infrared b arrier for perimeter protection range 250 m sma ...transformator, it is off if the...
TRANSCRIPT
-
Infrared barrier for perimeter protection
range 250 m
SMA technology
and RS485 output.
Installation Manual.
1.1.1.1.1.1.1.1
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 2
INDEX
1 MAIN COMPONENT LIST Pag. 4
2 ASSEMBLING THE CABLEPIT Pag. 5
CABLE PIT POSITIONNING Pag. 7
3 TRANSFORMER MOUNTING Pag. 8
4 POWER SUPPLY CABLE (PS01B) Pag. 10
5 CABLES AND WIRING Pag. 12
6 CONNECTION TO POWER SUPPLY Pag.13
CONNECTION TO BACK UP BATTERY Pag. 14
7 SERIAL CONNECTION TO ADEBUS Pag. 15
Connection to serial port for each column Pag. 15
8 MICROWAVE Pag. 16 TX MOTHER BOARD Pag. 16 RX MOTHER BOARD Pag. 17 Configuration dip switche Pag. 18 CONNECTIONS AND DESCRIPTIONS CAVITY TX AND RX Pag. 19 SENSITIVE ZONE Pag. 19 DEAD ZONE Pag. 20 START UP Pag. 21 TX COLUMN Pag. 21 RX COLUMN Pag. 21 ALIGNMET Pag. 22 WALK TEST Pag. 22 SENSITIVITY Pag. 23 DELAY Pag. 23 INSTALLATION GUIDE Pag. 24 sections Pag. 24 Particular conditions Pag. 25 MW TECHNICAL CHARACTERISTICS Pag. 25
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 3
9 IR SECTION Pag. 26
CABLES AND CONNECTION TO TERMINALS Pag. 26 CONNECTION TO TERMINAL BLOCK (MES9C) Pag. 26 CONNECTION AND SETTINGS HEATERS Pag. 27 SYNCHRONIZATION Pag. 28 Wired SYNC Pag. 28 Optical SYNC Pag. 30 OPTIC CONFIGURATION Pag. 32 OPTICAL TX Pag. 32 OPTICAL RX Pag. 33 TX/RX SETTINGS 3 OPTICS Pag. 34 10 TX/RX SETTINGS 2 OPTICS Pag. 34 COLUMN ALIGNMENT Pag. 35 CALIBRATION THROUGH SMA SYSTEM Pag. 36 CALIBRATION WITH PARALLEL BEAMS Pag. 38 CALIBRATION WITH CROSSED BEAMS Pag. 39 SETTING AND PROGRAMMING MOTHERBOARD Pag. 40 Led’s functionning Pag. 41 CHARACTERISTICS AND DIP SWITCHES SET Pag. 42 REACTION TIME ADJUSTMENT Pag. 44 TECHNICAL SPECIFICATION IR Pag. 45
10 DT3 SECTION Pag. 45 DETECTION AREA Pag. 45 PROGRAMMING & START UP Pag. 46 FIXED FUNCTION ADJUSTMENT Pag. 47 TECHNICAL CHARACTERISTICS DT3 Pag. 47
11 BARRIER TECHNICAL CHARACTERISTICS Pag. 48
Installation recommendation
Verify that the beam tower is fully watertight once the cover and end caps have been correctly filled at the end of the installation.
Use the cable glands supplied on the tower for all cabling must pass through the lower end cap using the cable glands supplied. The missed used of proper accessories decrease the IP grade protection of the
tower.
Avoid any type of obstruction between the transmitter and receiver.
Avoid installing the receivers beams in a position where direct sunlight, at the same angle as the receivers beams, can enter directly into optics especially at sunset and sunrise
Do not install multiple beams where the transmitter beam can interfere with other receiver beams. It is always better place either transmitter or receivers back to back.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 4
1. MAIN COMPONENT LIST
N° DESCRIPTION
1 Top cap
2 IR cover
3 Aluminium profile
4 Aluminium base
5 Motherboard IR
6 Optics TX/RX
7 Motherboard MW
TX/RX
8 Parable TX/RX
9 Heather
10 Terminal block
11 Supply board
12Vcc/24 Vac
12 DT3
1
2
3
4
5
6
7
8
9
10
11
12
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 5
2. ASSEMBLING THE CABLEPIT
7. Insert the highlighted edge into other section and fix with screws
8. Insert the third section in the same way and fix with screws.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 6
9. Enlarge the two opposite walls of cable pit to allow the positioning of last section.
10. Insert and well fix the missing screws.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 7
2.1 CABLE PIT POSITIONING
The placement of the cable pit for MANA columns, after assembling, have to be done in the following way:
cement all around the cable pit keeping the top edge of it at same level of ground.
POSSIBLE CORRECTION OF THE INCORRECT
POSITIONING
Placement should be perpendicular to the ground. If the base is not in perfectly at ground level, is possible to
adjust it through the insert regulation of cable pit.
On the side that must be corrected loosen the insert in order to get the right inclination.
CORRECT POSITIONING
BY ADJUSTING INSERTS
EXAMPLE
OF SETTING
WRONG POSITIONING
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 8
3. TRANSFORMER MOUNTING
Kit compodes by:
1 transformer 160VA with 2 output;
1 screw 8x60;
2 nut M8;
1 perforated plate;
1 plate;
2 black sheath insulating;
4 anchor screw barrier.
