installation manual - onezoneonezoneusa.com/wp-content/uploads/2015/10/mi_zbs_a4_en_100.pdf · zbs...
TRANSCRIPT
Table of contents 1. WARNINGS AND ENVIRONMENTAL POLICY ....................................................................... 5
1.1. Precautions ........................................................................................................................ 5 1.2. Environmental Policy ......................................................................................................... 5
1.3. FCC Regulatory Notices .................................................................................................... 6 1.4. INTERTEK / UL Regulatory Notices .................................................................................. 6
2. SYSTEM ELEMENTS .............................................................................................................. 7 2.1. ZBS Control Board (AZZBSxx) .......................................................................................... 7 2.2. Air-conditioning Gateway ................................................................................................... 7
2.3. ZBS Relay box radiant heat control (AZZBSOUTPUT5) .................................................... 7 2.4. Wired/Wireless local zone module (AZZBS [W/R] LMR) ................................................... 8
2.5. Wired/Wireless intelligent motorized round damper (AZZBS [06-08-10] [W/R])................. 8
2.6. Blueface Intelligent Thermostat (AZZBSBFSW) ................................................................ 8 2.7. Wired/Wireless Tacto thermostat (AZZBSTCSW [W/R]).................................................... 9 2.8. BACnet Gateway (AZZBSBACNET) .................................................................................. 9 2.9. Operation Mode Synchronizer (AZZBSMODESYNC) ........................................................ 9
3. DESCRIPTION, ASSEMBLY AND MODULES CONNECTION ............................................. 10
3.1. General recommendations............................................................................................... 10 3.2. ZBS control board (AZZBSxx) ......................................................................................... 11
3.2.1. Installation ................................................................................................................. 11
3.2.2. Connections............................................................................................................... 11 3.3. Wired/Wireless intelligent motorized round damper (AZZBS [06-08-10] [W/R])............... 14
3.3.1. Installation ................................................................................................................. 14 3.3.2. Damper setting .......................................................................................................... 14
3.3.3. Connection ................................................................................................................ 15 3.4. Wired/Wireless local zone module (AZZBS [W/R] LMR) ................................................. 15
3.4.1. Installation ................................................................................................................. 15
3.4.2. Connection ................................................................................................................ 15 3.5. ZBS Relay box radiant heat control (AZZBSOUTPUT5) .................................................. 16
3.5.1. Installation ................................................................................................................. 16 3.5.2. Connection ................................................................................................................ 16
3.6. Wired/Wireless thermostats (AZZBSBFSW and AZZBSTCSW [W/R]) ............................ 17 3.6.1. Installation ................................................................................................................. 17 3.6.2. Connection ................................................................................................................ 17
3.7. Operation Mode Synchronizer (AZZBSMODESYNC) ...................................................... 17
3.7.1. Installation ................................................................................................................. 17 3.7.2. Connection ................................................................................................................ 18
4. QUICK OR INITIAL SYSTEM CONFIGURATION ................................................................. 19 4.1. Configuration via Blueface ............................................................................................... 19 4.2. Configuration via Tacto .................................................................................................... 21
5. ADVANCED CONFIGURATION ............................................................................................ 24 5.1. Configuration via Blueface ............................................................................................... 24
5.1.1. Blueface configuration menu ..................................................................................... 24 5.1.2. Blueface Interface Menu ............................................................................................ 31
5.2. Configuration via Tacto .................................................................................................... 32
5.2.1. Tacto configuration menu .......................................................................................... 32
5.2.2. Basic /complete function .......................................................................... 39 6. EXCEPTION CODES............................................................................................................. 40
7. SELF-TESTING ..................................................................................................................... 41
7.1. ZBS Control board (AZZBSxx) ......................................................................................... 41 7.2. Inverter Integration gateway ............................................................................................ 42 7.3. ZBS relay box radiant supplemental heat control (AZZBSOUTPUT5) ............................. 42 7.4. BACnet Gateway (AZZBSBACNET) ................................................................................ 43
8. NAVIGATION GUIDE............................................................................................................. 44
8.1. Blueface navigation guide ................................................................................................ 44 8.2. Tacto navigation guide ..................................................................................................... 45
5
1. WARNINGS AND ENVIRONMENTAL POLICY 1.1. Precautions For your security, and to protect the devices, follow these instructions:
Do not handle the system with wet or damp hands.
Disconnect the power supply before making any connections.
Disconnect the power supply from the air conditioning and heating system before making any connection or disconnecting equipment.
Take care not to cause a short circuit in any of the system’s connections.
1.2. Environmental Policy
Do not dispose of this equipment in the household waste. Electrical and electronic products contain substances that can be harmful to the environment if they are not given proper treatment. The symbol of the crossed container indicates separate collection of electronic equipment, unlike the rest of urban garbage. For proper environmental management, the equipment to be disposed must be taken to the proper collection center at the end of its lifespan.
The components of this equipment can be recycled. Act in accordance with current regulations on environmental protection. If you replace it with other equipment, you must return it to the distributor or take it to a specialized collection center.
Those breaking the law or by-laws will be subject to such fines and measures as are laid down in environmental protection legislation.
6
1.3. FCC Regulatory Notices Modification statement
Corporación Empresarial Altra S.L. has not approved any changes or modifications to this device by the user. Any changes or modifications could void the user’s authority to operate the equipment. Interference statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Radiation Exposure Statement
This device complies with FCC radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure Guidelines in Supplement C to OET65 This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter. FCC Class B digital device notice
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
1.4. INTERTEK / UL Regulatory Notices The units shall be tested by a Nationally Recognized Testing Laboratory (NRTL) in
accordance with ANSI/UL Standard UL 1995/CAN/CSA-C22.2 No. 236-11 – 4th Edition (R2011) – Heating and Cooling Equipment, and will bear the Listed Mark.
All wiring shall be in accordance with the National Electric Code (NEC)/Canadian Electrical Code (CEC).
7
2. SYSTEM ELEMENTS 2.1. ZBS Control Board (AZZBSxx) Electronic equipment responsible of the system management through wired and wireless devices. It controls the following parameters:
Individually controlled dampers.
Q-Adapt Algorithm.
Control of optional auxiliary heat (up to two stages).
Supply temperature sensor.
Eco-Adapt Algorithm.
Seamless integration with the Indoor Unit Control. o On/Off status. o Fan speed Algorithm. o Indoor Unit Set point. o Operation Mode. o Energy Efficiency Control Algorithm.
2.2. Air-conditioning Gateway This gateway integrates the indoor unit with the ZBS control board. The Air conditioning gateway includes an Energy Efficiency Control Algorithm that is controlled with the Blueface main Thermostat, including the following functions:
Automatically changes the Indoor Unit operation mode (Stop, Ventilation, Cooling, Heating, or Dry) from the in the ZBS system’s Blueface main Thermostat.
Temperature setting for the AC unit based on the overall demand of the ZBS zone thermostats.
Automatically controls the speed.
2.3. ZBS Relay box radiant heat control (AZZBSOUTPUT5) Radiant element control Gateway for zone. Powered and communication by the ZBS control board. Maximun number of Relay box radiant Heat are 2 per ZBS System.
