remaining
interval between
irrigation days
Integer R/W
Applicable only
for the first
program in a
group
14 ICC PRO - OPC Server v4.4
RemainingWaterQuantity Remaining water
quantity Double R/W
Time in seconds
if irrigation basis
is time or
quantity in meter
volume unit if
irrigate basis is
quantity
Sample
If set by the
client, ICC will
sample the status
from the IRRInet
Boolean W
StartTime Group start time Integer R/W
Seconds since
midnight.
Applicable only
for the first
program in a
group
StopTime Group stop time Integer R/W
Seconds since
midnight.
Applicable only
for the first
program in a
group
Suspend
Suspend
irrigation
command
Boolean W
Applicable only
for the first
program in a
group. Write 1 to
suspend the
group or 0 to
resume
Suspended Group suspend
status Boolean R
1 if the group
suspened
UnopenAlarm Program unopen
alarm Boolean R
True if there is
unopen alarm in
the program
WaterQuantity Water quantity Double R/W
Time in seconds
if irrigation basis
is time or
quantity in meter
volume unit if
irrigate basis is
quantity
ICC PRO ICC PRO - OPC Server v4.4
15
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].IrrigationPrograms.[ELEMENT_NAME].[TAG_
NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Logic Flag
OPC Tag Description Type R/W Remarks
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
Status The current status
of the Logic Flag Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].LogicFlags.[ELEMENT_NAME].[TAG_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Main Line
OPC Tag Description Type R/W Remarks
BurstAlarm
True if there is a
burst alarm in the
main line
Boolean R
ClearAlarm Clear current
alarm Boolean W
Write 1 to
clear the
alarm
Run
Run status of the
main line. 1 – Run,
0 – Stop.
Boolean R/W
Write 1 to
run the main
line or 0 to
stop the
main line
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
UncontrolFertAlarm
True if there is a
fert leak alarm in
the main line
Boolean R
16 ICC PRO - OPC Server v4.4
UncontrolWaterAlarm
True if there is a
water leak alarm in
the main line
Boolean R
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].MainLines.[ELEMENT_NAME].[TAG_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Meter
OPC Tag Description Type R/W Remarks
Accumulator Meter accumulator Double R/W In meter
volume units
CommFailure
Communication
Failure with the
meter
Boolean R
Flow Current flow Double R In meter
flow units
HWFailure Hardware Failure
in the meter Boolean R
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
SampleRemote
If set by the client,
ICC will sample
the value from the
IRRInet and send
request to sample
the remote unit
(Scorpio, XR…)
Boolean W
DailyAcc Daily
accumulation Double R
In meter
volume units
WeeklyAcc
Weekly
accumulation Double R
In meter
volume units
MonthlyAcc
Monthly
accumulation Double R
In meter
volume units
YearlyAcc
Yearlyly
accumulation Double R
In meter
volume units
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].Meters.[ELEMENT_NAME].[TAG_NAME]
ICC PRO ICC PRO - OPC Server v4.4
17
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Sensor
OPC Tag Description Type R/W Remarks
Accumulator Sensor
accumulator Double R/W Pulses
CommFailure
Communication
Failure with the
sensor
Boolean R
HWFailure Hardware Failure
in the sensor Boolean R
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
SampleRemote
If set by the client,
ICC will sample
the value from the
IRRInet and send
request to sample
the remote unit
(Scorpio, XR…)
Boolean W
Value Current value Double R In sensor
units
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].Sensors.[ELEMENT_NAME].[TAG_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Virtual Analog Input
OPC Tag Description Type R/W Remarks
Sample
If set by the client,
ICC will sample the
value from the
IRRInet
Boolean W
Value
The current value of
the element in the
element
measurement units
Double R
18 ICC PRO - OPC Server v4.4
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].VirtualAnalogInputs.[ELEMENT_NAME].[TAG
_NAME]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
Virtual Meter
OPC Tag Description Type R/W Remarks
Accumulator Meter accumulator Double R/W In meter
volume units
Flow Current flow Double R In meter
flow units
Sample
If set by the client,
ICC will sample
the value from the
IRRInet
Boolean W
DailyAcc Daily
accumulation Double R
In meter
volume units
WeeklyAcc
Weekly
accumulation Double R
In meter
volume units
MonthlyAcc
Monthly
accumulation Double R
In meter
volume units
YearlyAcc
Yearlyly
accumulation Double R
In meter
volume units
The full path for the tag is
FieldUnits.[FIELD_UNIT_NAME].VirtulMeters.[ELEMENT_NAME].[TAG_NAM
E]
Where [FIELD_UNIT_NAME] is the name of the field unit in ICC,
{ELEMENT_NAME] is the name of the element is ICC and [TAG_NAME] is one of
the above tags.
ICC PRO ICC PRO - OPC Server v4.4
19
3. Access from remote workstation
This chapter describes the required configuration for accessing ICC PRO - OPC
Server from a client that is located on a remote workstation.
The OPC uses DCOM as the communication infrastructure so you need to configure
DCOM on the server machine to allow remote access.
Distributed OPC Overview
DCOM
DCOM (Distributed Component Object Model) is an extension of COM (Component
Object Model) that allow COM components to communicates with objects on
different computers.
