instruction sheet 666-510 - s & c electricseptember 27, 2010© s&c electric company instruction...
TRANSCRIPT
-
September 27, 2010© S&C Electric Company Instruction Sheet 666-510
S&C Remote Supervisory PME Pad-Mounted GearOutdoor Distribution (14.4 kV and 25 kV)
Fusing and Manual Switching
Operation
Table of Contents
Section Page Section Page
IntroductionQualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . 2Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . 2Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Special Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety InformationUnderstanding Safety-Alert Messages . . . . . . . . . . . . . . 7Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . 7Replacement Instructions and Labels . . . . . . . . . . . . . . . 7
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Manual Switching with Mini-RupterOperating the Mini-Rupter Switch . . . . . . . . . . . . . . . . . . 9
Fuse Access — OpeningOpening the TransFuser Mounting . . . . . . . . . . . . . . . . 10
FusingAssembling the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . 13Installing the Fuse in the Mounting . . . . . . . . . . . . . . . . 13
Fuse Access — ClosingClosing the TransFuser Mounting . . . . . . . . . . . . . . . . . 14
Re-FusingHow to Detect a Blown Fuse . . . . . . . . . . . . . . . . . . . . 15Replacing a Blown Fuse . . . . . . . . . . . . . . . . . . . . . . . . 17
MaintenanceComponents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Returning Equipment to Service . . . . . . . . . . . . . . . . . . 20Enclosure Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Appendix ADielectric Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Appendix BRatings for S&C Mini-Rupter Switches . . . . . . . . . . . . 22
Appendix CControl Equipment Groups . . . . . . . . . . . . . . . . . . . . . 23
Appendix DOptional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Appendix ECurrent-Limiting Fuses for Use in
S&C PME Pad-Mounted Gear . . . . . . . . . . . . . . . . 27
-
2 S&C Instruction Sheet 666-510
Introduction
Qualified Persons Ç WARNINGThe.equipment.covered.by.this.publication.must.be.installed,.operated,.and.main-tained.by.qualified.persons.who.are.knowledgeable.in.the.installation,.operation,.and.maintenance.of.underground.electric.power.distribution.equipment.along.with.the.associated.hazards ..A.qualified.person.is.one.who.is.trained.and.competent.in:
•. The.skills.and.techniques.necessary.to.distinguish.exposed.live.parts.from.non-live.parts.of.electrical.equipment .
•. The.skills.and.techniques.necessary.to.determine.the.proper.approach.distances.corresponding.to.the.voltages.to.which.the.qualified.person.will.be.exposed .
•. The. proper. use. of. the. special. precautionary. techniques,. personal. protective.equipment,.insulating.and.shielding.materials,.and.insulated.tools.for.working.on.or.near.exposed.energized.parts.of.electrical.equipment .
These. instructions.are. intended.only. for.such.qualified.persons ..They.are.not.intended.to.be.a.substitute.for.adequate.training.and.experience.in.safety.procedures.for.this.type.of.equipment .
NOTICEWhen.an.S&C.Voltage.Sensor.is.used.to.provide.ac.power.input.for.an.S&C.Battery.Charger.(Catalog.Number.Suffix.“-Y4”.or.“-Y7”),.the.gear.must.be.applied.at.system.line-to-line.voltages.ranging.from.11 .43.kV.through.17 .0.kV.for.14 .4-kV.models,.and.from.20 .44.kV.through.29.kV.for.25-kV.models ..In.addition,.when.voltage.sensors.are.used.to.provide.ac.power.input.for.the.battery.charger,.single-phase.voltage.sens-ing.(Catalog.Number.Suffix.“-Y2”.or.“-Y3”),.or.optional.three-phase.voltage.sensing.(Catalog.Number.Suffix.“-Wl”),.the.voltage.sensors.must.be.connected.to.the.voltage.limiter.at.all.times ..If the voltage sensors are disconnected from the voltage limiter while the gear is energized, the voltage sensors will be damaged.
Read this Instruction Sheet
Read. this. instruction. sheet. thoroughly. and. carefully. before. installing. or. operating..your.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..Familiarize.yourself.with.“Safety.Information”.on.page.6 .
Retain this Instruction Sheet
This.instruction.sheet.is.a.permanent.part.of.your.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..These.instructions.should.be.stored.in.the.instruction.manual.holder .
Proper Application Ç CAUTIONThe.equipment.in.this.publication.must.be.selected.for.a.specific.application ..The.application.must.be.within.the.ratings.furnished.for.the.equipment ..Ratings.for.this.gear.are.listed.on.the.ratings.label.on.the.interior.of.the.doors.(right-hand.door.only.for.double-door.models .)
General Instruction.manuals.regarding.installation.and.operation.of.the.pad-mounted.gear.are.included.in.the.“Installation.and.Operation.Information.Kit”.provided.with.each.unit.of.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..Wiring.diagrams.and.a.catalog.dimen-sional.drawing.showing.cable-locating.and.anchor-bolt.dimensions.is.also.provided.in.the.information.kit ..All.per.sonnel.involved.with.installation.and.operation.of.the.gear.should.be.thoroughly.familiar.with.the.contents.of.the.kit .
The.following.instructions.cover.operation.of.fuses.and.manual.Mini-Rupter.Switches.in.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..For.operating.instructions.regarding.Type.PM.Switch.Operators.or. the.control-equipment.group.components,. refer. to.S&C.Instruction.Sheet.666-510 .
-
S&C Instruction Sheet 666-510 3
Introduction
S&C. Remote. Supervisory. PME. Pad-Mounted. Gear. permits. automated. switching.and.provides.fault.protection.for.underground.distribution.systems ..This.gear.features.elbow-connected.encased.components.and.accommodates.separable.insu.lated.connec-tors ..See.Figure.1.on.page.5.and.Figure.2.on.page.6 ..Each.unit.contains.the.fol.lowing:
•. 600-ampere.S&C.Mini-Rupter.Switches. for. three-pole. live.switching.of. three-phase.source.circuits .
•. Type.PM.Switch.Operators.to.provide.power.operation.of.the.associated.Mini-Rupter.Switches .
•. Control-equipment-group.components.and.interconnecting-control-wiring.base.spacer.with.low-voltage.wiring.for.each.switch.operator ..(Refer.to.Appendix.C.on.page.23.for.descriptions.of.the.various.control.equipment.groups .)
•. S&C.TransFuser™.Mountings—fuse-handling.mechanisms.with.mechanical.interlocks ..Models.available.offer.a.choice.of.S&C.Type.SME-20.or.SME-4Z.Power.Fuses,.S&C.Fault.Fiter®.Electronic.Power.Fuses,.or.a.variety.of.single-barrel.current-limiting.fuses .
•. Penta-Latch®.Mechanism.on.doors.for.access.control ..Mechanism.provides.automatic.door.latching.and.permits.padlocking.only.when.the.door.is.latched.closed ..Doors.can.be.opened.only.with.a.pentahead.socket.wrench.or.tool.except.when.hexhead.actuators.(Catalog.Number.Suffix.“-Bl”.or.“-B2”).are.specified .
A.variety.of.optional. features.are.available.for.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..The.catalog.number.stamped.on.the.nameplate.affixed.to.the.enclosure.door.is.suffixed.with.letter-number.combinations.applicable.to.the.gear.furnished ..Refer.to.Appendix.D.on.pages.24.and.25.for.descriptions.of.the.optional.features .
