insulation coordination for gis - new aspects

Upload: hhipower

Post on 02-Jun-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Insulation coordination for GIS - New aspects

    1/6

    INSULATION COORDINATION FOR GIS - NEW ASPECTS

    M. P. Meirelles, R. Vaisman, R. Azevedo, A. J. S. Junqueira M. Lacorte, W. Hofbauer

    CEPEL ABB High Voltage Technologies

    BRAZIL SWITZERLAND

    Summary

    Insulation coordination is one of the most important

    aspects to be considered during the planning of a

    substation. Properly done it minimises the risk of

    failures in the substation caused by overvoltages and

    such contributes to a high availability of the substation.

    A characteristic layout of a GIS substation is considered

    in order to analyse - by using a simulation model - the

    lightning overvoltages occurring in this substation

    caused by a back flash in the transmission line. The

    impact of the location of the surge arrester, the effect of

    the length of the GIS as well as the effect of other

    design parameters of a GIS substation on the lightning

    overvoltages in the substation are investigated.

    Based on the results obtained conclusions for insulation

    coordination studies are drawn.

    Key-word: insulation coordination, GIS, lightning

    overvoltage.

    1 - Introduction

    Insulation coordination is one of the fundamental

    dimensioning criteria for all electric systems. Properly

    done it results in a restriction of insulation flashovers

    or breakdowns caused by overvoltages to those parts of

    a system where consequential damages are quite

    limited. Further improvement can be achieved by the

    correct application of surge arresters which effectively

    reduce the probability of costly damages.

    Based on many years experience general design rules

    were set up how to protect electric systems efficient and

    effective against damages caused by internally or

    externally generated overvoltages. Today software

    simulation tools are used which enable to calculate

    qualitatively and quantitatively the impact of insulation

    coordination measures on the propagation of

    overvoltage surges. An important aspect to be

    considered refers to the lightning surge injection into

    the substation [1].

    This is an important factor especially when it comes to

    the overall optimisation of a GIS substation surge

    protection. Traditionally a GIS substation is protected

    by an outdoor arrester at the GIS entrance. Depending

    on the layout of the GIS, additional GIS arresters have

    to be used to achieve full protection of the GIS. This

    raises the question whether and under which conditions

    it is technically and economically reasonable to use just

    GIS arresters instead of additional outdoor arresters

    and vice versa.

    This question is analysed more in detail for a GIS

    substation model typically used in a 500 kV AC

    transmission system. The analysis is based on digital

    simulations performed using EMTP - Electromagnetic

    Transients Program - worldwide used for this purpose.

    2 - GIS-Substation

    The electric system considered in this study consists of

    three sections which are characteristic for many GIS

    substations (Figure 1).

    21, rue dArtois, F-75008 Parishttp://www.cigre.org

    Session 1998 CIGR23-101

    CEPEL - Cx. Postal 68007, 21944-970, Rio de Janeiro - Brazil

    Tel. +55 21 260 8937 Fax: +55 21 260 2236

  • 8/10/2019 Insulation coordination for GIS - New aspects

    2/6

    Supply System

    Tower 5 Tower 4 Tower 3 Tower 2 Tower 1

    15m

    8m6m

    Stroken Tower

    Outdoor ArresterCVT

    GIS

    GIS Bushing

    300m300m300m300m2km

    Transformer

    Figure 1 - Schematic representation of the electrical system considered in the study

    2.1 - Transmission System

    The rated voltage of the transmission system considered

    in the study is 500 kV / 50 Hz.

    The towers are modeled by a T equivalent diagram of

    surge impedances as shown in Figure 2. Typical values

    for the footing resistances of the towers are:

    - 5 for Tower 1;

    - 10 for the other Towers.

    Figure 2 - Tower geometry and tower EMTP model

    The equivalent diagram of the supply system used

    consists of a power frequency voltage source in series

    with a resistance. This resistance has the same value as

    the transmission line surge impedance in order to avoid

    reflections.

