installation and operation manual 3500

30
Part Number 163860-01 Rev. A (07/07) Installation and Operation Manual 3500 Monitoring System

Upload: matteo

Post on 11-Jan-2016

683 views

Category:

Documents


73 download

DESCRIPTION

BN 3500 installation manual

TRANSCRIPT

Page 1: installation and operation manual 3500

Part Number 163860-01 Rev. A (07/07)

Installation and Operation Manual

3500 Monitoring System

Page 2: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

ii

Copyright © 2002 Bently Nevada LLC

All rights reserved.

The information contained in this document is subject to change without notice.

The following are trademarks of General Electric Company in the United States and other countries:

ACM™, Actionable Information®, Actionable Information to the Right People at the Right Time®, ADRE, Asset Condition Management™, Asset Condition Monitoring™, Bently ALIGN™, Bently BALANCE®, Bently DOCUVIEW™, Bently LUBE™, Bently

PERFORMANCE™, Bently Nevada™, CableLoc™, ClickLoc™, Data Manager, Decision

SupportSM, DemoNet™, Dynamic Data Manager, Engineer Assist™, FieldMonitor™, flexiTIM™, FluidLoc, Helping You Protect and Manage All Your Machinery,

HydroScan, HydroView™, Key ∅, Keyphasor, Machine Condition Manager™

2000, MachineLibrary™, Machine Manager™, MicroPROX, Move Data, Not People, Move Information, Not Data™, NSv™, Prime Spike™, PROXPAC, Proximitor, REBAM, RuleDesk™, SE™, Seismoprobe, Smart Monitor, Snapshot™, System 1®, System

Extender™, TDXnet™, TDIXconnX™, TipLoc™, TorXimitor, Transient Data Manager, Trendmaster, TrimLoc™, Velomitor

Contact Information

The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local representative:

Mailing Address 1631 Bently Parkway South

Minden, Nevada USA 89423

USA

Telephone 1.775.782.3611

1.800.227.5514

Fax 1.775.215.2873

Internet www.ge-energy.com/bently

Page 3: installation and operation manual 3500

iii

Additional Information

Notice:

This manual does not contain all the information required to operate and maintain the product. Refer to the following manuals for other required information.

3500 Monitoring System Rack Installation and Maintenance Manual (129766-01)

General description of a standard system.

General description of a Triple Modular Redundant (TMR) system

Instructions for installing and removing the module from a 3500 rack

3500 Monitoring System Rack Configuration and Utilities Guide (129777-01)

Guidelines for using the 3500 Rack Configuration software for setting the operating parameters of the module

Guidelines for using the 3500 test utilities to verify that the input and output terminals on the module are operating properly

3500 Monitoring System Computer Hardware and Software Manual (128158-01)

Instructions for connecting the rack to 3500 host computer

Procedures for verifying communication

Procedures for installing software

Guidelines for using Data Acquisition / DDE Server and Operator Display Software

Procedures and diagrams for setting up network and remote communications

3500 Field Wiring Diagram Package (130432-01)

Diagrams that show how to hook up a particular transducer

Lists of recommended wiring

Reference manuals for 3500 modules

Title Part number

3500 Monitoring System Computer Hardware and Software Manual 128158-01

3500 Monitoring System Rack Installation and Maintenance Manual 129766-01

3500 System Field Wiring Diagram Package 130432-01

Page 4: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

iv

Title Part number

3500 System Overview Datasheet 162096-01

3500/08 Diagnostic Access Panel 136275-01

3500/15 & 16 Power Supply Operation and Maintenance Manual 129767-01

3500/20 Rack Interface Module (Operations and Maintenance Manual) 129768-01

3500/22M Transient Data Interface Manual 161580-01

3500/25 Keyphasor Module (Operations and Maintenance Manual) 129770-01

3500/32 & 3500/34 4 Channel Relay Module & TMR Relay Module (Operations & Maintenance Manual)

