INSTRUCTION MANUAL IM 303 E
Device: Flow Rate Correction Calculator GDR 1403
for the collection of volumetric flow rate
of technical and medical gases
Content: Installation and operation manual
Rev.-Nr.: IM 303 E V 1.2-2014-07-17
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 2 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
User information
- Prior to installing the equipment or before attempting initial start-up, please read this manual
thoroughly.
- Please ensure to observe all information and warnings provided in this manual.
- The serial number of the equipment can be found on the identification plate. You will need this
information when ordering spare parts. The plate is attached to the outside of the device.
- Installation, start-up and maintenance may only be performed by an electrician. The local guidelines
of the place of installation have to be observed.
- Maintenance may only be performed under dead-voltage conditions for personal security reasons.
- In order of guarantee operational safety, only the manufacturer's original spare parts shall be
installed.
- Operating the equipment for purposes other than its intended use shall void all warranty claims and
product liability. Noncompliance with the intended use refers to but is not limited to improper
installation, start-up, operation, maintenance and neglecting the information provided in this
manual.
- The device must be integrated into the lightening protection concept of the plant.
Please ensure to operate this device only in accordance with this manual.
Departure from these instructions will void and nullify all warranty claims and
jeopardizes the operating safety of the device.
We reserve the right to engineering changes, which may necessitate deviations from the current data
provided in this manual. Should you require additional information or questions arise that are not
sufficiently covered in this manual, please contact us at the following address:
Imprint
Esters Elektronik GmbH
Görresstrasse 17
D-63739 Aschaffenburg
Tel.: +49 (0)6021 – 45 807 - 0
Fax: +49 (0)6021 – 45 807 - 20
eMail: [email protected]
Internet: www.esters.de
Copyright
Dieses Handbuch ist urheberrechtlich geschützt.
Vervielfältigung und Verbreitung sind ohne schriftliche Genehmigung nicht gestattet.
© Esters Elektronik GmbH, Aschaffenburg
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 3 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Table of content
1 Introduction ___________________________________________________________________ 4
1.1 Operating instructions, general information _____________________________________ 4
1.2 Goods receipt inspection, transportation, storage ________________________________ 4
2 Warranty ______________________________________________________________________ 5
3 General information _____________________________________________________________ 6
4 Benefits at a glance ______________________________________________________________ 7
5 Installation / servicing / maintenance _______________________________________________ 8
6 Technical specifications __________________________________________________________ 9
6.1 Input, output and relay ______________________________________________________ 9
6.2 Electrical values, mechanical values and environmental influences __________________ 10
6.3 Display and housing _______________________________________________________ 11
6.4 Interfaces _______________________________________________________________ 12
6.5 Software and recorder _____________________________________________________ 12
7 Device types __________________________________________________________________ 13
7.1 Devices with pulse input for flow rate measurement
(e.g. for GD 300 and GD 500 incl. signal amplifier)) _______________________________ 13
7.2 Devices with mA input for flow rate measurement
(e.g. Ecoflow rate2, third-party products) ______________________________________ 15
7.3 Devices with pulse input and mA-input for flow rate measurement
– diverse measurements ___________________________________________________ 16
7.4 Devices with RS 485 interface for flow rate measurement
(e.g. Ecoflow 3, third party products) __________________________________________ 18
7.5 Devices with RS 485 interface for flow rate measurement _________________________ 19
7.6 Devices with pulse input RS 485 interface for flow rate measurement
- diverse measurements ____________________________________________________ 21
7.7 Devices with RS 485 interface for flow rate measurement
- divers measurements _____________________________________________________ 22
7.8 Optional device functions and housing ________________________________________ 23
8 Operating panel of flow rate correction calculator ____________________________________ 24
8.1 Layout of LCD display ______________________________________________________ 24
8.2 Measured value display ____________________________________________________ 25
9 Operating overview ____________________________________________________________ 27
9.1 Operating overview in measurement mode ____________________________________ 27
9.2 Operating overview in configuration mode _____________________________________ 28
9.3 Operating overview in programming mode _____________________________________ 28
10 Configuration function codes _____________________________________________________ 29
10.1 Configuration function code types ____________________________________________ 30
10.2 Description of individual configuration function codes ____________________________ 34
11 Connecting diagram ____________________________________________________________ 41
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 4 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
1 Introduction
1.1 Operating instructions, general information
These operating instructions are intended for the use of the device and meant to provide support during
the installation, operation, and maintenance.
The structure of the document shall make this easy. Important text is highlighted.
Symbols
The following symbols are used in these operating instructions in order to highlight text that requires
special attention.
Notes
This arrow points to features that require your special attention.
Caution
This symbol points to important text.
Noncompliance or disregard may cause damage to components or destruction to
parts of the system.
Warning!
This symbol points to important text. Noncompliance will place the life and health
of persons at risk.
Reference
This symbol refers to additional information available in other manuals, chapters,
or sections.
1.2 Goods receipt inspection, transportation, storage
- Ensure the packaging is not damaged!
- Any damaged packaging must be reported to the supplier.
- Retain any damaged packaging until the matter has been resolved.
- Ensure the package's content is not damaged!
- Any damaged part received must be reported to the supplier.
- Retain any damaged goods until the matter has been resolved.
- Use the delivery documents to check the received goods and compare the goods with your order to
ensure completeness. For storage and transport purposes, the equipment must be packed with care
to prevent damage caused by impact or humidity. Only the original packaging can ensure optimal
protection. Furthermore, compliance with all allowable ambient conditions is mandatory (section 5).
- If you have any questions, please contact your supplier or the respective distribution centre.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 5 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
2 Warranty
The devices were built in compliance with current directives and have left the factory in technically
flawless condition.
