instruction manual - home - fire alarm resources · instruction manual document 50702 ... which...

32
PN 50702:B2 ECN 03-147 Auxiliary Power Supply APS-6R Instruction Manual Document 50702 4/14/03 Rev: B2 www.PDF-Zoo.com

Upload: vuongthuan

Post on 09-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

www

PN 50702:B2 ECN 03-147

Auxiliary Power Supply

APS-6RInstruction Manual

Document 507024/14/03 Rev: B2

.PDF-Zoo.com

Page 2: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

FWAsmauwwdoloThdeloN(NSttaDinMgooftethAwsoSnobedoantofirPinde•

ThaltosiloSsesethDtefirofdemSquwanim

w

ire Alarm System Limitationshile a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

n automatic fire alarm system—typically made up of oke detectors, heat detectors, manual pull stations, dible warning devices, and a fire alarm control panel

ith remote notification capability—can provide early arning of a developing fire. Such a system, however, es not assure protection against property damage or

ss of life resulting from a fire. e Manufacturer recommends that smoke and/or heat tectors be located throughout a protected premise fol-

wing the recommendations of the current edition of the ational Fire Protection Association Standard 72-1999 FPA 72-1999), manufacturer's recommendations, ate and local codes, and the recommendations con-ined in the Guide for Proper Use of System Smoke etectors, which is made available at no charge to all stalling dealers. A study by the Federal Emergency anagement Agency (an agency of the United States vernment) indicated that smoke detectors may not go

f in as many as 35% of all fires. While fire alarm sys-ms are designed to provide early warning against fire, ey do not guarantee warning or protection against fire. fire alarm system may not provide timely or adequate arning, or simply may not function, for a variety of rea-ns:

moke detectors may not sense fire where smoke can-t reach the detectors such as in chimneys, in or hind walls, on roofs, or on the other side of closed ors. Smoke detectors also may not sense a fire on other level or floor of a building. A second-floor detec-r, for example, may not sense a first-floor or basement e. articles of combustion or “smoke” from a develop-g fire may not reach the sensing chambers of smoke tectors because:Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets. Smoke particles may be drawn into air returns before reaching the detector. e amount of “smoke” present may be insufficient to

arm smoke detectors. Smoke detectors are designed alarm at various levels of smoke density. If such den-ty levels are not created by a developing fire at the cation of detectors, the detectors will not go into alarm. moke detectors, even when working properly, have nsing limitations. Detectors that have photoelectronic nsing chambers tend to detect smoldering fires better an flaming fires, which have little visible smoke. etectors that have ionizing-type sensing chambers nd to detect fast-flaming fires better than smoldering es. Because fires develop in different ways and are ten unpredictable in their growth, neither type of tector is necessarily best and a given type of detector ay not provide adequate warning of a fire. moke detectors cannot be expected to provide ade-ate warning of fires caused by arson, children playing

ith matches (especially in bedrooms), smoking in bed, d violent explosions (caused by escaping gas, proper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may dam-age the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con-sumed drugs, alcohol or medication. Please note that:• Strobes can, under certain circumstances, cause sei-

zures in people with conditions such as epilepsy. • Studies have shown that certain people, even when

they hear a fire alarm signal, do not respond or com-prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

A fire alarm system will not operate without any electri-cal power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis-sion systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72-1999 shall be fol-lowed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Ade-quate written records of all inspections should be kept.

Precau-S-4-2003.fm

2 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 3: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

-

-

-

www

Installation PrecautionsAdherence to the following will aid in problem-free installation with long-term reliability:WARNING - Several different sources of power can be connected to the fire alarm control panel. Discon-nect all sources of power before servicing. Control unit and associated equipment may be damaged by remov-ing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Soft-ware Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72-1999 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of sys-tem components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0°C to 49°C (32° F to 120° F) and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93%+ 2% at 32°C + 2°C (89.6°F + 1.1°F) per ULC. However, the useful life of the system's standby batter-ies and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi-nal room temperature of 15-27° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when sub-jected to lightning-induced transients. Although no sys-tem is completely immune from lightning transients andinterferences, proper grounding will reduce susceptibil-ity. Overhead or outside aerial wiring is not recom-mended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encoun-tered. Disconnect AC power and batteries prior to removingor inserting circuit boards. Failure to do so can damagecircuits. Remove all electronic assemblies prior to any drilling,filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assembliesremoved from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must befollowed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized person-nel.

Precau-S-4-2003.fm

FCC WarningWARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communi-cations. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a resi-dential area is likely to cause interference, in which case the user will be required to correct the interfer-ence at his own expense.