129771-01

3500/33 16 Channel Relay Module Operations and Maintenance Manual 162291-01

3500/40 Proximitor Monitor Module (Operations and Maintenance Manual) 129772-01

3500/40M Proximitor Monitor Module 143488-01

3500/42 Proximitor/Seismic Monitor Module (Op/Maintenance Manual) 129773-01

3500/42M Proximitor/Seismic Monitor Module (Op/Maintenance Manual) 143489-01

3500/44 Aeroderivative GT Vibration Monitor Module (Operations and Maintenance Manual) 129774-01

3500/44M Aeroderivative GT Vibration Monitor Module (Operations and Maintenance Manual) 143490-01

3500/45 Position Monitor Operation and Maintenance Manual 135545-01

3500/46M Hydro Monitor Manual 144403-01

3500/50 Tachometer Module Operation and Maintenance Manual 134938-01

3500/53 Overspeed Protection System Operation and Maintenance Manual 134939-01

3500/60 and 61 Temperature Module Operation & Maintenance Manual 134542-01

3500/62 Process Variable 136973-01

3500/64 Dynamic Pressure Monitor Operation and Maintenance Manual 142836-01

3500/72M Rod Position Monitor Operation and Maintenance Manual 146479-01

3500/77M Cylinder Pressure Manual 146282-01

3500/90 Communication Gateway Module (Operation and Maintenance Manual) 129769-01

3500/92 Communication Gateway Module (Operation and Maintenance Manual) 138629-01

3500/93 System Display Operation and Maintenance Manual 137412-01

3500/94 VGA Display Module Operation and Maintenance Manual 148636-01

3500/95 PC Display 145169-01

Rack Configuration and Utilities Guide 129777-01

Page 5: installation and operation manual 3500

v

Product Disposal Statement

Customers and third parties, who are not member states of the European Union, who are in control of the product at the end of its life or at the end of its use, are solely responsible for the proper disposal of the product. No person, firm, corporation, association or agency that is in control of product shall dispose of it in a manner that is in violation of any applicable federal, state, local or international law. Bently Nevada LLC is not responsible for the disposal of the product at the end of its life or at the end of its use.

Page 6: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

vi

Contents

Contact Information ......................................................................... ii

Reference manuals for 3500 modules ...........................................................iii

1. Installing a new system.............................................................. 1

1.1 Receiving, inspecting, and handling ..................................................................1

1.2 Installing the rack ..............................................................................................2

1.2.1 Installing a panel mount rack..............................................................2

1.2.2 Installing a Bulkhead mount rack .......................................................5

1.2.3 Installing a rack-mount rack ...............................................................6

1.3 Connecting power ...........................................................................................10

1.3.1 To connect power to your 3500 rack: ...............................................10

1.4 Connecting devices to the Rack Interface Module...........................................12

1.5 Connecting the field wiring to the I/O modules ................................................12

2. Operating the system ............................................................... 14

2.1 Verifying configuration.....................................................................................14

2.2 Operating switches..........................................................................................14

2.3 System contacts..............................................................................................15

2.4 Reading the LEDs...........................................................................................15

2.4.1 3500 LED Descriptions ....................................................................15

2.4.2 Power Supply OK LED.....................................................................16

2.4.3 OK and TX/RX LEDs........................................................................16

2.4.4 TM LED............................................................................................16

2.4.5 Config OK LED ................................................................................17

2.4.6 Bypass LED .....................................................................................17

2.4.7 Relay alarm LED..............................................................................17

2.4.8 Overspeed Detection System...........................................................17

2.5 Collecting data from output terminals ..............................................................18

3. Common maintenance procedures ......................................... 19

3.1 Changing configuration ...................................................................................19

3.2 Replacing modules..........................................................................................21

3.2.1 Replacing a main module.................................................................21

3.2.2 Replacing an I/O module..................................................................21

3.2.3 Removing and inserting a main module ...........................................22

3.3 Verifying channels...........................................................................................24

Page 7: installation and operation manual 3500

1

1. Installing a new system This section shows how to install a 3500 Monitoring System rack that is fully assembled and that has a complete configuration downloaded. If your rack is not fully assembled, contact your nearest Bently Nevada representative.

