FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT General The instruction provides all the necessary information to properly field install this economizer on the above indicated equipment. Economizer Model 2EE04705424 has a single input solid state enthalpy sensor that provides automatic 100% outdoor air capability with 2% leakage. Refer to the respective unit wiring diagram for information regarding electrical circuitry on the economizer. A relief air damper for barometric air balance is provided with each basic unit and is mounted on the face of the return air damper section. Refer to the basic unit installation instruction for additional information. Step 1: Verify all unit parts in box. a. 1 ea. - Return Air Damper b. 1 ea. - Fresh Air Damper c. 4 ea. - 24 5 8 “ x 23 1 8 “ x 1” Mist Eliminator Filter (shipped inside Return Air Damper) d. 1 ea. - Hood Package 1 ea. - Barometric Relief Hood 1 ea. - Barometric Relief Damper 1 ea. - Fresh Air Hood 1 ea. - Hardware Bag: 54 ea. - Type A #10 - 16 x ½ Screws 14 ea. - Self tapping #10 - 16 x ½ Screws 2 ea. - Seal Tight #10 - 32 x ½ Screws w / washers 4 ea. - Filter Clips 18 ea. - #8 Tinnerman Clips 10 ft. - 1 8 x ½ Gasket 11 ft. - 1 8 x ¾ Gasket PANELS TO BE REMOVED HOOD PACKAGE RETURN AIR DAMPER FRESH AIR DAMPER FIELD INSTALLED DOWNFLOW ECONOMIZER ACCESSORY MODEL 2EE04705424 INSTALLATION INSTRUCTIONS

Upload: others

Post on 06-Apr-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT

Gen eral

The instruction provides all the necessary information to properly field install this economizer on the above indicatedequipment.

Economizer Model 2EE04705424 has a single input solid state enthalpy sensor that provides automatic 100% outdoor aircapability with 2% leakage.

Refer to the respective unit wiring diagram for information regarding electrical circuitry on the economizer.

A relief air damper for barometric air balance is provided with each basic unit and is mounted on the face of the return airdamper section. Refer to the basic unit installation instruction for additional information.

Step 1:

Verify all unit parts in box.

a. 1 ea. - Return Air Damperb. 1 ea. - Fresh Air Damperc. 4 ea. - 24 5

8“ x 23 18“ x 1” Mist Eliminator Filter

(shipped inside Return Air Damper)d. 1 ea. - Hood Package

1 ea. - Barometric Relief Hood1 ea. - Barometric Relief Damper1 ea. - Fresh Air Hood1 ea. - Hardware Bag:

54 ea. - Type A #10 - 16 x ½ Screws14 ea. - Self tapping #10 - 16 x ½ Screws 2 ea. - Seal Tight #10 - 32 x ½ Screws

w / washers 4 ea. - Filter Clips18 ea. - #8 Tinnerman Clips10 ft. - 1

8 x ½ Gasket11 ft. - 1

8 x ¾ Gasket

PANELS TO BE REMOVED

HOOD PACKAGE

RETURN AIR DAMPER FRESH AIR DAMPER

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

Page 2: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

Step 2:

Remove the Enthalpy Control and Discharge Air Sensor fromthe return air damper and save for later installation (Steps 3 and 15).

ENTHALPY CONTROL

(2)

(9)

(5)

(4)

(2)

(1)

(11)

(10)

Follow these steps:

A. Take (1 and 2) and use the 2 Seal Tightscrews with washers and screw though (2)into (1) and tighten.

B. Take (3 and 4) and screw through (2) into(3 and 4) using the Type A screws.

C. Take (5 and 6) and screw through (7) into (5 and 6) using the Type A screws.

D. Take (8) and put to the inside of (2 and 7) andsecure with Type A screws.

E. Take (9) and place tabs into slots of (2 and 7)and bend tabs down on the outside of (2 and 7).

F. Take (10) and place flanges with the threeholes over (2 and 7) and secure with Type Ascrews.

G. Take (11) and secure to (2, 7, 10) with Type A screws.

H. Take filter clips and screw to (9 and 10) with Type A screws.

I. Place gasket on the back flanges of (2, 7, 8, 10)

J. Install filters in the hood and fasten clips tohold in place.

Set Fresh Air Hood to the side for use in Step 13.

Step 3:

To assemble the fresh air hood the following will be needed.

34 ea. - Type A #10 - 16 x ½ Screws 4 ea. - Filter Clips 2 ea. - Seal Tight #10 - 32 x ½ Screws w/ washers 5 ft. - 1

8 x ½ Gasket

23 516

35 1516

25 1116

GASKET

GASKET

GASKET

(8)

ENTHALPY SENSOR(FROM STEP 2)

(6)

FILTER CLIPS

(3)

(7)

DISCHARGE AIR SENSOR

Page 3: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

(5)

(4)

(2)

(3)

(1)

Step 6:

Install the fresh air damper into the horizontal return air ductopening as shown. Using the self tapping #10 - 16 x ½ screwsprovided secure to duct connection (two on each side). The twoholes with bushings will be on the right hand side and thedamper bracket will be on the damper bottom inside the unit.