In the unlikely event that you still may have reasons for a complaint and the fault can be traced to a
factory error, we shall correct any defects at no additional charge. However, in such case, it is your
responsibility to report the damage immediately after detection and/or within our permitted warranty
period.
Damage caused due to improper use or as a result of noncompliance with these operating instructions, is
excluded from this warranty.
The warranty period is 12 months. Unless otherwise agreed upon, the warranty period for spare parts is
12 months as well. The fulfilment of warranty claims shall not extend the warranty period.
The warranty shall become null and void if the measurement module has been opened, unless otherwise
expressly stated in the operating instructions or for maintenance purposes only. This shall also apply if
serial numbers have been changed, damaged, or removed.
Any repairs, adjustments or similar tasks necessary besides warranty performances shall be without
charge. Other services, including transport and packaging shall be invoiced.
Unless liability is mandatory by law, further claims, in particular claims based on damages that do not
concern the delivered components, are excluded.
Services provided after the warranty period
Of course, we will be pleased to assist you once the warranty has expired. You can reach us directly by
calling.
Contact:
Phone: +49 (6021) 45 807 - 0
Fax: +49 (6021) 45 807 - 20
eMail: [email protected]
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 6 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
3 General information
The flow correction calculator GDR 1403 records the volume flow as 4 – 20 mA signal, as 0 – 20 mA signal
or as frequency signal.
The mass flow is determined by means of a density correction with an additional pressure and
temperature measurement.
The three measurement values are used to calculate the current flow in standard cubic metres.
Programming of the GDR 1403 can be performed directly at the device (described below) or via a PC USB
interface by using the configuration software E3DM.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 7 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
4 Benefits at a glance
Application areas Benefits at a glance
- Combined heat and power plants
- Biogas plants
- Gas turbines
- Energy industry
- Chemical industry
- Heating and air-conditioning technology
- Pharmaceutical industry
- Foodstuffs industry
- Plant engineering and process equipment manufacturing
- Measuring and control technology
- Integrated recorder function for logging of measurement values (2 GB ring storage)
- Linearisation via a maximum of 12 support points
- Up to three limit values / relays / changeovers
- 2 digital inputs for start and stop function for control via PLC
- Integration in IT networks via Ethernet/IP for remote data transfer
- Integration in industry bus systems, e.g. Profibus DP, Modbus RTU, Modbus TCP, Profinet
- Up to 12 measuring computers can be networked via an internal CAN bus
- Persistent data retention of total counter reading in case of power loss for a period of up to 5 years
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 8 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
5 Installation / servicing / maintenance
This device has been designed for direct mounting on a DIN rail. The monitor can be mounted directly in
a switch cabinet or in a separately available housing. Installation may only be performed by specialist,
trained personnel.
Servicing and maintenance activities may only be performed by Esters Elektronik GmbH technicians or by
persons trained by Esters Elektronik GmbH.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 9 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
6 Technical specifications
The devices in the GDR 1403 series are available as 1 or 2-channel units. The device series has been
constructed according to the modular principle. The principle allows for configuration of inputs and
outputs as well as of interfaces and software options according to individual usage and operating system
requirements.
The section on technical specifications provides an overview in respect of the series.
6.1 Input, output and relay
MEASUREMENT INPUTS
INPUT 1 (CHANNEL "A")
TEMPERATURE/ PRESSURE
0 (4) - 20 mA, 2-/3-wire (temperature) = -100 - 2000 °C (14 bit),
input resistance < 100 Ohm using 20 mA or
0 (4) - 20 mA, 2-/3-wire (pressure) = 0 - 30 bar (14 bit),
input resistance < 100 Ohm at 20 mA
INPUT 2 (CHANNEL “A”)
FLOW RATE
0 (4) - 20 mA (flow rate) = 0 - 20.000 m³/h (14 bit),
input resistance < 100 Ohm using 20 mA or
pulse input for gas flow meter GD 300 / 500 (flow rate),
10 - 1 kHz at 5% duty cycle, pulse length > 500 ms
INPUT 1 AND 2 (CHANNEL „A“)
TEMPERATURE AND FLOW RATE
RS 485 interface for gas flow sensors, e.g. Ecoflow 3 (hot wire
anemometer)
INPUT 3 (CHANNEL “B”)
TEMPERATURE/ PRESSURE
0 (4) - 20 mA, 2-/3-wire (temperature) = -100 - 2000 °C (14 bit),
input resistance < 100 Ohm at 20 mA or
0 (4) - 20 mA, 2-/3-wire (pressure) = 0 - 30 bar (14 bit),
input resistance < 100 Ohm at 20 mA
INPUT 4 (CHANNEL “B”)
FLOW RATE
0 (4) - 20 mA, (flow rate) = 0 - 20.000 m³/h (14 bit),
input resistance < 100 Ohm using 20 mA or
pulse input for gas flow meter GD 300 / GD 500 (flow rate)
10 - 1 kHz at 5% duty cycle, pulse length > 500 ms
INPUT 3 AND 4 (CHANNEL “B”)
TEMPERATURE AND FLOW RATE
RS 485 interface for gas flow sensors, e.g. Ecoflow 3 (hot wire
anemometer)
INPUT 5 (CHANNEL “A”)
PRESSURE/ TEMPERATURE
0 (4) - 20 mA, 2-/3-wire (pressure) = 0 - 30 bar (14 bit),
input resistance < 100 Ohm or
virtual input using a programmable fixed value or
0 (4) - 20 mA, 2-/3-wire (temperature) = -100 - 2000 °C (14 bit),
input resistance < 100 Ohm at 20 mA
INPUT 6 (CHANNEL “B”)
PRESSURE/ TEMPERATURE
0 (4) - 20 mA, 2-/3-wire (pressure) = 0 - 30 bar (14 bit),
input resistance < 100 Ohm or
virtual input using a programmable fixed value or
0 (4) - 20 mA, 2-/3-wire (temperature) = -100 - 2000 °C (14 bit),
input resistance < 100 Ohm at 20 mA
DIGITAL INPUT S1 (CHANNEL Digital gate-input
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 10 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
“A”)
DIGITAL INPUT S2 (CHANNEL
“B”)
Digital gate-input
OUTPUTS