Special Warranty The.standard.warranty.contained.in.seller’s.standard.conditions.of.sale,.as.set.forth.in.Price.Sheet.150,.applies.to.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear,.includ-ing.the.associated.optional.features.and.accessories.purchased.therewith ..In.addition,.seller.warrants.for.a.period.of.2.years.from.the.date.of.shipment.all.components.not.of.S&C.manufacture.that.are.furnished.with.seller’s.control.equipment.groups,.such.as.the.remote.terminal.unit,.transceiver,.battery.packs,.current.sensors,.etc ..Also.included.in.this.2-year.warranty.is.a.software.warranty.provided.by.Harris.Controls.which.includes.customer.technical.assistance,.updates.(bug.or.error.corrections).as.required,.product.documentation,.a.Harris.Controls.quarterly.newsletter,.and.membership.in.the.Harris.Controls.User’s.Group ..Software.upgrades.involving.new.features.or.applications.will.be.made.available.for.a.separate.charge .
.Seller’s.standard.warranty.and.special.warranty.provisions.do.not.apply.to.any.com-ponents.not.of.S&C.manufacture.that.are.supplied.and.installed.by.the.purchaser,.nor.to.the.ability.of.seller’s.equipment.to.work.with.such.components .
-
4 S&C Instruction Sheet 666-510
Introduction
Warranty The.warranty.and/or.obligations.described.in.S&C’s.standard.conditions.of.sale,.as.set.forth.in.Price.Sheet.150,.plus.any.special.warranty.provisions,.as.set.forth.in.the.applicable.product-line.specification.bulletin,.are.exclusive ..The.remedies.provided.in.the.former.for.breach.of.these.warranties.shall.constitute.immediate.purchaser’s.or.end.user’s.exclusive.remedy.and.a.fulfillment.of.all.seller’s.liability ..In.no.event.shall.seller’s.liability.to.imme-diate.purchaser.or.end.user.exceed.the.price.of.the.specific.product.which.gives.rise.to.immediate.purchaser’s.or.end.user’s.claim ..All.other.warranties.whether.express.or.implied.or.arising.by.operation.of.law,.course.of.dealing,.usage.of.trade.or.otherwise,.are.excluded ..The.only.warranties.are.those.stated.in.Price.Sheet.150,.and.THERE.ARE.NO.EXPRESS.OR.IMPLIED.WARRANTIES.OF.MERCHANTABILITY.OR.FITNESS.FOR.A.PARTICULAR.PURPOSE ..ANY.EXPRESS.WARRANTY.OR.OTHER.OBLIGATION.PROVIDED.IN.PRICE.SHEET.150.IS.GRANTED.ONLY.TO.THE.IMMEDIATE.PURCHASER.AND.END.USER,.AS.DEFINED.THEREIN ..OTHER.THAN.AN.END.USER,.NO.REMOTE.PURCHASER.MAY.RELY.ON.ANY.AFFIRMATION.OF.FACT.OR.PROMISE.THAT.RELATES.TO.THE.GOODS.DESCRIBED.HEREIN,.ANY.DESCRIPTION.THAT.RELATES.TO.THE.GOODS,.OR.ANY.REMEDIAL.PROMISE.INCLUDED.IN.PRICE.SHEET.150 .
The.seller’s.warranties.do.not.apply.if.fuse.units,.fuse-unit.end.fittings,.holders,.refill.units,.or.switch.blades.of.other.than.S&C.manufacture.are.used.in.conjunction.with.S&C.SME.Mountings ..Nor.do.the.seller’s.warranties.apply.if.other.than.Fault.Fiter®.Electronic.Power.Fuses,.S&C.Switch.Blades,.or.selected.current-limiting.fuses.are.used.in.conjunc-tion.with.S&C.Fault.Fiter.Electronic.Power.Fuse.Mountings,.and.S&C.Holders.designed.therefore,.or.if.current-limiting.fuses.are.applied.other.than.as.set.forth.under.“Current-Limiting.Fuses.for.Use.in.S&C.PME.Pad-Mounted.Gear,”.in.S&C.Instruction.Sheet.666-510 .
-
S&C Instruction Sheet 666-510 5
Introduction
Low-voltage compartment
Interconnecting-control-wiring base spacer shields low-voltage wiring from high voltage
Type PM Switch Operator for power operation of associ ated Mini-Rupter Switch
Penta-Latch Mechanism
Figure 1. Remote Supervisory Model PME-9 with Type PM Switch Operator and low-voltage compartment.
-
6 S&C Instruction Sheet 666-510
Introduction
Figure 2. Remote Supervisory Model PME-9 showing open-door views of fuse-termination compartments (above) and switch-termination compartments (below).
Current sensors for three-phase current sensing (Catalog Number Suffixes“-Y2” through “-Y4”)
200-ampere bushing wells Ground tabs for grounding bushing well inserts Door holder TransFuserMounting
Cable guides are mounted horizontally, extend toward TransFuser Mounting
Ground bails are mounted vertically
600-ampere bushingsViewing windows allow visual verification of switch position Penta-Latch
MechanismDoor holder
Ground rods extendfull width of switch compartment
-
S&C Instruction Sheet 666-510 7
Safety Information
Understanding Safety-Alert Messages
There.are.several.types.of.safety-alert.messages.which.may.appear.throughout.this.instruction.sheet.as.well.as.on.labels.affixed.to.the.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..Familiarize.yourself.with.these.types.of.messages.and.the.importance.of.the.various.signal.words,.as.explained.below .
Ç DANGER“DANGER”. identifies. the. most. serious. and. immediate. hazards. which.will likely.result. in.serious.personal. injury.or.death. if. instructions,. including.recommended.precautions,.are.not.followed .
Ç WARNING“WARNING”.identifies.hazards.or.unsafe.practices.which.can.result.in.serious.personal.injury.or.death.if.instructions,.including.recommended.precautions,.are.not.followed .
Ç CAUTION“CAUTION”. identifies.hazards.or.unsafe.practices.which.can. result. in.minor.per-sonal.injury.or.product.or.property.damage.if.instructions,.including.recommended.precautions,.are.not.followed .
NOTICE“NOTICE”.identifies.important.procedures.or.requirements.that.can.result.in.product.or.property.damage.if.instructions.are.not.followed .
Following Safety Instructions
If.you.do.not.understand.any.portion.of.this.instruction.sheet.and.need.assistance,.contact.your.nearest.S&C.Sales.Office.or.S&C.Autho.rized.Distributor ..Their.telephone.numbers.are.listed.on.S&C’s.website.www .sandc .com ..Or.call.S&C.Headquarters.at.(773).338-1000;.in.Canada,.call.S&C.Electric.Canada.Ltd ..at.(416).249-9171 .
NOTICE
Read.this.instruction.sheet.thoroughly.and.carefully.before.operating.or.installing.your.S&C.Remote.Super-visory.PME.Pad-Mounted.Gear .
Replacement Instructions and Labels
If.you.need.additional.copies.of.this.instruction.sheet,.contact.your.nearest.S&C.Sales.Office,.S&C.Authorized.Distributor,.S&C.Headquarters,.or.S&C.Electric.Canada.Ltd .
It.is.important.that.any.missing,.damaged,.or.faded.labels.on.the.equipment.be.replaced.immediately ..Replacement.labels.are.available.by.contacting.your.nearest.S&C.Sales.Office,.S&C.Authorized.Distributor,.S&C.Headquarters,.or.S&C.Electric.Canada.Ltd .
-
8 S&C Instruction Sheet 666-510
Safety Precautions
Ç DANGER
Pad-mounted gear contains high voltage. Failure to observe the precautions below will result in serious personal injury or death.