DAMPER BRACKET

HOLES TO ATTACH RETURN AIR DAMPER

TWO HOLES WITH BUSHINGS

HORIZONTAL DUCT OPENING WITHCOVER AND END PANELS REMOVED

Step 5:

Remove the return air duct cover and the two (2) rear panels fromthe end of the unit as shown. Keep screws to use later in Steps 7and 14. Note: Tinnerman clips have been supplied in case holesin the side flanges of the unit have been stripped. Attach (14) clipsto the two side flanges as shown in figure.

(6)

HOLES IN SIDE FLANGESFOR TINNERMAN CLIPS

Step 4:

To assemble the Barometric Relief Hood the following will be needed.

20 ea. - Type A #10 - 16 x ½ Screws 5 ft. - 1

8 x ½ Gasket11 ft. - 1

8 x ¾ Gasket

Follow these steps:

A. Take (1 and 2) put the flange of (1) to the insideof (2) and screw in place.

B. Take (3) and screw in place like step A.C. Take (4) and place flanges over (2 and 3) and secure.D. Take (5) and do the same as step C.E. Take 1

8 x ¾ gasket and place around perimeter of (6)to seal between damper section and hood.

F. Take (6) and slide inside of (2 and 3) and secure.G. Place 1

8 x ½ gasket on flanges on (1,2, 3 and 5) thatattach to the face of the economizer when installed.

Set Barometric Relief Hood to the side for use in Step 13.

31 1116

21 916

18 ½

12 ¼

25 ¼

Page 4: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

Step 7:

Slide the return air damper into the unit as shown using some ofthe screws removed in Step 5.

Step 8:

Secure the return air damper to the unit with the screws removed in Step 6 through the slotted holes in the damper section.

Do Not tighten screws at this time.

Step 9:

Connect the linkage from the return air damper to the fresh airdamper. The linkage rod is shipped connected to the return air damper. To connect the linkage to the fresh air damper, openthe fresh air damper and insert the rod through the opening inthe damper bracket. With the rod through the fresh air damperbracket, close the fresh air damper tightly, and tighten the setscrew on the fresh air damper bracket as shown.

Note: A. Damper bracket is shipped in lower position. If

installing in small cabinet reposition bracket toholes 8" above current location

B. Linkage rod should be flush with the back of thefresh air damper bracket.

Step 10:

Route the blue and violet wire from the Logic Module “+” and“S” terminals through the lower bushing provided in the freshair damper as shown. These wires will be connected to theEnthalpy Control mounted on the fresh air hood as shown inStep 13.

NOTE A

Page 5: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

3”

Step 12:

Install the assembled Barometric Relief Hood as shown.Using the “keyhole” slots on the barometric relief hood, placethe barometric relief hood over the screws and slide down intothe slots and tighten screws in place. Attach (4) tinnermanclips to the top flange of Barometric Relief Hood as shown infigure.

This is the time to tighten all screws that were previouslynot tightened.

Step 13:

Install the assembled Fresh Air Hood as shown using #10 - 16x ½ self tapping screws. Place fresh air hood approximately 3” down from top of the unit and flush with flange on hood side.Route wire to Enthalpy Control in the lower right hand cornerof the Fresh Air Hood as shown. Connect the violet wire to the“+” terminal and the blue wire to the “S” terminal.

Step 11:

Plug the economizer cable into the unit as shown. The“jumper” plug that ships with the unit should be removed andsaved in the control compartment for future needs.

ECONOMIZER CABLE

Step 14:

Reinstall the top rear panel which was removed in Step 5 ofthe unit using the remaining screws also removed in Step 5.

TOP REAR PANEL

FLANGE ON HOOD SIDEHOLES FORTINNERMAN CLIPS

Page 6: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

FIELD INSTALLEDDOWNFLOW ECONOMIZER ACCESSORY

MODEL 2EE04705424

INSTALLATIONINSTRUCTIONS

Step 15:

The Discharge Air Sensor installs in the blower compartmentof the unit. Open the access door to the blower and you willsee a cable on the left side. The cable has two wires withinsulated connectors that the Discharge Air Sensor plugs into. These wires are shown in the photo. Plug the Discharge AirSensor wires into those provided inside the unit, and using awire tie, strap the Discharge Air Sensor to the cable as shownbelow.

DISCHARGE AIR SENSOR WIRES

WIRE TIE

DISCHARGE AIR SENSOR

SUPERCEDES 12-17-04JANUARY 14, 2005

035-18285-000-C-0105RSI FORM# YKIEC29DB

Page 7: INSTALLATION FIELD INSTALLED INSTRUCTIONS DOWNFLOW … · 2005-04-06 · FOR 6.5 THRU 12.5 TON SINGLE PACKAGE EQUIPMENT Gen eral The instruction provides all the necessary information

S7/P7 ECONOMIZER SECTION SOCKET /PLUG CONNECTIONDAS DISCHARGE AIR SENSORS12/P12 POWER EXHAUST SOCKET/PLUG

CONNECTIONM5 POWER EXHAUST CONTACTORRC CAPACITOR

NOTES:

1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCALAND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OFTHIS UNIT.

2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHENSERVICING CONTROLS. WIRING ERRORS CAN CAUSED IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE REMOVED. IT MAY BE REPLACED WITH TYPE 105DEGREE C, GOO VOLT WIRE OR EQUIVALENT CLEARLY RENUMBEREDFOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING.

3. WHEN ECONOMIZER IS INSTALLED REMOVE PLUG WITH JUMPER WIRE816/Y