Move the screw 60mm, as shown in the figure, in the perforated plate and screw the bolt lock.
Place the plate in the cavity, especially left, so you can screw tighten the screws to the column and have enough
space for the battery. Screw the 4 screws
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 9
Insert the sheath, the transformer then again the sheath and plate and fix everything with the nut. Follow the
wiring instruction in the manual.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 10
POWER SUPPLY CABLE (PS01B)
N . DECRIPTION
Power Connectors
(terminal 8)
1-2 19 Vac Input to be connected to the transformer
3-4 13.8 Vdc Output for power infrared
5-6 24 Vac Input to be connected to the transformer
7-8 24 Vac Output to be connected to the heaters
1 2 3 4 5 6 7 8
1
2
3
4
5
6
1 2 3 4 5 6
7
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 11
NB: in case of power failure the battery is disconnected to prevent its deterioration if its voltage drops
below 10,6V.
1 Power Connector circuit
TX or RX
Connect Flat Cable to the power connector of the board of MW TX or
MW RX
2 Battery Connect with two-wire cable red / black to the battery
3 V-Test jumper Insert in position 1-2 to enable LED power supply, 5V 9V 13.8V. The 4th
Led called "Mains" is always on when the board is powered by the
transformator, it is off if the battery intervenes
4 0,5 A battery jumper Insert jumper when using batteries at or above 7 Ah.
N.B. Current limit for battery charging 0.5 A. Without jumper the current
limit load is 0.25 A
5 Heater fuse Normally installed 5 A delayed protecting heaters circuits.
6 Circuit fuse Normally it installed by 0.8 A slow, protecting Tx or Rx and infrared
circuits.
7 J7 It forces the output of the power supply 24 Vac for the heaters irrespective
of the temperature measured in the barrier.
N NAME DESCRIPTION
Terminal 6
1 GND Negative power.
2 T Test battery. By applying 5V you can verify that the battery has an output
voltage> 11.4Vdc. Such information is given on the "B" terminal.
3 B
High impedance output if the voltage supplied by the battery is
11.4Vdc.
This information is valid if "T" is on.
4 15 Output high impedance if the voltage is supplied from the 12.4Vdc.
5 24
Output high impedance if the voltage supplied from the transformer
terminals "24Vin" is 18Vac.
6 NC Not connected
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 12
5. CABLES AND WIRING
The wiring requires to SEPARATE the power cable 12Vdc (ex. 2x0.5 + Nx0.22),to the power cable for heaters
24Vac (ex. 2x0.75) to prevent input of disorders of the AC voltage on the barrier.
Note: is absolutely necessary to shield the cable that provides 12 Vdc power supply and
put the metal braid to ground.
The cable dimension depends on the columns consumption and on the same cable resistance, taking care about
installation distances.
Cable 230Vac (culomn power) Cable 12Vcc (sync + signal)
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 13
CONNECTION TO POWER SUPPLY
The connection between the transformer and the network at 230 V ~ must be made with conductors whose
section is of 1.5 mm². It is highly recommended to use a delayed fuse above 1 A.
The cable that carries power from the transformer to MANA must be as short as possible and must be
shielded with shield to negative.
The two wires must be connected to terminals 1-2 of the "power connector". The transformer to be used
must have the following characteristics:
Primary tension 230 V ~ Secondary 18/19 V ~ 1 A Secondary 24 V ~ 6 A Minimum power 160 VA
In the case of greatly disturbed network add an effective filter - power supply 230V 1 A.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 14
10.1 CONNECTION TO BACKUP BATTERY
Inside each column is provided space to house a rechargeable Lead up to 12V-7Ah. The battery is normally
recharged by the internal supply, via a current limiter.
FU
SE
A
FU
SE
B
FUSE A: 5A-24Vac FUSE B: 0,8A-13,8Vac
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 15
7. SERIAL CONNECTION TO ADEBUS
Each column can be connected via the RS485 bus to the control panel ADEBUS for planning, monitoring and
managing local or remote system.
For more information, refer to "Manual ADEBUS EXPLORER"
7.1 Connection to serial port for each column
ADEBUS
MES9C
column 2
MES9C
column 1
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 16
MICROWAVE
10.2 TX MOTHERBOARD
1 POWER SUPPLY The power connector is linked to power supplier via a flat cable.
2 MW CONNECTOR The connectors "MW" or Output 1 / 2 are used to connect the cavity
transmission. Normally uses the output "Output 1", and only in case of
double barrier microwave using the synchronized output "Output 2".
3 LED
The "Led insert jumpers", inserted in position 2-3, enables the power of
Led Output "and" Led VDC ", indicating the presence of their tensions.
Return after the test at rest 1-2. NB The "Output LED" has a lower
light intensity of Led VDC, when the cavity "TX" is inserted.
4 DIP SWITCH The "channel selector" allows you to select the desired channel by
switching to "ON".
NB The selected channel must be the same as that of the Circuit "Rx”.
1
4
3
2
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 17
RX MOTHERBOARD
1 Input Connector Mw connect the receiver cavity
2 OUTPUT
CONNECTOR
1 NC alarm contact
2 3
Tamper contact 4
3 POWER SUPPLY Piacere The power connector is connected to power via a flat cable.
4 DIP SWITCH 1
allows you to check the voltage supply, the value of sensitivity, goodness of
the signal, the walk test and the test alignment (see table previous page).