Canadian RequirementsThis digital apparatus does not exceed the Class A limits for radiation noise emissions from digital appa-ratus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

Acclimate Plus™, AWACS™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ aretrademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER. NION™ andUniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks andNOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademarkand LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark ofDatapoint Corporation. Microsoft® and Windows® are registered trademarks of the MicrosoftCorporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General ElectricCompany.

PN 50702:B2 4/14/03 3.PDF-Zoo.com

Page 4: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

w

Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manual, you can email us.

Please include the following information:

• Product name and version number (if applicable)• Printed manual or online Help• Topic Title (for online Help)• Page number (for printed material)• Brief description of content you think should be improved or

corrected• Your suggestion for how to correct/improve documentation

Send email messages to:

[email protected]

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 5: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Table of Contents

www

Section 1 Overview ...................................................................................................7Introduction .........................................................................................7Description ..........................................................................................7Specifications ......................................................................................9

Section 2 Installation .............................................................................................11Introduction .......................................................................................11Mounting in CAB-3/CAB-4 Series Cabinets ....................................12

Instructions for mounting: .......................................................12Chassis Mounting .....................................................................12

Wiring the APS-6R ...........................................................................13Field Wiring an APS-6R ...........................................................13Connecting Multiple APS-6R Power Supplies .........................15

Wiring Applications ..........................................................................16Connecting the APS-6R to an ICM/ICE Module .....................16Supplying Power to a Control Module .....................................17

Configuring the APS-6R ...................................................................18Servicing the APS-6R .......................................................................19

Appendix A AFP-200 .............................................................................................20Mounting an APS-6R to an AFP-200 Backbox ................................20Connecting the APS-6R to an AFP-200 Power Supply ....................21

Appendix B AFP-300/AFP-400 ............................................................................22Mounting an APS-6R in a CAB-400AA Backbox ...........................22Connecting the APS-6R to an MPS-400 ...........................................23

Appendix C AFC-600 ............................................................................................24Mounting an APS-6R in a CAB-600AA Backbox ...........................24Connecting the APS-6R to an MPS-6 ...............................................24

Appendix D System 500 .........................................................................................25Mounting an APS-6R in a CAB-500 Backbox .................................25Connecting the APS-6R to an MPS-24BRB .....................................25

Appendix E System 5000, AM2020/AFP-1010 ....................................................26Mounting an APS-6R in a System 5000, AM2020 or AFP-1010 ....26Connecting the APS-6R to an MPS-24A ..........................................26Connecting the APS-6R to an MPS-24BRB .....................................26

Appendix F NFS-640 .............................................................................................27Mounting an APS-6R in a Chassis ...................................................27Connecting the APS-6R to an NFS-640 ...........................................27

Appendix G NFS-3030 ..........................................................................................28Mounting an APS-6R in a Chassis ...................................................28Connecting to the AMPS-24 and CPU-3030 ....................................28

PN 50702:B2 4/14/03 5.PDF-Zoo.com

Page 6: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

w

6 PN 50702:B2 4/14/03

ww.PDF-Zoo.com

Page 7: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 1 Overview

www

Section 1 OverviewIntroduction

This document contains information for installing, servicing, and configuring the APS-6R Auxiliary Power Supply. The table below contains a list of document sources for supplemental information:

Table 1 Supplemental Documentation

DescriptionThe APS-6R Auxiliary Power Supply is a 150W cabinet-mounted power supply, designed to power devices that require filtered, regulated, non-resettable power, such as XP Transponder modules, Notification Appliance Circuit Modules and Control Modules. The APS-6R provides three 24 VDC (filtered) output circuits.

Figure 1 APS-6R Auxilliary Power Supply

Control Panels Refer to... Part NumberNFS-3030 NFS-3030 Installation Manual 51330NFS-640 NFS-640 Installation Manual 51332System 500 System 500 Manual 15019System 5000 System 5000 Manual 15583AFP-200 AFP-200 Instruction Manual 15511AFP-300/AFP-400 AFP-300/AFP-400 Installation Manual 50253AFC-600 AFC-600 Installation Manual 51031AM2020/AFP-1010 AM2020/AFP-1010 Manual 15088XPIQ Transponder XPIQ Manual 51013XP Series Transponder XP Series Manual 15888XP5 Series Transponder XP5 Series Manual 50786All Notifier Device Compatibility Document 15378

APS-

6Ris

ovie

w.c

dr

APS-6R with Cover

APS-

6Rno

cove

r.cdr

Control board

Main Board

PN 50702:B2 4/14/03 7.PDF-Zoo.com

Page 8: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 1 Overview

w

The figures below identify the features of the APS-6R power supply:

Figure 2 APS-6R Control Board

Figure 3 APS-6R Main Board

J2J9

J3

J1

TB2

TB3

TB1

JP3

JP2

Fuse F1 for AC protection(4A, 3AG, slow blow)

Three 24 VDC output circuitsOne (1) non power-limited

Two (2) power-limited(Refer to Figure 5 on page page 14 for more specific

information on output circuits)

Trouble In (J4) - Trouble Out (J3)“P” style connectors for internal cabinet connections

LED Status Indicators:Green LED – Indicates AC power onYellow LED – Indicates loss of AC or battery

Fuse F2 for battery protection(10A, 3AG, slow blow)

Jumpers JP2 and JP3 for selecting 8-hour or 16-hour delay for AC loss reporting. Default is immediate. See Page 18 in "Configuring the APS-6R".

APS-

6Rsi

debr

d.cd

r

JP1

Jumper JP1 for selecting AC input voltage(120 VAC default). See Page 18 in "Configuring the APS-6R". WARNING: HIGH VOLTAGE. For 240 VAC operation, cut JP1 before connecting power.

APS-

6Rbo

ard.

cdr

8 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 9: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 1 Overview

www

SpecificationsThe APS-6R is compatible with the NFS-3030, NFS-640, AM2020, AFP-1010, AFC-600, AFP-400, AFP-300, AFP-200, System 5000, and System 500 control panels. Specifications for the APS-6R are:

Table 2 APS-6R Specifications

Electrical Specifications

AC Primary Input PowerWire Size: #14 AWG with 600 VAC insulation

120 VAC, 60 Hz, 2.5 A240 VAC, 50 Hz, 1.2 A

24 VDC Secondary Input Power(lead-acid batteries only)

25 mA DC standby current16 mA DC standby current (with AC fail delay operating)

Note: The APS-6R is not equipped with a battery charger. Batteries are charged by the system power supply.

24 VDC output powerCircuit 1Circuit 2Circuit 3

Total 6 A (4 A continuous)3 A @24 VDC power-limited (+10, –15%)3 A @24 VDC power-limited (+10, –15%)6 A @24 VDC non power-limited (+10, –15%)

FusesF1 (AC supervision)F2 (battery supervision)

250 VAC, 4A, 3 AG, slow blow32 VAC, 10 A, 3 AG, slow blow

Trouble supervision busJ3 outputJ4 inputNote: J3 and J4 can be interchanged.

Form A contact (open collector)Form A contact (open collector)

Loss of AC Indication Immediate indication (default)8 or 16 hour delay

Mechanical Specifications

Size of APS-6R Inches:6.09 x 4.23. x 2.92 (mm:154.7 x 107.4 x 74.2)

Cabinets for mounting CAB-3/CAB-4 Series for NFS-3030, NFS-640, AM2020, AFP-1010, AFC-600, AFP-300, AFP-400, and System 5000 control panels.CAB-400AA for AFP-300 and AFP-400 control panels; accepts one APS-6R.CAB-600AA for AFC-600 control panels; accepts one APS-6R.AFP-200 backbox; accepts one APS-6R.CAB-500 Can mount one APS-6R.

Note: An optional module (such as an ICM) without an expansion card can mount above an APS-6R in a CHS-4 Series chassis, a CAB-500, CAB-600AA and a CAB-400AA.

PN 50702:B2 4/14/03 9.PDF-Zoo.com

Page 10: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 1 Overview

w

Parts Kit

A parts kit is included for use in assembling and mounting the APS-6R. It consists of the following items:

Quantity Description Part No.

1 AC Power connector cover 02183

2 #6-32 1.25 in. (10 mm) long, .25 in. (2mm) hex standoff

42026

2 #6-32 self-tapping screw 38118

1 Trouble supervision cable 71033

10 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 11: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

www

Section 2 InstallationWARNING: Use extreme caution when working with the APS-6R. High voltage and AC line-connected circuits are present. Turn off and remove all power sources. To reduce the risk of electric shock make sure to properly ground the unit.

IntroductionThis section contains instructions for mounting, wiring, configuring and servicing the APS-6R.

Installation topics covered in detail:

Additional information regarding installation may be found in the appendices.

!

Topic Refer to...