Some.of.these.precautions.may.differ.from.company.operating.procedures.and.rules ..Where.a.discrepancy.exists,.users.should.follow.their.company’s.operating.procedures.and.rules .
1 .. QUALIFIED PERSONS..Access.to.pad-mounted.gear.......must.be.restricted.only.to.qualified.persons ..See.“Qual-ified.Persons”.on.page.2 .
2 .. SAFETY PROCEDURES..Always.follow.safe.operat-ing.procedures.and.rules .
3 .. PERSONAL PROTECTIVE EQUIPMENT.. Always.use. suitable. protective. equipment. such. as. rubber.gloves,.rubber.mats,.hard.hats,.safety.glasses,.and.flash.clothing.in.accordance.with.safe.operating.procedures.and.rules .
4 .. SAFETY LABELS..Do.not.remove.or.obscure.any.of.the.“CAUTION,”.“WARNING,”.or.“DANGER”.labels .
5 .. KEY INTERLOCKS.v. If.optional.key.interlocks.were.furnished,.they.must.
be.in.place .v. Check. the. operating. sequence. of. key. interlocks. to.
verify.proper.sequencing .v. After. the. pad-mounted. gear. is. installed,. either:. (1).
destroy. the. extra. set. of. keys. or. (2). make. them.accessi.ble.only.to.qualified.persons ..This.will.main-tain.the.integrity.of.the.key-interlock.scheme ..
v. Key.interlocks.are.not.security.locks.and.are.not..sub-stitutes.for.padlocks .
6 .. OPENING DOORS..Do.not.force.doors.open ..Forcing.a. door. open. can. damage. the. latching. mechanism .. If.optional.key.interlocks.are.provided,.correctly.position.the.interlocks.so.the.doors.can.be.opened .
7 .. CLOSING AND LOCKING DOORS.v. Doors.must.be.securely.closed.and.latched,.with...pad-
locks.in.place.at.all.times.unless.work.is.being..per-formed.inside.the.enclosure ..
v. Mini-Rupter. Switches. have. switch-operating-shaft. .access. covers. located. on. the. sides. of. the.pad-.mounted.gear.enclosure ..They.must.be.closed.and. .padlocked. at. all. times. unless. the. switches.are..being..operated ..
v. Do.not.close.a.door.on.a.TransFuser.Mounting.in.the.open.position.with.a.fuse.in.the.mounting ..The.door.will.strike.the.fuse.pull-ring.which.will..interfere.with.door.closing ..The.door.may.be.closed.if.the.fuse.is.removed.from.the.mounting .
8 .. ENERGIZED TERMINALS..Always.assume.that.both.sets.of.power.terminals.on.any.Mini-Rupter.Switch.or.fuse.are.energized.unless.proved.otherwise.by.test,.by..
visual.evidence.of.open-circuit.conditions.on.both.sets.of.terminals,.or.by.observing.that.both.sets.of.ter.minals.are.grounded .
. 9 ...BACKFEED..Mini-Rupter.Switches.and.fuses.may.be.energized.by.backfeed .
10 ...DE-ENERGIZING, TESTING, AND GROUNDING..Before. touching. any. device. that. is. to. be. inspected,.replaced,. serviced,. or. repaired. in. the. high-voltage.compartments,. always. disconnect. Mini-Rupter.Switches.and.fuses.from.all.power.sources.(including.backfeed),.test.for.voltage,.and.properly.ground .
11 ...TESTING..Test.for.voltage.on.both.sets.of.power.ter-minals.of.any.Mini-Rupter.Switch.or.fuse.using.proper.high-voltage. test. equipment. before. touching. any.device.that. is. to.be. inspected,.replaced,.serviced,.or.repaired.in.the.high-voltage.compartments .
12 .. GROUNDING.
v. Make.sure.that.the.pad-mounted.gear.enclosure.is.properly.grounded.to.the.station.or.facility.ground .
v. After.the.gear.has.been.completely.disconnected.from.all.sources.of.power.and.tested.for.voltage,.install. suitable. grounding. cables. in. all. compart-ments. before. touching. any. device. that. is. to. be.inspected,. replaced,.serviced,.or. repaired. in. the.high-voltage.compartments .
13 .. SWITCH POSITION.v. Always. confirm. the. open/close. position. of. Mini-
Rupter.Switches.by.visually.observing.the.position.of.the.switch.blades .
v. Switches.may.be.energized.by.backfeed .
v. Switches.may.be.energized.in.any.position .
14 .. MAINTAINING PROPER CLEARANCE.. Always.maintain. proper. clearance. from. energized.compo.nents .
15 .. FUSE STORAGE.
v. Always.store.fuses.in.a.clean,.dry.location .
v. Do. not. store. end. fittings,. holders,. interrupting.modules,. or. fuses. in. termination. compartments.unless.the.unit.is.equipped.with.the.optional.fuse-storage. feature. (Catalog. Number. Suffix. “-E1,”.“-E2,”.or.“-E3”) .
-
S&C Instruction Sheet 666-510 9
Manual Switching with Mini-Rupter
Figure 3. Switch-operating handle access.
Operating the Mini-Rupter Switch
The. following. instructions. are. for. operation. of. manual. Mini-Rupter. Switches .. For.Mini-Rupter.Switches.operated.by.Type.PM.Switch.Operators,.refer.to.S&C.Instruction.Sheet.669-515 ..Complete.ratings.for.Mini-Rupters.as.applied.in.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear.are.shown.in.Appendix.B.on.page.22 ..Before.proceeding,.refer.to.the.“DANGER”.on.page.8 ..
1 .. Remove.the.padlock.and.open.the.switch-operating-shaft.access.cover ..See.Figure.3 .
2 .. Remove.the.folding.switch-operating.handle.from.its.storage.pocket.behind.the.access.cover ..Unfold.the.handle.and.slide.it.onto.the.hex.switch-operating.shaft .
. Note.the.switch-position.indicator.which.is.attached.to.the.hex.switch-operating.shaft.and.rests.against.a.stop.in.either.the.open.or.closed.position ..Arrows.indi.cate.switch-open.or.switch-closed.position .
3 .. Rotate.the.handle.in.the.appropriate.direction.to.open.or.close.the.switch,.and.check.the. switch-position. indi.cator. to. verify. that. the. switch. is. in. the. desired. position .. A..window.is.provided.in.the.switch-termina.tion.compartment.to.allow.positive.visual.verification.of.switch-blade.position ..See.Figure.2.on.page.5 .
Ç WARNINGAlways. confirm. the. open/close. position. of. the. Mini-Rupter. Switch. by. visually.observing.the.position.of.the.switch.blades .
4 .. Remove.and. fold. the.switch-operating.handle,.and.return. the.handle. to. its.storage..position ..Then.close.and.padlock.the.access.cover .
Ç CAUTIONDo.not.leave.the.switch-operating-shaft.access.cover.unlocked.if.the.gear.is.left.unattended.by.qualified.persons .
Folding switch-operating handle in operating position
Hood shields padlock shackle
Access cover in padlocked position Connection diagram
Hex switch-operating shaft
Folding switch-operating handle in storage pocket
Access cover opened Switch-position indicator
-
10 S&C Instruction Sheet 666-510
Fuse Access — Opening
S&C.Remote.Supervisory.PME.Pad-Mounted.Gear.is.equipped.with.the.unique.TransFuser.Mounting—a. fuse-handling. mecha.nism. that. is. interlocked. with. the. loadbreak. elbow ..First,.the.elbow.is.removed.to.interrupt.any.fuse.load ..Then,.the.mechanical.interlock.is.actuated,.allowing.operation.of.the.TransFuser.mechanism ..This.permits.access.to.the.fuse.for.quick.and.easy.replacement.of.blown.fuses.with.a.conventional.shotgun.stick ..The.fuse.is.accessible.only.when.it.is.de-energized.and.isolated .