Control up to 5 zones of heating elements by means of free-voltage relays.
Demand Relay of Pump.
Demand Realy of Boiler.
Identified by means of a micro-switch.
8
2.4. Wired/Wireless local zone module (AZZBS [W/R] LMR) Local control board that command the relay of heating demand or motorized damper and allows wired or wireless communication with the zone thermostat. Power supplied by the ZBS control board.
Input of open window detection.
Input of occupancy detection.
Control of proportionality and minimum air in motorized dampers.
Control of Heating demand relay.
Bi-directional device-main control board of the system communication.
2.5. Wired/Wireless intelligent motorized round damper (AZZBS [06-08-10] [W/R]) Damper with wired/wireless local zone module. Damper size: 6-8-10 inches diameter. Powered with 12 VDC by the local zone module.
Wired/Wireless local zone module Local control board that commands the relay of heating demand or motorized damper and allows wired or wireless communication with the zone thermostat. Power supplied by the ZBS Control board.
Input of open window detection.
Input of occupancy detection.
Control of proportionality and minimum air in motorized dampers.
Control of Heating demand relay.
Bi-directional device-main control board of the system communication.
2.6. Blueface Intelligent Thermostat (AZZBSBFSW) Graphical color touch screen interface that controls the zone temperature. Configurable as master or zone. Powered by external transformer.
Graphical Interface available in 3 languages (English, French & Spanish).
Zone On/Off.
Selection of the set point temperature in intervals of 1ºF/0.5 ºC.
Selection of the system operation mode.
Sleep function.
Eco-Adapt function.
Zone temperature and system operation mode time schedule programming.
Remote access to other zones of the system.
Bi-directional thermostat-main control board of the system communication.
9
2.7. Wired/Wireless Tacto thermostat (AZZBSTCSW [W/R]) Wired/Wireless zone thermostat with backlit monochrome LCD touch screen that controls the zone temperature. Surface mounting. Available in white and gray.
Backlit LCD display.
Temperature sensor with configurable offset.
Display of Temperature and Set point in 1°F/0.5°C increments.
Remote zone control.
Powered by two 1,5V batteries (type AAA; included). (Only
wireless thermostat, AZZBSTCSWR)
2.8. BACnet Gateway (AZZBSBACNET) The BACnet interface allows a Building Management System to control all variables of the ZBS systems. Bus automation power supply. Assembly integrated in ZBS board. Its uses a standard open protocol based on ASHRAE Standard 135, and its objects are:
- Compatible with BACnet (ANSI /ASHRAE-135) - Compatible with BACnet/IP (ISO16484-5)
The BACnet interface is a Plug&Play device for ZBS, and it allows to control and monitor the following variables:
Operation Mode. Indoor Unit status. Fan status and Fan Speed. Set point setting for Cooling and Heating for each zone. On/Off for each zone. Room Temperature in each zone. Opening damper status for each zone. Indoor unit and ZBS errors. Relay supplemental heat status for each zone.
2.9. Operation Mode Synchronizer (AZZBSMODESYNC) Mode synchronization module for VRF Heat Pump installations with multiple indoor units. Power Connection to be wired from RS485 MODBUS interface included in the ZBS control board.
Synchronization module for Heat Pump installations with multiple indoor units with ZBS system.
Operation mode synchronizer controls up to 16 ZBS systems in the same VRF system.
10
3. DESCRIPTION, ASSEMBLY AND MODULES CONNECTION 3.1. General recommendations Closely follow the instructions on this manual to avoid installation and maintenance issues.
The system should only be installed by qualified personnel.
Never use solid wire to install the system. This is a communication device and requires the use of communication cables.
While connecting the devices, be sure the system is not powered.
Follow the local installation regulations for low and high voltage installation. The recommended specifications for the cable to install this system are:
o 4 wired o Stranded o AWG 20 o Plenum o Shielded
When interconnecting different ZBS systems only use the A and B contacts of the communication bus. It is not recommended to connect the + and – contacts, nor the ground.
Follow the color codes and polarity indications in the system components.
Do not run the bus cable near high power cables or near electrical motors to avoid electromagnetic interference in the system communications.
Use the following recommendations to locate the thermostat:
Use the following recommendations to wireless local module:
h= 5 ft
11
3.2. ZBS control board (AZZBSxx)
3.2.1. Installation The ZBS control board is delivered in a bolted case to facilitate its assembly (Fig. 1). This module is externally supplied with 120/230 VAC. The location and assembly of this module must fulfill all the current electrotechnic standards. To assemble this control board, follow these steps:
Place the control board next to the unit you want to check.
Unscrew the cover to secure the back to the wall.
Once all connections are made, screw the cover again.
Fig. Fig. 1
3.2.2. Connections
Fig. 2
1. - Power supply Power supply 120/230 VAC line. The ZBS control board is protected by a self-resettable fuse. This is an electronic component that does not require any action other than cycling the power to perform the reset. 2. - Heating Stage 1 Output If the system includes Auxiliary Heat, when required by the heat demand, this output enables the First Stage of Auxiliary Heat. The technical specifications for the 1st Stage Aux. Heat relay are: Imax. =1 A @ 24VAC, dry contacts.
If higher power is required for control, use external contactors of appropriate capabilities.
N.º Description
Power connection (120 / 230 V)
Heating stage output 1
Heating stage output 2
Protection probe input
Alarm input (normally closed)
Air conditioning gateway port
Automation bus
Reset system button
Expansion bus D.max = 1,5 m
Fig. 3
Fig. 4
12
3. - Heating Stage 2 Output This output enables Second Stage of Auxiliary Heat, if the system includes two stages Auxiliary Heat.
The technical specifications for the 2nd Stage Aux. Heat relay are: Imax. =1 A @ 24VAC, dry contacts.
If higher power is required for control, use external contactors with appropriate capabilities. 4. - Protection probe Input This input is used to connect the supply temperature sensor. 5. - Alarm input (NC) When this input is open it will stop the AC unit, and close all dampers. This input is shipped with a jumper in the connector that should be left in place unless an alarm input is connected. 6. - Air conditioning Gateway This Interface provides the communication between ZBS control board and AC Indoor unit (Fig. 7).
Fig. 7
7. - Automation bus These are the elements that can be connected:
Operation mode synchronizer.
BACnet Gateway.
The Operation mode Synchronizer allows the synchronization the VRF Heat Pump installations with multiple indoor units with ZBS System.
There is one connector with 5 contacts to connect the communication bus. This connector only supports the daisy chain configuration. Connect the cables to the connector contacts following the color code indicated below (Fig. 8). The BACnet Gateway is an integrated, disconnect the terminal and snap the connector and the gateway support tube as shown in the pictures (Fig. 9):
Fig. 5
Fig. 6
Fig. 8
13
Fig. 9
8. - Reset System Button If the whole system needs to be reset (normally a replacement board that has been used before, or at the request of the technical support as a last resource to fix a problem), press and hold SW1 until LED 19 stops flashing (Fig. 10). A system reset will return all configurations to default values and conditions. 9. - Expansion Bus The expansion bus allows the connection of the following devices:
Intelligent motorized round damper (wired / wireless).