INPUT 1 (CHANNEL "A") 0(4) - 20 mA = 0 - (x) Nm³/h flow rate, freely programmable,
load 500 ohm
INPUT 2 (CHANNEL "B") 0(4) - 20 mA = 0 - (x) Nm³/h flow rate, freely programmable,
load 500 ohm
INPUT 3 (CHANNEL "A") 0(4) - 20 mA = 0 - (x) Nm³/h partial quantity, freely programmable,
load 500 ohm
INPUT 4 (CHANNEL "B") 0(4) - 20 mA = 0 - (x) Nm³/h partial quantity, freely programmable,
load 500 ohm
RELAYS
K1: COUNTER OUTPUT (CHANNEL
"A")
Quantity, relay, NO contact (max. 2 pulses)
1, 10 or 100 Nm³ per pulse, freely programmable
K2: COUNTER OUTPUT
(CHANNEL "B")
Quantity, relay, NO contact (max. 2 pulses)
1, 10 or 100 Nm³ per pulse, freely programmable
K3: LIMIT VALUE
(CHANNEL "A")
Limit value, NO switch, 250 V, AC, 1A inductive
K4: LIMIT VALUE
(CHANNEL "B")
Limit value, NO switch, 250 V, AC, 1A inductive
6.2 Electrical values, mechanical values and environmental influences
ELECTRIC VALUES
ACCURACY ± 0.05% unit value ± 1 digit at 23°C
MAINS SUPPLY (STANDARD) 24 V, DC ± 3V
CURRENT CONSUMPTION max. 1.25 A, Fuse protection by means of 3A preliminary fuse or
inherently safe mains adaptor
POWER CONSUMPTION max. 30 VA
EXTERNAL MAINS ADAPTOR 24 V/DC
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 11 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
ENVIRONMENTAL INFLUENCES
AMBIENT TEMPERATURE -10 to +55°C
STORAGE TEMPERATURE -20 to +85°C
TEST VOLTAGE 3 kV
HUMIDITY CLASS E-DIN 40040
ELECTROMAGNETIC
COMPATIBILITY
as per DIN EN 61000
CLIMATIC CLASS as per IEC 60 654-1 Class B2 / EN 1434 Class "C"
(no condensation permitted)
ELECTRICAL SAFETY as per IEC 61010-1: Environment < 2000 m height above NN
OVERVOLTAGE CATEGORY IEC 61010-1, Protection class II, Overvoltage category II
DEGREE OF CONTAMINATION Degree of contamination 2
MECHANICAL VALUES
TORQUE CLAMPS 0.15 Nm max.
6.3 Display and housing
DISPLAY, HOUSING, WEIGHT
DISPLAY 6-digit LCD display for flow rate in Nm³/h
7-digit LCD display in Nm³
LCD height 8 mm
STANDARD HOUSING
DIN RAIL MOUNTING
Modular clamp housing made from Makrolon
Fire classification as per UL 94:V-D
35 mm standard rail as per DIN EN 50022
Dimensions: 100 (W) x 100 (H) x 107 (D) mm
Protection class IP 20
FIELD HOUSING ( OPTION M104) Dimensions: 343 (W) x 330 (H) x 210 (D) mm
Wall mounting
Protection class IP 65
FIELD HOUSING WITH EX-ZONE
(OPTION M105)
Dimensions: 385.5 (W) x 487 (H) x 210 (D) mm
Wall mounting
Protection class IP 65
TOTAL WEIGHT: GDR 1403
INCL. FIELDHOUSING M104
INCL. FIELDHOUSING M105
480 g
3650 g
5650 g
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 12 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
6.4 Interfaces
INTERFACES
RS 232 9-pin connection to update the firmware
USB Mini USB-connection (5-pin, USB 2.0) for configuration and data transfer
through PC
CAN-BUS (OPTIONAL) Internal communication of up to 12 curable devices
PROFIBUS DP (OPTIONAL) Data transmision via Profibus-DP protocol
MODBUS-RTU (OPTIONAL) Data transmision via MODBUS-RTU protocol
MODBUS-TCP (OPTIONAL) Data transmision via MODBUS-TCP protocol
ETHERNET (OPTIONAL) Integration into the IT-network for configuration and data transfer
through PC
6.5 Software and recorder
SOFTWARE AND RECORDER
PRECISION (OPTIONAL) Integrator with high-resolution (0,1 l) within liter mode
E3DM Configuration software for Microsoft Windows
(32-Bit)
RECORDER (OPTIONAL) 2 GB ring buffer
Integrated recorder function for logging measurement values over a
period of several years
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 13 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7 Device types
7.1 Devices with pulse input for flow rate measurement
(e.g. for GD 300 and GD 500 incl. signal amplifier))
1-CHANNEL „A“
GDR 1403-XXXX-00YY 0041 0241 0141 0341 0049 0249 0149 0349 0245 005D 025D
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • • • • •
2: Pulses, flow rate („A“) • • • • • • • • • • •
3: 0(4)-20mA, 2/3-wire temperature („B“)
4: Pulses, flow rate („B“)
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • v v • • •
6: 0(4)-20mA, 2/3-wire pressure („B“)
DIGITAL INPUTS
7: S1 • • •
8: S2
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“)
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„B“)
SOFTWARE
Precision • • • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 14 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-00YY 00C3 02C3 01C3 03C3 00CB 02CB 01CB 03CB 00DF 02DF
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • • • •
2: Pulses, flow rate („A“) • • • • • • • • • •
3: 0(4)-20mA, 2/3-wire temperature („B“) • • • • • • • • • •
4: Pulses, flow rate („B“) • • • • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • v v • •
6: 0(4)-20mA, 2/3-wire pressure („B“) • • v v • • v v • •
DIGITAL INPUTS
7: S1 • •
8: S2 • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“) • • • • • •
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„B“) • •
SOFTWARE
Precision • • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 15 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.2 Devices with mA input for flow rate measurement (e.g. Ecoflow rate2, third-party products)
1-CHANNEL „A“ 2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-00YY 0001 0101 0009 0109 001D 0003 0103 0007 000B 010B 001F
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • • • • •
2: 0(4)-20mA, Flow rate („A“) • • • • • • • • • • •
3: 0(4)-20mA, 2/3-wire temperature („B“) • • • • •
4: 0(4)-20mA, Flow rate („B“) • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • v • v • • • • • v •
6: 0(4)-20mA, 2/3-wire pressure („B“) • • • v •
DIGITAL INPUTS
7: S1 • • •
8: S2 • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“) • • •
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity(„B“) •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 16 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.3 Devices with pulse input and mA-input for flow rate measurement – diverse measurements
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-00YY 0043 0243 0143 0343 004B 024B 0247 005F 025F
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • • •
2: Pulses, flow rate („A“) • • • • • • • • •
3: 0(4)-20mA, 2/3-wire temperature („B“) • • • • • • • • •
4: 0(4)-20mA, Flow rate („B“) • • • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • • • •
6: 0(4)-20mA, 2/3-wire pressure („B“) • • v v • • • • •
