CE1G2406E SIGMAGYR ® RVP Installation and Commissioning RVP97... 1. Notes 1.1 Place of installation In a dry space (e.g. the boiler room), on a control panel or control panel rail, on the control panel fa- cia or in the sloping front of a control desk. The controller must not be exposed to dripping water. Permissible ambient temperature: 0...50 °C. 1.2 Electrical installation The local standards and regulations for electrical instal- lations must be observed. Cable tension relief must be ensured. The wires from the controller to the actuator and the pumps carry mains voltage. The wires from the controller to the detectors carry protective low voltage. The permissible cable lengths for all detectors are the following: Copper cable 0.6 mm dia. 20 m max. Copper cable 1.0 mm 2 80 m max. Copper cable 1.5 mm 2 120 m max. The cables to the detectors should not be run paral- lel to mains carrying cable (e.g. power supply for the pumps). 2. Installation and wiring 2.1 Wall mounting 1. Separate base from the controller by loosening the two fixing screws on the front of the controller (Fig. 1). 2. Fit base to the wall (Fig. 2) or to a DIN mounting rail (Fig. 3). 3. Wire base according to the plant wiring diagram. 4. Place the controller on the base and secure by tightening the two fixing screws on the front of the controller. 2.2 Flush panel mounting 1. Separate base from the controller by loosening the two fixing screws on the front of the controller (Fig. 1). 2. Remove terminal strips from the base (Fig. 4). 3. Wire the terminal strips. Make certain the cables will be sufficiently long, allowing the control panel door to be opened and the wired terminal strips to be moved about. 4. Introduce terminal strips through the panel cutout and plug them into the controller (Fig. 5). In that case, the base will no longer be required. 5. Place controller in the panel cutout and secure (Fig. 6). Note: tighten the fixing screws only slightly! 1 2 3 4 5 6

Upload: others

Post on 24-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E

SIGMAGYR® RVP

Installation and Commissioning RVP97...

1. Notes1.1 Place of installation• In a dry space (e.g. the boiler room), on a control

panel or control panel rail, on the control panel fa-cia or in the sloping front of a control desk.

• The controller must not be exposed to drippingwater.

• Permissible ambient temperature: 0...50 °C.

1.2 Electrical installationThe local standards and regulations for electrical instal-lations must be observed.Cable tension relief must be ensured.The wires from the controller to the actuator and thepumps carry mains voltage.The wires from the controller to the detectors carryprotective low voltage.

• The permissible cable lengths for all detectors arethe following:

– Copper cable 0.6 mm dia. 20 m max.– Copper cable 1.0 mm2 80 m max.– Copper cable 1.5 mm2 120 m max.

• The cables to the detectors should not be run paral-lel to mains carrying cable (e.g. power supply forthe pumps).

2. Installation and wiring2.1 Wall mounting1. Separate base from the controller by loosening the

two fixing screws on the front of the controller(Fig. 1).

2. Fit base to the wall (Fig. 2) or to a DIN mountingrail (Fig. 3).

3. Wire base according to the plant wiring diagram.4. Place the controller on the base and secure by

tightening the two fixing screws on the front of thecontroller.

2.2 Flush panel mounting1. Separate base from the controller by loosening the

two fixing screws on the front of the controller(Fig. 1).

2. Remove terminal strips from the base (Fig. 4).3. Wire the terminal strips. Make certain the cables

will be sufficiently long, allowing the control paneldoor to be opened and the wired terminal strips tobe moved about.

4. Introduce terminal strips through the panel cutoutand plug them into the controller (Fig. 5). In thatcase, the base will no longer be required.

5. Place controller in the panel cutout and secure(Fig. 6).Note: tighten the fixing screws only slightly!

1 2 3

4 5 6

Page 2: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

2 CE1G2406E

3. Functional check1. DO NOT switch on power yet!2. With wall mounting: separate controller from the

base.With flush panel mounting: separate terminal stripsfrom the controller.