    2.2 - Outdoor Section

    The outdoor connections between Tower 1 and GISbushing (Figure 1) are simulated by a 0.5 H/m

    inductance.

    As only a single phase is considered when performing

    the overvoltage calculations inside the GIS, the other 2

    phases of the transmission line are connected to earth at

    Tower 1 by lumped capacitances of 10 nF.

    Regarding the capacitive voltage transformer CVT, two

    different configurations are simulated :

    - no CVT;

    - CVT represented by 5 nF to ground.

    The outdoor surge arrester has a protection level of1055 kV at 20 kA. It is simulated as a non linear

    resistance connected to the phase-wire by a 5 H

    inductance representing the length of the connection

    leads plus the height of the arrester.

    A simulation with the surge arrester directly connected

    to the phase-wire is also performed in order to show the

    influence of the connection leads on the surge

    protection.

    2.3 - GIS Section

    The GIS bushing is modeled by two surge impedances

    in series represented by

    Zbushing= Z1 + Z2

    where: Z1 = 200 surge impedance, length = 3m.

    Z2 = 30 surge impedance, length =1 m.

    For comparison a simulation is also performed with

    the bushing modeled as a lumped capacitance of 150 pF

    [2]. The calculation results show that the two different

    models have a negligible effect on the overallovervoltages. Therefore the study is performed only

    Z

    Z

    Z

    R footing

  • 8/10/2019 Insulation coordination for GIS - New aspects

    3/6

    with one bushing model represented by two surge

    impedances in series.

    The GIS is simulated by a surge impedance of 60 ohms.

    The length of the GIS is varied in the range of 15 m to

    150 m. The termination of the GIS is either a power

    transformer directly connected to the GIS andsimulated by a 4 nF capacitance to ground or an open

    line-disconnector.

    The GIS surge arrester used in the study has a

    protection level of 1022 kV at 20 kA. It is simulated by

    a non linear resistance directly connected to the GIS.

    3 - Lightning

    According to the worldwide practice a lightning

    protection study must be performed considering two

    types of lightning strokes:

    a direct stroke;

    a back flash.

    3.1 -Direct Stroke

    This means a lightning stroke directly to a phase wire.

    3.2 - Back Flash

    A back flash is caused by a direct lightning stroke to

    the ground wire or to a tower of a line, followed by a

    flashover across the insulation between the tower and a

    phase wire.

    For a back flash calculation a lightning stroke in a

    critical distance to the substation and a current level

    which is the highest to be expected once in a period of

    400 years is considered [3]. In this study a lightning

    stroke to the second tower and a current magnitude of

    300 kA is assumed representing a 0.014% probability

    of incidence [4, 5].

    A simulation with 200 kA lightning current is done inorder to analyse its influence on the insulation

    coordination result, since this value is rarely

    exceeded [5].

    The back flash across the phase insulation of the struck

    tower is simulated by the so called Leader Progression

    Model [6] programmed in a subroutine TACS of

    EMTP.

    In general the overvoltage values resulting from a back

    flash are higher than those of a direct stroke to the

    phase wire. Therefore only lightning surge parametersof a back flash are considered in this study.

    4 - Simulations

    The main objective of insulation coordination studies

    for planned substations is to minimize the risk of

    failure due to overvoltages. Instead of applying

    probability concepts literature also suggests the use of a

    deterministic approach where a safety margin must betaken into account [1].

    In this way, although the standardized BIL for 500 kV

    systems is 1550 kV, the lightning studies must lead to

    overvoltages not higher than BIL/1.2, where the safety

    margin of 20% is used to determine the calculated

    maximum overvoltage, that will be used as reference.

    Ucwcoordination withstand voltage

    Ucw= BIL/1.2 = 1550/1.2 = 1292 kV

    A simulation with a safety margin of 15%

    (Ucw = BIL/1.15 = 1348 kV) is done in order to analyse

    the influence of this limit since this value is largely

    used [7].