Permette di verificare le tensioni di alimentazione, il valore di sensibilità, la
bontà del segnale, il walk test e il test di allineamento
5 DIP SWITCH 2 choose the desired channel by switching to"ON". NB The selected
channel must be the same as that of the Circuit "Tx".cosi
6 LED CHANNEL indicates that the channel is tuned with the transmitter.
7 LED ALARM indicates that the system is not in alarm (when there is the alarm LED goes
off).
5
1
3
4
11
9 7 6 8
10
10
2
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 18
8 LED ALIGNMENT Red: weak signal
Yellow: signal fair
Verde: segnale forte
9 Voltmeter indicates the voltage in volts of the selected function (see table previous
page).
10 Trimmer (Guadagno, Walk Test, Sensibilità, Ritardo), regolazioni da effettuare durante
l’installazione
11 Buzzer
is activated with the "Walk Test" (selector functions):
Continuous beep = Alarm
Sound intermittently variable = Tell sensitive area
8.3 CONFIGURATION DIP SWITCH
1 LEDS Insert LED bar for Test Alignment
2 FIELD Display on LED bar signal Rx strength
3 OPEN Disconnect CAG (automatic gain control)
4 WALK Walk Test (skill the "Buzzer")
5 CAG View the gain value (optimum 4.5-6.5)
6 SENS Display Value Sensitivity (0 to 9)
7 5V Display 0.2 ± 5V supply
8 9V Display 0.2 ± 9V supply
9 13V Display 13.8 ± 0.3 supply
10 VOLT Input Voltmeter (to display items 5 ÷ 9)
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 19
8.4 CONNECTIONS AND DESCRIPTIONS CAVITY TX
AND RX
The switch located on the cavity Tx and Rx is positioned to OFF only after installation and after giving
voltage to the columns. The ON position, the active protection of the "receiver" cavity by electrostatic
discharge and damage resulting from installation.
8.5 SENSITIVE ZONE
The sensitive area depends on the distance Tx Rx, the sensitivity and the type of antenna. The diagram
below illustrates the sensitive area of diameter at half length as a function of total distance and
sensitivity.
L’altezza consigliata per installazioni di tipo classico è di circa 70 cm dal centro dell’antenna al suolo, con la
sensibilità media impostata.
L
D
X
X
X
X
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 20
0 2 4 6 8 10 12 14 16 18 20
0
10
20
30
40
50
60
70
80
90
NB: remember to adjust the sensitivity of "MANA" according to half width of the beams is desired. As the threshold is higher, the lower the sensitivity and
vice versa.
8.6 DEAD ZONE
The length of dead zones in the vicinity of the columns is on the same apparatus is the distance from the
ground, the sensitivity is set to the Rx circuit. The recommended height for installation of a conventional
type is approximately 70 cm from the center of the antenna to the ground, with the sensitivity set to medium.
0 50 100 150 200 250 300
0
2
4
6
8
10
12 Diameter in the middle (m)
Maximum sensitivity
Minimum sensitivity
Length is in meters
H equipment ground (cm)
Length of the dead zone in meters
Maximum sensitivity
Minimum sensitivity
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 21
8.7 START UP
8.7.1 TX COLUMN
After you remove the cover and shield, make connections to the mains power transformer and tamper
circuit.
1. Check the various connections: the power transformer to the circuit, the battery, the power circuit to circuit and transmitter cavities TX (See pp. 9, 12-13).
2. Power board, check the LED lights on Mains power adapter and three power LEDs with V-Test jumper inserted in position 1-2 (see pp. 12-13).
3. Turn OFF the switch which is on cavity TX. (See page 14). 4. Verify that is in position ON one of the four switches of the "channel selector" tab, TX (same as
RX) See page. 9.
5. Insert the jumper in position 2-3 to verify that LEDs output and VCC (see page 10). 6. Replace the two jumpers in the resting position.
8.7.2 RX COLUMN
After you remove the cover and shield, make connections to the mains power transformer and tamper
circuit.
1. Check the various connections: the power transformer to the circuit, the battery, the power circuit to circuit and transmitter cavities RX (Vedi pagg. 10-13).
2. Power board, check the LED lights on Mains power adapter and three power LEDs with V-Test jumper inserted in position 1-2 (Vedi pagg. 12-13).
3. Turn OFF the switch which is on cavity RX.(Vedi Pag.14). 4. Verify that is in position ON one of the four switches of the "channel selector" tab(same as TX)
(Vedi pagg. 10-11).
5. Check the "voltages" on the receiver, turning in ON position the switch N.10 "selector function", and displaying the desired tension (5, 9, 13.8 volts) with dip No 7-8-9 (See pp. 11-12).
Perform an initial visual alignment between the two columns (TX and RX).
Horizontal orientation: Loosen the screws and turn the column.
Vertical orientation: Loosen the screws of the handling system of the parable, and rotate.
Verify that on the board RX the leds alarm and Channel are on. Otherwise proceed with the electronic
alignment, however, be made to obtain a precise alignment.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 22
8.8 ALIGNMENT
Turn ON the dip of the "Selector Function" numbers 1,2 and 3, leaving all others to OFF.
Align horizontally and vertically then the parable of the receiver for maximum signal seen on
"Led test alignment”.