DIGITAL INPUTS
7: S1 • • •
8: S2 • • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („A“) • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („B“) • • • •
3: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity(„A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity(„B“) • •
SOFTWARE
Precision • • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 17 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-00YY 0083 0283 0183 0383 008B 028B 009F 029F
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • •
2: Pulses, flow rate („A“) • • • • • • • •
3: 0(4)-20mA, 2/3-wire temperature („B“) • • • • • • • •
4: 0(4)-20mA, Flow rate („B“) • • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • • •
6: 0(4)-20mA, 2/3-wire pressure („B“) • • v v • • • •
DIGITAL INPUTS
7: S1 • •
8: S2 • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („A“) • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („B“) • • • •
3: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity(„A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity(„B“) • •
SOFTWARE
Precision • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 18 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.4 Devices with RS 485 interface for flow rate measurement
(e.g. Ecoflow 3, third party products)
1-CHANNEL „A“
GDR 1403-XXXX-01YY 0001 0241 0101 0341 0009 0249 0109 0349 0245 001D 025D
INPUTS
1,2: RS 485 for flow rate and temperature
(„A“) • • • • • • • • • • •
3,4: RS 485 for flow rate and temperature
(„B“)
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • v v • • •
6: 0(4)-20mA, 2/3-wire pressure („B“)
DIGITAL INPUTS
7: S1 • • •
8: S2
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“)
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („B“)
SOFTWARE
Precision • • • • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 19 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.5 Devices with RS 485 interface for flow rate measurement
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-01YY 0003 0243 0103 0343 000B 024B 010B
INPUTS
1,2: RS 485 for flow rate and temperature („A“) • • • • • • •
3,4: RS 485 for flow rate and temperature („B“) • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • v
6: 0(4)-20mA, 2/3-wire pressure („B“) • • v v • • v
DIGITAL INPUTS
7: S1
8: S2
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („A“) • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („B“) • • •
3: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity („A“)
4: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity („B“)
SOFTWARE
Precision • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 20 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-01YY 03CB 011B 03DB 0007 0247 001F 025F
INPUTS
1,2: RS 485 for flow rate and temperature („A“) • • • • • • •
3,4: RS 485 for flow rate and temperature („B“) • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) v v v • • • •
6: 0(4)-20mA, 2/3-wire pressure („B“) v v v • • • •
DIGITAL INPUTS
7: S1 • • • •
8: S2 • • • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („A“) • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h flow rate („B“) • • • • •
3: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity („A“) • • • •
4: 0(4) - 20 mA = 0 - (x) Nm³ partial quantity („B“) • • • •
SOFTWARE
Precision • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 21 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.6 Devices with pulse input RS 485 interface for flow rate measurement
- diverse measurements
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-01YY 0043 0243 0143 0343 004B 024B 01CB 03CB 005F 025F 0247
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • • • • • • •
2: Pulse, flow rate („A“) • • • • • • • • • • •
3,4: RS 485 for flow rate u. temperature
(„B“) • • • • • • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • • v v • • v v • • •
6: 0(4)-20mA, 2/3-wire pressure („B“) • • v v • • v v • • •
DIGITAL INPUTS
7: S1 • • •
8: S2 • • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • • • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“) • • • • • •
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („A“) • •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („B“) • •
SOFTWARE
Precision • • • • • •
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 22 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.7 Devices with RS 485 interface for flow rate measurement
- divers measurements
2-CHANNEL „A“ AND „B“
GDR 1403-XXXX-10YY 0003 0103 0007 000B 010B 001F
INPUTS
1: 0(4)-20mA, 2/3-wire temperature („A“) • • • • • •
2: 0(4)-20mA, flow rate („A“) • • • • • •
3,4: RS 485 for flow rate u. temperature („B“) • • • • • •
5: 0(4)-20mA, 2/3-wire pressure („A“) • v • • v •
6: 0(4)-20mA, 2/3-wire pressure („B“) • v • • v •
DIGITAL INPUTS
7: S1 • •
8: S2 • •
OUTPUTS
1: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („A“) • • •
2: 0(4) - 20 mA = 0 - (x) Nm³/h
flow rate („B“) • • •
3: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („A“) •
4: 0(4) - 20 mA = 0 - (x) Nm³
partial quantity („B“) •
SOFTWARE
Precision
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 23 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
7.8 Optional device functions and housing
GDR 1403-XXXX-XX
0 no selection
1 Interface PROFIBUS_DP
2 Interface Modbus-RTU
4 Interface Modbus-TCP
0 no selection
1 Interface CAN-Bus
4 Interface Ethernet TCP/IP
5 Interface CAN-Bus, Interface Ethernet TCP/IP
8 Ring storage 2 GB (data recorder)
9 Ring buffer 2 GB (data recorder), Interface CAN-Bus
C Ring buffer 2 GB (data recorder), Interface Ethernet TCP/IP
D Ring buffer 2 GB (data recorder), Interface CAN-Bus, Interface Ethernet
TCP/IP
HOUSING
M104 Field housing for wall mounting, protection class IP 65
M105 Field housing with EX-Zone for wall mounting, protection class IP 65
M112 Switchboard door housing, protection class IP 30
M122 Portable housing, protection class IP 30
M113 Switchboard door housing, protection class IP 65
M123 Portable housing, protection class IP 65
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 24 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
8 Operating panel of flow rate correction calculator
8.1 Layout of LCD display
The following figure provides information on the layout of the LCD display of the device.