3. Check wiring to make certain it is in compliancewith the plant wiring diagram.

4. Fit controller or terminal strips, depending on themethod of installation.

5. Check the regulating unit: Seat or slipper valve:– Ensure it is correctly fitted (observe direction of

flow indicated on the valve body)– Make certain the slipper operates in the correct

range (note position indicator)– Ensure the manual adjuster is disengaged

6. Note with underfloor and ceiling heating systems:the limit thermostat must be correctly set. Duringthe functional check, the flow temperature must notexceed the max. permissible level (usually 55 °C).If that is the case, proceed immediately as follows:– Close the seat or slipper valve manually– Switch off the pump– Close the pump isolating valve

7. Switch on power.The display must show something (e.g. the time ofday). If that is not the case, the cause is probablyone of the following:– No power– Main fuse blown– Manual switch not in position ΙΙ

3.1 Detector testThe detector test or the display of the actual tempera-ture is activated by pressing the TEMP button. PressTEMP several times. First, the 5 adjusted set valuetemperatures appear, then the 8 following temp.:

Display Detector VG1-VG6

VG0

TEMP 1 D.h.w. temperature detector 1 /Primary return temp. detector 2Remote telephone switch

B31 B11

TEMP 2 D.h.w. temperature detector 2Secondary return temp. detector 2

B3 B3

TEMP 3 Primary return temperature detector B7 B7

TEMP 4 Secondary return temperature detec-tor / D.h.w. charging detector

B71 B71

TEMP 5 Secondary flow temp. detector B1 B1

TEMP 6 Flow temp. detector heating circuitFlow temp. detector d.h.w. circuitPrimary return temp. detector 2

B11 B11

TEMP 7 Outside detector B9 B9

TEMP 8 Room temperature detector A6 A6

Check:If, in case of display of an actual temperature, o o oappears in place of the temperature, the respectivedetector has a short-circuit.If, in case of display of an actual temperature, - - - ap-pears in place of the temperature, the respective de-tector is not connected.The detector test mode can be quit either immediatelyby pressing one of the operating mode buttons, orautomatically after about eight minutes.

3.2 Relay test

Button Display Relay Effect

0 + Relay test modeactive

1 +

Q1 Heating circuitpump 1 on

2 +

Q3 /Y3

D.h.w. chargingpump on

3 +

Q4 Storage tankcharging pumpon

4 +

Q5 D.h.w. circulatingpump on

5 + 5:XX

5:XX

5:XX

Y1Y2 Control valve

opens

Control valvecloses

6 + 6

6

6

Y11Y22

Valve openingValve closing

The relay test mode can be quit immediately bypressing any of the operating mode buttons, or auto-matically after about eight minutes.

Note:– Test step 5

XX = valve position according to stroke model (in %)– Terminal Y4 is always under voltage when Q3/Y3 is

deenergized!

4. Enduser settingsThese are settings that can be made to meet individualneeds. They are directly accessible from the user inter-face. For procedure, please refer to the operating in-structions supplied with each controller.

5. Installer settingsThese are plant-related settings that should only bechanged by the heating installer. They are subdividedinto different groups that can only be selected bypressing combinations of buttons (please refer to thetable below).The display shows the selected group, the parameterand the adjusted value.

Combination ofbuttons

Function

1 + Selecting group C, F or H

2 +

5 Sek.

Selecting group UNote: first, select button combination 1

3 +

+

Selecting the parameters of the groupNote: forward and reverse selectionpossible

4 Adjusting the values

The parameter setting level can be quit either imme-diately by pressing one of the operating mode buttons,or automatically after about eight minutes.Factory-set parameters:Plant diagram VG1

Page 3: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 3

5.1 Plant diagram VG0

Heating circuit control with heating circuit pump, d.h.w. control with second heat transfer station and preheating.

5.1.1 Recommended components

• Fast-running actuator for valve Y11: SKD32.21; SQS35.53• Temperature detector B11: must be very fast

(use immersion type detector with no pocket! )• Temperature detector B3: required for fast controlled systems (fast heat exchangers)

5.1.2 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 0 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost (H-bus master) 10 0...15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temperatureacc. to U4

C8 Not used -

C9 Not used -

5.1.3 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for poorly insu-lated buildings

F6 Switching differential room temperature limitation with roomunit

0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value boost with boost heating 5 0…15 °C

2406S11 / VG0

B1

B71B9

Y1B7

A6

M1

M5

B3

B11Y11 B31

T

T

T

TT T

T

T

Page 4: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

4 CE1G2406E

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential between flow temperature androom temperature set value (F14)