If the signal is too strong or too weak to act on the knob of the "gain" so that only the first four
LEDs light up red.
Rerun the orientation of the parabola RX. Once the maximum orientate the parable TX.
Goodness signal: Turn OFF the switching of the "selector functions" 1 and 2 and ON the numbers 3,5 and 10 for the Voltmeter display the gain value. The optimal values are between 4.5 and 6.5
volts.
AGC: position ON the switches numbers 1 and 2 of the "Selector Function", leaving all others to OFF. Check after about a minute that the 4 LEDs are lit red and 2 yellow LEDs for "Led test
alignment”,too.
Verify that on the board RX the leds alarm and Channel are on. Otherwise proceed with the electronic alignment.
8.9 WALK TEST
1. Turn the knobs "sensitivity" and "Delay" to the minimum and reposition to ¼ of winder.
2. Turn ON the microswitch of the "selector function" Number 4 leaving all others to OFF. This operation is inserted to signal the buzzer will sound continuously when there is an alarm (see pp.
11, 12), while with a variable sound intermittently when in a sensitive area. 3. In the absence of disturbance signal, turn the potentiometer Walk Test to the point where you
hear no sound. 4. Approaching the center of the cone of the sensitive area, the buzzer there evidence of an
intermittent sound. The sensitive area is represented by the graph on page 17. 5. Test of the acrossing, making sure the intermittent sound of the buzzer and then the long beep
and shutdown "LED Alarm" column on the Rx.
Buzzer no signal Intermittent signal
buzzer
Fixed signal buzzer
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 23
8.10 SENSIBILITY
The sensitivity adjustment potentiometer (see page. 11, 12) affects the alert threshold, the "sensitive
area" (see p.17) and "dead zone" (see p. 18).
NB sensitivity too high can cause false alarms, conversely a too low can prevent the detection of the small
intruders.
Turn ON the dips of the "selector function" Numbers 6 and 10, leaving all others to OFF. In this manner
is displayed on the Voltmeter sensitivity value.
Note that small values indicate a higher value of sensitivity:
0V=maximum sensitivity
9V=minimum sensitivity
Calibration is performed taking into account the user requirements.
Example: the system should not go into alarm when it is crossed by an animal of a certain size. Keep in
mind that high sensitivity can generate false alarms.
8.11 DELAY The potentiometer adjustment of the delay (see page. 11, 12) affect the crossing speed. To verify the delay
is necessary to experiment crossing at reduced speed. Remember that setting too high or low could cause
false alarms
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 24
INSTALLATIONS GUIDE
8.12.1 SECTORS
Having to design protection with volumetric barriers of a closed perimeter within a certain number of
sections that take into account the management need of the entire plant, it must be remembered that it is
always preferable to install an even number of sections. This consideration is bound to the fact that the
likely reciprocal interferences between adjacent sections are annulled should at the vertices of the
polygon (cross), resulting from the installation of the various sections, be installed two equipment with
the same name, two transmitters or two receivers. It is evident that this might occur only if the number
of sections is even.Should it not be possible to have an even number of sections then some careful
considerations must be made on interferences that might likely occur in order to find the vertex point
where retained best to place the transmitter near the receiver. The following pictures show some typical
cases for which the most correct solution is given.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 25
8.12.2 Particolar conditions
1. Ground conditions: It is inadvisable to install the equipment along sections with tall grass (more that 10cm), ponds, longitudinal waterways, and all those types of grounds whose structure
is rapidly mutable.
2. Obstacles: the fences, are generally metallic therefore highly reflecting hence causing various problems, for this reasons some precautions are suggested:
First of all, make sure that fence has been properly fixed in order that the wind does not
move.
If it is possible the microwave beam shouldn’t be placed in parallel to a metallic fence, is necessary to create a corner with it
Metal fences placed behind the equipment night cause distorsions to the sensitive beam especially, and might cause movement detection in unexpected spots, with subsequent
likely generation of false alarms.
In case of Mw barrier should be installed in a corridor between two metallic fences, the width of the corridor should be necessary not less to 5m.
Along the section, within the area of the protectiion field, are allowed pipes, poles or similiar as long as
their dimensions, with respect to the protection beam, are not too excessive. The trees, hedges, bushes in
general, need very great attention if near or within the protection sections.
10.3 MW CHARACTERISTICS
FREQUENCE 24 Ghz in K band
CHANNEL 4 Exchengeable
MODULATION ON-OFF
SENSIBILITY ADJUSTMENT Trimmer.
DELAY ADJUSTMENT Trimmer.