Display
value 2(line 2)
Display
value 1(line 1)
Display
menu-no.
Display
device status(line 4a)
Display
programming or error code(line 4b)
Display
decription value 1(line 3)
Button „ESC“
Button „UP“
Button „DOWN“
Button „SCROLL“
Button „OK“
Display
dimension
unit
Display
Channel
Device type
Device descripition
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 25 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
8.2 Measured value display
Four-line LCD display, whereby lines 1 to 3 show a maximum of 10 digits. Measured value display
SCREEN CONTENT OF LINE 1 (VALUE 1) CONTENT OF LINE 2 (VALUE 2)
1 Current flow rate "A" [Bm³/h] Integrator value volume "A" [Bm³]
2 Current flow rate "A" [Nm³/h] Integrator value volume "A" [Nm³]
3 Gas temperature "A" [oC] Temperature average 24h [oC]
4 Gas pressure "A" [mbar] Gas pressure average 24h [mbar]
5 Current flow rate "B" [Bm³/h] Integrator value volume "B" [Bm³]
6 Current flow rate "B" [Nm³/h] Integrator value volume "B" [Nm³]
7 Gas temperature "B" [oC] Temperature average 24h [oC]
8 Gas pressure "A" [mbar] Gas pressure average 24h [mbar]
9 Partial quantity "A" [l] GATE TIME [s]
10 Partial quantity "A" [Nm³] GATE TIME [s]
11 Partial quantity "B" [l] GATE TIME [s]
12 Partial quantity "B" [Nm³] GATE TIME [s]
Note:
The average values are displayed as flashing values as long as the operating time of the device is less than
the capture time for the mean value. In this case, more significant deviations in the displayed value
cannot be avoided, or are normal.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 26 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
CONTENT OF LINE 3 Plain text in German, according to content of line 1.
CONTENT OF LINE 4A DEVICE
STATUS
DISPLAY
OK The device is ready for operation and is running
in standard function mode; no errors present.
M An application error has occurred,
i.e. a function failure was detected.
E
A system error (hardware defect, powering up
error etc.) was detected, i.e. the device can no
longer guarantee functionality. Please contact
the service department.
CONTENT OF LINE 4B DISPLAY OF PROGRAMMING
CODE
The code display can be found to the right of the status
display, and comprises a 9-digit LCD display. The line
contains the configuration function codes described
below.
DEVICE STATUS
"M" OR "E"
In the event of a system error (= "E"), a 4-digit error code
is displayed
Shows a malfunction or system error.
KEYS ON FRONT The five keys on the front Abort, Arrow down, Arrow up, OK and
Scroll can be used for operation.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 27 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
9 Operating overview
Programming can be performed directly at the device or via a PC USB interface by using the configuration
software E3DM (see instructions for use IM 507 D).
As soon as voltage is applied, the device is in measuring mode.
Pressing the key for at least 5 seconds causes the flow correction calculator to switch to the
configuration mode, in which the configuration is displayed or can be programmed. The measured value
display is switched off and the first configuration code appears in the programming code display.
9.1 Operating overview in measurement mode
In measurement mode, operation is performed by means of the five keys on the front according to the
following scheme:
Abort Stops automatically measurement value switching
�The measured value display mode currently selected remains active
Arrow down Switching of measured value display mode
Interruption of automatic run-through of measured value display modes
� Auto mode with key
Arrow up Switching of measured value display mode
Interruption of automatic run-through of measured value display modes
� Auto mode with key
OK No effect in measurement mode
Scroll 5-second configuration mode:
� Current configuration
� Programming mode
Auto mode for measured value display
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 28 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
9.2 Operating overview in configuration mode
9.3 Operating overview in programming mode
Pressing the key switches the displayed configuration function code to programming mode. The first
line of the measured value display shows the previous value of the configuration function. The new value
can be entered in the second line of the measured value display.
In programming mode, operation is performed by means of the five keys on the front.
Abort Switches from configuration mode to measurement mode
Arrow down Selection of configuration function
Arrow up Selection of configuration function
OK Pressing the key has no effect in the configuration mode
Scroll Switches programming mode for configuration function:
Setting via or
� Confirmation with
Abort Switches from configuration mode to measurement mode.
Arrow down Selection of configuration function
Arrow up Selection of configuration function
OK Pressing the confirms the programming
Scroll Switches Programming mode to configuration function:
Setting via or
� Confirmation with
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 29 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
10 Configuration function codes
As described in 9, the flow rate correction calculator can be switched to configuration mode by pressing
the key for at least 5 seconds. The measured value display is switched off and the first configuration
code appears in the programming code display. Pressing the keys or switches between the
configuration function codes listed below. Once the end or beginning of the code list has been reached,
no more switching takes place. Switching can only take place in the opposite direction.