Ç DANGERThe.following.procedures.presuppose.that.the.user.has.supplied.and.installed.load-break.inserts.and.loadbreak elbows .
Open the Mini-Rupter Switches before proceeding if deadbreak inserts and deadbreak elbows are installed, or if company operating procedures and rules do not permit switching with elbows. Failure to open the switches when deadbreak inserts and elbows are used will result in a flashover and serious injury.
Opening the TransFuser Mounting
1 .. Open.the.appropriate.fuse.termination-compartment.door.and.secure.it.with.the.door.holder ..See.Figure.4.on.page.11 ..On.double-door.models,.the.adjacent.door.should.be.closed.and.latched.to.minimize.exposure .
2 .. Using.a.shotgun.stick,.install.a.portable.feedthru.or.standoff.insulator.on.the.parking.stand.that.is.directly.above.the.cable.guide.of.the.elbow.to.be.moved ..This.will.ensure.that. once. the. elbow. is. moved,. the. cable. will. not. interfere. with. the. TransFuser.Mounting .. Using. the. shotgun. stick,. and. following. the. elbow. manufac.turer’s.instructions. for. loadbreak. operation,. remove. the. 200-ampere. loadbreak. elbow.(thus.interrupting.any.load.through.the.fuse.to.be.removed),.and.move.the.elbow.to.the.portable.feedthru.or.standoff.insu.lator ..See.Figure.5.on.page.12 .
Ç DANGERWhen.changing.fuses,.the.200-ampere.interface.need.not.be.covered.since.it.will.be.exposed.only.tempo.rarily ..If.company.operating.procedures.and.rules.require.it,.the.interface.may.be.covered.with.an.insu.lating.protective.cap.without a drain wire ..A.cap.with.a.drain.wire.must.not.be.used ..Operation of the TransFuser mecha-nism will draw the grounded drain wire inside the component compartment close to energized parts which can result in a flashover and serious injury.
Ç WARNINGIf.elbows.are.stored.on.feedthru.or.standoff.insulators.for.an.extended.period.of.time,.cover.the.200-ampere.interface.with.an.insulating.protective.cap.with.a.drain.wire.and.connect.the.drain.wire.to.the.ground.bail ..Failure to connect the drain wire to the ground bail can result in a flashover, injury, and equipment damage.
The.insulated.protective.cap.and.drain.wire.must.be.removed.before.operating.the.TransFuser.mechanism ..Failure to remove the cap and drain wire will in terfere with operation of the mechanism.
-
S&C Instruction Sheet 666-510 11
Fuse Access — Opening
Figure 4. Termination compartment for fuses with elbows installed on 200-ampere inserts in the bushing wells.
Ground bail
200-ampere loadbreak elbow Parking standDoor holder
Storage rack for S&C SMU-20 Fuse Units or SM-4 Refill Units
Cable guides
3 .. Once.the.elbow.has.been.moved.and.mounted.on.a.feedthru.or.standoff.insulator,.the.TransFuser.mecha.nism.may.be.operated ..Using.the.shotgun.stick,.raise.the.mechani-cal.interlock.to.unlock.the.TransFuser.Mounting ..See.Figure.6.on.page.12 ..This.inter-lock,.which.cannot.be.lifted.to.the.unlocked.position.until.the.elbow.has.been.removed,.guards.against.gaining.access.to.the.fuse.while.it.is.carrying.current .
4 .. Secure.the.shotgun.stick.to.the.pull-ring.at.the.lower.end.of.the.TransFuser.Mounting ..See.Figure.7.on.page.12 ..With.an.outward.pull,.rotate.the.TransFuser.Mounting.end-for-end.to.expose.the.fuse ..Make.certain.that.the.mounting.is.latched.before.removing.the.shotgun.stick ..Then.dis.engage.the.shotgun.stick.from.the.pull-ring ..Using.the.shot-gun.stick,.push.against.the.top.of.the.mounting.to.verify.that.it.has.securely.latched ..With.the.TransFuser.Mounting.latched.in.the.open.position,.the.fuse.is.de-energized,.isolated.from.high.voltage,.and.accessible.for.removal.from.the.mounting ..See.Figure.8.on.page.12 .
NOTICEDo.not.close.a.door.on.a.TransFuser.Mounting.in.the.open.position.with.a.fuse.in.the.mounting ..The door will strike the fuse pull-ring which will interfere with door closing. The.door.may.be.closed.if.the.fuse.is.removed.from.the.mounting .
-
12 S&C Instruction Sheet 666-510
Fuse Access — Opening
Figure 5. Removing the loadbreak elbow interrupts any load through the fuse to be removed.
Figure 6. Raising mechanical inter lock to unlock TransFuser Mounting.
Figure 7. Unlatching (or latching) Trans-Fuser Mounting in closed posi tion.
Figure 8. Latching (or unlatching) Trans -Fuser Mounting in the open positi on .
Bushing insert
Elbow installed on portable standoff insulatorMechanical interlock
in locked position
Mechanical interlockin unlocked position
Shotgun stick secured to TransFuserMounting pull-ring
TransFuser Mountingpull-ring
-
S&C Instruction Sheet 666-510 13
Fusing
S&C.Remote.Supervisory.PME.Pad-Mounted.Gear.is.furnished.with.TransFuser.Mountings.that.accommodate.S&C.Type.SME-20.Power.Fuses,.S&C.Type.SME-4Z.Power.Fuses,.or.S&C.Fault.Fiter®.Electronic.Power.Fuses ..Fault.Fiter.Electronic.Power.Fuse.Mountings.also.accommodate.a.variety.of.current-limiting.fuses .
Ç WARNINGWhen. selecting. current-limiting. fuses,. the. voltage. rating. of. the. fuses. must.conform.to.the.recommen.dations.in.Appendix.E.on.pages.27.and.28 ..Failure to conform to these recommendations can result in a flash over, injury, and equipment damage.
Assembling the Fuse S&C Power FuseInstall. an.SMU-20®.Fuse.Unit. into.each.set.of.end.fittings,.an.SM-4®.Refill.Unit. into.each.holder,.or.a.Fault.Fiter.Interrupting.Module.and.Control.Module.into.each.holder,.in.accordance.with.the.instruction.sheet.furnished.with.the.fuse.unit,.refill.unit,.or.inter-rupting.module .
Current-Limiting FusesS&C.Holders.for.current-limiting.fuses.are.designed.for.use.in.pad-mounted.gear.mod-els.that. include.mountings.for.Fault.Fiter.Electronic.Power.Fuses ..These.holders.will.accommodate.the.current-limiting.fuses.listed.in.Appen.dix.E.on.pages.27.and.28 ..For.instructions.on.installing.current-limiting.fuses.in.current-limiting.fuse.holders,.refer.to..S&C.Instruction.Sheet.660-501 .
Installing the Fuse in the Mounting
Fault.Fiter.Electronic.Power.Fuses.rated.25.kV.should.be.installed.in.their.mountings.by.hand.using.suitable.protec.tive.equipment ..Install.all.other.fuses.as.follows:
1 .. Secure.a.shotgun.stick.tightly.to.the.fuse.pull-ring.with.the.fuse.oriented.so.that.the.body.of.the.fuse.is.below.the.stick ..Grasp.the.shotgun.stick.with.both.hands.(approxi-mately.2.feet.apart),.placing.one.hand.on.the.shotgun-stick.latch.mechanism .