Zone local modules (wired / wireless).
Relay box radiant heat control. There are 3 connectors with 5 contacts available to connect the expansion Bus. Connect the cables to the connector contacts according with the color code indicated below (Fig. 11).
Fig. 10
Fig.11
14
3.3. Wired/Wireless intelligent motorized round damper (AZZBS [06-08-10] [W/R]) 3.3.1. Installation Follow the local recommendations to insulate and seal the ductwork with the damper. Keep the motor outside of the insulation.
3.3.2. Damper setting The motorized dampers included a control system that allows you to manually set the maximum and minimum opening of each damper. Maximum opening (REG) The Motorized damper offers maximum aperture adjustment which balances the airflow of each damper to the real needs of the installation. By default, the dampers are configured with a maximum opening at Position I. To adjust the control of the dampers proceed as follows:
The damper must be completely closed to mechanically adjust its flow. To make this adjustment create demand in all zones, so that the indoor unit runs at maximum capacity. Then deactivate the zone to be adjusted, and verify that there is no air supplied to that zone.
With the damper closed, place the lever marked REG in the actuator to the desired open position. There are 4 position - I, II, III, and IV, with position I being completely open and position IV having the slightest opening.
Using an anemometer verify that the flow in each grille is within the installation requirements.
Minimum Air (A-M) Similarly, the motorized damper allows a minimum air opening, if needed. By default, the “a” damper is configured in the full-close position. To adjust minimum air for any damper, proceed as follows:
Check that the dampers are completely opened to set the minimum air. To do so, set the system to STOP mode, from the Blueface main thermostat.
With the damper opened, place the handle A-M in the desired open position. It has 4 positions - a, b, c, d-, where "a" is fully closed and is "d" is the fully open for minimum air.
Check with an anemometer that the flow in each grille is within the installation requirements.
15
3.3.3. Connection The local zone module (Fig. 12) is responsible of the control and supply of the motorized damper and the communication with the zone thermostat. For zones where only radiant heating elements are controlled, it is required to install a module for controlling the temperature and the relay of the radiant control board. In addition, it offers these other functionalities:
- Zone control by occupancy contact. - Zone control by window contact.
*Note: To connect the window and occupancy detector inputs, use shielded wires.
Fig. 12
The zone local module (Fig. 12) is an element connected to the expansion bus of the main
control board . The connection is performed by means of a 5-pin terminal. Fit the wires with the terminal screws, following the associated color and letter code (Fig. 13).
The thermostat can communicate with the module either via wire or wireless. For the wired option, the connection
is performed through a 4-pin terminal . Fit the wires with the terminal screws, following the associated color and letter code (Fig. 14). Remember the distance between module-thermostat must not exceed 40 meters.
3.4. Wired/Wireless local zone module (AZZBS [W/R] LMR) 3.4.1. Installation To assembly the local zone module follows the next steps (Fig. 15):
Fix the support where are required.
Fit the module in the support.
3.4.2. Connection See point 3.3.3.
No. Description
Motorized element connector
Connection probe
Main control board connection
Thermostat connection (Only available in wired module)
Occupancy detector connection*
Window detector connection*
Fig. 13
Fig. 14
Fig. 15
16
3.5. ZBS Relay box radiant heat control (AZZBSOUTPUT5)
3.5.1. Installation The relay board for radiant elements control is fixed on the wall by screws (Fig. 16).
3.5.2. Connection
The relay board (Fig. 17) for radiant elements control is an element that is connected to the expansion bus of the ZBS control board.
Fig. 17
The connection to the expansion bus will be done through a 4-pin terminal located at the bottom right of the module (Fig. 17). Fit the wires with the terminal screws, following the associated color and letter code (Fig. 18).
The board has up to 5 relays for the control of radiant elements. The technical specifications for the demand Heat relay are: Imax. =1 A @ 24VAC, dry contacts. The 6th relay is to control a water pump. The technical specification for this relay is: Imax. =1 A @ 24VAC, dry contacts. The 7th relay is to control a boiler. The technical specification for this relay is: Imax. =1 A @ 24VAC, dry contacts.
If higher power is required for control, use external contactors of appropriate capabilities. The board has two microswitchs on the bottom of the module. Relay output addressing microswitch:
Zones 1-5
Zones 6-10
For example: The relay to control the radiant element of a zone module with address 6 is the R1 of the control board with address configured for zones 6-10.
Fig. 16
Fig. 18
17
3.6. Wired/Wireless thermostats (AZZBSBFSW and AZZBSTCSW [W/R]) 3.6.1. Installation ZBS wired/wireless thermostats are surface mounted. To fix a surface thermostat to the wall, follow these steps:
Separate the wall support from thermostat (Fig. 19).
Fix the wall support directly on the wall or on a wall-embedded flush box.
Replace the wall-support. Make sure that it is fixed by the support flaps.
Once connection is finished, place display on the wall-support (Fig. 20).
Maximum distance between local zone module – wired thermostat is 40 meters.
Maximum distance between local zone module – wireless thermostat is 20 meters in open space.
3.6.2. Connection The ZBS wired thermostats are elements connected to the zone module to be controlled. The surface thermostats are connected through tabs located at the back of the thermostat (Fig. 21). Fit wires with the terminal screws, following the associated color and letter code.
3.7. Operation Mode Synchronizer (AZZBSMODESYNC)
3.7.1. Installation The operation mode synchronizer is a synchronization module for VRF Heat pump installations with multiple indoor units with ZBS system (for VRF Heat recovery is not necessary).
The operation mode is set by the ZBS master system (System ID: 1) to the rest ZBS systems.
Heat Pump Changeover Master controls up to 16 ZBS systems.
The ZBS Master system (System ID: 1) must be connected to the Indoor unit with the remote control configured as the system Master.
Fig. 19
Fig. 20
Fig. 21
18
3.7.2. Connection The wiring should not exceed 40 meters between device and stranded AWG20 shielded cable should be used. Connect the operation mode synchronizer module with the interface on the ZBS Master system. Use a 4 wire shielded cable, stranded, plenum and shielded. Connect the cable from the ZBS Master System to the rest of the ZBS systems to be controlled by the operation mode synchronizer module. Connect only the communication wires A & B contacts.
AW
G 2
0 –
2 w
ired
*SYSTEM ID: 2 to 16> Secondary System
*SYSTEM ID: 1> Master System
19
4. QUICK OR INITIAL SYSTEM CONFIGURATION After system assembly and successful connection test, connect the system power supply to configure it. In order to facilitate the installation and reduce the operation times, this system has a self-guided configuration menu where you can configure the main system parameters. This menu is displayed by default on the thermostats when they are configured for the first time. The thermostats associated to the system work as configuration interfaces. There are 2 types of thermostats available:
Blueface (Graphic interface)
Tacto (Touch screen)
Caution: Do not forget to start configuring the zone modules that will be configured as subordinate (secondary).
System reset: If you need to reset all the system, press and hold SW1 until LED 19 stops flashing (Fig. 22).
4.1. Configuration via Blueface Important: Once you begin this process, you will not be able to go back. You must complete the configuration process.