The section is divided into the following parts:

• Receiving, inspecting, and handling

• Installing the rack

• Connecting power

• Connecting devices to the Rack Interface Module

• Connecting field wiring to the I/O modules

Notice that in order to connect field wiring to the I/O modules, you will need additional information provided in the 3500 Field Wiring Diagram Package, part number 130432-01.

1.1 Receiving, inspecting, and handling • Visually inspect the module for obvious shipping damage. If shipping

damage is apparent, file a claim with the carrier and submit a copy to Bently Nevada.

• Verify that your rack is fully assembled. A fully assembled rack has modules or covers labeled “Future Explansion” in all slots on the front of the rack and has I/O modules or connector covers on all slots on the back of the rack. If your rack is not fully assembled, contact your nearest Bently Nevada representative.

• Customers and third parties that are in control of product at the end of its life or at the end of its use are solely responsible for proper disposal of product. No person, firm, corporation, association or agency that is in control of product shall dispose of it in a manner that is in violation of United States state laws, United States federal laws, or any applicable international law. Bently Nevada is not responsible for disposal of product at the end of its life or at the end of its use.

Page 8: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

2

1.2 Installing the rack The 3500 rack has three mounting configurations as shown in the following table. To mount your rack, refer to the appropriate instructions.

Table 1-1 3500 Rack Mounting Configurations

Configuration type

Panel Bulkhead Rack mount

Illustration

Refer to page…

2 5 6

1.2.1 Installing a panel mount rack A Panel Mount rack allows you to install a 3500 rack behind a panel through a sheet metal cutout and clamp into place. The following figures show the dimensions of a panel mount for a full sized rack and for a mini rack.

1.2.1.1 Panel mount cutout dimensions

Figure 1-1 Dimensions of a Panel Mount 3500 Full-Size Rack

(1) 265.94 mm (10.470 inches) (2) 482.60 mm (19.000 inches). (3) 441.96 mm (17.400 inches). (4) 246.38 mm (9.700 inches). (5) 349.25 mm (13.750 inches), 422.91 mm (16.650 inches) if used with internal barriers

Page 9: installation and operation manual 3500

3

CAUTION Do not use clamps as handles while carrying or installing the rack. The clamps may fall off resulting in injury to personnel and damage to the rack.

Figure 1-2 Cutout for a Panel Mount 3500 Full-Size Rack

(1) 452.1 ± 1.5 mm (17.80 ± 0.06 inches). (2) 3.2 mm (0.125 inches) radius, maximum. (3) 251.5 ± 1.5 mm (9.90 ± 0.60 inches).

Figure 1-3 Dimensions of a Panel Mount 3500 Mini-Rack

(4) 265.94 mm (10.470 inches). (5) 304.80 mm (12.000 inches). (6) 264.16 mm (10.400 inches). (7) 246.38 mm (9.700 inches). (8) 349.25 mm (13.750 inches), 422.91 mm (16.650 inches) if used with internal barriers

Page 10: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

4

CAUTION Clamps must not be used as handles while carrying or installing the rack. The clamps may fall off resulting in injury to personnel and damage to the rack.

Figure 1-4 Panel cutout for the panel mount of 3500 Mini-Rack

(9) 274.3 ± 1.5 mm (10.80 ± 0.06 inches). (10) 3.2 mm (0.125 inches) radius, maximum. (11) 251.5 ±1.5 mm (9.90 ± 0.60 inches).

1.2.1.2 To install a panel mount rack 1. Cut panel cutout to the required dimensions.

2. If installed, remove the panel mount clamps from the rack. Slide rack through panel cutout.

Page 11: installation and operation manual 3500

5

3. Assemble the clamp.

(1) Rear of Rack. (2) Clamp.

4. Align the rack in the cutout.

5. Tighten the clamping screws.

1.2.2 Installing a Bulkhead mount rack A 3500 Bulkhead rack is attached to a wall and lets you change the field wiring from the front of the rack.

1.2.2.1 Dimensions of a bulkhead mount rack

Figure 1-5 Dimensions of a Bulkhead Mount 3500 rack

(12) 482.60 mm (19.000 inches). (13) 459.59 mm (18.094 inches). (14) 133.35 mm (5.250 inches). (15) 190.50 mm (7.500 inches). (16) 133.35 mm (5.250 inches).