2 .. Lift.the.fuse.and.lower.it.into.the.cradle.of.the.fuse.mounting ..
3 .. With.the.fuse.securely.seated.in.the.cradle,.push.the.fuse.forward.to.latch.it.in.the.closed.position ..See.Fig.ure.9 ..Disengage.the.shotgun.stick.from.the.fuse ..
4 .. Verify.that.the.fuse.is.properly.latched.in.the.fuse.mounting ..While.holding.the.shotgun.stick,.push.against.the.fuse.holder.assembly,.and.also.pull.on.the.fuse.assembly.as.shown.in.Figure.10,.by.locating.the.ring.of.the.stick.in.the.opening.below.the.pull-ring .
Figure 9. Fuse lowered into the cradle in preparation for latching to Trans Fuser Mounting.
Figure 10. Pull on the fuse assembly by locating the ring of the stick in the opening below the pull-ring.
-
14 S&C Instruction Sheet 666-510
Fuse Access — Closing
Closing the TransFuser Mounting
After.the.fuse.has.been.installed.or.replaced,.close.the.TransFuser.Mounting.(energize.the.fuse).as.follows:
1 .. Secure.a.shotgun.stick.to.the.pull-ring.at.the.top.of.the.TransFuser.Mounting ..See.Fig-ure.8.on.page.12 ..With.an.outward.pull,.rotate.the.TransFuser.Mounting.end-for-end.to.return.the.fuse.to.the.component.compartment ..Make.certain.that.the.mounting.latches.in.this.position.before.removing.the.shotgun.stick ..Then.disengage.the.shotgun.stick.from.the.pull-ring ..Using.the.shotgun.stick,.push.against.the.bottom.of.the.mounting.to.verify.that.it.has.securely.latched .
2 .. Using. the. shotgun. stick,. lower. the. mechanical. inter.lock. to. lock. the. TransFuser.Mounting .
3 .. If.a.protective.cap.was.placed.on.the.bushing.interface,.remove.it.with.the.shotgun.stick .
4 .. Using.the.shotgun.stick,.move.the.elbow.from.the.por.table.feedthru.or.standoff.insula-tor.to.the.bushing.in.accordance.with.the.elbow.manufacturer’s.instruc.tions ..Remove.the.portable.feedthru.or.standoff.insula.tor.from.the.parking.stand .
5 .. Close.and.latch.the.enclosure.doors ..Pull.outward.on.the.Penta-Latch.Mechanism.cover.to.verify.that.the.door.has.latched.securely,.then.padlock.the.door .
-
S&C Instruction Sheet 666-510 15
Re-Fusing
How to Detect a Blown Fuse
Open.the.appropriate.fuse.termination-compartment.door.and.secure.it.with.the.door.holder ..On.double-door.models,.the.adjacent.door.should.be.closed.and.latched.to.mini-mize.exposure .
S&C Power FusesObserve.the.blown-fuse.target.through.the.viewing.win.dows.provided.for.that.purpose ..Refer.to.Figure.11,.on.page.16,.for.blown-fuse.target.locations.for.S&C.Power.Fuses:
SME-20 Power Fuses or Fault Fiter Electronic Power Fuses—A.red.blown-fuse.target.projects.from.the.SME-20.Power.Fuse.end.fitting.or.the.Fault.Fiter.Holder.when.the.fuse.has.operated. .. .. ..making.it.easy.to.check.fuse.condition.with.the.fuse.in.the.closed.position ..The.blown-fuse.target.retracts.when.the.blown.fuse.unit.or.interrupting.module.is.replaced .
SME-4Z Power Fuses—A.fluorescent-orange.target.in.the.translucent.SME-4Z.Holder.moves.to.the.“BLOWN”.indicator.window.when.the.fuse.operates,.permitting.a.positive.visual.check.of.fuse.condition.without.moving.the.fuse.from.its.closed.position ..The.target.fluoresces.when.illuminated .
Current-Limiting FusesCurrent-Limiting Fuses with Blown-Fuse Indicators—To.find.a.blown. fuse,.gain.access.to.the.fuses.following.the.instructions.found.under.“Fuse.Access—Open.ing”.on.pages.9.through.11 ..A.blown-fuse.indicator.appears.at.the.trunnion.end.when.the.fuse.has.blown .
Current-Limiting Fuses Without Blown-Fuse Indica tors—To.find.a.blown.fuse,.remove.each.fuse.from.its.mounting.following.the.instructions.below ..Then.inspect..the.fuse.per.the.current-limiting.fuse.manufacturer’s.rec.ommendations.to.determine.whether.it.has.blown .
-
16 S&C Instruction Sheet 666-510
Re-Fusing
Red target projects from holderwhen fuse has operated
Fluorescent-orangetarget appears in“BLOWN” indicatorwindow when fusehas operated (visiblethrough translucentholder)
Blown-fuse targets are visible through viewing windows in termination compartments
Red target projects from endfitting when fuse has operated
SME-20 Power Fuse (Fault FiterElectronic Power Fuse is similar)
Pull-ring
SME-4Z Power Fuse
Pull-ring
Pull-ring
Figure 11. Blown-fuse target locations for S&C Power Fuses used in PME models of S&C Pad-Mounted Gear.
-
S&C Instruction Sheet 666-510 17
Replacing a Blown Fuse
1 .. Gain.access.to.the.blown.S&C.Power.Fuse.or.suspect.current-limiting.fuse.following.the.instructions.found.under.“Fuse.Access—Opening”.on.pages.10.through.12 .
2 .. Fault.Fiter.Electronic.Power.Fuses.rated.25.kV.should.be.removed.from.their.mount-ings.by.hand.using.suit.able.protective.equipment ..Remove.all.other.fuses.as.follows:
a .. Grasp.a.shotgun.stick.with.both.hands.(approxi.mately.2.feet.apart),.placing.one.hand.on.the.shot.gun-stick.latch.mechanism .
b .. Secure.the.shotgun.stick.tightly.to.the.fuse.pull-ring ..See.Figure.12 .
NOTICEDo.not permit.the.end.fitting.of.an.SME-20.Power.Fuse.to.strike.the.ground.dur-ing.the.following.removal.pro.cess ..The blown-fuse target may be damaged or become impacted with dirt and may not operate properly.
c .. Stand.in.a.normal,.upright.position.facing.the.shot.gun.stick ..Unlatch.the.fuse.with.a.short,.outward.pull.on.the.fuse.pull-ring ..Then,.remove.the.fuse.from.its.mounting.with.an.upward.and.outward.lift.ing.motion ..See.Figure.9.on.page.13 ..Once.the.fuse.has.been.removed.from.the.mounting,.the.TransFuser.Mounting.may.be.left.with.the.live.parts.in.the.ter.mination.compartment.and.the.doors.may.be.closed .
Figure 12. Shotgun stick secured to fuse pull-ring in preparation for unlatching fuse.
Re-Fusing
-
18 S&C Instruction Sheet 666-510
NOTICEAlways.store.fuses.in.a.clean,.dry.location ..Do.not.store.fuses.in.termination.com-partments.unless.the.unit.is.equipped.with.the.optional.fuse-storage.fea.ture.(Catalog.Number.Suffix.“-E1,”.“-E2,”.or.“-E3”) ..This.feature.accommodates.a.number.of.com-plete.fuse.assemblies—three.SME.Power.Fuses,.two.Fault.Fiter.Electronic.Power.Fuses,.or.two.current-limiting.fuses—per.switch-termination.compartment .