1) Language settings The languages available are: English (Default), Français and Español.
Once you have selected your language, press to go to the next step.
2) Select zone At this moment it is required to define the zone address associated to this module, from 1
to 10. Select the desired value using . Once you have selected the number of the
zone, press to go to the next step.
3) Select subordinate damper (secondary)
If needed, the system allows associating subordinate modules to control more than one damper. This allows managing dampers from the thermostat that is being configured. These are the available options:
NO, if there is no need to associate an additional damper with a zone.(Default)
LINK, if one or more additional dampers are needed for a zone. The system displays as subordinate modules the modules configured as not associated to another zone and that have no thermostats connected (either wireless or wired).
YES, if you need to associate an additional damper with a zone. If you confirm this option, the configuration process of this module will be completed.
Press on the value to select the desired option and press to confirm. If you select LINK,
select the number of the desired zone, using the icons and press to confirm. Repeat this process as needed to associate all the outlets you want.
Once this process is completed, including the option NO selection, press accept to go to the next step.
Fig. 22
20
4) Master thermostat configuration This step defines the operation of the thermostat as:
Master thermostat: Controlling the zone parameters and operation modes of the system.
Zone thermostat: Controlling the zone parameters.
Considering that only one thermostat can be configured as Master, this parameter will not appear for selection in the quick configuration menu. For installations with fan coil zone modules configured for 4 pipes, each module can be configured as master. If you want this thermostat to be configured as master of the system, select the option ON
using the icons and press . Otherwise, select the option OFF and press .
5) Zone control stages This step defines the zone control stages. The following options are available:
Cooling/Heating air: Uses only the air equipment for this zone.
Radiant Heating: Uses only the radiant element available for this zone.
Combined Heating: Allows the user to heat the zone simultaneously through the air equipment and radiant element of the zone. The air or the radiant element can operate as supplemental heating source to reduce the temperature difference between the set point temperature requested and the room temperature in the zone. Once the room temperature reaches the set gap, 2 ºC adjustable, the supplemental equipment stops working and the main heating source remains working normally.
Use the icons to select the desired option. Once you have selected the type of
heating of the zone, press to confirm.
6) Disassociate module-thermostat To control the zone module without a thermostat (standalone mode), the thermostat has to be disassociated from the module once its configuration is completed. In zone wired modules, you can simply disconnect the thermostat from the module. They will be displayed as available in order to be associated to another zone module as a subordinate (Fig. 23).
*Thermostat reset: If there is any error in the initial configuration process and it is required to repeat the process, access the advanced configuration menu. Follow the steps described in section 5.1.1, select the zone option and select the value 0 to reset the thermostat.
Fig. 23
21
4.2. Configuration via Tacto It is important to determinate whether the thermostat is wired or wireless, since wireless thermostats need some prior actions to enter the configuration mode.
1) Wireless association channel opening (Only wireless) In order to associate the wireless thermostats to the system, you must first open the association channel of the main control board. To open this association channel. From the Blueface thermostat:
Press to access Configuration menu Press Settings Press Configuration Press
Enter on the warning screen Press Permit to access Press On to activate Press to confirm the value
From the ZBS control board:
Press on SW1 (Fig. 24) Wait until the 19 LED lights red Once the association channel is open, you have 15 minutes to make the association. If the time runs out, do this operation again.
The Wireless Thermostat will display the letters . Press and hold the icon
until the zone selection menu displays .
When you finish the association, turn it OFF to close the zone search.
Remember: In wireless thermostats you should remove the battery protection to activate its operation.
2) Wireless zone module selection (Only wireless)
The wireless thermostat will display the word (Fig. 25), make a long press on
until the thermostat start searching the wireless zone modules of the installation.
The word will be displayed on the screen, indicating that the search for wireless zone modules begins. Once the search completed, the screen will display the wireless zone
modules found, . Use the arrows to navigate through the different modules
found. The signal reception power value of the module, is presented in the screen. Press
to select a module. After the power value a will be displayed. The module selected will begin to open and close the motorized element connected and to emit a "beep" for its identification. If it is not the desired module, use the arrows to return and select
module. If the identified module is the one desired, press .
Fig. 25
Fig. 24
22
3) Zone selection (Wired and wireless) It is now required to define the zone address associated with this module. By default, the menu displays the lowest free address value (Fig. 26). Use the arrows
to select the desired address value. The menu displays the address values that are not occupied by other modules. If the
menu displays directly , it indicates that all address values are already associated
and are not available. Once the zone number has been selected, press the icon to go to the next step.
4) Subordinate dampers selection (slave) The system allows a zone to be associated with more than one damper, if needed. This allows the control of several outlets from the same thermostat. (Fig. 27). The available options are:
, this option indicates that no subordinate damper is required to be associated with the zone.
, to associate an available subordinate damper. The system displays as subordinate modules the modules configured as not associated to other zone and that have no thermostats connected (either wireless or wired).
, if association with one subordinate damper is required. By confirming this option, the module configuration process will be completed.
By using the arrows , select the desired option and press to confirm (Fig. 28). By
default, the option is displayed. If you select , select the address value of the zone
module that you want to associate by using the arrows and press to confirm. Repeat this process to associate the dampers that are needed. Once this process
is completed, press with the option selected to go to the next step.
Fig. 28
5) Zone heating stage This step defines the heating stage to be controlled in this zone (Fig. 29). The following options are available:
Air : Uses only the air equipment for this zone.
Radiant : Uses only the radiant element available for this zone.
Combined : This option is only configurable for zones where air and radiant
sources are available.
Fig. 27
Fig. 26
23
By default, the option Air, , will be displayed. Use the arrows to select the desired
option and press to confirm.
Fig. 29
6) Disassociate module-thermostat
To control the zone module without a thermostat (standalone mode), the thermostat has to be disassociated from the module, once the configuration completed. In zone wired modules you can simply disconnect the thermostat from the module (Fig. 30). The will be displayed as available in order to be associated to another zone module as a subordinate.
In case of wireless zone modules, this represents an additional step in the configuration. The option
will be displayed at the screen (Fig. 31). This option allows disassociating the thermostat of the
zone module. The option is displayed by default.
If you want to disassociate it, selects the option
using the arrows and press to confirm.
*Thermostat reset: If there was some error in the initial configuration process and it is required to make changes, access the advanced configuration menu. Follow the steps described in
section 5.2.1, select the option and select the value to reset the thermostat.
Fig. 30
Fig. 31
24
5. ADVANCED CONFIGURATION 5.1. Configuration via Blueface 5.1.1. Blueface configuration menu Besides the quick setup menu, the system has a number of configuration parameters to complete the installation. The system parameters can only be changed from the main thermostat.