Page 12: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

6

(17) 532.64 mm (20.970 inches). (18) 266.70 mm (10.500 inches).

1.2.2.2 To install a bulkhead mount 3500 rack Install the 3500 rack using No. 10 flat washers (8 places) and 10-32 screws (8 places) in the locations shown in the diagram below.

1.2.3 Installing a rack-mount rack A Rack Mounted 3500 system is installed into a standard 19-inch EIA cabinet. The following figures show the dimensions for a full-sized rack-mount rack and for a mini rack.

Page 13: installation and operation manual 3500

7

1.2.3.1 Dimensions of a full-sized rack-mount rack

Figure 1-6 Dimensions of a Rack Mount 3500 Full-Size Rack

(19) 265.94 mm (10.470 inches). (20) 190.50 mm (7.500 inches). (21) 457.40 mm (18.008 inches). (22) 482.60 mm (19.000 inches). (23) 441.96 mm (17.400 inches). (24) 246.38 mm (9.700 inches). (25) 349.25 mm (13.750 inches), 422.91 mm (16.650 inches) if used with internal barriers

1.2.3.2 To install a rack mount 3500 full-size rack Install the 3500 rack using No. 10 flat washers (4 places) and 10-32 screws (4 places) at the locations shown by the arrows in the diagram below.

1.2.3.3 Dimensions of a rack mount 3500 mini rack The Mini-Rack Mounted 3500 system is installed into a standard 19-inch EIA cabinet by using the mini-rack Adapter Panel.

Page 14: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

8

Figure 1-7 Dimensions of a Rack Mount 3500 Mini-Rack

(26) 265.94 mm (10.470 inches). (27) 190.50 mm (7.500 inches). (28) 279.60 mm (11.008 inches). (29) 304.80 mm (12.000 inches). (30) 264.16 mm (10.400 inches). (31) 246.38 mm (9.700 inches). (32) 349.25 mm (13.750 inches), 422.91 mm (16.650 inches) if used with internal barriers

Page 15: installation and operation manual 3500

9

1.2.3.4 To install a rack mount 3500 Mini-rack Install the Mini-rack adapter panel into the EIA rack using No. 10 flat washers (4 places) and 10-32 screws (4 places). Next, install the 3500 Mini-rack onto the adapter panel using No. 10 flat washers (4 places) and 10-32 screws (4 places).

(33) 3500 Mini-rack (34) Adapter Panel (35) Standard 19-inch EIA rack

Page 16: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

10

1.3 Connecting power Connect power wires to the Power Supply I/O module. This module is located behind the power supply module on rack and panel mount racks and above the power supply module on bulkhead mount racks. If your rack has two power supplies, the upper supply is the primary supply and the lower one is the backup.

1.3.1 To connect power to your 3500 rack: 1. Identify the type of I/O module by using the following table.

Table 1-2 Power Supply I/O Modules

Module type

Low voltage AC

High voltage AC

High voltage DC

Low voltage DC

Power requirement

85 to 125 Vac

4.5 A

47 to 63 Hz

175 to 250 Vac

2.3 A

47 to 63 Hz

88 to 140 Vdc

2.5 A

20 to 30 Vdc

10 A

I/O Module

2. Verify that the power source matches the values listed under “Power requirements” in Table 1-2 Power Supply I/O Modules.

3. Install a power switch or circuit breaker close to the rack and mark the switch or breaker as the disconnect device for the rack.

CAUTION Touching exposed power wires can cause shock, burns, or death.

Turn off power before connecting the power cable to the Power Supply I/O module.

Page 17: installation and operation manual 3500

11

4. Open the hinged protector that covers the power terminals.

(1) Hinged terminal protector

5. Connect the power cable as shown in the following figure and table.

(1) Power cable. Select a wire gage and type that meets the local code requirements and meets the power requirements as listed in Table 1-2 Power Supply I/O Modules. Use Table 1-3 Power wire legend to identify the wires. (2) Chassis ground. To minimize ground loop noise, a single point earth ground (GRD) to the system common connection is recommended. When two supplies are used in the same system, both connections are considered a single point.