For.storage,.orient.the.fuse.with.silencer.or.trun.nion.at.the.bottom,.and.insert.it.into.the.bracket ..Then.turn.the.fuse.so.that.the.pull-ring.is.out.of.the.way.of.the.cables .
3 .. Install.a.new.fuse.unit,.refill.unit,.interrupting.module,.or.current-limiting.fuse.in.the.end.fittings.or.holder.as.follows:
. S&C Power Fuses—Follow.the.instructions.provided.with.each.fuse.unit,.refill.unit,.or.interrupting.module.for.removal.of.blown.SMU-20.Fuse.Units,.SM-4.Refill.Units,.or.Fault.Fiter.Interrupting.Modules,.and.for.insertion.of.replacements.in.the.end.fittings.or.holders .
. Current-Limiting Fuses—For. instructions. on. replac.ing. current-limiting. fuses. in.current-limiting.fuse.hold.ers,.refer.to.S&C.Instruction.Sheet.660-501 ..These.holders.will.accommodate.the.current-limiting.fuses.listed.in.Appendix.E.on.page.27 .
4 .. Install. the. fuse. in. its.mounting. following. the. instruc.tions. found.under.“Fusing”.on.page.13 .
Re-Fusing
-
S&C Instruction Sheet 666-510 19
Maintenancew
Components No.mechanical.maintenance.is.required.for.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear ..However,.occasional.inspection.of.the.gear.and.exercising.of.Mini-Rupter.Switches.is.recommended ..Exercising.of.Type.PM.Switch.Operators.once.per.year.in.accordance.with.“EXERCISING.AND.MAINTENANCE”.in.S&C.Instruction.Sheet.669-515.is.also.rec-ommended.to.verify.proper.functioning.of.the.system .
Ç DANGERWhen.access.to.high-voltage.compartments. is.required.for. inspection,.service,.or.repairs,.always.observe.the.precautions.below ..Failure to observe these precau-tions will result in serious personal injury or death.
1 .. Access. to. pad-mounted. gear. must. be. restricted. only. to. qualified. persons .. See.“Qualified.Persons”.on.page.2 .
2 .. Always.follow.safe.operating.procedures.and.rules .
3 .. Before.touching.any.device,.always.disconnect.switches,.fuses,.and.other.devices.such.as.voltage.sensors.from.all.power.sources.(includ.ing.backfeed).and.control.sources,.test.for.voltage,.and.properly.ground .
4 .. Always.assume.that.both.sets.of.power.terminals.on.any.switch.or.fuse.are.ener-gized.unless.proved.oth.erwise.by.test,.by.visual.evidence.of.open-circuit.conditions.on.both.sets.of.terminals,.or.by.observ.ing.that.both.sets.of.terminals.are.grounded .
5 .. Test.for.voltage.on.both.sets.of.power.terminals.of.any.switch.or.fuse.using.proper.high-voltage.test.equipment .
6 .. After.the.gear.has.been.completely.disconnected.from.all.sources.of.power.and.tested.for.voltage,.install.suitable.grounding.cables.in.all.compart.ments .
7 .. For.maintenance.of.non-S&C.equipment,.follow.the.manufacturer’s.instructions .
8 .. Make.sure.the.enclosure.is.properly.grounded.to.the.station.or.facility.ground ..Do.not.return.equipment.to.service.unless.such.grounds.are.properly.made .
Note:. Occasionally,. low-voltage. components. may. require. maintenance .. The.maintenance.of.other.low-voltage.components.isolated.from.high-voltage.compart-ments.may.be.performed.under. the.safety.rules. for.equipment.rated.600.volts.or.less ..If.maintenance.is.to.be.performed.on.devices.connected.to.the.secondary.of.a.voltage.sensor,.short-circuit.the.secondary.connections ..A.separate.drawing.will.be.provided.with.the.replacement.part.explaining.how.to.properly.short-circuit.the.secondary.connections .
w These recommendations may differ from company operating proce dures and rules . Where a discrepancy exists, users should follow their company’s operating procedures and rules .
-
20 S&C Instruction Sheet 666-510
Returning Equipment to Service
When.returning.the.equipment.to.service,.the.following.procedures.should.be.observed:
1 .. Make.sure.that.switch.and.fuse.grounding.means.are.removed .
2 .. Make.certain.that.the.Mini-Rupter.Switches.are.in.the.correct.positions.(open.or.closed).as.dictated.by.sys.tem.circumstances .
3 .. Close.each.door.to.the.termination.compartments ..Make.sure.that.the.associated.Penta-Latch.Mechanisms.are.securely.latched.before.energizing.the.circuit.or.operating.any.switching.device .
4 .. For.proper.setting.of.Type.PM.Switch.Operators,.refer.to.“FINAL.CHECKS.BEFORE.WALKING.AWAY”.in.S&C.Instruction.Sheet.669-515 .
5 .. For.proper.setting.of.the.components.furnished.with.the.communication.and.control.equipment.group,.refer.to.S&C.Instruction.Sheet.660-505 .
6 .. Padlock.all.doors.and.switch-operating-shaft.access.covers.before.leaving.the.instal-lation.site,.even.momen.tarily ..Observe.this.procedure.even.in.those.cases.where.the.gear.is.accessible.only.to.qualified.persons .
Enclosure Finish The. responsibility. for.ensuring. that.a.finish.protects. the.enclosure. lies.with.both. the.manufacturer.and.the.user ..S&C.Remote.Supervisory.PME.Pad-Mounted.Gear.is.finished.with.the.S&C.Ultradur®.Finishing.System,.which.provides.lasting.protection.for.the.enclo-sure ..To.retain.this.protection,.the.user.should.take.periodic.corrective.action.as.follows:
1 .. Touch.up.any.penetration.of.the.finish.to.bare.metal—such.as.scratches.and.abrasions.due.to.ship.ping.or.vandalism—to.maintain.the.original.integrity ..S&C.touch-up.finish.and.primer.are.available.in.aerosol.spray.cans—order.by.Catalog.Number:.9999-058.for.olive.green.finish,.9999-080.for.light.gray.finish,.and.9999-061.for.red-oxide.primer ..No.other.finish.or.primer.is.approved ..The.area.to.be.touched.up.should.be.cleaned.to.remove.all.oil.and.grease ..Sand.the.area,.removing.any.traces.of.rust.that.may.be.present,.and.make.sure.all.edges.are.feathered.before.applying.primer .
2 .. Provide.an.occasional.simple.washdown—such.as.an.automobile.would.be.given—to.remove.surface.con.taminants ..Use.any.ordinary.mild.household.detergent.solution .
In.those.cases.where.the.enclosure.must.be.refinished.by.the.user.before.the.finish.has.weathered—for.example,.to.match.other.equipment—a.special.precaution.must.be.taken ..The.entire.surface.must.be.sanded.to.provide.a.tooth.to.bond.the.new.coat.to.the.unusually.tough.and.smooth.S&C.Ultradur.Finish .
Maintenance
-
S&C Instruction Sheet 666-510 21
Appendix A
Dielectric Testing When.high-voltage.dielectric.tests.are.to.be.performed.on.S&C.Remote.Supervisory.PME.Pad-Mounted.Gear,.special.precautions.should.be.taken.to.prevent.damage.to.the.voltage.sensor(s).and.voltage.limiter ..Refer.to.S&C.Instruction.Sheet.591-500 .