ALIGNMENT Eletronic with instruments on motherboard
OUTPUTS Alarm Relè (NC: 40 Ohm)
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 26
9. IR SECTION
9.1 CONNECTION TO TERMINAL BLOCK (MES9C)
Positive supply +10 – 30Vdc 1 12 12/24 Vac-cc Heaters supply
Negative supply GND 2 13 12/24 Vac-cc Heaters supply
Tamper output TMP 3 14 G.IN Negative input to exclude the
barrier for 1 minute
Tamper output TMP 4 15 AND
+12 Vdc to have
AND RX1+RX2
0V to AND RANDOM
Alarm output (NO) NA 5 16 BEAM +12 Vcc - exclude RX1
0 V - exclude RX1+RX2
Alarm output (NC) NC 6 17 S.LOW
NEGATIVE
OPEN COLLECTOR
open in case of fog
Alarm output (C) COM 7 18 A.MASK
NEGATIVE
OPEN COLLECTOR
open in case of masking
Positive sync
input (TX=>RX) + S IN 8 19 + S OUT
Positive sync
output (TX=>RX)
Negative sync input
(TX=>RX) - S IN 9 20 - S OUT
Negative sync
output (TX=>RX)
Not in use 10 21 Not in use
Not in use 11 22 Not in use
9
11 13 14 15 16
17 18 19
20
21 22
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Serial connection to
ADEBUS (pag. 11)
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 27
9.2 CONNECTION AND SETTINGS HEATERS
The power of the heaters is by default set to 24 V (ac or dc), but you can set it to 12 VDC repositioning the
jumper on MES9C and on each optical as shown.
24V
Heaters supply
24V 12V
MES9C
BOARD
OPTICAL
12V
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 28
9.3 SYNCHRONIZATION
9.3.1 Wired SYNC
RX TX RX TX RX TX
SYNC IN+ (Clamp 8)
SYNC OUT+ (Clamp 19)
SYNC IN+ (Clamp 8)
SYNC OUT+ (Clamp 19)
SYNC IN+ (Clamp 8)
SYNC OUT+ (Clamp 19)
SYNC IN- (Clamp 9)
SYNC OUT- (Clamp 20)
SYNC IN- (Clamp 9)
SYNC OUT- (Clamp 20)
SYNC IN- (Clamp 9)
SYNC OUT- (Clamp 20)
The synchronisms have to be connected according to the diagram above, the Sync out corresponds to the TX
part of the column and will have to be connected to the Sync in on the RX opposite one. You must also connect
the negative of power supply in common between the columns; so it is appropriate to use a shielded cable
alarm, 2x0, 22, to connect the sync and the screens to negative Vdc of power supply on both columns.
19
20
19
20
8
9
8
9
19
20
8
9
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 29
SINGLE BARRIER CABLINGS.
Note: SYNC OUT- and SYNC IN - should not be connected to ground but to the dedicated clamp
(terminal numbers are related to the image of p. 11).
DIP4 in OFF
1 2 3 4 5 6 7 8 9 10 11 12
ON
Canal RX
1 2 3 4
ON
Canal TX
1 2 3 4
ON
19
20
19
20
8
9
8
9
SYNC IN+ Clamp 8
SYNC OUT+ Clamp 19
SYNC IN+ Clamp 8
SYNC OUT+ Clamp 19
SYNC IN- Clamp 9
SYNC OUT- Clamp 20
SYNC IN- Clamp 9
SYNC OUT- Clamp 20
TX4
RX4
TX3
RX3
TX2
RX2
TX1
RX1
TX4
RX4
TX3
RX3
TX2
RX2
TX1
RX1
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 30
9.3.2 Optical SYNC
Position in ON DIP 4 on the bench of 12 and select the transmission channel 1 to 3 (default is set to channel 1),
on the bench of 4; the selected channel must be the same on both TX and RX boards.
Note: for information and for other configuration of MES9012, please check page 27.
DIP 4 in ON
1 2 3 4 5 6 7 8 9 10 11 12
ON
Canal RX
1 2 3 4
ON
Canal TX
1 2 3 4
ON
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 31
COLUMN
1
COLUMN
2
Canal TX
1 2 3 4
ON
Canal RX
1 2 3 4
ON
Canal TX
1 2 3 4
ON
Canal RX
1 2 3 4
ON
COLUMN 1 COLUMN 2
TX4
RX4
TX3
RX3
TX2
RX2
TX1
RX1
TX4
RX4
TX3
RX3
TX2
RX2
TX1
RX1
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 32
9.4 OPTICS CONFIGURATION
9.4.1 OPTICAL TX
1 2 3 4 5 6 7 1 2 3 4 5 6
TX1
ON
TX2
ON
TX3
ON
TX4
ON
Through DIP 7 in ON (as default) and lighted LED POWER is occur the correct operation of TX optics.
The power of the heaters is set by default to 24V; you can use 12V by changing the configuration of the jumper
(SW4).
The voltage can be both AC and DC.
Note: The settings and relative addresses are already set by Default.
TAMPER
POWER ON LED
HEATERS SUPPLY
24V
12V
TX1: Not in use in
the case of column
with 3TX
TX1 and TX2: Not
in use in the case of
column with 2TX
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 33
9.4.2 OPTICAL RX
1 2 3 4 5 6 7 1 2 3 4 5 6
RX1
ON
RX2
ON
RX3
ON
RX4
ON
Through DIP 7 in ON (as default) and lighted LED POWER is occur the correct operation of RX optics.
The power of the heaters is set by default to 24V; you can use 12V by changing the configuration of the jumper
(SW4).
The voltage can be both AC and DC.
In jumper J4 is possible to read the signal value in volts.
Note: The settings relating to addresses are already set to Default.