Page 18: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

12

Table 1-3 Power wire legend

Type of Power Supply I/O module

AC DC

Wire

High voltage Low voltage High voltage Low voltage

Line 1 Line 1 Positive DC Positive DC

Line 2 Neutral Line 2 Negative DC Negative DC

Ground Ground Ground Ground

6. Close the hinged terminal protector.

1.4 Connecting devices to the Rack Interface Module

OK Relay System Contacts

The OK Relay is normally energized and is used to indicate whether the 3500 Monitoring

System is OK. OK Relay contact rating: 5 A @ 24 Vdc or 5 A @ 120 Vac 50/60 Hz or 3 A @ 220 Vac 50/60 Hz resistive maximum.

System contacts let you use external contacts to control the operation of the rack. Wiring recommendations: 18 AWG to 22 AWG stranded 2-wire shielded with insulating sheath.

Note: Shields are spliced into a single wire then grounded at the stud marked “SHIELD”. Shields should be insulated.

Table 1-4 System contacts

Label Name Description

TM Trip mulitply temporarily increases the alarm (Alert and Danger) setpoint values by a specific multiple (usually two or three). This function is normally applied by manual (operator) action during startup to allow a machine to pass through high vibration speed ranges without monitor alarm indications.

INHB Rack alarm inhibit Used to prevent an alarm from being declared on any monitor or relay in the 3500 rack. This is typically used when performing maintenance functions.

RST Reset Used to signal when the modules in the 3500 rack are to be reset. This contact has the same function as the Rack Reset switch on the front panel of the Rack Interface Module.

1.5 Connecting the field wiring to the I/O modules You connect transducer field wiring to a 3500 rack by using either internal or external termination. The type of termination is determined by the type of I/O modules that are installed on the rack.

Page 19: installation and operation manual 3500

13

Internal termination Connect transducer wires directly to the I/O modules

External termination Simplify wiring at the rear of the rack by using cables to connect external temination I/O modules to external termination blocks.

(1) To Transducers. (2) Internal Termination I/O Modules.

(1) To Transducers. (2) External Termination Blocks. (3) External Termination I/O Modules.

Refer to the 3500 Field Wiring Diagram package, part number 130143-01, for information about how to connect transducer field wiring to the I/O modules in your rack.

Page 20: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

14

2. Operating the system This section shows how to use the various indicators and connections of a 3500 rack to control operation and collect data.

The section is divided into the following parts:

• Verifying configuration

• Operating switches

• Reading LEDs

• Collecting data from output terminals

2.1 Verifying configuration A 3500 rack can contain a variety of modules that can be set up to operate different ways. The process of setting system, module, and channel options so that all the modules in the 3500 rack work together is called configuration.

After power is applied to the rack, the configuration LED (CONFIG OK) indicates that the rack contains a complete and correct configuration.

If the configuration LED is not ON, contact your local Bently Nevada representative.

2.2 Operating switches Hardware switches let you control the operation of the rack as follows:

Reset switch clears latched alarms and resets Timed OK Channel Defeat indications. If the Configuration LED is blinking at 5 Hz, it will be stopped. This switch performs the same function as the Rack Reset contact on the Rack Interface I/O Module.

Key switch prevents unauthorized changes to the configuration settings. When the switch is in the RUN position, the 3500 rack cannot be configured. When the switch is in the PROGRAM position, the 3500 rack can be configured and the rack continues to operate normally. By removing the key, you can lock the Rack Interface Module in the RUN or PROGRAM position.

Page 21: installation and operation manual 3500

15

2.3 System contacts System contacts provide additional control by connecting external contacts to the rack.

Trip multiply ( TM ) temporarily increases the alarm (Alert and Danger) setpoint values by a specific multiple (usually two or three). This function is normally applied by manual (operator) action during startup to allow a machine to pass through high vibration speed ranges without monitor alarm indications.