6 0…30 °C

5.1.4 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Valuesset

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 No function -

H5 (Function acc. to U18) -

H6 No function -

H7 (Function acc. to U19) -

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Not used -

H12 Not used -

H13 Not used -

H14 Not used -

5.1.5 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Valuesset

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemperature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temp. 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential of primary andsecondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke %

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Popen for valve Y11Control gain (KP), multiplied by running time open , dividedby 5 ⇒ For SKD32.21 (30 s open/10 s close), SQS35.53(35 s open/close)

SKD:15

SQS:17

0…255 Contr. system oscillates:reduce setting valueContr. system too slow:increase setting value

U15 Integral action time of valve Y11 60 30/60/120/240

s

U16 Pclosed for valve Y11Control gain (KP), multiplied by running time close , dividedby 5 ⇒ For SKD32.21 (30 s open/10 s close), SQS35.53(35 s open/close)

SKD: 5

SQS:17

0…255 Contr. system oscillates:reduce setting valueContr. system too slow:increase setting value

U17 Limitation of return temperature differential between primaryand secondary circuit during d.h.w. charging

0 00.5...50

PassiveActive

°C

U18 Derivative action time, d.h.w. charging, VG0 1 0...15 s

U19 Authority of cold water detector B3, VG00.5 °C per controller sampling rate of 2 s

4 0...15

Page 5: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 5

5.2 Plant diagram VG1 (factory-setting)

Heating circuit control with heating circuit pump, d.h.w. temperature control with d.h.w. pump

5.2.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 1 0…6 Acc. to plant diagram VG...

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost (H-bus master) 10 0...15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp.acc.to U4

C8 Not used -

C9 Not used -

5.2.2 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperautre 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

VG1 B71

B1

B9

Y1 B7

A6

M1

M3

TT

T

TT2406S14

BW1

B3

B31

M5

T

T2406S21

BW2B3

B31 M5

M4

T

T

TB71

2406S22

Page 6: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

6 CE1G2406E

F15 Min. temperature differential between flow temperature androom temperature set value with convectors (F14)

6 0…30 °C

5.2.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Values set

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 °C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging setvalue

H7 Switching differential d.h.w. 8 0…15 °C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temperature with d.h.w. charging(for M4)

50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temperature during the legionella func-tion

65 01…80

PassiveActive

°C

H14 Pump overrun time of M4 (after M3) 0 0...15 min

5.2.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Values set

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemperature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temperature 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential of primary andsecondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke%

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Not used -

U15 Not used -

U16 Not used -

U17 Limitation of return temperature differential between primaryand secondary circuit during d.h.w. charging

0 00.5...50

PassiveActive

°C

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 7: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 7

5.3 Plant diagram VG2

Heating circuit control with main pump and changeover valve for d.h.w. control

5.3.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 2 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost (H-bus master) 10 0...15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc. toU4

C8 Not used -

C9 Not used -

5.3.2 Paramete settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

VG2B71

B1

B9

Y1 B7

A6

M1Y3

T

T

T

T T2406S15

BW1

B3

B31

M5

T

T2406S21

BW2B3

B31 M5

M4

T

T

TB71

2406S22

Page 8: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

8 CE1G2406E

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential between flow temperature androom temperature set value with convectors (F14)

6 0…30 °C

5.3.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Values set

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 °C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging setvalue

H7 Switching differential d.h.w. 8 0…15 °C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temp. with d.h.w. charging (for M4) 50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temp. during the legionella function 65 01…80

PassiveActive

°C

H14 Pump overrun time for M4 (after M3) 0 0...15 min

5.3.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Values set

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemperature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temperature 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential of primary andsecondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke %

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Not used -

U15 Not used -

U16 Not used -

U17 Limitation of return temperature differential between primaryand secondary circuit during d.h.w. charging

0 00.5...50

PassiveActive

°C

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 9: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 9

5.4 Plant diagram VG3

Heating circuit control with mixing valve and heating circuit pump, d.h.w. control with d.h.w. pump

5.4.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 3 1…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost mixing circuit and H-bus master 10 0…15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc. toU4