Parameter Description Options Type
System ID System ID 1-16 Zone
Zone ID Zone ID associated to the thermostat Zone: 1-10 Reset: 0
Zone
Subordinate Secondary control dampers associated with this
thermostat (secondary)
Look up Link
Release Zone
Master Thermostat settings Master Zone
Zone
Set point Maximum temperature in heating mode and minimum
in cooling mode or mode deactivation Heating: 66 - 86ºF, OFF Cooling: 64 - 78ºF, OFF
System
Proportionally Damper proportional opening All/Nothing
Proportional (Default) System
Minimum Air Minimum opening of the damper Activate
Deactivate (Default) System
Window Zone control by open window Deactivate (Default)
Normally open Normally closed
Zone
Occupancy Zone control by occupancy Deactivate (Default)
Normally open Normally closed
Zone
Heating stages Configuration of the zone heating source Air: Yes-No
Radiant: Yes-No Zone
Heating conf. It sets the temperature difference of the heating stage
and the principal heating stage
Heat temp. gap: 0-2-4 Heat main stage: Air or
Radiant Zone
Permit Activation of the radio association channel Activate
Deactivate Zone
Function Thermostat features Advanced
Basic Zone
Q-Adapt Configuration of the zone weight Auto
Manual: 1-99 Zone
Ambient Hides the room temperature On Off
System
Offset Room temperature correction -5 ºF to 5 ºF Zone
Auto mode Auto mode configuration Set point differential Mode change time
Heating Factor System
25
AC Unit errors It displays the errors of the system On Off
System
BACNET IP It displays the IP of the BACnet gateway, the network
mask and the uplink port and allows you to modify them
IP address Subnet mask Gateway IP
System
Auxiliary heat Auxiliary heat for Air conditioning System
Information Information about system check-up
Room Devices
Firmware Errors
Zone
To access the setup menu of the Blueface controller, from the main screen, press the icon
and select the option Settings . In this menu select Configuration, a pop up warning message appears to alert you that it is exclusive for installers. Select Enter to access this menu. If you want to return to the previous menu, press Exit.
If you want to return to the setup menu, press . If you don't want to modify any other
parameter or return to the main menu, press .
System ID: This option allows defining the number of this system inside the whole
installation. By default, the value is 1. To modify the ID value, use . The system will display the address values available with a maximum value of 16.
Once the desired value has been selected, press to confirm.
Zone ID: This option displays the address associated with the zone of the thermostat. To
modify the address value, use to select the value 0, it will reset the thermostat and damper associated, leaving them free for a new configuration. The thermostat will redirect you to the quick configuration menu (see section 4.1) to begin the process again.
Once the desired value has been selected, press to confirm.
Subordinate zones ID (slave): This option shows the secondary zone modules associated with the thermostat. You have the following selection options:
o Look up: This option allows checking the information about the subordinate modules associated with the main module. The value is enabled by default in
the menu of secondary zones. Use to display the associated modules. If NO is displayed, this thermostat has no associated secondary control dampers.
o Associate: Allows associating secondary dampers to the thermostat. Press Associate to activate this option. If NO is displayed, no zones are available to associate. The system displays as subordinate modules the modules configured as not associated to other zone and have no thermostats connected (either
wireless or wired). Use to select the zone to associate. Press to confirm. Repeat this process to associate the dampers required. Once this
process is completed, with the option NO selected, press accept to go to the next step.
26
o Release: Allows releasing a zone that has been associated as slave. Press Release to activate this option. If NO is displayed, there is no secondary zones
associated to release. Use to select the zone to be released and press
to confirm.
Master: Shows whether the Blueface is configured as Master or Zone. If you want to
change the thermostat function, use to select the desired value and press to confirm.
*Note: Only available if the thermostat is configured as Master or if you do not have Blueface configured as Master.
Set point: This menu allows you to change the maximum set point temperature for heating mode [86ºF - 66ºF] and minimum temperature in cooling mode temperature [64ºF - 78ºF]. If you want to disable any of the modes, select OFF and the mode will be disabled for the user. By default the system has the maximum temperature in 86ºF for heating and minimum temperature of 64ºF for cooling. If you want to modify the limit temperature, press on the value you want to modify and it will be highlighted by a blue
background. Use the arrows to select the desired value and press to confirm.
Damper proportionality: This menu allows you to activate/deactivate the proportionality
of the system dampers. The proportionality adjusts the damper opening or closing in 4 steps based on the temperature demand of the zone, regulating the flow. It is configured with proportionality, Proportional, by default. If you want to activate the
function, press All/nothing. Once it is selected, press to confirm the change.
Damper minimum air: This menu allows you to activate/deactivate the minimum air opening of the system dampers. This allows the access of a minimum air flow in zones where the comfort temperature has been already reached. This way, there is a fresh air flow through the air conditioning ducts. If the zone is deactivated, the damper will be totally closed. The system is configured without minimum air, Deactivate, by default. Press Activate if
you want to activate the function. Once it is selected, press to confirm the change.
Zone Control by window contact: This option allows controlling the state of a zone
module based on the opening of the window. It only acts on the control element of the zone module. If it is connected to a thermostat, that thermostat will alert through a message in its main screen in case of its activation. The system will be configured as Deactivate by default. If you want to activate it, press
Step 4 (REG)
Step 3
Step 2
Step 1 . Step 0
(A-M)
27
Norm. Open if you want the logic of the contact to be normally open or Norm. Closed if
you want the logic of the contact to be normally closed. Once it is selected, press to confirm the change.
Zone control through occupancy detector: This option allows controlling a zone module based on the occupancy through a detector. In an active zone, if it does not detect any occupancy after 5 minutes, it activates the sleep function and the zone will deactivate in 90 minutes. This function is only available in zone modules associated to a thermostat. It does not work in secondary zones modules. The system will be configured as Deactivate by default. If you want to activate it, press Norm. Open if you want the logic of the contact to be normally open or Norm. Closed if
you want the logic of the contact to be normally closed. Once it is selected, press to confirm the change.
Heating stages: This menu allows the configuration of the heating source of the zone. It takes the parameters established in the initial configuration by default. These are the features to be configured:
o Air: It activates the air heating in the zone. o Radiant: It activates the radiant heating in the zone. o Combined: It activates the air & radiant combined heating at the same time. o Off: It disables the heating source in the zone.
Use to choose the desired option and press to confirm.
Heating configuration: This option allows you to set the temperature difference of the heating stage (available values: 0, 2 or 4. It is set on 4 by default) and the principal heating stage (Air or Radiant).
Permit: This option allows you to open the wireless association channel of the system to connect the ZBS wireless thermostats. The channel is closed Deactivate by default.
Press Activate if you want to open the association channel and press to confirm. Press Deactivate if it is active and you want to deactivate it.
Function: This option allows you to disable the thermostat advanced settings of the thermostat and use only the basic controls. These are parameters to control in basic mode:
o On/Off o Temperature o Operation Modes o Eco-Adapt o Interface configuration
It is configured as Complete by default. Press Basic to change the configuration. Moreover, the master thermostat allows you to send its configuration to the rest of zones. To do that, select YES. Once the parameters you want to modify are configured,
press to confirm. If you want to go from Basic to Complete function, press and hold on the main screen
clock to access the function menu.
28
Q-Adapt: This option allows to define the individual weight of each zone to adapt the flow of the system to the zone needs. The total weight of the system is 100. These are the available configuration options:
o Automatic: The system proportionally divides its total weight (100) among the zone modules configured with air stage.
o Manual: It allows modifying the zone total weight with values from 1 to 99. The weight shown is sum of the main and subordinate modules of the zone. It shows the assigned value in automatic mode by default. Based on its modification, the different levels of each zone are indicated:
- Q-Power: Highest value assigned in automatic mode. - Q-Standard: Value assigned in automatic mode. - Q-Silence: Lowest value assigned in automatic mode. - Q-Minimum: Value 1.