Mounting to a CAB-3/CAB-4 Series Cabinet

Page 12 in "Mounting in CAB-3/CAB-4 Series Cabinets"

Field Wiring Page 13 in "Field Wiring an APS-6R"

Wiring Multiple APS-6Rs Page 15 in "Connecting Multiple APS-6R Power Supplies"

Connecting to an ICM/ICE Page 16 in "Connecting the APS-6R to an ICM/ICE Module"

Powering a Control Module Page 17 in "Supplying Power to a Control Module"

Configuring Page 18 in "Configuring the APS-6R"

Servicing Page 19 in "Servicing the APS-6R"

PN 50702:B2 4/14/03 11.PDF-Zoo.com

Page 12: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

w

Mounting in CAB-3/CAB-4 Series CabinetsThis section contains instructions for the installation of the Auxiliary Power Supply into a CAB-3/CAB-4 Series cabinet.

These cabinets use a CHS-4 Series chassis to mount the APS-6R.

Instructions for mounting:

Chassis MountingThe illustration below shows an APS-6R being mounted in a CHS-4L chassis. Mounting in any CHS-4 Series chassis is accomplished in the same way.

Figure 4 Mounting an APS-6R to a CHS-4L Chassis

Step Action

1 Remove plastic cover from APS-6R.

2 If 240 VAC is to be used, cut JP1 jumper at this time. See instructions and high voltage warning on Page 18 in "Configuring the APS-6R".

3 Place the APS-6R onto the mounting studs of the chassis (Figure 4 on page 12).

4 Insert a standoff through each of the printed circuit board mounting holes, threading each standoff to the mounting studs on the chassis. Use #6-32 hex standoffs, 1.25 in. (32 mm) long.

5 Tighten the standoffs until the APS-6R is securely fastened to the chassis.

6 Reinstall the plastic chassis cover.

Mounting Studs

CHS-4L Chassis

Standoff(2 places)

APS-6R Assembly

APS-

6R to

CH

S-4L

.cdr

12 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 13: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

www

Wiring the APS-6RThis section contains instructions for wiring the APS-6R as follows:

• Typical field wiring from an APS-6R to a control panel and optional devices.

• Wiring multiple APS-6R power supplies.

Field Wiring an APS-6RJ1 and J2 can be used in place of TB2 when the APS-6R is powering internal modules (such as an ICM/ICE or XP6-C) with compatible connectors.

Output Circuit 3 (J9) can be used as a source of power for the XPIQ Audio Transponder only.

Note: When using the J9 connector do not use the J2 connector. This will satisfy the 0.25 (6.35mm) requirement for separation between power-limited and nonpower-limited circuits.

Primary and Secondary Power Connections - See appendix for your specific system information.

CAUTION: When finished wiring AC connections, install the press-fit terminal block cover over TB1 AC connections.

CAUTION: To maintain proper supervision, APS-6Rs used to power Panel Circuits, such as the ICM/ICE, must be connected to the same batteries as the main power supply. Failure to do so may result in improper operation.

!

PN 50702:B2 4/14/03 13.PDF-Zoo.com

Page 14: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

w

.

Figure 5 Typical Wiring for an APS-6R

J2J9

J3

J1

TB2

TB3

TB1

JP3JP2

TB2: Output Circuit 1

TB1 - Primary Power: 120 VAC or 240 VAC.

TB3 - Secondary Power: 24 VDC batteries.

Trouble Bus In/Out

TB2:Output Circuit 2

Earth Ground - Connects to chassis or EARTH ground terminal on main power supply. If 2 or more units are connected, secondary units connect to earth ground on the previous APS-6R in the chain.AP

S-6R

side

brd.

cdr

BATT (+)

BATT (–)

HOT

NEUTRAL

EARTH

J9:Output Circuit 3 - Non Power-limited, 6 A @24 VDC (+10, –15%)

+

+

- +J1:Output Circuit 1J2:Output Circuit 2

- + - +

(Refer to the caution above this illustration about secondary power and supervision)

Output Circuit 2 (J2 and TB2):Power-limited3 A @24 VDC(+10, –15%)

Output Circuit 1 (J1 and TB2):Power-limited3 A @24 VDC(+10, –15%)

See Page 18 in "Configuring the APS-6R".

14 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 15: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

www

Connecting Multiple APS-6R Power SuppliesTypical trouble bus connections for multiple APS-6R power supplies using trouble connectors J3 and J4.

Use Cable 71033 for all wiring.

See appendix on your system for specific “Trouble Input” connection.

Note: J3 and J4 can be interchanged.