C8 Not used -

C9 Not used -

5.4.2 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

VG3 B71

B1

A6

M1

Y11

B11 T

T

T

T

B9

Y1 B7

M3

T

T2406S16

BW1

B3

B31

M5

T

T2406S21

BW2B3

B31 M5

M4

T

T

TB71

2406S22

Page 10: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

10 CE1G2406E

F15 Min. temp. differential between flow temp. and room temp.set value with convectors (F14)

6 0…30 °C

5.4.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Valuesset

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 °C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging set value

H7 Switching differential d.h.w. 8 0…15 °C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temp. with d.h.w. charging (for M4) 50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temperature during the legionella func-tion

65 01…80

PassiveActive

°C

H14 Pump overrun time for M4 (after M3) 0 0...15 min

5.4.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Valuesset

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemperature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temp. 7 0…39.5

U8 Max. set value of return temp. with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential of primary andsecondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke%

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Popen for valve Y11Control gain (KP), multiplied by running time open ,divided by 5

72 0…255 Controlled system oscillates: reducesetting value/Controlled system tooslow: increase setting value

U15 Integral action time valve Y11 60 30/60/120/240

s

U16 Pclosed for valve Y11Control gain (KP), multiplied by running time close , dividedby 5

72 0…255 Controlled system oscillates: reducesetting value/Controlled system tooslow: increase setting value

U17 Limitation of return temperature differential between primaryand secondary circuit during d.h.w. charging

0 00.5...50

PassiveActive

°C

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 11: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 11

5.5 Plant diagram VG4

Heating circuit control with heating circuit pump, d.h.w. control with mixing valve and d.h.w. pump.

5.5.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 4 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost mixing circuit and H-bus master 10 0…15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc.to U4

C8 Not used -

C9 Not used -

5.5.2 Parameter settings F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential between flow temperature androom temperature set value with convectors (F14)

6 0…30 °C

VG4

B1

B9

Y1 B7

A6

M1

M3

Y11

B11

T

T

T

T

T

B71

T

2406S17

BW1

B3

B31

M5

T

T2406S21

BW2B3

B31 M5

M4

T

T

TB71

2406S22

Page 12: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

12 CE1G2406E

5.5.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Valuesset

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charg-ing

0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 °C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging set value

H7 Switching differential d.h.w. 8 0…15 °C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temeprature with d.h.w. charg-ing (for M4)

50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temperature during the legionellafunction

65 01…80

PassiveActive

°C

H14 Pump overrun time for M4 (after M3) 0 0...15 min

5.5.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Valuesset

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemperature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temp. 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charg-ing

50 8…119.5 °C

U9 Limitation of return temperature differential of primaryand secondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke %

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Popen for valve Y11Control gain (KP), multiplied by running time open ,divided by 5

72 0…255 Controlled system oscillates:reducesetting value/Controlled system tooslow: increase setting value

U15 Integral action time valve Y11 60 30/60/120/240

s

U16 Pclosed for valve Y11Control gain (KP), multiplied by running time close ,divided by 5

72 0…255 Controlled system oscillates:reducesetting value/Controlled system tooslow: increase setting value

U17 Limitation of return temperature differential of primaryand secondary circuit during d.h.w.

0 00.5...50

PassiveActive

°C

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 13: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 13

5.6 Plant diagram VG5a

Heating circuit control with heating circuit pump, d.h.w. control with second heat transfer station and d.h.w. pump.

5.6.1 Parameter settings group C - „General parameter“

No. Function Recomm.setting

Range Remarks Unit Valuesset

C1 Type of plant 5 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost mixing circuit and H-bus master 10 0...15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc.to U4

C8 Not used -

C9 Not used -

5.6.2 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Valuesset

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temeprature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

VG5a

B1

B9

B7

M3

B11

T

T

T

T

B71T

Y11

M1

Y1

TA6

• For the d.h.w. diagrams 1.) and 2.) no special set-tings are required!

• For d.h.w. diagram 3.):Parameter H5 should be set as follows:

H5 (H7

21)≈ +

⇒ H5 only permits even setting values; select the nexthigher value for H5 !(Example: H7=8: H5 = 8/2+1 = 5 ⇒ Setting: H5 = 6)

1.) BW1

B3

B31

M5

T

T2406S21

2.)

BW2B3

B31 M5

M4

T

T

TB71

2406S22

3.)