Please note:
The configuration function codes may be protected with a 4-digit code for the various user groups. In this
case, you will only be able to view the configuration function codes for the user group ALL. For enabling
user groups OEM or SRV, you need to enter the corresponding code under configuration function code
50 – PIN entry.
Functions within configuration codes
- You can change the preset values by pressing the key within a configurable configuration code.
- By pressing the keys or , you can continue switching the relevant display in the configuration menu. Fast scrolling can be performed by holding down the key. The longer you press the key, the faster the display changes. The value selected remains active until the keys or are pressed or fine-tuning has taken place or programming has been confirmed by means of the key.
- Where programming is not completed within the preset time or is cancelled by pressing the key, the timeout function cause programming to be aborted. The change is not stored.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 30 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
10.1 Configuration function code types
CODE DESCRIPTION ACCESS ADJUSTMENT RANGE STEP
0001 Device ID ALL - -
0002 Available options and features ALL - -
0003 SW version & BUILD ID ALL - -
0004 SW version communication subsystem1) /
Ethernet subsystem1)
ALL - -
0005 Operating hours ALL - -
0006 Serial number ALL - -
0007 Ethernet IP address 1) ALL - -
0008 Ethernet subnet mask 1) ALL - -
0009 Ethernet gateway address 1) ALL - -
0010 Ethernet MAC address 1) ALL - -
0015 Trigger Ethernet broadcast 1) ALL 0-1 1
0020 Display device time ALL - -
0050 PIN entry 2) ALL 0000-9999 1
0051 Service PIN 2) SRV 0000-9999 1
0052 OEM PIN 2) OEM 0000-9999 1
0053 Parameter code 2) SRV 0000-9999 1
0054 Parameter index 2) SRV 0000-9999
0055 Parameter value 2) SRV -231±(231-1) 1*
0080 Data logger on/off 1) SRV 0-1 1
0088 Reboot device SRV 0-1 1
0100 Timeout in settings menu ALL 30-300sec 1
0110 Interval for automatic measurement value
switching
ALL 500-3000ms 250ms
0111 Hold time for quick adjustment of menu ALL 1-30s 1s
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 31 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
CODE DESCRIPTION ACCESS ADJUSTMENT RANGE STEP
0120 Default measured value display at startup SRV (-1)-10 1
0150 Brightness display SRV 1/10/100Nm3 -
0160 LCD contrast SRV 250-5000ms 250ms
0161 LCD illumination, negative display SRV 1/10/100Nm3 -
1020 Counter output "A" duty cycle 1) SRV 50-100% 5
1021 Counter output "A" unit 1) SRV (-1)-10 1
1030 Counter output "B" duty cycle 1) SRV (-4) - 3 1
1031 Counter output "B" unit 1) SRV -1...22000µA 1µA
2000 Fixed value specification slot 0 SRV -1...22000µA 1µA
2001 Fixed value specification slot 1 SRV -1...22000µA 1µA
2002 Fixed value specification slot 2 SRV -1...22000µA 1µA
2003 Fixed value specification slot 3 SRV -1...22000µA 1µA
2004 Fixed value specification slot 4 SRV -1...22000µA 1µA
2005 Fixed value specification slot 5 SRV -1...22000µA 1µA
2006 Fixed value specification slot 6 SRV -1...22000µA 1µA
2007 Fixed value specification slot 7 SRV -1...22000µA 1µA
2010 Fixed value specification slot 8 SRV -1...22000µA 1µA
2011 Fixed value specification slot 9 SRV -1...22000µA 1µA
2012 Fixed value specification slot 10 SRV -1...22000µA 1µA
2013 Fixed value specification slot 11 SRV -1...22000µA 1µA
2014 Fixed value specification slot 12 SRV -1...22000µA 1µA
2015 Fixed value specification slot 13 SRV -1...22000µA 1µA
2016 Fixed value specification slot 14 SRV -1...22000µA 1µA
2017 Fixed value specification slot 15 SRV 0/1 1
3000 Delete integrator "A" slave pointer 1) SRV 0/1 1
3001 Delete integrator "A" partial quantity 1) OEM 0/1 1
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 32 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
CODE DESCRIPTION ACCESS ADJUSTMENT RANGE STEP
3002 Delete integrator "A" total quantity 1) OEM 0/1 1
3003 Delete integrator "A" all 1) SRV 0/1 1
3010 Delete integrator "B" slave pointer 1) SRV 0/1 1
3011 Delete integrator "B" partial quantity 1) OEM 0/1 1
3012 Delete integrator "B" total quantity 1) OEM 0/1 1
3013 Delete integrator "B" all 1) SRV 0.1-60s 0.1s
4000 Time constant filter input #0 SRV 0.1-60s 0.1s
4001 Time constant filter input #1 SRV 0.1-60s 0.1s
4002 Time constant filter input #2 SRV 0.1-60s 0.1s
4003 Time constant filter input #3 SRV 0.1-60s 0.1s
4004 Time constant filter input #4 SRV 0.1-60s 0.1s
4005 Time constant filter input #5 SRV 0.1-60s 0.1s
4006 Time constant filter input #6 SRV 0.1-60s 0.1s
4007 Time constant filter input #7 SRV 0.1-60s 0.1s
4100 Time constant filter output #0 SRV 0.1-60s 0.1s
4101 Time constant filter output #1 SRV 0.1-60s 0.1s
4102 Time constant filter output #2 SRV 0.1-60s 0.1s
4103 Time constant filter output #3 SRV 0.1-60s 0.1s
4104 Time constant filter output #4 SRV 0.1-60s 0.1s
4105 Time constant filter output #5 SRV 0.1-60s 0.1s
4016 Time constant filter output #6 SRV 0.1-60s 0.1s
4107 Time constant filter output #7 SRV 0 / 4000µA -
4200 Offset current input #0 SRV 0 / 4000µA -
4201 Offset current input #1 SRV 0 / 4000µA -
4202 Offset current input #2 SRV 0 / 4000µA -
4203 Offset current input #3 SRV 0 / 4000µA -
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 33 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
CODE DESCRIPTION ACCESS ADJUSTMENT RANGE STEP
4204 Offset current input #4 SRV 0 / 4000µA -
4205 Offset current input #5 SRV 0 / 4000µA -
4206 Offset current input #6 SRV 0 / 4000µA -
4207 Offset current input #7 SRV 0 / 4000µA -
4300 Offset current output #0 SRV 0 / 4000µA -
4301 Offset current output #1 SRV 0 / 4000µA -
4302 Offset current output #2 SRV 0 / 4000µA -
4303 Offset current output #3 SRV 0 / 4000µA -
4304 Offset current output #4 SRV 0 / 4000µA -
4305 Offset current output #5 SRV 0 / 4000µA -
4306 Offset current output #6 SRV 0 / 4000µA -
4307 Offset current output #7 SRV 0 / 4000µA -
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 34 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
10.2 Description of individual configuration function codes
Configuration function code 0001 - Device ID
Device ID is shown in the measured value display.
