igv (inert) - hvacecohvac.com.au/files/apreco-pressure-relief-vent-igv-inert.pdf · igv (inert)...

2
IGV (Inert) Pressure Relief Vent APPROVED ME 5073 Items: EWCL5 listed single-way pressure relief vent with 4 Hour Fire Resistance rating in accordance to EN 1634-1:2014. Switchable flange for reverse flow configuration. Standard Materials: Carbon steel frame and blades, stainless steel as an option. Standard Finish: White RAL 9010 powder coated. Customer specific colours on request. Pressure Setting: 95Pa fully open. Vents suitable for room integrity tests remaining closed below 70Pa. Values based on pressure differentials of 95 Pascal and above following test methods used in EN 13030:2001. Equivalent area based on BSRIA test figures and calculated in accordance with EN 13141-1:2004. Technical Data Sheet Email: sales@ecohvac.com.au Tel: 1300 770 908 Model No. Over flange size (W x H mm) Installation hole size (W x H mm) Indicative weight (Vent + Wall Liner) IGV-0301 440 x 252 360 x 170 6.0 Kg IGV-0501 640 x 252 560 x 170 7.0 Kg IGV-0303 440 x 452 360 x 370 9.0 Kg IGV-0505 640 x 652 560 x 570 17.0 Kg IGV-0707 840 x 852 760 x 770 28.0 Kg IGV-1010 1140 x 1152 1060 x 1070 50.0 Kg Dimensional Data © 2018 Apreco Limited www.apreco.com 007-12 Free Vent Equivalent Area m 2 Product Data 0.034 0.055 0.092 0.250 0.483 0.976 0.034 0.055 0.059 0.163 0.319 0.650 0301 0501 0303 0505 0707 1010 External Internal

Upload: others

Post on 23-Apr-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IGV (Inert) - HVACecohvac.com.au/files/apreco-pressure-relief-vent-igv-inert.pdf · IGV (Inert) Pressure Relief Vent. APPROVED ME 5073 . Items: EWCL5 listed single-way pressure relief

IGV (Inert)Pressure Relief Vent

APPROVEDME 5073

Items: EWCL5 listed single-way pressure relief vent with 4 Hour Fire Resistance rating in accordance to EN 1634-1:2014.

Switchable flange for reverse flow configuration.

Standard Materials: Carbon steel frame and blades, stainless steel as an option.

Standard Finish: White RAL 9010 powder coated. Customer specific colours on request.

Pressure Setting: 95Pa fully open. Vents suitable for room integrity tests remaining closed below 70Pa.

Values based on pressure differentials of 95 Pascal and above following test methods used in EN 13030:2001.

Equivalent area based on BSRIA test figures and calculated in accordance with EN 13141-1:2004.

Technical Data Sheet Email: [email protected] Tel: 1300 770 908

Model No. Over flange size(W x H mm)

Installation hole size (W x H mm)

Indicative weight(Vent + Wall Liner)

IGV-0301 440 x 252 360 x 170 6.0 KgIGV-0501 640 x 252 560 x 170 7.0 KgIGV-0303 440 x 452 360 x 370 9.0 KgIGV-0505 640 x 652 560 x 570 17.0 KgIGV-0707 840 x 852 760 x 770 28.0 KgIGV-1010 1140 x 1152 1060 x 1070 50.0 Kg

Dimensional Data

© 2018 Apreco Limited www.apreco.com 007-12

Free Vent Equivalent Area m2

Product Data

0.034

0.055

0.092

0.250

0.483

0.976

0.034

0.055

0.059

0.163

0.319

0.650

0301

0501

0303

0505

0707

1010

External Internal

Page 2: IGV (Inert) - HVACecohvac.com.au/files/apreco-pressure-relief-vent-igv-inert.pdf · IGV (Inert) Pressure Relief Vent. APPROVED ME 5073 . Items: EWCL5 listed single-way pressure relief

IGV (Inert)Pressure Relief Vent

Technical Data Sheet Email: [email protected] Tel: 1300 770 908

© 2018 Apreco Limited www.apreco.com 007-12

Typical Internal Wall Installation Typical External Wall Installation

Typical Internal Deeper Wall Installation Typical Internal Narrow Wall Installation

Typical External Wall Installation with Cowl

Cover Grille Vent Liner Extension Wall Liner

C-Frame Kit Weather Louvre Dynamic Cover Weather Cowl

Standard internal wall depth range is 125 to 205mm with an external wall depth range of 200 to 220mm on model sizes of 0303 upwards. Models 0301 & 0501 for both internal and external standard wall depths have a range of 125 to 205mm. Extension sleeves can be added in 75mm increments to accommodate deeper walls. Bespoke / custom sizes are available to order.

Warranty is a Return-to-Base (RTB) for manufacturing defects of the vent only please refer to our T&C’s.

Standard for Models 0301 & 0501

or