Rack alarm inhibit ( INHB ) prevents an alarm from being declared on any monitor or relay in the 3500 rack. This is typically used when performing maintenance functions.

Reset ( RST ) Same function as pressing in the RESET switch on the front of the rack.

2.4 Reading the LEDs The LEDs on the front panel of 3500 modules indicate the operating status of the module.

2.4.1 3500 LED Descriptions 3500 Module LED label Description Detailed description

see page…

3500/15 Power Supply

SUPPLY OK all of the output voltages from the supply are within specification.

page 16

OK The module and I/O module are operating correctly.

page 16

TX/RX Flashes at the rate that messages are sent from the module.

page 16 Most 3500 modules

BYPASS Some of the monitor functions are temporarily suppressed.

page 17

TM Indicates whether the rack is in Trip Mulitply mode.

page 16 3500/20 RIM Module

CONFIG OK The configuration of the rack is correct.

page 17

3500/32 and 34 Relay

CHn ALARM An alarm condition has occurred with this relay. (Where “n” is the channel number 1 through 4.)

page 17

3500/53 Overspeed Protection system

TEST MODE The module is in test mode

page 17

Page 22: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

16

3500 Module LED label Description Detailed description see page…

ALARMS

2.4.2 Power Supply OK LED Supply OK Condition Solution

On all of the output voltages from the supply are within specification

No action required

Off An output voltage from the supply is not within specification

Refer to the following procedures

If the Power Supply OK LED is off, check the following items:

6. Verify that the correct voltage is connected to the Power Input Module (refer to Table 1-2 Power Supply I/O Modules on page 10).

7. Verify that the installed Power Input Module matches the installed Power Supply. For example, an AC Power Input Module with the AC version of the Power Supply.

8. Check to see if the fuse on the Power Input Module has blown. If the fuse is blown, replace it. A blown fuse may be due to:

- Severe overvoltage on the Power Input Module.

- A fault within the 3500 Power Supply.

2.4.3 OK and TX/RX LEDs OK TX/RX Condition Solution

1 Hz 1 Hz Module is not configured or is in configuration mode

Reconfigure the module (see 3500 Rack Configuration Guide, part number 129777-01)

5 Hz XX Module has detected an intenal fault and is not OK

Check the System Event List

ON Flashing Module is operating correctly No action required XX Not flashing Module is not operating

correctly Check the System Event list

XX = behavior of the LED is not related to the condition

Event lists Contain records of things that happen to the rack. The system maintains two event lists -- the Alarm Event list and the System Event list. To view these lists, refer to the 3500 Monitoring System Configuration Guide, part number 129777-01.

2.4.4 TM LED Trip multiply

temporarily increases the alarm (Alert and Danger) setpoint values by a specific multiple (usually two or three). This function is normally applied by manual (operator) action during startup to allow a machine to pass through high vibration speed ranges without monitor alarm indications.

Page 23: installation and operation manual 3500

17

TIM LED Condition Solution

ON Rack is in Trip Multiply No action required OFF Rack is not in Trip Multiply No action required

2.4.5 Config OK LED Configuration

the process of setting system, module, and channel options so that all the modules in a 3500 rack work together.

CONFIG OK Condition Solution

ON Configuration information for every module in the rack is valid.

No action required.

5 Hz One of the selected security options has not been met

Check the System Event List. Press the Rack Reset Switch to clear.

OFF At lease one module in the rack has a configuration fault A non-configured active Power Supply is present in the rack

One or more of the following configuration problems exist: -- a module in the rack is not configured -- the configuration in the RIM does not match the physical configuration of the rack -- a configuration security option condition is not met

2.4.6 Bypass LED Bypass

an operating condition of a 3500 monitoring module where functions of all 4 channels in the monitor are suppressed. When the channels in a bypassed 3500 monitor go in alarm, the alarm events are posted to the Alarm Event List but any relays that use the alarms from the monitor in the relay alarm logic will not be activiated.