Figure 6 Trouble Bus Connections for Multiple APS-6R Configurations

J2J9

J3

J1

TB2

JP3JP2

J2J9

J3

J1

TB2

JP3JP2

J2J9

J3

J1

TB2

JP3JP2

To trouble input on main power supply or control panel

First APS-6R Last APS-6RAP

S-6R

mul

tiple

3.cd

r

Connect power as shown in Figure 5

PN 50702:B2 4/14/03 15.PDF-Zoo.com

Page 16: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

w

Wiring ApplicationsThis section contains instructions for wiring the APS-6R assembly as follows:

• Connecting the APS-6R to an ICM/ICE module

• Supplying notification appliance power to a control module

Connecting the APS-6R to an ICM/ICE ModuleAll four (4) NACs on the ICM are powered from the APS-6R output circuit 2 (J2) and the four (4) NACs on the ICE are powered from circuit 1 (J1). The NACs share the total 3A available from each circuit.

Typical connections for wiring:

Figure 7 Typical APS-6R Wiring to an ICM/ICE Module

J 65 J

J 65 J

J2J9

J3

J1

TB2

JP3JP2

ICM

ICE

Auxiliary Power HarnessPN 71091

BlackBlueBlue

Black

APS-6R

APS-

6Ric

m.c

dr

16 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 17: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

www

Supplying Power to a Control ModuleThe circuit is power-limited.

Typical connections for wiring:

Figure 8 Typical APS-6R Wiring to a Control ModuleRefer to relevant control module installation documents for specific wiring instructions.

J2J9

J3

J1

TB2

JP3JP2

8 910111213

1415012345 6 7

8 9

012345 6 7

TENS

ONESLOOPLOOP ADDRESSADDRESS

8

9

765

9

8765

0

12344321

0

TENS

ONES

8 9

012345 6 7

8 9101112

131415012

345 6 7

SLC loop

To next device on SLC loop

APS-

6Rfc

m.c

dr

NAC

PN 50702:B2 4/14/03 17.PDF-Zoo.com

Page 18: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

w

Configuring the APS-6RThe APS-6R may be configured for the following:

• 8-hour delay for reporting loss of AC: cut jumper JP2.

• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.

• 240 VAC operation: See WARNING below. Cut jumper JP1 before applying power.

The figure below illustrates the location of the jumpers:

Figure 9 Configuring the APS-6R

JP1

J2J9

J3

J1

TB2

JP3

JP2

JP3 JP2

JP1AP

S-6R

conf

ig.c

drWARNING: HIGH VOLTAGE! Cut JP1 before applying power for 240 VAC operation.

18 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 19: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Section 2 Installation

www

Servicing the APS-6RThe only serviceable components on the APS-6R are fuses F1 and F2. If a fuse fails, replace it with a fuse of the same type and rating:

• F1 AC protection - 4A, 3 AG

• F2 Battery protection - 10A, 3 AG

To replace either fuse remove the vertical APS-6R control board as follows:

1. Turn off and remove all power sources.

2. Remove plastic cover.

3. Remove the two retaining screws securing control board.

4. Unplug the control PC board from the connectors.

5. Replace fuses as required.

6. Reinstall board in reverse order, install plastic cover and connect all power.

The figure below illustrates the location of the fuses.

Figure 10 Servicing the APS-6R

J2J9

J3

J1

TB2

JP3

JP2

F2 FuseRetaining Screw (typ)

F1 Fuse

Connector (typ)

APS-

6Rse

rvic

e.cd

r

Main Circuit Board

PN 50702:B2 4/14/03 19.PDF-Zoo.com

Page 20: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX A - AFP-200

w

APPENDIX A - AFP-200Mounting an APS-6R to an AFP-200 Backbox

The Auxiliary Power Supply is mounted in the bottom of the backbox.

Note: If an APS-6R is installed in the backbox, the batteries must be installed in a separate battery box, such as the BB-17. The battery box must be located within 20 feet (6 meters) of the enclosure containing the control panel and all connections must be contained in conduit.

To mount the APS-6R, follow these instructions:

Figure 11 Mounting the APS-6R to an AFP-200 Backbox

Step Action

1 Remove plastic cover from APS-6R.

2 If 240 VAC is to be used, cut JP1 jumper at this time. See instructions and high voltage warning on Page 18 in "Configuring the APS-6R".

3 Locate the mounting holes in the AFP-200 backbox. Insert a self-tapping screw through each of the APS-6R mounting slots.

4 Position the APS-6R in line with the holes in the AFP-200 backbox; then, thread the self-tapping screws until the APS-6R is securely fastened to the AFP-200 backbox.

6 Reinstall the plastic chassis cover.

APS-6R Assembly

AFP-200 Backbox

APS-

6R to

AFP

-200

.cdr

Self-tapping screws(2 places)

20 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 21: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX A - AFP-200

www

Connecting the APS-6R to an AFP-200 Power SupplyMake the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to terminal block TB7 (NEUT and HOT) on the AFP-200.