BW2B3

B31 M5T

T

2406S22

Page 14: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

14 CE1G2406E

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential of flow temperature and roomtemperature set value with convectors (F14)

6 0…30 °C

5.6.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Valuesset

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 2°C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging set value

H7 Switching differential d.h.w. 8 0…15 1°C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temp. with d.h.w. charging (for M4) 50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temp. during the legionella function 65 01…80

PassiveActive

°C

H14 Pump overrun time for M4 (after M3) 0 0...15 min

5.6.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Valuesset

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point const./shifting max. set value of return temp. 10 -10…20 °C

U7 Slope of shifting range max. set value of return temp. 7 0…39.5

U8 Max. set value of return temp. with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential between primaryand secondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke %

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Popen for valve Y11Control gain (KP), multiplied by running time open , dividedby 5

72 0…255 Controlled system oscilates:reducesetting value/Controlled system tooslow: increase setting value

U15 Integral action time valve Y11 60 30/60/120/240

s

U16 Pclosed for valve Y11Control gain (KP), multiplied by running time close , dividedby 5

72 0…255 Controlled system oscilates:reducesetting value/Controlled system tooslow: increase setting value

U17 Not used -

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 15: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 15

5.7 Plant diagram VG5b

Heating circuit control with heating circuit pump and direct d.h.w. control.

5.7.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Values set

C1 Type of plant 5 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost mixing circuit and H-bus master 10 0...15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc. to U4

C8 Not used -

C9 Not used -

5.7.2 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Values set

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temperature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temperature limitation with roomunit

0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

VG5b

B1

B9

B7T

T

T

B71

TM1

Y1

2406S19

B3

B31

M5

T

T

Y3

A6

T

Page 16: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

16 CE1G2406E

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential between flow temperature androom temperature set value with convectors (F14)

6 0…30 °C

5.7.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Values set

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Not used -

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging setvalue

H7 Switching differential d.h.w. 8 0…15 1°C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Not used -

H12 Not used -

H13 Set value of d.h.w. temperature during the legionellafunction

65 01…80

PassiveActive

°C

H14 Not used -

5.7.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Values set

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of returntemeprature

10 -10…20 °C

U7 Slope of shifting range max. set value of return temperature 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential between primaryand secondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke %

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Not used -

U15 Not used -

U16 Not used -

U17 Not used -

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 17: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 17

5.8 Plant diagram VG6

Heating circuit control HK1 with heating circuit pump, heating circuit control HK2 with mixing valve and heating circuitpump, d.h.w. control with d.h.w. pump.

5.8.1 Parameter settings group C - „General parameters“

No. Function Recomm.setting

Range Remarks Unit Valuesset

C1 Type of plant 6 0…6 Acc. to plant diagram VG…

C2 Bus address 0 01…715

StandaloneSlaveMaster

C3 Set value boost mixing circuit and H-bus master 10 0…15 °C

C4 Pump overrun time 4 0…7.5 min

C5 Display 1 01

Outside temperatureTime of day

C6 Pump Q1 0 01

Heating circuit pumpMain pump

C7 H4 function 0 01

Ymin functionMin. flow temp. acc.to U4

C8 Slope of heating circuit 2 8 0...39.5 8 - for underfloor heating cir-cuit15 - for radiator circuit

C9 Weekly program heating circuit 2 1 01

PROG1PROG2

5.8.2 Parameter settings group F - „Heating circuit“

No. Function Recomm.setting

Range Remarks Unit Valuesset

F1 Min. limitation of flow temperature 8 8…119.5 °C

F2 Max. limitation of flow temperature 95 8…119.5 °C

F3 Room temperature detector 1 01

PassiveActive

F4 Room temeprature compensation 4 01…15

PassiveActive

F5 Optimum start control and quick setback with no room unit 8 0…15 Smaller for buildings withpoor insulation