BYPASS Condition Solution

OFF Alarm Enabled No action required ON Some or all alarming in the

module disabled No action required

2.4.7 Relay alarm LED Relay alarm

the alarm status of a 3500 relay channel. A relay channel is in alarm if the alarm logic as defined in the configuration for the relay channel is true. Use the 3500 Configuration program to view the alarm logic for relay channels.

Relay alarm LED Condition Solution

ON Relay channel is in alarm No action required. OFF Relay channel is not in alarm No action required.

2.4.8 Overspeed Detection System Test mode

The 3500 Overspeed Detection Module has an on board frequency generator that can generate a test signal for testing the overspeed detection function of the monitor. When the test function is enabled in the configuration software (option box is checked), you can invoke the function by closing a contact on the Overspeed Detection I/O module or via a software switch. When the test

Page 24: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

18

is invoked, the test frequency sweeps through a start RPM and an end RPM. (The start and end RPM are set in the configuration for the module.) When the test input speed exceeds the over Alert/ /Alarm 1 and Overspeed (Danger) setpoints, the associated alarms will be driven.

TEST MODE Condition Solution

ON The overspeed module is in test mode.

No action required.

OFF The overspeed module is not in test mode.

No action required.

Alarm LED

The 3500 Overspeed Detection System (ODS) consists of mulitiple ODS modules that operate as a group. The alarms generated from this group are the result of a voting process that is set up in configuration. The alarm LEDs on the modules in overspeed detection systems indicate the result of this voting. Use the 3500 Configuration program to determine how this voting has been configured for the modules in the ODS.

ALARM Condition Solution

OFF Relay is not in alarm No action required. ON Relay is in alarm No action required.

2.5 Collecting data from output terminals Buffered Transducer Outputs provide the unfiltered output from the channels in the modules. All outputs are short circuit protected.

Page 25: installation and operation manual 3500

19

3. Common maintenance procedures Once a 3500 Monitoring System is operating, it continuously measures and monitors a variety of supervisory parameters. The boards and components inside of 3500 modules cannot be repaired in the field and require no calibration. This section provides information for common tasks required under normal operating condititions. For procedures that require more detailed information, refer to the reference manuals listed in 3500 Field Wiring Diagram Package (130432-01)

Diagrams that show how to hook up a particular transducer

Lists of recommended wiring Reference manuals for 3500 modules on page iii.

This section includes the following topics:

• Changing configuration

• Replacing modules

• Verifying channels

3.1 Changing configuration The process of setting system, module, and channel options so that all the modules in the 3500 rack work together is called configuration. These settings are established and adjusted by using the 3500 Rack Configuration program.

Configuration settings are usually protected by security settings. The security setting for a typical 3500 Monitoring System that is operating normally is “Change Setpoints in Program Mode”. This section shows how to adjust setpoints. To change other configuration settings, refer to the 3500 Monitoring System Rack Configuration and Utilities Guide, part number 129777-01.

To adjust alarm setpoints

9. Place the rack in program mode by using the key switch on the Rack Interface Module.

10. In the 3500 Rack Configuration program, click the Setpoints pushbutton.

Page 26: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

20

11. Click on the monitor module to be adjusted.

The Configuration Setpoint dialog for that monitor module will appear.

12. Select the monitor channel to be adjusted in the Monitor Channel list box.

13. For all measurement parameters except phase, adjust the setpoint level by dragging the bar in the bar graph or by entering a value in the text box above or below the parameter.

Notice that setpoints can be adjusted only for those parameters that are enabled and that some parameters have both upper and lower setpoint values. Parameters are enabled or disabled by using the Channel Option screen. Refer to the 3500 Monitoring System Rack Configuration and Utilities Guide for more information.

14. For phase setpoints, enter the values for the beginning and ending setpoint in the text boxes below the phase diagrams.

15. Apply the adjusted setpoints to the rack by clicking OK and then downloading the revised configuration to the rack.

Page 27: installation and operation manual 3500

21

3.2 Replacing modules The boards and components inside of 3500 modules cannot be repaired in the field and require no calibration. For 3500 modules that are not operating properly, use the information in this section to replace the module with a spare and then contact your local Bently Nevada representative for information about returning the faulty module for failure analysis.