• Connect secondary power from TB3 on the APS-6R to terminal block J3 (+ and –) on the AFP-200.

• Connect trouble input from J3 on the APS-6R to terminal block J11 on the AFP-200.

Figure 12 Wiring to AFP-200 Power Supply

J2J9

J3

J1

TB2

JP3JP2

APS-

6R to

AFP

-200

ps.c

dr

To battery backup+-

PN 50702:B2 4/14/03 21.PDF-Zoo.com

Page 22: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX B - AFP-300/AFP-400

w

APPENDIX B - AFP-300/AFP-400Mounting an APS-6R in a CAB-400AA Backbox

An Auxiliary Power Supply is mounted as shown in the figure below.

To mount the APS-6R, follow these instructions:

Figure 13 Mounting an APS-6R to a CAB-400AA Backbox

Step Action

1 Remove plastic cover from APS-6R.

2 If 240 VAC is to be used, cut JP1 jumper at this time. See instructions and high voltage warning in Page 18 in "Configuring the APS-6R".

3 Place the APS-6R onto the mounting studs in the backbox.

4 Insert a standoff through each of the printed circuit board mounting holes, threading each standoff to the mounting studs.

5 Tighten the standoffs until the APS-6R is securely fastened to the backbox.

6 Reinstall the plastic chassis cover.

Standoff(2 places)

APS-6R Assembly

CAB-400AA Backbox

Mounting Studs

APS-

6R to

CAB

-AA.

cdr

22 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 23: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX B - AFP-300/AFP-400

www

Connecting the APS-6R to an MPS-400Make the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to MPS-400 terminal block TB1 (NEU and HOT).

• Connect secondary power from TB3 on the APS-6R to MPS-400 terminal block TB1 (+ and –).

• Connect trouble input from J3 on the APS-6R to MPS-400 terminal block J4.

Figure 14 Wiring to MPS-400

J2J9

J3

J1

TB2

JP3JP2

J4

APS-

6R to

MPS

-400

.cdr

To battery backup+-

PN 50702:B2 4/14/03 23.PDF-Zoo.com

Page 24: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX C - AFC-600

w

APPENDIX C - AFC-600Mounting an APS-6R in a CAB-600AA Backbox

An Auxiliary Power Supply is mounted in the same way as the AFP-400, see Appendix B.

Connecting the APS-6R to an MPS-6Make the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to MPS-6 terminal block TB1 (NEUTRAL and HOT).

• Connect secondary power from TB3 on the APS-6R to MPS-6 terminal block TB11 (+ and –).

• Connect trouble input from J3 on the APS-6R to MPS-6 terminal block J4.

Figure 15 Wiring to MPS-6

J2J9

J3

J1

TB2

JP3JP2

TB2 TB7 TB9

B+ B- A+ A-B+ B- A+ A-

B+ B- A+ A- B+ B- A+ A-

NO NC C NO NC C

NO NC C NO NC C

ALARMTB3

TROUBLETB5

ACCESSORIES

J1

J6

J2

+ - + - + -

AFP-600 C

ON

NE

CTO

RB

ATT– BATT+

AC ONLED

J7TB11

J8

EARTH FAULTLED

24V POWER LIMITED

RESETNONRESET

NAC1LED

NAC2LED

MH4

MH6MH3

MH1 JP4JP2

NAC3LED

NAC4LED

CB1

JP5 JP6

J4 J5 J3

JP3

IF BOX IS CHECKED THIS POWER SUPPLY HAS BEENCONFIGURED FOR 240 VAC OPERATION

REFER TO SYSTEM DOCUMENTATION FOR ADDITIONAL INFORMATIONWARNING - SEVERAL DIFFERENT SOURCES OF POWER CAN BE

CONNECTED TO THIS CONTROL UNIT.DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING.

CAUTIONHAZARDOUSVOLTAGES

APS-

6R to

MPS

-6.c

dr

To battery backup+-

24 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 25: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX D - System 500

www

APPENDIX D - System 500Mounting an APS-6R in a CAB-500 Backbox

An Auxiliary Power Supply is mounted in the same way as the AFP-400, see Appendix B.

Connecting the APS-6R to an MPS-24BRBMake the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to MPS-24BRB terminal block TB1, Pin 3(NEUT) and Pin 4(HOT).

• Connect secondary power from TB3 on the APS-6R to MPS-24BRB terminal block TB3, Pin 1(+) and Pin 2(–).

• Connect trouble input from J3 on the APS-6R to MPS-24BRB terminal block P4.