-
22 S&C Instruction Sheet 666-510
Appendix B
Ratings for S&C Mini-Rupter Switches
Complete. ratings. for. Mini-Rupters. as. applied. in. S&C. Remote. Supervisory. PME. Pad-Mounted.Gear.are. shown. in. the. table.below .. In.addition. to. the. load-dropping. ratings.shown,.Mini-Rupter.is.capable.of.interrupting.transformer.magnetizing.currents.associated.with.the.applicable.loads,.as.well.as.line-charging.and.cable-charging.currents.typical.for.distribution.systems.of.these.voltage.ratings ..For.applications.on.systems.rated.higher.than.7 .2.kV.and.involving.load.current.with.high.harmonic.content.(such.as.rectifier.load.currents),.refer.to.the.nearest.S&C.Sales.Office ..The.three-time.duty-cycle.fault-closing.ratings.shown.for.Mini-Rupters.define.the.ability.to.close.the.Mini-Rupter.three.times.against.a.three-phase.fault.with.asym.metrical.current.in.at.least.one.phase.equal.to.the.rated.value,.with.the.switch.remaining.operable.and.able.to.carry.and.interrupt.rated.current .
RATINGS FOR S&C MINI-RUPTER SWITCHES
Voltage, kV Current, Amperes
Nom. Max BIL Cont.
Live SwitchingThree-Time Duty-Cycle
Fault-ClosingShort-Circuit
Load Splitting Parallel or
Loop SwitchingLoad Dropping Peak RMS, Sym
Peak Withstand, Peak
One-Second Short-Time Withstand, RMS, Sym.
14 .4 17 .5 95 600 600 600 65 000 25 000 65 000 25 000
25 29 125 600 600 600 32 500 12 500 32 500 12 500
-
S&C Instruction Sheet 666-510 23
Appendix C
CONTROL EQUIPMENT GROUPS
Item
Suffix to beAdded to
Pad-Mounted Gear Catalog Number
Communication and Control Equipment Group12—includes user-spec ified remote terminal unit (RTU) or S&C 5800 Series Switch Control3; user-specified communication device; battery charger; battery packs; voltage sensor for power input to battery charger and for single-phase voltage sensing; and current sensors for three-phase current sensing on each power-operated switch45
a
Switch-Control Equipment Groups for use with RTU by others126—includes provisions for mounting of user-sup-plied and installed RTU, com munication device, etc . in low-voltage compartment; current sensors (5-amperes ac output) for three-phase current sensing on each power-oper-ated switch; voltage sensor (user-selectable 5-volts ac or 69-volts ac output) for single-phase voltage sens ing (except suffix “-Y4”); with power for the switch operators supplied by4
User-supplied 24-volt dc source or provisions for S&C 5800 Series Switch Control3 -Y2
External control power—user-supplied 120-volt ac source to an S&C Battery Charger and battery packs -Y3
Internal control power—S&C-supplied (voltage sensor) 20 volt-ampere source to an S&C Battery Charger and battery packs
-Y4
Switch-Control Equipment Groups for use without RTU67—includes provi sions in low-voltage compartment for connection of switch operators to user’s wiring; with power for the switch operators supplied by
External control power—user-supplied 120-volt ac source to an S&C Ac Power Supply (furnished) to develop control power input to the switch operators
-Y5
External control power—user-supplied 120-volt ac source to an S&C Battery Charger and battery packs -Y6
Internal control power—S&C-supplied (voltage sensor) 20 volt-ampere source to an S&C Battery Charger and battery packs1
-Y7
1 The S&C Voltage Sensor is mounted on the center phase at the hinge-contact side of the switch in Compartment 2 (Compartment 1 of PME-5 Models) .
2 Current sensors must not be installed on unshielded cables or on cables where the insulation is exposed but ungrounded (for example, where dielectric tape or heat-shrink tubing is used) . These sensors are intended for application at ground potential and may be damaged by the voltage gradient between the cable insulation and ground .
3 Refer to S&C Specification Bulletin 1041-31 for more information about S&C 5800 Series Switch Controls . Always specify Catalog Number Suffix “-Y2” for communication and control equipment Group with S&C 5800 Series Switch Control .
4 The S&C Battery Charger is factory-calibrated to accommodate the loads supplied with the Communication and Control Equipment Group
at the time of shipment . If additional loads are subsequently added, S&C recommends recalibration of the charging output to the batteries to ensure optimal battery life . Refer to the “ACCESSORIES” table on page 26 for recalibration instructions .
5 The battery charger and battery packs furnished with this option are not intended to provide power to any user-supplied and installed equipment .
6 When this option is specified, the connectors from each switch operator for connection to user’s wiring will be located in the low-voltage compartment .
7 Current and voltage sensing are not included and cannot be provided .a Refer to your nearest S&C Sales Office for application information .
-
24 S&C Instruction Sheet 666-510
1 Fuse assemblies (fuse holders or fuse units with end fittings) are not included . For units equipped with Fault Fiter Electronic Power Fuse Mountings, only two spare Fault Fiter Electronic Power Fuse Holders or two spare current-limiting fuse holders can be accommodated in each compartment .
n Specify Catalog Number Suffix “-B11” for gear with stainless-steel enclosure .
f Specify Catalog Number Suffix “-B12” for gear with stainless-steel enclosure .
_ Specify Catalog Number Suffix “-F12” for gear with stainless-steel enclosure .
OPTIONAL FEATURES
Item
Suffix to beAdded to
Pad-Mounted GearCatalog Number
Light Gray Outdoor Ultradur Finish instead of olive green -A2
Equipment Green Outdoor Finish (Toronto Standard) instead of olive green -A3
Seafoam Green Outdoor Finish instead of olive green -A4
Special Color Outdoor Ultradur Finish instead of olive green -A5
Stainless-Steel Enclosure
With olive green finish -A10
With light gray finish -A12
With special color outdoor Ultradur Finish -A15
Hexhead Actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms
For use except when Catalog Number Suffix “-F2” is specified -B1n
For use when Catalog Number Suffix “-F2” is specified -B2f
Key Interlocks to prevent paralleling of switches in Compartments 1 and 2 -C1
Key Interlocks to prevent opening fuse termination-compartment doors unless all switches are locked open -C3
Key Interlocks . Combines functions of Catalog Number Suffixes “-C1” and “-C3” above -C4
Fuse-Storage Feature for three spare fuse assem blies per compartment1
Located in Compartment 1 -E1
Located in Compartment 2 -E2
Located in Compartments 1 and 2 -E3
Mounting Provisions for a Fault Indicator in each switch compartment
Note: Accommodates three-phase indicator with single-phase sensors
Without viewing window in door -F1
With viewing window in door -F2_
Appendix D
TABLE CONTINUED v
-
S&C Instruction Sheet 666-510 25
Appendix D
1 When Catalog Number Suffix “-M4” is specified, the continuouscurrent and short-circuit ratings are limited to the ratings of the bushing wells and the bushing inserts and elbows used . In addition, the pad-mounted gear will not be capable of carrying a 25,000 amperes, RMS, symmetrical short-circuit rating and a 620 MVA rating .