The logic of the system speed change based on the weights is shown in the following table:
2 Fan speeds 3 Fan speeds 4 Fan speeds 5 Fan speeds
Speed 1 1-50 1-33 1-25 1-20
Speed 2 ≥51 34-66 26-50 21-40
Speed 3 - ≥67 51-75 47-60
Speed 4 - - ≥76 61-80
Speed 5 - - - ≥81
By default, it is set to Automatic. If you want to change it to Manual, press on it. In Manual mode, it will show the value of the zone total weight. If you want to change this
parameter, press the value 1-99 to select it and use to determine the weight. Once
the desired value has been selected, press to confirm.
Ambient: This option allows you to hide the information about the room temperature of the thermostat. It is activated by default. If you do not want your thermostat to show this
information, press Deactivate. Once the desired value is selected, press to confirm.
Offset: This option allows correcting the room temperature measured by the thermostat as it may be slightly altered due to close heating or cooling sources. It allows you to regulate the temperature with a correction factor between -5ºF/-2.5ºC and 5ºF/2.5ºC in intervals of 1ºF/0.5ºC. It is configured at 0ºF/ºC by default. To adjust the temperature
value use and press to confirm.
Auto mode: This option allows you to configure the operation parameters that affect the Auto Mode performance.
o Set point differential: It defines the minimum difference required between the cooling and heating set-points. The differential values range between 0ºF/ºC and 7ºF/3.5ºC, in steps 1ºF/0.5ºC. The value is 2ºF/1ºC by default. Press on the
variable to select it and use to select to the desired value. Then, press to confirm.
o Mode change time: It defines the minimum amount of time a mode has to work before the mode change. You can select the following values: 15, 30, 60 and 90
29
minutes. It is set in 30 minutes by default. On the variable to select it and use
to select the desired value. Then, press to confirm.
o Heating factor: It defines a temperature differential in heating mode. If the zone surpasses this differential, the system gives to prioritize the heating mode. The differential values to be selected are between 3ºF/1.5ºC and 8ºF/4ºC in intervals of 1ºF/0.5ºC. It is deactivated N/A by default. Press on the variable to select it
and use to select the desired value. Then, press to confirm.
AC Unit error: This option allows you to activate/deactivate the error display. It is activated by default.
BACNET IP: This parameter displays the IP of the BACnet gateway, the network mask and the uplink port and allows you to modify them. Press on the value you want to
change, modify it and then press to confirm.
The values by default are: - BACnet gateway IP: 192.168.1.100 - Subnet Mask: 255.255.255.0 - Connection Port: 192.168.1.1
Note: In case of system reset, it will return to default values.
Auxiliary heat: The operation of auxiliary heat is influenced by several parameters:
o Auxiliary heat (1) - Defines how many stages of auxiliary heat a system has. Possible values are
0, 1, and 2, with a default of 0.
0: There is no auxiliary heat. The system works only with the heat pump. If set to 0, Emergency Heat mode will not be available.
1: One-Stage Auxiliary Heat. 2: Two-Stage Auxiliary Heat.
- First Supply Heat. If the setting for Auxiliary heat is 1 or 2, then the first system to supply heat must be defined as either: Heat Pump. Aux. Heat. Note: If the auxiliary heat is electrical and the installation has a Heat Pump changeover master, then the first to supply heat must be set to be the Heat Pump.
o Auxiliary Heat (2), Fan Configuration: In the second screen configuration, there are the following parameters:
- Heating device: Defines if the ID unit fan must be active during the auxiliary heat operation. Electric (Fan ON) Furnace (Fan OFF)
- Fan delay (sec): Defines the delay time (in seconds) to turn off the fan. Possible values are 0, 45, 60 and 120.
o Auxiliary Heat (3), First Stage Activation: the user must define three parameters:
30
- First Stage Differential: Temperature the system has to surpass to activate the first stage of auxiliary heat. Values [2-10]ºF / [1-5]ºC, by default 2ºF/1ºC.
- First stage hysteresis: Defines the hysteresis for the operation of the first stage. Range: 1ºF/0.5ºC to First Stage differential value still 6ºF/3ºC at maximum. By default 1ºF/0.5ºC.
- Minimum time exhausted: The minimum time that the Heat Pump must be active before the first stage of auxiliary heat can be activated. Values [0-120] minutes, by default, 30 minutes.
o Auxiliary Heat (4), Second stage activation: The user must define three parameters:
- Second stage differential: Temperature the system has to surpass to
activate the second stage of heating. Values [2-10 ºF / [1-5]ºC, by default
2ºF/1ºC.
- Second stage hysteresis: Defines the hysteresis for the operation of the
second stage. Range: 1ºF/0.5ºC to Second Stage differential value still
6ºF/3ºC at maximum. By default 1ºF/0.5ºC.
- Minimum time exhausted: The minimum time that the first stage must be
active before the second stage of auxiliary heat can be activated. Values [0-
120] minutes, by default, 30 minutes.
If you want to modify any parameter, use to change its value or press on the option
you want. Once you have selected the correct value, press to confirm.
If you want to return to the configuration value, press . Otherwise, if you do not want to
change any other parameter or if you want to return to the main value, press .
Information: This menu shows control information about the system.
o Room temperatures of the zones: This section shows the room temperatures
of the different zones of the system. Select the zone you want to see using .
Press to return to Information.
o Devices: It shows you a detailed list of the different devices installed in the
system. Press to return to Information.
o Firmware: It shows the control information of the system. - Tacto version. - Zone module version. - Main control board version. - Relay board version.
Press to return to Information.
o Errors: It shows if there is any incidence in the system (see section 6).
Press to return to Information.
If you want to return to the previous menu, press .
31
5.1.2. Blueface Interface Menu
To enter the Blueface Interface menu, from the stand-by screen, press icon and select
Settings . On this sub-menu, press on the option Interface
If you want to modify any parameter, use to change its value or press on the option you
want. Once you have selected the correct value, press to confirm.
If you want to return to the configuration value, press . Otherwise, if you do not want to
change any other parameter or if you want to return to the main value, press .
Brightness: Configure screen brightness for both active mode and stand-by mode of the Blueface. For the stand-by mode the brightness can be configured so that it remains dimly back lighted or completely shut off. To configure this parameter simply press son it so that it switch for the desired status.
The Blueface in stand-by backlits slightly, this way it will be deactivated (the Blueface switches off completely when it is in stand-by). Otherwise, press Off to enable the brightness in stand-by.
Date and time: You can adjust the day of the week, the time, the time format and the automatic time change. To modify the day of the week, press on the different parameters
(day, month and year). Use to select the desired value. Press to save the changes.
If you want to modify the system time, press on the parameter you want to modify (hour
or minute) and it will change its color. Use to modify the value. To modify the format, press on the parameter format (24h/AM) to select the desirable value.