24V
12V
HEATERS SUPPLY
TEST SIGNAL POINT
J4
(FEEBLE) SIGNAL LED
TAMPER
RX1: Not in use in
the case of column
with 3RX
RX1 and RX2: Not
in use in the case of
column with 2RX
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 34
Default barriers with 2 or 3 RX are set during testing in the factory. In case you want to change the original
number of RX optics in the field it is necessary to set the DIP SWITCH six and seven as follows:
9.5 TX/RX SETTINGS 3 OPTICS
The setting of the DIP SWITCHES on the lenses is set:
1 2 3 4 5 6 7 1 2 3 4 5 6
1 2 3 4 5 6 7 1 2 3 4 5 6
RX2
ON TX2
ON
RX3
ON TX3
ON
RX4
ON TX4
ON
It should be set to ON the DIP on the motherboard RX exclusion 1
9.6 10 TX/RX SETTINGS 2 OPTICS
The setting of the DIP SWITCHES on the lenses is set:
1 2 3 4 5 6 7
1 2 3 4 5 6
1 2 3 4 5 6 7
1 2 3 4 5 6
RX3 ON
TX3 ON
RX4 ON
TX4 ON
It should be set to ON the DIP on the motherboard RX exclusion 1 + 2
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 35
9.7 COLUMN ALIGNEMENT
For proper alignment, once the barriers are installed, orient the optical of transmitters and receivers in the
direction of each other by adjusting the lens holder horizontally through the manual movement after loosening
the locking screw on the joint, and vertically through the front screw on the left side of the lens.
Vertical adjustment
Horizontal adjustment
N.B.: FASTEN THE UNLOCKED SCREW AFTER THE ADJUSTMENT
SCREW
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 36
9.8 CALIBRATION THROUGH SMA SYSTEM
1) Start the alignment of the transmitter is on the barrier by checking the position of the DIP switch 7 to ON and activating the TEST optics TX (1 or 2 or 3 or 4), by pressing the dedicated button for about 3 seconds
until the orange LED TEST will lit up.
2) Place in the corresponding optical TEST (1 or 2 or 3 or 4) on coral receiver, checking the position of the DIP switch 7 to ON and pressing the dedicated button for 3 seconds until the the BUZZER and the LED
TEST turns ON, (with high brightness)
3) Place the filter in front of the optic Transmitter you are aligning. It is recommended that the calibration with the use of the filter over long distances and
then search for the maximum signal.
TEST
BUTTON
DIP 7 ON
ORANGE
LED
DIP 7 ON
TO ACTIVATE
THE LED
DIP 7 ON
TO ACTIVATE
THE LED
TEST
BUTTON
DIP 7 ON
ORANGE
LED
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 37
4) Through the TRANSMITTER lens shifts, find the maximum optical alignment based on the Buzzer and LEDs (with high brightness), the increase in the frequency of flashing (until the LEDs is fix on and the
whistle of the corresponding BUZZER) indicate a better ALIGNMENT.
5) With a FULL rotation on the horizontal RX lens, is carried out the SCANNING of the optical signal.
6) Rotating the lens RX find the maximum value of ALIGNMENT corresponding to the LEDs (with high brightness) FIXED and the whistle of the BUZZER CONTINUOUS.
7) Exit the function of by repressing the ALIGNMENT TEST button for about 3 seconds on both optics (TX-RX) making sure that the orange LED TEST is shown in original condition.
NB: you can SEE the calibration value through the multimeter on each optical receiver. For this procedure, you
must have the pair of lenses (T-RX) in TEST.
TEST
BUTTON
ORANGE
LED
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 38
9.9 CALIBRATION WITH PARALLEL BEAMS
N.B.: during the testing phase of an optical transmitter the other TX not in test are switched off
automatically.
Tx4 RX4
Tx3 RX3
Tx2 RX2
Tx1 RX1
1) Put in test the optical TX1
and RX1 (if present see p.11-
12) and proceed with the
calibration as explained
2) Put in test the optical TX2
and RX2 (if present see p.11-
12) and proceed with the
calibration as explained
3) Put in test the optical TX3
and RX3 and proceed with
the calibration as explained .
4) Put in test the optical TX4
and RX4 and proceed with
the calibration as explained
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 39
9.10 CALIBRATION WITH CROSSED BEAMS
To activate this function, move ON DIP2 of 12 DIPSWITCH bench on MES9012.
1 2 3 4 5 6 7 8 9 10 11 12
ON
Tx3
Tx2
Tx1 RX1
Tx4
RX2
RX3
RX4
RX1
RX2
RX3
RX4
RX1
RX2
RX3
RX4
RX1
RX2
RX3
RX4
1) Put in test the optical TX1 and
RX1 (if present see p.11-12)
and proceed with the calibration
as explained on p. 13 and 14. REPEAT the setting of RX2,
RX3 and RX4. Make sure that it
still aligned with RX1.
2) Put in test the optical TX2 and
RX1 (if present see p.11-12)
and proceed with the calibration
as explained on p. 13 and 14. REPEAT the setting of RX2,
RX3 and RX4. Make sure that it
still aligned with RX1.
3) Put in test the optical TX3 and
RX1 and proceed with the
calibration as explained on p. 13
and 14. REPEAT the setting of RX2,
RX3 and RX4. Make sure that it
still aligned with RX1.