Because DCOM can cause security threats, you should take care how you configure
your server to allow remote clients to access it.
OPCEnum
OPC clients need to discover OPC servers that are running on a computer.
To do so, a component named OPCEnum is available from the OPC Foundation.
This component runs as system service and inform clients about the OPC servers that
available on the computer.
Configuring DCOM
To allow secured connection we need to define a user and group that will have access
to the OPC Server.
When working in a domain, the network administrator will need to create the user and
the group. If we work in a workgroup, we need to manually add the user and the
group.
Please note: The workgroup option is possible also if working in a domain.
Adding a local user
Launch the Local User and Group snap-in. You can run it by entering lusrmgr.msc
command.
20 ICC PRO - OPC Server v4.4
Right click on Users and select New User…
Type the new user information.
Click Create and Close.
Adding a group
Right click on Groups and select New Group…
ICC PRO ICC PRO - OPC Server v4.4
21
Type the new group information.
Click on Add… then click on Advanced… and then click on Find Now.
Select IccOpc and click OK and another OK.
Click on Create and then on Close.
Configuring OPC Server
Launch dcomcnfg.exe from the Start-Run or Windows 7 "Search Programs and Files".
Please Note: On windows 64 there is a known problem with the dcomcnfg utility, so
run the 32 bit version from C:\WINDOWS\SysWOW64/mmc comexp.msc /32
22 ICC PRO - OPC Server v4.4
Right click on My Computer and select Properties.
Please note: If you do not get a dialog like the following (not all tabs available or
the application crashes), you need to modify the security for
C:\Windows\Registration folder and assign full access to the Administrators group.
ICC PRO ICC PRO - OPC Server v4.4
23
Ensure that the Default Properties tab definition is as follow:
24 ICC PRO - OPC Server v4.4
Now, open the COM Security tab.
ICC PRO ICC PRO - OPC Server v4.4
25
Click on Access Permissions – Edit Default… and allow local and remote access to
the Network, System, INTERACTIVE and IccOpcGroup users/groups.
Do the same for Edit Limits…
Click on Launch and Activation Permissions – Edit Default… and allow local
Launch, remote launch, local Activation and remote Activation to the Network,
System, INTERACTIVE and IccOpcGroup users/groups.
Do the same for Edit Limits…
Click OK to apply the changes.
Open the DCOM Config branch and select the OpcEnum component.
Right click on OpcEnum and select Properties.
26 ICC PRO - OPC Server v4.4
In the General tab, set the Authentication Level to None.
Open the Location tab.
ICC PRO ICC PRO - OPC Server v4.4
27
Ensure that "Run application on this computer" is checked.
Select the Security tab.
28 ICC PRO - OPC Server v4.4
Ensure that Launch and Activation Permissions and Access Permissions set to Use
Defaults.
Set the Configuration Permissions to Customize.
Allow Full Control to the Network, System, INTERACTIVE and IccOpcGroup
users/groups.
Open the Identity tab and ensure that the system account selected.
ICC PRO ICC PRO - OPC Server v4.4
29
Click on OK to apply the changes.
Now, select the ICC PRO - OPC Server.
In DCOM Config branch select ICC_OPC_Server OPC DA Server.
Right click on it and select properties.
30 ICC PRO - OPC Server v4.4
In the General tab, set the Authentication Level to None.
Open the Location tab.
ICC PRO ICC PRO - OPC Server v4.4
31
Ensure that "Run application on this computer" is checked.
Select the Security tab.
32 ICC PRO - OPC Server v4.4
ICC PRO ICC PRO - OPC Server v4.4
33
Ensure that Launch and Activation Permissions and Access Permissions set to Use
Defaults.
Set the Configuration Permissions to Customize.
Allow Full Control to the Network, System, INTERACTIVE and IccOpcGroup
users/groups.
Open the Identity tab.
34 ICC PRO - OPC Server v4.4
Select the "This user" option and enter the IccOpcClient user you defined and the
password.
This will ensure that all clients will run the same instance of the OPC Server.
Click on OK to apply the changes.
To enable the new configuration you need to restart the PC or at least, restart the
OpcEnum service the stop the ICC OPC Server if it runs (use the task manager to kill
it).
Firewall settings
You will need to add an exception to the firewall that enables DCOM connection.
Please note: You can turn off the firewall during the testing and when everything is
working ok, turn on the firewall and apply the following exceptions.
ICC PRO ICC PRO - OPC Server v4.4
35
Open the firewall configuration and add an exception.
Add the OPCEnum.exe program that is located in C:\Windows\System32 folder
(C:\Windows\SysWOW64 on 64 bits machines)
Add the ICC OPC Server located at C:\Program Files\ICC PRO\ICC_OPCServer.exe
(C:\Program Files (x86)\ICC PRO\ICC_OPCServer.exe on 64 bits machines)
Add the 135 port with TCP protocol.
Click OK to accept the changes.
You may also need to add firewall exception on the client machine.
Add the OPC client program as an exception.
Add port 135 with the TCP protocol.
Now you can connect with ICC PRO - OPC Server from remote stations.