    Four different surge protection concepts of the

    substation regarding arrester types and their positioning

    are simulated:

    outdoor surge arrester positioned between the CVT

    and the GIS bushing;

    GIS surge arrester positioned at the GIS bushing

    (GIS entrance);

    GIS surge arrester positioned at half length of the

    GIS;

    GIS surge arrester positioned at the transformer.

    5 - Results

    5.1 - GIS Length Effect

    Figures 3 to 5 show the calculated overvoltages at the

    CVT outside the GIS, at the GIS entrance and at the

    transformer respectively considering the four different

    locations of the arrester.

    The resulting overvoltages as a function of the GIS

    length is strongly non-linear which results from

    different reflections of the surge waves. Therefore no

    general statement can be made that the longer a GIS

    the higher the overvoltage.

    For any fixed reference node in the substation the local

    overvoltage occurring in general strongly depends onboth the location of the surge arrester and the length of

  • 8/10/2019 Insulation coordination for GIS - New aspects

    4/6

  • 8/10/2019 Insulation coordination for GIS - New aspects

    5/6

    5.4 - Connection Leads

    Figure 8 shows the influence of the connection lead

    between the phase wire and the outdoor surge arrester

    on the overvoltage protection. The longer the lead the

    less effective is the surge arrester which is again an

    effect of the traveling surge wave.

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150

    Length [m]

    PeakVoltage[MV]

    OUTDOOR ARRESTER WITH LEAD

    OUTDOOR ARRESTER WITHOUT LEAD

    Ucw = 1292 kV

    Figure 8 - Voltage at coupling capacitor in function of

    the GIS length

    5.5 - GIS Termination Effect

    The influence of the GIS termination on the

    overvoltage at the termination is analysed for the

    substation protected with an outdoor surge arrester and

    presented in Figure 9.

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150

    Length [m]

    PeakVoltage[MV]

    GIS WITH OPEN-END

    GIS WITH CAPACITIVE-END

    Ucw = 1292 kV

    Figure 9 - Voltage at transformer in function of the GIS

    length

    No general statement can be made that the overvoltage

    at an open end will always be higher than at any other

    termination of the GIS as demonstrated for the

    transformer [7]. There is also a strong influence of the

    length of the GIS due to the wave characteristic of the

    surges.

    5.6 - Lightning Current Magnitude Effect

    The effect of the lightning current magnitude on the

    overvoltages in different reference nodes is shown for

    an outdoor surge arrester (Figure 10) and a GIS surge

    arrester at the GIS bushing (Figure 11).

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150

    Length [m]

    PeakVoltage[MV]

    VOLTAGE AT CVT - 200kA

    VOLTAGE AT CVT - 300kA

    VOLTAGE AT THE TRANSFORMER - 200kA

    VOLTAGE AT THE TRANSFORMER - 300kA

    Ucw = 1292 kV

    Figure 10 - Overvoltage in function of the GIS length

    considering outdoor surge arrester

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150Length [m]

    PeakVoltage[MV]

    VOLTAGE AT CVT - 200kA

    VOLTAGE AT CVT - 300kA

    VOLTAGE AT THE TRANSFORMER - 200kA

    VOLTAGE AT THE TRANSFORMER - 300kA

    Ucw = 1292 kV

    Figure 11 - Overvoltage in function of the GIS length

    considering GIS surge arrester

    While for both locations of the arrester the current

    magnitude has a quite high influence on the

    overvoltage outside the GIS there is much less or nearly

    no influence at the transformer.

    5.7 - Safety Margin

    The adopted safety margin of 20%, which is a very

    restrict condition, can be reduced to 15% assuming that

    the substation has an accurate representation. Figures

    12 and 13 shows the overvoltages at CVT and at the

    transformer considering the outdoor arrester and the

    GIS arrester positioned at the GIS bushing respectively.