4) Put in test the optical TX4 and
RX1 and proceed with the
calibration as explained on p. 13
and 14. REPEAT the setting of RX2,
RX3 and RX4. Make sure that it
still aligned with RX1.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 40
9.11 SETTING AND PROGRAMMING MOTHER BOARD
1 SUPPLY LED Red
2 ALARM LED ALM Red
3 MASKING LED MASK Green
4 DISQ. LED S.LOW Green
5 HEATINGS LED HTR Yellow
6 SYNCHRONISM SYNC Yellow
7 TRIMMER Response time
adjustment
8 TEST J7
9 DIP SWITCH 12 Function selector
(pag. 23)
10 TAMPER
11 DIP SWITCH TX
12 DIP SWITCH RX
3
4
5
6
8
7
1
2
9
12
11
10
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 41
9.12 LED FUNCTIONING
The motherboard has six LED signaling and control, which can be activated via the dip switches 12 on the
board MES9012S dedicated in the ON position.
It is recommended that at the end of the testing set dip switches in the OFF position, both to avoid a glimpse of
the signals, both to reduce consumption of the system.
POWER
Supply led
The SUPPLY LED is the only one to always be on in normal
conditions of operation, confirm that the card is properly powered.
LED ALM
Alarm led
Normally off, in the event of ignition, indicates the alarm status. The
alarm condition will depend on the setting of the jumpers composing
the board and the delay time set on trimmer SPEED will be adjusted
from a minimum of 50 msec to 500 msec. Increasing clockwise.
LED MASK
Signals of Masking
The ignition of the MASK LED indicates the presence of an infrared
signal modulated not desired. On the terminal, in the presence of an
attempt to blindness, it can obtain the signaling ANTIMASK.
N.B.: In normal operation the LED should be OFF.
In the event that is either on or flashing check the setting of the jumpers
for selecting beam on the various transmitters.
LED SIG LOW
Indicates the low level of signals
(fog presence)
The lighting SIG LOW LED indicates the presence of FOG INTENSE.
In the presence of intense fog before having an alarm condition due to
lack of signal, the LED SIG LOW lights on the terminal and you can
have the message DISQUALIFICATION.
N.B.: By placing the jumper SIG LOW in the ON position, and by the
intervention of the disqualification is obtained the exclusion of the
barrier, which will return to work as soon as the fog lifts.
LED HTR
Indicates the heaters functioning
The automatic heating system, electronically controlled to ensure in all
climatic conditions an internal temperature between 17 ° C and 22 ° C.
Normally off, when turned on the heater is on.
LED SINC
Indicates the functioning of the
synchronism
The LED SINC continuously flashing indicates the proper operation
and wiring of sync both outgoing and incoming.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 42
9.13 CHARACTERISTICS AND DIP SWITCHES SET
The motherboard has several configurations programmable via dip switches.
DIP SWITCH 12 DIP
1
RND DLY
ON
In the ON position the alarm from time to time is generated with a random delay varying
from 0 to 1 sec
This function serves to confuse and mislead the intruder who wants to identify the
detection system
HEATER
TEST
Turn ON and OFF DIP1 for 3 times in order to switch on heaters for 20 min bypassing
thermostat.
2 CROSSING In the ON position activates the detention Crossed beams
3 A.CRAWL
In the ON position it has the "normal" operation of the barrier, set to OFF mode is
activated to "ANTI CRAWLING" means that the darkening of the radius RX1 (the first
down) for at least 2 sec. causing the alarm condition, regardless of whether it was
previously set to OR or AND.
4 SYNC Irrelevant.
5 DISQ In the ON position activates the disqualification (with at least two optics that detect a low
signal).
6 BEAM OFF
1 + 2
In the ON position you get the exclusion of the first two rays starting from the bottom
while the remaining rays continue to operate. The function can also be programmed
remotely giving a positive control on the 12V + terminal of the terminal block marked
BEAM. If you want to enable this function remotely DIP6 must remain OFF.
7 BEAM OFF
1
In the ON position is obtained the exclusion of the first beam in the bottom, while the
remaining continue to function.
The function can also be programmed remotely giving a negative command 0 V on
terminal marked BEAM ON on the terminal block MES9C.
If you want to enable this function remotely DIP7 must remain OFF.
8 AND 1 + 2
In the ON position is obtained the AND function of the first two receivers, that is to say
that both must be interrupted to generate the alarm condition, while the remaining Rx
remain be alarmed individually.
This configuration can be useful in the presence of tall grass or small animals.
The function can also be programmed remotely giving a positive command +12V on the
terminal marked AND.
If you want to enable this function remotely DIP8 must remain OFF.
9 AND RND
In the ON position is obtained the AND between two random Rx, ie that to have an alarm
condition should always be alarmed at least two Rx among all those used.
The function can also be programmed remotely giving a negative command 0 V on the
terminal block labeled AND.
If you want to enable this function remotely DIP9 must remain OFF.
10 ANTIMASK In the ON position the enable function ANTI MASKING (ANTIMASK activating the
output on the terminal MES9C.
11 CLOSE
RS485
In the ON position closes the RS485 communication. To finish you need to put in ON
only the switches of the column as far as the entire line.
12 LEDS In the ON position activates the LEDs.
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 43
JUMPER J7
If the disqualification function is activeted, you can increase the sensitivity of the disqualification by jumper J7
4 DIP SWITCH TX
TEST TX
By setting all DIP to OFF will turn off all transmitters of the column; moving all DIP ON
transmitters are activated at high frequency in order to allow a first visual contact between
transmitter and receiver in case of difficulties at great distances.