The device ID cannot be change d; it is specified ex factory.
Access group: User identification by means of a PIN is not required.
Configuration function code 0002 - Available options
The available options are shown in the measured value display. The options are preceded by a hyphen in
each case, resulting in several options being separated from each other as well. The end of the list of
available options is represented by two consecutive decimal points. If the list of available options is too
long to be shown in the first line of the measured value display, pressing the keys or will continue
switching the display.
The available options cannot be changed; they are specified ex factory.
Access group: ALL
Configuration function code 0003 - SW version & BUILD ID
The first line of the measured value display shows the software version and the second line shows the
BUILD ID of the software installed in the device.
The software version and BUILD ID cannot be changed; the information is specified ex factory.
Access group: ALL
Configuration function code 0004 - SW version communication subsystem
Where this is available as an option, the software version of the PLC is displayed in the first line. The
second line contains the software version for the Ethernet subsystem.
The software version communication subsystem cannot be changed; the information is specified ex
factory.
Access group: ALL
Configuration function code 0005 - Operating hours
The first line of the measured value display shows the total counter reading for the operating hours.
The operating hours reading cannot be changed.
Access group: ALL
Configuration function code 0006 - Serial number
The first line displays the serial number.
The serial number cannot be changed.
Access group: ALL
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 35 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 0007 - Ethernet IP address
Where this is available as an option, the IP address of the device is displayed.
The IP address cannot be changed.
Access group: ALL
Configuration function code 0008 - Ethernet subnet mask
Where this is available as an option, the Ethernet subnet mask of the device is displayed.
The subnet mask cannot be changed.
Access group: ALL
Configuration function code 0009 - Ethernet gateway address
Where this is available as an option, the Ethernet gateway address of the device is displayed.
The gateway address cannot be changed.
Access group: ALL
Configuration function code 0010 - Ethernet MAC address
Where this is available as an option, the Ethernet MAC address of the device is displayed.
The MAC address cannot be changed.
Access group: ALL
Configuration function code 0015 - Trigger Ethernet broadcast
Where the Ethernet option is available, EDIT is shown in the first line of the display. The display in the
second line 0000 can be edited.
The subnet mask cannot be changed.
Access group: ALL
Adjustment range: 0-1
Step: 1
Configuration function code 0020 - Show device time
The first line of the display shows the device time comprising the date and time.
The device time cannot be changed.
Access group: ALL
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 36 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 0051 - PIN entry
Where identification of the user was correctly completed by entering the user PIN, all configuration
function codes for the access group ALL are enabled for viewing/modifying until the configuration mode
is exited.
Access group: ALL
Adjustment range: 0000 ... 9999
Step: 1
Configuration function code 0052 - OEM PIN
Where identification of the user of the OEM user group was correctly completed by entering the OEM
PIN, all configuration function codes for the access groups ALL, SRV and OEM are enabled for
viewing/modifying until the configuration mode is exited.
Access group: OEM
Adjustment range: 0000 … 9999
Step: 1
Configuration function code 0080 - Data logger on/off
The device is equipped with 2 GB ring storage, which can be activated by means of the configuration
function code Data logger on/off.
Access group: SRV
Adjustment range: 0 - 1
Step: 1
Configuration function code 0088 - Reboot device
To perform a reboot without disconnecting the flow rate correction calculator from the voltage supply,
the value of the display must be changed.
Access group: SRV
Adjustment range: 0 - 1
Step: 1
Configuration function code 0100 - Timeout in settings menu
The first line of the measured value display shows the value of the timeout function.
Value of timeout function:
Access group: ALL, SRV, OEM
Adjustment range: 30 ... 300 sec
Step: 1 sec
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 37 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 0110 - Interval for automatic measurement value switching
The first line of the measured value display shows the interval for automatic measurement value
switching.
If the flow rate correction calculator is in measurement mode and automatic measurement value
switching is active, the switch to the next measurement value mode takes place in the time set here.
Access group: ALL, SRV, OEM
Adjustment range: 250 ... 5000 ms
Step: 250 ms
Configuration function code 0111 - Time interval for quick adjustment of menu
You can set the time intervals for quick adjustment of the menu as required. The second line shows the
current time.
Access group: ALL
Adjustment range: 500 – 3000 ms
Step: 250 ms
Configuration function code 0120 - Default measured value display at startup
The first line of the measured value display shows the value for the measured value display mode.