    Considering this new margin, practically there is no

    restriction of using only one arrester to achieve full

    protection of all sections of a GIS substation, for GIS

    lengths less than 100m.

  • 8/10/2019 Insulation coordination for GIS - New aspects

    6/6

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150

    Length [m]

    PeakVoltage[MV]

    VOLTAGE AT CVT

    VOLTAGE AT THE TRANSFORMER

    Ucw = 1348 kV - Safety Margin of 15%

    Ucw = 1292 kV - Safety Margin of 20%

    Figure 12 - Comparison of diferent safety margins

    considering overvoltages with the outdoor arrester

    1,00

    1,10

    1,20

    1,30

    1,40

    1,50

    1,60

    0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150

    Length [m]

    PeakVoltage[MV]

    VOLTAGE AT CVT

    VOLTAGE AT THE TRANSFORMER

    Ucw = 1348 kV - Safety Margin of 15%

    Ucw = 1292 kV - Safety Margin of 20%

    Figure 13 - Comparison of diferent safety margins

    considering overvoltages with the GIS arrester at GISbushing

    6 - Conclusions

    Due to the wave characteristic of lightning surges a

    proper insulation coordination for a GIS substation has

    to consider many different aspects:

    The length of the GIS has a significant influence on

    the overvoltages in the substation. No general

    statement can be given for common lengths of GIS

    that the longer the GIS the higher the overvoltages.

    The location of a GIS arrester at the GIS bushing

    offers an equivalent lightning protection for the GIS

    substation as an outdoor surge arrester as long as

    the effective length of the GIS is less than 100 m.

    For GIS lengths more than 100 m in minimum two

    surge arresters at different locations should be

    considered for an effective protection of the GIS

    substation.

    The impact of capacitive devices in the GIS

    substation on the overvoltages is not predictable.Detailed analyses are required.

    The connection lead of an outdoor surge arrester

    has a significant impact on the effectiveness of the

    arrester. The longer the connection lead the higher

    the overvoltages in the GIS substation.

    The GIS termination has a strong impact on the

    overvoltages at the termination. No generalstatement can be given that the overvoltages at an

    open termination are the highest.

    The lightning current magnitude has a strong

    impact on the overvoltages outside the GIS but it is

    minor inside the GIS.

    Proper insulation coordination of any GIS

    substation requires an accurate digital simulation.

    Doing this, a safety margin of 15% can be adopted,

    which may lead to the use of only one arrester to

    protect the GIS substation for usual GIS lengths.

    7 - References

    [1] - "A Simplified Method for Estimating Lightning

    Performance of Transmission Lines"; IEEE WG on

    Lightning Performance of Transmission Lines, IEEE

    Trans. PAS-104, April/1985.

    [2] - "Electric Transients and Insulation Coordination";

    Salgado F.M., Vaisman R. et al, EDUFF/FURNAS -

    Centrais Eltricas SA, 1987 (in Portuguese).

    [3] - "Lightning Overvoltage Protection of GIS"; GIS

    Technical Information; ABB Hochspannungstechnik

    AG, Doc. No.: HASV 685 401 E - AK 4G.1- A05/92.

    [4] - "Simplified Procedures for Determining

    Representative Substation Impinging Lightning

    Overvoltages"; Erikson A. and Weck K., CIGRE Paper

    no. 33-16, Paris, 1988.

    [5] - "Modeling Guidelines for Fast Front Transients";

    IEEE WG on Modeling and Analysis of System

    Transients, IEEE Trans. PWRD, Vol. 11, No.1,January 1996.

    [6] - "Modeling of Transmission Line Exposure to

    Direct Lightning Strokes"; Farouk A.M. Rizk, IEEE 90

    WM 084-4 PWRD, Atlanta, Georgia.

    [7] - "Re-evaluation of the Ligthning Impulse Level of

    Transformers and Shunt Reactors"; Vaisman R. et al,

    CIER Congress, Chile, 1987.