Figure 16 Wiring to MPS-24BRB

J2J9

J3

J1

TB2

JP3JP2

JP3

P3

P4

TB3

P1

TB2

TB1

CB1 P2

R55 1 2 3 4 6 7 8

7

5

3 21

EARTH AC NEUTCOMMON COMMON BATT -+24 VRESET

AC HOT

MPS-24BPCCREV ___

+24 VPOWER BATT +

TROUBLES

AC BATT +EF -EF

2 3 4 1 2 3 4 1 2

APS-

6R to

MPS

-24B

.cdr

To battery backup+-

PN 50702:B2 4/14/03 25.PDF-Zoo.com

Page 26: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX E - System 5000, AM2020/AFP-1010

w

APPENDIX E - System 5000, AM2020/AFP-1010

Mounting an APS-6R in a System 5000, AM2020 or AFP-1010

An Auxiliary Power Supply is mounted on a CHS-4 Series chassis. See “Mounting in CAB-3/CAB-4 Series Cabinets” on page 12.

Connecting the APS-6R to an MPS-24AMake the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to MPS-24A terminal block TB1, Pin 5(NEUT) and Pin 7(HOT).

• Connect secondary power from TB3 on the APS-6R to MPS-24A terminal block TB2, Pin 1(+) and Pin 2(–).

• Connect trouble input from J3 on the APS-6R to MPS-24A terminal block P5.

Figure 17 Wiring to MPS-24A

Connecting the APS-6R to an MPS-24BRBThe connections are the same as for the System 500. Refer to Page 25 in "System 500" for wiring instructions.

P4P3

JP5

TB1

TB2

F1CB1P5

R27

P2E ARTH G ND AC NEUTRA L A C HOT

+24R CO MMON +24 COMMONP OWER LIMI TED

B AT + BAT -

J2J9

J3

J1

TB2

JP3JP2

APS-

6R to

MPS

-24A

.cdr

To battery backup+-

26 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 27: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX F - NFS-640

www

APPENDIX F - NFS-640Mounting an APS-6R in a Chassis

An Auxiliary Power Supply is mounted on a CHS-4 Series chassis. See “Mounting in CAB-3/CAB-4 Series Cabinets” on page 12..

Connecting the APS-6R to an NFS-640Make the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to TB2 HOT NEUTRAL and EARTH on the NFS-640.

• Connect secondary power from TB3 on the APS-6R to TB1 on the NFS-640, BATT- and BATT+.

• Connect trouble input from J3 on the APS-6R to J11 on the NFS-640.

Figure 18 Wiring to the NFS-640

J2J9

J3

J1

TB2

TB3

TB1

JP3JP2

To battery backup+- AP

S-6R

to N

FS-6

40.c

dr

PN 50702:B2 4/14/03 27.PDF-Zoo.com

Page 28: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

APPENDIX G - NFS-3030

w

APPENDIX G - NFS-3030Mounting an APS-6R in a Chassis

An Auxiliary Power Supply is mounted on a CHS-4 Series chassis. See “Mounting in CAB-3/CAB-4 Series Cabinets” on page 12..

Connecting to the AMPS-24 and CPU-3030Make the following connections as shown in the figure below.

• Connect primary power from TB1 on the APS-6R to TB3 HOT, NEUT and EARTH on the AMPS-24.

• Connect secondary power from TB3 BATT(+) and BATT(-)on the APS-6R to TB5 (BAT IN +) and TB4 (BAT OUT-) respectively on the AMPS-24.

• Connect trouble input from J3 on the APS-6R to the J5 Trouble bus connection on the CPU-3030.

Figure 19 Wiring to AMPS-24 and CPU-3030

J2J9

J3

J1

TB2

TB3

TB1

JP3JP2

To battery backup +

-

AMPS-24

CPU-3030

APS-

6R to

NFS

-303

0.cd

r

28 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 29: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Index

www

Numerics240 VAC

cabinet mounting 12, 20, 22to configure for operation 18

AAC Loss Delay reporting

16-hour, configuration for 188-hour, configuration for 18

AC protection fuse 19AFC-600 7, 9, 24AFP-1010 7, 9, 26AFP-200 7, 9, 20AFP-300 7, 9, 22AFP-400 7, 9, 22AM2020 7, 9, 26AMPS-24 28BBackbox 20, 22, 24, 25Battery box, separate 20Battery protection fuse 19BB-17 20CCAB-3/CAB-4 Series cabinet 9, 12CAB-400AA 9, 22CAB-500 9, 25CAB-600AA 9, 24Cable for trouble bus 15CAUTION