1 CH 1 ON Wire sync: normal operation of transmitter
OFF Optical sync: operation with transmission frequency 1
2 CH 2 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 2
3 CH 3 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 3
4 CH 4 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 4, only 2 transmitter active
4 DIP SWITCH RX
TERMINAL
and only TX
By setting all DIP to OFF will turn off all transmitters of the column; moving all DIP ON
transmitters are activated at high frequency in order to allow a first visual contact between
transmitter and receiver in case of difficulties at great distances.
1 CH 1 ON Wire sync: normal operation of transmitter
OFF Optical sync: operation with transmission frequency 1
2 CH 2 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 2
3 CH 3 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 3
4 CH 4 ON Wire sync: not in use
OFF Optical sync: operation with transmission frequency 4, only 2 transmitter active
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 44
9.14 REACTION TIME ADJUSTMENT
There is a potentiometer to adjust the TIME OF INTERVENTION. In particular, you can set the barrier for the
rapid alert system (cross running) or slow (cross by walk).
By adjusting the potentiometer counterclockwise to increase the trip time up to 500ms. In this condition ensures
that the alarm of a person walking through the barrier, with the advantage of excluding the possibility of any
false alarms (ex. animals).
Adjusting the potentiometer clockwise decreases the trip time until 50ms. In this condition
ensures the alarm of a person crossing the barrier running at maximum speed
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 45
9.15 TECHNICAL SPECIFICATION IR
OPTICS Impulsive double lenses 950 nm
DISQUALIFICATION Automatic with signaling out, open collector negative
MASKING Detection of blindness by another infrared signal by signaling out, open
collector negative.
OPERATING TEMPERATURE - 25°C / + 65°C. Available Kit heaters for temperatures down to -50 ° C.
ADJUSTMENT ANGLE 10° vertical – 180° horizontal
DETECTION OPTIONS And/Or on Rx / AND 1° + 2°.
BEAMS EXCLUSION 1° / 1° + 2°
REMOTE CONTROLS AND Random / AND 1° + 2° beam / exclusion 1° o 1° e 2°
10. DT3 SECTION
10.1 DETECTION AREA
Regolando opportunamente la sensibilità è possibile coprire completamente le zone morte immediatamente
sottostanti e sovrastanti la parabola MW.
IR IR
MW
3
DT3 DT3
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 46
10.2 PROGRAMMING & START UP
Connect the power supply respecting the polarity (10-30V), and make the connections Alarm output
according to your needs.
1 SUPPLY 10-30 Vcc – GND 3 SBY
(Positive input) The system is inhibited and gives no signal if the positive is connected
5 ALARM (NC output)
It opens in case of alarm generated by MW
7 DIP SWITCHES System Configurations
8 TRIMMER MW MW sensitivity adjustment
10 RED LED (alarm)
It lights up in case of general alarm
12 GREEN LED (MW)
It lights up in case of MW alarm
13 MICROWAVE 24Ghz MW SENSOR
POWER LED FOR DETECTION TEST: Activate
with the Dip Switch number 4 the functionality of
detection LED.
1 2 3 4
ON
NB: turning on for a duration of about 30 seconds if the
DIP4 of the LEDs is activated you will see a flashing
alternately, of these, for the stabilization of the system.
At the end of flashes you can proceed with the next
settings..
Setting trimmer RANGE SENSITIVITY MW (range 1-8 m) : Adjust through the
trimmer the range of MW, by implementing crossover trials. The LED signaling GREEN
will help to verify the detection of the passage in different areas (example. 1 m, 4 m, 8 m).
3
1
8
10
13
5
7
12
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 47
10.3 FIXED FUNCTION ADJUSTMENT
PET IMMUNITY
The pet immunity system is able to discriminate the small animals up to a maximum of 7 kg and to not give an alarm signal. In the case of the area with high presence of animals, such as dogs and cats, however, carry out tests for the correct adjustment.
SELF DIAGNOSYS
The system performs a check every 50sec of the micronda functionality. In case of malfunction it is signaled by the flashing of dedicated LED (GREEN)
10.4 TECHNICAL CHARACTERISTICS DT3
Microwave 24 Ghz
MW adjustable range from 1m to 8m RF immunity up to 2Ghz
Pet Immunity MW Digital signal processing
Technology MW operation Self-diagnosis Programming Dip-Switches
Microwave 24 Ghz
MW adjustable range from 1m to 8m RF immunity up to 2Ghz
Pet Immunity MW Digital signal processing
-
Politec Srl | Manual MANA DT SMA + DT3 – Ver 2.5.2 48
11. BARRIER TECHNICAL CHARACTERISTICS
OUTDOOR RANGE MAX 250 m
DIMENSIONS High
from 100 to 300 cm Width 25 cm
P 20 cm
PESO Variabile Da 10 a 20 kg per barriera
OPERATING TEMP. - 25°C / + 65°C.
SUPPLY 230Vac 50hz
HEATERS 24 Vac (Internal supplier)
ELECTRONIC COMP. 13.8 Vdc (Internal supplier)
POWER CONS. 13.8Vdc Tx e Rx = 290 mA per column 24Vac Tx e Rx = 200W per column
OUTPUT Alarm relay and Tamper relay
OPERATING TEMP. - 25°C / + 65°C.
SUPPLY 230Vac 50hz
HEATERS 24 Vac (Internal supplier)
ASSISTENZA TECNICA: +39 039 9081616