F6 Switching differential room temp. limitation with room unit 0 0…15 ¼ °C

F7 Type of building structure 1 01

HeavyLight

F8 Adaptation of heating curve 0 01

PassiveActive

F9 Frost protection for the plant 1 01

PassiveActive

F10 Max. forward shift for optimum start control 0 010…150

PassiveActive

min

F11 Max. forward shift for optimum stop control 0 010…150

PassiveActive

min

F12 ECO extension 0 0…150 min

F13 Room set value temperature boost with boost heating 5 0…15 °C

VG6

B1

B9

Y1 B7

M5

M3Y11

T

T

T

A6T

M1

HK2 HK1

B11 T

B71

T

2406S20

BW3

B3

B31 T

T2406S23

BW4B3

B31

M4

T

T

TB71

2406S24

Page 18: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

18 CE1G2406E

F14 Type of heating system 1 012

ConvectorsRadiatorsUnderfloor

F15 Min. temperature differential between flow temperature androom temperature set value with convectors (F14)

6 0…30 °C

5.8.3 Parameter settings group H - „D.h.w.“

No. Function Recomm.setting

Range Remarks Unit Valuesset

H1 D.h.w. charging time 1 012

PROG1PROG224h/day

H2 Enabling of d.h.w. charging 1 01

Once/daySeveral times/day

H3 D.h.w. circulating pump 1 012

PROG1PROG224h/day

H4 Enabling of d.h.w. circulating pump during d.h.w. charging 0 01

EnabledDisabled

H5 Boost with d.h.w. charging 16 0…30 °C

H6 Set value of flow temperature during d.h.w. charging 1 01

Max. selectionD.h.w. charging set value

H7 Switching differential d.h.w. 8 0…15 °C

H8 D.h.w. priority 0 012

None (parallel)ShiftingAbsolute

H9 Delay time for d.h.w. priority, shifting 3 0…15 min

H10 Heating circuit locking time with d.h.w. charging, shifting 10 0…150 min

H11 Min. actual value of flow temp. with d.h.w. charging (for M4) 50 8…119.5 °C

H12 D.h.w. charging detector (B71) 0 01

NoYes

H13 Set value of d.h.w. temperature during the legionellafunction

65 01…80

PassiveActive

°C

H14 Pump overrun time for M4 (after M3) 0 0...15 min

5.8.4 Parameter settings group U - „Precontroller“

No. Function Recomm.setting

Range Remarks Unit Valuesset

U1 Control gain KP of primary control valve Y1 3 1…25.5

U2 Integral action time of primary control valve Y1 60 30/60/120/240

s

U3 Running time of primary control valve Y1 120 0 …255 s

U4 Min. limitation of secondary flow temperature 0 0…119.5 °C

U5 Max. set value of return temperature, constant range 50 8…119.5 °C

U6 Inflection point constant/shifting max. set value of retur temp. 10 -10…20 °C

U7 Slope of shifting range max. set value of return temperature 7 0…39.5

U8 Max. set value of return temperature with d.h.w. charging 50 8…119.5 °C

U9 Limitation of return temperature differential between primaryand secondary circuit in heating mode

0 00.5…50

PassiveActive

°C

U10 Max. limitation of pulse rate per minute 0 01…2047

PassiveActive

U11 Integral action time for U8, U9, U10 16 4/8/16/32 min

U12 Min. limitation of primary flow rate (hydraulic creep) 4 0…15 Stroke%

U13 Locking time after min. limitation (U12) 6 0…15 min

U14 Popen for valve Y11Control gain (KP), multiplied by running time open ,divided by 5

72 0…255 Controlled system oscilates:reducesetting value/ Controlled systemtoo slow: increase setting value

U15 Integral action time of valve Y11 60 30/60/120/240

s

U16 Pclosed for valve Y11Control gain (KP), multiplied by running time close ,divided by 5

72 0…255 Controlled system oscilates:reducesetting value/ Controlled systemtoo slow: increase setting value

U17 Limitation of return temperature differential between primaryand secondary circuit during d.h.w. charging

0 00.5...50

PassiveActive

°C

U18 (Function according to H5) -

U19 (Function according to H7) -

Page 19: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 19

5.9 Setting the heating curve

The setting must be made according to the data usedfor plant sizing.

Press briefly until ADAPT1 appears.

Press to adjust the displayed value.

Note:The value displayed is ten times the actual slope S.This means that if the value displayed reads 14, forexample, the actual slope is 1.4.