The automatic time change will be activated by default. Press on the value if you want to
deactivate this option. Press to save the changes. Language: Select among three languages for the interface: English, French and Spanish
are available.
Beeping: Allows activating or deactivating the beeping of the touch screen. By default is activating.
32
5.2. Configuration via Tacto 5.2.1. Tacto configuration menu Besides the functions defined in the quick configuration menu, the system has other configuration parameters to complete its installation:
Parameter Description Options Type
System ID ()
It shows the system address Zone
Zone ID ()
Zone ID associated to the thermostat Zone:
Reset: Zone
Slave ()
Secondary control dampers associated with this thermostat (secondaries)
Zone
Window contact ()
Zone control by open window
Zone
Occupancy
contact () Zone control by occupancy
Zone
Heating stages
() Control of the zone heating stages
Zone
Permit () Activation of the radio association channel
Zone
Disassociate
() Disassociate the zone module thermostat (subordinate
module) (Only for wireless Tacto)
Zone
System information
() Information of the system control
(Wireless Tacto)
(Wireless Tacto)
Zone
Q-Adapt () Configuration of the zone weight Auto ()
Manual (): Zone
Offset () Room temperature correction - ºF to ºF Zone
To access the advanced configuration, the thermostat must be in
main screen while the zone is Off. Press and hold until the room temperature is displayed in the screen (Fig. 32). Once you are
in this screen, press and hold and you will access the advanced configuration menu.
If you want to go back to the main screen, press .
System ID (): This option displays the system address associated. Fig. 32
33
Zone ID (): This option displays the address associated with the zone of the
thermostat. To modify the zone value . The configured value will start flashing.
That indicates that you can modify it. Use the arrows to select the value , this will reset the zone module the thermostat is associated to and the secondary modules (subordinate) associated to it. That way, they are free for a new configuration. The thermostat will redirect you to the quick configuration menu (see section 4.2) to begin the process again.
Once the desired value has been selected, press to confirm (Fig. 33).
Fig. 33
Subordinate zones ID (secondary) (): It shows the address of the subordinate
zone modules associated to it. If the value is displayed, that indicates that the zone module has not secondary zone modules associated. To see, add or remove a
subordinate zone module, press and the menu value will start flashing. That indicates you are in the menu.
Use the arrows to see the associated modules (Fig. 34).
Fig. 34
o Associate a secondary zone module (): If you want to add a module of secondary zone more, select
and press the icon to access the menu of association (Fig. 35). If you do not see this option, it means that there are no available dampers to associate. The system displays as subordinate modules the modules configured that have not been associated to another zone and having no thermostats connected, either wireless or wired.
Use the arrows to select the value you want to associate and press
to confirm. Then, the menu will show the value of the next available
damper. If it shows the value , that indicates there are no available dampers in the system.
Fig. 35
34
o Release a control damper (): If you want to release a subordinate zone
module that has been associated, select it using the arrows and press
to access the release menu. This menu displays the option to release the control damper, by default. If you do not want to release that zone,
select and press to return to the previous menu (Fig. 36).
Fig. 36
Zone control through window contact (): This option allows controlling the state
of a zone module based on the opening of the window. It only acts on the control element of the zone module. If it is connected to a thermostat, that thermostat will alert through a message in its main screen in case of its activation. This parameter is off by
default . If you want to modify it press and the menu value will start flashing. That indicates you are in the menu. To activate the function, define the logic of
the contact. You could choose either normally open, , or normally closed, . Choose
the desired option using the arrows and press to confirm (Fig. 37).
Fig. 37
Zone control through occupancy detector (): This option allows controlling a zone module based on the occupancy through a detector. In an active zone, if it does not detect any occupancy after 5 minutes, it activates the sleep function and the zone will deactivate in 90 minutes. This function is only available in zone modules associated to a thermostat. It does not work in secondary zones modules.
If you want to modify it press and the menu value will start flashing. That indicates you are in the menu. To activate the function, define the logic of the contact.
You could choose either normally open, , or normally closed, . Choose the desired
option using the arrows and press to confirm (Fig. 38).
35
Fig. 38
Stages control (): This option allows managing which elements are available to
control the temperature of the zone. The following options are available:
o Air (): Uses only the air equipment for this zone.
o Radiant (): Uses only the radiant element available for this zone.
o Combined (): This option is only configurable for zones where air and radiant sources are available. The air equipment operates as support of the radiant element of the zone to reduce the temperature difference between the set point temperature requested and the room temperature in the zone. Once the room temperature is within the temperature difference set, 1ºF/2ºC configurable, the air equipment fails to act to operate only with the radiant element.
o : This option allows the user to block the system operation in cooling
mode , or heating mode .
The heating mode is configured first and the cooling mode is configured afterwards.
Press to start the modification. Then, the value of the menu will start flashing.
That indicates you are in the menu. Use the arrows to select the desired option. Once the type of air conditioning option you want to use for the zone is selected, press
to confirm.
Disassociate module-thermostat (secondary module) () (Only wireless): To
control the zone module without a thermostat (standalone mode), the thermostat has to
be disassociated from the module, once the configuration completed. The option will be displayed at the screen. This option allows disassociating the thermostat of the
zone module. The option is displayed by default. If you want to disassociate it,
selects the option using the arrows and press to confirm (Fig. 39).
Fig. 39
36
System information (): This menu shows control
information about the system. Press to access the menu. To navigate between the different sections,
use the arrows and press to access. If
you want to leave this menu, press to return to the previous menu (Fig. 40).
o Room temperatures of the zones (): This section shows the room
temperatures of the different zones of the system. Press to access
and use the arrows to navigate through the room temperature of the
different zones :. If you want to leave this menu, press to return to the previous menu (Fig. 41).
Fig. 41
o Wireless output strength () (Only available in wireless thermostats): It shows a percentage that reflects the data reception strength of the wireless thermostat.
If is displayed at the screen, it indicates that it is not communicating. If you
want to return to the previous menu, press. If you want to leave this menu,
press to return to the previous menu.
o Thermostat battery () (Only available in wireless thermostats): This menu displays the percentage of battery left in the wireless thermostat. If you want
to leave this menu, press to return to the previous menu.
o Devices connected to the system (): This section shows the number or type of devices connected to the system. You could see the following icons:
- : Wireless Tacto thermostats connected to the system.
- : Wired Tacto thermostats connected to the system.
- : Blueface thermostats connected to the system.
- : The communications channel in which the wireless thermostats.
Values are between .
- : Control board of the radiant element connected to the system.
- : Zone local modules.
Fig. 40
37
To agree to the menu press , utilize the arrows to navigate
between the different parameters. If you want to leave this menu, press to return to the previous menu (Fig. 42).
Fig. 42
o Firmware (): It shows the firmware version
of the following system elements (Fig. 43):
- : Main control board.
- : Tacto thermostats.
- : Zone module.
- “”: Radiant elements control board. The value in quotation marks indicates the ID of the board.