3.2.1 Replacing a main module 16. Save the configuration of the module to be replaced.

3500 modules must have valid configuration settings in order to operate properly. Replacement modules are not configured. By saving the configuration, you can download the original configuration settings to the replacement module.

The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01, shows how to save configuration files.

17. Remove the module to be replaced.

Refer to Removing and inserting a main module on page 22.

18. Insert the new module

Refer to Removing and inserting a main module on page 22.

19. Download the configuration to the new module.

The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01, shows how to download configuration files.

20. Verify operation.

- Check that the LEDs for the replaced module are indicating correct operation (see Reading the LEDs on page 15).

- The values of the measurement parameters of a channel are verified by using the Verification utility in the 3500 Rack Configuration program and the verification procedure in the reference manual for that module.

3.2.2 Replacing an I/O module This procedure applies only to the I/O module of a monitor or the PIM of a power supply that is to be replaced. Prior to removing any module, refer to the applicable reference manual to see how rack behavior may be affected and for any special handling requirements required for personal safety.

21. If necessary, upload and save the configuration of the module to be replaced.

3500 modules must have valid configuration settings in order to operate properly. Replacement modules are not configured. By saving the configuration, you can download the original configuration settings to the replacement module.

The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01, shows how to save configuration files.

22. Remove the main module from the rack.

Refer to Removing and inserting a main module on page 22.

Page 28: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

22

23. Remove the field wiring from the I/O module.

If the wires connected to the I/O module are not labeled, label the wires before you remove them.

24. Remove the old I/O module from the rack.

25. Install the new I/O module into the rack.

26. Connect the field wiring to the new I/O module.

27. Install the main module into the rack.

Refer to Removing and inserting a main module on page 22.

28. Download the configuration to the new module.

The 3500 Monitoring System Configuration and Utilities Guide, part number 129777-01, shows how to download configuration files.

29. Verify operation.

- Check that the LEDs for the replaced module are indicating correct operation (see Reading the LEDs on page 15.

- The values of the measurement parameters of a channel are verified by using the Verification untility in the 3500 Rack Configuration program and the verification procedure in the reference manual for that module.

3.2.3 Removing and inserting a main module When performed properly, modules may be removed from or installed into the rack while power is applied to the rack.

3.2.3.1 To remove the old full-height module This procedure shows how to remove any full-height 3500 module. Refer to the reference manual for the module for details and safety considerations.

30. Loosen the screws to the main module so that they are free of the rack chassis, but still attached to the main module.

31. Use the ejectors to pry the main module loose from the backplane connectors.

32. Once freed from the backplane, the main module can be removed completely from the rack

Page 29: installation and operation manual 3500

23

3.2.3.2 To install a spare full-height module 33. Ensure that the ejectors are in their normal position, flush with the front of the

module.

34. Slide the main module into place, ensuring that they are properly in the guides provided on the floor and roof of the rack chassis.

35. Tighten the screws securely.

Application Advisory: It is important to tightly secure the thumb screws to ensure each module is Chassis grounded. Loose thumb screws may allow noise to show on the channel readings.

3.2.3.3 To add or remove a half-height card guide

Installing the card guide Removing the card guide

Page 30: installation and operation manual 3500

3500 Monitoring System Installation and Operation Manual

24

3.3 Verifying channels The boards and components inside of 3500 modules cannot be repaired in the field. Maintaining a 3500 rack consists of testing module channels to verify that they are operating correctly. Modules that are not operating correctly should be replaced with a spare. When performed properly, modules may be removed from or installed into the rack while power is applied to the rack.

The 3500 Monitoring System is a high precision instrument that requires no calibration. The functions of the 3500 modules, however, must be verified at regular intervals. All modules in the 3500 Monitoring System should be verified at these maintenance intervals. The procedures in the Maintenance and Troubleshooting sections of the module reference manuals describe the verification and troubleshooting process. (Refer to the reference manuals listed in 3500 Field Wiring Diagram Package (130432-01)

Diagrams that show how to hook up a particular transducer

Lists of recommended wiring Reference manuals for 3500 modules on page iii.)