To maintain supervision... 13Wiring AC connections... 13

CHS-4 Series 9, 26, 27, 28CHS-4L 12Configuring the APS-6R 18Connections

to AFP-200 21to AMPS-24 28to CPU-3030 28to MPS-24A 26to MPS-24BRB 25, 26to MPS-400 23to MPS-6 24to NFS-640 27

Control module, typical connections 17CPU-3030 28

DDocument sources, list of 7EEarth Ground 14Electrical Specifications 9FFeatures of the APS-6R 8Field wiring 13Fuses 8, 19HHigh Voltage Warning 11, 18IICM/ICE 13, 16Installation topics 11JJP1 jumper 8, 18JP2 jumper 8, 18JP3 jumper 8, 18Jumpers, locations of 18LLED Status Indicators 8MMechanical Specifications 9MPS-24A 26MPS-24BRB 25, 26MPS-400 23MPS-6 24Multiple power supplies, trouble busconnections 15NNFS-3030 7, 9, 28NFS-640 7, 9, 27Non Power-limited circuit 8, 14OOutput circuit 8, 14

for use with XPIQ 13Non Power-limited 14Power-limited 14

PParts kit 10Power-limited circuit 8, 14Primary power 14, 21, 23, 24, 26, 27,28

PN 50702:B2 4/14/03 29.PDF-Zoo.com

Page 30: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

Index

w

SSecondary power 14, 21, 23, 24, 26,27, 28Self-tapping screw 20Serviceable components 19Specifications 9Standoff 12, 22Status Indicators 8System 500 7, 9, 25System 5000 7, 9, 26TTerminal block cover 13Trouble Bus connectors 14, 15Trouble input 21, 23, 24, 26, 27, 28WWarning, High Voltage 11, 12, 18, 20,22Wiring 13XXP Series Transponder 7XP5 Series Transponder 7XP6-C 13XPIQ 7, 13

30 PN 50702:B2 4/14/03 ww.PDF-Zoo.com

Page 31: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

www

Limited Warranty

NOTIFIER® warrants its products to be free from defects in materialsand workmanship for eighteen (18) months from the date ofmanufacture, under normal use and service. Products are datestamped at time of manufacture. The sole and exclusive obligation ofNOTIFIER® is to repair or replace, at its option, free of charge forparts and labor, any part which is defective in materials orworkmanship under normal use and service. For products not underNOTIFIER® manufacturing date-stamp control, the warranty iseighteen (18) months from date of original purchase by NOTIFIER®’sdistributor unless the installation instructions or catalog sets forth ashorter period, in which case the shorter period shall apply. Thiswarranty is void if the product is altered, repaired or serviced byanyone other than NOTIFIER® or its authorized distributors or if thereis a failure to maintain the products and systems in which theyoperate in a proper and workable manner. In case of defect, secure aReturn Material Authorization form from our customer servicedepartment. Return product, transportation prepaid, to NOTIFIER®,12 Clintonville Road, Northford, Connecticut 06472-1653.

This writing constitutes the only warranty made by NOTIFIER® withrespect to its products. NOTIFIER® does not represent that itsproducts will prevent any loss by fire or otherwise, or that its productswill in all cases provide the protection for which they are installed orintended. Buyer acknowledges that NOTIFIER® is not an insurer andassumes no risk for loss or damages or the cost of anyinconvenience, transportation, damage, misuse, abuse, accident orsimilar incident.

NOTIFIER® GIVES NO WARRANTY, EXPRESSED OR IMPLIED,OF MERCHANTABILITY, FITNESS FOR ANY PARTICULARPURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THEDESCRIPTION ON THE FACE HEREOF. UNDER NOCIRCUMSTANCES SHALL NOTIFIER® BE LIABLE FOR ANY LOSSOF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL ORCONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITYTO USE NOTIFIER® PRODUCTS. FURTHERMORE, NOTIFIER®SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATHWHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITSPRODUCTS.

This warranty replaces all previous warranties and is the onlywarranty made by NOTIFIER®. No increase or alteration, written orverbal, of the obligation of this warranty is authorized.

“NOTIFIER” is a registered trademark.

Warn-NS-10-2001.fm

.PDF-Zoo.com

Page 32: Instruction Manual - Home - Fire Alarm Resources · Instruction Manual Document 50702 ... which have little visible smoke. Detectors that have ionizing-type sensing chambers ... NOTIFIER

w

World Headquarters12 Clintonville Road

Northford, CT 06472-1653 USA203-484-7161

fax 203-484-7118

www.notifier.com

NOTIFIER is a company.

ww.PDF-Zoo.com