Press to access the firmware menu. Use the arrows to navigate between the different parameters. If you want to leave this menu,
press to return to the previous menu.
o Q-Adapt (): This option allows you to define the individual weight of each zone to
adapt the flow of the system to the zone needs. The total weight of the system is . These are the available configuration options:
o Automatic (): The system distributes proportionally its total weight () among the zone modules that have air stage.
o Manual (): It allows to modify the zone total weight with values between
. The weight shown is sum of the main and subordinate modules of the zone. It shows the assigned value in automatic mode by default. Based on its modification, the different levels of each zone are indicated:
- Q-Power (): Highest value assigned in automatic mode.
- Q-Standard (): Value assigned in automatic mode.
- Q-Silence (): Lowest value assigned in automatic mode.
- Q-Minimum (): Value 1.
The logic of the system speed change based on the weights is shown in the following table:
2 Fan speeds 3 Fan speeds 4 Fan speeds 5 Fan speeds Speed 1 1-50 1-33 1-25 1-20 Speed 2 ≥51 34-66 26-50 21-40 Speed 3 - ≥67 51-75 47-60 Speed 4 - - ≥76 61-80 Speed 5 - - - ≥81
Fig. 43
38
By default, the Automatic option is displayed. Press to modify the value.
The configured value of the will start flashing. Use the arrows to select the value.
Once the desired value has been selected, press to confirm. If you want to
leave this menu, press to return to the previous menu.
Offset (): This option allows correcting the room
temperature measured by the thermostat as it may be slightly altered due to close heating or cooling sources. You can adjust the temperature with a correction factor
between -ºF/-.ºC and ºF/.ºC, in intervals of
1ºF/0.5 ºC. It is configured at ºF/ºC by default. to access the menu and the value will start flashing. That indicates you are in the menu.
Use the arrows to select the desired value, press to confirm (Fig. 44).
Fig. 44
39
5.2.2. Basic /complete functionThis option allows you to disable the thermostat advanced functions of the thermostat and use only the basic controls. These are parameters to control in basic mode:
o On/Off o Temperature
It is configured as Complete by default . To change it to basic mode, press and hold on the
zone emphasized in the Fig. 45 until and the zone number you are modifying are displayed on the screen. Besides, the master thermostat can send its configuration to the rest of
zones. Utilize the arrows to select and to send the order to all the zones. Press
to confirm. If you do not want to activate the function , press to leave this menu.
Fig. 45
If you want to have complete functions, , press and hold the zone emphasized in the Fig.
46 until the menu is displayed on the screen. Besides, the master thermostat can send its
configuration to the rest of zones. Utilize the arrows to select and to send the order to
all the zones. Press to confirm. If you do not want to activate the function , press
to leave this menu.
Fig. 46
40
6. EXCEPTION CODES When the system detects an anomaly, the message Error or is displayed in the zone where the error is produced. There are two types of anomalies: blocking anomalies and non-blocking anomalies (in the cases of blocking errors). The blocking anomalies hinder the basic operation of the system, blocking the thermostat until the incidence is solved. The non-blocking anomalies allow the basic operation of the system. They are shown in the screensaver in TACTO thermostats and in the configuration menu in BLUEFACE thermostats. Once the incidence is solved, it will disappear from the screen. The errors that you may see in your screen are:
Error Description Blocking Corrective actions
Error 1
Erroneous thermostat communication (wired)
YES
Check the main control board state. Check all the connections and the wiring
between the zone module and the thermostat.
Erroneous thermostat communication (wireless)
YES Check the main control board state. Check the state of the wireless communications
of the zone-thermostat module.
Error 2
Erroneous communication with the
bus YES
Check the connection from the zone module to the bus.
Error 5
Probe in open circuit NO
Check that the connection from the probe to the zone module is not in open circuit.
Error 6
Probe in short circuit NO
Check that the connection from the probe to the zone module is not in short circuit.
Error 9
Machine-system
communications error NO
Check the connection from the communications gateway to the main control board.
Error 10 BACnet gateway-system
communications error NO
Check the connection from the BACnet gateway to the main control board.
*Blueface Thermostat reset: If you want to reset the Blueface with ERROR 1, press and hold on the word ERROR 1. It will reset, releasing the zones associated to the thermostat. Moreover, it will get you back to the quick configuration menu (see section 4.1) to reconfigure it.
41
7. SELF-TESTING 7.1. ZBS Control board (AZZBSxx) The main control board have integrated LEDs that detect unusual operations.
Fig. 47
Meaning
D1 Automation bus data reception Blink Green
D2 Automation bus data transmission Blink Red
D3 Main controller activity Blink Green
D4 Expansion bus data transmission Blink Red
D5 Expansion bus data reception Blink Green
D6 AC Unit ON/OFF Switch Green
D7 VMC Switch Green
D8 AC Unit bus data transmission Blink Red
D9 AC Unit data bus reception Blink Green
D10 Wireless frame communication reception Switch Green
D11 Device associated Fixed Red
D18 Wireless activity Fixed Green
D19 Main controller power supply Fixed Red
You can accomplish the self-testing of the system through the D2 self-testing LED that illuminates red (Fig. 47).
To do that, set your thermostat in STOP mode. The condition of the alarm jumper and the return probe is tested. If there is a communications gateway connected to the AC system, only the alarm jumper will be tested.
42
7.2. Inverter Integration gateway The inverter integration gateways have integrated LEDs detect unusual operations.
1) The supply gateways LED does not illuminate
Check the air conditioning equipment is powered.
Check the connection between the gateway and air conditioning equipment.
2) The microcontroller activity LED does not blink
Contact the Airzone after-sales department. Your microcontroller does not have activity.
3) The LEDs of communications with Airzone do not blink
Check the polarity of the A to B cable between the main control board and the gateway.
Check the wires.
Check the contacts of the wires inside the screw terminal.
4) The LEDs of communication with the indoor unit do not blink
Make sure the connections between the supply cable and the gateways and between the supply cable and the indoor unit board are correct.
5) The LEDs of machine thermostats communications do not blink
See section 3 solutions.
7.3. ZBS relay box radiant supplemental heat control (AZZBSOUTPUT5) The ZBS relay box radiant supplemental heat control have integrated LEDs that detect unusual operations.
Fig. 48
Meaning
D1 Alimentation Fixed Red
D2 Micro controller activity Blink Green
D3 Expansion bus data reception Blink Green
D4 Expansion bus data transmission Blink Red
D6-D12 Relay status led Switch Green
43
7.4. BACnet Gateway (AZZBSBACNET) The BACnet gateway have integrated LEDs that detect unusual operations.
Fig. 49
Meaning
U3 Ethernet data reception Blink Red
U4 Ethernet data transmission Blink Green
U5 Automation bus data
transmission Blink Red
U6 Automation bus data reception Blink Green
U66
Micro controller activity Blink Green
Ethernet connected Fixed Yellow
Ethernet activity Blink Green
1) All LEDs flashing
It indicates the IP selected for the ZBS BACnet Interface is already being used by other device. Access settings (See on page 11) and change the parameter IP Address.
Parque Tecnológico de Andalucía C/ Marie Curie, 21-29590 Campanillas - Málaga SPAIN TEL: +34 902 400 445 Fax: +34 902 400 446 http://www.airzone.es http://www.airzonefrance.fr/ http://www.airzoneitalia.it/