2 Not available with switch-control equipment group Catalog Number Suffixes “-Y5” and “-Y6 .”
OPTIONAL FEATURES—Continued
Item
Suffix to beAdded to
Pad-Mounted Gear
Catalog Number
Base Adapter, to permit a PME model to be installed on a mounting pad having anchor bolts located to suit the comparable PMH model . This adapter increases the height of the unit 6 inches
Carbon steel
-K
Base Spacer, increases the height of the unit 6 inches -K7
Base Spacer, increases the height of the unit 12 inches -K8
Base Adapter, to permit a PME model to be installed on a mounting pad having anchor bolts located to suit the comparable PMH model . This adapter increases the height of the unit 6 inches
Stainless steel
-K10
Base Spacer, increases the height of the unit 6 inches -K17
Base Spacer, increases the height of the unit 12 inches -K18
International Crating -L71
600-Ampere Bushings Without Studs, at switch terminals -M1
200-Ampere Bushing Wells in lieu of 600-Ampere Bushings—at Switch Terminals1 -M4
Three-Phase Voltage Sensing using S&C Voltage Sensors2 -W1
-
26 S&C Instruction Sheet 666-510
Appendix D
ACCESSORIES
Item Catalog Number
Shotgun Clamp Sticks for use with separable connectors and voltage testers
69 5Z\x0 length 9933-150
89 5Z\x0 length 9933-151
Storage Bag, heavy canvas For shotgunclamp stick
69 60 length 9933-152
89 60 length 9933-153
Voltage Tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and storage case1 9931-072Current Sensors, set of three—split core, rated 600/5 amperes for application in conjunction with manually operated switches for monitoring load currents—for conductors of up to 3Z\x-inch diameter2 TA-2224
Detailed Hardware Manual—includes schematic diagrams, circuit-board layouts, parts lists, bench-check procedures, and operating descriptions for the switch control and battery charger, as applicable
For Switch-Control Equip ment Groups for use with RTU by others
Catalog Number Suffix “-Y2” RD-3602
Catalog Number Suffix “-Y3” RD-3603
Catalog Number Suffix “-Y4” RD-3604
For Switch-Control Equip ment Groups for use without RTU
Catalog Number Suffix “-Y5” RD-3605
Catalog Number Suffix “-Y6” RD-3606
Catalog Number Suffix “-Y7” RD-3607
Pentahead Socket, for Z\x-inch drive 9931-074
S&C Battery Charger Recalibration Procedure—includes detailed instructions on calibrating the charging voltage to the batteries to ensure optimal battery life RD-3808
1 For end users other than electric utilities, also specify a shotgun clamp stick of the appropriate length .
2 Current sensors must not be installed on unshielded cables or on cables where the insulation is exposed but ungrounded (for example, where
dielectric tape or heat-shrink tubing is used) . These sensors are intended for application at ground potential and may be damaged by the voltage gradient between the cable insulation and ground .
-
S&C Instruction Sheet 666-510 27
Appendix E
Current-Limiting Fuses for Use in S&C PME Pad-Mounted Gear
Types Accommodated and Adapters RequiredS&C.Holders.for.current-limiting.fuses.are.designed.for.use.in.pad-mounted.gear.models.that. include.mountings. for.Fault.Fiter.Electronic.Power.Fuses .. In.PME.Pad-Mounted.Gear,.these.holders.will.accommodate.the.single-barrel.current-limiting.fuses.listed.in.the.table.below.when.the.fuses.are.equipped.with.B\,-inch.diameter.mounting.studs.at.both.ends ..Depending.on.the.length.of.the.current-limiting.fuse.to.be.used,.an.adapter.may.be.required.in.order.to.fit.the.fuse.in.the.holder ..The.adapter,.when.required,.is.furnished.with.the.S&C.Holder.and.is.signified.by.a.suffix.to.the.catalog.number.of.the.holder ..For.instructions.on.installing.current-limiting.fuses.in.S&C.Holders,.refer.to.S&C.Instruction.Sheet.660-501 .
CURRENT-LIMITING FUSES ACCOMMODATED IN FAULT FITER MOUNTINGS
For Use inPME ModelsWith Nominal
VoltageRating, kV
Current-Limiting Fuse1Requires
S&C Holder3Catalog Number4Manufacturer Type
Rating2
Max Voltage, kV Max Current, Amperes, RMS
14 .4
Cooper5
Kearney B 8 .3 30 –112 3122-A1
Kearney Q8 .3
15 .56–100 3122-A1
McGraw-Edison NX®8 .3
15 .51 .5C–100C 3122-A1
RTE® ELX8 .3
15 .53 –50 3122-A1
CombinedTechnologies, Inc .
X Limiter™
8 .315 .5
12 –140 3122-A1
Eaton5Cutler Hammer CX
8 .315 .5
3 .5C– 40C4C – 40C
3122-A1
Cutler Hammer CXN8 .3
15 .53 .5C– 40C4C – 40C
3122
25
Cooper
Kearney B15 .522
30 – 10025 – 65
3123-A1
Kearney Q 15 .5 6–100 3123-A1
McGraw-Edison NX®15 .523
1 .5C–100C6C – 40C
3123-A1
RTE® ELX15 .523
3 –503 – 40
3123-A1
CombinedTechnologies, Inc .
X Limiter™
15 .523
12–10012– 40
3123-A1
EatonCutler Hammer CX 15 .5 4C – 40C 3123-A1
Cutler Hammer CXN 15 .5 45C–100C 3123
1 Fuses must be furnished by others .2 Maximum voltage and current ratings listed apply to the complete pad-mounted gear unit . Consult fuse manufacturer for complete fuse ratings .
3 Holders for 14 .4-kV PME models are rated 14 .4 kV nominal, 17 .0 kV maximum, and 200 amperes maximum . Holders for 25-kV PME models are rated 25 kV nominal, 29 kV maximum, and 200 amperes maximum .
4 Includes adapter when required .
5 All 15 .5-kV fuse types listed—except RTE ELX Current-Limiting Fuses—when used in 14 .4-kV Model PME-4, PME-5, PME-6, PME-9, PME-11, or PME-12 Pad-Mounted Gear furnished with Fault Fiter mount-ings, permit the gear to achieve a 25-kA short-circuit rating . Separable connectors and cables installed in the switch compartments must be rated 25,000 amperes, RMS, symmetrical . In addition, the gear cannot be furnished with optional 200-ampere bushing wells in lieu of 600-ampere bushings at the switch terminals, Catalog Number Suffix “-M4 .”
-
Prin
ted
in U
.S .A
.
28 S&C Instruction Sheet 666-510
Recommended Voltage RatingsIn.general,.current-limiting.fuses.should.have.a.maximum.voltage.rating.equal.to,.but.not.greater.than.140%.of,.the.system.line-to-line.voltage.since,.for.most.applications,.the.fuses.can.be.exposed.to.full.system.line-to-line.voltage.in.clearing.faults ..Although.there.may.be.economic.or.space-saving.incentives.for.using.current-limiting.fuses.with.voltage.ratings.“appropriate.for.system.line-to-ground.voltage”.(i .e .,.fuses.with.a.voltage.rating.lower.than.line-to-line.voltage.but.greater than or equal to.maxi.mum.system.line-to-ground.voltage),.S&C.can.only.recom.mend.such.use.in.the.following.applications:
•. Protection.of.single-phase.transformers.serving.single-phase.loads .
•. Protection.of.three-phase.lateral.circuits.fed.by.single-conductor.shielded.cable.(pro-vided.that.each.trans.former.on.the.lateral.is.individually.fused.so.that.the.current-lim-iting.fuse.serving.the.lateral.will.not.be.required.to.clear.secondary.faults) .
•. Protection. of. single-phase. lateral. circuits. fed. by. single-conductor. shielded. cable.where.the.load.is.line-to-ground.connected .
Appendix E