Messwertanzeigemodus beim Start:
As soon as voltage is applied, the device is in measuring mode. The values for the selected measured
value display mode are displayed. If automatic measurement value switching is active, the switch to the
next measurement value mode takes place in the present time. Alternatively, one of the 12 measured
value display modes can be programmed as default at startup.
Access group: SRV
Adjustment range: -1 automatic measurement switching
0 ... 11 measured value display modes 1 to12 Step: 1
Configuration function code 0160 - LCD contrast
The first line of the measured value display shows the value of the display contrast.
Access group: SRV
Adjustment range: 0 – 63
Step: 1
Configuration function code 0161 - LCD illumination, negative display
The first line of the measured value display shows the type of LCD display as well as the display
brightness of the device.
Access group: SRV
Adjustment range: (-4) - 3
Step: 1
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 38 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 1020 - Counter output "A" duty cycle
The first line of the measured value display shows the value of the duty cycle of counter output "A" of the
device.
Access group: SRV
Adjustment range: 250 ... 2500 ms
Step: 250 ms
Configuration function code 1021 - Counter output "A" unit
The first line of the measured value display shows the value of the unit of counter output "A".
Access group: SRV, OEM
Adjustment range: 1 is equivalent to 1 Nm3/h
10 is equivalent to 1/10 Nm3/h
100 is equivalent to 1/100 Nm3/h Step: Switching between values 1, 10 and 100
Configuration function code 1030 - Counter output "B" duty cycle <optional>
The first line of the measured value display shows the value of the duty cycle of counter output "B".
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: SRV, OEM
Adjustment range: 250 ... 2500 ms
Step: 250 ms
Configuration function code 1031 - Counter output "B" unit <optional>
The first line of the measured value display shows the value of the unit of counter output "B".
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: SRV, OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
The first line of the measured value display shows the value of the unit of counter output "B".
Configuration function code 2000 - 2007 and 2010 - 2017 – Fixed value specification slot 0 to 15
The fixed value for the relevant slot can be edited in the second line.
Access group: SRV
Adjustment range: -1…22000 µA Step: 1 µA
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 39 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 3000 - Delete integrator "A" slave display
The first line of the measured value display shows the value Do not delete (0) or Delete (1) of the
integrator "A" slave display.
Access group: SRV, OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3001 - Delete integrator "A" partial quantity
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "A" partial quantity.
Access group: SRV, OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3002 - Delete integrator "A" total quantity
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "A" total quantity.
Access group: OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3003 - Delete integrator "A" all
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "A" all.
Access group: OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 40 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
Configuration function code 3010 - Delete integrator "B" slave display <optional>
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "B" slave display.
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: SRV, OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3011 - Delete integrator "B" partial quantity <optional>
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "B" partial quantity.
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: SRV, OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3012 - Delete integrator "B" total quantity <optional>
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "B" total quantity.
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
Configuration function code 3013 - Delete integrator "B" all <optional>
The first line of the measured value display shows the value for selecting Do not delete (0) or Delete (1)
of the integrator "B" all.
Option: Display/use of the function is only possible for 2-channel flow rate correction
calculators
Access group: OEM
Adjustment range: 0 is equivalent to >Do not delete<
1 is equivalent to >Delete< Step: Switching between values 0 and 1 is possible.
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 41 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
11 Connecting diagram
P=
Speed Pressure Flow Rate Temperature
Instruction Manual IM 303 E Page 42 Phone: +49 (0)6021 - 45 80 7 - 0
Fax: +49 (0)6021 - 45 80 7 - 20
Esters Elektronik GmbH
Görresstrasse 17 · D-63739 Aschaffenburg
eMail: [email protected]
Internet: http://www.esters.de
Re
v.-N
r.:
IM 3
03
E V
1.2
-20
14
-07
-17
ABABABAB
24 VDC
ABCABCABCABC ABCABC ABCABC
24 V/DC ±3 V/DC
321
24 V/DC -
+
-+
Port XPort X
AB AB-+ -+
1918
K 4
1716
K 3
30 V/DC, 1 A
Port 16Port 15
1514
K 2
1312
K 1Port 14Port 13
UB+ Æ ca. 23 V/DC,
100 mA
C B A C B A
Port X Port X
C B A C B A
Port X Port X
+18V A GND
Re
se
rve
B
GN
D
Flow Sensor
4 1 3 2
ABC
UB+ E
5 6 GND
1 2 3 4
GD-100,
LRM
UNI 100
-+
UB+E
ABC C B A
UB+E
+
C B A
UB+ E
+ -
ABC
UB+ E
ABC
UB+ E
4 5 6
3 2 1
SC 300,SC 310,SC 310c
GD 300,
GD 500
ABC
UB+ E
P
S
+IOUT
┴
+24V DC
Shield
HB 300 ** oder HB 300
GD 300 / 500
En
Wiring recommendation: preferably 1 mm², max. 1,5 mm²
Wiring recommendation: preferably 0,5 mm², max. 0,75 mm²
Gas - Flow - Calculator
Supply voltage
0(4)..20 mA,load max. 500 Ohm
AA Analogue output
Sensor connection
DE Digital input
EE RS485 input
AE Analogue input
0(4)..20 mA
Input resistance
100 Ohm 2 - wire transducer
4..20 mA, double conductor
3 - wire transducer
0(4)..20 mA, triple conductor max. 1 kHz,
pulse width > 5 ms,
max. 20 V/DC
PVC cable2 x 0,5 mm²;
shielded;< 35 m
IE Pulse input
PVC cable3 x 0,75 mm²;
shielded; < 300 m
IE Pulse input
PVC cable2 x 0,5 mm²;
shielded;< 35 m
P=
Speed Pressure Flow Rate Temperature