6. Connection diagrams

20 10 0 -10 -20 -30

90

80

70

60

50

40

30

°C

°C

4 3,5 3 2,75 2,5 2,25

2

1,75

1,5

1,25

1

0,75

0,5

0,25

100

20

00

D0

2

Connection terminals for measuringvoltage

A6 Room unit (PPS)B1 Secondary flow temperature

detector 1B3 D.h.w. temperature detector 2,

or secondary return tempera-ture detector 2 with VG0

B7 Primary return temperaturedetector 1

B9 Outside detectorB11 Heating circuit flow temperature

detector with VG3 and VG6D.h.w. flow temperature detctorwith VG4 and VG5aD.h.w. temperature detectorwith VG0

B31 D.h.w. temperature detector 1,or primary return temperaturedetector 2 with VG0

B71 Secondary return temperaturedetector 1, or d.h.w. chargingdetector with VG0

D H-busH4 Auxiliary switchP Pulse input

Connector at the rear of the RVP97...

S1 Connector for communicationinterface

2406A13

D

H4

A6

M

P

B31

B3

B7

B71

B1

B11

B9

N

L

Q1

Y2

Y1

F1

Q3/Y3

Y4

Q4

Q5

Y22

Y11S1

B1

BM

Y1 Y2

N

LN

Q1Y1 Y2

B1

F1

M1 240

6A

08

N1

MH4M

H4

Q4

M4

Y3Q3

M3

Q5

M5

B9

BM

B9

M A6

BM

A6

MB3

BM

B3

M B7

BM

B7

M B71

BM

B71

MB31

BM

B31

M

Y1 Y2

N

Y11 Y22

B11

BM

B11

M

VG2(VG5b)

N

Y4

M3

VG1 VG0

N

Y11 Y22

B11

BM

B11

M

Y3Q3L N Y4 Y4

Y3Q3

VG5a

PD

BUSVG3VG4 VG6

Y1 Y2 Y1 Y2

Connection terminals for mains voltage

F1 Live of control relayL Live, AC 230 VM Measuring neutralN Neutral conductorQ1 Heating circuit pump M1 or

main pump M1 with VG2Q3 D.h.w. pump M3Q4 Storage tank charging pump M4Q5 D.h.w. circulating pump M5, or HK2

pump M5 with VG6Y1 Primary control valve 1 (open)Y2 Primary control valve 1 (closed)Y3 Changeover valve on d.h.w. with

VG2/ Primary control valve 2 (open)with VG5b

Y4 Changeover valve on heating circuitwith VG2/ Primary control valve 2(closed) with VG5b

Y11 Heating circuit valve open with VG3and VG6/ D.h.w. valve open withVG4/ Primary control valve 2 openwith VG0 and VG5a

Y22 Heating circuit valve closed withVG3 and VG6/ D.h.w. valve closedwith VG4/ Primary control valve 2closed with VG0 and VG5a

Page 20: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

20 CE1G2406E

7. Dimensions

Controller with base

138

92

240

5M

01

+1- 0

+0.8

- 0

0 2 4 6 8 10 12 14 16 18 20 22 24

2406M01

1

137

32 32

32

32

144

72

10

82

36 91

96

H 4 319 2506 0 e 30. September 1996

Panel cutout

Page 21: Installation and Commissioning RVP971...U10 Max. limitation of pulse rate per minute 0 0 1…2047 Passive Active U11 Integral action time for U8, U9, U10 4/8/16/32 min U12 Min. limitation

CE1G2406E 21

Commissioning Protocol for RVP97

Serial number: - - - - - - - - - - - - - - - - - - - - - - -

Type of plant: - - - - - - - - - - - - - - - - - - - - - - - Plant no.: - - - - - - - - - - - - - - - - - -Operator/owner: - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Location: - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Program 1 Program 2

Weekly program NZ1 NZ2 NZ3 NZ1 NZ2 NZ3

1 Monday Start - end

2 Tuesday Start - end

3 Wednesday Start - end

4 Thursday Start - end

5 Friday Start - end

6 Saturday Start - end

7 Sunday Start - end

Heating curve Slope ADAPT 1

Set values Temperature °C

TEMP Normal room temperature set value

TEMP Reduced room temperature set value

TEMP D.h.w. temperature set value

TEMP Room temperature set value for frostprotection

TEMP Summer/winter changeover

_________________ Signature customer Signature commissioning engineer